Summary of October 6, 2021, Public Observation Meeting with Exelon Generation Company, LLC Proposed License Amendment Request to Modify Emergency Diesel Generator and Emregency Core Cooling System Surveillance Requirements
ML21294A369
Person / Time
Site: Limerick  
Issue date: 11/15/2021
From: V Sreenivas
Plant Licensing Branch 1
To: Rhoades D
Exelon Nuclear, Exelon Generation Co
Sreenivas V, NRR/DORL/LPLI, 415-2597
References
EPID L-2021-LRM-0094 TS 3/4.8.1
Download: ML21294A369 (24)


Text

November 15, 2021 Mr. David P. Rhoades Senior Vice President Exelon Generation Company, LLC President and Chief Nuclear Officer Exelon Nuclear 4300 Winfield Road Warrenville, IL 60555

SUBJECT:

LIMERICK GENERATING STATION, UNITS 1 AND 2 -

SUMMARY

OF OCTOBER 6, 2021, PUBLIC OBSERVATION MEETING WITH EXELON GENERATION COMPANY, LLC RE: PROPOSED LICENSE AMENDMENT REQUEST TO MODIFY EMERGENCY DIESEL GENERATOR AND EMREGENCY CORE COOLING SYSTEM SURVEILLANCE REQUIREMENTS (EPID L-2021-LRM-0094)

Dear Mr. Rhoades:

On October 6, 2021, the U.S. Nuclear Regulatory Commission (NRC) staff held a virtual Observation public meeting with representatives from Exelon Generation Company, LLC (the licensee). The purpose of the meeting was to discuss the licensees plans to submit a license amendment request (LAR) regarding modifying technical specification (TS) surveillance requirements (SRs) for the emergency diesel generators (EDGs) and emergency core cooling system (ECCS). The meeting notice and agenda, dated September 23, 2021, are available in Agencywide Documents Access and Management System (ADAMS) under Accession No. ML21266A081. Enclosure 1 to this summary contains a list of attendees. Enclosure 2 to this summary contains the licensees presentation slides shown during the meeting.

During the meeting, the licensee stated that the proposed LAR would request revising certain frequency and voltage acceptance criteria for steady-state EDG SRs under TS 3/4.8.1, AC [Alternating Current] Sources - Operating, consistent with the Westinghouse Electric Company, LLC topical report WCAP-17308-NP-A, Revision 0, Treatment of Diesel Generator (DG) Technical Specification Frequency and Voltage Tolerances (ADAMS Accession No. ML17215A230), with minor deviations. The proposed LAR would also request revising the flow acceptance criteria of the ECCS pump SRs under TS 3/4.5.1, ECCS - Operating, to gain additional margin at the proposed EDG frequency and voltage values. The licensee stated that it would submit the LAR to address a nonconservative TS and to correct a typographical error.

The licensee discussed its calculations and analyses that will support the LAR and proposed electrical, mechanical, and motor-operated valve (MOV) related deviations from WCAP-17308-NP-A. The licensee requested the NRC to complete its review within a year and stated that the LAR would not contain any risk insights.

The NRC staff asked the licensee questions regarding the design flow for ECCS pumps, whether the LAR would provide examples of how the licensee calculated the new frequency, voltage, and flow values, and whether the LAR would identify any issues with the MOVs or ECCS pumps resulting from the proposed frequency changes. The NRC staff also asked the

D. Rhoades licensee whether the LAR would include equation no. five from WCAP-17308-NP-A, whether the licensee performed an EDG dynamic or transient study using the proposed frequency values, and whether the LAR would provide any single line diagrams showing the EDGs, buses, and safety-related loads.

The NRC staff also asked the licensee about whether the licensee had a list of the EDG loads (e.g., pumps, valves, and fans) that it evaluated and whether the licensee evaluated the EDGs fuel oil transfer pumps, engine-driven fuel and cooling water pumps, and any skid-mounted components. The NRC staff also asked whether the licensee developed inservice testing five-point curves for the pumps during preservice testing, as required by the American Society of Mechanical Engineers Code for Operation and Maintenance of Nuclear Power Plants (OM Code).

The NRC staff requested the licensee to have the LAR reference the source documentation for the typographical error so that the NRC can confirm the correct information.

The NRC staff did not make any regulatory decisions or commitments at the meeting. One member of the public identified herself on the teleconference and asked questions about whether the licensee considered changes in flow rates and diesel frequencies in its severe accident and other analyses. The licensee addressed the questions. The NRC staff did not receive any Public Meeting Feedback forms.

Please direct any inquiries to me at 301-415-2597 or by e-mail to v.sreenivas@nrc.gov.

Sincerely,

/RA - A. Klett for/

V. Sreenivas, Project Manager Plant Licensing Branch I Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-352 and 50-353

Enclosures:

1. List of Attendees
2. Licensee Presentation cc: Listserv List of Attendees

LIST OF ATTENDEES OCTOBER 6, 2021, VIRTUAL PUBLIC MEETING WITH EXELON GENERATING COMPANY, LLC LIMERICK GENERATING STATION, UNITS 1 AND 2 PRESUBMITTAL MEETING FOR LICENSE AMENDMENT REQUEST U.S. Nuclear Regulatory Commission Exelon Generation Company, LLC Santosh Bhatt, NRR1/DSS2/SNSB3 George Budock Jim Danna, NRR/DORL4/LPL15 Greg Curtin Jonathan Evans, NRR/DRA6/APLA7 John George Jr.

Jason Huang, NRR/DEX8/EMIB9 David Helker Audrey Klett, NRR/DORL/LPL1 Francis Mascitelli Hari Kodali, NRR/DEX/EEEB10 Darani Reddick V Sreenivas, NRR/DORL/LPL1 Emmanuel Rosa Khadijah West, NRR/DSS/STSB11 Baris Sarikaya Bob Wolfgang, NRR/DEX/EMIB Jacob Sherk Diana Woodyatt, NRR/DSS/SNSB Laura Velez Danyal Waseem Anim Xhafa Members of the Public Peter Zeppos Peng Yan 1 Office of Nuclear Reactor Regulation 2 Division of Safety Systems 3 Nuclear Systems Performance Branch 4 Division of Operating Reactor Licensing 5 Plant Licensing Branch I 6 Division of Risk Assessment 7 Probabilistic Risk Assessment Branch A 8 Division of Engineering and External Hazards 9 Mechanical Engineering and Inservice Testing Branch 10 Electrical Engineering Branch 11 Technical Specifications Branch Licensee Presentation

Limerick Generating Station (LGS)

WCAP-17308 Implementation LAR NRC Pre-submittal Meeting October 06, 2021

Agenda / Opening Remarks

  • Introductions
  • License Amendment Request (LAR) Team
  • Goals of Meeting
  • Overview

Pump Technical Specification (TS) Surveillance Requirement (SR) flow acceptance criteria changes

  • Proposed TS Changes
  • NRC Feedback
  • Closing Remarks 1

Introductions / LAR Team LAR Team

  • Sponsor - Matt Bonanno Director Site Engineering
  • Lead Licensing Engineer - Frank Mascitelli
  • Manager Engineering Lead - Laura Velez
  • Central Design Organization (CDO) Lead - Jacob Giovanni Sherk
  • CDO Manager - Brian Madderom
  • Maintenance Manager I&C - Joe Drahus
  • Supporting Engineering Staff
  • Senior Staff Engineer - Greg Curtin
  • ECCS System Engineers - Jim Berg, John George
  • Operations - Craig Myers 2

Goals Of Meeting

  • Present clear description of the LAR and proposed changes
  • NRC has clear understanding of minor deviations to WCAP-17308 Methodology
  • NRC has clear understanding of the proposed ECCS Pump TS SR changes that are not within the scope of WCAP-17308
  • NRC provides feedback to Exelon approach and justification
  • Discuss potential for future audit of supporting calculations and analyses
  • Results of NRC feedback contribute to an efficient Acceptance Review and reduction of future potential Requests for Additional Information (RAIs)
  • NRC review time is less than or equal to one year 3

Overview

  • The proposed amendments would revise certain frequency and voltage acceptance criteria for steady-state emergency diesel generator surveillance requirements under TS 3/4.8.1, "AC Sources - Operating. The proposed changes are consistent with WCAP-17308. In addition, the proposed amendment would revise the flow acceptance criteria of the emergency core cooling system pumps surveillance requirements under TS 3/4.5.1, ECCS-Operating.
  • The LAR is required to correct a non-conservative TS. Plant operations are currently administratively controlled as described in NRC Administrative Letter (AL) 98-10, "Dispositioning of Technical Specifications that are Insufficient to Assure Plant Safety." In accordance with the guidance in AL 98-10, this LAR is required to resolve a non-conservative TS and is not a voluntary request to change the LGS licensing basis.
  • The LAR will be a non-proprietary submittal, but parts of the LAR are based on proprietary analyses.

4

Overview The analysis performed per LM-0736, Analyses of Emergency Diesel Generator Technical Specification Voltage and Frequency Range and Tolerances, revealed that a Technical Specification (TS) change is needed to maintain margin for ECCS pumps and to correct a non-conservative TS. This LAR will change the Emergency Diesel Generator (EDG) steady-state operating frequency band from 60 Hz +/- 1.2 Hz to 59.8 - 60.8 Hz for eight TS SRs. Note that the steady-state TS voltage tolerance expressed as 4280 +/- 120 volts is proposed to change to 4160 V and 4400 V for greater clarification and the actual voltage tolerance is not changed. The functions of the EDGs are not changed as a result of this modification. The LAR is changing the steady-state operating frequency of the EDGs to a more realistic value, is more conservative and resolves a non-conservative TS.

In addition, to address the non-conservative TS and to gain additional margin at the proposed EDG frequency and voltage steady state frequency tolerances, the ECCS Core Spray System (CSS) and Low Pressure Coolant Injection (LPCI) Pumps will have their TS SR flow acceptance criteria revised from 3,175 and 10,000 gpm to 2,500 and 8,000 gpm, respectively.

Also, this LAR will include correcting a typographical error. For Unit 1, TS 3.8.3.1.a.8.b, the 480-VAC load center labeled D224 is a typographical error and should be labeled as D244.

5

Consistency with WCAP-17308

  • To evaluate the acceptability of the proposed change, Exelon evaluated the proposed change consistent with WCAP-17308-NP-A, Revision 0, Treatment of Diesel Generator (DG)

Technical Specification Frequency and Voltage Tolerances

  • The analysis and supporting calculations are contained in Exelon Design Analysis, LM-0736, Revision 0, Analyses of Emergency Diesel Generator Technical Specification Voltage and Frequency Range and Tolerances
  • Specifically, the following items were evaluated for changes in steady-state voltage and frequency:

- Impact on Safety-Related Systems which include ECCS

- Impact on EDG Loading

- Impact on EDG Fuel Oil Consumption Calculations

- Impact on Motor Operated Valve (MOV) Performance 6

Consistency with WCAP-17308

  • Minor Electrical Deviations:

Per Section 3.1.1 of WCAP-17308-NP-A, the impact of frequency variation on EDG loading is to be determined by assuming that the EDG entire load is an induction motor and the increase in frequency is determined by a factor using the pump/fan affinity laws (e.g., speed increases by a cubic factor). A more realistic approach of separating the load profile out by either induction motor, static, or lumped load, then applying the appropriate factor based on the loads behavior to the effects of frequency and voltage changes was used.

The load factor for induction motors was derived by using the equation 5 in WCAP-17308-NP-A to determine the uncertainty in motor speed then applying classical machine theory to determine the impacts or power changes. The load factor for static loads was derived by using classic electrical power laws. This results in not only a more realistic but also a more conservative result since in LGSs case, static loads provide a higher load factor than induction loads since the voltage variation is larger.

7

Consistency with WCAP-17308

  • Minor Mechanical Deviations:

The In-Service Test (IST) program at Limerick does not produce, or have available, 5-point IST curves. In some cases, either pre-operation test data (Residual Heat Removal (RHR), CS) were used, or vendor pump data were used to develop pump curves.

The TS listed by WCAP-17308-NP Section 5.2 regarding fan acceptability do not encompass General Electric-built plants. However, LGS TS 4.6.5.3 and 4.6.5.4 require that flow rates for Standby Gas Treatment subsystems and Reactor Enclosure Recirculation subsystems not vary more than 10% from their nominal flowrates. Therefore, the modified fan performance for the Standby Gas Treatment System Room Unit Coolers, Standby Gas Treatment System Room Access Unit Coolers, Standby Gas Treatment System Exhaust Fan, Reactor Building Recirculation Fan, and Standby Gas Treatment System Room Vent Exhaust Fan are deemed acceptable so long as the flow rate at underfrequency and undervoltage is not less than 90% of the nominal flowrate. The acceptability of fans not included within the scope of LGS TS 4.6.5.3 and 4.6.5.4 is evaluated based on the ability of the fans to provide sufficient cooling load to their respective systems.

8

Consistency with WCAP-17308

  • Minor MOV Deviations:

The frequency and voltage uncertainty is treated as an added uncertainty similar to how MOV testing uncertainties are evaluated.

This WCAP described uncertainty is shown to be small relative to the pre-existing test uncertainty for all valves in the MOV testing population. The additional uncertainties are combined with the existing MOV testing uncertainty using standard square-root-sum-of-the-squares methods when the uncertainties are independent, and by sum when the uncertainty is not independent. The result is effectively an increased testing variability, which is compared against the existing valve capabilities. All valves are found to have sufficient margin to existing valve capabilities even upon imposing this increased uncertainty.

9

Need for ECCS Pump TS SR Flow Acceptance Criteria Change

  • The results shown in calculation LM-0736 for LPCI and CS do not meet the required TS flow value of 10,000 gpm and 3,175 gpm, respectively. They do, however, exceed their respective flow values of 8,000 gpm and 2,500 gpm contained in the 10CFR50.46 Analysis of Record (AOR) 0000-0111-9078 (GNF2 fuel evaluation) and 005N3990 (GNF3 fuel evaluation).
  • The AOR provides the results of the loss-of-coolant accident (LOCA) analysis performed by GE Nuclear Energy for LGS Units 1 and 2. The analysis, which uses the NRC approved SAFER/GESTR-LOCA application methodology, was performed in accordance with NRC requirements and demonstrates conformance with Emergency Core Cooling System (ECCS) acceptance criteria of 10CFR50.46 Appendix K.
  • Exelon is proposing a TS change to reduce the allowable RHR and CS pump flow rates from their present values by 20% to match the existing LOCA AOR that meets the requirements of 10 CFR 50.46. Consistent with the existing LOCA analysis, the proposed TS changes, relating to ECCS flow, are justified.

10

Need for ECCS Pump TS SR Flow Acceptance Criteria Change

  • To support the TS ECCS flow rate changes, LGS requested GEH to perform a supplemental LOCA analysis using NRC approved SAFER/PRIME methodology using nominal assumptions (GEH document 006N4699) per the rules of engagement contained in NEDC-30936P at the Limerick 10CFR50.46 LOCA AOR flowrate of 8,000 gpm for a LPCI pump and 5,000 gpm for CS loop for both limiting liquid line breaks (recirculation suction line breaks, RSLB) and the limiting steam line breaks (main steam line breaks inside containment, STML).
  • The supplemental GEH 006N4699 analysis concluded that the limiting Peak Cladding Temperature (PCT) for all cases was below the acceptance criteria of 2200F for ECCS performance, same acceptance criteria as that specified in Section 3.3.2 of NEDC-30936P.
  • With the revised ECCS Pump flow acceptance criteria, the CSS and LPCI pumps can deliver these lower flows within the new proposed TS SR EDG steady state frequency uncertainty bands.

11

Need for ECCS Pump TS SR Flow Acceptance Criteria Change

  • References / Precedent:

GE-Hitachi Nuclear Energy, 0000-0111-9078-R0, Limerick Generating Station Units 1 and 2 GNF2 ECCS-LOCA Evaluation, February 2011 GE-Hitachi Nuclear Energy, 005n3990, Limerick Generating Station Units 1 and 2 GNF3 ECCS-LOCA Evaluation, December 2020

  • GEH document 006N4699, Limerick Supplemental ECCS Flow Reduction LOCA Analysis for NEDC30936, dated June 2021
  • There is applicable precedent for ECCS Pump flow consideration with a Susquehanna submittal (ADAMS Accession No. ML17352A711); however, Susquehanna did not formally change their TS SR flow acceptance criteria 12

Proposed TS Changes 13 Surveillance Requirement Description Frequency (from current SFCP***)

SR 4.8.1.1.2.a.4 Verify that the diesel can start* and gradually accelerate to synchronous speed with steady-state generator voltage 4160 V and 4400 V and frequency 59.8 Hz and 60.8 Hz.

In accordance with Surveillance Control Program SR 4.8.1.1.2.e.2.b Within 1.8 seconds following the load rejection, the voltage is 3865 V and 4705 V, and frequency 58.8 Hz and 61.2 Hz; and

SR 4.8.1.1.2.e.2.c After steady-state conditions are reached, voltage is maintained 4160 V and 4400 V and frequency 59.8 Hz and 60.8 Hz.

SR 4.8.1.1.2.e.4.b Verifying the diesel generator starts* on the auto-start signal, energizes the emergency busses within 10 seconds, energizes the auto-connected loads through the individual load timers and operates for greater than or equal to 5 minutes while its generator is loaded with the shutdown loads. After energization, the steady-state voltage and frequency of the emergency busses is 4160 V and 4400 V and 59.8 Hz and 60.8 Hz during the test.

Table 2.3 Proposed TS SR Changes

Proposed TS Changes 14 Table 2.3 Proposed TS SR Changes SR 4.8.1.1.2.e.5 Verifying that on an ECCS actuation test signal, without loss-of offsite power, the diesel generator starts* on the auto-start signal and operates on standby for greater than or equal to 5 minutes. The generator voltage and frequency is 4160 V and 4400 V and 58.8 Hz 61.2 Hz within 10 seconds after auto-start signal; the steady-state generator voltage and frequency shall be maintained 4160 V and 4400 V and 59.8 Hz and 60.8 Hz during this test.

SR 4.8.1.1.2.e.6.b Verifying the diesel generator starts* on the auto-start signal, energizes the emergency busses within 10 seconds, energizes the auto-connected shutdown loads through the individual load timers and operates for greater than or equal to 5 minutes while its generator is loaded with the emergency loads. After energization, the steady-state voltage and frequency of the emergency busses shall be maintained 4160 V and 4400 V and 59.8 Hz and 60.8 Hz during this test.

SR 4.8.1.1.2.e.8.b Verifying that, within 5 minutes of shutting down the diesel generator after the diesel generator has operated* for at least 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> at an indicated 2700-2800 kW**, the diesel generator starts*. The generator voltage and frequency is 4160 V and 4400 V and 58.8 Hz 61.2 Hz within 10 seconds after the start signal. After steady-state conditions are reached, voltage is maintained 4160 V and 4400 V and frequency is maintained 59.8 Hz and 60.8 Hz.

Proposed TS Changes 15 Table 2.3 Proposed TS SR Changes SR 4.8.1.1.2.h In accordance with the Surveillance Frequency Control Program the diesel generator shall be started* and verified to accelerate to synchronous speed in less than or equal to 10 seconds. The generator voltage and frequency shall reach 4160 V and 4400 V and 58.8 Hz and 61.2 Hz within 10 seconds after the start signal. After steady-state conditions are reached, voltage is maintained 4160 V and 4400 V and frequency is maintained 59.8 Hz and 60.8 Hz. The diesel generator shall be started for this test by using one of the following signals:

SR 4.5.1.b.1 Each CSS pump in each subsystem develops a flow of at least 2500 gpm against a test line pressure corresponding to a reactor vessel to primary containment differential pressure of 105 psid plus head and line losses.

SR 4.5.1.b.2 Each LPCI pump in each subsystem develops a flow of at least 8000 gpm against a test line pressure corresponding to a reactor vessel to primary containment differential pressure of 20 psid plus head and line losses.

NRC Feedback

  • Feedback on minor WCAP-17308 Methodology deviations?
  • Feedback on proposed ECCS Pump Flow Acceptance Criteria changes?
  • Results of Design Analysis LM-0736 (over 600 pages) and GEH LOCA Analysis (proprietary) will be described, but full copies are not included in the LAR.
  • Will NRC be considering a Design Audit? There were no Design Audits for Braidwood/Byron WCAP-17308 submittals; Calvert Cliffs WCAP-17308 submittal did have a Design Audit.
  • Any other concerns / insights?

16

Closing Remarks

  • Questions?
  • Summary of Feedback gained
  • Schedule for Submittal

- Submittal planned by 10/29/21 17

ML21294A369 OFFICE NRR/DORL/LPL1/PM NRR/DORL/LPL1/LA NRR/DEX/EEEB/BC NAME AKlett KZelenock WMorton DATE 11/04/2021 10/25/2021 10/27/2021 OFFICE NRR/DEX/EMIB/BC (A)

NRR/DRA/APLA/BC NRR/DSS/SNSB/BC NAME ITseng BPascarelli SKrepel DATE 11/08/2021 10/21/2021 10/21/2021 OFFICE NRR/DSS/STSB/BC (A)

NRR/DORL/LPL1/BC DORL/LPL1/PM NAME NJordan JDanna VSreenivas (AKlett for)

DATE 10/23/2021 11/12/2021 11/15/2021