Summary of Telephone Conference Call Held on August 11, 2011, Between the NRC and Energy Northwest, Concerning the Response to the Request for Additional Information Pertaining to the Columbia Generation Station, LRA
ML11223A351
Person / Time
Site: Columbia 
(NPF-021)
Issue date: 08/23/2011
From: Cunanan A
License Renewal Projects Branch 1
To:
Energy Northwest
Cunanan A
References
TAC ME3058
Download: ML11223A351 (5)


Text

t.,,11 REG,.

c,\\.

vl..q UNITED STATES 11 NUCLEAR REGULATORY COMMISSION

~

.4

..~.:;~'"0 WASHINGTON. D.C. 20555-0001 0

0 UI s::

cs.

August 23.2011

~...

f?!

')

....0 Jt***~

APPLICANT: Energy Northwest FACILITY:

Columbia Generating Station

SUBJECT:

SUMMARY

OF TELEPHONE CONFERENCE CALL HELD ON AUGUST 11,2011, BETWEEN THE U.S. NUCLEAR REGULATORY COMMISSION AND ENERGY NORTHWEST, CONCERNING THE RESPONSE TO THE REQUEST FOR ADDITIONAL INFORMATION PERTAINING TO THE COLUMBIA GENERATING STATION, LICENSE RENEWAL APPLICATION (TAC NO. ME3058)

The U.S. Nuclear Regulatory Commission and representatives of Energy Northwest (the applicant). held a telephone conference call on August 11. 2011, to discuss and clarify the response to the request for additional information (RAI) concerning the Columbia Generating Station, license renewal application. provides a listing of the participants and Enclosure 2 contains a listing of the RAI discussed with the applicant, including a brief description on the status of the item.

The applicant had an opportunity to comment on this summary.

~b~

Arthur D. Cunanan, Project Manager Projects Branch 1 Division of License Renewal Office of Nuclear Reactor Regulation Docket No. 50-397

Enclosures:

As stated cc w/encls: Listserv

TELEPHONE CONFERENCE CALL COLUMBIA GENERATING STATION LICENSE RENEWAL APPLICATION PARTlel PANTS:

Arthur Cunanan Allen Hiser Abbas Mostala Janet Worthington Ron Finnin David Lee LIST OF PARTICIPANTS August 11, 2011 AFFILIATIONS:

U.S. Nuclear Regulatory Commission (NRC)

NRC Energy Northwest (EN)

EN AREVA AREVA ENCLOSURE 1

TELEPHONE CONFERENCE CALL COLUMBIA GENERATING STATION LICENSE RENEWAL APPLICATIONS AUGUST 11, 2011 The U.S. Nuclear Regulatory Commission (NRC or the staff) and representatives of Energy Northwest (the applicant), held telephone conference calls on August 11, 2011, to discuss the following response to the request for additional information (RAJ) concerning the Columbia Generating Station (Columbia) license renewal application (LRA).

Response to RAI B.2.1 0-2: Related to the core plate rim hold-down bolts Discussion:

The NRC noted that the applicant did not disposition the core plate rim hold-down bolts time limited aging analysis (TLAA) in accordance with Title 10 of the Code of Federal Regulations (10 CFR) 54.21 (c)(1), or provide an Aging Management Report (AMR) line item for the core plate rim hold-down bolts with an aging effect of loss of preload due to stress relaxation.

The applicant stated that it will provide an LRA supplement to include dispositioning the core plate rim hold-down bolts TLAA under 10 CFR 54.21 (c)(1 )(iii) which will credit the BWRVIP Program for managing the effects of aging related to core plate rim hold-down bolts. The applicant will also include an AMR line item for the core plate rim hold-down bolts.

The staff finds the proposed statement acceptable but due to the schedule for issuing the safety evaluation report with open items, this issue will be identified as confirmatory item (CI) 4.7.4-1 The staff will not send an additional RAJ.

ENCLOSURE 2

August 23, 2011 APPLICANT: Energy Northwest FACILITY:

Columbia Generating Station

SUBJECT:

SUMIVIARY OF TELEPHONE CONFERENCE CALL HELD ON AUGUST 11, 2011, BETWEEN THE U.S. NUCLEAR REGULATORY COMMISSION AND ENERGY NORTHWEST, CONCERNING THE RESPONSE TO THE REQUEST FOR ADDITIONAL INFORMATION PERTAINING TO THE COLUMBIA GENERATING STATION, LICENSE RENEWAL APPLICATION (TAC NO. ME3058)

The U.S. Nuclear Regulatory Commission and representatives of Energy Northwest (the applicant), held a telephone conference call on August 11, 2011, to discuss and clarify the response to the request for additional information (RAI) concerning the Columbia Generating Station, license renewal application. provides a listing of the participants and Enclosure 2 contains a listing of the RAI discussed with the applicant, including a brief description on the status of the item.

The applicant had an opportunity to comment on this summary.

IRA!

Arthur D. Cunanan, Project Manager Projects Branch 1 Division of License Renewal Office of Nuclear Reactor Regulation Docket No. 50-397

Enclosures:

As stated cc w/encls: Listserv DISTRIBUTION:

See next page ADAMS Accession No.: ML11223A351

  • concurrence via e-mail

[I OFFICE. 1 LADLR/RPB1*i NAME I SFigueroa ACunanan DATE 1081' 12/2011 08/22/2011 LA: DLR/RPB1 IPM: DLR/RPB1 DMorey SFigueroa ACunanan 08/22/2011 08/23/2011 08/23/2011 OFFICIAL RECORD COpy