UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 September 23,2011 APPLICANT: Energy Northwest FACILITY:

Columbia Generating Station

SUBJECT:

SUMMARY

OF TELEPHONE CONFERENCE CALL HELD ON SEPTEMBER 12, 2011, BETWEEN THE U.S. NUCLEAR REGULATORY COMMISSION AND ENERGY NORTHWEST, CONCERNING THE DRAFT REQUEST FOR ADDITIONAL INFORMATION PERTAINING TO THE COLUMBIA GENERATING STATION, LICENSE RENEWAL APPLICATION (TAC NO. ME3058)

The U.S. Nuclear Regulatory Commission and representatives of Energy Northwest (the applicant), held a telephone conference call on September 12, 2011, to discuss and clarify the draft request for additional information (RAI) concerning the Columbia Generating Station, license renewal application. provides a listing of the participants and Enclosure 2 contains a listing of the RAI discussed with the applicant, including a brief description on the status of the item.

The applicant had an opportunity to comment on this summary.

Arthur D. Cunanan, Project Manager Projects Branch 1 Division of License Renewal Office of Nuclear Reactor Regulation Docket No. 50-397

Enclosures:

As stated cc w/encls: Listserv

TELEPHONE CONFERENCE CALL COLUMBIA GENERATING STATION LICENSE RENEWAL APPLICATION PARTICIPANTS:

Arthur Cunanan Chris Sydnor Abbas Mostala Scott Wood John Sisk Lori Tilly George Depta LIST OF PARTICIPANTS September 12, 2011 AFFI LlA TIONS:

U.S. Nuclear Regulatory Commission (NRC)

NRC Energy Northwest (EN)

EN EN General Electric (GE)

GE ENCLOSURE 1

TELEPHONE CONFERENCE CALL COLUMBIA GENERATING STATION LICENSE RENEWAL APPLICATIONS SEPTEMBER 12, 2011 The U.S. Nuclear Regulatory Commission (NRC or the staff) and representatives of Energy Northwest (the applicant), held telephone conference calls on September 12, 2011, to discuss the following draft request for additional information (RAI) concerning the Columbia Generating Station (Columbia) license renewal application (LRA).

Draft RAI 4.2-7: Related to the upper shelf energy of the N 12 nozzle forging Discussion:

The staff discussed the need for the applicant to provide a technical basis for initial upper shelf energy (USE) values of 62 ft-Ib and copper content of 0.27 percent for SA-508 Class 1 forgings material, which can be verified by the staff, in order for the applicant to demonstrate that the USE value for the N12 nozzle forgings will not pass below 50 ft-Ibs prior to the period of extended operation.

The applicant understands the staff's concern and will submit the SA-508 Class 1 raw data and calculations to the NRC so that the staff can verify the results. Some of the information is proprietary, so the applicant will submit an affidavit to redact proprietary information from being viewed by the public. A non-proprietary version of the document will be available to the public.

The staff will send an RAI.

ENCLOSURE 2

ML11256A300

  • concurrence via e-mail OFFICE LA: DLR/RPB1* PM: DLR/RPB1 BC: DLR/RPB1 LA: DLR/RPB1 PM: DLR/RPB1 NAME SFigueroa ACunanan DMorey SFigueroa ACunanan 114/2011 09116/2011 09/21/2011 09/22/2011 09/23/2011

Letter to Energy Northwest from Arthur D. Cunanan dated September 23,2011

SUBJECT:

SUMMARY

OF TELEPHONE CONFERENCE CALL HELD ON SEPTEMBER 12. 2011, BETWEEN THE U.S. NUCLEAR REGULATORY COMMISSION AND ENERGY NORTHWEST, CONCERNING THE DRAFT REQUEST FOR ADDITIONAL INFORMATION PERTAINING TO THE COLUMBIA GENERATING STATION, LICENSE RENEWAL APPLICATION (TAC NO. ME3058)

DISTRIBUTION:

E-MAIL:

PUBLIC RidsNrrDlr Resource RidsNrrDlrRpb1 Resource RidsNrrDlrRpb2 Resource RidsNrrDIrRarb Resource RidsNrrDlrRapb Resource RidsNrrDlrRasb Resource RidsNrrDlrRerb Resource RidsNrrDlrRpob Resource DDoyle MThadani WWalker. RIV RCohen, RIV LSubin,OGC