NAI-1149-016, Rev. 1 Page 1 of 249 NAI Report Release Calculation Number: NAI-1149-016 Revision Number: 1

Title:

Palisades Design Basis Fuel Handling Accident AST Radiological Analysis

==

Description:==

Revision 0 This calculation reanalyzes the radiological consequences of the Fuel Handling Accident presented in Section 14.19 of the Palisades FSAR using the AST methodology described in USNRC Reg. Guide 1.183.

Revision 1 This revision corrects the values and header for the table in Section 7.1.10. No models or results are impacted by the typographicalcorrection.

w - L b I17Ioc Author Date Steven G. Thomasson 6 / f7b.S Date Jim Harrell NAI Management Tim ~ u i d s l

NAI-1149-016, Rev. 1 Page 2 of 249 NAI Calculation Approval Calculation Number: NAI-1149-016 Revision Number: 1

Title:

Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation

Description:

Revision 0 This calculation reanalyzes the radiological consequences of the Fuel Handling Accident presented in Section 14.19 of the Palisades FSAR using the AST methodology described in USNRC Reg. Guide 1.183.

Revision 1 This revision corrects the values and header for the table in Section 7.1 .lo. No models or results are impacted by the typographical correction.

,$ti- G.T(--.- b\r>l o <

I .

Author Date Steven G. Thomasson

NAI-1149-016, Rev. 1 Page 3 of 249 Scope of Review: i I

1 Review included:

e A review of calculation methods was completed for consistency with plant-specific and generic regulatory requirements and guidance.

e Computer codes (RADTRAD-NAI) were checked for appropriate qualification.

o Calculation and code inputs and assumptions were verified against IAM document(s) and/or checked for reasonableness and conservatism.

e Computations were checked for correctness.

e References were verified as appropriate.

e Outputs from spreadsheets and utility programs were checked.

0 Reported Results were verified against computer outputs.

o Results and conclusions were reviewed for reasonableness.

e Cases run were checked against procurement documents.

Design Verification - See Attachment 1 for Rev. 0 comments. There are no Rev. 1 comments.

  1. L Dafl17/05-eviewer Jim Harrell

NAI-1149-016, Rev. 1 Page 4 of 249 I

i r

Check items in the following lists to verify that project documentation and engineering I calculations are complete. Mark any items that are not applicable with NIA notation.

Project Documentation Checklist:

Project QA Plan.

Project Organization.

o Project Work Scope and Design Plan.

Project Calculation and Document Index.

Project QA Requirements.

Project Engineer Training and Qualification Forms.

Project QA Training Certification Forms.

o Project Correspondence.

Engineering Calculations Checklist:

d Identification by subject, originator, reviewer, date and Project so that the calculation

's retrievable.

d I/

Table of contents.

Statement of the objective of the analysis.

d ~ n a l ~ sinputs i s and their sources.

Q/ ssumptions and how they were developed or determined.

9 2

and calculations.

Identification of computer calculations, including computer type, computer program ame and version, code input and output.

Conclusions.

d Review summary.

d Responses to review comments.

d~eferences.

d Each page of the calculation shall be numbered and the first page shall indicate the total number of pages. The calculation pages may be numbered by sections with the first page of the section indicating the total number of pages in the section.

d The Calculation Approval Sheet shall be signed and dated by the originator.

Numerical Applications Inc. Page 5 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Table of Contents

1.0 INTRODUCTION

............................................................................................................................ 7 2.0

SUMMARY

OF RESULTS ............................................................................................................. 7 3.0 DESIGN INPUT ............................................................................................................................... 9 3.1 SOURCE TERM INPUT ...................................................................................................................... 9 3.2 OTHER INPUT .................................................................................................................................. 9 4.0 ASSUMPTIONS ............................................................................................................................... 9 5.0 ACCEPTANCE CRITERIA.......................................................................................................... 10 6.0 COMPUTER CODES .................................................................................................................... 11 7.0 CALCULATIONS.......................................................................................................................... 12 7.1 FUEL HANDLING ACCIDENT BASE CASE RADTRAD-NAI MODEL .............................................. 12 7.1.1 Fuel Pool Release-Unfiltered (Compartment 1)................................................................... 14 7.1.2 Environment (Compartment 2) ............................................................................................. 14 7.1.3 Control Room (Compartment 3) ........................................................................................... 14 7.1.4 Fuel Pool Release-Filtered (Compartment 4) ...................................................................... 14 7.1.5 Fuel Pool Unfiltered Release to Environment (Pathway 1).................................................. 14 7.1.6 Control Room Unfiltered Makeup (Pathway 2).................................................................... 15 7.1.7 Control Room Filtered Makeup (Pathway 3) ....................................................................... 15 7.1.8 Control Room Unfiltered Inleakage (Pathway 4) ................................................................. 15 7.1.9 Control Room Exhaust (Pathway 5) ..................................................................................... 15 7.1.10 Fuel Pool Filtered Release to Environment (Pathway 6) ..................................................... 16 7.1.11 Plant Power and Release Information.................................................................................. 16 7.1.12 Overlying Pool...................................................................................................................... 16 7.1.13 Dose Location Information................................................................................................... 18 7.1.14 Source Term.......................................................................................................................... 21 7.1.15 Release Fraction Timing File ............................................................................................... 21 7.2 FUEL HANDLING ACCIDENT CASE 1 RADTRAD-NAI MODEL ..................................................... 21 7.3 FUEL HANDLING ACCIDENT CASE 2 RADTRAD-NAI MODEL ..................................................... 21 7.4 FUEL HANDLING ACCIDENT CASE 3 RADTRAD-NAI MODEL ..................................................... 22

8.0 REFERENCES

............................................................................................................................... 24 9.0 FHA RADTRAD-NAI ANALYSIS FILES................................................................................... 25

Numerical Applications Inc. Page 6 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Tables Table 2-1 Radiological Doses for Fuel Handling Accident - Base Case ...................................... 7 Table 2-2 Radiological Doses for Fuel Handling Accident - Case 1 - 10% Filtered .................... 8 Table 2-3 Radiological Doses for Fuel Handling Accident - Case 2 - 34% Filtered .................... 8 Table 2-4 Radiological Doses for Fuel Handling Accident - Case 3 - 50% Filtered .................... 8 Table 7-1 FHA Release Fraction Timing File .............................................................................. 23 Figures Figure 1 FHA RADTRAD-NAI Model........................................................................................... 13 Attachments Verification Comments for Calculation NAI-1149-016 Rev. 0.............................. 26 RADTRAD-NAI FHA Output - Base Case............................................................ 28 RADTRAD-NAI FHA Output - Case 1 - 10% Filtered.......................................... 72 RADTRAD-NAI FHA Output - Case 2 - 34% Filtered........................................ 121 RADTRAD-NAI FHA Output - Case 3 - 50% Filtered........................................ 170 FHA Nuclide Inventory File ................................................................................. 219 RADTRAD-NAI Dose Conversion Factor File..................................................... 233

Numerical Applications Inc. Page 7 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 1.0 Introduction The purpose of this calculation is to reanalyze the radiological consequences of the Fuel Handling Accident (FHA) presented in Section 14.19 of the Palisades FSAR (Reference 2). This reanalysis will use the AST methodology described in Regulatory Guide 1.183 (Reference 1).

Appendix B of the Reg. Guide outlines the requirements for performing a radiological analysis of a FHA.

There are two possible release paths for the activity that escapes the fuel pool in containment; an unfiltered release via the containment equipment hatch, and a filtered release via the FHB ventilation system which exhausts via the plant stack. A series of cases were run:

  • Base Case with 100% of the release via the plant equipment hatch
  • Case 1 with 10% of the release via the FHB filtration system
  • Case 2 with 34% of the release via the FHB filtration system
  • Case 3 with 50% of the release via the FHB filtration system The results presented in this document are bounding values that cover a FHA accident in either the fuel handling building or containment.

2.0 Summary of Results The following table presents the results of the Fuel Handling Accident case analyzed. The direct shine dose contribution is the sum of the cloud and filter shine doses documented in Table 1 of Reference 12.

Table 2-1 Radiological Doses for Fuel Handling Accident - Base Case Dose (rem TEDE)

Dose Contribution EAB LPZ CR 2-hr 30 days 30 days Fuel Damage Dose 2.2004E+00 2.7622E-01 3.7755E+00 Shine Dose 0.268 Total 2.20 0.28 4.04 Acceptance Criteria 6.3 6.3 5 Control Room Unfiltered Inleakage = 100 cfm The analysis demonstrates that a FHA within the containment while the maintenance hatch is open or within the Fuel Handling Building (FHB) will not produce doses in excess of the prescribed limits. The results presented in this document are bounding values that cover a FHA accident in either the fuel handling building or containment.

Numerical Applications Inc. Page 8 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Table 2-2 Radiological Doses for Fuel Handling Accident - Case 1 - 10% Filtered Dose (rem TEDE)

Dose Contribution EAB LPZ CR 2-hr 30 days 30 days Fuel Damage Dose 2.0224E+00 2.5413E-01 3.4115E+00 Shine Dose 0.268 Total 2.02 0.25 3.68 Acceptance Criteria 6.3 6.3 5 Control Room Unfiltered Inleakage = 100 cfm Table 2-3 Radiological Doses for Fuel Handling Accident - Case 2 - 34% Filtered Dose (rem TEDE)

Dose Contribution EAB LPZ CR 2-hr 30 days 30 days Fuel Damage Dose 1.5953E+00 2.0111E-01 2.5381E+00 Shine Dose 0.268 Total 1.60 0.20 2.81 Acceptance Criteria 6.3 6.3 5 Control Room Unfiltered Inleakage = 100 cfm Table 2-4 Radiological Doses for Fuel Handling Accident - Case 3 - 50% Filtered Dose (rem TEDE)

Dose Contribution EAB LPZ CR 2-hr 30 days 30 days Fuel Damage Dose 1.3106E+00 1.6576E-01 1.9558E+00 Shine Dose 0.268 Total 1.31 0.17 2.22 Acceptance Criteria 6.3 6.3 5 Control Room Unfiltered Inleakage = 100 cfm

Numerical Applications Inc. Page 9 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 3.0 Design Input 3.1 Source Term Input Reference 5 defines the event as damage to all of the fuel pins in 1 fuel assembly. As described in Section 6.3 of Reference 8, the design basis source term for a limiting fuel assembly for a FHA was defined in Table 6-8 of that calculation and incorporated into the nif file included as 5 to that calculation. Note that per the discussion given in Section 7.1.15, the activites for I-131 and Kr-85 will be adjusted to account for different gap release fractions for these isotopes as specified by Table 3 of Reg. Guide 1.183.

3.2 Other Input Reference 5 lists other input, provided by Palisades, used in the development of the Palisades FHA RADTRAD-NAI models.

4.0 Assumptions

  • Mixing of the release from the fuel pool with the containment (or fuel handling building) atmosphere is ignored.
  • At all times, a minimum of 22.5 feet of water is maintained above the damaged fuel. Thus, per Section 2.0 of Appendix B to Reg. Guide 1.183, the decontamination factor for elemental iodine will be adjusted to account for less than 23 feet of water coverage.
  • The analysis will assume a decay time of 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> before fuel movement as identified in Reference 5. This decay time is included in the FHA source term presented in Reference 8.
  • Per Reg. Guide 1.183, the release is assumed to occur over a 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> period.

Numerical Applications Inc. Page 10 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 5.0 Acceptance Criteria Per Section 4.4 and Table 6 of Reg. Guide 1.183, the acceptable dose limits for the Exclusion Area Boundary (EAB), Low Population Zone (LPZ), and Control Room (CR) for a FHA are:

Fuel Handling Accident Dose Limits Area Dose Criteria EAB 6.3 rem (TEDE) (worst 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />)

LPZ 6.3 rem (TEDE) (for 30 days)

Control Room 5 rem (TEDE) (for 30 days)

Control room dose limit is specified in 10CFR50.67

Numerical Applications Inc. Page 11 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 6.0 Computer Codes The following computer code was used for performing the analyses presented in this calculation:

Computer Code Version Reference Purpose RADTRAD-NAI 1.1a(QA) 3 Radiological Dose Calculations RADTRAD-NAI (Reference 3) is qualified and maintained under the Numerical Applications Inc.

QA program (Reference 4). This QA program meets the requirements of 10CFR50 Appendix B with code error reporting per 10CFR21. RADTRAD-NAI is accessed via a controlled access web-based interface that provides a front-end for developing and submitting input models. The input developed via the interface is submitted to the RADTRAD-NAI solver that runs on an AMD-ATHLON based personal computer running LINUX.

Numerical Applications Inc. Page 12 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 7.0 Calculations Appendix B to Reg. Guide 1.183 sets the requirements for the transport, reduction, and release of radionuclides for the FHA. Per Reg. Guide 1.183, a FHA within the fuel building and a FHA within the containment must be considered. Since all of the release within the FHB would be filtered, the most limiting FHA will be a release inside the containment (with the assumption that the containment equipment hatch is open).

The analysis will assume a decay time of 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> before fuel movement as identified in Reference 5. The 48 hour5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> delay is included in the FHA source term provided by Reference 8.

7.1 Fuel Handling Accident Base Case RADTRAD-NAI Model The RADTRAD-NAI model developed for the FHA calculation consists of three compartments and five pathways (see Figure 1):

Compartment RADTRAD-NAI Compartment Description Number Compartment Type Fuel Pool - Unfiltered 1 (3) Normal Environment 2 (2) Environment Control Room 3 (1) Control Room Compartment Pathway RADTRAD-NAI Pathway Description Connections Number Pathway Type Fuel Pool Release-Unfiltered 1 to 2 1 Filtered Control Room Unfiltered Makeup 2 to 3 2 Filtered Control Room Filtered Makeup 2 to 3 3 Filtered Control Room Unfiltered Inleakage 2 to 3 4 Filtered Control Room Exhaust 3 to 2 5 Filtered

Numerical Applications Inc. Page 13 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Figure 1 FHA RADTRAD-NAI Model Unfiltered Inleakage Compartment 1 Compartment 2 Compartment 3 Fuel Pool Release Fuel Pool Environment Control Room Leakage Filtered Unfiltered Unfiltered Makeup Unfiltered Makeup Compartment 4 Exhaust Fuel Pool Release Flow Fuel Pool Filtered Leakage Filtered

Numerical Applications Inc. Page 14 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 The subsections that follow describe the RADTRAD-NAI input for the FHA.

7.1.1 Fuel Pool Release-Unfiltered (Compartment 1)

The following input was specified for the Fuel Pool Source Volume:

Dummy value assumed, a convective flow path is used Volume 10,000 ft3 to release the fuel pool activity to the environment Source Fraction 1.00 100% of source term applied to Fuel Pool volume Recirculation Filters no Natural Deposition no Overlying Pool yes Model 22.5 feet of water above damaged fuel assembly 7.1.2 Environment (Compartment 2)

The only required input for the environment compartment is volume. This value is a dummy value; however, an input is required for this field. An arbitrary value of 2.0E20 ft3 was specified.

7.1.3 Control Room (Compartment 3)

The control room volume was set to 35,923 ft3. The control room HVAC system is assumed to be operating in normal mode at the beginning of the event. The control room enters emergency mode at 20 minutes (manual operator action).

Time Flow Rate Filter Efficiency (hours) (cfm) Aerosol Elemental Organic 0.0 0.0 99 99 99 0.3333 1413.6 99 99 99 720.0 1413.6 99 99 99 7.1.4 Fuel Pool Release-Filtered (Compartment 4)

The following input was specified for the Fuel Pool Source Volume:

Dummy value assumed, a convective flow path is used Volume 10,000 ft3 to release the fuel pool activity to the environment Source Fraction 0.0 No unfiltered release Recirculation Filters no Natural Deposition no Overlying Pool yes Model 22.5 feet of water above damaged fuel assembly 7.1.5 Fuel Pool Unfiltered Release to Environment (Pathway 1)

This pathway connects the Fuel Pool-Unfiltered (Compartment 1) with the Environment Compartment (Compartment 2) and represents the unfiltered release that exits via the equipment hatch. Reg. Guide 1.183 specifies that the release from the spent fuel pool be leaked to the environment over a two hour period. The two hour release period is handled via the release fraction timing file; therefore, a high flow rate is used to extract the release from the fuel pool

Numerical Applications Inc. Page 15 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 compartment. A 100% filter efficiency is specified for the aerosol release fraction (no aerosol release per page B-2 of Reg. Guide 1.183).

Equipment Hatch Release Time Flow Rate Filter Efficiency (hours) (cfm) Aerosol Elemental Organic 0.0 1e6 100 0 0 720.0 1e6 100 0 0 7.1.6 Control Room Unfiltered Makeup (Pathway 2)

The initial unfiltered makeup flow rate is 660 cfm. After control room isolation at 20 minutes, the flow is 0 cfm.

Unfiltered Makeup Flow Time Flow Rate Filter Efficiency (hours) (cfm) Aerosol Elemental Organic 0.0 660.0 0 0 0 0.3333 0.0 0 0 0 720.0 0.0 0 0 0 7.1.7 Control Room Filtered Makeup (Pathway 3)

The control room filtered makeup flow of 1413.6 cfm starts at 20 minutes (time of control room isolation).

Filtered Makeup Flow Time Flow Rate Filter Efficiency (hours) (cfm) Aerosol Elemental Organic 0.0 0.0 99 99 99 0.3333 1413.6 99 99 99 720.0 1413.6 99 99 99 7.1.8 Control Room Unfiltered Inleakage (Pathway 4)

The unfiltered inleakage was set to 100 cfm.

Unfiltered Inleakage Time Flow Rate Filter Efficiency (hours) (cfm) Aerosol Elemental Organic 0.0 0.0 0 0 0 0.3333 100.0 0 0 0 720.0 100.0 0 0 0 7.1.9 Control Room Exhaust (Pathway 5)

The control room exhaust is equal to the sum of the control room intake and inleakage flows.

Numerical Applications Inc. Page 16 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Exhaust Flow Time Flow Rate Filter Efficiency (hours) (cfm) Aerosol Elemental Organic 0.0 660.0 0 0 0 0.3333 1513.6 0 0 0 720.0 1513.6 0 0 0 7.1.10 Fuel Pool Filtered Release to Environment (Pathway 6)

This pathway connects the Fuel Pool-Filtered Compartment (Compartment 4) with the Environment Compartment (Compartment 2) and represents the filtered release that exits via the FHB filtration system exhausting via the plant stack. Reg. Guide 1.183 specifies that the release from the spent fuel pool be leaked to the environment over a two hour period. The two hour release period is handled via the release fraction timing file; therefore, a high flow rate is used to extract the release from the fuel pool compartment. A 100% filter efficiency is specified for the aerosol release fraction, and a 94% elemental and organic efficiency was specified (Reference14).

Fuel Pool Filtered Release Time Flow Rate Filter Efficiency (hours) (cfm) Aerosol Elemental Organic 0.0 1e6 100 94 94 720.0 1e6 100 94 94 7.1.11 Plant Power and Release Information The design basis power in the FHA nuclide inventory file is 2703 MWth. The nuclide inventory file contains the total number of curies for one damaged fuel assembly; therefore, the plant power entry in the RADTRAD-NAI input file was also set to 2703 MWth. Item 1.3 of Appendix B to Reg.

Guide 1.183 specifies that the makeup of the iodine species is 99.85% elemental and 0.15%

organic:

Start of first release time (hours) 0.0 Calculate decay yes Calculate daughters yes Iodine Fraction - aerosol 0.0 Iodine Fraction - elemental 0.9985 Iodine Fraction - organic 0.0015 7.1.12 Overlying Pool Item 2 of Appendix B to Reg. Guide 1.183 states:

If the depth of water above the damaged fuel is 23 feet or greater, the decontamination factors for the elemental and organic species are 500 and 1, respectively, giving an overall effective decontamination factor of 200 (i.e., 99.5% of the total iodine released from the damaged rods is retained by the water). This difference in decontamination factors for elemental (99.85%) and organic iodine (0.15%) species results in the iodine above the water being

Numerical Applications Inc. Page 17 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 composed of 57% elemental and 43% organic species. If the depth of water is not 23 feet, the decontamination factor will have to be determined on a case-by-case method (Ref. B-1).

The guidance quoted above sets out an inconsistent set of conditions for the elemental iodine decontamination factor. Recent clarification from the NRC indicates that the appropriate criteria is on overall decontamination factor of 200. Based on the release fractions of 99.85% elemental and 0.15% organic, an elemental iodine decontamination factor of approximately 285 is required to produce an overall decontamination factor of 200.

In addition, Section 3.0 of Appendix B to Reg. Guide 1.183 states:

The retention of noble gases in the water in the fuel pool or reactor cavity is negligible (i.e., decontamination factor of 1). Particulate radionuclides are assumed to be retained by the water in the fuel pool or reactor cavity (i.e., infinite decontamination factor).

Per the inputs listed in Reference 5, 22.5 feet of water will be maintained above the damaged fuel; therefore, the decontamination factor for elemental iodine must be adjusted. The decontamination factor for organic iodine was set to 1.0.

Page 26 of Reference 6 gives an equation for the DF for elemental iodine as a function of pool depth:

( 6 / d b )( k eff )( H ) /( vb )

DFF = e where: H = bubble rise height (cm) vb = rise velocity keff = effective mass transfer coefficient db = bubble diameter DF = I2 decontamination factor Since there is only a 6 difference between 23 and 22.5 it is assumed that all of the parameters listed above are the same at both 23 and 22.5, the equation above can be rewritten as follows:

DFF = e ( cons tan t )( H )

Thus for a DF of 285 for elemental iodine with a pool depth of 23 (701.04 cm):

285 = e(constant)(701.04) constant = 0.008063 The DF for elemental iodine for a pool depth of 22.5 (685.8 cm) is:

DF = e(0.008063)(685.8) = 252 Therefore, with a pool depth of 22.5, the DF for organic iodine is 1 and the DF for elemental iodine is 252.

The effective DF for iodine (page 26 of Reference 6) for a pool depth of 22.5 is:

DFeff = [(elemental fraction / DFelemental) + (organic fraction / DForganic)]-1 DFeff = [(0.9985 / 252) + (0.0015 / 1)]-1 = 183.07

Numerical Applications Inc. Page 18 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 7.1.13 Dose Location Information Three dose locations were specified; the Exclusion Boundary (EAB), the Low Population Zone (LPZ), and the Control Room (CR). The X/Qs for the EAB and LPZ are from Table 5 of Reference 10. The breathing rates are from Section 4.1.3 of Reg. Guide 1.183:

Exclusion Boundary Data:

EAB /Q X/Q Table 1 Time (hours) X/Q (sec/m3) 0.0 5.39E-4 720.0 5.39E-4 EAB & LPZ Breathing Rate Breathing Rate Time (hours)

(m3/sec) 0.0 3.5E-4 8.0 1.8E-4 24.0 2.3E-4 720.0 2.3E-4 Low Population Zone Data:

LPZ /Q X/Q Table 2 Time (hours) X/Q (sec/m3) 0.0 6.66E-5 2.0 3.03E-5 8.0 2.04E-5 24.0 8.67E-6 96.0 2.54E-6 720.0 2.54E-6

Numerical Applications Inc. Page 19 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Control Room Data:

The breathing rates and occupancy factor for the control room are from Section 4.2.6 of Reg.

Guide 1.183. The X/Qs are from Table 4 of Reference 10. The X/Qs for unfiltered release correspond to the containment equipment hatch. The X/Qs for the filtered release correspond to the plant stack.

Control Room /Q for Equipment Hatch to Normal Intake Table 3 Time (hours) X/Q (sec/m3) 0.0 1.25E-2 2.0 9.83E-3 8.0 3.62E-3 24.0 2.86E-3 96.0 2.28E-3 720.0 2.28E-3 Control Room /Q for Equipment Hatch to Emergency Intake Table 4 Time (hours) X/Q (sec/m3) 0.0 7.32E-4 2.0 6.13E-4 8.0 2.45E-4 24.0 1.75E-4 96.0 1.29E-4 720.0 1.29E-4 Control Room /Q for Plant Stack to Normal Intake Table 5 Time (hours) X/Q (sec/m3) 0.0 6.10E-3 2.0 4.32E-3 8.0 1.73E-3 24.0 1.27E-3 96.0 9.79E-4 720.0 9.79E-4

Numerical Applications Inc. Page 20 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Control Room /Q for Plant Stack to Emergency Intake Table 6 Time (hours) X/Q (sec/m3) 0.0 8.32E-4 2.0 7.69E-4 8.0 2.83E-4 24.0 2.15E-4 96.0 1.57E-4 720.0 1.57E-4 Control Room Breathing Rate Breathing Rate Time (hours)

(m3/sec) 0.0 3.5E-4 720.0 3.5E-4 Control Room Occupancy Factor Time (hours) Factor 0.0 1.0 24.0 0.6 96.0 0.4 720.0 0.4 Dose Location Pathway Combinations Control Room Intake Release Path X/Q Table Path 2 1 3 3 1 4 4 1 3 2 6 5 3 6 6 4 6 5

Numerical Applications Inc. Page 21 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 7.1.14 Source Term Item 1.2 of Appendix B to Reg. Guide 1.183 specifies the radionuclide groups that should be considered for an radiological analysis of a FHA. Reference 9 provides a listing of the individual nuclides and dose conversion factors used for the analyses presented in this calculation. The data provided in Reference 9 are consistent with Reg. Guide 1.183. The dose conversion factors provided in Reference 9 were obtained from Table 2.1 of Federal Guidance Report 11 and Table III.1 of Federal Guidance Report 12.

7.1.15 Release Fraction Timing File Table 7-1 presents the release fraction timing file used for the FHA. The minimum allowable decay time before movement of fuel is 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />. As discussed in a previous section, the 48 hour5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> decay time is accounted for in the FHA source term.

Table 3 of Reg. Guide 1.183 specifies the following composition for the non-LOCA fraction of fission product inventory in the fuel rod gap:

Group Fraction I-131 0.08 Kr-85 0.10 Other Noble Gases 0.05 Other Halogens 0.05 Alkali Metals 0.12 The release fractions for iodine and noble gases, were set to 5% in the release fraction timing file.

The release fraction for I-131 is 0.08 versus 0.05 for the remaining iodine isotopes. To account for this difference, the source term for I-131 in the RADTRAD-NAI nuclide inventory (nif) file was increased by a factor of 1.6 (0.08 / 0.05) to 0.1028E7. Similarly, the Kr-85 source was increased by a factor of 2.0 to 0.2104E5 to adjust the Kr-85 release to the specified 10% while retaining other noble gas releases at 5% as prescribed in the release fraction timing file pal_fha_ast.rft (Table 7-1). The adjusted FHA nif file, pal_FHA_db_ast_adj.nif, is provided in Attachment 6.

7.2 Fuel Handling Accident Case 1 RADTRAD-NAI Model This model is similar to that documented in Section 7.1. The only difference is that the source term fraction for Volume 1 was set to 0.90 and the source term fraction for Volume 4 was set to 0.10.

7.3 Fuel Handling Accident Case 2 RADTRAD-NAI Model This model is similar to that documented in Section 7.1. The only difference is that the source term fraction for Volume 1 was set to 0.66 and the source term fraction for Volume 4 was set to 0.34.

Numerical Applications Inc. Page 22 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 7.4 Fuel Handling Accident Case 3 RADTRAD-NAI Model This model is similar to that documented in Section 7.1. The only difference is that the source term fraction for Volume 1 was set to 0.50 and the source term fraction for Volume 4 was set to 0.50.

Numerical Applications Inc. Page 23 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Table 7-1 FHA Release Fraction Timing File Release Fraction and Timing Name:

PWR, NUREG 1.183, Palisades FHA Release AST Duration (h): Design Basis Accident 0.1000E-02 0.1000E-02 0.2000E+01 0.0000E+00 Noble Gases:

0.0000E+00 0.0000E+00 0.0500E+00 0.0000E+00 Iodine:

0.0000E+00 0.0000E+00 0.0500E+00 0.0000E+00 Cesium:

0.0000E+00 0.0000E+00 0.1200E+00 0.0000E+00 Tellurium:

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Strontium:

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Barium:

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Ruthenium:

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Cerium:

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Lanthanum:

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Non-Radioactive Aerosols (kg):

0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 End of Release File

Numerical Applications Inc. Page 24 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 8.0 References

1. USNRC, Regulatory Guide 1.183, Alternative Radiological Source Terms for Evaluating Design Basis Accidents at Nuclear Power Plants, July 2000.
2. Palisades Nuclear Plant FSAR, Revision 24.
3. Numerical Applications Inc., NAI-9912-04, Revision 4, RADTRAD-NAI Version 1.1a(QA)

Documentation, October 2004.

4. Numerical Applications Inc., Dose Methodology Quality Assurance Procedures, Revision 1, June 4, 2001.
5. Email Jeffery Voskuil (NMC) to Jim Harrell (NAI), dated June 28 2004,

Subject:

FHA Inputs.

6. G. Burley, Evaluation of Fission Product Release and Transport for a Fuel Handling Accident, October 5 1971.
7. Palisades Plant Technical Specifications through Amendment 213.
8. NAI Calculation Number NAI-1149-001 Rev. 1, Source Terms for Palisades Dose Calculations.
9. NAI Calculation Number NAI-1101-001 Rev. 1, Generation of .nif and .inp Files for RADTRAD-NAI.
10. NAI Calculation Number NAI-1149-002 Rev. 0, Determination of Atmospheric Dispersion Factors for Palisades.
11. Reference deleted.
12. NAI Calculation Number NAI-1149-003 Rev. 1, Determination of Direct Shine Doses for a LOCA for Palisades.
13. NAI-E03-211 Project Memo 2004-09, Additional Inputs, October 20 2004.
14. Email Jeffery Voskuil (NMC) to Jim Harrell and Steve Thomasson (NAI), dated October 8 2004,

Subject:

Response to Input Questions from NAI.

Numerical Applications Inc. Page 25 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 9.0 FHA RADTRAD-NAI Analysis Files RADTRAD-NAI FHA Cases File Name Attachment Description pal_fha_db_ast_nofilter.out Attachment 2 FHA Base Case RADTRAD-NAI Model output pal_fha_db_ast_10filter.out Attachment 3 FHA Case 1 RADTRAD-NAI Model output pal_fha_db_ast_34filter.out Attachment 4 FHA Case 2 RADTRAD-NAI Model output pal_fha_db_ast_50filter.out Attachment 5 FHA Case 3 RADTRAD-NAI Model output pal_FHA_db_ast_adj.nif Attachment 6 FHA Nuclide Inventory File pal_fha_ast.rft Table 7-1 FHA Release Fraction Timing File NAI-1101-001rev0.dcf Attachment 7 Dose Conversion Factor File

Numerical Applications Inc. Attachment 1 Page 26 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Attachment 1 Verification Comments for Calculation NAI-1149-016 Rev. 0 Comment 1 Page 6, Tables - Table 2-1 Radiological Doses for Fuel Handling Accident - Case 3 - 50%

Filtered should be Table 2-4.

Response: TOC has been updated.

Comment 2 Page 9 - This page is blank, but it may be associated with the version of Word or printer selected.

Response: Blank page has been removed.

Comment 3 Page 10, Section 3.1 - Check Section, Table and Attachment numbers from Reference 8 (NAI-1149-001, R1) for correct selection of the design basis FHA source term. It appears that the section should be 6.3 versus 6.4, that the Table should be 6-8 versus 6-5 and that the Attachment should be 25 versus 19. The table numbers in the pdf for NAI-1149-001, R1 (page 19) appear to be corrupted and/or incorrect in many cases. Please re-convert the file with corrected table numbers and provide a copy of the re-converted file to the appropriate distribution.

Response: References have been changed to point to design basis data (Section 6.3, Table 6-8, and Attachment 25)

Comment 4 Page 13, Section 7.0 - Suggest rewording containment equipment door to containment equipment hatch for consistency.

Response: Fixed.

Comment 5 Page 15, Section 7.1.5 - Suggest adding the basis for no aerosol release (e.g., item 3 on page B-2 of RG 1.183) in section 3.0 or 4.0. This basis appears to be after this section in section 7.1.12.

Response: Basis has been added.

Comment 6 Page 17, Section 7.1.10 - Suggest adding the word Compartment after Fuel Pool-Filtered.

Response: Fixed

Numerical Applications Inc. Attachment 1 Page 27 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Comment 7 Page 17, Section 7.1.11 - 2703 MWt is the design basis value for plant power, not best-estimate.

Response: Best-estimate changed to Design basis.

Comment 8 Page 18, Section 7.1.12 - Since the bubble diameter (and to some extent, the shape factor) is the key parameter that impacts the rise velocity and the effective mass transfer coefficient and since the bubble diameter is predominantly based on the fuel configuration, the constant assumption is reasonable. No response required.

Numerical Applications Inc. Attachment 2 Page 28 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Attachment 2 RADTRAD-NAI FHA Output - Base Case RADTRAD-NAI Version 1.1a(QA) run on May 20, 2005 at 07:09:52 File information Plant file name = pal/FHA/db/pal_fha_db_ast_nofilter.psf Inventory file name = pal/FHA/db/palisades_fha_db_ast_adj.nif Scenario file name = pal/FHA/db/pal_fha_db_ast_nofilter.psf Release file name = pal/FHA/db/pal_fha_ast.rft Dose conversion file name = pal/FHA/db/nai-1101-001rev0.dcf

  • RADTRAD-NAI 1.1a(QA)
  • 20 May 2005 07:09:48
    • Palisades FHA Design Basis
    • No release filtration
  • Nuclide inventory file pal/FHA/db/palisades_fha_db_ast_adj.nif
  • Plant power 2703
  • Compartments 4
  • Compartment 1:

Fuel Pool-Unfiltered 3

10000 0

0 0

1

  • Compartment 2:

Environment 2

2e+20 0

0 0

0

  • Compartment 3:

Control Room 1

35923 0

1 0

0

  • Compartment 4:

Fuel Pool-Filtered 3

10000 0

0 0

1

Numerical Applications Inc. Attachment 2 Page 29 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1

  • Pathways 6
  • Pathway 1:

Fuel Pool Release-Unfiltered 1

2 2

  • Pathway 2:

Control Room Unfiltered Makeup 2

3 2

  • Pathway 3:

Control Room Filtered Makeup 2

3 2

  • Pathway 4:

Control Room Unfiltered Inleakage 2

3 2

  • Pathway 5:

Control Room Exhaust 3

2 2

  • Pathway 6:

Fuel Pool Release-Filtered 4

2 2

  • Sources 4

1 1 2 0 3 0 4 0

  • dose conversion factors filename pal/FHA/db/nai-1101-001rev0.dcf
  • release fraction and timing filename pal/FHA/db/pal_fha_ast.rft 0

1 1

  • Iodine 0 0.9985 0.0015
  • Overlying pool
  • aerosol model 0
  • elemental model 1

2 0 252 720 252

  • organic model 1

2 0 1 720 1

  • pH tracking 0
  • Compartment detail
  • Compartment 1:

1

  • spray model 0

0 0

  • filter model 0
  • deposition model 0

Numerical Applications Inc. Attachment 2 Page 30 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 0

  • Compartment 2:

1

  • spray model 0

0 0

  • filter model 0
  • deposition model 0

0

  • Compartment 3:

1

  • spray model 0

0 0

  • filter model 1

3 0 0 99 99 99 0.3333 1413.6 99 99 99 720 1413.6 99 99 99

  • deposition model 0

0

  • Compartment 4:

1

  • spray model 0

0 0

  • filter model 0
  • deposition model 0

0

  • Pathways:
  • Pathway 1
  • filter efficiency model 1

2 0 1000000 100 0 0 720 1000000 100 0 0

  • Pathway 2
  • filter efficiency model 1

3 0 660 0 0 0 0.3333 0 0 0 0 720 0 0 0 0

  • Pathway 3
  • filter efficiency model 1

3 0 0 99 99 99 0.3333 1413.6 99 99 99 720 1413.6 99 99 99

  • Pathway 4
  • filter efficiency model 1

3 0 0 0 0 0 0.3333 100 0 0 0 720 100 0 0 0

  • Pathway 5
  • filter efficiency model 1

3 0 660 0 0 0 0.3333 1513.6 0 0 0 720 1513.6 0 0 0

Numerical Applications Inc. Attachment 2 Page 31 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1

  • Pathway 6
  • filter efficiency model 1

2 0 1000000 100 94 94 720 1000000 100 94 94

  • x/q tables 6

EAB 2

0 0.000539 720 0.000539 LPZ 6

0 6.66e-05 2 3.03e-05 8 2.04e-05 24 8.67e-06 96 2.54e-06 720 2.54e-06 Equip Hatch-Normal 6

0 0.0125 2 0.00983 8 0.00362 24 0.00286 96 0.00228 720 0.00228 Equip Hatch-Emergency 6

0 0.000732 2 0.000613 8 0.000245 24 0.000175 96 0.000129 720 0.000129 Stack-Normal 6

0 0.0061 2 0.00432 8 0.00173 24 0.00127 96 0.000979 720 0.000979 Stack-Emergency 6

0 0.000832 2 0.000769 8 0.000283 24 0.000215 96 0.000157 720 0.000157

  • dose locations 3
  • location name, compartment number and x/q table EAB 2

1

  • br model 1

4 0 0.00035 8 0.00018 24 0.00023 720 0.00023

  • of model 0
  • location x/q input to be included 0
  • location name, compartment number and x/q table LPZ 2

2

Numerical Applications Inc. Attachment 2 Page 32 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1

  • br model 1

4 0 0.00035 8 0.00018 24 0.00023 720 0.00023

  • of model 0
  • location x/q input to be included 0
  • location name, compartment number and x/q table Control Room 3

0

  • br model 1

2 0 0.00035 720 0.00035

  • of model 1

4 0 1 24 0.6 96 0.4 720 0.4

  • location x/q input to be included 1
  • number of intake combinations 6
  • intake combinations 2 1 3 3 1 4 4 1 3 2 6 5 3 6 6 4 6 5
  • time step count 3

0 1e-06 0.001 0.02 720 0.02

  • show plant, scenario, event, step, model 1

1 1

0 1

RADTRAD-NAI Version 1.1a(QA) run on May 20, 2005 at 07:09:52 Plant Description Number of Nuclides = 107 Inventory Power = 2.7030E+03 MWth Plant Power Level = 2.7030E+03 MWth Number of compartments = 4 Compartment information Compartment number 1 (Source term fraction = 1.0000E+00)

Name: Fuel Pool-Unfiltered Compartment volume = 1.0000E+04 (Cubic feet)

Removal devices within compartment:

Suppression pool Pathways into and out of compartment 1

Numerical Applications Inc. Attachment 2 Page 33 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Pathway to compartment number 2: Fuel Pool Release-Unfiltered Compartment number 2 Name: Environment Pathways into and out of compartment 2 Pathway to compartment number 3: Control Room Unfiltered Makeup Pathway to compartment number 3: Control Room Filtered Makeup Pathway to compartment number 3: Control Room Unfiltered Inleakage Pathway from compartment number 1: Fuel Pool Release-Unfiltered Pathway from compartment number 3: Control Room Exhaust Pathway from compartment number 4: Fuel Pool Release-Filtered Compartment number 3 Name: Control Room Compartment volume = 3.5923E+04 (Cubic feet)

Removal devices within compartment:

Filter(s)

Pathways into and out of compartment 3 Pathway to compartment number 2: Control Room Exhaust Pathway from compartment number 2: Control Room Unfiltered Makeup Pathway from compartment number 2: Control Room Filtered Makeup Pathway from compartment number 2: Control Room Unfiltered Inleakage Compartment number 4 Name: Fuel Pool-Filtered Compartment volume = 1.0000E+04 (Cubic feet)

Removal devices within compartment:

Suppression pool Pathways into and out of compartment 4 Pathway to compartment number 2: Fuel Pool Release-Filtered Total number of pathways = 6 RADTRAD-NAI Version 1.1a(QA) run on May 20, 2005 at 07:09:52 Scenario Description Radioactive Decay is enabled Calculation of Daughters is enabled Iodine fractions Aerosol = 0.0000E+00 Elemental = 9.9850E-01 Organic = 1.5000E-03 Overlying pool characteristics Elemental Removal Data:

Time (hr) DF 0.0000E+00 2.5200E+02 7.2000E+02 2.5200E+02 Organic Removal Data:

Time (hr) DF 0.0000E+00 1.0000E+00 7.2000E+02 1.0000E+00 COMPARTMENT DATA Compartment number 1: Fuel Pool-Unfiltered Compartment number 2: Environment Compartment number 3: Control Room Compartment Filter Data Time (hr) Flow Rate Filter Efficiencies (%)

Numerical Applications Inc. Attachment 2 Page 34 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 (cfm) Aerosol Elemental Organic 0.0000E+00 0.0000E+00 9.9000E+01 9.9000E+01 9.9000E+01 3.3330E-01 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 7.2000E+02 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 Compartment number 4: Fuel Pool-Filtered PATHWAY DATA Pathway number 1: Fuel Pool Release-Unfiltered Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 1.0000E+06 1.0000E+02 0.0000E+00 0.0000E+00 7.2000E+02 1.0000E+06 1.0000E+02 0.0000E+00 0.0000E+00 Pathway number 2: Control Room Unfiltered Makeup Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 6.6000E+02 0.0000E+00 0.0000E+00 0.0000E+00 3.3330E-01 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 3: Control Room Filtered Makeup Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 0.0000E+00 9.9000E+01 9.9000E+01 9.9000E+01 3.3330E-01 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 7.2000E+02 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 Pathway number 4: Control Room Unfiltered Inleakage Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 3.3330E-01 1.0000E+02 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 1.0000E+02 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 5: Control Room Exhaust Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 6.6000E+02 0.0000E+00 0.0000E+00 0.0000E+00 3.3330E-01 1.5136E+03 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 1.5136E+03 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 6: Fuel Pool Release-Filtered Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 1.0000E+06 1.0000E+02 9.4000E+01 9.4000E+01 7.2000E+02 1.0000E+06 1.0000E+02 9.4000E+01 9.4000E+01 X/Q DATA X/Q table 1: EAB Time (hr) X/Q (s

  • m^-3) 0.0000E+00 5.3900E-04 7.2000E+02 5.3900E-04

Numerical Applications Inc. Attachment 2 Page 35 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 X/Q table 2: LPZ Time (hr) X/Q (s

  • m^-3) 0.0000E+00 6.6600E-05 2.0000E+00 3.0300E-05 8.0000E+00 2.0400E-05 2.4000E+01 8.6700E-06 9.6000E+01 2.5400E-06 7.2000E+02 2.5400E-06 X/Q table 3: Equip Hatch-Normal Time (hr) X/Q (s
  • m^-3) 0.0000E+00 1.2500E-02 2.0000E+00 9.8300E-03 8.0000E+00 3.6200E-03 2.4000E+01 2.8600E-03 9.6000E+01 2.2800E-03 7.2000E+02 2.2800E-03 X/Q table 4: Equip Hatch-Emergency Time (hr) X/Q (s
  • m^-3) 0.0000E+00 7.3200E-04 2.0000E+00 6.1300E-04 8.0000E+00 2.4500E-04 2.4000E+01 1.7500E-04 9.6000E+01 1.2900E-04 7.2000E+02 1.2900E-04 X/Q table 5: Stack-Normal Time (hr) X/Q (s
  • m^-3) 0.0000E+00 6.1000E-03 2.0000E+00 4.3200E-03 8.0000E+00 1.7300E-03 2.4000E+01 1.2700E-03 9.6000E+01 9.7900E-04 7.2000E+02 9.7900E-04 X/Q table 6: Stack-Emergency Time (hr) X/Q (s
  • m^-3) 0.0000E+00 8.3200E-04 2.0000E+00 7.6900E-04 8.0000E+00 2.8300E-04 2.4000E+01 2.1500E-04 9.6000E+01 1.5700E-04 7.2000E+02 1.5700E-04 LOCATION DATA Location EAB is in compartment 2 Using X/Q Table 1 Location Breathing Rate Data Time (hr) Breathing Rate (m^3
  • sec^-1) 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 2.3000E-04 Location LPZ is in compartment 2 Using X/Q Table 2 Location Breathing Rate Data Time (hr) Breathing Rate (m^3
  • sec^-1) 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 2.3000E-04 Location Control Room is in compartment 3 Inleakage X/Q Table Assignments

Numerical Applications Inc. Attachment 2 Page 36 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Inleakage Path Source Path X/Q Table 2 1 3 3 1 4 4 1 3 2 6 5 3 6 6 4 6 5 Location Breathing Rate Data Time (hr) Breathing Rate (m^3

  • sec^-1) 0.0000E+00 3.5000E-04 7.2000E+02 3.5000E-04 Location Occupancy Factor Data Time (hr) Occupancy Factor 0.0000E+00 1.0000E+00 2.4000E+01 6.0000E-01 9.6000E+01 4.0000E-01 7.2000E+02 4.0000E-01 USER SPECIFIED TIME STEP DATA - SUPPLEMENTAL TIME STEPS Time Time step 0.0000E+00 1.0000E-06 1.0000E-03 2.0000E-02 7.2000E+02 2.0000E-02 RADTRAD-NAI Version 1.1a(QA) run on May 20, 2005 at 07:09:52 Dose, Detailed Model and Detailed Inventory Output Detailed model information at time (H) = 0.0010 EAB Doses:

Time (h) = 0.0010 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 LPZ Doses:

Time (h) = 0.0010 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Control Room Doses:

Time (h) = 0.0010 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 0.0010 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 2 Page 37 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0010 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Environment Transport Group Inventory:

Present Release Integral Time (h) = 0.0010 Release Rate/s Release Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 2 Page 38 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Transport Group Inventory:

Overlying Time (h) = 0.0010 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0010 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 0.0010 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0010 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 2 Page 39 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 0.0020 EAB Doses:

Time (h) = 0.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 LPZ Doses:

Time (h) = 0.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Control Room Doses:

Time (h) = 0.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 0.0020 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Environment Transport Group Inventory:

Present Release Integral Time (h) = 0.0020 Release Rate/s Release Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 2 Page 40 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Transport Group Inventory:

Overlying Time (h) = 0.0020 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 2 Page 41 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 0.0020 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 0.3333 EAB Doses:

Time (h) = 0.3333 Whole Body Thyroid Skin TEDE Delta dose (rem) 6.0452E-02 9.9401E+00 1.7438E-01 3.6519E-01 Accumulated dose (rem) 6.0452E-02 9.9401E+00 1.7438E-01 3.6519E-01 LPZ Doses:

Time (h) = 0.3333 Whole Body Thyroid Skin TEDE Delta dose (rem) 7.4696E-03 1.2282E+00 2.1547E-02 4.5124E-02 Accumulated dose (rem) 7.4696E-03 1.2282E+00 2.1547E-02 4.5124E-02 Control Room Doses:

Time (h) = 0.3333 Whole Body Thyroid Skin TEDE Delta dose (rem) 6.6813E-03 3.7491E+01 6.5477E-01 1.1559E+00 Accumulated dose (rem) 6.6813E-03 3.7491E+01 6.5477E-01 1.1559E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Numerical Applications Inc. Attachment 2 Page 42 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 8.7666E-02 2.2345E-07 1.5831E+18 3.2437E+09 Kr-85m 4.6458E-04 5.6453E-14 3.9996E+11 1.7189E+07 Kr-88 1.6525E-05 1.3178E-15 9.0184E+09 6.1141E+05 Rb-86 1.8181E-02 2.2344E-10 1.5646E+15 6.7268E+08 I-131 2.3370E-02 1.8850E-10 8.6657E+14 8.6468E+08 I-132 1.5963E-02 1.5465E-12 7.0553E+12 5.9063E+08 I-133 6.7952E-03 5.9986E-12 2.7161E+13 2.5142E+08 I-135 1.9668E-04 5.6005E-14 2.4983E+11 7.2772E+06 Xe-133 5.5757E+00 2.9788E-08 1.3488E+17 2.0630E+11 Xe-135 3.9514E-01 1.5473E-10 6.9024E+14 1.4620E+10 Cs-134 2.0340E+00 1.5721E-06 7.0650E+18 7.5257E+10 Cs-136 5.2801E-01 7.2043E-09 3.1901E+16 1.9536E+10 Cs-137 1.1000E+00 1.2646E-05 5.5590E+19 4.0700E+10 I-130 5.6873E-05 2.9161E-14 1.3508E+11 2.1043E+06 Kr-83m 4.7428E-06 2.2988E-16 1.6679E+09 1.7549E+05 Xe-131m 3.7523E-02 4.4797E-10 2.0594E+15 1.3883E+09 Xe-133m 1.5385E-01 3.4287E-10 1.5525E+15 5.6923E+09 Xe-135m 4.0250E-01 4.4186E-12 1.9711E+13 1.4893E+10 Cs-134m 4.7298E-06 5.8651E-16 2.6358E+09 1.7500E+05 Rb-88 4.4076E-05 3.6718E-16 2.5128E+09 1.6308E+06 Ba-137m 2.2554E-01 4.1938E-13 1.8435E+12 8.3451E+09 Br-82 4.6579E-05 4.3024E-14 3.1597E+11 1.7234E+06 Br-83 1.8251E-09 1.1553E-19 8.3824E+05 6.7530E+01 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 0.3333 Atmosphere Sump Pool Noble gases (atoms) 1.7223E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 6.5393E+14 0.0000E+00 3.2614E+20 Organic I (atoms) 2.4756E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 1.4226E-05 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.3333 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 3.5158E+01 4.3209E-07 3.0257E+18 1.3008E+12 Cs-134 3.9333E+03 3.0400E-03 1.3662E+22 1.4553E+14 Cs-136 1.0211E+03 1.3932E-05 6.1690E+19 3.7780E+13 Cs-137 2.1272E+03 2.4455E-02 1.0750E+23 7.8706E+13 Cs-134m 9.1465E-03 1.1342E-12 5.0972E+12 3.3842E+08 Rb-88 6.0711E-02 5.0576E-13 3.4611E+12 2.2463E+09 Ba-137m 2.0057E+03 3.7294E-09 1.6393E+16 7.4210E+13 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 2.7510E-02 Environment Integral Nuclide Release:

Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 1.7361E+02 4.4250E-04 3.1350E+21 6.4235E+12 Kr-85m 9.2002E-01 1.1179E-10 7.9205E+14 3.4041E+10 Kr-87 1.1332E-08 4.0007E-19 2.7693E+06 4.1930E+02 Kr-88 3.2724E-02 2.6097E-12 1.7859E+13 1.2108E+09 I-131 4.6279E+01 3.7329E-07 1.7160E+18 1.7123E+12 I-132 3.0154E+01 2.9213E-09 1.3328E+16 1.1157E+12 I-133 1.3457E+01 1.1879E-08 5.3787E+16 4.9790E+11 I-135 3.8949E-01 1.1091E-10 4.9474E+14 1.4411E+10

Numerical Applications Inc. Attachment 2 Page 43 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Xe-133 1.0695E+04 5.7139E-05 2.5872E+20 3.9573E+14 Xe-135 6.6148E+02 2.5902E-07 1.1555E+18 2.4475E+13 I-130 1.1263E-01 5.7747E-11 2.6751E+14 4.1672E+09 Kr-83m 2.7898E-03 1.3522E-13 9.8108E+11 1.0322E+08 Xe-131m 6.8306E+01 8.1548E-07 3.7488E+18 2.5273E+12 Xe-133m 2.7986E+02 6.2371E-07 2.8241E+18 1.0355E+13 Xe-135m 1.1204E+01 1.2299E-10 5.4866E+14 4.1454E+11 Rb-88 1.0961E-02 9.1312E-14 6.2488E+11 4.0556E+08 Br-82 9.2241E-02 8.5200E-11 6.2572E+14 3.4129E+09 Br-83 3.6143E-06 2.2879E-16 1.6600E+09 1.3373E+05 Environment Transport Group Inventory:

Present Release Integral Time (h) = 0.3333 Release Rate/s Release Noble gases (atoms) 1.3670E+20 1.8986E+18 3.4015E+21 Elemental I (atoms) 5.2041E+16 7.2280E+14 1.2945E+18 Organic I (atoms) 1.9701E+16 2.7363E+14 4.9005E+17 Aerosols (kg) 3.4477E-16 4.7885E-18 9.1312E-14 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 3.5158E+01 4.3209E-07 3.0257E+18 1.3008E+12 Cs-134 3.9333E+03 3.0400E-03 1.3662E+22 1.4553E+14 Cs-136 1.0211E+03 1.3932E-05 6.1690E+19 3.7780E+13 Cs-137 2.1272E+03 2.4455E-02 1.0750E+23 7.8706E+13 Cs-134m 9.1465E-03 1.1342E-12 5.0972E+12 3.3842E+08 Rb-88 6.0711E-02 5.0576E-13 3.4611E+12 2.2463E+09 Ba-137m 2.0057E+03 3.7294E-09 1.6393E+16 7.4210E+13 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 2.7510E-02 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 2 Page 44 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 5.6817E-01 1.4482E-06 1.0260E+19 2.1022E+10 Kr-85m 3.0110E-03 3.6587E-13 2.5922E+12 1.1141E+08 Kr-88 1.0710E-04 8.5409E-15 5.8448E+10 3.9626E+06 I-131 1.5146E-01 1.2217E-09 5.6161E+15 5.6039E+09 I-132 9.8977E-02 9.5888E-12 4.3746E+13 3.6622E+09 I-133 4.4040E-02 3.8877E-11 1.7603E+14 1.6295E+09 I-135 1.2747E-03 3.6297E-13 1.6191E+12 4.7164E+07 Xe-133 3.5004E+01 1.8700E-07 8.4674E+17 1.2951E+12 Xe-135 2.1651E+00 8.4784E-10 3.7821E+15 8.0110E+10 I-130 3.6860E-04 1.8899E-13 8.7548E+11 1.3638E+07 Kr-83m 9.1462E-06 4.4330E-16 3.2164E+09 3.3841E+05 Xe-131m 2.2356E-01 2.6690E-09 1.2270E+16 8.2718E+09 Xe-133m 9.1598E-01 2.0414E-09 9.2432E+15 3.3891E+10 Xe-135m 3.8219E-02 4.1956E-13 1.8716E+12 1.4141E+09 Rb-88 3.4056E-05 2.8371E-16 1.9415E+09 1.2601E+06 Br-82 3.0188E-04 2.7884E-13 2.0478E+12 1.1170E+07 Br-83 1.1829E-08 7.4876E-19 5.4327E+06 4.3766E+02 Control Room Transport Group Inventory:

Overlying Time (h) = 0.3333 Atmosphere Sump Pool Noble gases (atoms) 1.1132E+19 0.0000E+00 0.0000E+00 Elemental I (atoms) 4.2366E+15 0.0000E+00 0.0000E+00 Organic I (atoms) 1.6038E+15 0.0000E+00 0.0000E+00 Aerosols (kg) 2.8371E-16 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.3333 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 2 Page 45 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 0.3333 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.3333 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 2.0000 EAB Doses:

Time (h) = 2.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.0468E-01 4.9928E+01 8.7324E-01 1.8352E+00 Accumulated dose (rem) 3.6513E-01 5.9868E+01 1.0476E+00 2.2004E+00 LPZ Doses:

Time (h) = 2.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.7647E-02 6.1693E+00 1.0790E-01 2.2676E-01 Accumulated dose (rem) 4.5116E-02 7.3975E+00 1.2945E-01 2.7189E-01 Control Room Doses:

Time (h) = 2.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.0321E-02 7.8949E+01 3.1244E+00 2.4499E+00 Accumulated dose (rem) 3.7002E-02 1.1644E+02 3.7792E+00 3.6058E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 8.7665E-02 2.2345E-07 1.5831E+18 3.2436E+09 Kr-85m 3.5898E-04 4.3621E-14 3.0905E+11 1.3282E+07 Kr-88 1.1002E-05 8.7740E-16 6.0043E+09 4.0707E+05 Rb-86 1.8134E-02 2.2286E-10 1.5606E+15 6.7095E+08 I-131 2.3235E-02 1.8742E-10 8.6157E+14 8.5970E+08 I-132 1.5714E-02 1.5224E-12 6.9454E+12 5.8143E+08 I-133 6.4281E-03 5.6745E-12 2.5694E+13 2.3784E+08 I-135 1.6514E-04 4.7024E-14 2.0977E+11 6.1102E+06 Xe-133 6.8643E+00 3.6672E-08 1.6605E+17 2.5398E+11 Xe-135 7.6366E-01 2.9904E-10 1.3340E+15 2.8255E+10 Cs-134 2.0338E+00 1.5720E-06 7.0646E+18 7.5252E+10 Cs-136 5.2608E-01 7.1779E-09 3.1784E+16 1.9465E+10 Cs-137 1.1000E+00 1.2646E-05 5.5589E+19 4.0700E+10

Numerical Applications Inc. Attachment 2 Page 46 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 I-130 5.1798E-05 2.6558E-14 1.2303E+11 1.9165E+06 Kr-83m 1.9535E-05 9.4682E-16 6.8697E+09 7.2279E+05 Xe-131m 6.1866E-02 7.3860E-10 3.3954E+15 2.2890E+09 Xe-133m 2.4646E-01 5.4927E-10 2.4870E+15 9.1190E+09 Xe-135m 3.0276E+00 3.3237E-11 1.4826E+14 1.1202E+11 Cs-134m 3.1757E-06 3.9379E-16 1.7697E+09 1.1750E+05 Rb-88 2.9447E-05 2.4531E-16 1.6787E+09 1.0895E+06 Ba-137m 3.3916E-01 6.3065E-13 2.7721E+12 1.2549E+10 Br-82 4.5079E-05 4.1638E-14 3.0579E+11 1.6679E+06 Br-83 1.1255E-09 7.1247E-20 5.1694E+05 4.1645E+01 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 2.0000 Atmosphere Sump Pool Noble gases (atoms) 1.7565E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 6.4912E+14 0.0000E+00 1.9493E+21 Organic I (atoms) 2.4573E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 1.4226E-05 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 2.1641E+02 2.6596E-06 1.8624E+19 8.0071E+12 Cs-134 2.4272E+04 1.8760E-02 8.4309E+22 8.9806E+14 Cs-136 6.2782E+03 8.5661E-05 3.7931E+20 2.3229E+14 Cs-137 1.3127E+04 1.5092E-01 6.6340E+23 4.8571E+14 Cs-134m 3.7898E-02 4.6995E-12 2.1120E+13 1.4022E+09 Rb-88 8.2296E-02 6.8558E-13 4.6916E+12 3.0449E+09 Ba-137m 1.4225E+04 2.6450E-08 1.1627E+17 5.2633E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.6977E-01 Environment Integral Nuclide Release:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 1.0506E+03 2.6779E-03 1.8972E+22 3.8873E+13 Kr-85m 4.3021E+00 5.2277E-10 3.7037E+15 1.5918E+11 Kr-88 1.3185E-01 1.0515E-11 7.1958E+13 4.8785E+09 I-131 2.7823E+02 2.2442E-06 1.0317E+19 1.0294E+13 I-132 1.4286E+02 1.3840E-08 6.3140E+16 5.2857E+12 I-133 7.6982E+01 6.7956E-08 3.0770E+17 2.8483E+12 I-135 1.9777E+00 5.6315E-10 2.5121E+15 7.3175E+10 Xe-133 6.4278E+04 3.4340E-04 1.5549E+21 2.3783E+15 Xe-135 3.5727E+03 1.3990E-06 6.2407E+18 1.3219E+14 I-130 6.2032E-01 3.1806E-10 1.4734E+15 2.2952E+10 Kr-83m 1.0427E-02 5.0537E-13 3.6667E+12 3.8579E+08 Xe-131m 4.1398E+02 4.9424E-06 2.2721E+19 1.5317E+13 Xe-133m 1.6659E+03 3.7127E-06 1.6811E+19 6.1639E+13 Xe-135m 5.6577E+01 6.2109E-10 2.7706E+15 2.0933E+12 Rb-88 1.1594E-01 9.6586E-13 6.6097E+12 4.2898E+09 Br-82 5.3986E-01 4.9865E-10 3.6621E+15 1.9975E+10 Br-83 1.3479E-05 8.5325E-16 6.1908E+09 4.9874E+05 Environment Transport Group Inventory:

Present Release Integral Time (h) = 2.0000 Release Rate/s Release Noble gases (atoms) 2.0604E+20 2.8617E+18 2.0573E+22

Numerical Applications Inc. Attachment 2 Page 47 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 7.7834E+16 1.0810E+15 7.7582E+18 Organic I (atoms) 2.9465E+16 4.0924E+14 2.9370E+18 Aerosols (kg) 5.1926E-16 7.2120E-18 9.6586E-13 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 2.1641E+02 2.6596E-06 1.8624E+19 8.0071E+12 Cs-134 2.4272E+04 1.8760E-02 8.4309E+22 8.9806E+14 Cs-136 6.2782E+03 8.5661E-05 3.7931E+20 2.3229E+14 Cs-137 1.3127E+04 1.5092E-01 6.6340E+23 4.8571E+14 Cs-134m 3.7898E-02 4.6995E-12 2.1120E+13 1.4022E+09 Rb-88 8.2296E-02 6.8558E-13 4.6916E+12 3.0449E+09 Ba-137m 1.4225E+04 2.6450E-08 1.1627E+17 5.2633E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.6977E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0000 Ci kg Atoms Bq I-131 1.1232E-01 9.0603E-10 4.1651E+15 4.1560E+09 I-132 6.0106E-02 5.8230E-12 2.6566E+13 2.2239E+09 I-133 3.1078E-02 2.7435E-11 1.2422E+14 1.1499E+09 I-135 7.9842E-04 2.2735E-13 1.0142E+12 2.9542E+07 I-130 2.5043E-04 1.2840E-13 5.9482E+11 9.2659E+06 Br-82 2.1795E-04 2.0131E-13 1.4784E+12 8.0640E+06 Br-83 5.4418E-09 3.4446E-19 2.4993E+06 2.0135E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.1329E+15 Organic I (atoms) 1.1860E+15 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Numerical Applications Inc. Attachment 2 Page 48 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 2.2943E-01 5.8479E-07 4.1432E+18 8.4891E+09 Kr-85m 9.3951E-04 1.1416E-13 8.0883E+11 3.4762E+07 Kr-88 2.8794E-05 2.2963E-15 1.5714E+10 1.0654E+06 I-131 1.7083E-02 1.3779E-10 6.3345E+14 6.3207E+08 I-132 1.0919E-02 1.0578E-12 4.8259E+12 4.0399E+08 I-133 4.7262E-03 4.1721E-12 1.8891E+13 1.7487E+08 I-135 1.2142E-04 3.4574E-14 1.5423E+11 4.4925E+06 Xe-133 1.4055E+01 7.5090E-08 3.4000E+17 5.2005E+11 Xe-135 7.8640E-01 3.0794E-10 1.3737E+15 2.9097E+10 I-130 3.8084E-05 1.9527E-14 9.0456E+10 1.4091E+06 Kr-83m 2.4994E-06 1.2114E-16 8.7896E+08 9.2479E+04 Xe-131m 9.0739E-02 1.0833E-09 4.9800E+15 3.3574E+09 Xe-133m 3.6512E-01 8.1373E-10 3.6845E+15 1.3510E+10 Xe-135m 3.3258E-02 3.6511E-13 1.6287E+12 1.2306E+09 Rb-88 1.0505E-05 8.7513E-17 5.9888E+08 3.8868E+05 Br-82 3.3144E-05 3.0614E-14 2.2483E+11 1.2263E+06 Br-83 8.2755E-10 5.2384E-20 3.8008E+05 3.0619E+01 Control Room Transport Group Inventory:

Overlying Time (h) = 2.0000 Atmosphere Sump Pool Noble gases (atoms) 4.4932E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 4.7704E+14 0.0000E+00 0.0000E+00 Organic I (atoms) 1.8059E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 8.7513E-17 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 2.0000 Ci kg Atoms Bq I-131 1.3056E-01 1.0531E-09 4.8412E+15 4.8307E+09 I-132 5.9175E-02 5.7328E-12 2.6154E+13 2.1895E+09 I-133 3.6126E-02 3.1891E-11 1.4440E+14 1.3367E+09 I-135 9.2811E-04 2.6428E-13 1.1789E+12 3.4340E+07 I-130 2.9111E-04 1.4926E-13 6.9144E+11 1.0771E+07 Rb-88 1.2034E-05 1.0025E-16 6.8608E+08 4.4527E+05 Br-82 2.5335E-04 2.3401E-13 1.7186E+12 9.3739E+06 Br-83 6.3257E-09 4.0042E-19 2.9053E+06 2.3405E+02 Deposition Recirculating Time (h) = 2.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 3.6381E+15 Organic I (atoms) 0.0000E+00 1.3773E+15 Aerosols (kg) 0.0000E+00 1.0025E-16 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0000 Ci kg Atoms Bq I-131 1.1232E-01 9.0603E-10 4.1651E+15 4.1560E+09 I-132 6.0106E-02 5.8230E-12 2.6566E+13 2.2239E+09 I-133 3.1078E-02 2.7435E-11 1.2422E+14 1.1499E+09 I-135 7.9842E-04 2.2735E-13 1.0142E+12 2.9542E+07 I-130 2.5043E-04 1.2840E-13 5.9482E+11 9.2659E+06

Numerical Applications Inc. Attachment 2 Page 49 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Br-82 2.1795E-04 2.0131E-13 1.4784E+12 8.0640E+06 Br-83 5.4418E-09 3.4446E-19 2.4993E+06 2.0135E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.1329E+15 Organic I (atoms) 1.1860E+15 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq I-131 2.4289E-01 1.9592E-09 9.0063E+15 8.9868E+09 I-132 1.1928E-01 1.1556E-11 5.2720E+13 4.4134E+09 I-133 6.7205E-02 5.9326E-11 2.6862E+14 2.4866E+09 I-135 1.7265E-03 4.9163E-13 2.1931E+12 6.3881E+07 I-130 5.4154E-04 2.7766E-13 1.2863E+12 2.0037E+07 Rb-88 1.2034E-05 1.0025E-16 6.8608E+08 4.4527E+05 Br-82 4.7130E-04 4.3532E-13 3.1970E+12 1.7438E+07 Br-83 1.1767E-08 7.4488E-19 5.4045E+06 4.3540E+02 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 2.0000 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 2.0020 EAB Doses:

Time (h) = 2.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 4.8929E-04 5.9663E-02 1.2420E-03 2.3181E-03

Numerical Applications Inc. Attachment 2 Page 50 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Accumulated dose (rem) 3.6562E-01 5.9928E+01 1.0489E+00 2.2027E+00 LPZ Doses:

Time (h) = 2.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.7506E-05 3.3540E-03 6.9819E-05 1.3031E-04 Accumulated dose (rem) 4.5144E-02 7.4008E+00 1.2952E-01 2.7202E-01 Control Room Doses:

Time (h) = 2.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.6486E-05 4.7969E-02 2.7549E-03 1.4965E-03 Accumulated dose (rem) 3.7029E-02 1.1649E+02 3.7819E+00 3.6073E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 8.7665E-02 2.2345E-07 1.5831E+18 3.2436E+09 Kr-85m 3.5887E-04 4.3607E-14 3.0895E+11 1.3278E+07 Kr-88 1.0996E-05 8.7697E-16 6.0014E+09 4.0687E+05 Rb-86 1.8134E-02 2.2286E-10 1.5606E+15 6.7095E+08 I-131 2.3235E-02 1.8742E-10 8.6157E+14 8.5970E+08 I-132 1.5797E-02 1.5304E-12 6.9820E+12 5.8449E+08 I-133 6.4277E-03 5.6741E-12 2.5692E+13 2.3782E+08 I-135 1.6511E-04 4.7014E-14 2.0972E+11 6.1089E+06 Xe-133 5.5137E+00 2.9456E-08 1.3338E+17 2.0401E+11 Xe-135 3.4466E-01 1.3496E-10 6.0204E+14 1.2752E+10 Cs-134 2.0338E+00 1.5720E-06 7.0646E+18 7.5252E+10 Cs-136 5.2607E-01 7.1779E-09 3.1784E+16 1.9465E+10 Cs-137 1.1000E+00 1.2646E-05 5.5589E+19 4.0700E+10 I-130 5.1792E-05 2.6555E-14 1.2302E+11 1.9163E+06 Kr-83m 2.7334E-06 1.3249E-16 9.6126E+08 1.0114E+05 Xe-131m 3.7281E-02 4.4508E-10 2.0461E+15 1.3794E+09 Xe-133m 1.4977E-01 3.3377E-10 1.5113E+15 5.5413E+09 Xe-135m 3.0721E-01 3.3725E-12 1.5044E+13 1.1367E+10 Cs-134m 3.1741E-06 3.9360E-16 1.7689E+09 1.1744E+05 Rb-88 3.0079E-05 2.5058E-16 1.7148E+09 1.1129E+06 Ba-137m 3.3918E-02 6.3068E-14 2.7723E+11 1.2550E+09 Br-82 4.5077E-05 4.1637E-14 3.0578E+11 1.6679E+06 Br-83 1.1249E-09 7.1206E-20 5.1664E+05 4.1621E+01 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 2.0020 Atmosphere Sump Pool Noble gases (atoms) 1.7206E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 6.4914E+14 0.0000E+00 1.9512E+21 Organic I (atoms) 2.4574E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 1.4226E-05 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 2.1663E+02 2.6623E-06 1.8643E+19 8.0151E+12 Cs-134 2.4296E+04 1.8779E-02 8.4394E+22 8.9896E+14 Cs-136 6.2845E+03 8.5747E-05 3.7969E+20 2.3253E+14 Cs-137 1.3141E+04 1.5107E-01 6.6407E+23 4.8620E+14 Cs-134m 3.7918E-02 4.7020E-12 2.1131E+13 1.4030E+09 Rb-88 8.2268E-02 6.8535E-13 4.6901E+12 3.0439E+09 Ba-137m 1.4176E+04 2.6359E-08 1.1587E+17 5.2451E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 2 Page 51 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.6994E-01 Environment Integral Nuclide Release:

Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 1.0517E+03 2.6805E-03 1.8991E+22 3.8912E+13 Kr-85m 4.3051E+00 5.2313E-10 3.7063E+15 1.5929E+11 Kr-88 1.3192E-01 1.0520E-11 7.1995E+13 4.8810E+09 I-131 2.7850E+02 2.2464E-06 1.0327E+19 1.0305E+13 I-132 1.4296E+02 1.3850E-08 6.3186E+16 5.2895E+12 I-133 7.7054E+01 6.8020E-08 3.0799E+17 2.8510E+12 I-135 1.9793E+00 5.6360E-10 2.5141E+15 7.3233E+10 Xe-133 6.4343E+04 3.4375E-04 1.5565E+21 2.3807E+15 Xe-135 3.5762E+03 1.4004E-06 6.2469E+18 1.3232E+14 I-130 6.2087E-01 3.1834E-10 1.4747E+15 2.2972E+10 Kr-83m 1.0448E-02 5.0639E-13 3.6742E+12 3.8657E+08 Xe-131m 4.1442E+02 4.9477E-06 2.2745E+19 1.5334E+13 Xe-133m 1.6677E+03 3.7166E-06 1.6828E+19 6.1703E+13 Xe-135m 5.9335E+01 6.5137E-10 2.9056E+15 2.1954E+12 Rb-88 1.1602E-01 9.6649E-13 6.6140E+12 4.2926E+09 Br-82 5.4038E-01 4.9913E-10 3.6657E+15 1.9994E+10 Br-83 1.3485E-05 8.5360E-16 6.1934E+09 4.9895E+05 Environment Transport Group Inventory:

Present Release Integral Time (h) = 2.0020 Release Rate/s Release Noble gases (atoms) 2.0644E+19 2.8673E+17 2.0594E+22 Elemental I (atoms) 7.7852E+15 1.0813E+14 7.7659E+18 Organic I (atoms) 2.9472E+15 4.0934E+13 2.9399E+18 Aerosols (kg) 5.5776E-18 7.7467E-20 9.6649E-13 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 2.1663E+02 2.6623E-06 1.8643E+19 8.0151E+12 Cs-134 2.4296E+04 1.8779E-02 8.4394E+22 8.9896E+14 Cs-136 6.2845E+03 8.5747E-05 3.7969E+20 2.3253E+14 Cs-137 1.3141E+04 1.5107E-01 6.6407E+23 4.8620E+14 Cs-134m 3.7918E-02 4.7020E-12 2.1131E+13 1.4030E+09 Rb-88 8.2268E-02 6.8535E-13 4.6901E+12 3.0439E+09 Ba-137m 1.4176E+04 2.6359E-08 1.1587E+17 5.2451E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.6994E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0020 Ci kg Atoms Bq I-131 1.1244E-01 9.0693E-10 4.1692E+15 4.1602E+09 I-132 6.0147E-02 5.8269E-12 2.6584E+13 2.2254E+09 I-133 3.1107E-02 2.7460E-11 1.2434E+14 1.1510E+09 I-135 7.9905E-04 2.2753E-13 1.0150E+12 2.9565E+07 I-130 2.5065E-04 1.2852E-13 5.9535E+11 9.2742E+06 Br-82 2.1816E-04 2.0151E-13 1.4799E+12 8.0718E+06 Br-83 5.4441E-09 3.4461E-19 2.5003E+06 2.0143E+02

Numerical Applications Inc. Attachment 2 Page 52 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.1360E+15 Organic I (atoms) 1.1872E+15 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 2.2919E-01 5.8418E-07 4.1388E+18 8.4802E+09 Kr-85m 9.3823E-04 1.1401E-13 8.0773E+11 3.4714E+07 Kr-88 2.8749E-05 2.2928E-15 1.5690E+10 1.0637E+06 I-131 1.7047E-02 1.3751E-10 6.3212E+14 6.3075E+08 I-132 1.0895E-02 1.0555E-12 4.8153E+12 4.0310E+08 I-133 4.7160E-03 4.1631E-12 1.8850E+13 1.7449E+08 I-135 1.2114E-04 3.4495E-14 1.5388E+11 4.4822E+06 Xe-133 1.4042E+01 7.5017E-08 3.3967E+17 5.1955E+11 Xe-135 7.8584E-01 3.0772E-10 1.3727E+15 2.9076E+10 I-130 3.8000E-05 1.9484E-14 9.0258E+10 1.4060E+06 Kr-83m 2.5102E-06 1.2167E-16 8.8277E+08 9.2879E+04 Xe-131m 9.0666E-02 1.0824E-09 4.9760E+15 3.3546E+09 Xe-133m 3.6482E-01 8.1305E-10 3.6814E+15 1.3498E+10 Xe-135m 3.5576E-02 3.9055E-13 1.7422E+12 1.3163E+09 Rb-88 1.0489E-05 8.7381E-17 5.9798E+08 3.8810E+05 Br-82 3.3074E-05 3.0549E-14 2.2436E+11 1.2237E+06 Br-83 8.2535E-10 5.2244E-20 3.7906E+05 3.0538E+01 Control Room Transport Group Inventory:

Overlying Time (h) = 2.0020 Atmosphere Sump Pool Noble gases (atoms) 4.4885E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 4.7604E+14 0.0000E+00 0.0000E+00 Organic I (atoms) 1.8021E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 8.7381E-17 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 2.0020 Ci kg Atoms Bq I-131 1.3064E-01 1.0538E-09 4.8442E+15 4.8337E+09 I-132 5.9190E-02 5.7343E-12 2.6161E+13 2.1900E+09 I-133 3.6146E-02 3.1908E-11 1.4448E+14 1.3374E+09

Numerical Applications Inc. Attachment 2 Page 53 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 I-135 9.2848E-04 2.6438E-13 1.1794E+12 3.4354E+07 I-130 2.9125E-04 1.4933E-13 6.9178E+11 1.0776E+07 Rb-88 1.2027E-05 1.0019E-16 6.8565E+08 4.4500E+05 Br-82 2.5349E-04 2.3414E-13 1.7196E+12 9.3793E+06 Br-83 6.3259E-09 4.0043E-19 2.9053E+06 2.3406E+02 Deposition Recirculating Time (h) = 2.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 3.6403E+15 Organic I (atoms) 0.0000E+00 1.3781E+15 Aerosols (kg) 0.0000E+00 1.0019E-16 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0020 Ci kg Atoms Bq I-131 1.1244E-01 9.0693E-10 4.1692E+15 4.1602E+09 I-132 6.0147E-02 5.8269E-12 2.6584E+13 2.2254E+09 I-133 3.1107E-02 2.7460E-11 1.2434E+14 1.1510E+09 I-135 7.9905E-04 2.2753E-13 1.0150E+12 2.9565E+07 I-130 2.5065E-04 1.2852E-13 5.9535E+11 9.2742E+06 Br-82 2.1816E-04 2.0151E-13 1.4799E+12 8.0718E+06 Br-83 5.4441E-09 3.4461E-19 2.5003E+06 2.0143E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.1360E+15 Organic I (atoms) 1.1872E+15 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq I-131 2.4308E-01 1.9607E-09 9.0134E+15 8.9938E+09 I-132 1.1934E-01 1.1561E-11 5.2745E+13 4.4155E+09 I-133 6.7254E-02 5.9369E-11 2.6882E+14 2.4884E+09 I-135 1.7275E-03 4.9191E-13 2.1944E+12 6.3919E+07 I-130 5.4191E-04 2.7785E-13 1.2871E+12 2.0051E+07 Rb-88 1.2027E-05 1.0019E-16 6.8565E+08 4.4500E+05 Br-82 4.7165E-04 4.3565E-13 3.1994E+12 1.7451E+07 Br-83 1.1770E-08 7.4504E-19 5.4057E+06 4.3549E+02 Fuel Pool-Filtered Transport Group Inventory:

Numerical Applications Inc. Attachment 2 Page 54 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Overlying Time (h) = 2.0020 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 8.0000 EAB Doses:

Time (h) = 8.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.4638E-02 5.4379E-01 6.0799E-02 5.1306E-02 Accumulated dose (rem) 4.0026E-01 6.0472E+01 1.1097E+00 2.2540E+00 LPZ Doses:

Time (h) = 8.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 1.9472E-03 3.0569E-02 3.4178E-03 2.8842E-03 Accumulated dose (rem) 4.7091E-02 7.4314E+00 1.3293E-01 2.7490E-01 Control Room Doses:

Time (h) = 8.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 6.2923E-03 5.2643E+00 6.1707E-01 1.6759E-01 Accumulated dose (rem) 4.3321E-02 1.2175E+02 4.3990E+00 3.7749E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq Xe-133 1.2412E+00 6.6308E-09 3.0024E+16 4.5923E+10 Xe-135 2.5063E-01 9.8145E-11 4.3781E+14 9.2735E+09 Kr-83m 3.3084E-06 1.6035E-16 1.1635E+09 1.2241E+05 Xe-131m 2.7008E-02 3.2244E-10 1.4823E+15 9.9928E+08 Xe-133m 8.8860E-02 1.9804E-10 8.9669E+14 3.2878E+09 Xe-135m 1.6274E+00 1.7866E-11 7.9696E+13 6.0215E+10 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 8.0000 Atmosphere Sump Pool Noble gases (atoms) 3.2920E+16 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.9080E+21 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 8.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 8.0000 Ci kg Atoms Bq

Numerical Applications Inc. Attachment 2 Page 55 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Rb-86 2.1764E+02 2.6748E-06 1.8730E+19 8.0528E+12 Cs-134 2.4632E+04 1.9038E-02 8.5561E+22 9.1140E+14 Cs-136 6.2891E+03 8.5810E-05 3.7997E+20 2.3270E+14 Cs-137 1.3325E+04 1.5319E-01 6.7340E+23 4.9303E+14 Cs-134m 9.1685E-03 1.1369E-12 5.1095E+12 3.3924E+08 Rb-88 7.1629E-08 5.9672E-19 4.0835E+06 2.6503E+03 Ba-137m 1.4771E+04 2.7466E-08 1.2073E+17 5.4654E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.7232E-01 Environment Integral Nuclide Release:

Time (h) = 8.0000 Ci kg Atoms Bq Kr-85 1.0614E+03 2.7054E-03 1.9167E+22 3.9272E+13 Xe-133 6.3291E+04 3.3812E-04 1.5310E+21 2.3418E+15 Xe-135 2.3824E+03 9.3292E-07 4.1616E+18 8.8149E+13 Kr-83m 1.8585E-03 9.0080E-14 6.5359E+11 6.8766E+07 Xe-131m 4.2038E+02 5.0188E-06 2.3072E+19 1.5554E+13 Xe-133m 1.5834E+03 3.5289E-06 1.5979E+19 5.8587E+13 Xe-135m 3.0471E+01 3.3451E-10 1.4922E+15 1.1274E+12 Environment Transport Group Inventory:

Present Release Integral Time (h) = 8.0000 Release Rate/s Release Noble gases (atoms) 3.2938E+16 4.5748E+14 2.0741E+22 Elemental I (atoms) 5.5581E+00 7.7196E-02 7.5947E+18 Organic I (atoms) 2.1041E+00 2.9224E-02 2.8751E+18 Aerosols (kg) 4.3715E-25 6.0716E-27 2.9327E-13 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 8.0000 Ci kg Atoms Bq Rb-86 2.1764E+02 2.6748E-06 1.8730E+19 8.0528E+12 Cs-134 2.4632E+04 1.9038E-02 8.5561E+22 9.1140E+14 Cs-136 6.2891E+03 8.5810E-05 3.7997E+20 2.3270E+14 Cs-137 1.3325E+04 1.5319E-01 6.7340E+23 4.9303E+14 Cs-134m 9.1685E-03 1.1369E-12 5.1095E+12 3.3924E+08 Rb-88 7.1629E-08 5.9672E-19 4.0835E+06 2.6503E+03 Ba-137m 1.4771E+04 2.7466E-08 1.2073E+17 5.4654E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.7232E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 8.0000 Ci kg Atoms Bq I-131 1.1159E-01 9.0008E-10 4.1377E+15 4.1287E+09 I-132 1.0043E-02 9.7297E-13 4.4389E+12 3.7160E+08 I-133 2.5830E-02 2.2801E-11 1.0324E+14 9.5570E+08 I-135 4.3199E-04 1.2301E-13 5.4873E+11 1.5984E+07

Numerical Applications Inc. Attachment 2 Page 56 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 I-130 1.8157E-04 9.3099E-14 4.3127E+11 6.7182E+06 Br-82 1.9664E-04 1.8163E-13 1.3339E+12 7.2759E+06 Br-83 9.6942E-10 6.1365E-20 4.4524E+05 3.5869E+01 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.0812E+15 Organic I (atoms) 1.1665E+15 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq Kr-85 6.1757E-08 1.5741E-13 1.1152E+12 2.2850E+03 Xe-133 2.1270E-02 1.1363E-10 5.1453E+14 7.8700E+08 Xe-135 4.7194E-03 1.8480E-12 8.2438E+12 1.7462E+08 Kr-83m 5.4092E-08 2.6217E-18 1.9022E+07 2.0014E+03 Xe-131m 4.5771E-04 5.4645E-12 2.5120E+13 1.6935E+07 Xe-133m 1.5176E-03 3.3822E-12 1.5314E+13 5.6152E+07 Xe-135m 1.3200E-02 1.4491E-13 6.4640E+11 4.8839E+08 Control Room Transport Group Inventory:

Overlying Time (h) = 8.0000 Atmosphere Sump Pool Noble gases (atoms) 5.6497E+14 0.0000E+00 0.0000E+00 Elemental I (atoms) 1.0467E+02 0.0000E+00 0.0000E+00 Organic I (atoms) 3.9623E+01 0.0000E+00 0.0000E+00 Aerosols (kg) 8.2485E-24 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 8.0000 Ci kg Atoms Bq I-131 1.3643E-01 1.1005E-09 5.0590E+15 5.0480E+09 I-132 1.0633E-02 1.0301E-12 4.6995E+12 3.9341E+08 I-133 3.1583E-02 2.7880E-11 1.2624E+14 1.1686E+09 I-135 5.2822E-04 1.5041E-13 6.7095E+11 1.9544E+07 I-130 2.2202E-04 1.1384E-13 5.2733E+11 8.2147E+06 Br-82 2.4045E-04 2.2209E-13 1.6311E+12 8.8965E+06 Br-83 1.1854E-09 7.5033E-20 5.4441E+05 4.3858E+01 Deposition Recirculating Time (h) = 8.0000 Surfaces Filter

Numerical Applications Inc. Attachment 2 Page 57 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 3.7668E+15 Organic I (atoms) 0.0000E+00 1.4260E+15 Aerosols (kg) 0.0000E+00 5.9838E-22 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 8.0000 Ci kg Atoms Bq I-131 1.1159E-01 9.0008E-10 4.1377E+15 4.1287E+09 I-132 1.0043E-02 9.7297E-13 4.4389E+12 3.7160E+08 I-133 2.5830E-02 2.2801E-11 1.0324E+14 9.5570E+08 I-135 4.3199E-04 1.2301E-13 5.4873E+11 1.5984E+07 I-130 1.8157E-04 9.3099E-14 4.3127E+11 6.7182E+06 Br-82 1.9664E-04 1.8163E-13 1.3339E+12 7.2759E+06 Br-83 9.6942E-10 6.1365E-20 4.4524E+05 3.5869E+01 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.0812E+15 Organic I (atoms) 1.1665E+15 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq I-131 2.4802E-01 2.0006E-09 9.1967E+15 9.1767E+09 I-132 2.0676E-02 2.0031E-12 9.1384E+12 7.6501E+08 I-133 5.7413E-02 5.0682E-11 2.2948E+14 2.1243E+09 I-135 9.6021E-04 2.7342E-13 1.2197E+12 3.5528E+07 I-130 4.0359E-04 2.0693E-13 9.5861E+11 1.4933E+07 Br-82 4.3709E-04 4.0373E-13 2.9650E+12 1.6172E+07 Br-83 2.1548E-09 1.3640E-19 9.8964E+05 7.9727E+01 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 8.0000 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating

Numerical Applications Inc. Attachment 2 Page 58 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 8.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 24.0000 EAB Doses:

Time (h) = 24.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.0567E-02 2.1476E-16 5.2440E-02 3.0567E-02 Accumulated dose (rem) 4.3082E-01 6.0472E+01 1.1621E+00 2.2846E+00 LPZ Doses:

Time (h) = 24.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 1.1569E-03 8.1283E-18 1.9847E-03 1.1569E-03 Accumulated dose (rem) 4.8248E-02 7.4314E+00 1.3492E-01 2.7606E-01 Control Room Doses:

Time (h) = 24.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 4.7285E-04 1.0854E-12 3.0866E-02 4.7285E-04 Accumulated dose (rem) 4.3794E-02 1.2175E+02 4.4299E+00 3.7754E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 7.2823E-01 3.8905E-09 1.7616E+16 2.6944E+10 Xe-135 4.6814E-02 1.8332E-11 8.1775E+13 1.7321E+09 Kr-83m 3.1942E-08 1.5482E-18 1.1233E+07 1.1818E+03 Xe-131m 2.5499E-02 3.0443E-10 1.3995E+15 9.4347E+08 Xe-133m 5.2137E-02 1.1619E-10 5.2611E+14 1.9291E+09 Xe-135m 3.0397E-01 3.3370E-12 1.4886E+13 1.1247E+10 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 24.0000 Atmosphere Sump Pool Noble gases (atoms) 1.9638E+16 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.7826E+21 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 24.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 2.1232E+02 2.6094E-06 1.8272E+19 7.8558E+12 Cs-134 2.4617E+04 1.9027E-02 8.5508E+22 9.1084E+14 Cs-136 6.0712E+03 8.2836E-05 3.6680E+20 2.2463E+14 Cs-137 1.3325E+04 1.5319E-01 6.7337E+23 4.9301E+14 Cs-134m 2.0019E-04 2.4824E-14 1.1156E+11 7.4071E+06 Ba-137m 1.4771E+04 2.7465E-08 1.2073E+17 5.4651E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Numerical Applications Inc. Attachment 2 Page 59 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.7230E-01 Environment Integral Nuclide Release:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 5.8814E+04 3.1421E-04 1.4227E+21 2.1761E+15 Xe-135 7.6014E+02 2.9766E-07 1.3278E+18 2.8125E+13 Kr-83m 1.8046E-05 8.7465E-16 6.3461E+09 6.6770E+05 Xe-131m 4.2507E+02 5.0748E-06 2.3329E+19 1.5728E+13 Xe-133m 1.3315E+03 2.9674E-06 1.3436E+19 4.9264E+13 Xe-135m 5.6929E+00 6.2496E-11 2.7879E+14 2.1064E+11 Environment Transport Group Inventory:

Present Release Integral Time (h) = 24.0000 Release Rate/s Release Noble gases (atoms) 1.9648E+16 2.7289E+14 2.0626E+22 Elemental I (atoms) 8.0586E-34 1.1193E-35 7.0957E+18 Organic I (atoms) 3.0507E-34 4.2371E-36 2.6862E+18 Aerosols (kg) 2.3822E-44 3.3086E-46 5.9065E-15 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 2.1232E+02 2.6094E-06 1.8272E+19 7.8558E+12 Cs-134 2.4617E+04 1.9027E-02 8.5508E+22 9.1084E+14 Cs-136 6.0712E+03 8.2836E-05 3.6680E+20 2.2463E+14 Cs-137 1.3325E+04 1.5319E-01 6.7337E+23 4.9301E+14 Cs-134m 2.0019E-04 2.4824E-14 1.1156E+11 7.4071E+06 Ba-137m 1.4771E+04 2.7465E-08 1.2073E+17 5.4651E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.7230E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 24.0000 Ci kg Atoms Bq I-131 1.0535E-01 8.4981E-10 3.9066E+15 3.8981E+09 I-132 8.0863E-05 7.8339E-15 3.5740E+10 2.9919E+06 I-133 1.5155E-02 1.3378E-11 6.0576E+13 5.6074E+08 I-135 8.0689E-05 2.2976E-14 1.0249E+11 2.9855E+06 I-130 7.4024E-05 3.7954E-14 1.7582E+11 2.7389E+06 Br-82 1.4363E-04 1.3266E-13 9.7430E+11 5.3142E+06 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.8787E+15 Organic I (atoms) 1.0898E+15 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 2 Page 60 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 4.8243E-03 2.5773E-11 1.1670E+14 1.7850E+08 Xe-135 3.4079E-04 1.3345E-13 5.9529E+11 1.2609E+07 Xe-131m 1.6707E-04 1.9946E-12 9.1694E+12 6.1817E+06 Xe-133m 3.4425E-04 7.6721E-13 3.4739E+12 1.2737E+07 Xe-135m 9.5372E-04 1.0470E-14 4.6704E+10 3.5287E+07 Control Room Transport Group Inventory:

Overlying Time (h) = 24.0000 Atmosphere Sump Pool Noble gases (atoms) 1.2998E+14 0.0000E+00 0.0000E+00 Elemental I (atoms) 1.5175E-32 0.0000E+00 0.0000E+00 Organic I (atoms) 5.7449E-33 0.0000E+00 0.0000E+00 Aerosols (kg) 4.4982E-43 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 24.0000 Ci kg Atoms Bq I-131 1.2881E-01 1.0390E-09 4.7764E+15 4.7661E+09 I-132 8.5610E-05 8.2938E-15 3.7838E+10 3.1676E+06 I-133 1.8531E-02 1.6358E-11 7.4069E+13 6.8564E+08 I-135 9.8661E-05 2.8094E-14 1.2532E+11 3.6505E+06 I-130 9.0512E-05 4.6408E-14 2.1498E+11 3.3489E+06 Br-82 1.7562E-04 1.6221E-13 1.1913E+12 6.4979E+06 Deposition Recirculating Time (h) = 24.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 3.5197E+15 Organic I (atoms) 0.0000E+00 1.3324E+15 Aerosols (kg) 0.0000E+00 3.7269E-38 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup

Numerical Applications Inc. Attachment 2 Page 61 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 24.0000 Ci kg Atoms Bq I-131 1.0535E-01 8.4981E-10 3.9066E+15 3.8981E+09 I-132 8.0863E-05 7.8339E-15 3.5740E+10 2.9919E+06 I-133 1.5155E-02 1.3378E-11 6.0576E+13 5.6074E+08 I-135 8.0689E-05 2.2976E-14 1.0249E+11 2.9855E+06 I-130 7.4024E-05 3.7954E-14 1.7582E+11 2.7389E+06 Br-82 1.4363E-04 1.3266E-13 9.7430E+11 5.3142E+06 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.8787E+15 Organic I (atoms) 1.0898E+15 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq I-131 2.3417E-01 1.8888E-09 8.6830E+15 8.6642E+09 I-132 1.6647E-04 1.6128E-14 7.3578E+10 6.1595E+06 I-133 3.3686E-02 2.9736E-11 1.3464E+14 1.2464E+09 I-135 1.7935E-04 5.1070E-14 2.2781E+11 6.6360E+06 I-130 1.6454E-04 8.4363E-14 3.9080E+11 6.0878E+06 Br-82 3.1925E-04 2.9488E-13 2.1656E+12 1.1812E+07 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 24.0000 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 24.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 96.0000 EAB Doses:

Numerical Applications Inc. Attachment 2 Page 62 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 96.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 9.7779E-03 3.0348E-38 2.2081E-02 9.7779E-03 Accumulated dose (rem) 4.4060E-01 6.0472E+01 1.1842E+00 2.2944E+00 LPZ Doses:

Time (h) = 96.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 1.5728E-04 4.8816E-40 3.5518E-04 1.5728E-04 Accumulated dose (rem) 4.8405E-02 7.4314E+00 1.3527E-01 2.7621E-01 Control Room Doses:

Time (h) = 96.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 7.9745E-05 7.2023E-35 7.0624E-03 7.9745E-05 Accumulated dose (rem) 4.3874E-02 1.2175E+02 4.4369E+00 3.7755E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 6.6106E-02 3.5316E-10 1.5991E+15 2.4459E+09 Xe-135 2.4625E-05 9.6429E-15 4.3015E+10 9.1113E+05 Xe-131m 1.9688E-02 2.3505E-10 1.0805E+15 7.2845E+08 Xe-133m 4.7328E-03 1.0548E-11 4.7759E+13 1.7511E+08 Xe-135m 1.5990E-04 1.7553E-15 7.8302E+09 5.9162E+06 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 96.0000 Atmosphere Sump Pool Noble gases (atoms) 2.7274E+15 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.3575E+21 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 96.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 1.8993E+02 2.3342E-06 1.6345E+19 7.0274E+12 Cs-134 2.4549E+04 1.8974E-02 8.5272E+22 9.0833E+14 Cs-136 5.1800E+03 7.0678E-05 3.1296E+20 1.9166E+14 Cs-137 1.3322E+04 1.5316E-01 6.7324E+23 4.9292E+14 Ba-137m 1.4768E+04 2.7460E-08 1.2070E+17 5.4641E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.7221E-01 Environment Integral Nuclide Release:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 4.0614E+04 2.1698E-04 9.8246E+20 1.5027E+15 Xe-135 3.4893E+00 1.3663E-09 6.0951E+15 1.2910E+11 Xe-131m 4.3126E+02 5.1487E-06 2.3669E+19 1.5957E+13 Xe-133m 5.5327E+02 1.2330E-06 5.5831E+18 2.0471E+13 Xe-135m 2.9947E-03 3.2876E-14 1.4665E+11 1.1081E+08 Environment Transport Group Inventory:

Present Release Integral Time (h) = 96.0000 Release Rate/s Release

Numerical Applications Inc. Attachment 2 Page 63 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Noble gases (atoms) 2.7284E+15 3.7894E+13 2.0166E+22 Elemental I (atoms) 0.0000E+00 0.0000E+00 5.4035E+18 Organic I (atoms) 0.0000E+00 0.0000E+00 2.0456E+18 Aerosols (kg) 0.0000E+00 0.0000E+00 1.3791E-22 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 1.8993E+02 2.3342E-06 1.6345E+19 7.0274E+12 Cs-134 2.4549E+04 1.8974E-02 8.5272E+22 9.0833E+14 Cs-136 5.1800E+03 7.0678E-05 3.1296E+20 1.9166E+14 Cs-137 1.3322E+04 1.5316E-01 6.7324E+23 4.9292E+14 Ba-137m 1.4768E+04 2.7460E-08 1.2070E+17 5.4641E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.7221E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 96.0000 Ci kg Atoms Bq I-131 8.1344E-02 6.5614E-10 3.0163E+15 3.0097E+09 I-133 1.3757E-03 1.2144E-12 5.4989E+12 5.0902E+07 I-135 4.2444E-08 1.2086E-17 5.3914E+07 1.5704E+03 I-130 1.3056E-06 6.6940E-16 3.1010E+09 4.8306E+04 Br-82 3.4933E-05 3.2267E-14 2.3697E+11 1.2925E+06 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.1922E+15 Organic I (atoms) 8.2988E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 2 Page 64 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 3.3142E-04 1.7706E-12 8.0171E+12 1.2263E+07 Xe-135 1.3566E-07 5.3123E-17 2.3697E+08 5.0195E+03 Xe-131m 9.7624E-05 1.1655E-12 5.3579E+12 3.6121E+06 Xe-133m 2.3650E-05 5.2706E-14 2.3865E+11 8.7504E+05 Xe-135m 3.7977E-07 4.1690E-18 1.8597E+07 1.4051E+04 Control Room Transport Group Inventory:

Overlying Time (h) = 96.0000 Atmosphere Sump Pool Noble gases (atoms) 1.3614E+13 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 96.0000 Ci kg Atoms Bq I-131 9.9457E-02 8.0223E-10 3.6879E+15 3.6799E+09 I-133 1.6822E-03 1.4849E-12 6.7237E+12 6.2240E+07 I-135 5.1898E-08 1.4778E-17 6.5922E+07 1.9202E+03 I-130 1.5964E-06 8.1851E-16 3.7917E+09 5.9066E+04 Br-82 4.2714E-05 3.9454E-14 2.8975E+11 1.5804E+06 Deposition Recirculating Time (h) = 96.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 2.6803E+15 Organic I (atoms) 0.0000E+00 1.0147E+15 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 96.0000 Ci kg Atoms Bq I-131 8.1344E-02 6.5614E-10 3.0163E+15 3.0097E+09 I-133 1.3757E-03 1.2144E-12 5.4989E+12 5.0902E+07 I-135 4.2444E-08 1.2086E-17 5.3914E+07 1.5704E+03 I-130 1.3056E-06 6.6940E-16 3.1010E+09 4.8306E+04 Br-82 3.4933E-05 3.2267E-14 2.3697E+11 1.2925E+06 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.1922E+15 Organic I (atoms) 8.2988E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 2 Page 65 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq I-131 1.8080E-01 1.4584E-09 6.7042E+15 6.6896E+09 I-133 3.0579E-03 2.6994E-12 1.2223E+13 1.1314E+08 I-135 9.4342E-08 2.6864E-17 1.1984E+08 3.4907E+03 I-130 2.9019E-06 1.4879E-15 6.8926E+09 1.0737E+05 Br-82 7.7648E-05 7.1721E-14 5.2672E+11 2.8730E+06 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 96.0000 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 96.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 720.0000 EAB Doses:

Time (h) = 720.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 5.2148E-04 6.3027-125 3.4903E-03 5.2148E-04 Accumulated dose (rem) 4.4112E-01 6.0472E+01 1.1877E+00 2.2949E+00 LPZ Doses:

Time (h) = 720.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.4574E-06 2.9701-127 1.6448E-05 2.4574E-06 Accumulated dose (rem) 4.8407E-02 7.4314E+00 1.3529E-01 2.7622E-01 Control Room Doses:

Time (h) = 720.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.1231E-06 9.9719-122 7.0622E-04 3.1231E-06 Accumulated dose (rem) 4.3877E-02 1.2175E+02 4.4376E+00 3.7755E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-133 6.1566E-11 3.2891E-19 1.4893E+06 2.2779E+00 Xe-131m 2.0928E-03 2.4985E-11 1.1486E+14 7.7432E+07 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying

Numerical Applications Inc. Attachment 2 Page 66 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 720.0000 Atmosphere Sump Pool Noble gases (atoms) 1.1486E+14 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.4402E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 720.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 720.0000 Ci kg Atoms Bq Rb-86 7.2302E+01 8.8858E-07 6.2223E+18 2.6752E+12 Cs-134 2.3969E+04 1.8526E-02 8.3256E+22 8.8685E+14 Cs-136 1.3088E+03 1.7857E-05 7.9073E+19 4.8425E+13 Cs-137 1.3300E+04 1.5291E-01 6.7214E+23 4.9211E+14 Ba-137m 1.4744E+04 2.7414E-08 1.2051E+17 5.4551E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.7145E-01 Environment Integral Nuclide Release:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-133 1.3242E+03 7.0744E-06 3.2032E+19 4.8995E+13 Xe-131m 1.9138E+02 2.2848E-06 1.0503E+19 7.0811E+12 Environment Transport Group Inventory:

Present Release Integral Time (h) = 720.0000 Release Rate/s Release Noble gases (atoms) 1.1486E+14 1.5953E+12 1.9109E+22 Elemental I (atoms) 0.0000E+00 0.0000E+00 5.7328E+17 Organic I (atoms) 0.0000E+00 0.0000E+00 2.1703E+17 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 720.0000 Ci kg Atoms Bq Rb-86 7.2302E+01 8.8858E-07 6.2223E+18 2.6752E+12 Cs-134 2.3969E+04 1.8526E-02 8.3256E+22 8.8685E+14 Cs-136 1.3088E+03 1.7857E-05 7.9073E+19 4.8425E+13 Cs-137 1.3300E+04 1.5291E-01 6.7214E+23 4.9211E+14 Ba-137m 1.4744E+04 2.7414E-08 1.2051E+17 5.4551E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.7145E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 2 Page 67 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 720.0000 Ci kg Atoms Bq I-131 8.6467E-03 6.9745E-11 3.2062E+14 3.1993E+08 Br-82 1.6669E-10 1.5397E-19 1.1308E+06 6.1676E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.3258E+14 Organic I (atoms) 8.8046E+13 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-131m 8.0321E-06 9.5893E-14 4.4082E+11 2.9719E+05 Control Room Transport Group Inventory:

Overlying Time (h) = 720.0000 Atmosphere Sump Pool Noble gases (atoms) 4.4082E+11 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 720.0000 Ci kg Atoms Bq I-131 1.0572E-02 8.5275E-11 3.9201E+14 3.9116E+08 Br-82 2.0382E-10 1.8826E-19 1.3826E+06 7.5414E+00 Deposition Recirculating Time (h) = 720.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 2.8436E+14 Organic I (atoms) 0.0000E+00 1.0765E+14 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter

Numerical Applications Inc. Attachment 2 Page 68 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 720.0000 Ci kg Atoms Bq I-131 8.6467E-03 6.9745E-11 3.2062E+14 3.1993E+08 Br-82 1.6669E-10 1.5397E-19 1.1308E+06 6.1676E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.3258E+14 Organic I (atoms) 8.8046E+13 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq I-131 1.9219E-02 1.5502E-10 7.1264E+14 7.1109E+08 Br-82 3.7051E-10 3.4223E-19 2.5134E+06 1.3709E+01 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 720.0000 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 720.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Transport Group Totals in Model:

Noble Gases (atoms) 1.9109E+22

Numerical Applications Inc. Attachment 2 Page 69 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 1.4460E+20 Organic I (atoms) 2.1722E+17 Aerosols (kg) 1.7145E-01 37004 I-131 Summary Fuel Pool-Unfiltered Environment Control Room Time (hr) I-131 (Curies) I-131 (Curies) I-131 (Curies) 0.000 0.0000E+00 0.0000E+00 0.0000E+00 0.001 0.0000E+00 0.0000E+00 0.0000E+00 0.002 0.0000E+00 0.0000E+00 0.0000E+00 0.280 2.3374E-02 3.8833E+01 1.3068E-01 0.333 2.3370E-02 4.6279E+01 1.5146E-01 0.600 2.3348E-02 8.3618E+01 5.3783E-02 0.860 2.3327E-02 1.1992E+02 2.7446E-02 1.120 2.3306E-02 1.5614E+02 2.0009E-02 1.380 2.3285E-02 1.9229E+02 1.7901E-02 1.640 2.3264E-02 2.2837E+02 1.7296E-02 1.900 2.3243E-02 2.6439E+02 1.7114E-02 2.000 2.3235E-02 2.7823E+02 1.7083E-02 2.002 2.3235E-02 2.7850E+02 1.7047E-02 2.280 0.0000E+00 2.8076E+02 4.7235E-03 2.540 0.0000E+00 2.8050E+02 1.3319E-03 2.800 0.0000E+00 2.8024E+02 3.7554E-04 3.060 0.0000E+00 2.7998E+02 1.0589E-04 3.320 0.0000E+00 2.7971E+02 2.9858E-05 3.580 0.0000E+00 2.7945E+02 8.4189E-06 3.840 0.0000E+00 2.7919E+02 2.3738E-06 4.100 0.0000E+00 2.7893E+02 6.6934E-07 4.360 0.0000E+00 2.7867E+02 1.8873E-07 4.620 0.0000E+00 2.7841E+02 5.3216E-08 4.880 0.0000E+00 2.7815E+02 1.5005E-08 5.140 0.0000E+00 2.7789E+02 4.2309E-09 5.400 0.0000E+00 2.7763E+02 1.1930E-09 5.660 0.0000E+00 2.7737E+02 3.3638E-10 5.920 0.0000E+00 2.7711E+02 9.4848E-11 6.180 0.0000E+00 2.7686E+02 2.6744E-11 6.440 0.0000E+00 2.7660E+02 7.5409E-12 6.700 0.0000E+00 2.7634E+02 2.1263E-12 6.960 0.0000E+00 2.7608E+02 5.9954E-13 7.220 0.0000E+00 2.7582E+02 1.6905E-13 7.480 0.0000E+00 2.7557E+02 4.7666E-14 7.740 0.0000E+00 2.7531E+02 1.3440E-14 8.000 0.0000E+00 2.7505E+02 3.7897E-15 8.260 0.0000E+00 2.7479E+02 1.0686E-15 8.520 0.0000E+00 2.7454E+02 3.0130E-16 8.780 0.0000E+00 2.7428E+02 8.4957E-17 9.040 0.0000E+00 2.7403E+02 2.3955E-17 9.300 0.0000E+00 2.7377E+02 6.7545E-18 9.560 0.0000E+00 2.7351E+02 1.9045E-18 9.820 0.0000E+00 2.7326E+02 5.3702E-19 10.080 0.0000E+00 2.7300E+02 1.5142E-19 24.000 0.0000E+00 2.5969E+02 5.5539E-49 96.000 0.0000E+00 2.0051E+02 3.1013-201 720.000 0.0000E+00 2.1313E+01 0.0000E+00 Fuel Pool-Filtered Time (hr) I-131 (Curies) 0.000 0.0000E+00 0.001 0.0000E+00 0.002 0.0000E+00 0.280 0.0000E+00 0.333 0.0000E+00 0.600 0.0000E+00 0.860 0.0000E+00 1.120 0.0000E+00 1.380 0.0000E+00 1.640 0.0000E+00

Numerical Applications Inc. Attachment 2 Page 70 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 1.900 0.0000E+00 2.000 0.0000E+00 2.002 0.0000E+00 2.280 0.0000E+00 2.540 0.0000E+00 2.800 0.0000E+00 3.060 0.0000E+00 3.320 0.0000E+00 3.580 0.0000E+00 3.840 0.0000E+00 4.100 0.0000E+00 4.360 0.0000E+00 4.620 0.0000E+00 4.880 0.0000E+00 5.140 0.0000E+00 5.400 0.0000E+00 5.660 0.0000E+00 5.920 0.0000E+00 6.180 0.0000E+00 6.440 0.0000E+00 6.700 0.0000E+00 6.960 0.0000E+00 7.220 0.0000E+00 7.480 0.0000E+00 7.740 0.0000E+00 8.000 0.0000E+00 8.260 0.0000E+00 8.520 0.0000E+00 8.780 0.0000E+00 9.040 0.0000E+00 9.300 0.0000E+00 9.560 0.0000E+00 9.820 0.0000E+00 10.080 0.0000E+00 24.000 0.0000E+00 96.000 0.0000E+00 720.000 0.0000E+00 Cumulative Dose Summary EAB LPZ Control Room Time Thyroid TEDE Thyroid TEDE Thyroid TEDE (hr) (rem) (rem) (rem) (rem) (rem) (rem) 0.000 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.001 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.002 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.280 8.3404E+00 3.0641E-01 1.0306E+00 3.7861E-02 2.6890E+01 8.2912E-01 0.333 9.9401E+00 3.6519E-01 1.2282E+00 4.5124E-02 3.7491E+01 1.1559E+00 0.600 1.7965E+01 6.6009E-01 2.2198E+00 8.1563E-02 7.2199E+01 2.2277E+00 0.860 2.5771E+01 9.4700E-01 3.1843E+00 1.1701E-01 8.6080E+01 2.6586E+00 1.120 3.3565E+01 1.2335E+00 4.1473E+00 1.5241E-01 9.4485E+01 2.9206E+00 1.380 4.1348E+01 1.5196E+00 5.1091E+00 1.8776E-01 1.0134E+02 3.1346E+00 1.640 4.9121E+01 1.8053E+00 6.0696E+00 2.2307E-01 1.0775E+02 3.3348E+00 1.900 5.6885E+01 2.0907E+00 7.0288E+00 2.5834E-01 1.1404E+02 3.5308E+00 2.000 5.9868E+01 2.2004E+00 7.3975E+00 2.7189E-01 1.1644E+02 3.6058E+00 2.002 5.9928E+01 2.2027E+00 7.4008E+00 2.7202E-01 1.1649E+02 3.6073E+00 2.280 6.0471E+01 2.2244E+00 7.4314E+00 2.7323E-01 1.2039E+02 3.7296E+00 2.540 6.0472E+01 2.2262E+00 7.4314E+00 2.7333E-01 1.2137E+02 3.7608E+00 2.800 6.0472E+01 2.2279E+00 7.4314E+00 2.7343E-01 1.2164E+02 3.7700E+00 3.060 6.0472E+01 2.2295E+00 7.4314E+00 2.7352E-01 1.2172E+02 3.7727E+00 3.320 6.0472E+01 2.2312E+00 7.4314E+00 2.7362E-01 1.2174E+02 3.7736E+00 3.580 6.0472E+01 2.2327E+00 7.4314E+00 2.7370E-01 1.2175E+02 3.7740E+00 3.840 6.0472E+01 2.2343E+00 7.4314E+00 2.7379E-01 1.2175E+02 3.7741E+00 4.100 6.0472E+01 2.2358E+00 7.4314E+00 2.7387E-01 1.2175E+02 3.7742E+00 4.360 6.0472E+01 2.2372E+00 7.4314E+00 2.7396E-01 1.2175E+02 3.7743E+00 4.620 6.0472E+01 2.2386E+00 7.4314E+00 2.7404E-01 1.2175E+02 3.7743E+00 4.880 6.0472E+01 2.2400E+00 7.4314E+00 2.7411E-01 1.2175E+02 3.7744E+00 5.140 6.0472E+01 2.2414E+00 7.4314E+00 2.7419E-01 1.2175E+02 3.7744E+00 5.400 6.0472E+01 2.2427E+00 7.4314E+00 2.7426E-01 1.2175E+02 3.7745E+00 5.660 6.0472E+01 2.2439E+00 7.4314E+00 2.7433E-01 1.2175E+02 3.7745E+00 5.920 6.0472E+01 2.2452E+00 7.4314E+00 2.7440E-01 1.2175E+02 3.7746E+00

Numerical Applications Inc. Attachment 2 Page 71 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 6.180 6.0472E+01 2.2464E+00 7.4314E+00 2.7447E-01 1.2175E+02 3.7746E+00 6.440 6.0472E+01 2.2476E+00 7.4314E+00 2.7454E-01 1.2175E+02 3.7747E+00 6.700 6.0472E+01 2.2487E+00 7.4314E+00 2.7460E-01 1.2175E+02 3.7747E+00 6.960 6.0472E+01 2.2498E+00 7.4314E+00 2.7467E-01 1.2175E+02 3.7748E+00 7.220 6.0472E+01 2.2509E+00 7.4314E+00 2.7473E-01 1.2175E+02 3.7748E+00 7.480 6.0472E+01 2.2520E+00 7.4314E+00 2.7479E-01 1.2175E+02 3.7748E+00 7.740 6.0472E+01 2.2530E+00 7.4314E+00 2.7484E-01 1.2175E+02 3.7749E+00 8.000 6.0472E+01 2.2540E+00 7.4314E+00 2.7490E-01 1.2175E+02 3.7749E+00 8.260 6.0472E+01 2.2550E+00 7.4314E+00 2.7494E-01 1.2175E+02 3.7749E+00 8.520 6.0472E+01 2.2560E+00 7.4314E+00 2.7497E-01 1.2175E+02 3.7750E+00 8.780 6.0472E+01 2.2569E+00 7.4314E+00 2.7501E-01 1.2175E+02 3.7750E+00 9.040 6.0472E+01 2.2578E+00 7.4314E+00 2.7504E-01 1.2175E+02 3.7750E+00 9.300 6.0472E+01 2.2587E+00 7.4314E+00 2.7508E-01 1.2175E+02 3.7750E+00 9.560 6.0472E+01 2.2595E+00 7.4314E+00 2.7511E-01 1.2175E+02 3.7750E+00 9.820 6.0472E+01 2.2604E+00 7.4314E+00 2.7514E-01 1.2175E+02 3.7750E+00 10.080 6.0472E+01 2.2612E+00 7.4314E+00 2.7517E-01 1.2175E+02 3.7750E+00 24.000 6.0472E+01 2.2846E+00 7.4314E+00 2.7606E-01 1.2175E+02 3.7754E+00 96.000 6.0472E+01 2.2944E+00 7.4314E+00 2.7621E-01 1.2175E+02 3.7755E+00 720.000 6.0472E+01 2.2949E+00 7.4314E+00 2.7622E-01 1.2175E+02 3.7755E+00 Worst Two-Hour Dose (Provided for Dose Location 1)

EAB Time Whole Body Thyroid Skin TEDE (hr) (rem) (rem) (rem) (rem) 0.0 3.6513E-01 5.9868E+01 1.0476E+00 2.2004E+00 30 Day Control Room Skin Dose Control Room Time Skin (hr) (rem) 720.0 4.4376E+00

Numerical Applications Inc. Attachment 3 Page 72 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Attachment 3 RADTRAD-NAI FHA Output - Case 1 - 10% Filtered RADTRAD-NAI Version 1.1a(QA) run on May 9, 2005 at 06:46:46 File information Plant file name = pal/FHA/db/pal_fha_db_ast_10filter.psf Inventory file name = pal/FHA/db/palisades_fha_db_ast_adj.nif Scenario file name = pal/FHA/db/pal_fha_db_ast_10filter.psf Release file name = pal/FHA/db/pal_fha_ast.rft Dose conversion file name = pal/FHA/db/nai-1101-001rev0.dcf

  • RADTRAD-NAI 1.1a(QA)
  • 09 May 2005 06:41:56
    • Palisades FHA Design Basis
    • 10% release filtration
  • Nuclide inventory file pal/FHA/db/palisades_fha_db_ast_adj.nif
  • Plant power 2703
  • Compartments 4
  • Compartment 1:

Fuel Pool-Unfiltered 3

10000 0

0 0

1

  • Compartment 2:

Environment 2

2e+20 0

0 0

0

  • Compartment 3:

Control Room 1

35923 0

1 0

0

  • Compartment 4:

Fuel Pool-Filtered 3

10000 0

0 0

1

Numerical Applications Inc. Attachment 3 Page 73 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1

  • Pathways 6
  • Pathway 1:

Fuel Pool Release-Unfiltered 1

2 2

  • Pathway 2:

Control Room Unfiltered Makeup 2

3 2

  • Pathway 3:

Control Room Filtered Makeup 2

3 2

  • Pathway 4:

Control Room Unfiltered Inleakage 2

3 2

  • Pathway 5:

Control Room Exhaust 3

2 2

  • Pathway 6:

Fuel Pool Release-Filtered 4

2 2

  • Sources 4

1 0.9 2 0 3 0 4 0.1

  • dose conversion factors filename pal/FHA/db/nai-1101-001rev0.dcf
  • release fraction and timing filename pal/FHA/db/pal_fha_ast.rft 0

1 1

  • Iodine 0 0.9985 0.0015
  • Overlying pool
  • aerosol model 0
  • elemental model 1

2 0 252 720 252

  • organic model 1

2 0 1 720 1

  • pH tracking 0
  • Compartment detail
  • Compartment 1:

1

  • spray model 0

0 0

  • filter model 0
  • deposition model 0

Numerical Applications Inc. Attachment 3 Page 74 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 0

  • Compartment 2:

1

  • spray model 0

0 0

  • filter model 0
  • deposition model 0

0

  • Compartment 3:

1

  • spray model 0

0 0

  • filter model 1

3 0 0 99 99 99 0.3333 1413.6 99 99 99 720 1413.6 99 99 99

  • deposition model 0

0

  • Compartment 4:

1

  • spray model 0

0 0

  • filter model 0
  • deposition model 0

0

  • Pathways:
  • Pathway 1
  • filter efficiency model 1

2 0 1000000 100 0 0 720 1000000 100 0 0

  • Pathway 2
  • filter efficiency model 1

3 0 660 0 0 0 0.3333 0 0 0 0 720 0 0 0 0

  • Pathway 3
  • filter efficiency model 1

3 0 0 99 99 99 0.3333 1413.6 99 99 99 720 1413.6 99 99 99

  • Pathway 4
  • filter efficiency model 1

3 0 0 0 0 0 0.3333 100 0 0 0 720 100 0 0 0

  • Pathway 5
  • filter efficiency model 1

3 0 660 0 0 0 0.3333 1513.6 0 0 0 720 1513.6 0 0 0

Numerical Applications Inc. Attachment 3 Page 75 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1

  • Pathway 6
  • filter efficiency model 1

2 0 1000000 100 94 94 720 1000000 100 94 94

  • x/q tables 6

EAB 2

0 0.000539 720 0.000539 LPZ 6

0 6.66e-05 2 3.03e-05 8 2.04e-05 24 8.67e-06 96 2.54e-06 720 2.54e-06 Equip Hatch-Normal 6

0 0.0125 2 0.00983 8 0.00362 24 0.00286 96 0.00228 720 0.00228 Equip Hatch-Emergency 6

0 0.000732 2 0.000613 8 0.000245 24 0.000175 96 0.000129 720 0.000129 Stack-Normal 6

0 0.0061 2 0.00432 8 0.00173 24 0.00127 96 0.000979 720 0.000979 Stack-Emergency 6

0 0.000832 2 0.000769 8 0.000283 24 0.000215 96 0.000157 720 0.000157

  • dose locations 3
  • location name, compartment number and x/q table EAB 2

1

  • br model 1

4 0 0.00035 8 0.00018 24 0.00023 720 0.00023

  • of model 0
  • location x/q input to be included 0
  • location name, compartment number and x/q table LPZ 2

2

Numerical Applications Inc. Attachment 3 Page 76 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1

  • br model 1

4 0 0.00035 8 0.00018 24 0.00023 720 0.00023

  • of model 0
  • location x/q input to be included 0
  • location name, compartment number and x/q table Control Room 3

0

  • br model 1

2 0 0.00035 720 0.00035

  • of model 1

4 0 1 24 0.6 96 0.4 720 0.4

  • location x/q input to be included 1
  • number of intake combinations 6
  • intake combinations 2 1 3 3 1 4 4 1 3 2 6 5 3 6 6 4 6 5
  • time step count 3

0 1e-06 0.001 0.02 720 0.02

  • show plant, scenario, event, step, model 1

1 1

0 1

RADTRAD-NAI Version 1.1a(QA) run on May 9, 2005 at 06:46:46 Plant Description Number of Nuclides = 107 Inventory Power = 2.7030E+03 MWth Plant Power Level = 2.7030E+03 MWth Number of compartments = 4 Compartment information Compartment number 1 (Source term fraction = 9.0000E-01)

Name: Fuel Pool-Unfiltered Compartment volume = 1.0000E+04 (Cubic feet)

Removal devices within compartment:

Suppression pool Pathways into and out of compartment 1

Numerical Applications Inc. Attachment 3 Page 77 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Pathway to compartment number 2: Fuel Pool Release-Unfiltered Compartment number 2 Name: Environment Pathways into and out of compartment 2 Pathway to compartment number 3: Control Room Unfiltered Makeup Pathway to compartment number 3: Control Room Filtered Makeup Pathway to compartment number 3: Control Room Unfiltered Inleakage Pathway from compartment number 1: Fuel Pool Release-Unfiltered Pathway from compartment number 3: Control Room Exhaust Pathway from compartment number 4: Fuel Pool Release-Filtered Compartment number 3 Name: Control Room Compartment volume = 3.5923E+04 (Cubic feet)

Removal devices within compartment:

Filter(s)

Pathways into and out of compartment 3 Pathway to compartment number 2: Control Room Exhaust Pathway from compartment number 2: Control Room Unfiltered Makeup Pathway from compartment number 2: Control Room Filtered Makeup Pathway from compartment number 2: Control Room Unfiltered Inleakage Compartment number 4 (Source term fraction = 1.0000E-01)

Name: Fuel Pool-Filtered Compartment volume = 1.0000E+04 (Cubic feet)

Removal devices within compartment:

Suppression pool Pathways into and out of compartment 4 Pathway to compartment number 2: Fuel Pool Release-Filtered Total number of pathways = 6 RADTRAD-NAI Version 1.1a(QA) run on May 9, 2005 at 06:46:46 Scenario Description Radioactive Decay is enabled Calculation of Daughters is enabled Iodine fractions Aerosol = 0.0000E+00 Elemental = 9.9850E-01 Organic = 1.5000E-03 Overlying pool characteristics Elemental Removal Data:

Time (hr) DF 0.0000E+00 2.5200E+02 7.2000E+02 2.5200E+02 Organic Removal Data:

Time (hr) DF 0.0000E+00 1.0000E+00 7.2000E+02 1.0000E+00 COMPARTMENT DATA Compartment number 1: Fuel Pool-Unfiltered Compartment number 2: Environment Compartment number 3: Control Room Compartment Filter Data Time (hr) Flow Rate Filter Efficiencies (%)

Numerical Applications Inc. Attachment 3 Page 78 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 (cfm) Aerosol Elemental Organic 0.0000E+00 0.0000E+00 9.9000E+01 9.9000E+01 9.9000E+01 3.3330E-01 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 7.2000E+02 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 Compartment number 4: Fuel Pool-Filtered PATHWAY DATA Pathway number 1: Fuel Pool Release-Unfiltered Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 1.0000E+06 1.0000E+02 0.0000E+00 0.0000E+00 7.2000E+02 1.0000E+06 1.0000E+02 0.0000E+00 0.0000E+00 Pathway number 2: Control Room Unfiltered Makeup Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 6.6000E+02 0.0000E+00 0.0000E+00 0.0000E+00 3.3330E-01 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 3: Control Room Filtered Makeup Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 0.0000E+00 9.9000E+01 9.9000E+01 9.9000E+01 3.3330E-01 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 7.2000E+02 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 Pathway number 4: Control Room Unfiltered Inleakage Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 3.3330E-01 1.0000E+02 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 1.0000E+02 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 5: Control Room Exhaust Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 6.6000E+02 0.0000E+00 0.0000E+00 0.0000E+00 3.3330E-01 1.5136E+03 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 1.5136E+03 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 6: Fuel Pool Release-Filtered Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 1.0000E+06 1.0000E+02 9.4000E+01 9.4000E+01 7.2000E+02 1.0000E+06 1.0000E+02 9.4000E+01 9.4000E+01 X/Q DATA X/Q table 1: EAB Time (hr) X/Q (s

  • m^-3) 0.0000E+00 5.3900E-04 7.2000E+02 5.3900E-04

Numerical Applications Inc. Attachment 3 Page 79 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 X/Q table 2: LPZ Time (hr) X/Q (s

  • m^-3) 0.0000E+00 6.6600E-05 2.0000E+00 3.0300E-05 8.0000E+00 2.0400E-05 2.4000E+01 8.6700E-06 9.6000E+01 2.5400E-06 7.2000E+02 2.5400E-06 X/Q table 3: Equip Hatch-Normal Time (hr) X/Q (s
  • m^-3) 0.0000E+00 1.2500E-02 2.0000E+00 9.8300E-03 8.0000E+00 3.6200E-03 2.4000E+01 2.8600E-03 9.6000E+01 2.2800E-03 7.2000E+02 2.2800E-03 X/Q table 4: Equip Hatch-Emergency Time (hr) X/Q (s
  • m^-3) 0.0000E+00 7.3200E-04 2.0000E+00 6.1300E-04 8.0000E+00 2.4500E-04 2.4000E+01 1.7500E-04 9.6000E+01 1.2900E-04 7.2000E+02 1.2900E-04 X/Q table 5: Stack-Normal Time (hr) X/Q (s
  • m^-3) 0.0000E+00 6.1000E-03 2.0000E+00 4.3200E-03 8.0000E+00 1.7300E-03 2.4000E+01 1.2700E-03 9.6000E+01 9.7900E-04 7.2000E+02 9.7900E-04 X/Q table 6: Stack-Emergency Time (hr) X/Q (s
  • m^-3) 0.0000E+00 8.3200E-04 2.0000E+00 7.6900E-04 8.0000E+00 2.8300E-04 2.4000E+01 2.1500E-04 9.6000E+01 1.5700E-04 7.2000E+02 1.5700E-04 LOCATION DATA Location EAB is in compartment 2 Using X/Q Table 1 Location Breathing Rate Data Time (hr) Breathing Rate (m^3
  • sec^-1) 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 2.3000E-04 Location LPZ is in compartment 2 Using X/Q Table 2 Location Breathing Rate Data Time (hr) Breathing Rate (m^3
  • sec^-1) 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 2.3000E-04 Location Control Room is in compartment 3 Inleakage X/Q Table Assignments

Numerical Applications Inc. Attachment 3 Page 80 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Inleakage Path Source Path X/Q Table 2 1 3 3 1 4 4 1 3 2 6 5 3 6 6 4 6 5 Location Breathing Rate Data Time (hr) Breathing Rate (m^3

  • sec^-1) 0.0000E+00 3.5000E-04 7.2000E+02 3.5000E-04 Location Occupancy Factor Data Time (hr) Occupancy Factor 0.0000E+00 1.0000E+00 2.4000E+01 6.0000E-01 9.6000E+01 4.0000E-01 7.2000E+02 4.0000E-01 USER SPECIFIED TIME STEP DATA - SUPPLEMENTAL TIME STEPS Time Time step 0.0000E+00 1.0000E-06 1.0000E-03 2.0000E-02 7.2000E+02 2.0000E-02 RADTRAD-NAI Version 1.1a(QA) run on May 9, 2005 at 06:46:46 Dose, Detailed Model and Detailed Inventory Output Detailed model information at time (H) = 0.0010 EAB Doses:

Time (h) = 0.0010 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 LPZ Doses:

Time (h) = 0.0010 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Control Room Doses:

Time (h) = 0.0010 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 0.0010 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 3 Page 81 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0010 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Environment Transport Group Inventory:

Present Release Integral Time (h) = 0.0010 Release Rate/s Release Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 3 Page 82 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Transport Group Inventory:

Overlying Time (h) = 0.0010 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0010 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 0.0010 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0010 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 3 Page 83 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 0.0020 EAB Doses:

Time (h) = 0.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 LPZ Doses:

Time (h) = 0.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Control Room Doses:

Time (h) = 0.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 0.0020 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Environment Transport Group Inventory:

Present Release Integral Time (h) = 0.0020 Release Rate/s Release Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 3 Page 84 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Transport Group Inventory:

Overlying Time (h) = 0.0020 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 3 Page 85 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 0.0020 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 0.3333 EAB Doses:

Time (h) = 0.3333 Whole Body Thyroid Skin TEDE Delta dose (rem) 5.9551E-02 9.0058E+00 1.7304E-01 3.3565E-01 Accumulated dose (rem) 5.9551E-02 9.0058E+00 1.7304E-01 3.3565E-01 LPZ Doses:

Time (h) = 0.3333 Whole Body Thyroid Skin TEDE Delta dose (rem) 7.3582E-03 1.1128E+00 2.1382E-02 4.1473E-02 Accumulated dose (rem) 7.3582E-03 1.1128E+00 2.1382E-02 4.1473E-02 Control Room Doses:

Time (h) = 0.3333 Whole Body Thyroid Skin TEDE Delta dose (rem) 6.2908E-03 3.3851E+01 6.1879E-01 1.0440E+00 Accumulated dose (rem) 6.2908E-03 3.3851E+01 6.1879E-01 1.0440E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Numerical Applications Inc. Attachment 3 Page 86 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 7.8900E-02 2.0110E-07 1.4248E+18 2.9193E+09 Kr-85m 4.1812E-04 5.0808E-14 3.5997E+11 1.5471E+07 Kr-88 1.4872E-05 1.1860E-15 8.1165E+09 5.5027E+05 Rb-86 1.6363E-02 2.0109E-10 1.4082E+15 6.0541E+08 I-131 2.1033E-02 1.6965E-10 7.7991E+14 7.7822E+08 I-132 1.4367E-02 1.3918E-12 6.3498E+12 5.3156E+08 I-133 6.1157E-03 5.3987E-12 2.4445E+13 2.2628E+08 I-135 1.7701E-04 5.0404E-14 2.2484E+11 6.5494E+06 Xe-133 5.0182E+00 2.6809E-08 1.2139E+17 1.8567E+11 Xe-135 3.5563E-01 1.3926E-10 6.2121E+14 1.3158E+10 Cs-134 1.8306E+00 1.4149E-06 6.3585E+18 6.7731E+10 Cs-136 4.7521E-01 6.4839E-09 2.8711E+16 1.7583E+10 Cs-137 9.9000E-01 1.1382E-05 5.0031E+19 3.6630E+10 I-130 5.1186E-05 2.6244E-14 1.2158E+11 1.8939E+06 Kr-83m 4.2686E-06 2.0689E-16 1.5011E+09 1.5794E+05 Xe-131m 3.3771E-02 4.0318E-10 1.8534E+15 1.2495E+09 Xe-133m 1.3846E-01 3.0858E-10 1.3972E+15 5.1231E+09 Xe-135m 3.6225E-01 3.9768E-12 1.7740E+13 1.3403E+10 Cs-134m 4.2568E-06 5.2786E-16 2.3723E+09 1.5750E+05 Rb-88 3.9668E-05 3.3046E-16 2.2615E+09 1.4677E+06 Ba-137m 2.0299E-01 3.7744E-13 1.6591E+12 7.5106E+09 Br-82 4.1921E-05 3.8721E-14 2.8437E+11 1.5511E+06 Br-83 1.6426E-09 1.0398E-19 7.5442E+05 6.0777E+01 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 0.3333 Atmosphere Sump Pool Noble gases (atoms) 1.5501E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 5.8853E+14 0.0000E+00 2.9353E+20 Organic I (atoms) 2.2280E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 1.2803E-05 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.3333 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 3.1642E+01 3.8888E-07 2.7231E+18 1.1708E+12 Cs-134 3.5400E+03 2.7360E-03 1.2296E+22 1.3098E+14 Cs-136 9.1896E+02 1.2539E-05 5.5521E+19 3.4002E+13 Cs-137 1.9145E+03 2.2010E-02 9.6749E+22 7.0835E+13 Cs-134m 8.2318E-03 1.0208E-12 4.5875E+12 3.0458E+08 Rb-88 5.4640E-02 4.5519E-13 3.1150E+12 2.0217E+09 Ba-137m 1.8051E+03 3.3565E-09 1.4754E+16 6.6789E+13 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 2.4759E-02 Environment Integral Nuclide Release:

Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 1.7364E+02 4.4257E-04 3.1356E+21 6.4246E+12 Kr-85m 9.2017E-01 1.1181E-10 7.9218E+14 3.4046E+10 Kr-87 1.1334E-08 4.0014E-19 2.7698E+06 4.1937E+02 Kr-88 3.2729E-02 2.6102E-12 1.7862E+13 1.2110E+09 I-131 4.1929E+01 3.3821E-07 1.5548E+18 1.5514E+12 I-132 2.7320E+01 2.6467E-09 1.2075E+16 1.0108E+12 I-133 1.2192E+01 1.0763E-08 4.8732E+16 4.5110E+11 I-135 3.5288E-01 1.0048E-10 4.4824E+14 1.3057E+10

Numerical Applications Inc. Attachment 3 Page 87 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Xe-133 1.0697E+04 5.7148E-05 2.5876E+20 3.9579E+14 Xe-135 6.6159E+02 2.5907E-07 1.1557E+18 2.4479E+13 I-130 1.0204E-01 5.2319E-11 2.4237E+14 3.7755E+09 Kr-83m 2.7903E-03 1.3524E-13 9.8125E+11 1.0324E+08 Xe-131m 6.8317E+01 8.1562E-07 3.7494E+18 2.5277E+12 Xe-133m 2.7991E+02 6.2382E-07 2.8246E+18 1.0357E+13 Xe-135m 1.1206E+01 1.2301E-10 5.4875E+14 4.1461E+11 Rb-88 1.0963E-02 9.1327E-14 6.2498E+11 4.0562E+08 Br-82 8.3571E-02 7.7192E-11 5.6691E+14 3.0921E+09 Br-83 3.2746E-06 2.0728E-16 1.5040E+09 1.2116E+05 Environment Transport Group Inventory:

Present Release Integral Time (h) = 0.3333 Release Rate/s Release Noble gases (atoms) 1.3672E+20 1.8989E+18 3.4021E+21 Elemental I (atoms) 4.7150E+16 6.5486E+14 1.1728E+18 Organic I (atoms) 1.7849E+16 2.4791E+14 4.4399E+17 Aerosols (kg) 3.4462E-16 4.7865E-18 9.1327E-14 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 3.1642E+01 3.8888E-07 2.7231E+18 1.1708E+12 Cs-134 3.5400E+03 2.7360E-03 1.2296E+22 1.3098E+14 Cs-136 9.1896E+02 1.2539E-05 5.5521E+19 3.4002E+13 Cs-137 1.9145E+03 2.2010E-02 9.6749E+22 7.0835E+13 Cs-134m 8.2318E-03 1.0208E-12 4.5875E+12 3.0458E+08 Rb-88 5.4640E-02 4.5519E-13 3.1150E+12 2.0217E+09 Ba-137m 1.8051E+03 3.3565E-09 1.4754E+16 6.6789E+13 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 2.4759E-02 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 3 Page 88 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 3.5158E+00 4.3209E-08 3.0257E+17 1.3008E+11 I-131 4.2480E+00 3.4265E-08 1.5752E+17 1.5718E+11 I-132 2.7636E+00 2.6774E-10 1.2215E+15 1.0225E+11 I-133 1.2352E+00 1.0904E-09 4.9373E+15 4.5703E+10 I-135 3.5752E-02 1.0180E-11 4.5413E+13 1.3228E+09 Cs-134 3.9333E+02 3.0400E-04 1.3662E+21 1.4553E+13 Cs-136 1.0211E+02 1.3932E-06 6.1690E+18 3.7780E+12 Cs-137 2.1272E+02 2.4455E-03 1.0750E+22 7.8706E+12 I-130 1.0338E-02 5.3007E-12 2.4555E+13 3.8251E+08 Cs-134m 9.1465E-04 1.1342E-13 5.0972E+11 3.3842E+07 Rb-88 6.0711E-03 5.0576E-14 3.4611E+11 2.2463E+08 Ba-137m 2.0057E+02 3.7294E-10 1.6393E+15 7.4210E+12 Br-82 8.4670E-03 7.8207E-12 5.7436E+13 3.1328E+08 Br-83 3.3177E-07 2.1001E-17 1.5237E+08 1.2275E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.1882E+17 Organic I (atoms) 4.4982E+16 Aerosols (kg) 2.7510E-03 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 5.3908E-01 1.3740E-06 9.7348E+18 1.9946E+10 Kr-85m 2.8568E-03 3.4714E-13 2.4594E+12 1.0570E+08 Kr-88 1.0161E-04 8.1036E-15 5.5456E+10 3.7597E+06 I-131 1.3676E-01 1.1031E-09 5.0710E+15 5.0600E+09 I-132 8.9369E-02 8.6580E-12 3.9500E+13 3.3067E+09 I-133 3.9765E-02 3.5103E-11 1.5894E+14 1.4713E+09 I-135 1.1510E-03 3.2773E-13 1.4620E+12 4.2585E+07 Xe-133 3.3212E+01 1.7743E-07 8.0339E+17 1.2288E+12 Xe-135 2.0543E+00 8.0443E-10 3.5884E+15 7.6009E+10 I-130 3.3282E-04 1.7065E-13 7.9050E+11 1.2314E+07 Kr-83m 8.6779E-06 4.2060E-16 3.0517E+09 3.2108E+05 Xe-131m 2.1211E-01 2.5324E-09 1.1641E+16 7.8482E+09 Xe-133m 8.6908E-01 1.9369E-09 8.7699E+15 3.2156E+10 Xe-135m 3.6262E-02 3.9808E-13 1.7758E+12 1.3417E+09 Rb-88 3.2312E-05 2.6918E-16 1.8421E+09 1.1956E+06 Br-82 2.7258E-04 2.5177E-13 1.8490E+12 1.0085E+07 Br-83 1.0680E-08 6.7608E-19 4.9053E+06 3.9518E+02 Control Room Transport Group Inventory:

Overlying Time (h) = 0.3333 Atmosphere Sump Pool Noble gases (atoms) 1.0562E+19 0.0000E+00 0.0000E+00 Elemental I (atoms) 3.8254E+15 0.0000E+00 0.0000E+00 Organic I (atoms) 1.4482E+15 0.0000E+00 0.0000E+00 Aerosols (kg) 2.6918E-16 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.3333 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 3 Page 89 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 8.7666E-03 2.2345E-08 1.5831E+17 3.2437E+08 Kr-85m 4.6458E-05 5.6453E-15 3.9996E+10 1.7189E+06 Kr-88 1.6525E-06 1.3178E-16 9.0184E+08 6.1141E+04 Rb-86 1.8181E-03 2.2344E-11 1.5646E+14 6.7268E+07 I-131 2.3370E-03 1.8850E-11 8.6657E+13 8.6468E+07 I-132 1.5963E-03 1.5465E-13 7.0553E+11 5.9063E+07 I-133 6.7952E-04 5.9986E-13 2.7161E+12 2.5142E+07 I-135 1.9668E-05 5.6005E-15 2.4983E+10 7.2772E+05 Xe-133 5.5757E-01 2.9788E-09 1.3488E+16 2.0630E+10 Xe-135 3.9514E-02 1.5473E-11 6.9024E+13 1.4620E+09 Cs-134 2.0340E-01 1.5721E-07 7.0650E+17 7.5257E+09 Cs-136 5.2801E-02 7.2043E-10 3.1901E+15 1.9536E+09 Cs-137 1.1000E-01 1.2646E-06 5.5590E+18 4.0700E+09 I-130 5.6873E-06 2.9161E-15 1.3508E+10 2.1043E+05 Kr-83m 4.7428E-07 2.2988E-17 1.6679E+08 1.7549E+04 Xe-131m 3.7523E-03 4.4797E-11 2.0594E+14 1.3883E+08 Xe-133m 1.5385E-02 3.4287E-11 1.5525E+14 5.6923E+08 Xe-135m 4.0250E-02 4.4186E-13 1.9711E+12 1.4893E+09 Cs-134m 4.7298E-07 5.8651E-17 2.6358E+08 1.7500E+04 Rb-88 4.4076E-06 3.6718E-17 2.5128E+08 1.6308E+05 Ba-137m 2.2554E-02 4.1938E-14 1.8435E+11 8.3451E+08 Br-82 4.6579E-06 4.3024E-15 3.1597E+10 1.7234E+05 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 0.3333 Atmosphere Sump Pool Noble gases (atoms) 1.7223E+17 0.0000E+00 0.0000E+00 Elemental I (atoms) 6.5393E+13 0.0000E+00 3.2614E+19 Organic I (atoms) 2.4756E+13 0.0000E+00 0.0000E+00 Aerosols (kg) 1.4226E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.3333 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered

Numerical Applications Inc. Attachment 3 Page 90 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 3.5158E+00 4.3209E-08 3.0257E+17 1.3008E+11 I-131 4.2480E+00 3.4265E-08 1.5752E+17 1.5718E+11 I-132 2.7636E+00 2.6774E-10 1.2215E+15 1.0225E+11 I-133 1.2352E+00 1.0904E-09 4.9373E+15 4.5703E+10 I-135 3.5752E-02 1.0180E-11 4.5413E+13 1.3228E+09 Cs-134 3.9333E+02 3.0400E-04 1.3662E+21 1.4553E+13 Cs-136 1.0211E+02 1.3932E-06 6.1690E+18 3.7780E+12 Cs-137 2.1272E+02 2.4455E-03 1.0750E+22 7.8706E+12 I-130 1.0338E-02 5.3007E-12 2.4555E+13 3.8251E+08 Cs-134m 9.1465E-04 1.1342E-13 5.0972E+11 3.3842E+07 Rb-88 6.0711E-03 5.0576E-14 3.4611E+11 2.2463E+08 Ba-137m 2.0057E+02 3.7294E-10 1.6393E+15 7.4210E+12 Br-82 8.4670E-03 7.8207E-12 5.7436E+13 3.1328E+08 Br-83 3.3177E-07 2.1001E-17 1.5237E+08 1.2275E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.1882E+17 Organic I (atoms) 4.4982E+16 Aerosols (kg) 2.7510E-03 Detailed model information at time (H) = 2.0000 EAB Doses:

Time (h) = 2.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.0012E-01 4.5235E+01 8.6642E-01 1.6868E+00 Accumulated dose (rem) 3.5967E-01 5.4241E+01 1.0395E+00 2.0224E+00 LPZ Doses:

Time (h) = 2.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.7084E-02 5.5893E+00 1.0706E-01 2.0842E-01 Accumulated dose (rem) 4.4442E-02 6.7021E+00 1.2844E-01 2.4990E-01 Control Room Doses:

Time (h) = 2.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.9138E-02 7.1287E+01 3.0093E+00 2.2139E+00 Accumulated dose (rem) 3.5429E-02 1.0514E+02 3.6281E+00 3.2579E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 7.8899E-02 2.0110E-07 1.4248E+18 2.9193E+09 Kr-85m 3.2308E-04 3.9259E-14 2.7814E+11 1.1954E+07 Kr-88 9.9017E-06 7.8966E-16 5.4039E+09 3.6636E+05 Rb-86 1.6320E-02 2.0058E-10 1.4045E+15 6.0385E+08 I-131 2.0912E-02 1.6868E-10 7.7542E+14 7.7373E+08 I-132 1.4143E-02 1.3701E-12 6.2509E+12 5.2328E+08 I-133 5.7853E-03 5.1070E-12 2.3124E+13 2.1406E+08 I-135 1.4863E-04 4.2322E-14 1.8879E+11 5.4992E+06 Xe-133 6.1779E+00 3.3005E-08 1.4944E+17 2.2858E+11 Xe-135 6.8729E-01 2.6913E-10 1.2006E+15 2.5430E+10 Cs-134 1.8305E+00 1.4148E-06 6.3581E+18 6.7727E+10 Cs-136 4.7347E-01 6.4601E-09 2.8606E+16 1.7518E+10 Cs-137 9.8999E-01 1.1382E-05 5.0030E+19 3.6630E+10 I-130 4.6618E-05 2.3903E-14 1.1073E+11 1.7249E+06 Kr-83m 1.7581E-05 8.5213E-16 6.1827E+09 6.5051E+05 Xe-131m 5.5679E-02 6.6474E-10 3.0558E+15 2.0601E+09 Xe-133m 2.2181E-01 4.9434E-10 2.2383E+15 8.2071E+09 Xe-135m 2.7249E+00 2.9913E-11 1.3344E+14 1.0082E+11 Cs-134m 2.8581E-06 3.5441E-16 1.5928E+09 1.0575E+05 Rb-88 2.6502E-05 2.2078E-16 1.5109E+09 9.8057E+05 Ba-137m 3.0525E-01 5.6758E-13 2.4949E+12 1.1294E+10 Br-82 4.0571E-05 3.7474E-14 2.7522E+11 1.5011E+06 Br-83 1.0130E-09 6.4123E-20 4.6525E+05 3.7481E+01

Numerical Applications Inc. Attachment 3 Page 91 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 2.0000 Atmosphere Sump Pool Noble gases (atoms) 1.5808E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 5.8421E+14 0.0000E+00 1.7544E+21 Organic I (atoms) 2.2116E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 1.2803E-05 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 1.9477E+02 2.3937E-06 1.6762E+19 7.2064E+12 Cs-134 2.1845E+04 1.6884E-02 7.5878E+22 8.0825E+14 Cs-136 5.6504E+03 7.7095E-05 3.4138E+20 2.0906E+14 Cs-137 1.1815E+04 1.3583E-01 5.9706E+23 4.3714E+14 Cs-134m 3.4108E-02 4.2295E-12 1.9008E+13 1.2620E+09 Rb-88 7.4066E-02 6.1702E-13 4.2225E+12 2.7405E+09 Ba-137m 1.2803E+04 2.3805E-08 1.0464E+17 4.7369E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.5279E-01 Environment Integral Nuclide Release:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 1.0506E+03 2.6779E-03 1.8972E+22 3.8873E+13 Kr-85m 4.3022E+00 5.2277E-10 3.7038E+15 1.5918E+11 Kr-88 1.3185E-01 1.0515E-11 7.1958E+13 4.8785E+09 I-131 2.5207E+02 2.0333E-06 9.3470E+18 9.3267E+12 I-132 1.2943E+02 1.2539E-08 5.7205E+16 4.7888E+12 I-133 6.9745E+01 6.1569E-08 2.7878E+17 2.5806E+12 I-135 1.7918E+00 5.1021E-10 2.2760E+15 6.6297E+10 Xe-133 6.4278E+04 3.4340E-04 1.5549E+21 2.3783E+15 Xe-135 3.5727E+03 1.3990E-06 6.2408E+18 1.3219E+14 I-130 5.6201E-01 2.8816E-10 1.3349E+15 2.0794E+10 Kr-83m 1.0427E-02 5.0537E-13 3.6668E+12 3.8579E+08 Xe-131m 4.1398E+02 4.9424E-06 2.2721E+19 1.5317E+13 Xe-133m 1.6659E+03 3.7127E-06 1.6811E+19 6.1639E+13 Xe-135m 5.6577E+01 6.2110E-10 2.7706E+15 2.0934E+12 Rb-88 1.1594E-01 9.6586E-13 6.6097E+12 4.2898E+09 Br-82 4.8911E-01 4.5178E-10 3.3179E+15 1.8097E+10 Br-83 1.2212E-05 7.7304E-16 5.6089E+09 4.5186E+05 Environment Transport Group Inventory:

Present Release Integral Time (h) = 2.0000 Release Rate/s Release Noble gases (atoms) 2.0604E+20 2.8617E+18 2.0573E+22 Elemental I (atoms) 7.0518E+16 9.7941E+14 7.0290E+18 Organic I (atoms) 2.6696E+16 3.7077E+14 2.6609E+18 Aerosols (kg) 5.1917E-16 7.2106E-18 9.6586E-13 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 1.9477E+02 2.3937E-06 1.6762E+19 7.2064E+12 Cs-134 2.1845E+04 1.6884E-02 7.5878E+22 8.0825E+14 Cs-136 5.6504E+03 7.7095E-05 3.4138E+20 2.0906E+14 Cs-137 1.1815E+04 1.3583E-01 5.9706E+23 4.3714E+14

Numerical Applications Inc. Attachment 3 Page 92 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Cs-134m 3.4108E-02 4.2295E-12 1.9008E+13 1.2620E+09 Rb-88 7.4066E-02 6.1702E-13 4.2225E+12 2.7405E+09 Ba-137m 1.2803E+04 2.3805E-08 1.0464E+17 4.7369E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.5279E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0000 Ci kg Atoms Bq I-131 1.0186E-01 8.2161E-10 3.7770E+15 3.7688E+09 I-132 5.4505E-02 5.2804E-12 2.4091E+13 2.0167E+09 I-133 2.8182E-02 2.4878E-11 1.1265E+14 1.0427E+09 I-135 7.2402E-04 2.0617E-13 9.1967E+11 2.6789E+07 I-130 2.2710E-04 1.1644E-13 5.3939E+11 8.4025E+06 Br-82 1.9764E-04 1.8255E-13 1.3407E+12 7.3126E+06 Br-83 4.9347E-09 3.1237E-19 2.2664E+06 1.8258E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.8410E+15 Organic I (atoms) 1.0755E+15 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 2.1641E+01 2.6596E-07 1.8624E+18 8.0071E+11 I-131 2.6062E+01 2.1022E-07 9.6639E+17 9.6429E+11 I-132 1.3359E+01 1.2942E-09 5.9044E+15 4.9427E+11 I-133 7.2110E+00 6.3656E-09 2.8823E+16 2.6681E+11 I-135 1.8525E-01 5.2751E-11 2.3532E+14 6.8544E+09 Cs-134 2.4272E+03 1.8760E-03 8.4309E+21 8.9806E+13 Cs-136 6.2782E+02 8.5661E-06 3.7931E+19 2.3229E+13 Cs-137 1.3127E+03 1.5092E-02 6.6340E+22 4.8571E+13 I-130 5.8107E-02 2.9793E-11 1.3801E+14 2.1499E+09 Cs-134m 3.7898E-03 4.6995E-13 2.1120E+12 1.4022E+08

Numerical Applications Inc. Attachment 3 Page 93 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Rb-88 8.2296E-03 6.8558E-14 4.6916E+11 3.0449E+08 Ba-137m 1.4225E+03 2.6450E-09 1.1627E+16 5.2633E+13 Br-82 5.0570E-02 4.6710E-11 3.4304E+14 1.8711E+09 Br-83 1.2626E-06 7.9925E-17 5.7990E+08 4.6718E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 7.2672E+17 Organic I (atoms) 2.7511E+17 Aerosols (kg) 1.6977E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 2.2418E-01 5.7140E-07 4.0483E+18 8.2947E+09 Kr-85m 9.1799E-04 1.1155E-13 7.9031E+11 3.3966E+07 Kr-88 2.8134E-05 2.2437E-15 1.5354E+10 1.0410E+06 I-131 1.5425E-02 1.2442E-10 5.7198E+14 5.7073E+08 I-132 9.8591E-03 9.5514E-13 4.3576E+12 3.6479E+08 I-133 4.2676E-03 3.7672E-12 1.7058E+13 1.5790E+08 I-135 1.0964E-04 3.1219E-14 1.3926E+11 4.0565E+06 Xe-133 1.3734E+01 7.3371E-08 3.3222E+17 5.0815E+11 Xe-135 7.6841E-01 3.0090E-10 1.3423E+15 2.8431E+10 I-130 3.4388E-05 1.7632E-14 8.1678E+10 1.2724E+06 Kr-83m 2.4428E-06 1.1840E-16 8.5904E+08 9.0382E+04 Xe-131m 8.8662E-02 1.0585E-09 4.8660E+15 3.2805E+09 Xe-133m 3.5677E-01 7.9510E-10 3.6002E+15 1.3200E+10 Xe-135m 3.2534E-02 3.5715E-13 1.5932E+12 1.2037E+09 Rb-88 1.0259E-05 8.5461E-17 5.8484E+08 3.7957E+05 Br-82 2.9928E-05 2.7643E-14 2.0301E+11 1.1073E+06 Br-83 7.4724E-10 4.7301E-20 3.4319E+05 2.7648E+01 Control Room Transport Group Inventory:

Overlying Time (h) = 2.0000 Atmosphere Sump Pool Noble gases (atoms) 4.3903E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 4.3075E+14 0.0000E+00 0.0000E+00 Organic I (atoms) 1.6307E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 8.5461E-17 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 2.0000 Ci kg Atoms Bq I-131 1.1789E-01 9.5091E-10 4.3714E+15 4.3619E+09 I-132 5.3432E-02 5.1764E-12 2.3616E+13 1.9770E+09 I-133 3.2620E-02 2.8796E-11 1.3038E+14 1.2069E+09 I-135 8.3803E-04 2.3863E-13 1.0645E+12 3.1007E+07 I-130 2.6285E-04 1.3477E-13 6.2433E+11 9.7256E+06 Rb-88 1.1685E-05 9.7345E-17 6.6616E+08 4.3235E+05 Br-82 2.2876E-04 2.1130E-13 1.5518E+12 8.4641E+06 Br-83 5.7117E-09 3.6155E-19 2.6233E+06 2.1133E+02 Deposition Recirculating Time (h) = 2.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 3.2850E+15 Organic I (atoms) 0.0000E+00 1.2436E+15 Aerosols (kg) 0.0000E+00 9.7345E-17 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup

Numerical Applications Inc. Attachment 3 Page 94 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 2.0000 Ci kg Atoms Bq I-131 1.0186E-01 8.2161E-10 3.7770E+15 3.7688E+09 I-132 5.4505E-02 5.2804E-12 2.4091E+13 2.0167E+09 I-133 2.8182E-02 2.4878E-11 1.1265E+14 1.0427E+09 I-135 7.2402E-04 2.0617E-13 9.1967E+11 2.6789E+07 I-130 2.2710E-04 1.1644E-13 5.3939E+11 8.4025E+06 Br-82 1.9764E-04 1.8255E-13 1.3407E+12 7.3126E+06 Br-83 4.9347E-09 3.1237E-19 2.2664E+06 1.8258E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.8410E+15 Organic I (atoms) 1.0755E+15 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq I-131 2.1975E-01 1.7725E-09 8.1483E+15 8.1306E+09 I-132 1.0794E-01 1.0457E-11 4.7706E+13 3.9937E+09 I-133 6.0802E-02 5.3674E-11 2.4303E+14 2.2497E+09 I-135 1.5620E-03 4.4479E-13 1.9842E+12 5.7796E+07 I-130 4.8995E-04 2.5121E-13 1.1637E+12 1.8128E+07 Rb-88 1.1685E-05 9.7345E-17 6.6616E+08 4.3235E+05 Br-82 4.2640E-04 3.9385E-13 2.8925E+12 1.5777E+07 Br-83 1.0646E-08 6.7392E-19 4.8897E+06 3.9392E+02 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 8.7665E-03 2.2345E-08 1.5831E+17 3.2436E+08 Kr-85m 3.5898E-05 4.3621E-15 3.0905E+10 1.3282E+06 Kr-88 1.1002E-06 8.7740E-17 6.0043E+08 4.0707E+04 Rb-86 1.8134E-03 2.2286E-11 1.5606E+14 6.7095E+07 I-131 2.3235E-03 1.8742E-11 8.6157E+13 8.5970E+07 I-132 1.5714E-03 1.5224E-13 6.9454E+11 5.8143E+07 I-133 6.4281E-04 5.6745E-13 2.5694E+12 2.3784E+07 I-135 1.6514E-05 4.7024E-15 2.0977E+10 6.1102E+05 Xe-133 6.8643E-01 3.6672E-09 1.6605E+16 2.5398E+10 Xe-135 7.6366E-02 2.9904E-11 1.3340E+14 2.8255E+09 Cs-134 2.0338E-01 1.5720E-07 7.0646E+17 7.5252E+09 Cs-136 5.2608E-02 7.1779E-10 3.1784E+15 1.9465E+09 Cs-137 1.1000E-01 1.2646E-06 5.5589E+18 4.0700E+09 I-130 5.1798E-06 2.6558E-15 1.2303E+10 1.9165E+05 Kr-83m 1.9535E-06 9.4682E-17 6.8697E+08 7.2279E+04 Xe-131m 6.1866E-03 7.3860E-11 3.3954E+14 2.2890E+08 Xe-133m 2.4646E-02 5.4927E-11 2.4870E+14 9.1190E+08 Xe-135m 3.0276E-01 3.3237E-12 1.4826E+13 1.1202E+10 Cs-134m 3.1757E-07 3.9379E-17 1.7697E+08 1.1750E+04 Rb-88 2.9447E-06 2.4531E-17 1.6787E+08 1.0895E+05 Ba-137m 3.3916E-02 6.3065E-14 2.7721E+11 1.2549E+09

Numerical Applications Inc. Attachment 3 Page 95 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Br-82 4.5079E-06 4.1638E-15 3.0579E+10 1.6679E+05 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 2.0000 Atmosphere Sump Pool Noble gases (atoms) 1.7565E+17 0.0000E+00 0.0000E+00 Elemental I (atoms) 6.4912E+13 0.0000E+00 1.9493E+20 Organic I (atoms) 2.4573E+13 0.0000E+00 0.0000E+00 Aerosols (kg) 1.4226E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 2.1641E+01 2.6596E-07 1.8624E+18 8.0071E+11 I-131 2.6062E+01 2.1022E-07 9.6639E+17 9.6429E+11 I-132 1.3359E+01 1.2942E-09 5.9044E+15 4.9427E+11 I-133 7.2110E+00 6.3656E-09 2.8823E+16 2.6681E+11 I-135 1.8525E-01 5.2751E-11 2.3532E+14 6.8544E+09 Cs-134 2.4272E+03 1.8760E-03 8.4309E+21 8.9806E+13 Cs-136 6.2782E+02 8.5661E-06 3.7931E+19 2.3229E+13 Cs-137 1.3127E+03 1.5092E-02 6.6340E+22 4.8571E+13 I-130 5.8107E-02 2.9793E-11 1.3801E+14 2.1499E+09 Cs-134m 3.7898E-03 4.6995E-13 2.1120E+12 1.4022E+08 Rb-88 8.2296E-03 6.8558E-14 4.6916E+11 3.0449E+08 Ba-137m 1.4225E+03 2.6450E-09 1.1627E+16 5.2633E+13 Br-82 5.0570E-02 4.6710E-11 3.4304E+14 1.8711E+09 Br-83 1.2626E-06 7.9925E-17 5.7990E+08 4.6718E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 7.2672E+17 Organic I (atoms) 2.7511E+17 Aerosols (kg) 1.6977E-02 Detailed model information at time (H) = 2.0020 EAB Doses:

Time (h) = 2.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 4.8388E-04 5.4054E-02 1.2339E-03 2.1407E-03 Accumulated dose (rem) 3.6016E-01 5.4295E+01 1.0407E+00 2.0246E+00 LPZ Doses:

Time (h) = 2.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.7202E-05 3.0387E-03 6.9364E-05 1.2034E-04 Accumulated dose (rem) 4.4469E-02 6.7052E+00 1.2851E-01 2.5002E-01 Control Room Doses:

Time (h) = 2.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.5784E-05 4.3314E-02 2.6870E-03 1.3531E-03 Accumulated dose (rem) 3.5454E-02 1.0518E+02 3.6308E+00 3.2592E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 7.8899E-02 2.0110E-07 1.4248E+18 2.9193E+09 Kr-85m 3.2298E-04 3.9247E-14 2.7806E+11 1.1950E+07 Kr-88 9.8968E-06 7.8927E-16 5.4012E+09 3.6618E+05 Rb-86 1.6320E-02 2.0058E-10 1.4045E+15 6.0385E+08 I-131 2.0912E-02 1.6868E-10 7.7541E+14 7.7373E+08

Numerical Applications Inc. Attachment 3 Page 96 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 I-132 1.4217E-02 1.3774E-12 6.2838E+12 5.2604E+08 I-133 5.7849E-03 5.1067E-12 2.3123E+13 2.1404E+08 I-135 1.4860E-04 4.2313E-14 1.8875E+11 5.4981E+06 Xe-133 4.9623E+00 2.6511E-08 1.2004E+17 1.8361E+11 Xe-135 3.1019E-01 1.2147E-10 5.4184E+14 1.1477E+10 Cs-134 1.8305E+00 1.4148E-06 6.3581E+18 6.7727E+10 Cs-136 4.7347E-01 6.4601E-09 2.8606E+16 1.7518E+10 Cs-137 9.8999E-01 1.1382E-05 5.0030E+19 3.6630E+10 I-130 4.6613E-05 2.3900E-14 1.1071E+11 1.7247E+06 Kr-83m 2.4601E-06 1.1924E-16 8.6513E+08 9.1024E+04 Xe-131m 3.3553E-02 4.0058E-10 1.8415E+15 1.2414E+09 Xe-133m 1.3479E-01 3.0040E-10 1.3602E+15 4.9872E+09 Xe-135m 2.7649E-01 3.0353E-12 1.3540E+13 1.0230E+10 Cs-134m 2.8567E-06 3.5424E-16 1.5920E+09 1.0570E+05 Rb-88 2.7071E-05 2.2552E-16 1.5433E+09 1.0016E+06 Ba-137m 3.0526E-02 5.6762E-14 2.4951E+11 1.1295E+09 Br-82 4.0570E-05 3.7473E-14 2.7520E+11 1.5011E+06 Br-83 1.0124E-09 6.4085E-20 4.6498E+05 3.7459E+01 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 2.0020 Atmosphere Sump Pool Noble gases (atoms) 1.5486E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 5.8423E+14 0.0000E+00 1.7561E+21 Organic I (atoms) 2.2117E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 1.2803E-05 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 1.9496E+02 2.3961E-06 1.6779E+19 7.2136E+12 Cs-134 2.1867E+04 1.6901E-02 7.5954E+22 8.0907E+14 Cs-136 5.6560E+03 7.7172E-05 3.4172E+20 2.0927E+14 Cs-137 1.1826E+04 1.3596E-01 5.9766E+23 4.3758E+14 Cs-134m 3.4126E-02 4.2318E-12 1.9018E+13 1.2627E+09 Rb-88 7.4041E-02 6.1681E-13 4.2211E+12 2.7395E+09 Ba-137m 1.2758E+04 2.3723E-08 1.0428E+17 4.7206E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.5295E-01 Environment Integral Nuclide Release:

Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 1.0517E+03 2.6806E-03 1.8991E+22 3.8912E+13 Kr-85m 4.3051E+00 5.2313E-10 3.7063E+15 1.5929E+11 Kr-88 1.3192E-01 1.0520E-11 7.1995E+13 4.8810E+09 I-131 2.5232E+02 2.0353E-06 9.3563E+18 9.3360E+12 I-132 1.2952E+02 1.2548E-08 5.7246E+16 4.7923E+12 I-133 6.9811E+01 6.1626E-08 2.7904E+17 2.5830E+12 I-135 1.7932E+00 5.1062E-10 2.2778E+15 6.6349E+10 Xe-133 6.4343E+04 3.4375E-04 1.5565E+21 2.3807E+15 Xe-135 3.5762E+03 1.4004E-06 6.2469E+18 1.3232E+14 I-130 5.6251E-01 2.8842E-10 1.3361E+15 2.0813E+10 Kr-83m 1.0448E-02 5.0640E-13 3.6742E+12 3.8658E+08 Xe-131m 4.1442E+02 4.9477E-06 2.2745E+19 1.5334E+13 Xe-133m 1.6677E+03 3.7166E-06 1.6829E+19 6.1704E+13 Xe-135m 5.9335E+01 6.5137E-10 2.9057E+15 2.1954E+12 Rb-88 1.1602E-01 9.6650E-13 6.6141E+12 4.2926E+09

Numerical Applications Inc. Attachment 3 Page 97 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Br-82 4.8958E-01 4.5221E-10 3.3211E+15 1.8115E+10 Br-83 1.2217E-05 7.7337E-16 5.6112E+09 4.5205E+05 Environment Transport Group Inventory:

Present Release Integral Time (h) = 2.0020 Release Rate/s Release Noble gases (atoms) 2.0644E+19 2.8672E+17 2.0594E+22 Elemental I (atoms) 7.0534E+15 9.7964E+13 7.0359E+18 Organic I (atoms) 2.6702E+15 3.7086E+13 2.6636E+18 Aerosols (kg) 5.5673E-18 7.7323E-20 9.6650E-13 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 1.9496E+02 2.3961E-06 1.6779E+19 7.2136E+12 Cs-134 2.1867E+04 1.6901E-02 7.5954E+22 8.0907E+14 Cs-136 5.6560E+03 7.7172E-05 3.4172E+20 2.0927E+14 Cs-137 1.1826E+04 1.3596E-01 5.9766E+23 4.3758E+14 Cs-134m 3.4126E-02 4.2318E-12 1.9018E+13 1.2627E+09 Rb-88 7.4041E-02 6.1681E-13 4.2211E+12 2.7395E+09 Ba-137m 1.2758E+04 2.3723E-08 1.0428E+17 4.7206E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.5295E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0020 Ci kg Atoms Bq I-131 1.0196E-01 8.2243E-10 3.7807E+15 3.7725E+09 I-132 5.4542E-02 5.2840E-12 2.4107E+13 2.0181E+09 I-133 2.8209E-02 2.4902E-11 1.1275E+14 1.0437E+09 I-135 7.2460E-04 2.0633E-13 9.2040E+11 2.6810E+07 I-130 2.2730E-04 1.1654E-13 5.3988E+11 8.4100E+06 Br-82 1.9783E-04 1.8273E-13 1.3420E+12 7.3197E+06 Br-83 4.9368E-09 3.1250E-19 2.2674E+06 1.8266E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.8438E+15 Organic I (atoms) 1.0766E+15 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway

Numerical Applications Inc. Attachment 3 Page 98 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 2.1663E+01 2.6623E-07 1.8643E+18 8.0151E+11 I-131 2.6088E+01 2.1043E-07 9.6735E+17 9.6525E+11 I-132 1.3369E+01 1.2951E-09 5.9087E+15 4.9463E+11 I-133 7.2178E+00 6.3716E-09 2.8850E+16 2.6706E+11 I-135 1.8540E-01 5.2793E-11 2.3550E+14 6.8599E+09 Cs-134 2.4296E+03 1.8779E-03 8.4394E+21 8.9896E+13 Cs-136 6.2845E+02 8.5747E-06 3.7969E+19 2.3253E+13 Cs-137 1.3141E+03 1.5107E-02 6.6407E+22 4.8620E+13 I-130 5.8159E-02 2.9820E-11 1.3814E+14 2.1519E+09 Cs-134m 3.7918E-03 4.7020E-13 2.1131E+12 1.4030E+08 Rb-88 8.2268E-03 6.8535E-14 4.6901E+11 3.0439E+08 Ba-137m 1.4176E+03 2.6359E-09 1.1587E+16 5.2451E+13 Br-82 5.0619E-02 4.6755E-11 3.4337E+14 1.8729E+09 Br-83 1.2632E-06 7.9959E-17 5.8015E+08 4.6737E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 7.2744E+17 Organic I (atoms) 2.7539E+17 Aerosols (kg) 1.6994E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 2.2395E-01 5.7081E-07 4.0441E+18 8.2861E+09 Kr-85m 9.1676E-04 1.1140E-13 7.8925E+11 3.3920E+07 Kr-88 2.8092E-05 2.2403E-15 1.5331E+10 1.0394E+06 I-131 1.5393E-02 1.2416E-10 5.7078E+14 5.6954E+08 I-132 9.8374E-03 9.5304E-13 4.3480E+12 3.6398E+08 I-133 4.2584E-03 3.7591E-12 1.7021E+13 1.5756E+08 I-135 1.0938E-04 3.1147E-14 1.3894E+11 4.0472E+06 Xe-133 1.3721E+01 7.3301E-08 3.3190E+17 5.0766E+11 Xe-135 7.6788E-01 3.0069E-10 1.3413E+15 2.8411E+10 I-130 3.4313E-05 1.7593E-14 8.1499E+10 1.2696E+06 Kr-83m 2.4535E-06 1.1892E-16 8.6280E+08 9.0778E+04 Xe-131m 8.8593E-02 1.0577E-09 4.8622E+15 3.2779E+09 Xe-133m 3.5648E-01 7.9445E-10 3.5972E+15 1.3190E+10 Xe-135m 3.4812E-02 3.8216E-13 1.7047E+12 1.2880E+09 Rb-88 1.0243E-05 8.5332E-17 5.8396E+08 3.7900E+05 Br-82 2.9864E-05 2.7585E-14 2.0258E+11 1.1050E+06 Br-83 7.4525E-10 4.7175E-20 3.4228E+05 2.7574E+01 Control Room Transport Group Inventory:

Overlying Time (h) = 2.0020 Atmosphere Sump Pool Noble gases (atoms) 4.3858E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 4.2985E+14 0.0000E+00 0.0000E+00 Organic I (atoms) 1.6273E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 8.5332E-17 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 2.0020 Ci kg Atoms Bq I-131 1.1796E-01 9.5148E-10 4.3740E+15 4.3645E+09 I-132 5.3445E-02 5.1777E-12 2.3622E+13 1.9775E+09 I-133 3.2638E-02 2.8811E-11 1.3046E+14 1.2076E+09 I-135 8.3836E-04 2.3872E-13 1.0649E+12 3.1019E+07 I-130 2.6299E-04 1.3484E-13 6.2464E+11 9.7305E+06 Rb-88 1.1678E-05 9.7286E-17 6.6576E+08 4.3209E+05 Br-82 2.2889E-04 2.1142E-13 1.5527E+12 8.4689E+06

Numerical Applications Inc. Attachment 3 Page 99 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Br-83 5.7119E-09 3.6156E-19 2.6234E+06 2.1134E+02 Deposition Recirculating Time (h) = 2.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 3.2870E+15 Organic I (atoms) 0.0000E+00 1.2443E+15 Aerosols (kg) 0.0000E+00 9.7286E-17 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0020 Ci kg Atoms Bq I-131 1.0196E-01 8.2243E-10 3.7807E+15 3.7725E+09 I-132 5.4542E-02 5.2840E-12 2.4107E+13 2.0181E+09 I-133 2.8209E-02 2.4902E-11 1.1275E+14 1.0437E+09 I-135 7.2460E-04 2.0633E-13 9.2040E+11 2.6810E+07 I-130 2.2730E-04 1.1654E-13 5.3988E+11 8.4100E+06 Br-82 1.9783E-04 1.8273E-13 1.3420E+12 7.3197E+06 Br-83 4.9368E-09 3.1250E-19 2.2674E+06 1.8266E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.8438E+15 Organic I (atoms) 1.0766E+15 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq I-131 2.1992E-01 1.7739E-09 8.1547E+15 8.1370E+09 I-132 1.0799E-01 1.0462E-11 4.7729E+13 3.9955E+09 I-133 6.0847E-02 5.3713E-11 2.4321E+14 2.2513E+09 I-135 1.5630E-03 4.4505E-13 1.9853E+12 5.7830E+07 I-130 4.9028E-04 2.5138E-13 1.1645E+12 1.8140E+07 Rb-88 1.1678E-05 9.7286E-17 6.6576E+08 4.3209E+05 Br-82 4.2672E-04 3.9415E-13 2.8947E+12 1.5789E+07 Br-83 1.0649E-08 6.7406E-19 4.8907E+06 3.9400E+02 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 8.7665E-03 2.2345E-08 1.5831E+17 3.2436E+08 Kr-85m 3.5887E-05 4.3607E-15 3.0895E+10 1.3278E+06

Numerical Applications Inc. Attachment 3 Page 100 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Kr-88 1.0996E-06 8.7697E-17 6.0014E+08 4.0687E+04 Rb-86 1.8134E-03 2.2286E-11 1.5606E+14 6.7095E+07 I-131 2.3235E-03 1.8742E-11 8.6157E+13 8.5970E+07 I-132 1.5797E-03 1.5304E-13 6.9820E+11 5.8449E+07 I-133 6.4277E-04 5.6741E-13 2.5692E+12 2.3782E+07 I-135 1.6511E-05 4.7014E-15 2.0972E+10 6.1089E+05 Xe-133 5.5137E-01 2.9456E-09 1.3338E+16 2.0401E+10 Xe-135 3.4466E-02 1.3496E-11 6.0204E+13 1.2752E+09 Cs-134 2.0338E-01 1.5720E-07 7.0646E+17 7.5252E+09 Cs-136 5.2607E-02 7.1779E-10 3.1784E+15 1.9465E+09 Cs-137 1.1000E-01 1.2646E-06 5.5589E+18 4.0700E+09 I-130 5.1792E-06 2.6555E-15 1.2302E+10 1.9163E+05 Kr-83m 2.7334E-07 1.3249E-17 9.6126E+07 1.0114E+04 Xe-131m 3.7281E-03 4.4508E-11 2.0461E+14 1.3794E+08 Xe-133m 1.4977E-02 3.3377E-11 1.5113E+14 5.5413E+08 Xe-135m 3.0721E-02 3.3725E-13 1.5044E+12 1.1367E+09 Cs-134m 3.1741E-07 3.9360E-17 1.7689E+08 1.1744E+04 Rb-88 3.0079E-06 2.5058E-17 1.7148E+08 1.1129E+05 Ba-137m 3.3918E-03 6.3068E-15 2.7723E+10 1.2550E+08 Br-82 4.5077E-06 4.1637E-15 3.0578E+10 1.6679E+05 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 2.0020 Atmosphere Sump Pool Noble gases (atoms) 1.7206E+17 0.0000E+00 0.0000E+00 Elemental I (atoms) 6.4914E+13 0.0000E+00 1.9512E+20 Organic I (atoms) 2.4574E+13 0.0000E+00 0.0000E+00 Aerosols (kg) 1.4226E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 2.1663E+01 2.6623E-07 1.8643E+18 8.0151E+11 I-131 2.6088E+01 2.1043E-07 9.6735E+17 9.6525E+11 I-132 1.3369E+01 1.2951E-09 5.9087E+15 4.9463E+11 I-133 7.2178E+00 6.3716E-09 2.8850E+16 2.6706E+11 I-135 1.8540E-01 5.2793E-11 2.3550E+14 6.8599E+09 Cs-134 2.4296E+03 1.8779E-03 8.4394E+21 8.9896E+13 Cs-136 6.2845E+02 8.5747E-06 3.7969E+19 2.3253E+13 Cs-137 1.3141E+03 1.5107E-02 6.6407E+22 4.8620E+13 I-130 5.8159E-02 2.9820E-11 1.3814E+14 2.1519E+09 Cs-134m 3.7918E-03 4.7020E-13 2.1131E+12 1.4030E+08 Rb-88 8.2268E-03 6.8535E-14 4.6901E+11 3.0439E+08 Ba-137m 1.4176E+03 2.6359E-09 1.1587E+16 5.2451E+13 Br-82 5.0619E-02 4.6755E-11 3.4337E+14 1.8729E+09 Br-83 1.2632E-06 7.9959E-17 5.8015E+08 4.6737E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 7.2744E+17 Organic I (atoms) 2.7539E+17 Aerosols (kg) 1.6994E-02 Detailed model information at time (H) = 8.0000 EAB Doses:

Time (h) = 8.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.4587E-02 4.9267E-01 6.0721E-02 4.9688E-02 Accumulated dose (rem) 3.9474E-01 5.4788E+01 1.1014E+00 2.0743E+00 LPZ Doses:

Numerical Applications Inc. Attachment 3 Page 101 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 8.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 1.9443E-03 2.7695E-02 3.4134E-03 2.7932E-03 Accumulated dose (rem) 4.6414E-02 6.7329E+00 1.3192E-01 2.5281E-01 Control Room Doses:

Time (h) = 8.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 6.1446E-03 4.7534E+00 6.0286E-01 1.5178E-01 Accumulated dose (rem) 4.1599E-02 1.0993E+02 4.2337E+00 3.4110E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq Xe-133 1.1170E+00 5.9677E-09 2.7021E+16 4.1331E+10 Xe-135 2.2557E-01 8.8330E-11 3.9403E+14 8.3461E+09 Kr-83m 2.9776E-06 1.4432E-16 1.0471E+09 1.1017E+05 Xe-131m 2.4307E-02 2.9019E-10 1.3340E+15 8.9935E+08 Xe-133m 7.9974E-02 1.7823E-10 8.0702E+14 2.9590E+09 Xe-135m 1.4647E+00 1.6079E-11 7.1726E+13 5.4193E+10 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 8.0000 Atmosphere Sump Pool Noble gases (atoms) 2.9628E+16 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.7172E+21 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 8.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 8.0000 Ci kg Atoms Bq Rb-86 1.9588E+02 2.4073E-06 1.6857E+19 7.2475E+12 Cs-134 2.2169E+04 1.7134E-02 7.7005E+22 8.2026E+14 Cs-136 5.6602E+03 7.7229E-05 3.4198E+20 2.0943E+14 Cs-137 1.1993E+04 1.3787E-01 6.0606E+23 4.4373E+14 Cs-134m 8.2517E-03 1.0232E-12 4.5985E+12 3.0531E+08 Rb-88 6.4466E-08 5.3704E-19 3.6752E+06 2.3852E+03 Ba-137m 1.3294E+04 2.4719E-08 1.0866E+17 4.9188E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.5509E-01 Environment Integral Nuclide Release:

Time (h) = 8.0000 Ci kg Atoms Bq Kr-85 1.0614E+03 2.7054E-03 1.9167E+22 3.9272E+13 Xe-133 6.3291E+04 3.3812E-04 1.5310E+21 2.3418E+15 Xe-135 2.3824E+03 9.3292E-07 4.1616E+18 8.8149E+13 Kr-83m 1.8585E-03 9.0080E-14 6.5359E+11 6.8766E+07 Xe-131m 4.2038E+02 5.0188E-06 2.3072E+19 1.5554E+13 Xe-133m 1.5834E+03 3.5289E-06 1.5979E+19 5.8587E+13 Xe-135m 3.0471E+01 3.3451E-10 1.4922E+15 1.1274E+12 Environment Transport Group Inventory:

Present Release Integral Time (h) = 8.0000 Release Rate/s Release Noble gases (atoms) 3.2938E+16 4.5748E+14 2.0741E+22

Numerical Applications Inc. Attachment 3 Page 102 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 5.0187E+00 6.9704E-02 6.8808E+18 Organic I (atoms) 1.8999E+00 2.6388E-02 2.6048E+18 Aerosols (kg) 4.2723E-25 5.9337E-27 2.9327E-13 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 8.0000 Ci kg Atoms Bq Rb-86 1.9588E+02 2.4073E-06 1.6857E+19 7.2475E+12 Cs-134 2.2169E+04 1.7134E-02 7.7005E+22 8.2026E+14 Cs-136 5.6602E+03 7.7229E-05 3.4198E+20 2.0943E+14 Cs-137 1.1993E+04 1.3787E-01 6.0606E+23 4.4373E+14 Cs-134m 8.2517E-03 1.0232E-12 4.5985E+12 3.0531E+08 Rb-88 6.4466E-08 5.3704E-19 3.6752E+06 2.3852E+03 Ba-137m 1.3294E+04 2.4719E-08 1.0866E+17 4.9188E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.5509E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 8.0000 Ci kg Atoms Bq I-131 1.0119E-01 8.1622E-10 3.7522E+15 3.7440E+09 I-132 9.1074E-03 8.8232E-13 4.0253E+12 3.3698E+08 I-133 2.3423E-02 2.0677E-11 9.3624E+13 8.6666E+08 I-135 3.9175E-04 1.1155E-13 4.9761E+11 1.4495E+07 I-130 1.6466E-04 8.4425E-14 3.9109E+11 6.0923E+06 Br-82 1.7832E-04 1.6471E-13 1.2097E+12 6.5980E+06 Br-83 8.7910E-10 5.5647E-20 4.0375E+05 3.2527E+01 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.7942E+15 Organic I (atoms) 1.0578E+15 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered

Numerical Applications Inc. Attachment 3 Page 103 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 8.0000 Ci kg Atoms Bq Rb-86 2.1764E+01 2.6748E-07 1.8730E+18 8.0528E+11 I-131 2.5891E+01 2.0884E-07 9.6005E+17 9.5796E+11 I-132 2.2340E+00 2.1643E-10 9.8739E+14 8.2658E+10 I-133 5.9932E+00 5.2906E-09 2.3955E+16 2.2175E+11 I-135 1.0024E-01 2.8542E-11 1.2732E+14 3.7087E+09 Cs-134 2.4632E+03 1.9038E-03 8.5561E+21 9.1140E+13 Cs-136 6.2891E+02 8.5810E-06 3.7997E+19 2.3270E+13 Cs-137 1.3325E+03 1.5319E-02 6.7340E+22 4.9303E+13 I-130 4.2131E-02 2.1602E-11 1.0007E+14 1.5588E+09 Cs-134m 9.1685E-04 1.1369E-13 5.1095E+11 3.3924E+07 Rb-88 7.1629E-09 5.9672E-20 4.0835E+05 2.6503E+02 Ba-137m 1.4771E+03 2.7466E-09 1.2073E+16 5.4654E+13 Br-82 4.5627E-02 4.2145E-11 3.0951E+14 1.6882E+09 Br-83 2.2493E-07 1.4238E-17 1.0331E+08 8.3226E+03 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 7.1489E+17 Organic I (atoms) 2.7064E+17 Aerosols (kg) 1.7232E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq Kr-85 6.0355E-08 1.5384E-13 1.0899E+12 2.2331E+03 Xe-133 2.0890E-02 1.1160E-10 5.0533E+14 7.7292E+08 Xe-135 4.6350E-03 1.8150E-12 8.0963E+12 1.7149E+08 Kr-83m 5.3124E-08 2.5748E-18 1.8682E+07 1.9656E+03 Xe-131m 4.4952E-04 5.3667E-12 2.4671E+13 1.6632E+07 Xe-133m 1.4905E-03 3.3217E-12 1.5041E+13 5.5148E+07 Xe-135m 1.2964E-02 1.4231E-13 6.3484E+11 4.7966E+08 Control Room Transport Group Inventory:

Overlying Time (h) = 8.0000 Atmosphere Sump Pool Noble gases (atoms) 5.5486E+14 0.0000E+00 0.0000E+00 Elemental I (atoms) 9.4507E+01 0.0000E+00 0.0000E+00 Organic I (atoms) 3.5777E+01 0.0000E+00 0.0000E+00 Aerosols (kg) 8.0612E-24 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 8.0000 Ci kg Atoms Bq I-131 1.2319E-01 9.9368E-10 4.5680E+15 4.5581E+09 I-132 9.6007E-03 9.3011E-13 4.2434E+12 3.5523E+08 I-133 2.8518E-02 2.5174E-11 1.1399E+14 1.0552E+09 I-135 4.7695E-04 1.3581E-13 6.0583E+11 1.7647E+07 I-130 2.0047E-04 1.0279E-13 4.7615E+11 7.4174E+06 Br-82 2.1711E-04 2.0054E-13 1.4728E+12 8.0330E+06 Br-83 1.0703E-09 6.7750E-20 4.9157E+05 3.9601E+01 Deposition Recirculating Time (h) = 8.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 3.4012E+15 Organic I (atoms) 0.0000E+00 1.2876E+15 Aerosols (kg) 0.0000E+00 5.8426E-22 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup

Numerical Applications Inc. Attachment 3 Page 104 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 8.0000 Ci kg Atoms Bq I-131 1.0119E-01 8.1622E-10 3.7522E+15 3.7440E+09 I-132 9.1074E-03 8.8232E-13 4.0253E+12 3.3698E+08 I-133 2.3423E-02 2.0677E-11 9.3624E+13 8.6666E+08 I-135 3.9175E-04 1.1155E-13 4.9761E+11 1.4495E+07 I-130 1.6466E-04 8.4425E-14 3.9109E+11 6.0923E+06 Br-82 1.7832E-04 1.6471E-13 1.2097E+12 6.5980E+06 Br-83 8.7910E-10 5.5647E-20 4.0375E+05 3.2527E+01 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.7942E+15 Organic I (atoms) 1.0578E+15 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq I-131 2.2438E-01 1.8099E-09 8.3202E+15 8.3021E+09 I-132 1.8708E-02 1.8124E-12 8.2687E+12 6.9220E+08 I-133 5.1941E-02 4.5851E-11 2.0761E+14 1.9218E+09 I-135 8.6870E-04 2.4736E-13 1.1034E+12 3.2142E+07 I-130 3.6513E-04 1.8721E-13 8.6724E+11 1.3510E+07 Br-82 3.9543E-04 3.6525E-13 2.6824E+12 1.4631E+07 Br-83 1.9494E-09 1.2340E-19 8.9532E+05 7.2128E+01 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq Xe-133 1.2412E-01 6.6308E-10 3.0024E+15 4.5923E+09 Xe-135 2.5063E-02 9.8145E-12 4.3781E+13 9.2735E+08 Kr-83m 3.3084E-07 1.6035E-17 1.1635E+08 1.2241E+04 Xe-131m 2.7008E-03 3.2244E-11 1.4823E+14 9.9928E+07 Xe-133m 8.8860E-03 1.9804E-11 8.9669E+13 3.2878E+08 Xe-135m 1.6274E-01 1.7866E-12 7.9696E+12 6.0215E+09 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 8.0000 Atmosphere Sump Pool Noble gases (atoms) 3.2920E+15 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.9080E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 8.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 3 Page 105 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 8.0000 Ci kg Atoms Bq Rb-86 2.1764E+01 2.6748E-07 1.8730E+18 8.0528E+11 I-131 2.5891E+01 2.0884E-07 9.6005E+17 9.5796E+11 I-132 2.2340E+00 2.1643E-10 9.8739E+14 8.2658E+10 I-133 5.9932E+00 5.2906E-09 2.3955E+16 2.2175E+11 I-135 1.0024E-01 2.8542E-11 1.2732E+14 3.7087E+09 Cs-134 2.4632E+03 1.9038E-03 8.5561E+21 9.1140E+13 Cs-136 6.2891E+02 8.5810E-06 3.7997E+19 2.3270E+13 Cs-137 1.3325E+03 1.5319E-02 6.7340E+22 4.9303E+13 I-130 4.2131E-02 2.1602E-11 1.0007E+14 1.5588E+09 Cs-134m 9.1685E-04 1.1369E-13 5.1095E+11 3.3924E+07 Rb-88 7.1629E-09 5.9672E-20 4.0835E+05 2.6503E+02 Ba-137m 1.4771E+03 2.7466E-09 1.2073E+16 5.4654E+13 Br-82 4.5627E-02 4.2145E-11 3.0951E+14 1.6882E+09 Br-83 2.2493E-07 1.4238E-17 1.0331E+08 8.3226E+03 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 7.1489E+17 Organic I (atoms) 2.7064E+17 Aerosols (kg) 1.7232E-02 Detailed model information at time (H) = 24.0000 EAB Doses:

Time (h) = 24.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.0567E-02 1.9395E-16 5.2440E-02 3.0567E-02 Accumulated dose (rem) 4.2531E-01 5.4788E+01 1.1539E+00 2.1048E+00 LPZ Doses:

Time (h) = 24.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 1.1569E-03 7.3406E-18 1.9847E-03 1.1569E-03 Accumulated dose (rem) 4.7570E-02 6.7329E+00 1.3391E-01 2.5397E-01 Control Room Doses:

Time (h) = 24.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 4.6355E-04 9.8024E-13 3.0259E-02 4.6355E-04 Accumulated dose (rem) 4.2063E-02 1.0993E+02 4.2639E+00 3.4115E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 6.5540E-01 3.5014E-09 1.5854E+16 2.4250E+10 Xe-135 4.2133E-02 1.6498E-11 7.3597E+13 1.5589E+09 Kr-83m 2.8748E-08 1.3933E-18 1.0110E+07 1.0637E+03 Xe-131m 2.2949E-02 2.7398E-10 1.2595E+15 8.4912E+08 Xe-133m 4.6923E-02 1.0457E-10 4.7350E+14 1.7361E+09 Xe-135m 2.7357E-01 3.0033E-12 1.3397E+13 1.0122E+10 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 24.0000 Atmosphere Sump Pool Noble gases (atoms) 1.7674E+16 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.6044E+21 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 24.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 3 Page 106 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 1.9109E+02 2.3484E-06 1.6445E+19 7.0702E+12 Cs-134 2.2155E+04 1.7124E-02 7.6957E+22 8.1975E+14 Cs-136 5.4640E+03 7.4553E-05 3.3012E+20 2.0217E+14 Cs-137 1.1992E+04 1.3787E-01 6.0603E+23 4.4371E+14 Cs-134m 1.8017E-04 2.2342E-14 1.0041E+11 6.6664E+06 Ba-137m 1.3294E+04 2.4718E-08 1.0865E+17 4.9186E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.5507E-01 Environment Integral Nuclide Release:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 5.8814E+04 3.1421E-04 1.4227E+21 2.1761E+15 Xe-135 7.6014E+02 2.9766E-07 1.3278E+18 2.8125E+13 Kr-83m 1.8046E-05 8.7465E-16 6.3461E+09 6.6770E+05 Xe-131m 4.2507E+02 5.0748E-06 2.3329E+19 1.5728E+13 Xe-133m 1.3315E+03 2.9674E-06 1.3436E+19 4.9264E+13 Xe-135m 5.6929E+00 6.2496E-11 2.7879E+14 2.1064E+11 Environment Transport Group Inventory:

Present Release Integral Time (h) = 24.0000 Release Rate/s Release Noble gases (atoms) 1.9648E+16 2.7289E+14 2.0626E+22 Elemental I (atoms) 7.2764E-34 1.0106E-35 6.4287E+18 Organic I (atoms) 2.7546E-34 3.8259E-36 2.4337E+18 Aerosols (kg) 2.3822E-44 3.3086E-46 5.9065E-15 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 1.9109E+02 2.3484E-06 1.6445E+19 7.0702E+12 Cs-134 2.2155E+04 1.7124E-02 7.6957E+22 8.1975E+14 Cs-136 5.4640E+03 7.4553E-05 3.3012E+20 2.0217E+14 Cs-137 1.1992E+04 1.3787E-01 6.0603E+23 4.4371E+14 Cs-134m 1.8017E-04 2.2342E-14 1.0041E+11 6.6664E+06 Ba-137m 1.3294E+04 2.4718E-08 1.0865E+17 4.9186E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.5507E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 24.0000 Ci kg Atoms Bq I-131 9.5539E-02 7.7063E-10 3.5426E+15 3.5349E+09 I-132 7.3329E-05 7.1040E-15 3.2410E+10 2.7132E+06 I-133 1.3743E-02 1.2132E-11 5.4932E+13 5.0849E+08

Numerical Applications Inc. Attachment 3 Page 107 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 I-135 7.3171E-05 2.0835E-14 9.2944E+10 2.7073E+06 I-130 6.7127E-05 3.4418E-14 1.5944E+11 2.4837E+06 Br-82 1.3025E-04 1.2030E-13 8.8352E+11 4.8191E+06 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.6105E+15 Organic I (atoms) 9.8824E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 2.1232E+01 2.6094E-07 1.8272E+18 7.8558E+11 I-131 2.4445E+01 1.9718E-07 9.0643E+17 9.0446E+11 I-132 1.7987E-02 1.7426E-12 7.9500E+12 6.6552E+08 I-133 3.5164E+00 3.1042E-09 1.4055E+16 1.3011E+11 I-135 1.8722E-02 5.3311E-12 2.3781E+13 6.9272E+08 Cs-134 2.4617E+03 1.9027E-03 8.5508E+21 9.1084E+13 Cs-136 6.0712E+02 8.2836E-06 3.6680E+19 2.2463E+13 Cs-137 1.3325E+03 1.5319E-02 6.7337E+22 4.9301E+13 I-130 1.7176E-02 8.8065E-12 4.0795E+13 6.3550E+08 Cs-134m 2.0019E-05 2.4824E-15 1.1156E+10 7.4071E+05 Ba-137m 1.4771E+03 2.7465E-09 1.2073E+16 5.4651E+13 Br-82 3.3326E-02 3.0782E-11 2.2607E+14 1.2331E+09 Br-83 2.1717E-09 1.3747E-19 9.9740E+05 8.0352E+01 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 6.6793E+17 Organic I (atoms) 2.5286E+17 Aerosols (kg) 1.7230E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 4.7286E-03 2.5262E-11 1.1439E+14 1.7496E+08 Xe-135 3.3403E-04 1.3080E-13 5.8348E+11 1.2359E+07 Xe-131m 1.6376E-04 1.9551E-12 8.9876E+12 6.0591E+06 Xe-133m 3.3742E-04 7.5199E-13 3.4050E+12 1.2485E+07 Xe-135m 9.3476E-04 1.0262E-14 4.5776E+10 3.4586E+07 Control Room Transport Group Inventory:

Overlying Time (h) = 24.0000 Atmosphere Sump Pool Noble gases (atoms) 1.2741E+14 0.0000E+00 0.0000E+00 Elemental I (atoms) 1.3702E-32 0.0000E+00 0.0000E+00 Organic I (atoms) 5.1873E-33 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 3 Page 108 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Aerosols (kg) 4.4001E-43 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 24.0000 Ci kg Atoms Bq I-131 1.1631E-01 9.3818E-10 4.3129E+15 4.3035E+09 I-132 7.7301E-05 7.4888E-15 3.4166E+10 2.8601E+06 I-133 1.6732E-02 1.4770E-11 6.6880E+13 6.1909E+08 I-135 8.9086E-05 2.5367E-14 1.1316E+11 3.2962E+06 I-130 8.1727E-05 4.1904E-14 1.9412E+11 3.0239E+06 Br-82 1.5857E-04 1.4647E-13 1.0757E+12 5.8672E+06 Deposition Recirculating Time (h) = 24.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 3.1780E+15 Organic I (atoms) 0.0000E+00 1.2031E+15 Aerosols (kg) 0.0000E+00 3.6391E-38 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 24.0000 Ci kg Atoms Bq I-131 9.5539E-02 7.7063E-10 3.5426E+15 3.5349E+09 I-132 7.3329E-05 7.1040E-15 3.2410E+10 2.7132E+06 I-133 1.3743E-02 1.2132E-11 5.4932E+13 5.0849E+08 I-135 7.3171E-05 2.0835E-14 9.2944E+10 2.7073E+06 I-130 6.7127E-05 3.4418E-14 1.5944E+11 2.4837E+06 Br-82 1.3025E-04 1.2030E-13 8.8352E+11 4.8191E+06 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.6105E+15 Organic I (atoms) 9.8824E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq I-131 2.1185E-01 1.7088E-09 7.8555E+15 7.8384E+09 I-132 1.5063E-04 1.4593E-14 6.6576E+10 5.5733E+06 I-133 3.0475E-02 2.6902E-11 1.2181E+14 1.1276E+09 I-135 1.6226E-04 4.6203E-14 2.0610E+11 6.0035E+06 I-130 1.4885E-04 7.6322E-14 3.5356E+11 5.5076E+06

Numerical Applications Inc. Attachment 3 Page 109 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Br-82 2.8882E-04 2.6677E-13 1.9592E+12 1.0686E+07 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 7.2823E-02 3.8905E-10 1.7616E+15 2.6944E+09 Xe-135 4.6814E-03 1.8332E-12 8.1775E+12 1.7321E+08 Kr-83m 3.1942E-09 1.5482E-19 1.1233E+06 1.1818E+02 Xe-131m 2.5499E-03 3.0443E-11 1.3995E+14 9.4347E+07 Xe-133m 5.2137E-03 1.1619E-11 5.2611E+13 1.9291E+08 Xe-135m 3.0397E-02 3.3370E-13 1.4886E+12 1.1247E+09 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 24.0000 Atmosphere Sump Pool Noble gases (atoms) 1.9638E+15 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.7826E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 24.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 2.1232E+01 2.6094E-07 1.8272E+18 7.8558E+11 I-131 2.4445E+01 1.9718E-07 9.0643E+17 9.0446E+11 I-132 1.7987E-02 1.7426E-12 7.9500E+12 6.6552E+08 I-133 3.5164E+00 3.1042E-09 1.4055E+16 1.3011E+11 I-135 1.8722E-02 5.3311E-12 2.3781E+13 6.9272E+08 Cs-134 2.4617E+03 1.9027E-03 8.5508E+21 9.1084E+13 Cs-136 6.0712E+02 8.2836E-06 3.6680E+19 2.2463E+13 Cs-137 1.3325E+03 1.5319E-02 6.7337E+22 4.9301E+13 I-130 1.7176E-02 8.8065E-12 4.0795E+13 6.3550E+08 Cs-134m 2.0019E-05 2.4824E-15 1.1156E+10 7.4071E+05 Ba-137m 1.4771E+03 2.7465E-09 1.2073E+16 5.4651E+13 Br-82 3.3326E-02 3.0782E-11 2.2607E+14 1.2331E+09 Br-83 2.1717E-09 1.3747E-19 9.9740E+05 8.0352E+01 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 6.6793E+17 Organic I (atoms) 2.5286E+17 Aerosols (kg) 1.7230E-02 Detailed model information at time (H) = 96.0000 EAB Doses:

Time (h) = 96.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 9.7779E-03 2.9659E-38 2.2081E-02 9.7779E-03 Accumulated dose (rem) 4.3509E-01 5.4788E+01 1.1759E+00 2.1146E+00 LPZ Doses:

Time (h) = 96.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 1.5728E-04 4.7708E-40 3.5518E-04 1.5728E-04 Accumulated dose (rem) 4.7728E-02 6.7329E+00 1.3426E-01 2.5412E-01 Control Room Doses:

Time (h) = 96.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 7.8127E-05 7.0388E-35 6.9191E-03 7.8127E-05 Accumulated dose (rem) 4.2141E-02 1.0993E+02 4.2709E+00 3.4115E+00

Numerical Applications Inc. Attachment 3 Page 110 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 5.9495E-02 3.1785E-10 1.4392E+15 2.2013E+09 Xe-135 2.2163E-05 8.6786E-15 3.8714E+10 8.2002E+05 Xe-131m 1.7719E-02 2.1154E-10 9.7248E+14 6.5561E+08 Xe-133m 4.2595E-03 9.4929E-12 4.2983E+13 1.5760E+08 Xe-135m 1.4391E-04 1.5798E-15 7.0472E+09 5.3245E+06 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 96.0000 Atmosphere Sump Pool Noble gases (atoms) 2.4547E+15 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.2217E+21 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 96.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 1.7094E+02 2.1008E-06 1.4711E+19 6.3246E+12 Cs-134 2.2094E+04 1.7077E-02 7.6745E+22 8.1749E+14 Cs-136 4.6620E+03 6.3610E-05 2.8167E+20 1.7250E+14 Cs-137 1.1990E+04 1.3784E-01 6.0592E+23 4.4362E+14 Ba-137m 1.3291E+04 2.4714E-08 1.0863E+17 4.9177E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.5499E-01 Environment Integral Nuclide Release:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 4.0614E+04 2.1698E-04 9.8246E+20 1.5027E+15 Xe-135 3.4893E+00 1.3663E-09 6.0951E+15 1.2910E+11 Xe-131m 4.3126E+02 5.1487E-06 2.3669E+19 1.5957E+13 Xe-133m 5.5327E+02 1.2330E-06 5.5831E+18 2.0471E+13 Xe-135m 2.9947E-03 3.2876E-14 1.4665E+11 1.1081E+08 Environment Transport Group Inventory:

Present Release Integral Time (h) = 96.0000 Release Rate/s Release Noble gases (atoms) 2.7284E+15 3.7894E+13 2.0166E+22 Elemental I (atoms) 0.0000E+00 0.0000E+00 4.8955E+18 Organic I (atoms) 0.0000E+00 0.0000E+00 1.8533E+18 Aerosols (kg) 0.0000E+00 0.0000E+00 1.3791E-22 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 1.7094E+02 2.1008E-06 1.4711E+19 6.3246E+12 Cs-134 2.2094E+04 1.7077E-02 7.6745E+22 8.1749E+14 Cs-136 4.6620E+03 6.3610E-05 2.8167E+20 1.7250E+14 Cs-137 1.1990E+04 1.3784E-01 6.0592E+23 4.4362E+14 Ba-137m 1.3291E+04 2.4714E-08 1.0863E+17 4.9177E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Numerical Applications Inc. Attachment 3 Page 111 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.5499E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 96.0000 Ci kg Atoms Bq I-131 7.3766E-02 5.9501E-10 2.7353E+15 2.7293E+09 I-133 1.2475E-03 1.1013E-12 4.9865E+12 4.6159E+07 I-135 3.8490E-08 1.0960E-17 4.8890E+07 1.4241E+03 I-130 1.1839E-06 6.0704E-16 2.8120E+09 4.3805E+04 Br-82 3.1679E-05 2.9261E-14 2.1489E+11 1.1721E+06 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.9879E+15 Organic I (atoms) 7.5256E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 1.8993E+01 2.3342E-07 1.6345E+18 7.0274E+11 I-131 1.8874E+01 1.5224E-07 6.9986E+17 6.9834E+11 I-133 3.1921E-01 2.8178E-10 1.2759E+15 1.1811E+10 I-135 9.8483E-06 2.8043E-15 1.2510E+10 3.6439E+05 Cs-134 2.4549E+03 1.8974E-03 8.5272E+21 9.0833E+13 Cs-136 5.1800E+02 7.0678E-06 3.1296E+19 1.9166E+13 Cs-137 1.3322E+03 1.5316E-02 6.7324E+22 4.9292E+13 I-130 3.0293E-04 1.5532E-13 7.1951E+11 1.1208E+07 Ba-137m 1.4768E+03 2.7460E-09 1.2070E+16 5.4641E+13 Br-82 8.1055E-03 7.4868E-12 5.4984E+13 2.9990E+08 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 5.0863E+17 Organic I (atoms) 1.9255E+17

Numerical Applications Inc. Attachment 3 Page 112 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Aerosols (kg) 1.7221E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 3.2469E-04 1.7346E-12 7.8542E+12 1.2014E+07 Xe-135 1.3291E-07 5.2044E-17 2.3216E+08 4.9175E+03 Xe-131m 9.5641E-05 1.1418E-12 5.2490E+12 3.5387E+06 Xe-133m 2.3169E-05 5.1635E-14 2.3380E+11 8.5726E+05 Xe-135m 3.7203E-07 4.0841E-18 1.8218E+07 1.3765E+04 Control Room Transport Group Inventory:

Overlying Time (h) = 96.0000 Atmosphere Sump Pool Noble gases (atoms) 1.3337E+13 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 96.0000 Ci kg Atoms Bq I-131 8.9804E-02 7.2437E-10 3.3300E+15 3.3227E+09 I-133 1.5189E-03 1.3408E-12 6.0711E+12 5.6199E+07 I-135 4.6861E-08 1.3344E-17 5.9524E+07 1.7339E+03 I-130 1.4414E-06 7.3906E-16 3.4237E+09 5.3333E+04 Br-82 3.8569E-05 3.5625E-14 2.6163E+11 1.4270E+06 Deposition Recirculating Time (h) = 96.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 2.4201E+15 Organic I (atoms) 0.0000E+00 9.1618E+14 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 96.0000 Ci kg Atoms Bq I-131 7.3766E-02 5.9501E-10 2.7353E+15 2.7293E+09 I-133 1.2475E-03 1.1013E-12 4.9865E+12 4.6159E+07 I-135 3.8490E-08 1.0960E-17 4.8890E+07 1.4241E+03 I-130 1.1839E-06 6.0704E-16 2.8120E+09 4.3805E+04 Br-82 3.1679E-05 2.9261E-14 2.1489E+11 1.1721E+06 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.9879E+15 Organic I (atoms) 7.5256E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Numerical Applications Inc. Attachment 3 Page 113 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq I-131 1.6357E-01 1.3194E-09 6.0652E+15 6.0521E+09 I-133 2.7664E-03 2.4421E-12 1.1058E+13 1.0236E+08 I-135 8.5351E-08 2.4304E-17 1.0841E+08 3.1580E+03 I-130 2.6254E-06 1.3461E-15 6.2357E+09 9.7138E+04 Br-82 7.0247E-05 6.4885E-14 4.7652E+11 2.5991E+06 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 6.6106E-03 3.5316E-11 1.5991E+14 2.4459E+08 Xe-135 2.4625E-06 9.6429E-16 4.3015E+09 9.1113E+04 Xe-131m 1.9688E-03 2.3505E-11 1.0805E+14 7.2845E+07 Xe-133m 4.7328E-04 1.0548E-12 4.7759E+12 1.7511E+07 Xe-135m 1.5990E-05 1.7553E-16 7.8302E+08 5.9162E+05 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 96.0000 Atmosphere Sump Pool Noble gases (atoms) 2.7274E+14 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.3575E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 96.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 1.8993E+01 2.3342E-07 1.6345E+18 7.0274E+11 I-131 1.8874E+01 1.5224E-07 6.9986E+17 6.9834E+11 I-133 3.1921E-01 2.8178E-10 1.2759E+15 1.1811E+10 I-135 9.8483E-06 2.8043E-15 1.2510E+10 3.6439E+05 Cs-134 2.4549E+03 1.8974E-03 8.5272E+21 9.0833E+13 Cs-136 5.1800E+02 7.0678E-06 3.1296E+19 1.9166E+13 Cs-137 1.3322E+03 1.5316E-02 6.7324E+22 4.9292E+13 I-130 3.0293E-04 1.5532E-13 7.1951E+11 1.1208E+07 Ba-137m 1.4768E+03 2.7460E-09 1.2070E+16 5.4641E+13 Br-82 8.1055E-03 7.4868E-12 5.4984E+13 2.9990E+08 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 5.0863E+17 Organic I (atoms) 1.9255E+17 Aerosols (kg) 1.7221E-02 Detailed model information at time (H) = 720.0000 EAB Doses:

Time (h) = 720.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 5.2148E-04 6.1596-125 3.4903E-03 5.2148E-04 Accumulated dose (rem) 4.3561E-01 5.4788E+01 1.1794E+00 2.1151E+00

Numerical Applications Inc. Attachment 3 Page 114 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 LPZ Doses:

Time (h) = 720.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.4574E-06 2.9027-127 1.6448E-05 2.4574E-06 Accumulated dose (rem) 4.7730E-02 6.7329E+00 1.3428E-01 2.5413E-01 Control Room Doses:

Time (h) = 720.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.0498E-06 9.7455-122 6.8962E-04 3.0498E-06 Accumulated dose (rem) 4.2144E-02 1.0993E+02 4.2715E+00 3.4115E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-133 5.5409E-11 2.9602E-19 1.3403E+06 2.0501E+00 Xe-131m 1.8835E-03 2.2486E-11 1.0337E+14 6.9689E+07 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 720.0000 Atmosphere Sump Pool Noble gases (atoms) 1.0337E+14 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.2962E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 720.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 720.0000 Ci kg Atoms Bq Rb-86 6.5072E+01 7.9973E-07 5.6001E+18 2.4077E+12 Cs-134 2.1572E+04 1.6673E-02 7.4931E+22 7.9816E+14 Cs-136 1.1779E+03 1.6072E-05 7.1166E+19 4.3583E+13 Cs-137 1.1970E+04 1.3762E-01 6.0492E+23 4.4289E+14 Ba-137m 1.3269E+04 2.4673E-08 1.0846E+17 4.9096E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.5431E-01 Environment Integral Nuclide Release:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-133 1.3242E+03 7.0744E-06 3.2032E+19 4.8995E+13 Xe-131m 1.9138E+02 2.2848E-06 1.0503E+19 7.0811E+12 Environment Transport Group Inventory:

Present Release Integral Time (h) = 720.0000 Release Rate/s Release Noble gases (atoms) 1.1486E+14 1.5953E+12 1.9109E+22 Elemental I (atoms) 0.0000E+00 0.0000E+00 5.1939E+17 Organic I (atoms) 0.0000E+00 0.0000E+00 1.9663E+17 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 720.0000 Ci kg Atoms Bq Rb-86 6.5072E+01 7.9973E-07 5.6001E+18 2.4077E+12 Cs-134 2.1572E+04 1.6673E-02 7.4931E+22 7.9816E+14 Cs-136 1.1779E+03 1.6072E-05 7.1166E+19 4.3583E+13

Numerical Applications Inc. Attachment 3 Page 115 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Cs-137 1.1970E+04 1.3762E-01 6.0492E+23 4.4289E+14 Ba-137m 1.3269E+04 2.4673E-08 1.0846E+17 4.9096E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.5431E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 720.0000 Ci kg Atoms Bq I-131 7.8410E-03 6.3247E-11 2.9075E+14 2.9012E+08 Br-82 1.5116E-10 1.3962E-19 1.0254E+06 5.5930E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.1091E+14 Organic I (atoms) 7.9843E+13 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 720.0000 Ci kg Atoms Bq Rb-86 7.2302E+00 8.8858E-08 6.2223E+17 2.6752E+11 I-131 2.0062E+00 1.6183E-08 7.4392E+16 7.4231E+10 I-133 2.9729E-10 2.6243E-19 1.1883E+06 1.1000E+01 Cs-134 2.3969E+03 1.8526E-03 8.3256E+21 8.8685E+13 Cs-136 1.3088E+02 1.7857E-06 7.9073E+18 4.8425E+12 Cs-137 1.3300E+03 1.5291E-02 6.7214E+22 4.9211E+13 Ba-137m 1.4744E+03 2.7414E-09 1.2051E+16 5.4551E+13 Br-82 3.8678E-08 3.5725E-17 2.6237E+08 1.4311E+03 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 5.3963E+16 Organic I (atoms) 2.0429E+16

Numerical Applications Inc. Attachment 3 Page 116 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Aerosols (kg) 1.7145E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-131m 7.8428E-06 9.3633E-14 4.3044E+11 2.9018E+05 Control Room Transport Group Inventory:

Overlying Time (h) = 720.0000 Atmosphere Sump Pool Noble gases (atoms) 4.3044E+11 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 720.0000 Ci kg Atoms Bq I-131 9.5458E-03 7.6998E-11 3.5396E+14 3.5320E+08 Br-82 1.8404E-10 1.6999E-19 1.2484E+06 6.8094E+00 Deposition Recirculating Time (h) = 720.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 2.5676E+14 Organic I (atoms) 0.0000E+00 9.7202E+13 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 720.0000 Ci kg Atoms Bq I-131 7.8410E-03 6.3247E-11 2.9075E+14 2.9012E+08 Br-82 1.5116E-10 1.3962E-19 1.0254E+06 5.5930E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.1091E+14 Organic I (atoms) 7.9843E+13 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Numerical Applications Inc. Attachment 3 Page 117 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 720.0000 Ci kg Atoms Bq I-131 1.7387E-02 1.4025E-10 6.4471E+14 6.4331E+08 Br-82 3.3520E-10 3.0961E-19 2.2738E+06 1.2402E+01 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-133 6.1566E-12 3.2891E-20 1.4893E+05 2.2779E-01 Xe-131m 2.0928E-04 2.4985E-12 1.1486E+13 7.7432E+06 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 720.0000 Atmosphere Sump Pool Noble gases (atoms) 1.1486E+13 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.4402E+19 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 720.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 720.0000 Ci kg Atoms Bq Rb-86 7.2302E+00 8.8858E-08 6.2223E+17 2.6752E+11 I-131 2.0062E+00 1.6183E-08 7.4392E+16 7.4231E+10 I-133 2.9729E-10 2.6243E-19 1.1883E+06 1.1000E+01 Cs-134 2.3969E+03 1.8526E-03 8.3256E+21 8.8685E+13 Cs-136 1.3088E+02 1.7857E-06 7.9073E+18 4.8425E+12 Cs-137 1.3300E+03 1.5291E-02 6.7214E+22 4.9211E+13 Ba-137m 1.4744E+03 2.7414E-09 1.2051E+16 5.4551E+13 Br-82 3.8678E-08 3.5725E-17 2.6237E+08 1.4311E+03 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 5.3963E+16 Organic I (atoms) 2.0429E+16 Aerosols (kg) 1.7145E-02 Transport Group Totals in Model:

Noble Gases (atoms) 1.9109E+22 Elemental I (atoms) 1.4460E+20 Organic I (atoms) 2.1723E+17 Aerosols (kg) 1.7145E-01 37004 I-131 Summary Fuel Pool-Unfiltered Environment Control Room Time (hr) I-131 (Curies) I-131 (Curies) I-131 (Curies) 0.000 0.0000E+00 0.0000E+00 0.0000E+00 0.001 0.0000E+00 0.0000E+00 0.0000E+00 0.002 0.0000E+00 0.0000E+00 0.0000E+00 0.280 2.1037E-02 3.5183E+01 1.1799E-01 0.333 2.1033E-02 4.1929E+01 1.3676E-01 0.600 2.1013E-02 7.5758E+01 4.8562E-02 0.860 2.0994E-02 1.0864E+02 2.4783E-02 1.120 2.0976E-02 1.4146E+02 1.8068E-02 1.380 2.0957E-02 1.7421E+02 1.6164E-02

Numerical Applications Inc. Attachment 3 Page 118 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 1.640 2.0938E-02 2.0691E+02 1.5617E-02 1.900 2.0919E-02 2.3954E+02 1.5453E-02 2.000 2.0912E-02 2.5207E+02 1.5425E-02 2.002 2.0912E-02 2.5232E+02 1.5393E-02 2.280 0.0000E+00 2.5437E+02 4.2651E-03 2.540 0.0000E+00 2.5413E+02 1.2026E-03 2.800 0.0000E+00 2.5390E+02 3.3909E-04 3.060 0.0000E+00 2.5366E+02 9.5613E-05 3.320 0.0000E+00 2.5342E+02 2.6960E-05 3.580 0.0000E+00 2.5319E+02 7.6017E-06 3.840 0.0000E+00 2.5295E+02 2.1434E-06 4.100 0.0000E+00 2.5271E+02 6.0437E-07 4.360 0.0000E+00 2.5248E+02 1.7041E-07 4.620 0.0000E+00 2.5224E+02 4.8051E-08 4.880 0.0000E+00 2.5201E+02 1.3549E-08 5.140 0.0000E+00 2.5177E+02 3.8203E-09 5.400 0.0000E+00 2.5154E+02 1.0772E-09 5.660 0.0000E+00 2.5130E+02 3.0373E-10 5.920 0.0000E+00 2.5107E+02 8.5642E-11 6.180 0.0000E+00 2.5083E+02 2.4148E-11 6.440 0.0000E+00 2.5060E+02 6.8090E-12 6.700 0.0000E+00 2.5036E+02 1.9199E-12 6.960 0.0000E+00 2.5013E+02 5.4135E-13 7.220 0.0000E+00 2.4990E+02 1.5264E-13 7.480 0.0000E+00 2.4966E+02 4.3040E-14 7.740 0.0000E+00 2.4943E+02 1.2136E-14 8.000 0.0000E+00 2.4920E+02 3.4219E-15 8.260 0.0000E+00 2.4896E+02 9.6486E-16 8.520 0.0000E+00 2.4873E+02 2.7206E-16 8.780 0.0000E+00 2.4850E+02 7.6711E-17 9.040 0.0000E+00 2.4827E+02 2.1630E-17 9.300 0.0000E+00 2.4804E+02 6.0989E-18 9.560 0.0000E+00 2.4780E+02 1.7197E-18 9.820 0.0000E+00 2.4757E+02 4.8489E-19 10.080 0.0000E+00 2.4734E+02 1.3672E-19 24.000 0.0000E+00 2.3528E+02 5.0148E-49 96.000 0.0000E+00 1.8166E+02 2.8003-201 720.000 0.0000E+00 1.9310E+01 0.0000E+00 Fuel Pool-Filtered Time (hr) I-131 (Curies) 0.000 0.0000E+00 0.001 0.0000E+00 0.002 0.0000E+00 0.280 2.3374E-03 0.333 2.3370E-03 0.600 2.3348E-03 0.860 2.3327E-03 1.120 2.3306E-03 1.380 2.3285E-03 1.640 2.3264E-03 1.900 2.3243E-03 2.000 2.3235E-03 2.002 2.3235E-03 2.280 0.0000E+00 2.540 0.0000E+00 2.800 0.0000E+00 3.060 0.0000E+00 3.320 0.0000E+00 3.580 0.0000E+00 3.840 0.0000E+00 4.100 0.0000E+00 4.360 0.0000E+00 4.620 0.0000E+00 4.880 0.0000E+00 5.140 0.0000E+00 5.400 0.0000E+00 5.660 0.0000E+00 5.920 0.0000E+00 6.180 0.0000E+00 6.440 0.0000E+00 6.700 0.0000E+00 6.960 0.0000E+00

Numerical Applications Inc. Attachment 3 Page 119 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 7.220 0.0000E+00 7.480 0.0000E+00 7.740 0.0000E+00 8.000 0.0000E+00 8.260 0.0000E+00 8.520 0.0000E+00 8.780 0.0000E+00 9.040 0.0000E+00 9.300 0.0000E+00 9.560 0.0000E+00 9.820 0.0000E+00 10.080 0.0000E+00 24.000 0.0000E+00 96.000 0.0000E+00 720.000 0.0000E+00 Cumulative Dose Summary EAB LPZ Control Room Time Thyroid TEDE Thyroid TEDE Thyroid TEDE (hr) (rem) (rem) (rem) (rem) (rem) (rem) 0.000 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.001 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.002 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.280 7.5565E+00 2.8162E-01 9.3370E-01 3.4798E-02 2.4280E+01 7.4882E-01 0.333 9.0058E+00 3.3565E-01 1.1128E+00 4.1473E-02 3.3851E+01 1.0440E+00 0.600 1.6276E+01 6.0669E-01 2.0112E+00 7.4963E-02 6.5190E+01 2.0121E+00 0.860 2.3348E+01 8.7038E-01 2.8850E+00 1.0755E-01 7.7725E+01 2.4014E+00 1.120 3.0410E+01 1.1337E+00 3.7575E+00 1.4008E-01 8.5313E+01 2.6383E+00 1.380 3.7461E+01 1.3967E+00 4.6288E+00 1.7258E-01 9.1504E+01 2.8318E+00 1.640 4.4504E+01 1.6593E+00 5.4990E+00 2.0503E-01 9.7295E+01 3.0128E+00 1.900 5.1538E+01 1.9216E+00 6.3681E+00 2.3744E-01 1.0297E+02 3.1901E+00 2.000 5.4241E+01 2.0224E+00 6.7021E+00 2.4990E-01 1.0514E+02 3.2579E+00 2.002 5.4295E+01 2.0246E+00 6.7052E+00 2.5002E-01 1.0518E+02 3.2592E+00 2.280 5.4787E+01 2.0446E+00 6.7328E+00 2.5114E-01 1.0870E+02 3.3698E+00 2.540 5.4787E+01 2.0464E+00 6.7328E+00 2.5124E-01 1.0959E+02 3.3981E+00 2.800 5.4788E+01 2.0481E+00 6.7329E+00 2.5134E-01 1.0984E+02 3.4064E+00 3.060 5.4788E+01 2.0498E+00 6.7329E+00 2.5143E-01 1.0991E+02 3.4089E+00 3.320 5.4788E+01 2.0514E+00 6.7329E+00 2.5152E-01 1.0993E+02 3.4098E+00 3.580 5.4788E+01 2.0530E+00 6.7329E+00 2.5161E-01 1.0993E+02 3.4101E+00 3.840 5.4788E+01 2.0545E+00 6.7329E+00 2.5170E-01 1.0993E+02 3.4102E+00 4.100 5.4788E+01 2.0560E+00 6.7329E+00 2.5178E-01 1.0993E+02 3.4103E+00 4.360 5.4788E+01 2.0575E+00 6.7329E+00 2.5187E-01 1.0993E+02 3.4104E+00 4.620 5.4788E+01 2.0589E+00 6.7329E+00 2.5194E-01 1.0993E+02 3.4104E+00 4.880 5.4788E+01 2.0603E+00 6.7329E+00 2.5202E-01 1.0993E+02 3.4105E+00 5.140 5.4788E+01 2.0616E+00 6.7329E+00 2.5210E-01 1.0993E+02 3.4105E+00 5.400 5.4788E+01 2.0629E+00 6.7329E+00 2.5217E-01 1.0993E+02 3.4106E+00 5.660 5.4788E+01 2.0642E+00 6.7329E+00 2.5224E-01 1.0993E+02 3.4106E+00 5.920 5.4788E+01 2.0654E+00 6.7329E+00 2.5231E-01 1.0993E+02 3.4107E+00 6.180 5.4788E+01 2.0666E+00 6.7329E+00 2.5238E-01 1.0993E+02 3.4107E+00 6.440 5.4788E+01 2.0678E+00 6.7329E+00 2.5245E-01 1.0993E+02 3.4108E+00 6.700 5.4788E+01 2.0690E+00 6.7329E+00 2.5251E-01 1.0993E+02 3.4108E+00 6.960 5.4788E+01 2.0701E+00 6.7329E+00 2.5257E-01 1.0993E+02 3.4108E+00 7.220 5.4788E+01 2.0712E+00 6.7329E+00 2.5264E-01 1.0993E+02 3.4109E+00 7.480 5.4788E+01 2.0722E+00 6.7329E+00 2.5269E-01 1.0993E+02 3.4109E+00 7.740 5.4788E+01 2.0733E+00 6.7329E+00 2.5275E-01 1.0993E+02 3.4110E+00 8.000 5.4788E+01 2.0743E+00 6.7329E+00 2.5281E-01 1.0993E+02 3.4110E+00 8.260 5.4788E+01 2.0752E+00 6.7329E+00 2.5285E-01 1.0993E+02 3.4110E+00 8.520 5.4788E+01 2.0762E+00 6.7329E+00 2.5288E-01 1.0993E+02 3.4110E+00 8.780 5.4788E+01 2.0771E+00 6.7329E+00 2.5292E-01 1.0993E+02 3.4111E+00 9.040 5.4788E+01 2.0780E+00 6.7329E+00 2.5295E-01 1.0993E+02 3.4111E+00 9.300 5.4788E+01 2.0789E+00 6.7329E+00 2.5299E-01 1.0993E+02 3.4111E+00 9.560 5.4788E+01 2.0798E+00 6.7329E+00 2.5302E-01 1.0993E+02 3.4111E+00 9.820 5.4788E+01 2.0806E+00 6.7329E+00 2.5305E-01 1.0993E+02 3.4111E+00 10.080 5.4788E+01 2.0814E+00 6.7329E+00 2.5308E-01 1.0993E+02 3.4111E+00 24.000 5.4788E+01 2.1048E+00 6.7329E+00 2.5397E-01 1.0993E+02 3.4115E+00 96.000 5.4788E+01 2.1146E+00 6.7329E+00 2.5412E-01 1.0993E+02 3.4115E+00 720.000 5.4788E+01 2.1151E+00 6.7329E+00 2.5413E-01 1.0993E+02 3.4115E+00 Worst Two-Hour Dose

Numerical Applications Inc. Attachment 3 Page 120 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 (Provided for Dose Location 1)

EAB Time Whole Body Thyroid Skin TEDE (hr) (rem) (rem) (rem) (rem) 0.0 3.5967E-01 5.4241E+01 1.0395E+00 2.0224E+00 30 Day Control Room Skin Dose Control Room Time Skin (hr) (rem) 720.0 4.2715E+00

Numerical Applications Inc. Attachment 4 Page 121 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Attachment 4 RADTRAD-NAI FHA Output - Case 2 - 34% Filtered RADTRAD-NAI Version 1.1a(QA) run on May 9, 2005 at 06:51:53 File information Plant file name = pal/FHA/db/pal_fha_db_ast_34filter.psf Inventory file name = pal/FHA/db/palisades_fha_db_ast_adj.nif Scenario file name = pal/FHA/db/pal_fha_db_ast_34filter.psf Release file name = pal/FHA/db/pal_fha_ast.rft Dose conversion file name = pal/FHA/db/nai-1101-001rev0.dcf

  • RADTRAD-NAI 1.1a(QA)
  • 09 May 2005 06:51:48
    • Palisades FHA Design Basis
    • 34% release filtration
  • Nuclide inventory file pal/FHA/db/palisades_fha_db_ast_adj.nif
  • Plant power 2703
  • Compartments 4
  • Compartment 1:

Fuel Pool-Unfiltered 3

10000 0

0 0

1

  • Compartment 2:

Environment 2

2e+20 0

0 0

0

  • Compartment 3:

Control Room 1

35923 0

1 0

0

  • Compartment 4:

Fuel Pool-Filtered 3

10000 0

0 0

1

Numerical Applications Inc. Attachment 4 Page 122 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1

  • Pathways 6
  • Pathway 1:

Fuel Pool Release-Unfiltered 1

2 2

  • Pathway 2:

Control Room Unfiltered Makeup 2

3 2

  • Pathway 3:

Control Room Filtered Makeup 2

3 2

  • Pathway 4:

Control Room Unfiltered Inleakage 2

3 2

  • Pathway 5:

Control Room Exhaust 3

2 2

  • Pathway 6:

Fuel Pool Release-Filtered 4

2 2

  • Sources 4

1 0.66 2 0 3 0 4 0.34

  • dose conversion factors filename pal/FHA/db/nai-1101-001rev0.dcf
  • release fraction and timing filename pal/FHA/db/pal_fha_ast.rft 0

1 1

  • Iodine 0 0.9985 0.0015
  • Overlying pool
  • aerosol model 0
  • elemental model 1

2 0 252 720 252

  • organic model 1

2 0 1 720 1

  • pH tracking 0
  • Compartment detail
  • Compartment 1:

1

  • spray model 0

0 0

  • filter model 0
  • deposition model 0

Numerical Applications Inc. Attachment 4 Page 123 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 0

  • Compartment 2:

1

  • spray model 0

0 0

  • filter model 0
  • deposition model 0

0

  • Compartment 3:

1

  • spray model 0

0 0

  • filter model 1

3 0 0 99 99 99 0.3333 1413.6 99 99 99 720 1413.6 99 99 99

  • deposition model 0

0

  • Compartment 4:

1

  • spray model 0

0 0

  • filter model 0
  • deposition model 0

0

  • Pathways:
  • Pathway 1
  • filter efficiency model 1

2 0 1000000 100 0 0 720 1000000 100 0 0

  • Pathway 2
  • filter efficiency model 1

3 0 660 0 0 0 0.3333 0 0 0 0 720 0 0 0 0

  • Pathway 3
  • filter efficiency model 1

3 0 0 99 99 99 0.3333 1413.6 99 99 99 720 1413.6 99 99 99

  • Pathway 4
  • filter efficiency model 1

3 0 0 0 0 0 0.3333 100 0 0 0 720 100 0 0 0

  • Pathway 5
  • filter efficiency model 1

3 0 660 0 0 0 0.3333 1513.6 0 0 0 720 1513.6 0 0 0

Numerical Applications Inc. Attachment 4 Page 124 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1

  • Pathway 6
  • filter efficiency model 1

2 0 1000000 100 94 94 720 1000000 100 94 94

  • x/q tables 6

EAB 2

0 0.000539 720 0.000539 LPZ 6

0 6.66e-05 2 3.03e-05 8 2.04e-05 24 8.67e-06 96 2.54e-06 720 2.54e-06 Equip Hatch-Normal 6

0 0.0125 2 0.00983 8 0.00362 24 0.00286 96 0.00228 720 0.00228 Equip Hatch-Emergency 6

0 0.000732 2 0.000613 8 0.000245 24 0.000175 96 0.000129 720 0.000129 Stack-Normal 6

0 0.0061 2 0.00432 8 0.00173 24 0.00127 96 0.000979 720 0.000979 Stack-Emergency 6

0 0.000832 2 0.000769 8 0.000283 24 0.000215 96 0.000157 720 0.000157

  • dose locations 3
  • location name, compartment number and x/q table EAB 2

1

  • br model 1

4 0 0.00035 8 0.00018 24 0.00023 720 0.00023

  • of model 0
  • location x/q input to be included 0
  • location name, compartment number and x/q table LPZ 2

2

Numerical Applications Inc. Attachment 4 Page 125 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1

  • br model 1

4 0 0.00035 8 0.00018 24 0.00023 720 0.00023

  • of model 0
  • location x/q input to be included 0
  • location name, compartment number and x/q table Control Room 3

0

  • br model 1

2 0 0.00035 720 0.00035

  • of model 1

4 0 1 24 0.6 96 0.4 720 0.4

  • location x/q input to be included 1
  • number of intake combinations 6
  • intake combinations 2 1 3 3 1 4 4 1 3 2 6 5 3 6 6 4 6 5
  • time step count 3

0 1e-06 0.001 0.02 720 0.02

  • show plant, scenario, event, step, model 1

1 1

0 1

RADTRAD-NAI Version 1.1a(QA) run on May 9, 2005 at 06:51:53 Plant Description Number of Nuclides = 107 Inventory Power = 2.7030E+03 MWth Plant Power Level = 2.7030E+03 MWth Number of compartments = 4 Compartment information Compartment number 1 (Source term fraction = 6.6000E-01)

Name: Fuel Pool-Unfiltered Compartment volume = 1.0000E+04 (Cubic feet)

Removal devices within compartment:

Suppression pool Pathways into and out of compartment 1

Numerical Applications Inc. Attachment 4 Page 126 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Pathway to compartment number 2: Fuel Pool Release-Unfiltered Compartment number 2 Name: Environment Pathways into and out of compartment 2 Pathway to compartment number 3: Control Room Unfiltered Makeup Pathway to compartment number 3: Control Room Filtered Makeup Pathway to compartment number 3: Control Room Unfiltered Inleakage Pathway from compartment number 1: Fuel Pool Release-Unfiltered Pathway from compartment number 3: Control Room Exhaust Pathway from compartment number 4: Fuel Pool Release-Filtered Compartment number 3 Name: Control Room Compartment volume = 3.5923E+04 (Cubic feet)

Removal devices within compartment:

Filter(s)

Pathways into and out of compartment 3 Pathway to compartment number 2: Control Room Exhaust Pathway from compartment number 2: Control Room Unfiltered Makeup Pathway from compartment number 2: Control Room Filtered Makeup Pathway from compartment number 2: Control Room Unfiltered Inleakage Compartment number 4 (Source term fraction = 3.4000E-01)

Name: Fuel Pool-Filtered Compartment volume = 1.0000E+04 (Cubic feet)

Removal devices within compartment:

Suppression pool Pathways into and out of compartment 4 Pathway to compartment number 2: Fuel Pool Release-Filtered Total number of pathways = 6 RADTRAD-NAI Version 1.1a(QA) run on May 9, 2005 at 06:51:53 Scenario Description Radioactive Decay is enabled Calculation of Daughters is enabled Iodine fractions Aerosol = 0.0000E+00 Elemental = 9.9850E-01 Organic = 1.5000E-03 Overlying pool characteristics Elemental Removal Data:

Time (hr) DF 0.0000E+00 2.5200E+02 7.2000E+02 2.5200E+02 Organic Removal Data:

Time (hr) DF 0.0000E+00 1.0000E+00 7.2000E+02 1.0000E+00 COMPARTMENT DATA Compartment number 1: Fuel Pool-Unfiltered Compartment number 2: Environment Compartment number 3: Control Room Compartment Filter Data Time (hr) Flow Rate Filter Efficiencies (%)

Numerical Applications Inc. Attachment 4 Page 127 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 (cfm) Aerosol Elemental Organic 0.0000E+00 0.0000E+00 9.9000E+01 9.9000E+01 9.9000E+01 3.3330E-01 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 7.2000E+02 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 Compartment number 4: Fuel Pool-Filtered PATHWAY DATA Pathway number 1: Fuel Pool Release-Unfiltered Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 1.0000E+06 1.0000E+02 0.0000E+00 0.0000E+00 7.2000E+02 1.0000E+06 1.0000E+02 0.0000E+00 0.0000E+00 Pathway number 2: Control Room Unfiltered Makeup Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 6.6000E+02 0.0000E+00 0.0000E+00 0.0000E+00 3.3330E-01 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 3: Control Room Filtered Makeup Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 0.0000E+00 9.9000E+01 9.9000E+01 9.9000E+01 3.3330E-01 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 7.2000E+02 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 Pathway number 4: Control Room Unfiltered Inleakage Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 3.3330E-01 1.0000E+02 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 1.0000E+02 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 5: Control Room Exhaust Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 6.6000E+02 0.0000E+00 0.0000E+00 0.0000E+00 3.3330E-01 1.5136E+03 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 1.5136E+03 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 6: Fuel Pool Release-Filtered Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 1.0000E+06 1.0000E+02 9.4000E+01 9.4000E+01 7.2000E+02 1.0000E+06 1.0000E+02 9.4000E+01 9.4000E+01 X/Q DATA X/Q table 1: EAB Time (hr) X/Q (s

  • m^-3) 0.0000E+00 5.3900E-04 7.2000E+02 5.3900E-04

Numerical Applications Inc. Attachment 4 Page 128 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 X/Q table 2: LPZ Time (hr) X/Q (s

  • m^-3) 0.0000E+00 6.6600E-05 2.0000E+00 3.0300E-05 8.0000E+00 2.0400E-05 2.4000E+01 8.6700E-06 9.6000E+01 2.5400E-06 7.2000E+02 2.5400E-06 X/Q table 3: Equip Hatch-Normal Time (hr) X/Q (s
  • m^-3) 0.0000E+00 1.2500E-02 2.0000E+00 9.8300E-03 8.0000E+00 3.6200E-03 2.4000E+01 2.8600E-03 9.6000E+01 2.2800E-03 7.2000E+02 2.2800E-03 X/Q table 4: Equip Hatch-Emergency Time (hr) X/Q (s
  • m^-3) 0.0000E+00 7.3200E-04 2.0000E+00 6.1300E-04 8.0000E+00 2.4500E-04 2.4000E+01 1.7500E-04 9.6000E+01 1.2900E-04 7.2000E+02 1.2900E-04 X/Q table 5: Stack-Normal Time (hr) X/Q (s
  • m^-3) 0.0000E+00 6.1000E-03 2.0000E+00 4.3200E-03 8.0000E+00 1.7300E-03 2.4000E+01 1.2700E-03 9.6000E+01 9.7900E-04 7.2000E+02 9.7900E-04 X/Q table 6: Stack-Emergency Time (hr) X/Q (s
  • m^-3) 0.0000E+00 8.3200E-04 2.0000E+00 7.6900E-04 8.0000E+00 2.8300E-04 2.4000E+01 2.1500E-04 9.6000E+01 1.5700E-04 7.2000E+02 1.5700E-04 LOCATION DATA Location EAB is in compartment 2 Using X/Q Table 1 Location Breathing Rate Data Time (hr) Breathing Rate (m^3
  • sec^-1) 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 2.3000E-04 Location LPZ is in compartment 2 Using X/Q Table 2 Location Breathing Rate Data Time (hr) Breathing Rate (m^3
  • sec^-1) 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 2.3000E-04 Location Control Room is in compartment 3 Inleakage X/Q Table Assignments

Numerical Applications Inc. Attachment 4 Page 129 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Inleakage Path Source Path X/Q Table 2 1 3 3 1 4 4 1 3 2 6 5 3 6 6 4 6 5 Location Breathing Rate Data Time (hr) Breathing Rate (m^3

  • sec^-1) 0.0000E+00 3.5000E-04 7.2000E+02 3.5000E-04 Location Occupancy Factor Data Time (hr) Occupancy Factor 0.0000E+00 1.0000E+00 2.4000E+01 6.0000E-01 9.6000E+01 4.0000E-01 7.2000E+02 4.0000E-01 USER SPECIFIED TIME STEP DATA - SUPPLEMENTAL TIME STEPS Time Time step 0.0000E+00 1.0000E-06 1.0000E-03 2.0000E-02 7.2000E+02 2.0000E-02 RADTRAD-NAI Version 1.1a(QA) run on May 9, 2005 at 06:51:53 Dose, Detailed Model and Detailed Inventory Output Detailed model information at time (H) = 0.0010 EAB Doses:

Time (h) = 0.0010 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 LPZ Doses:

Time (h) = 0.0010 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Control Room Doses:

Time (h) = 0.0010 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 0.0010 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 130 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0010 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Environment Transport Group Inventory:

Present Release Integral Time (h) = 0.0010 Release Rate/s Release Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 131 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Transport Group Inventory:

Overlying Time (h) = 0.0010 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0010 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 0.0010 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0010 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 132 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 0.0020 EAB Doses:

Time (h) = 0.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 LPZ Doses:

Time (h) = 0.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Control Room Doses:

Time (h) = 0.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 0.0020 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Environment Transport Group Inventory:

Present Release Integral Time (h) = 0.0020 Release Rate/s Release Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 133 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Transport Group Inventory:

Overlying Time (h) = 0.0020 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 134 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 0.0020 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 0.3333 EAB Doses:

Time (h) = 0.3333 Whole Body Thyroid Skin TEDE Delta dose (rem) 5.7387E-02 6.7636E+00 1.6984E-01 2.6474E-01 Accumulated dose (rem) 5.7387E-02 6.7636E+00 1.6984E-01 2.6474E-01 LPZ Doses:

Time (h) = 0.3333 Whole Body Thyroid Skin TEDE Delta dose (rem) 7.0908E-03 8.3572E-01 2.0986E-02 3.2712E-02 Accumulated dose (rem) 7.0908E-03 8.3572E-01 2.0986E-02 3.2712E-02 Control Room Doses:

Time (h) = 0.3333 Whole Body Thyroid Skin TEDE Delta dose (rem) 5.3536E-03 2.5117E+01 5.3245E-01 7.7530E-01 Accumulated dose (rem) 5.3536E-03 2.5117E+01 5.3245E-01 7.7530E-01 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Numerical Applications Inc. Attachment 4 Page 135 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 5.7860E-02 1.4748E-07 1.0448E+18 2.1408E+09 Kr-85m 3.0662E-04 3.7259E-14 2.6397E+11 1.1345E+07 Kr-88 1.0906E-05 8.6977E-16 5.9521E+09 4.0353E+05 Rb-86 1.1999E-02 1.4747E-10 1.0327E+15 4.4397E+08 I-131 1.5424E-02 1.2441E-10 5.7193E+14 5.7069E+08 I-132 1.0535E-02 1.0207E-12 4.6565E+12 3.8981E+08 I-133 4.4848E-03 3.9590E-12 1.7926E+13 1.6594E+08 I-135 1.2981E-04 3.6963E-14 1.6489E+11 4.8029E+06 Xe-133 3.6800E+00 1.9660E-08 8.9019E+16 1.3616E+11 Xe-135 2.6079E-01 1.0212E-10 4.5556E+14 9.6494E+09 Cs-134 1.3424E+00 1.0376E-06 4.6629E+18 4.9670E+10 Cs-136 3.4849E-01 4.7549E-09 2.1055E+16 1.2894E+10 Cs-137 7.2600E-01 8.3466E-06 3.6689E+19 2.6862E+10 I-130 3.7536E-05 1.9246E-14 8.9155E+10 1.3888E+06 Kr-83m 3.1303E-06 1.5172E-16 1.1008E+09 1.1582E+05 Xe-131m 2.4765E-02 2.9566E-10 1.3592E+15 9.1631E+08 Xe-133m 1.0154E-01 2.2629E-10 1.0246E+15 3.7569E+09 Xe-135m 2.6565E-01 2.9163E-12 1.3009E+13 9.8292E+09 Cs-134m 3.1217E-06 3.8709E-16 1.7397E+09 1.1550E+05 Rb-88 2.9090E-05 2.4234E-16 1.6584E+09 1.0763E+06 Ba-137m 1.4886E-01 2.7679E-13 1.2167E+12 5.5078E+09 Br-82 3.0742E-05 2.8396E-14 2.0854E+11 1.1375E+06 Br-83 1.2046E-09 7.6250E-20 5.5324E+05 4.4570E+01 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 0.3333 Atmosphere Sump Pool Noble gases (atoms) 1.1367E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 4.3159E+14 0.0000E+00 2.1526E+20 Organic I (atoms) 1.6339E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 9.3890E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.3333 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 2.3204E+01 2.8518E-07 1.9969E+18 8.5855E+11 Cs-134 2.5960E+03 2.0064E-03 9.0172E+21 9.6051E+13 Cs-136 6.7391E+02 9.1949E-06 4.0716E+19 2.4935E+13 Cs-137 1.4039E+03 1.6141E-02 7.0949E+22 5.1946E+13 Cs-134m 6.0367E-03 7.4856E-13 3.3641E+12 2.2336E+08 Rb-88 4.0069E-02 3.3380E-13 2.2843E+12 1.4826E+09 Ba-137m 1.3238E+03 2.4614E-09 1.0820E+16 4.8979E+13 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.8156E-02 Environment Integral Nuclide Release:

Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 1.7371E+02 4.4275E-04 3.1368E+21 6.4271E+12 Kr-85m 9.2054E-01 1.1186E-10 7.9250E+14 3.4060E+10 Kr-87 1.1339E-08 4.0030E-19 2.7709E+06 4.1953E+02 Kr-88 3.2743E-02 2.6112E-12 1.7869E+13 1.2115E+09 I-131 3.1490E+01 2.5400E-07 1.1677E+18 1.1651E+12 I-132 2.0518E+01 1.9877E-09 9.0685E+15 7.5916E+11 I-133 9.1564E+00 8.0829E-09 3.6599E+16 3.3879E+11 I-135 2.6502E-01 7.5465E-11 3.3664E+14 9.8058E+09

Numerical Applications Inc. Attachment 4 Page 136 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Xe-133 1.0701E+04 5.7171E-05 2.5887E+20 3.9595E+14 Xe-135 6.6185E+02 2.5917E-07 1.1561E+18 2.4489E+13 I-130 7.6635E-02 3.9293E-11 1.8202E+14 2.8355E+09 Kr-83m 2.7914E-03 1.3529E-13 9.8164E+11 1.0328E+08 Xe-131m 6.8345E+01 8.1595E-07 3.7510E+18 2.5288E+12 Xe-133m 2.8002E+02 6.2407E-07 2.8257E+18 1.0361E+13 Xe-135m 1.1210E+01 1.2306E-10 5.4897E+14 4.1478E+11 Rb-88 1.0967E-02 9.1361E-14 6.2522E+11 4.0577E+08 Br-82 6.2764E-02 5.7973E-11 4.2576E+14 2.3223E+09 Br-83 2.4593E-06 1.5567E-16 1.1295E+09 9.0995E+04 Environment Transport Group Inventory:

Present Release Integral Time (h) = 0.3333 Release Rate/s Release Noble gases (atoms) 1.3677E+20 1.8995E+18 3.4034E+21 Elemental I (atoms) 3.5410E+16 4.9181E+14 8.8082E+17 Organic I (atoms) 1.3405E+16 1.8618E+14 3.3345E+17 Aerosols (kg) 3.4427E-16 4.7816E-18 9.1361E-14 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 2.3204E+01 2.8518E-07 1.9969E+18 8.5855E+11 Cs-134 2.5960E+03 2.0064E-03 9.0172E+21 9.6051E+13 Cs-136 6.7391E+02 9.1949E-06 4.0716E+19 2.4935E+13 Cs-137 1.4039E+03 1.6141E-02 7.0949E+22 5.1946E+13 Cs-134m 6.0367E-03 7.4856E-13 3.3641E+12 2.2336E+08 Rb-88 4.0069E-02 3.3380E-13 2.2843E+12 1.4826E+09 Ba-137m 1.3238E+03 2.4614E-09 1.0820E+16 4.8979E+13 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.8156E-02 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 137 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 1.1954E+01 1.4691E-07 1.0287E+18 4.4228E+11 I-131 1.4443E+01 1.1650E-07 5.3556E+17 5.3440E+11 I-132 9.3963E+00 9.1031E-10 4.1530E+15 3.4766E+11 I-133 4.1997E+00 3.7074E-09 1.6787E+16 1.5539E+11 I-135 1.2156E-01 3.4613E-11 1.5440E+14 4.4976E+09 Cs-134 1.3373E+03 1.0336E-03 4.6452E+21 4.9481E+13 Cs-136 3.4716E+02 4.7368E-06 2.0975E+19 1.2845E+13 Cs-137 7.2324E+02 8.3148E-03 3.6550E+22 2.6760E+13 I-130 3.5150E-02 1.8022E-11 8.3487E+13 1.3005E+09 Cs-134m 3.1098E-03 3.8562E-13 1.7330E+12 1.1506E+08 Rb-88 2.0642E-02 1.7196E-13 1.1768E+12 7.6374E+08 Ba-137m 6.8193E+02 1.2680E-09 5.5738E+15 2.5232E+13 Br-82 2.8788E-02 2.6590E-11 1.9528E+14 1.0651E+09 Br-83 1.1280E-06 7.1403E-17 5.1807E+08 4.1736E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 4.0400E+17 Organic I (atoms) 1.5294E+17 Aerosols (kg) 9.3533E-03 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 4.6926E-01 1.1961E-06 8.4741E+18 1.7363E+10 Kr-85m 2.4868E-03 3.0218E-13 2.1409E+12 9.2012E+07 Kr-88 8.8453E-05 7.0541E-15 4.8274E+10 3.2728E+06 I-131 1.0147E-01 8.1847E-10 3.7626E+15 3.7544E+09 I-132 6.6310E-02 6.4241E-12 2.9308E+13 2.4535E+09 I-133 2.9505E-02 2.6046E-11 1.1793E+14 1.0917E+09 I-135 8.5399E-04 2.4317E-13 1.0848E+12 3.1598E+07 Xe-133 2.8910E+01 1.5445E-07 6.9934E+17 1.0697E+12 Xe-135 1.7882E+00 7.0025E-10 3.1237E+15 6.6165E+10 I-130 2.4694E-04 1.2662E-13 5.8653E+11 9.1369E+06 Kr-83m 7.5540E-06 3.6613E-16 2.6565E+09 2.7950E+05 Xe-131m 1.8464E-01 2.2044E-09 1.0134E+16 6.8318E+09 Xe-133m 7.5652E-01 1.6860E-09 7.6341E+15 2.7991E+10 Xe-135m 3.1567E-02 3.4654E-13 1.5458E+12 1.1680E+09 Rb-88 2.8128E-05 2.3432E-16 1.6035E+09 1.0407E+06 Br-82 2.0225E-04 1.8681E-13 1.3719E+12 7.4831E+06 Br-83 7.9247E-09 5.0163E-19 3.6397E+06 2.9321E+02 Control Room Transport Group Inventory:

Overlying Time (h) = 0.3333 Atmosphere Sump Pool Noble gases (atoms) 9.1943E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 2.8383E+15 0.0000E+00 0.0000E+00 Organic I (atoms) 1.0745E+15 0.0000E+00 0.0000E+00 Aerosols (kg) 2.3432E-16 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.3333 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 138 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 2.9807E-02 7.5972E-08 5.3825E+17 1.1028E+09 Kr-85m 1.5796E-04 1.9194E-14 1.3599E+11 5.8444E+06 Kr-88 5.6184E-06 4.4806E-16 3.0662E+09 2.0788E+05 Rb-86 6.1814E-03 7.5969E-11 5.3197E+14 2.2871E+08 I-131 7.9457E-03 6.4092E-11 2.9463E+14 2.9399E+08 I-132 5.4274E-03 5.2580E-13 2.3988E+12 2.0081E+08 I-133 2.3104E-03 2.0395E-12 9.2347E+12 8.5484E+07 I-135 6.6871E-05 1.9042E-14 8.4941E+10 2.4742E+06 Xe-133 1.8958E+00 1.0128E-08 4.5858E+16 7.0143E+10 Xe-135 1.3435E-01 5.2609E-11 2.3468E+14 4.9709E+09 Cs-134 6.9155E-01 5.3450E-07 2.4021E+18 2.5587E+10 Cs-136 1.7952E-01 2.4495E-09 1.0846E+16 6.6424E+09 Cs-137 3.7400E-01 4.2997E-06 1.8900E+19 1.3838E+10 I-130 1.9337E-05 9.9146E-15 4.5928E+10 7.1546E+05 Kr-83m 1.6126E-06 7.8158E-17 5.6708E+08 5.9665E+04 Xe-131m 1.2758E-02 1.5231E-10 7.0018E+14 4.7204E+08 Xe-133m 5.2308E-02 1.1657E-10 5.2784E+14 1.9354E+09 Xe-135m 1.3685E-01 1.5023E-12 6.7017E+12 5.0635E+09 Cs-134m 1.6081E-06 1.9941E-16 8.9618E+08 5.9501E+04 Rb-88 1.4986E-05 1.2484E-16 8.5434E+08 5.5448E+05 Ba-137m 7.6685E-02 1.4259E-13 6.2678E+11 2.8373E+09 Br-82 1.5837E-05 1.4628E-14 1.0743E+11 5.8596E+05 Br-83 6.2054E-10 3.9280E-20 2.8500E+05 2.2960E+01 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 0.3333 Atmosphere Sump Pool Noble gases (atoms) 5.8558E+17 0.0000E+00 0.0000E+00 Elemental I (atoms) 2.2234E+14 0.0000E+00 1.1089E+20 Organic I (atoms) 8.4169E+13 0.0000E+00 0.0000E+00 Aerosols (kg) 4.8368E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.3333 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 139 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 1.1954E+01 1.4691E-07 1.0287E+18 4.4228E+11 I-131 1.4443E+01 1.1650E-07 5.3556E+17 5.3440E+11 I-132 9.3963E+00 9.1031E-10 4.1530E+15 3.4766E+11 I-133 4.1997E+00 3.7074E-09 1.6787E+16 1.5539E+11 I-135 1.2156E-01 3.4613E-11 1.5440E+14 4.4976E+09 Cs-134 1.3373E+03 1.0336E-03 4.6452E+21 4.9481E+13 Cs-136 3.4716E+02 4.7368E-06 2.0975E+19 1.2845E+13 Cs-137 7.2324E+02 8.3148E-03 3.6550E+22 2.6760E+13 I-130 3.5150E-02 1.8022E-11 8.3487E+13 1.3005E+09 Cs-134m 3.1098E-03 3.8562E-13 1.7330E+12 1.1506E+08 Rb-88 2.0642E-02 1.7196E-13 1.1768E+12 7.6374E+08 Ba-137m 6.8193E+02 1.2680E-09 5.5738E+15 2.5232E+13 Br-82 2.8788E-02 2.6590E-11 1.9528E+14 1.0651E+09 Br-83 1.1280E-06 7.1403E-17 5.1807E+08 4.1736E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 4.0400E+17 Organic I (atoms) 1.5294E+17 Aerosols (kg) 9.3533E-03 Detailed model information at time (H) = 2.0000 EAB Doses:

Time (h) = 2.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.8919E-01 3.3971E+01 8.5005E-01 1.3306E+00 Accumulated dose (rem) 3.4658E-01 4.0735E+01 1.0199E+00 1.5953E+00 LPZ Doses:

Time (h) = 2.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.5733E-02 4.1976E+00 1.0503E-01 1.6441E-01 Accumulated dose (rem) 4.2824E-02 5.0333E+00 1.2602E-01 1.9712E-01 Control Room Doses:

Time (h) = 2.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.6298E-02 5.2896E+01 2.7332E+00 1.6474E+00 Accumulated dose (rem) 3.1652E-02 7.8013E+01 3.2656E+00 2.4227E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 5.7859E-02 1.4747E-07 1.0448E+18 2.1408E+09 Kr-85m 2.3693E-04 2.8790E-14 2.0397E+11 8.7663E+06 Kr-88 7.2612E-06 5.7908E-16 3.9628E+09 2.6867E+05 Rb-86 1.1968E-02 1.4709E-10 1.0300E+15 4.4283E+08 I-131 1.5335E-02 1.2370E-10 5.6864E+14 5.6740E+08 I-132 1.0371E-02 1.0048E-12 4.5840E+12 3.8374E+08 I-133 4.2425E-03 3.7452E-12 1.6958E+13 1.5697E+08 I-135 1.0899E-04 3.1036E-14 1.3845E+11 4.0328E+06 Xe-133 4.5304E+00 2.4203E-08 1.0959E+17 1.6763E+11 Xe-135 5.0402E-01 1.9736E-10 8.8041E+14 1.8649E+10 Cs-134 1.3423E+00 1.0375E-06 4.6626E+18 4.9666E+10 Cs-136 3.4721E-01 4.7374E-09 2.0977E+16 1.2847E+10 Cs-137 7.2600E-01 8.3465E-06 3.6689E+19 2.6862E+10 I-130 3.4187E-05 1.7529E-14 8.1200E+10 1.2649E+06 Kr-83m 1.2893E-05 6.2490E-16 4.5340E+09 4.7704E+05 Xe-131m 4.0832E-02 4.8748E-10 2.2410E+15 1.5108E+09 Xe-133m 1.6266E-01 3.6252E-10 1.6414E+15 6.0185E+09 Xe-135m 1.9982E+00 2.1936E-11 9.7854E+13 7.3934E+10 Cs-134m 2.0959E-06 2.5990E-16 1.1680E+09 7.7549E+04 Rb-88 1.9435E-05 1.6190E-16 1.1080E+09 7.1909E+05 Ba-137m 2.2385E-01 4.1623E-13 1.8296E+12 8.2823E+09 Br-82 2.9752E-05 2.7481E-14 2.0182E+11 1.1008E+06 Br-83 7.4286E-10 4.7023E-20 3.4118E+05 2.7486E+01

Numerical Applications Inc. Attachment 4 Page 140 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 2.0000 Atmosphere Sump Pool Noble gases (atoms) 1.1593E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 4.2842E+14 0.0000E+00 1.2865E+21 Organic I (atoms) 1.6218E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 9.3889E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 1.4283E+02 1.7554E-06 1.2292E+19 5.2847E+12 Cs-134 1.6019E+04 1.2381E-02 5.5644E+22 5.9272E+14 Cs-136 4.1436E+03 5.6536E-05 2.5035E+20 1.5331E+14 Cs-137 8.6640E+03 9.9607E-02 4.3785E+23 3.2057E+14 Cs-134m 2.5013E-02 3.1017E-12 1.3939E+13 9.2547E+08 Rb-88 5.4315E-02 4.5248E-13 3.0965E+12 2.0097E+09 Ba-137m 9.3885E+03 1.7457E-08 7.6737E+16 3.4738E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.1205E-01 Environment Integral Nuclide Release:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 1.0506E+03 2.6779E-03 1.8973E+22 3.8873E+13 Kr-85m 4.3022E+00 5.2278E-10 3.7038E+15 1.5918E+11 Kr-88 1.3185E-01 1.0515E-11 7.1959E+13 4.8786E+09 I-131 1.8931E+02 1.5270E-06 7.0196E+18 7.0043E+12 I-132 9.7200E+01 9.4166E-09 4.2961E+16 3.5964E+12 I-133 5.2379E+01 4.6238E-08 2.0936E+17 1.9380E+12 I-135 1.3456E+00 3.8317E-10 1.7093E+15 4.9789E+10 Xe-133 6.4279E+04 3.4340E-04 1.5549E+21 2.3783E+15 Xe-135 3.5727E+03 1.3990E-06 6.2408E+18 1.3219E+14 I-130 4.2207E-01 2.1641E-10 1.0025E+15 1.5617E+10 Kr-83m 1.0427E-02 5.0538E-13 3.6668E+12 3.8580E+08 Xe-131m 4.1399E+02 4.9425E-06 2.2721E+19 1.5318E+13 Xe-133m 1.6660E+03 3.7128E-06 1.6811E+19 6.1640E+13 Xe-135m 5.6579E+01 6.2111E-10 2.7707E+15 2.0934E+12 Rb-88 1.1594E-01 9.6588E-13 6.6098E+12 4.2899E+09 Br-82 3.6732E-01 3.3929E-10 2.4917E+15 1.3591E+10 Br-83 9.1714E-06 5.8055E-16 4.2122E+09 3.3934E+05 Environment Transport Group Inventory:

Present Release Integral Time (h) = 2.0000 Release Rate/s Release Noble gases (atoms) 2.0604E+20 2.8617E+18 2.0573E+22 Elemental I (atoms) 5.2958E+16 7.3553E+14 5.2787E+18 Organic I (atoms) 2.0048E+16 2.7845E+14 1.9984E+18 Aerosols (kg) 5.1893E-16 7.2074E-18 9.6588E-13 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 1.4283E+02 1.7554E-06 1.2292E+19 5.2847E+12 Cs-134 1.6019E+04 1.2381E-02 5.5644E+22 5.9272E+14 Cs-136 4.1436E+03 5.6536E-05 2.5035E+20 1.5331E+14

Numerical Applications Inc. Attachment 4 Page 141 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Cs-137 8.6640E+03 9.9607E-02 4.3785E+23 3.2057E+14 Cs-134m 2.5013E-02 3.1017E-12 1.3939E+13 9.2547E+08 Rb-88 5.4315E-02 4.5248E-13 3.0965E+12 2.0097E+09 Ba-137m 9.3885E+03 1.7457E-08 7.6737E+16 3.4738E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.1205E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0000 Ci kg Atoms Bq I-131 7.6739E-02 6.1899E-10 2.8455E+15 2.8393E+09 I-132 4.1064E-02 3.9782E-12 1.8150E+13 1.5194E+09 I-133 2.1232E-02 1.8743E-11 8.4867E+13 7.8560E+08 I-135 5.4547E-04 1.5532E-13 6.9287E+11 2.0182E+07 I-130 1.7109E-04 8.7724E-14 4.0637E+11 6.3304E+06 Br-82 1.4890E-04 1.3753E-13 1.0101E+12 5.5093E+06 Br-83 3.7177E-09 2.3533E-19 1.7075E+06 1.3756E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.1404E+15 Organic I (atoms) 8.1028E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 7.3579E+01 9.0428E-07 6.3322E+18 2.7224E+12 I-131 8.8610E+01 7.1475E-07 3.2857E+18 3.2786E+12 I-132 4.5420E+01 4.4002E-09 2.0075E+16 1.6805E+12 I-133 2.4517E+01 2.1643E-08 9.7998E+16 9.0715E+11 I-135 6.2987E-01 1.7935E-10 8.0007E+14 2.3305E+10 Cs-134 8.2524E+03 6.3783E-03 2.8665E+22 3.0534E+14 Cs-136 2.1346E+03 2.9125E-05 1.2897E+20 7.8980E+13 Cs-137 4.4633E+03 5.1313E-02 2.2556E+23 1.6514E+14 I-130 1.9756E-01 1.0130E-10 4.6925E+14 7.3098E+09

Numerical Applications Inc. Attachment 4 Page 142 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Cs-134m 1.2885E-02 1.5978E-12 7.1808E+12 4.7676E+08 Rb-88 2.7981E-02 2.3310E-13 1.5952E+12 1.0353E+09 Ba-137m 4.8365E+03 8.9931E-09 3.9531E+16 1.7895E+14 Br-82 1.7194E-01 1.5881E-10 1.1663E+15 6.3617E+09 Br-83 4.2930E-06 2.7175E-16 1.9717E+09 1.5884E+05 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.4708E+18 Organic I (atoms) 9.3538E+17 Aerosols (kg) 5.7721E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 2.1157E-01 5.3926E-07 3.8206E+18 7.8281E+09 Kr-85m 8.6635E-04 1.0527E-13 7.4585E+11 3.2055E+07 Kr-88 2.6552E-05 2.1175E-15 1.4491E+10 9.8241E+05 I-131 1.1447E-02 9.2331E-11 4.2445E+14 4.2353E+08 I-132 7.3162E-03 7.0879E-13 3.2336E+12 2.7070E+08 I-133 3.1668E-03 2.7956E-12 1.2658E+13 1.1717E+08 I-135 8.1358E-05 2.3167E-14 1.0334E+11 3.0102E+06 Xe-133 1.2961E+01 6.9244E-08 3.1353E+17 4.7957E+11 Xe-135 7.2523E-01 2.8399E-10 1.2668E+15 2.6833E+10 I-130 2.5519E-05 1.3084E-14 6.0611E+10 9.4419E+05 Kr-83m 2.3068E-06 1.1181E-16 8.1122E+08 8.5352E+04 Xe-131m 8.3677E-02 9.9900E-10 4.5925E+15 3.0961E+09 Xe-133m 3.3671E-01 7.5040E-10 3.3977E+15 1.2458E+10 Xe-135m 3.0794E-02 3.3806E-13 1.5080E+12 1.1394E+09 Rb-88 9.6672E-06 8.0535E-17 5.5112E+08 3.5769E+05 Br-82 2.2209E-05 2.0513E-14 1.5065E+11 8.2172E+05 Br-83 5.5451E-10 3.5101E-20 2.5467E+05 2.0517E+01 Control Room Transport Group Inventory:

Overlying Time (h) = 2.0000 Atmosphere Sump Pool Noble gases (atoms) 4.1434E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 3.1965E+14 0.0000E+00 0.0000E+00 Organic I (atoms) 1.2101E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 8.0535E-17 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 2.0000 Ci kg Atoms Bq I-131 8.7476E-02 7.0559E-10 3.2437E+15 3.2366E+09 I-132 3.9648E-02 3.8410E-12 1.7524E+13 1.4670E+09 I-133 2.4205E-02 2.1367E-11 9.6748E+13 8.9558E+08 I-135 6.2184E-04 1.7707E-13 7.8987E+11 2.3008E+07 I-130 1.9504E-04 1.0001E-13 4.6326E+11 7.2166E+06 Rb-88 1.0847E-05 9.0361E-17 6.1837E+08 4.0133E+05 Br-82 1.6974E-04 1.5679E-13 1.1515E+12 6.2805E+06 Br-83 4.2382E-09 2.6828E-19 1.9465E+06 1.5681E+02 Deposition Recirculating Time (h) = 2.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 2.4376E+15 Organic I (atoms) 0.0000E+00 9.2278E+14 Aerosols (kg) 0.0000E+00 9.0361E-17 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 143 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0000 Ci kg Atoms Bq I-131 7.6739E-02 6.1899E-10 2.8455E+15 2.8393E+09 I-132 4.1064E-02 3.9782E-12 1.8150E+13 1.5194E+09 I-133 2.1232E-02 1.8743E-11 8.4867E+13 7.8560E+08 I-135 5.4547E-04 1.5532E-13 6.9287E+11 2.0182E+07 I-130 1.7109E-04 8.7724E-14 4.0637E+11 6.3304E+06 Br-82 1.4890E-04 1.3753E-13 1.0101E+12 5.5093E+06 Br-83 3.7177E-09 2.3533E-19 1.7075E+06 1.3756E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.1404E+15 Organic I (atoms) 8.1028E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq I-131 1.6421E-01 1.3246E-09 6.0892E+15 6.0759E+09 I-132 8.0712E-02 7.8193E-12 3.5673E+13 2.9863E+09 I-133 4.5437E-02 4.0110E-11 1.8162E+14 1.6812E+09 I-135 1.1673E-03 3.3239E-13 1.4827E+12 4.3190E+07 I-130 3.6613E-04 1.8773E-13 8.6964E+11 1.3547E+07 Rb-88 1.0847E-05 9.0361E-17 6.1837E+08 4.0133E+05 Br-82 3.1864E-04 2.9432E-13 2.1615E+12 1.1790E+07 Br-83 7.9560E-09 5.0361E-19 3.6540E+06 2.9437E+02 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 2.9806E-02 7.5971E-08 5.3825E+17 1.1028E+09 Kr-85m 1.2205E-04 1.4831E-14 1.0508E+11 4.5159E+06 Kr-88 3.7406E-06 2.9831E-16 2.0415E+09 1.3840E+05 Rb-86 6.1655E-03 7.5773E-11 5.3060E+14 2.2812E+08 I-131 7.9000E-03 6.3722E-11 2.9294E+14 2.9230E+08 I-132 5.3428E-03 5.1761E-13 2.3614E+12 1.9768E+08 I-133 2.1856E-03 1.9293E-12 8.7358E+12 8.0865E+07 I-135 5.6148E-05 1.5988E-14 7.1321E+10 2.0775E+06 Xe-133 2.3339E+00 1.2468E-08 5.6456E+16 8.6353E+10 Xe-135 2.5964E-01 1.0167E-10 4.5355E+14 9.6068E+09 Cs-134 6.9151E-01 5.3447E-07 2.4020E+18 2.5586E+10 Cs-136 1.7887E-01 2.4405E-09 1.0807E+16 6.6180E+09 Cs-137 3.7400E-01 4.2997E-06 1.8900E+19 1.3838E+10 I-130 1.7611E-05 9.0299E-15 4.1830E+10 6.5162E+05 Kr-83m 6.6418E-06 3.2192E-16 2.3357E+09 2.4575E+05 Xe-131m 2.1034E-02 2.5112E-10 1.1544E+15 7.7827E+08 Xe-133m 8.3796E-02 1.8675E-10 8.4559E+14 3.1005E+09 Xe-135m 1.0294E+00 1.1301E-11 5.0410E+13 3.8087E+10 Cs-134m 1.0797E-06 1.3389E-16 6.0171E+08 3.9950E+04 Rb-88 1.0012E-05 8.3406E-17 5.7077E+08 3.7044E+05

Numerical Applications Inc. Attachment 4 Page 144 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Ba-137m 1.1532E-01 2.1442E-13 9.4253E+11 4.2667E+09 Br-82 1.5327E-05 1.4157E-14 1.0397E+11 5.6710E+05 Br-83 3.8269E-10 2.4224E-20 1.7576E+05 1.4159E+01 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 2.0000 Atmosphere Sump Pool Noble gases (atoms) 5.9721E+17 0.0000E+00 0.0000E+00 Elemental I (atoms) 2.2070E+14 0.0000E+00 6.6276E+20 Organic I (atoms) 8.3550E+13 0.0000E+00 0.0000E+00 Aerosols (kg) 4.8367E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 7.3579E+01 9.0428E-07 6.3322E+18 2.7224E+12 I-131 8.8610E+01 7.1475E-07 3.2857E+18 3.2786E+12 I-132 4.5420E+01 4.4002E-09 2.0075E+16 1.6805E+12 I-133 2.4517E+01 2.1643E-08 9.7998E+16 9.0715E+11 I-135 6.2987E-01 1.7935E-10 8.0007E+14 2.3305E+10 Cs-134 8.2524E+03 6.3783E-03 2.8665E+22 3.0534E+14 Cs-136 2.1346E+03 2.9125E-05 1.2897E+20 7.8980E+13 Cs-137 4.4633E+03 5.1313E-02 2.2556E+23 1.6514E+14 I-130 1.9756E-01 1.0130E-10 4.6925E+14 7.3098E+09 Cs-134m 1.2885E-02 1.5978E-12 7.1808E+12 4.7676E+08 Rb-88 2.7981E-02 2.3310E-13 1.5952E+12 1.0353E+09 Ba-137m 4.8365E+03 8.9931E-09 3.9531E+16 1.7895E+14 Br-82 1.7194E-01 1.5881E-10 1.1663E+15 6.3617E+09 Br-83 4.2930E-06 2.7175E-16 1.9717E+09 1.5884E+05 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.4708E+18 Organic I (atoms) 9.3538E+17 Aerosols (kg) 5.7721E-02 Detailed model information at time (H) = 2.0020 EAB Doses:

Time (h) = 2.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 4.7090E-04 4.0595E-02 1.2145E-03 1.7152E-03 Accumulated dose (rem) 3.4705E-01 4.0775E+01 1.0211E+00 1.5970E+00 LPZ Doses:

Time (h) = 2.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.6472E-05 2.2820E-03 6.8273E-05 9.6420E-05 Accumulated dose (rem) 4.2850E-02 5.0356E+00 1.2609E-01 1.9722E-01 Control Room Doses:

Time (h) = 2.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.4099E-05 3.2142E-02 2.5240E-03 1.0091E-03 Accumulated dose (rem) 3.1676E-02 7.8046E+01 3.2682E+00 2.4237E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 5.7859E-02 1.4747E-07 1.0448E+18 2.1408E+09 Kr-85m 2.3685E-04 2.8781E-14 2.0391E+11 8.7635E+06 Kr-88 7.2577E-06 5.7880E-16 3.9609E+09 2.6853E+05

Numerical Applications Inc. Attachment 4 Page 145 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Rb-86 1.1968E-02 1.4709E-10 1.0300E+15 4.4283E+08 I-131 1.5335E-02 1.2370E-10 5.6864E+14 5.6740E+08 I-132 1.0426E-02 1.0101E-12 4.6081E+12 3.8576E+08 I-133 4.2423E-03 3.7449E-12 1.6957E+13 1.5696E+08 I-135 1.0897E-04 3.1029E-14 1.3842E+11 4.0319E+06 Xe-133 3.6390E+00 1.9441E-08 8.8029E+16 1.3464E+11 Xe-135 2.2747E-01 8.9075E-11 3.9735E+14 8.4165E+09 Cs-134 1.3423E+00 1.0375E-06 4.6626E+18 4.9666E+10 Cs-136 3.4721E-01 4.7374E-09 2.0977E+16 1.2847E+10 Cs-137 7.2600E-01 8.3465E-06 3.6689E+19 2.6862E+10 I-130 3.4183E-05 1.7527E-14 8.1190E+10 1.2648E+06 Kr-83m 1.8041E-06 8.7440E-17 6.3443E+08 6.6751E+04 Xe-131m 2.4605E-02 2.9376E-10 1.3504E+15 9.1039E+08 Xe-133m 9.8845E-02 2.2029E-10 9.9746E+14 3.6573E+09 Xe-135m 2.0276E-01 2.2259E-12 9.9292E+12 7.5021E+09 Cs-134m 2.0949E-06 2.5978E-16 1.1675E+09 7.7512E+04 Rb-88 1.9852E-05 1.6538E-16 1.1318E+09 7.3453E+05 Ba-137m 2.2386E-02 4.1625E-14 1.8297E+11 8.2828E+08 Br-82 2.9751E-05 2.7480E-14 2.0182E+11 1.1008E+06 Br-83 7.4243E-10 4.6996E-20 3.4098E+05 2.7470E+01 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 2.0020 Atmosphere Sump Pool Noble gases (atoms) 1.1356E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 4.2843E+14 0.0000E+00 1.2878E+21 Organic I (atoms) 1.6219E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 9.3889E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 1.4297E+02 1.7571E-06 1.2304E+19 5.2900E+12 Cs-134 1.6036E+04 1.2394E-02 5.5700E+22 5.9332E+14 Cs-136 4.1477E+03 5.6593E-05 2.5060E+20 1.5347E+14 Cs-137 8.6728E+03 9.9708E-02 4.3829E+23 3.2089E+14 Cs-134m 2.5026E-02 3.1033E-12 1.3947E+13 9.2596E+08 Rb-88 5.4297E-02 4.5233E-13 3.0954E+12 2.0090E+09 Ba-137m 9.3562E+03 1.7397E-08 7.6473E+16 3.4618E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.1216E-01 Environment Integral Nuclide Release:

Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 1.0517E+03 2.6806E-03 1.8992E+22 3.8912E+13 Kr-85m 4.3052E+00 5.2314E-10 3.7064E+15 1.5929E+11 Kr-88 1.3192E-01 1.0521E-11 7.1996E+13 4.8811E+09 I-131 1.8949E+02 1.5285E-06 7.0265E+18 7.0113E+12 I-132 9.7270E+01 9.4234E-09 4.2992E+16 3.5990E+12 I-133 5.2428E+01 4.6281E-08 2.0956E+17 1.9398E+12 I-135 1.3467E+00 3.8347E-10 1.7106E+15 4.9828E+10 Xe-133 6.4344E+04 3.4375E-04 1.5565E+21 2.3807E+15 Xe-135 3.5762E+03 1.4004E-06 6.2470E+18 1.3232E+14 I-130 4.2245E-01 2.1660E-10 1.0034E+15 1.5630E+10 Kr-83m 1.0448E-02 5.0640E-13 3.6743E+12 3.8658E+08 Xe-131m 4.1443E+02 4.9478E-06 2.2745E+19 1.5334E+13 Xe-133m 1.6677E+03 3.7167E-06 1.6829E+19 6.1704E+13

Numerical Applications Inc. Attachment 4 Page 146 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Xe-135m 5.9337E+01 6.5139E-10 2.9058E+15 2.1955E+12 Rb-88 1.1602E-01 9.6651E-13 6.6142E+12 4.2927E+09 Br-82 3.6768E-01 3.3961E-10 2.4941E+15 1.3604E+10 Br-83 9.1753E-06 5.8080E-16 4.2140E+09 3.3949E+05 Environment Transport Group Inventory:

Present Release Integral Time (h) = 2.0020 Release Rate/s Release Noble gases (atoms) 2.0644E+19 2.8672E+17 2.0594E+22 Elemental I (atoms) 5.2971E+15 7.3571E+13 5.2840E+18 Organic I (atoms) 2.0053E+15 2.7851E+13 2.0003E+18 Aerosols (kg) 5.5425E-18 7.6979E-20 9.6651E-13 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 1.4297E+02 1.7571E-06 1.2304E+19 5.2900E+12 Cs-134 1.6036E+04 1.2394E-02 5.5700E+22 5.9332E+14 Cs-136 4.1477E+03 5.6593E-05 2.5060E+20 1.5347E+14 Cs-137 8.6728E+03 9.9708E-02 4.3829E+23 3.2089E+14 Cs-134m 2.5026E-02 3.1033E-12 1.3947E+13 9.2596E+08 Rb-88 5.4297E-02 4.5233E-13 3.0954E+12 2.0090E+09 Ba-137m 9.3562E+03 1.7397E-08 7.6473E+16 3.4618E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.1216E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0020 Ci kg Atoms Bq I-131 7.6816E-02 6.1961E-10 2.8484E+15 2.8422E+09 I-132 4.1091E-02 3.9809E-12 1.8162E+13 1.5204E+09 I-133 2.1252E-02 1.8761E-11 8.4947E+13 7.8633E+08 I-135 5.4590E-04 1.5545E-13 6.9342E+11 2.0198E+07 I-130 1.7124E-04 8.7802E-14 4.0674E+11 6.3360E+06 Br-82 1.4904E-04 1.3767E-13 1.0110E+12 5.5146E+06 Br-83 3.7193E-09 2.3543E-19 1.7082E+06 1.3762E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.1425E+15 Organic I (atoms) 8.1108E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Numerical Applications Inc. Attachment 4 Page 147 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 7.3653E+01 9.0519E-07 6.3386E+18 2.7251E+12 I-131 8.8699E+01 7.1546E-07 3.2890E+18 3.2819E+12 I-132 4.5453E+01 4.4034E-09 2.0089E+16 1.6818E+12 I-133 2.4540E+01 2.1663E-08 9.8090E+16 9.0800E+11 I-135 6.3037E-01 1.7950E-10 8.0071E+14 2.3324E+10 Cs-134 8.2607E+03 6.3847E-03 2.8694E+22 3.0565E+14 Cs-136 2.1367E+03 2.9154E-05 1.2909E+20 7.9059E+13 Cs-137 4.4678E+03 5.1365E-02 2.2578E+23 1.6531E+14 I-130 1.9774E-01 1.0139E-10 4.6967E+14 7.3164E+09 Cs-134m 1.2892E-02 1.5987E-12 7.1846E+12 4.7701E+08 Rb-88 2.7971E-02 2.3302E-13 1.5946E+12 1.0349E+09 Ba-137m 4.8198E+03 8.9621E-09 3.9395E+16 1.7833E+14 Br-82 1.7210E-01 1.5897E-10 1.1675E+15 6.3678E+09 Br-83 4.2948E-06 2.7186E-16 1.9725E+09 1.5891E+05 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.4733E+18 Organic I (atoms) 9.3631E+17 Aerosols (kg) 5.7779E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 2.1136E-01 5.3873E-07 3.8169E+18 7.8205E+09 Kr-85m 8.6524E-04 1.0514E-13 7.4489E+11 3.2014E+07 Kr-88 2.6513E-05 2.1144E-15 1.4469E+10 9.8098E+05 I-131 1.1423E-02 9.2137E-11 4.2356E+14 4.2264E+08 I-132 7.3000E-03 7.0722E-13 3.2265E+12 2.7010E+08 I-133 3.1600E-03 2.7895E-12 1.2631E+13 1.1692E+08 I-135 8.1171E-05 2.3113E-14 1.0310E+11 3.0033E+06 Xe-133 1.2950E+01 6.9182E-08 3.1325E+17 4.7914E+11 Xe-135 7.2477E-01 2.8381E-10 1.2660E+15 2.6816E+10 I-130 2.5462E-05 1.3055E-14 6.0478E+10 9.4211E+05 Kr-83m 2.3172E-06 1.1231E-16 8.1488E+08 8.5737E+04 Xe-131m 8.3616E-02 9.9827E-10 4.5891E+15 3.0938E+09 Xe-133m 3.3645E-01 7.4983E-10 3.3952E+15 1.2449E+10 Xe-135m 3.2976E-02 3.6201E-13 1.6149E+12 1.2201E+09 Rb-88 9.6529E-06 8.0415E-17 5.5031E+08 3.5716E+05 Br-82 2.2161E-05 2.0470E-14 1.5033E+11 8.1997E+05 Br-83 5.5303E-10 3.5007E-20 2.5399E+05 2.0462E+01 Control Room Transport Group Inventory:

Overlying Time (h) = 2.0020 Atmosphere Sump Pool Noble gases (atoms) 4.1394E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 3.1898E+14 0.0000E+00 0.0000E+00 Organic I (atoms) 1.2075E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 8.0415E-17 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 2.0020 Ci kg Atoms Bq I-131 8.7529E-02 7.0602E-10 3.2456E+15 3.2386E+09 I-132 3.9658E-02 3.8420E-12 1.7528E+13 1.4673E+09 I-133 2.4218E-02 2.1379E-11 9.6801E+13 8.9607E+08 I-135 6.2208E-04 1.7714E-13 7.9019E+11 2.3017E+07 I-130 1.9514E-04 1.0005E-13 4.6350E+11 7.2202E+06

Numerical Applications Inc. Attachment 4 Page 148 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Rb-88 1.0841E-05 9.0312E-17 6.1804E+08 4.0112E+05 Br-82 1.6984E-04 1.5688E-13 1.1521E+12 6.2841E+06 Br-83 4.2384E-09 2.6829E-19 1.9466E+06 1.5682E+02 Deposition Recirculating Time (h) = 2.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 2.4390E+15 Organic I (atoms) 0.0000E+00 9.2333E+14 Aerosols (kg) 0.0000E+00 9.0312E-17 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0020 Ci kg Atoms Bq I-131 7.6816E-02 6.1961E-10 2.8484E+15 2.8422E+09 I-132 4.1091E-02 3.9809E-12 1.8162E+13 1.5204E+09 I-133 2.1252E-02 1.8761E-11 8.4947E+13 7.8633E+08 I-135 5.4590E-04 1.5545E-13 6.9342E+11 2.0198E+07 I-130 1.7124E-04 8.7802E-14 4.0674E+11 6.3360E+06 Br-82 1.4904E-04 1.3767E-13 1.0110E+12 5.5146E+06 Br-83 3.7193E-09 2.3543E-19 1.7082E+06 1.3762E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.1425E+15 Organic I (atoms) 8.1108E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq I-131 1.6434E-01 1.3256E-09 6.0940E+15 6.0807E+09 I-132 8.0750E-02 7.8229E-12 3.5690E+13 2.9877E+09 I-133 4.5470E-02 4.0139E-11 1.8175E+14 1.6824E+09 I-135 1.1680E-03 3.3258E-13 1.4836E+12 4.3216E+07 I-130 3.6639E-04 1.8786E-13 8.7023E+11 1.3556E+07 Rb-88 1.0841E-05 9.0312E-17 6.1804E+08 4.0112E+05 Br-82 3.1888E-04 2.9454E-13 2.1632E+12 1.1799E+07 Br-83 7.9577E-09 5.0372E-19 3.6548E+06 2.9443E+02 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq

Numerical Applications Inc. Attachment 4 Page 149 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Kr-85 2.9806E-02 7.5971E-08 5.3825E+17 1.1028E+09 Kr-85m 1.2201E-04 1.4826E-14 1.0504E+11 4.5146E+06 Kr-88 3.7388E-06 2.9817E-16 2.0405E+09 1.3834E+05 Rb-86 6.1655E-03 7.5773E-11 5.3060E+14 2.2812E+08 I-131 7.8999E-03 6.3722E-11 2.9293E+14 2.9230E+08 I-132 5.3710E-03 5.2034E-13 2.3739E+12 1.9873E+08 I-133 2.1854E-03 1.9292E-12 8.7352E+12 8.0860E+07 I-135 5.6136E-05 1.5985E-14 7.1306E+10 2.0770E+06 Xe-133 1.8747E+00 1.0015E-08 4.5348E+16 6.9362E+10 Xe-135 1.1718E-01 4.5887E-11 2.0469E+14 4.3358E+09 Cs-134 6.9151E-01 5.3447E-07 2.4020E+18 2.5586E+10 Cs-136 1.7886E-01 2.4405E-09 1.0807E+16 6.6180E+09 Cs-137 3.7400E-01 4.2997E-06 1.8900E+19 1.3838E+10 I-130 1.7609E-05 9.0289E-15 4.1825E+10 6.5154E+05 Kr-83m 9.2937E-07 4.5045E-17 3.2683E+08 3.4387E+04 Xe-131m 1.2675E-02 1.5133E-10 6.9566E+14 4.6899E+08 Xe-133m 5.0920E-02 1.1348E-10 5.1384E+14 1.8841E+09 Xe-135m 1.0445E-01 1.1467E-12 5.1150E+12 3.8647E+09 Cs-134m 1.0792E-06 1.3382E-16 6.0142E+08 3.9931E+04 Rb-88 1.0227E-05 8.5196E-17 5.8303E+08 3.7839E+05 Ba-137m 1.1532E-02 2.1443E-14 9.4258E+10 4.2669E+08 Br-82 1.5326E-05 1.4156E-14 1.0397E+11 5.6707E+05 Br-83 3.8247E-10 2.4210E-20 1.7566E+05 1.4151E+01 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 2.0020 Atmosphere Sump Pool Noble gases (atoms) 5.8501E+17 0.0000E+00 0.0000E+00 Elemental I (atoms) 2.2071E+14 0.0000E+00 6.6342E+20 Organic I (atoms) 8.3553E+13 0.0000E+00 0.0000E+00 Aerosols (kg) 4.8367E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 7.3653E+01 9.0519E-07 6.3386E+18 2.7251E+12 I-131 8.8699E+01 7.1546E-07 3.2890E+18 3.2819E+12 I-132 4.5453E+01 4.4034E-09 2.0089E+16 1.6818E+12 I-133 2.4540E+01 2.1663E-08 9.8090E+16 9.0800E+11 I-135 6.3037E-01 1.7950E-10 8.0071E+14 2.3324E+10 Cs-134 8.2607E+03 6.3847E-03 2.8694E+22 3.0565E+14 Cs-136 2.1367E+03 2.9154E-05 1.2909E+20 7.9059E+13 Cs-137 4.4678E+03 5.1365E-02 2.2578E+23 1.6531E+14 I-130 1.9774E-01 1.0139E-10 4.6967E+14 7.3164E+09 Cs-134m 1.2892E-02 1.5987E-12 7.1846E+12 4.7701E+08 Rb-88 2.7971E-02 2.3302E-13 1.5946E+12 1.0349E+09 Ba-137m 4.8198E+03 8.9621E-09 3.9395E+16 1.7833E+14 Br-82 1.7210E-01 1.5897E-10 1.1675E+15 6.3678E+09 Br-83 4.2948E-06 2.7186E-16 1.9725E+09 1.5891E+05 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.4733E+18 Organic I (atoms) 9.3631E+17 Aerosols (kg) 5.7779E-02 Detailed model information at time (H) = 8.0000 EAB Doses:

Time (h) = 8.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.4466E-02 3.6998E-01 6.0534E-02 4.5806E-02

Numerical Applications Inc. Attachment 4 Page 150 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Accumulated dose (rem) 3.8151E-01 4.1145E+01 1.0816E+00 1.6428E+00 LPZ Doses:

Time (h) = 8.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 1.9375E-03 2.0798E-02 3.4029E-03 2.5750E-03 Accumulated dose (rem) 4.4788E-02 5.0564E+00 1.2949E-01 1.9979E-01 Control Room Doses:

Time (h) = 8.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 5.7901E-03 3.5271E+00 5.6878E-01 1.1386E-01 Accumulated dose (rem) 3.7466E-02 8.1573E+01 3.8369E+00 2.5376E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq Xe-133 8.1916E-01 4.3763E-09 1.9816E+16 3.0309E+10 Xe-135 1.6542E-01 6.4776E-11 2.8895E+14 6.1205E+09 Kr-83m 2.1836E-06 1.0583E-16 7.6789E+08 8.0792E+04 Xe-131m 1.7825E-02 2.1281E-10 9.7829E+14 6.5953E+08 Xe-133m 5.8647E-02 1.3070E-10 5.9181E+14 2.1700E+09 Xe-135m 1.0741E+00 1.1791E-11 5.2599E+13 3.9742E+10 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 8.0000 Atmosphere Sump Pool Noble gases (atoms) 2.1727E+16 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.2593E+21 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 8.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 8.0000 Ci kg Atoms Bq Rb-86 1.4364E+02 1.7654E-06 1.2362E+19 5.3148E+12 Cs-134 1.6257E+04 1.2565E-02 5.6470E+22 6.0152E+14 Cs-136 4.1508E+03 5.6635E-05 2.5078E+20 1.5358E+14 Cs-137 8.7946E+03 1.0111E-01 4.4444E+23 3.2540E+14 Cs-134m 6.0512E-03 7.5037E-13 3.3723E+12 2.2390E+08 Rb-88 4.7275E-08 3.9383E-19 2.6951E+06 1.7492E+03 Ba-137m 9.7490E+03 1.8128E-08 7.9684E+16 3.6071E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.1373E-01 Environment Integral Nuclide Release:

Time (h) = 8.0000 Ci kg Atoms Bq Kr-85 1.0614E+03 2.7054E-03 1.9167E+22 3.9272E+13 Xe-133 6.3291E+04 3.3812E-04 1.5310E+21 2.3418E+15 Xe-135 2.3824E+03 9.3292E-07 4.1616E+18 8.8149E+13 Kr-83m 1.8585E-03 9.0080E-14 6.5359E+11 6.8766E+07 Xe-131m 4.2038E+02 5.0188E-06 2.3072E+19 1.5554E+13 Xe-133m 1.5834E+03 3.5289E-06 1.5979E+19 5.8587E+13 Xe-135m 3.0472E+01 3.3452E-10 1.4922E+15 1.1275E+12 Environment Transport Group Inventory:

Numerical Applications Inc. Attachment 4 Page 151 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Present Release Integral Time (h) = 8.0000 Release Rate/s Release Noble gases (atoms) 3.2938E+16 4.5748E+14 2.0741E+22 Elemental I (atoms) 3.7239E+00 5.1721E-02 5.1674E+18 Organic I (atoms) 1.4098E+00 1.9580E-02 1.9562E+18 Aerosols (kg) 4.0341E-25 5.6029E-27 2.9327E-13 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 8.0000 Ci kg Atoms Bq Rb-86 1.4364E+02 1.7654E-06 1.2362E+19 5.3148E+12 Cs-134 1.6257E+04 1.2565E-02 5.6470E+22 6.0152E+14 Cs-136 4.1508E+03 5.6635E-05 2.5078E+20 1.5358E+14 Cs-137 8.7946E+03 1.0111E-01 4.4444E+23 3.2540E+14 Cs-134m 6.0512E-03 7.5037E-13 3.3723E+12 2.2390E+08 Rb-88 4.7275E-08 3.9383E-19 2.6951E+06 1.7492E+03 Ba-137m 9.7490E+03 1.8128E-08 7.9684E+16 3.6071E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.1373E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 8.0000 Ci kg Atoms Bq I-131 7.6239E-02 6.1495E-10 2.8270E+15 2.8208E+09 I-132 6.8618E-03 6.6476E-13 3.0328E+12 2.5389E+08 I-133 1.7647E-02 1.5578E-11 7.0538E+13 6.5296E+08 I-135 2.9515E-04 8.4044E-14 3.7490E+11 1.0921E+07 I-130 1.2406E-04 6.3607E-14 2.9465E+11 4.5901E+06 Br-82 1.3435E-04 1.2410E-13 9.1138E+11 4.9710E+06 Br-83 6.6233E-10 4.1926E-20 3.0420E+05 2.4506E+01 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.1052E+15 Organic I (atoms) 7.9695E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 152 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 8.0000 Ci kg Atoms Bq Rb-86 7.3998E+01 9.0943E-07 6.3683E+18 2.7379E+12 I-131 8.8029E+01 7.1006E-07 3.2642E+18 3.2571E+12 I-132 7.5956E+00 7.3585E-10 3.3571E+15 2.8104E+11 I-133 2.0377E+01 1.7988E-08 8.1449E+16 7.5395E+11 I-135 3.4080E-01 9.7043E-11 4.3289E+14 1.2610E+10 Cs-134 8.3750E+03 6.4730E-03 2.9091E+22 3.0987E+14 Cs-136 2.1383E+03 2.9176E-05 1.2919E+20 7.9117E+13 Cs-137 4.5305E+03 5.2086E-02 2.2896E+23 1.6763E+14 I-130 1.4324E-01 7.3446E-11 3.4023E+14 5.3000E+09 Cs-134m 3.1173E-03 3.8655E-13 1.7372E+12 1.1534E+08 Rb-88 2.4354E-08 2.0288E-19 1.3884E+06 9.0109E+02 Ba-137m 5.0222E+03 9.3384E-09 4.1049E+16 1.8582E+14 Br-82 1.5513E-01 1.4329E-10 1.0523E+15 5.7399E+09 Br-83 7.6478E-07 4.8410E-17 3.5125E+08 2.8297E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.4306E+18 Organic I (atoms) 9.2016E+17 Aerosols (kg) 5.8589E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq Kr-85 5.6991E-08 1.4526E-13 1.0291E+12 2.1087E+03 Xe-133 1.9977E-02 1.0672E-10 4.8324E+14 7.3914E+08 Xe-135 4.4324E-03 1.7357E-12 7.7425E+12 1.6400E+08 Kr-83m 5.0803E-08 2.4623E-18 1.7866E+07 1.8797E+03 Xe-131m 4.2988E-04 5.1322E-12 2.3593E+13 1.5905E+07 Xe-133m 1.4253E-03 3.1766E-12 1.4383E+13 5.2738E+07 Xe-135m 1.2397E-02 1.3609E-13 6.0709E+11 4.5869E+08 Control Room Transport Group Inventory:

Overlying Time (h) = 8.0000 Atmosphere Sump Pool Noble gases (atoms) 5.3060E+14 0.0000E+00 0.0000E+00 Elemental I (atoms) 7.0126E+01 0.0000E+00 0.0000E+00 Organic I (atoms) 2.6547E+01 0.0000E+00 0.0000E+00 Aerosols (kg) 7.6118E-24 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 8.0000 Ci kg Atoms Bq I-131 9.1411E-02 7.3733E-10 3.3896E+15 3.3822E+09 I-132 7.1240E-03 6.9017E-13 3.1487E+12 2.6359E+08 I-133 2.1161E-02 1.8680E-11 8.4581E+13 7.8295E+08 I-135 3.5391E-04 1.0078E-13 4.4954E+11 1.3095E+07 I-130 1.4875E-04 7.6270E-14 3.5332E+11 5.5039E+06 Br-82 1.6110E-04 1.4880E-13 1.0928E+12 5.9607E+06 Br-83 7.9419E-10 5.0272E-20 3.6475E+05 2.9385E+01 Deposition Recirculating Time (h) = 8.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 2.5238E+15 Organic I (atoms) 0.0000E+00 9.5542E+14 Aerosols (kg) 0.0000E+00 5.5035E-22 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 153 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 8.0000 Ci kg Atoms Bq I-131 7.6239E-02 6.1495E-10 2.8270E+15 2.8208E+09 I-132 6.8618E-03 6.6476E-13 3.0328E+12 2.5389E+08 I-133 1.7647E-02 1.5578E-11 7.0538E+13 6.5296E+08 I-135 2.9515E-04 8.4044E-14 3.7490E+11 1.0921E+07 I-130 1.2406E-04 6.3607E-14 2.9465E+11 4.5901E+06 Br-82 1.3435E-04 1.2410E-13 9.1138E+11 4.9710E+06 Br-83 6.6233E-10 4.1926E-20 3.0420E+05 2.4506E+01 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.1052E+15 Organic I (atoms) 7.9695E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq I-131 1.6765E-01 1.3523E-09 6.2165E+15 6.2030E+09 I-132 1.3986E-02 1.3549E-12 6.1815E+12 5.1747E+08 I-133 3.8808E-02 3.4258E-11 1.5512E+14 1.4359E+09 I-135 6.4906E-04 1.8482E-13 8.2445E+11 2.4015E+07 I-130 2.7281E-04 1.3988E-13 6.4797E+11 1.0094E+07 Br-82 2.9545E-04 2.7290E-13 2.0042E+12 1.0932E+07 Br-83 1.4565E-09 9.2198E-20 6.6895E+05 5.3891E+01 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq Xe-133 4.2199E-01 2.2545E-09 1.0208E+16 1.5614E+10 Xe-135 8.5216E-02 3.3369E-11 1.4885E+14 3.1530E+09 Kr-83m 1.1249E-06 5.4520E-17 3.9558E+08 4.1620E+04 Xe-131m 9.1826E-03 1.0963E-10 5.0397E+14 3.3976E+08 Xe-133m 3.0212E-02 6.7332E-11 3.0487E+14 1.1179E+09 Xe-135m 5.5332E-01 6.0743E-12 2.7097E+13 2.0473E+10 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 8.0000 Atmosphere Sump Pool Noble gases (atoms) 1.1193E+16 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 6.4871E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 8.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 154 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 8.0000 Ci kg Atoms Bq Rb-86 7.3998E+01 9.0943E-07 6.3683E+18 2.7379E+12 I-131 8.8029E+01 7.1006E-07 3.2642E+18 3.2571E+12 I-132 7.5956E+00 7.3585E-10 3.3571E+15 2.8104E+11 I-133 2.0377E+01 1.7988E-08 8.1449E+16 7.5395E+11 I-135 3.4080E-01 9.7043E-11 4.3289E+14 1.2610E+10 Cs-134 8.3750E+03 6.4730E-03 2.9091E+22 3.0987E+14 Cs-136 2.1383E+03 2.9176E-05 1.2919E+20 7.9117E+13 Cs-137 4.5305E+03 5.2086E-02 2.2896E+23 1.6763E+14 I-130 1.4324E-01 7.3446E-11 3.4023E+14 5.3000E+09 Cs-134m 3.1173E-03 3.8655E-13 1.7372E+12 1.1534E+08 Rb-88 2.4354E-08 2.0288E-19 1.3884E+06 9.0109E+02 Ba-137m 5.0222E+03 9.3384E-09 4.1049E+16 1.8582E+14 Br-82 1.5513E-01 1.4329E-10 1.0523E+15 5.7399E+09 Br-83 7.6478E-07 4.8410E-17 3.5125E+08 2.8297E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.4306E+18 Organic I (atoms) 9.2016E+17 Aerosols (kg) 5.8589E-02 Detailed model information at time (H) = 24.0000 EAB Doses:

Time (h) = 24.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.0567E-02 1.4400E-16 5.2440E-02 3.0567E-02 Accumulated dose (rem) 4.1208E-01 4.1145E+01 1.1341E+00 1.6734E+00 LPZ Doses:

Time (h) = 24.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 1.1569E-03 5.4501E-18 1.9847E-03 1.1569E-03 Accumulated dose (rem) 4.5945E-02 5.0564E+00 1.3148E-01 2.0095E-01 Control Room Doses:

Time (h) = 24.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 4.4120E-04 7.2779E-13 2.8802E-02 4.4120E-04 Accumulated dose (rem) 3.7907E-02 8.1573E+01 3.8657E+00 2.5380E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 4.8063E-01 2.5677E-09 1.1626E+16 1.7783E+10 Xe-135 3.0897E-02 1.2099E-11 5.3971E+13 1.1432E+09 Kr-83m 2.1082E-08 1.0218E-18 7.4137E+06 7.8002E+02 Xe-131m 1.6829E-02 2.0092E-10 9.2365E+14 6.2269E+08 Xe-133m 3.4410E-02 7.6688E-11 3.4724E+14 1.2732E+09 Xe-135m 2.0062E-01 2.2024E-12 9.8246E+12 7.4230E+09 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 24.0000 Atmosphere Sump Pool Noble gases (atoms) 1.2961E+16 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 1.1765E+21 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 24.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 155 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 1.4013E+02 1.7222E-06 1.2060E+19 5.1848E+12 Cs-134 1.6247E+04 1.2558E-02 5.6435E+22 6.0115E+14 Cs-136 4.0070E+03 5.4672E-05 2.4209E+20 1.4826E+14 Cs-137 8.7942E+03 1.0110E-01 4.4442E+23 3.2539E+14 Cs-134m 1.3213E-04 1.6384E-14 7.3632E+10 4.8887E+06 Ba-137m 9.7486E+03 1.8127E-08 7.9680E+16 3.6070E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.1372E-01 Environment Integral Nuclide Release:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 5.8814E+04 3.1421E-04 1.4227E+21 2.1761E+15 Xe-135 7.6014E+02 2.9766E-07 1.3278E+18 2.8125E+13 Kr-83m 1.8046E-05 8.7465E-16 6.3461E+09 6.6770E+05 Xe-131m 4.2507E+02 5.0748E-06 2.3329E+19 1.5728E+13 Xe-133m 1.3315E+03 2.9674E-06 1.3436E+19 4.9264E+13 Xe-135m 5.6930E+00 6.2497E-11 2.7879E+14 2.1064E+11 Environment Transport Group Inventory:

Present Release Integral Time (h) = 24.0000 Release Rate/s Release Noble gases (atoms) 1.9648E+16 2.7289E+14 2.0626E+22 Elemental I (atoms) 5.3992E-34 7.4989E-36 4.8279E+18 Organic I (atoms) 2.0440E-34 2.8388E-36 1.8277E+18 Aerosols (kg) 2.2421E-44 3.1140E-46 5.9065E-15 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 1.4013E+02 1.7222E-06 1.2060E+19 5.1848E+12 Cs-134 1.6247E+04 1.2558E-02 5.6435E+22 6.0115E+14 Cs-136 4.0070E+03 5.4672E-05 2.4209E+20 1.4826E+14 Cs-137 8.7942E+03 1.0110E-01 4.4442E+23 3.2539E+14 Cs-134m 1.3213E-04 1.6384E-14 7.3632E+10 4.8887E+06 Ba-137m 9.7486E+03 1.8127E-08 7.9680E+16 3.6070E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.1372E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 24.0000 Ci kg Atoms Bq

Numerical Applications Inc. Attachment 4 Page 156 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 I-131 7.1981E-02 5.8061E-10 2.6691E+15 2.6633E+09 I-132 5.5248E-05 5.3524E-15 2.4419E+10 2.0442E+06 I-133 1.0354E-02 9.1404E-12 4.1387E+13 3.8311E+08 I-135 5.5128E-05 1.5698E-14 7.0025E+10 2.0398E+06 I-130 5.0575E-05 2.5931E-14 1.2012E+11 1.8713E+06 Br-82 9.8130E-05 9.0639E-14 6.6566E+11 3.6308E+06 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.9668E+15 Organic I (atoms) 7.4456E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 7.2188E+01 8.8719E-07 6.2125E+18 2.6710E+12 I-131 8.3112E+01 6.7040E-07 3.0819E+18 3.0752E+12 I-132 6.1156E-02 5.9247E-12 2.7030E+13 2.2628E+09 I-133 1.1956E+01 1.0554E-08 4.7788E+16 4.4237E+11 I-135 6.3655E-02 1.8126E-11 8.0857E+13 2.3552E+09 Cs-134 8.3699E+03 6.4691E-03 2.9073E+22 3.0968E+14 Cs-136 2.0642E+03 2.8164E-05 1.2471E+20 7.6375E+13 Cs-137 4.5303E+03 5.2084E-02 2.2895E+23 1.6762E+14 I-130 5.8397E-02 2.9942E-11 1.3870E+14 2.1607E+09 Cs-134m 6.8065E-05 8.4402E-15 3.7932E+10 2.5184E+06 Ba-137m 5.0220E+03 9.3380E-09 4.1047E+16 1.8581E+14 Br-82 1.1331E-01 1.0466E-10 7.6862E+14 4.1924E+09 Br-83 7.3837E-09 4.6739E-19 3.3912E+06 2.7320E+02 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.2709E+18 Organic I (atoms) 8.5971E+17 Aerosols (kg) 5.8582E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 4.4990E-03 2.4035E-11 1.0883E+14 1.6646E+08 Xe-135 3.1781E-04 1.2445E-13 5.5515E+11 1.1759E+07 Xe-131m 1.5581E-04 1.8601E-12 8.5511E+12 5.7648E+06 Xe-133m 3.2104E-04 7.1547E-13 3.2396E+12 1.1878E+07 Xe-135m 8.8927E-04 9.7623E-15 4.3548E+10 3.2903E+07 Control Room Transport Group Inventory:

Overlying Time (h) = 24.0000 Atmosphere Sump Pool

Numerical Applications Inc. Attachment 4 Page 157 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Noble gases (atoms) 1.2122E+14 0.0000E+00 0.0000E+00 Elemental I (atoms) 1.0167E-32 0.0000E+00 0.0000E+00 Organic I (atoms) 3.8490E-33 0.0000E+00 0.0000E+00 Aerosols (kg) 4.1619E-43 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 24.0000 Ci kg Atoms Bq I-131 8.6305E-02 6.9615E-10 3.2002E+15 3.1933E+09 I-132 5.7359E-05 5.5569E-15 2.5352E+10 2.1223E+06 I-133 1.2416E-02 1.0960E-11 4.9626E+13 4.5938E+08 I-135 6.6103E-05 1.8823E-14 8.3966E+10 2.4458E+06 I-130 6.0643E-05 3.1094E-14 1.4404E+11 2.2438E+06 Br-82 1.1767E-04 1.0868E-13 7.9818E+11 4.3536E+06 Deposition Recirculating Time (h) = 24.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 2.3582E+15 Organic I (atoms) 0.0000E+00 8.9273E+14 Aerosols (kg) 0.0000E+00 3.4285E-38 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 24.0000 Ci kg Atoms Bq I-131 7.1981E-02 5.8061E-10 2.6691E+15 2.6633E+09 I-132 5.5248E-05 5.3524E-15 2.4419E+10 2.0442E+06 I-133 1.0354E-02 9.1404E-12 4.1387E+13 3.8311E+08 I-135 5.5128E-05 1.5698E-14 7.0025E+10 2.0398E+06 I-130 5.0575E-05 2.5931E-14 1.2012E+11 1.8713E+06 Br-82 9.8130E-05 9.0639E-14 6.6566E+11 3.6308E+06 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.9668E+15 Organic I (atoms) 7.4456E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq I-131 1.5829E-01 1.2768E-09 5.8693E+15 5.8566E+09 I-132 1.1261E-04 1.0909E-14 4.9771E+10 4.1665E+06

Numerical Applications Inc. Attachment 4 Page 158 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 I-133 2.2770E-02 2.0100E-11 9.1013E+13 8.4249E+08 I-135 1.2123E-04 3.4521E-14 1.5399E+11 4.4856E+06 I-130 1.1122E-04 5.7025E-14 2.6416E+11 4.1151E+06 Br-82 2.1580E-04 1.9932E-13 1.4638E+12 7.9844E+06 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 2.4760E-01 1.3228E-09 5.9894E+15 9.1611E+09 Xe-135 1.5917E-02 6.2328E-12 2.7803E+13 5.8892E+08 Kr-83m 1.0860E-08 5.2638E-19 3.8192E+06 4.0183E+02 Xe-131m 8.6697E-03 1.0351E-10 4.7582E+14 3.2078E+08 Xe-133m 1.7726E-02 3.9506E-11 1.7888E+14 6.5588E+08 Xe-135m 1.0335E-01 1.1346E-12 5.0611E+12 3.8240E+09 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 24.0000 Atmosphere Sump Pool Noble gases (atoms) 6.6769E+15 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 6.0609E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 24.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 7.2188E+01 8.8719E-07 6.2125E+18 2.6710E+12 I-131 8.3112E+01 6.7040E-07 3.0819E+18 3.0752E+12 I-132 6.1156E-02 5.9247E-12 2.7030E+13 2.2628E+09 I-133 1.1956E+01 1.0554E-08 4.7788E+16 4.4237E+11 I-135 6.3655E-02 1.8126E-11 8.0857E+13 2.3552E+09 Cs-134 8.3699E+03 6.4691E-03 2.9073E+22 3.0968E+14 Cs-136 2.0642E+03 2.8164E-05 1.2471E+20 7.6375E+13 Cs-137 4.5303E+03 5.2084E-02 2.2895E+23 1.6762E+14 I-130 5.8397E-02 2.9942E-11 1.3870E+14 2.1607E+09 Cs-134m 6.8065E-05 8.4402E-15 3.7932E+10 2.5184E+06 Ba-137m 5.0220E+03 9.3380E-09 4.1047E+16 1.8581E+14 Br-82 1.1331E-01 1.0466E-10 7.6862E+14 4.1924E+09 Br-83 7.3837E-09 4.6739E-19 3.3912E+06 2.7320E+02 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.2709E+18 Organic I (atoms) 8.5971E+17 Aerosols (kg) 5.8582E-02 Detailed model information at time (H) = 96.0000 EAB Doses:

Time (h) = 96.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 9.7779E-03 2.8006E-38 2.2081E-02 9.7779E-03 Accumulated dose (rem) 4.2186E-01 4.1145E+01 1.1562E+00 1.6832E+00 LPZ Doses:

Time (h) = 96.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 1.5728E-04 4.5048E-40 3.5518E-04 1.5728E-04 Accumulated dose (rem) 4.6102E-02 5.0564E+00 1.3183E-01 2.0110E-01 Control Room Doses:

Numerical Applications Inc. Attachment 4 Page 159 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 96.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 7.4244E-05 6.6464E-35 6.5753E-03 7.4244E-05 Accumulated dose (rem) 3.7982E-02 8.1573E+01 3.8723E+00 2.5381E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 4.3630E-02 2.3309E-10 1.0554E+15 1.6143E+09 Xe-135 1.6253E-05 6.3643E-15 2.8390E+10 6.0135E+05 Xe-131m 1.2994E-02 1.5513E-10 7.1315E+14 4.8078E+08 Xe-133m 3.1236E-03 6.9614E-12 3.1521E+13 1.1557E+08 Xe-135m 1.0553E-04 1.1585E-15 5.1679E+09 3.9047E+06 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 96.0000 Atmosphere Sump Pool Noble gases (atoms) 1.8001E+15 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 8.9594E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 96.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 1.2535E+02 1.5406E-06 1.0788E+19 4.6381E+12 Cs-134 1.6203E+04 1.2523E-02 5.6280E+22 5.9949E+14 Cs-136 3.4188E+03 4.6647E-05 2.0656E+20 1.2650E+14 Cs-137 8.7925E+03 1.0108E-01 4.4434E+23 3.2532E+14 Ba-137m 9.7468E+03 1.8123E-08 7.9665E+16 3.6063E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.1366E-01 Environment Integral Nuclide Release:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 4.0614E+04 2.1698E-04 9.8246E+20 1.5027E+15 Xe-135 3.4893E+00 1.3663E-09 6.0951E+15 1.2910E+11 Xe-131m 4.3126E+02 5.1487E-06 2.3669E+19 1.5957E+13 Xe-133m 5.5327E+02 1.2330E-06 5.5831E+18 2.0471E+13 Xe-135m 2.9948E-03 3.2876E-14 1.4666E+11 1.1081E+08 Environment Transport Group Inventory:

Present Release Integral Time (h) = 96.0000 Release Rate/s Release Noble gases (atoms) 2.7284E+15 3.7894E+13 2.0166E+22 Elemental I (atoms) 0.0000E+00 0.0000E+00 3.6765E+18 Organic I (atoms) 0.0000E+00 0.0000E+00 1.3918E+18 Aerosols (kg) 0.0000E+00 0.0000E+00 1.3791E-22 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 1.2535E+02 1.5406E-06 1.0788E+19 4.6381E+12 Cs-134 1.6203E+04 1.2523E-02 5.6280E+22 5.9949E+14 Cs-136 3.4188E+03 4.6647E-05 2.0656E+20 1.2650E+14 Cs-137 8.7925E+03 1.0108E-01 4.4434E+23 3.2532E+14 Ba-137m 9.7468E+03 1.8123E-08 7.9665E+16 3.6063E+14

Numerical Applications Inc. Attachment 4 Page 160 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.1366E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 96.0000 Ci kg Atoms Bq I-131 5.5576E-02 4.4829E-10 2.0608E+15 2.0563E+09 I-133 9.3992E-04 8.2973E-13 3.7569E+12 3.4777E+07 I-135 2.8999E-08 8.2574E-18 3.6835E+07 1.0730E+03 I-130 8.9199E-07 4.5735E-16 2.1186E+09 3.3004E+04 Br-82 2.3867E-05 2.2045E-14 1.6190E+11 8.8309E+05 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.4977E+15 Organic I (atoms) 5.6699E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 6.4576E+01 7.9363E-07 5.5574E+18 2.3893E+12 I-131 6.4171E+01 5.1762E-07 2.3795E+18 2.3743E+12 I-133 1.0853E+00 9.5807E-10 4.3381E+15 4.0156E+10 I-135 3.3484E-05 9.5346E-15 4.2532E+10 1.2389E+06 Cs-134 8.3468E+03 6.4512E-03 2.8993E+22 3.0883E+14 Cs-136 1.7612E+03 2.4030E-05 1.0641E+20 6.5165E+13 Cs-137 4.5295E+03 5.2074E-02 2.2890E+23 1.6759E+14 I-130 1.0300E-03 5.2809E-13 2.4463E+12 3.8108E+07 Ba-137m 5.0211E+03 9.3363E-09 4.1040E+16 1.8578E+14 Br-82 2.7559E-02 2.5455E-11 1.8695E+14 1.0197E+09 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter

Numerical Applications Inc. Attachment 4 Page 161 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.7294E+18 Organic I (atoms) 6.5468E+17 Aerosols (kg) 5.8550E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 3.0853E-04 1.6483E-12 7.4633E+12 1.1416E+07 Xe-135 1.2629E-07 4.9454E-17 2.2061E+08 4.6728E+03 Xe-131m 9.0880E-05 1.0850E-12 4.9877E+12 3.3625E+06 Xe-133m 2.2016E-05 4.9065E-14 2.2216E+11 8.1458E+05 Xe-135m 3.5345E-07 3.8802E-18 1.7309E+07 1.3078E+04 Control Room Transport Group Inventory:

Overlying Time (h) = 96.0000 Atmosphere Sump Pool Noble gases (atoms) 1.2673E+13 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 96.0000 Ci kg Atoms Bq I-131 6.6636E-02 5.3750E-10 2.4709E+15 2.4655E+09 I-133 1.1270E-03 9.9491E-13 4.5049E+12 4.1701E+07 I-135 3.4772E-08 9.9013E-18 4.4168E+07 1.2866E+03 I-130 1.0696E-06 5.4840E-16 2.5404E+09 3.9574E+04 Br-82 2.8619E-05 2.6434E-14 1.9413E+11 1.0589E+06 Deposition Recirculating Time (h) = 96.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 1.7958E+15 Organic I (atoms) 0.0000E+00 6.7983E+14 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 96.0000 Ci kg Atoms Bq I-131 5.5576E-02 4.4829E-10 2.0608E+15 2.0563E+09 I-133 9.3992E-04 8.2973E-13 3.7569E+12 3.4777E+07 I-135 2.8999E-08 8.2574E-18 3.6835E+07 1.0730E+03 I-130 8.9199E-07 4.5735E-16 2.1186E+09 3.3004E+04 Br-82 2.3867E-05 2.2045E-14 1.6190E+11 8.8309E+05 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.4977E+15 Organic I (atoms) 5.6699E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 162 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq I-131 1.2221E-01 9.8579E-10 4.5317E+15 4.5219E+09 I-133 2.0670E-03 1.8246E-12 8.2618E+12 7.6478E+07 I-135 6.3771E-08 1.8159E-17 8.1003E+07 2.3595E+03 I-130 1.9616E-06 1.0058E-15 4.6591E+09 7.2578E+04 Br-82 5.2486E-05 4.8480E-14 3.5604E+11 1.9420E+06 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 2.2476E-02 1.2008E-10 5.4369E+14 8.3161E+08 Xe-135 8.3726E-06 3.2786E-15 1.4625E+10 3.0979E+05 Xe-131m 6.6939E-03 7.9917E-11 3.6738E+14 2.4767E+08 Xe-133m 1.6091E-03 3.5862E-12 1.6238E+13 5.9538E+07 Xe-135m 5.4365E-05 5.9681E-16 2.6623E+09 2.0115E+06 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 96.0000 Atmosphere Sump Pool Noble gases (atoms) 9.2733E+14 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 4.6155E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 96.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 6.4576E+01 7.9363E-07 5.5574E+18 2.3893E+12 I-131 6.4171E+01 5.1762E-07 2.3795E+18 2.3743E+12 I-133 1.0853E+00 9.5807E-10 4.3381E+15 4.0156E+10 I-135 3.3484E-05 9.5346E-15 4.2532E+10 1.2389E+06 Cs-134 8.3468E+03 6.4512E-03 2.8993E+22 3.0883E+14 Cs-136 1.7612E+03 2.4030E-05 1.0641E+20 6.5165E+13 Cs-137 4.5295E+03 5.2074E-02 2.2890E+23 1.6759E+14 I-130 1.0300E-03 5.2809E-13 2.4463E+12 3.8108E+07 Ba-137m 5.0211E+03 9.3363E-09 4.1040E+16 1.8578E+14 Br-82 2.7559E-02 2.5455E-11 1.8695E+14 1.0197E+09 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.7294E+18 Organic I (atoms) 6.5468E+17 Aerosols (kg) 5.8550E-02 Detailed model information at time (H) = 720.0000 EAB Doses:

Time (h) = 720.0000 Whole Body Thyroid Skin TEDE

Numerical Applications Inc. Attachment 4 Page 163 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Delta dose (rem) 5.2148E-04 5.8163-125 3.4903E-03 5.2148E-04 Accumulated dose (rem) 4.2238E-01 4.1145E+01 1.1597E+00 1.6837E+00 LPZ Doses:

Time (h) = 720.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.4574E-06 2.7409-127 1.6448E-05 2.4574E-06 Accumulated dose (rem) 4.6105E-02 5.0564E+00 1.3185E-01 2.0111E-01 Control Room Doses:

Time (h) = 720.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.8737E-06 9.2022-122 6.4978E-04 2.8737E-06 Accumulated dose (rem) 3.7985E-02 8.1573E+01 3.8730E+00 2.5381E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-133 4.0633E-11 2.1708E-19 9.8292E+05 1.5034E+00 Xe-131m 1.3812E-03 1.6490E-11 7.5806E+13 5.1105E+07 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 720.0000 Atmosphere Sump Pool Noble gases (atoms) 7.5806E+13 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 9.5055E+19 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 720.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 720.0000 Ci kg Atoms Bq Rb-86 4.7719E+01 5.8647E-07 4.1067E+18 1.7656E+12 Cs-134 1.5819E+04 1.2227E-02 5.4949E+22 5.8532E+14 Cs-136 8.6380E+02 1.1786E-05 5.2188E+19 3.1961E+13 Cs-137 8.7781E+03 1.0092E-01 4.4361E+23 3.2479E+14 Ba-137m 9.7307E+03 1.8094E-08 7.9534E+16 3.6004E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.1316E-01 Environment Integral Nuclide Release:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-133 1.3242E+03 7.0744E-06 3.2032E+19 4.8995E+13 Xe-131m 1.9138E+02 2.2848E-06 1.0503E+19 7.0811E+12 Environment Transport Group Inventory:

Present Release Integral Time (h) = 720.0000 Release Rate/s Release Noble gases (atoms) 1.1486E+14 1.5953E+12 1.9109E+22 Elemental I (atoms) 0.0000E+00 0.0000E+00 3.9006E+17 Organic I (atoms) 0.0000E+00 0.0000E+00 1.4766E+17 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 720.0000 Ci kg Atoms Bq

Numerical Applications Inc. Attachment 4 Page 164 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Rb-86 4.7719E+01 5.8647E-07 4.1067E+18 1.7656E+12 Cs-134 1.5819E+04 1.2227E-02 5.4949E+22 5.8532E+14 Cs-136 8.6380E+02 1.1786E-05 5.2188E+19 3.1961E+13 Cs-137 8.7781E+03 1.0092E-01 4.4361E+23 3.2479E+14 Ba-137m 9.7307E+03 1.8094E-08 7.9534E+16 3.6004E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.1316E-01 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 720.0000 Ci kg Atoms Bq I-131 5.9076E-03 4.7652E-11 2.1906E+14 2.1858E+08 Br-82 1.1389E-10 1.0519E-19 7.7256E+05 4.2139E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.5890E+14 Organic I (atoms) 6.0155E+13 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 720.0000 Ci kg Atoms Bq Rb-86 2.4583E+01 3.0212E-07 2.1156E+18 9.0956E+11 I-131 6.8212E+00 5.5021E-08 2.5293E+17 2.5238E+11 I-133 1.0108E-09 8.9227E-19 4.0401E+06 3.7399E+01 Cs-134 8.1494E+03 6.2987E-03 2.8307E+22 3.0153E+14 Cs-136 4.4499E+02 6.0715E-06 2.6885E+19 1.6465E+13 Cs-137 4.5220E+03 5.1988E-02 2.2853E+23 1.6732E+14 Ba-137m 5.0128E+03 9.3209E-09 4.0972E+16 1.8547E+14 Br-82 1.3150E-07 1.2147E-16 8.9205E+08 4.8656E+03 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter

Numerical Applications Inc. Attachment 4 Page 165 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.8348E+17 Organic I (atoms) 6.9458E+16 Aerosols (kg) 5.8293E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-131m 7.3886E-06 8.8211E-14 4.0551E+11 2.7338E+05 Control Room Transport Group Inventory:

Overlying Time (h) = 720.0000 Atmosphere Sump Pool Noble gases (atoms) 4.0551E+11 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 720.0000 Ci kg Atoms Bq I-131 7.0832E-03 5.7134E-11 2.6265E+14 2.6208E+08 Br-82 1.3656E-10 1.2614E-19 9.2636E+05 5.0528E+00 Deposition Recirculating Time (h) = 720.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 1.9052E+14 Organic I (atoms) 0.0000E+00 7.2126E+13 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 720.0000 Ci kg Atoms Bq I-131 5.9076E-03 4.7652E-11 2.1906E+14 2.1858E+08 Br-82 1.1389E-10 1.0519E-19 7.7256E+05 4.2139E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.5890E+14 Organic I (atoms) 6.0155E+13 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 166 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Control Room Total Filter Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq I-131 1.2991E-02 1.0479E-10 4.8171E+14 4.8066E+08 Br-82 2.5045E-10 2.3133E-19 1.6989E+06 9.2666E+00 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-133 2.0932E-11 1.1183E-19 5.0635E+05 7.7450E-01 Xe-131m 7.1154E-04 8.4949E-12 3.9051E+13 2.6327E+07 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 720.0000 Atmosphere Sump Pool Noble gases (atoms) 3.9051E+13 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 4.8968E+19 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 720.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 720.0000 Ci kg Atoms Bq Rb-86 2.4583E+01 3.0212E-07 2.1156E+18 9.0956E+11 I-131 6.8212E+00 5.5021E-08 2.5293E+17 2.5238E+11 I-133 1.0108E-09 8.9227E-19 4.0401E+06 3.7399E+01 Cs-134 8.1494E+03 6.2987E-03 2.8307E+22 3.0153E+14 Cs-136 4.4499E+02 6.0715E-06 2.6885E+19 1.6465E+13 Cs-137 4.5220E+03 5.1988E-02 2.2853E+23 1.6732E+14 Ba-137m 5.0128E+03 9.3209E-09 4.0972E+16 1.8547E+14 Br-82 1.3150E-07 1.2147E-16 8.9205E+08 4.8656E+03 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.8348E+17 Organic I (atoms) 6.9458E+16 Aerosols (kg) 5.8293E-02 Transport Group Totals in Model:

Noble Gases (atoms) 1.9109E+22 Elemental I (atoms) 1.4460E+20 Organic I (atoms) 2.1726E+17 Aerosols (kg) 1.7145E-01 37004 I-131 Summary Fuel Pool-Unfiltered Environment Control Room Time (hr) I-131 (Curies) I-131 (Curies) I-131 (Curies) 0.000 0.0000E+00 0.0000E+00 0.0000E+00 0.001 0.0000E+00 0.0000E+00 0.0000E+00 0.002 0.0000E+00 0.0000E+00 0.0000E+00 0.280 1.5427E-02 2.6424E+01 8.7548E-02 0.333 1.5424E-02 3.1490E+01 1.0147E-01 0.600 1.5410E-02 5.6895E+01 3.6033E-02

Numerical Applications Inc. Attachment 4 Page 167 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 0.860 1.5396E-02 8.1591E+01 1.8390E-02 1.120 1.5382E-02 1.0624E+02 1.3407E-02 1.380 1.5368E-02 1.3083E+02 1.1995E-02 1.640 1.5354E-02 1.5539E+02 1.1589E-02 1.900 1.5341E-02 1.7989E+02 1.1468E-02 2.000 1.5335E-02 1.8931E+02 1.1447E-02 2.002 1.5335E-02 1.8949E+02 1.1423E-02 2.280 0.0000E+00 1.9103E+02 3.1647E-03 2.540 0.0000E+00 1.9085E+02 8.9235E-04 2.800 0.0000E+00 1.9067E+02 2.5161E-04 3.060 0.0000E+00 1.9050E+02 7.0946E-05 3.320 0.0000E+00 1.9032E+02 2.0004E-05 3.580 0.0000E+00 1.9014E+02 5.6406E-06 3.840 0.0000E+00 1.8996E+02 1.5905E-06 4.100 0.0000E+00 1.8979E+02 4.4845E-07 4.360 0.0000E+00 1.8961E+02 1.2645E-07 4.620 0.0000E+00 1.8943E+02 3.5654E-08 4.880 0.0000E+00 1.8926E+02 1.0053E-08 5.140 0.0000E+00 1.8908E+02 2.8347E-09 5.400 0.0000E+00 1.8890E+02 7.9929E-10 5.660 0.0000E+00 1.8873E+02 2.2537E-10 5.920 0.0000E+00 1.8855E+02 6.3548E-11 6.180 0.0000E+00 1.8837E+02 1.7918E-11 6.440 0.0000E+00 1.8820E+02 5.0523E-12 6.700 0.0000E+00 1.8802E+02 1.4246E-12 6.960 0.0000E+00 1.8785E+02 4.0169E-13 7.220 0.0000E+00 1.8767E+02 1.1326E-13 7.480 0.0000E+00 1.8750E+02 3.1936E-14 7.740 0.0000E+00 1.8732E+02 9.0049E-15 8.000 0.0000E+00 1.8715E+02 2.5391E-15 8.260 0.0000E+00 1.8697E+02 7.1594E-16 8.520 0.0000E+00 1.8680E+02 2.0187E-16 8.780 0.0000E+00 1.8662E+02 5.6921E-17 9.040 0.0000E+00 1.8645E+02 1.6050E-17 9.300 0.0000E+00 1.8627E+02 4.5255E-18 9.560 0.0000E+00 1.8610E+02 1.2760E-18 9.820 0.0000E+00 1.8593E+02 3.5980E-19 10.080 0.0000E+00 1.8575E+02 1.0145E-19 24.000 0.0000E+00 1.7669E+02 3.7211E-49 96.000 0.0000E+00 1.3643E+02 2.0779-201 720.000 0.0000E+00 1.4502E+01 0.0000E+00 Fuel Pool-Filtered Time (hr) I-131 (Curies) 0.000 0.0000E+00 0.001 0.0000E+00 0.002 0.0000E+00 0.280 7.9472E-03 0.333 7.9457E-03 0.600 7.9384E-03 0.860 7.9312E-03 1.120 7.9241E-03 1.380 7.9170E-03 1.640 7.9098E-03 1.900 7.9027E-03 2.000 7.9000E-03 2.002 7.8999E-03 2.280 0.0000E+00 2.540 0.0000E+00 2.800 0.0000E+00 3.060 0.0000E+00 3.320 0.0000E+00 3.580 0.0000E+00 3.840 0.0000E+00 4.100 0.0000E+00 4.360 0.0000E+00 4.620 0.0000E+00 4.880 0.0000E+00 5.140 0.0000E+00 5.400 0.0000E+00 5.660 0.0000E+00 5.920 0.0000E+00 6.180 0.0000E+00

Numerical Applications Inc. Attachment 4 Page 168 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 6.440 0.0000E+00 6.700 0.0000E+00 6.960 0.0000E+00 7.220 0.0000E+00 7.480 0.0000E+00 7.740 0.0000E+00 8.000 0.0000E+00 8.260 0.0000E+00 8.520 0.0000E+00 8.780 0.0000E+00 9.040 0.0000E+00 9.300 0.0000E+00 9.560 0.0000E+00 9.820 0.0000E+00 10.080 0.0000E+00 24.000 0.0000E+00 96.000 0.0000E+00 720.000 0.0000E+00 Cumulative Dose Summary EAB LPZ Control Room Time Thyroid TEDE Thyroid TEDE Thyroid TEDE (hr) (rem) (rem) (rem) (rem) (rem) (rem) 0.000 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.001 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.002 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.280 5.6751E+00 2.2212E-01 7.0123E-01 2.7446E-02 1.8015E+01 5.5610E-01 0.333 6.7636E+00 2.6474E-01 8.3572E-01 3.2712E-02 2.5117E+01 7.7530E-01 0.600 1.2224E+01 4.7851E-01 1.5104E+00 5.9125E-02 4.8370E+01 1.4946E+00 0.860 1.7535E+01 6.8650E-01 2.1666E+00 8.4826E-02 5.7671E+01 1.7843E+00 1.120 2.2838E+01 8.9421E-01 2.8219E+00 1.1049E-01 6.3302E+01 1.9607E+00 1.380 2.8133E+01 1.1017E+00 3.4762E+00 1.3612E-01 6.7896E+01 2.1050E+00 1.640 3.3422E+01 1.3089E+00 4.1298E+00 1.6172E-01 7.2193E+01 2.2400E+00 1.900 3.8705E+01 1.5158E+00 4.7825E+00 1.8729E-01 7.6403E+01 2.3722E+00 2.000 4.0735E+01 1.5953E+00 5.0333E+00 1.9712E-01 7.8013E+01 2.4227E+00 2.002 4.0775E+01 1.5970E+00 5.0356E+00 1.9722E-01 7.8046E+01 2.4237E+00 2.280 4.1145E+01 1.6132E+00 5.0563E+00 1.9812E-01 8.0659E+01 2.5063E+00 2.540 4.1145E+01 1.6150E+00 5.0563E+00 1.9822E-01 8.1315E+01 2.5276E+00 2.800 4.1145E+01 1.6167E+00 5.0564E+00 1.9832E-01 8.1500E+01 2.5339E+00 3.060 4.1145E+01 1.6183E+00 5.0564E+00 1.9841E-01 8.1552E+01 2.5358E+00 3.320 4.1145E+01 1.6200E+00 5.0564E+00 1.9851E-01 8.1567E+01 2.5365E+00 3.580 4.1145E+01 1.6215E+00 5.0564E+00 1.9859E-01 8.1571E+01 2.5367E+00 3.840 4.1145E+01 1.6231E+00 5.0564E+00 1.9868E-01 8.1572E+01 2.5368E+00 4.100 4.1145E+01 1.6246E+00 5.0564E+00 1.9876E-01 8.1573E+01 2.5369E+00 4.360 4.1145E+01 1.6260E+00 5.0564E+00 1.9885E-01 8.1573E+01 2.5370E+00 4.620 4.1145E+01 1.6274E+00 5.0564E+00 1.9893E-01 8.1573E+01 2.5370E+00 4.880 4.1145E+01 1.6288E+00 5.0564E+00 1.9900E-01 8.1573E+01 2.5371E+00 5.140 4.1145E+01 1.6302E+00 5.0564E+00 1.9908E-01 8.1573E+01 2.5371E+00 5.400 4.1145E+01 1.6315E+00 5.0564E+00 1.9915E-01 8.1573E+01 2.5372E+00 5.660 4.1145E+01 1.6327E+00 5.0564E+00 1.9922E-01 8.1573E+01 2.5372E+00 5.920 4.1145E+01 1.6340E+00 5.0564E+00 1.9929E-01 8.1573E+01 2.5373E+00 6.180 4.1145E+01 1.6352E+00 5.0564E+00 1.9936E-01 8.1573E+01 2.5373E+00 6.440 4.1145E+01 1.6364E+00 5.0564E+00 1.9943E-01 8.1573E+01 2.5374E+00 6.700 4.1145E+01 1.6375E+00 5.0564E+00 1.9949E-01 8.1573E+01 2.5374E+00 6.960 4.1145E+01 1.6386E+00 5.0564E+00 1.9956E-01 8.1573E+01 2.5374E+00 7.220 4.1145E+01 1.6397E+00 5.0564E+00 1.9962E-01 8.1573E+01 2.5375E+00 7.480 4.1145E+01 1.6408E+00 5.0564E+00 1.9968E-01 8.1573E+01 2.5375E+00 7.740 4.1145E+01 1.6418E+00 5.0564E+00 1.9973E-01 8.1573E+01 2.5376E+00 8.000 4.1145E+01 1.6428E+00 5.0564E+00 1.9979E-01 8.1573E+01 2.5376E+00 8.260 4.1145E+01 1.6438E+00 5.0564E+00 1.9983E-01 8.1573E+01 2.5376E+00 8.520 4.1145E+01 1.6448E+00 5.0564E+00 1.9986E-01 8.1573E+01 2.5376E+00 8.780 4.1145E+01 1.6457E+00 5.0564E+00 1.9990E-01 8.1573E+01 2.5376E+00 9.040 4.1145E+01 1.6466E+00 5.0564E+00 1.9993E-01 8.1573E+01 2.5377E+00 9.300 4.1145E+01 1.6475E+00 5.0564E+00 1.9997E-01 8.1573E+01 2.5377E+00 9.560 4.1145E+01 1.6483E+00 5.0564E+00 2.0000E-01 8.1573E+01 2.5377E+00 9.820 4.1145E+01 1.6492E+00 5.0564E+00 2.0003E-01 8.1573E+01 2.5377E+00 10.080 4.1145E+01 1.6500E+00 5.0564E+00 2.0006E-01 8.1573E+01 2.5377E+00 24.000 4.1145E+01 1.6734E+00 5.0564E+00 2.0095E-01 8.1573E+01 2.5380E+00 96.000 4.1145E+01 1.6832E+00 5.0564E+00 2.0110E-01 8.1573E+01 2.5381E+00 720.000 4.1145E+01 1.6837E+00 5.0564E+00 2.0111E-01 8.1573E+01 2.5381E+00

Numerical Applications Inc. Attachment 4 Page 169 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Worst Two-Hour Dose (Provided for Dose Location 1)

EAB Time Whole Body Thyroid Skin TEDE (hr) (rem) (rem) (rem) (rem) 0.0 3.4658E-01 4.0735E+01 1.0199E+00 1.5953E+00 30 Day Control Room Skin Dose Control Room Time Skin (hr) (rem) 720.0 3.8730E+00

Numerical Applications Inc. Attachment 5 Page 170 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Attachment 5 RADTRAD-NAI FHA Output - Case 3 - 50% Filtered RADTRAD-NAI Version 1.1a(QA) run on May 9, 2005 at 06:56:50 File information Plant file name = pal/FHA/db/pal_fha_db_ast_50filter.psf Inventory file name = pal/FHA/db/palisades_fha_db_ast_adj.nif Scenario file name = pal/FHA/db/pal_fha_db_ast_50filter.psf Release file name = pal/FHA/db/pal_fha_ast.rft Dose conversion file name = pal/FHA/db/nai-1101-001rev0.dcf

  • RADTRAD-NAI 1.1a(QA)
  • 09 May 2005 06:56:45
    • Palisades FHA Design Basis
    • 50% release filtration
  • Nuclide inventory file pal/FHA/db/palisades_fha_db_ast_adj.nif
  • Plant power 2703
  • Compartments 4
  • Compartment 1:

Fuel Pool-Unfiltered 3

10000 0

0 0

1

  • Compartment 2:

Environment 2

2e+20 0

0 0

0

  • Compartment 3:

Control Room 1

35923 0

1 0

0

  • Compartment 4:

Fuel Pool-Filtered 3

10000 0

0 0

Numerical Applications Inc. Attachment 5 Page 171 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 1

  • Pathways 6
  • Pathway 1:

Fuel Pool Release-Unfiltered 1

2 2

  • Pathway 2:

Control Room Unfiltered Makeup 2

3 2

  • Pathway 3:

Control Room Filtered Makeup 2

3 2

  • Pathway 4:

Control Room Unfiltered Inleakage 2

3 2

  • Pathway 5:

Control Room Exhaust 3

2 2

  • Pathway 6:

Fuel Pool Release-Filtered 4

2 2

  • Sources 4

1 0.5 2 0 3 0 4 0.5

  • dose conversion factors filename pal/FHA/db/nai-1101-001rev0.dcf
  • release fraction and timing filename pal/FHA/db/pal_fha_ast.rft 0

1 1

  • Iodine 0 0.9985 0.0015
  • Overlying pool
  • aerosol model 0
  • elemental model 1

2 0 252 720 252

  • organic model 1

2 0 1 720 1

  • pH tracking 0
  • Compartment detail
  • Compartment 1:

1

  • spray model 0

0 0

  • filter model 0
  • deposition model

Numerical Applications Inc. Attachment 5 Page 172 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 0

0

  • Compartment 2:

1

  • spray model 0

0 0

  • filter model 0
  • deposition model 0

0

  • Compartment 3:

1

  • spray model 0

0 0

  • filter model 1

3 0 0 99 99 99 0.3333 1413.6 99 99 99 720 1413.6 99 99 99

  • deposition model 0

0

  • Compartment 4:

1

  • spray model 0

0 0

  • filter model 0
  • deposition model 0

0

  • Pathways:
  • Pathway 1
  • filter efficiency model 1

2 0 1000000 100 0 0 720 1000000 100 0 0

  • Pathway 2
  • filter efficiency model 1

3 0 660 0 0 0 0.3333 0 0 0 0 720 0 0 0 0

  • Pathway 3
  • filter efficiency model 1

3 0 0 99 99 99 0.3333 1413.6 99 99 99 720 1413.6 99 99 99

  • Pathway 4
  • filter efficiency model 1

3 0 0 0 0 0 0.3333 100 0 0 0 720 100 0 0 0

  • Pathway 5
  • filter efficiency model 1

3 0 660 0 0 0 0.3333 1513.6 0 0 0

Numerical Applications Inc. Attachment 5 Page 173 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 720 1513.6 0 0 0

  • Pathway 6
  • filter efficiency model 1

2 0 1000000 100 94 94 720 1000000 100 94 94

  • x/q tables 6

EAB 2

0 0.000539 720 0.000539 LPZ 6

0 6.66e-05 2 3.03e-05 8 2.04e-05 24 8.67e-06 96 2.54e-06 720 2.54e-06 Equip Hatch-Normal 6

0 0.0125 2 0.00983 8 0.00362 24 0.00286 96 0.00228 720 0.00228 Equip Hatch-Emergency 6

0 0.000732 2 0.000613 8 0.000245 24 0.000175 96 0.000129 720 0.000129 Stack-Normal 6

0 0.0061 2 0.00432 8 0.00173 24 0.00127 96 0.000979 720 0.000979 Stack-Emergency 6

0 0.000832 2 0.000769 8 0.000283 24 0.000215 96 0.000157 720 0.000157

  • dose locations 3
  • location name, compartment number and x/q table EAB 2

1

  • br model 1

4 0 0.00035 8 0.00018 24 0.00023 720 0.00023

  • of model 0
  • location x/q input to be included 0
  • location name, compartment number and x/q table LPZ 2

Numerical Applications Inc. Attachment 5 Page 174 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 2

  • br model 1

4 0 0.00035 8 0.00018 24 0.00023 720 0.00023

  • of model 0
  • location x/q input to be included 0
  • location name, compartment number and x/q table Control Room 3

0

  • br model 1

2 0 0.00035 720 0.00035

  • of model 1

4 0 1 24 0.6 96 0.4 720 0.4

  • location x/q input to be included 1
  • number of intake combinations 6
  • intake combinations 2 1 3 3 1 4 4 1 3 2 6 5 3 6 6 4 6 5
  • time step count 3

0 1e-06 0.001 0.02 720 0.02

  • show plant, scenario, event, step, model 1

1 1

0 1

RADTRAD-NAI Version 1.1a(QA) run on May 9, 2005 at 06:56:50 Plant Description Number of Nuclides = 107 Inventory Power = 2.7030E+03 MWth Plant Power Level = 2.7030E+03 MWth Number of compartments = 4 Compartment information Compartment number 1 (Source term fraction = 5.0000E-01)

Name: Fuel Pool-Unfiltered Compartment volume = 1.0000E+04 (Cubic feet)

Removal devices within compartment:

Suppression pool

Numerical Applications Inc. Attachment 5 Page 175 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Pathways into and out of compartment 1 Pathway to compartment number 2: Fuel Pool Release-Unfiltered Compartment number 2 Name: Environment Pathways into and out of compartment 2 Pathway to compartment number 3: Control Room Unfiltered Makeup Pathway to compartment number 3: Control Room Filtered Makeup Pathway to compartment number 3: Control Room Unfiltered Inleakage Pathway from compartment number 1: Fuel Pool Release-Unfiltered Pathway from compartment number 3: Control Room Exhaust Pathway from compartment number 4: Fuel Pool Release-Filtered Compartment number 3 Name: Control Room Compartment volume = 3.5923E+04 (Cubic feet)

Removal devices within compartment:

Filter(s)

Pathways into and out of compartment 3 Pathway to compartment number 2: Control Room Exhaust Pathway from compartment number 2: Control Room Unfiltered Makeup Pathway from compartment number 2: Control Room Filtered Makeup Pathway from compartment number 2: Control Room Unfiltered Inleakage Compartment number 4 (Source term fraction = 5.0000E-01)

Name: Fuel Pool-Filtered Compartment volume = 1.0000E+04 (Cubic feet)

Removal devices within compartment:

Suppression pool Pathways into and out of compartment 4 Pathway to compartment number 2: Fuel Pool Release-Filtered Total number of pathways = 6 RADTRAD-NAI Version 1.1a(QA) run on May 9, 2005 at 06:56:50 Scenario Description Radioactive Decay is enabled Calculation of Daughters is enabled Iodine fractions Aerosol = 0.0000E+00 Elemental = 9.9850E-01 Organic = 1.5000E-03 Overlying pool characteristics Elemental Removal Data:

Time (hr) DF 0.0000E+00 2.5200E+02 7.2000E+02 2.5200E+02 Organic Removal Data:

Time (hr) DF 0.0000E+00 1.0000E+00 7.2000E+02 1.0000E+00 COMPARTMENT DATA Compartment number 1: Fuel Pool-Unfiltered Compartment number 2: Environment Compartment number 3: Control Room Compartment Filter Data

Numerical Applications Inc. Attachment 5 Page 176 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 0.0000E+00 9.9000E+01 9.9000E+01 9.9000E+01 3.3330E-01 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 7.2000E+02 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 Compartment number 4: Fuel Pool-Filtered PATHWAY DATA Pathway number 1: Fuel Pool Release-Unfiltered Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 1.0000E+06 1.0000E+02 0.0000E+00 0.0000E+00 7.2000E+02 1.0000E+06 1.0000E+02 0.0000E+00 0.0000E+00 Pathway number 2: Control Room Unfiltered Makeup Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 6.6000E+02 0.0000E+00 0.0000E+00 0.0000E+00 3.3330E-01 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 3: Control Room Filtered Makeup Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 0.0000E+00 9.9000E+01 9.9000E+01 9.9000E+01 3.3330E-01 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 7.2000E+02 1.4136E+03 9.9000E+01 9.9000E+01 9.9000E+01 Pathway number 4: Control Room Unfiltered Inleakage Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 3.3330E-01 1.0000E+02 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 1.0000E+02 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 5: Control Room Exhaust Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 6.6000E+02 0.0000E+00 0.0000E+00 0.0000E+00 3.3330E-01 1.5136E+03 0.0000E+00 0.0000E+00 0.0000E+00 7.2000E+02 1.5136E+03 0.0000E+00 0.0000E+00 0.0000E+00 Pathway number 6: Fuel Pool Release-Filtered Pathway Filter: Removal Data Time (hr) Flow Rate Filter Efficiencies (%)

(cfm) Aerosol Elemental Organic 0.0000E+00 1.0000E+06 1.0000E+02 9.4000E+01 9.4000E+01 7.2000E+02 1.0000E+06 1.0000E+02 9.4000E+01 9.4000E+01 X/Q DATA X/Q table 1: EAB Time (hr) X/Q (s

  • m^-3) 0.0000E+00 5.3900E-04

Numerical Applications Inc. Attachment 5 Page 177 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 7.2000E+02 5.3900E-04 X/Q table 2: LPZ Time (hr) X/Q (s

  • m^-3) 0.0000E+00 6.6600E-05 2.0000E+00 3.0300E-05 8.0000E+00 2.0400E-05 2.4000E+01 8.6700E-06 9.6000E+01 2.5400E-06 7.2000E+02 2.5400E-06 X/Q table 3: Equip Hatch-Normal Time (hr) X/Q (s
  • m^-3) 0.0000E+00 1.2500E-02 2.0000E+00 9.8300E-03 8.0000E+00 3.6200E-03 2.4000E+01 2.8600E-03 9.6000E+01 2.2800E-03 7.2000E+02 2.2800E-03 X/Q table 4: Equip Hatch-Emergency Time (hr) X/Q (s
  • m^-3) 0.0000E+00 7.3200E-04 2.0000E+00 6.1300E-04 8.0000E+00 2.4500E-04 2.4000E+01 1.7500E-04 9.6000E+01 1.2900E-04 7.2000E+02 1.2900E-04 X/Q table 5: Stack-Normal Time (hr) X/Q (s
  • m^-3) 0.0000E+00 6.1000E-03 2.0000E+00 4.3200E-03 8.0000E+00 1.7300E-03 2.4000E+01 1.2700E-03 9.6000E+01 9.7900E-04 7.2000E+02 9.7900E-04 X/Q table 6: Stack-Emergency Time (hr) X/Q (s
  • m^-3) 0.0000E+00 8.3200E-04 2.0000E+00 7.6900E-04 8.0000E+00 2.8300E-04 2.4000E+01 2.1500E-04 9.6000E+01 1.5700E-04 7.2000E+02 1.5700E-04 LOCATION DATA Location EAB is in compartment 2 Using X/Q Table 1 Location Breathing Rate Data Time (hr) Breathing Rate (m^3
  • sec^-1) 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 2.3000E-04 Location LPZ is in compartment 2 Using X/Q Table 2 Location Breathing Rate Data Time (hr) Breathing Rate (m^3
  • sec^-1) 0.0000E+00 3.5000E-04 8.0000E+00 1.8000E-04 2.4000E+01 2.3000E-04 7.2000E+02 2.3000E-04 Location Control Room is in compartment 3

Numerical Applications Inc. Attachment 5 Page 178 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Inleakage X/Q Table Assignments Inleakage Path Source Path X/Q Table 2 1 3 3 1 4 4 1 3 2 6 5 3 6 6 4 6 5 Location Breathing Rate Data Time (hr) Breathing Rate (m^3

  • sec^-1) 0.0000E+00 3.5000E-04 7.2000E+02 3.5000E-04 Location Occupancy Factor Data Time (hr) Occupancy Factor 0.0000E+00 1.0000E+00 2.4000E+01 6.0000E-01 9.6000E+01 4.0000E-01 7.2000E+02 4.0000E-01 USER SPECIFIED TIME STEP DATA - SUPPLEMENTAL TIME STEPS Time Time step 0.0000E+00 1.0000E-06 1.0000E-03 2.0000E-02 7.2000E+02 2.0000E-02 RADTRAD-NAI Version 1.1a(QA) run on May 9, 2005 at 06:56:50 Dose, Detailed Model and Detailed Inventory Output Detailed model information at time (H) = 0.0010 EAB Doses:

Time (h) = 0.0010 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 LPZ Doses:

Time (h) = 0.0010 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Control Room Doses:

Time (h) = 0.0010 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 0.0010 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 179 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0010 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Environment Transport Group Inventory:

Present Release Integral Time (h) = 0.0010 Release Rate/s Release Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 180 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Transport Group Inventory:

Overlying Time (h) = 0.0010 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0010 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 0.0010 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0010 Surfaces Filter

Numerical Applications Inc. Attachment 5 Page 181 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0010 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 0.0020 EAB Doses:

Time (h) = 0.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 LPZ Doses:

Time (h) = 0.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Control Room Doses:

Time (h) = 0.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Accumulated dose (rem) 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 0.0020 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Environment Transport Group Inventory:

Present Release Integral Time (h) = 0.0020 Release Rate/s Release Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 182 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Transport Group Inventory:

Overlying Time (h) = 0.0020 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 183 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 0.0020 Atmosphere Sump Pool Noble gases (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Detailed model information at time (H) = 0.3333 EAB Doses:

Time (h) = 0.3333 Whole Body Thyroid Skin TEDE Delta dose (rem) 5.5944E-02 5.2687E+00 1.6770E-01 2.1747E-01 Accumulated dose (rem) 5.5944E-02 5.2687E+00 1.6770E-01 2.1747E-01 LPZ Doses:

Time (h) = 0.3333 Whole Body Thyroid Skin TEDE Delta dose (rem) 6.9126E-03 6.5102E-01 2.0722E-02 2.6871E-02 Accumulated dose (rem) 6.9126E-03 6.5102E-01 2.0722E-02 2.6871E-02 Control Room Doses:

Time (h) = 0.3333 Whole Body Thyroid Skin TEDE Delta dose (rem) 4.7289E-03 1.9294E+01 4.7488E-01 5.9618E-01 Accumulated dose (rem) 4.7289E-03 1.9294E+01 4.7488E-01 5.9618E-01

Numerical Applications Inc. Attachment 5 Page 184 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 4.3833E-02 1.1172E-07 7.9155E+17 1.6218E+09 Kr-85m 2.3229E-04 2.8226E-14 1.9998E+11 8.5947E+06 Kr-88 8.2623E-06 6.5892E-16 4.5092E+09 3.0570E+05 Rb-86 9.0903E-03 1.1172E-10 7.8231E+14 3.3634E+08 I-131 1.1685E-02 9.4252E-11 4.3328E+14 4.3234E+08 I-132 7.9814E-03 7.7323E-13 3.5277E+12 2.9531E+08 I-133 3.3976E-03 2.9993E-12 1.3581E+13 1.2571E+08 I-135 9.8340E-05 2.8002E-14 1.2491E+11 3.6386E+06 Xe-133 2.7879E+00 1.4894E-08 6.7439E+16 1.0315E+11 Xe-135 1.9757E-01 7.7366E-11 3.4512E+14 7.3101E+09 Cs-134 1.0170E+00 7.8603E-07 3.5325E+18 3.7629E+10 Cs-136 2.6401E-01 3.6022E-09 1.5951E+16 9.7682E+09 Cs-137 5.5000E-01 6.3232E-06 2.7795E+19 2.0350E+10 I-130 2.8436E-05 1.4580E-14 6.7542E+10 1.0521E+06 Kr-83m 2.3714E-06 1.1494E-16 8.3395E+08 8.7743E+04 Xe-131m 1.8761E-02 2.2399E-10 1.0297E+15 6.9417E+08 Xe-133m 7.6923E-02 1.7143E-10 7.7624E+14 2.8462E+09 Xe-135m 2.0125E-01 2.2093E-12 9.8554E+12 7.4463E+09 Cs-134m 2.3649E-06 2.9325E-16 1.3179E+09 8.7501E+04 Rb-88 2.2038E-05 1.8359E-16 1.2564E+09 8.1541E+05 Ba-137m 1.1277E-01 2.0969E-13 9.2174E+11 4.1726E+09 Br-82 2.3289E-05 2.1512E-14 1.5798E+11 8.6171E+05 Br-83 9.1256E-10 5.7765E-20 4.1912E+05 3.3765E+01 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 0.3333 Atmosphere Sump Pool Noble gases (atoms) 8.6115E+17 0.0000E+00 0.0000E+00 Elemental I (atoms) 3.2696E+14 0.0000E+00 1.6307E+20 Organic I (atoms) 1.2378E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 7.1129E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.3333 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 1.7579E+01 2.1604E-07 1.5128E+18 6.5042E+11 Cs-134 1.9666E+03 1.5200E-03 6.8312E+21 7.2766E+13 Cs-136 5.1053E+02 6.9659E-06 3.0845E+19 1.8890E+13 Cs-137 1.0636E+03 1.2228E-02 5.3750E+22 3.9353E+13 Cs-134m 4.5732E-03 5.6709E-13 2.5486E+12 1.6921E+08 Rb-88 3.0355E-02 2.5288E-13 1.7305E+12 1.1232E+09 Ba-137m 1.0028E+03 1.8647E-09 8.1967E+15 3.7105E+13 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.3755E-02 Environment Integral Nuclide Release:

Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 1.7375E+02 4.4287E-04 3.1377E+21 6.4289E+12 Kr-85m 9.2079E-01 1.1189E-10 7.9271E+14 3.4069E+10 Kr-87 1.1342E-08 4.0041E-19 2.7716E+06 4.1965E+02 Kr-88 3.2751E-02 2.6119E-12 1.7874E+13 1.2118E+09 I-131 2.4530E+01 1.9786E-07 9.0959E+17 9.0761E+11 I-132 1.5983E+01 1.5484E-09 7.0643E+15 5.9138E+11 I-133 7.1327E+00 6.2965E-09 2.8510E+16 2.6391E+11

Numerical Applications Inc. Attachment 5 Page 185 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 I-135 2.0645E-01 5.8786E-11 2.6224E+14 7.6386E+09 Xe-133 1.0704E+04 5.7187E-05 2.5894E+20 3.9606E+14 Xe-135 6.6203E+02 2.5924E-07 1.1564E+18 2.4495E+13 I-130 5.9698E-02 3.0609E-11 1.4179E+14 2.2088E+09 Kr-83m 2.7922E-03 1.3533E-13 9.8191E+11 1.0331E+08 Xe-131m 6.8363E+01 8.1617E-07 3.7520E+18 2.5294E+12 Xe-133m 2.8010E+02 6.2423E-07 2.8265E+18 1.0364E+13 Xe-135m 1.1213E+01 1.2310E-10 5.4911E+14 4.1489E+11 Rb-88 1.0970E-02 9.1385E-14 6.2538E+11 4.0588E+08 Br-82 4.8892E-02 4.5160E-11 3.3166E+14 1.8090E+09 Br-83 1.9158E-06 1.2127E-16 8.7988E+08 7.0884E+04 Environment Transport Group Inventory:

Present Release Integral Time (h) = 0.3333 Release Rate/s Release Noble gases (atoms) 1.3680E+20 1.9000E+18 3.4043E+21 Elemental I (atoms) 2.7584E+16 3.8311E+14 6.8615E+17 Organic I (atoms) 1.0442E+16 1.4503E+14 2.5975E+17 Aerosols (kg) 3.4404E-16 4.7784E-18 9.1385E-14 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 1.7579E+01 2.1604E-07 1.5128E+18 6.5042E+11 Cs-134 1.9666E+03 1.5200E-03 6.8312E+21 7.2766E+13 Cs-136 5.1053E+02 6.9659E-06 3.0845E+19 1.8890E+13 Cs-137 1.0636E+03 1.2228E-02 5.3750E+22 3.9353E+13 Cs-134m 4.5732E-03 5.6709E-13 2.5486E+12 1.6921E+08 Rb-88 3.0355E-02 2.5288E-13 1.7305E+12 1.1232E+09 Ba-137m 1.0028E+03 1.8647E-09 8.1967E+15 3.7105E+13 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 1.3755E-02 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 186 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 1.7579E+01 2.1604E-07 1.5128E+18 6.5042E+11 I-131 2.1240E+01 1.7133E-07 7.8759E+17 7.8588E+11 I-132 1.3818E+01 1.3387E-09 6.1074E+15 5.1127E+11 I-133 6.1761E+00 5.4520E-09 2.4686E+16 2.2852E+11 I-135 1.7876E-01 5.0902E-11 2.2706E+14 6.6141E+09 Cs-134 1.9666E+03 1.5200E-03 6.8312E+21 7.2766E+13 Cs-136 5.1053E+02 6.9659E-06 3.0845E+19 1.8890E+13 Cs-137 1.0636E+03 1.2228E-02 5.3750E+22 3.9353E+13 I-130 5.1691E-02 2.6504E-11 1.2278E+14 1.9126E+09 Cs-134m 4.5732E-03 5.6709E-13 2.5486E+12 1.6921E+08 Rb-88 3.0355E-02 2.5288E-13 1.7305E+12 1.1232E+09 Ba-137m 1.0028E+03 1.8647E-09 8.1967E+15 3.7105E+13 Br-82 4.2335E-02 3.9103E-11 2.8718E+14 1.5664E+09 Br-83 1.6588E-06 1.0500E-16 7.6187E+08 6.1377E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 5.9411E+17 Organic I (atoms) 2.2491E+17 Aerosols (kg) 1.3755E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 4.2272E-01 1.0774E-06 7.6336E+18 1.5641E+10 Kr-85m 2.2402E-03 2.7221E-13 1.9286E+12 8.2886E+07 Kr-88 7.9680E-05 6.3545E-15 4.3486E+10 2.9482E+06 I-131 7.7946E-02 6.2873E-10 2.8903E+15 2.8840E+09 I-132 5.0938E-02 4.9348E-12 2.2514E+13 1.8847E+09 I-133 2.2665E-02 2.0008E-11 9.0593E+13 8.3860E+08 I-135 6.5601E-04 1.8680E-13 8.3328E+11 2.4272E+07 Xe-133 2.6043E+01 1.3913E-07 6.2998E+17 9.6358E+11 Xe-135 1.6109E+00 6.3079E-10 2.8139E+15 5.9602E+10 I-130 1.8969E-04 9.7262E-14 4.5056E+11 7.0187E+06 Kr-83m 6.8048E-06 3.2982E-16 2.3930E+09 2.5178E+05 Xe-131m 1.6633E-01 1.9858E-09 9.1286E+15 6.1542E+09 Xe-133m 6.8149E-01 1.5188E-09 6.8769E+15 2.5215E+10 Xe-135m 2.8436E-02 3.1217E-13 1.3925E+12 1.0521E+09 Rb-88 2.5338E-05 2.1108E-16 1.4445E+09 9.3749E+05 Br-82 1.5536E-04 1.4350E-13 1.0539E+12 5.7483E+06 Br-83 6.0875E-09 3.8534E-19 2.7959E+06 2.2524E+02 Control Room Transport Group Inventory:

Overlying Time (h) = 0.3333 Atmosphere Sump Pool Noble gases (atoms) 8.2824E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 2.1803E+15 0.0000E+00 0.0000E+00 Organic I (atoms) 8.2540E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 2.1108E-16 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.3333 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 187 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 0.3333 Ci kg Atoms Bq Kr-85 4.3833E-02 1.1172E-07 7.9155E+17 1.6218E+09 Kr-85m 2.3229E-04 2.8226E-14 1.9998E+11 8.5947E+06 Kr-88 8.2623E-06 6.5892E-16 4.5092E+09 3.0570E+05 Rb-86 9.0903E-03 1.1172E-10 7.8231E+14 3.3634E+08 I-131 1.1685E-02 9.4252E-11 4.3328E+14 4.3234E+08 I-132 7.9814E-03 7.7323E-13 3.5277E+12 2.9531E+08 I-133 3.3976E-03 2.9993E-12 1.3581E+13 1.2571E+08 I-135 9.8340E-05 2.8002E-14 1.2491E+11 3.6386E+06 Xe-133 2.7879E+00 1.4894E-08 6.7439E+16 1.0315E+11 Xe-135 1.9757E-01 7.7366E-11 3.4512E+14 7.3101E+09 Cs-134 1.0170E+00 7.8603E-07 3.5325E+18 3.7629E+10 Cs-136 2.6401E-01 3.6022E-09 1.5951E+16 9.7682E+09 Cs-137 5.5000E-01 6.3232E-06 2.7795E+19 2.0350E+10 I-130 2.8436E-05 1.4580E-14 6.7542E+10 1.0521E+06 Kr-83m 2.3714E-06 1.1494E-16 8.3395E+08 8.7743E+04 Xe-131m 1.8761E-02 2.2399E-10 1.0297E+15 6.9417E+08 Xe-133m 7.6923E-02 1.7143E-10 7.7624E+14 2.8462E+09 Xe-135m 2.0125E-01 2.2093E-12 9.8554E+12 7.4463E+09 Cs-134m 2.3649E-06 2.9325E-16 1.3179E+09 8.7501E+04 Rb-88 2.2038E-05 1.8359E-16 1.2564E+09 8.1541E+05 Ba-137m 1.1277E-01 2.0969E-13 9.2174E+11 4.1726E+09 Br-82 2.3289E-05 2.1512E-14 1.5798E+11 8.6171E+05 Br-83 9.1256E-10 5.7765E-20 4.1912E+05 3.3765E+01 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 0.3333 Atmosphere Sump Pool Noble gases (atoms) 8.6115E+17 0.0000E+00 0.0000E+00 Elemental I (atoms) 3.2696E+14 0.0000E+00 1.6307E+20 Organic I (atoms) 1.2378E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 7.1129E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 0.3333 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 188 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 0.3333 Ci kg Atoms Bq Rb-86 1.7579E+01 2.1604E-07 1.5128E+18 6.5042E+11 I-131 2.1240E+01 1.7133E-07 7.8759E+17 7.8588E+11 I-132 1.3818E+01 1.3387E-09 6.1074E+15 5.1127E+11 I-133 6.1761E+00 5.4520E-09 2.4686E+16 2.2852E+11 I-135 1.7876E-01 5.0902E-11 2.2706E+14 6.6141E+09 Cs-134 1.9666E+03 1.5200E-03 6.8312E+21 7.2766E+13 Cs-136 5.1053E+02 6.9659E-06 3.0845E+19 1.8890E+13 Cs-137 1.0636E+03 1.2228E-02 5.3750E+22 3.9353E+13 I-130 5.1691E-02 2.6504E-11 1.2278E+14 1.9126E+09 Cs-134m 4.5732E-03 5.6709E-13 2.5486E+12 1.6921E+08 Rb-88 3.0355E-02 2.5288E-13 1.7305E+12 1.1232E+09 Ba-137m 1.0028E+03 1.8647E-09 8.1967E+15 3.7105E+13 Br-82 4.2335E-02 3.9103E-11 2.8718E+14 1.5664E+09 Br-83 1.6588E-06 1.0500E-16 7.6187E+08 6.1377E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 0.3333 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 5.9411E+17 Organic I (atoms) 2.2491E+17 Aerosols (kg) 1.3755E-02 Detailed model information at time (H) = 2.0000 EAB Doses:

Time (h) = 2.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.8190E-01 2.6462E+01 8.3914E-01 1.0931E+00 Accumulated dose (rem) 3.3785E-01 3.1731E+01 1.0068E+00 1.3106E+00 LPZ Doses:

Time (h) = 2.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.4833E-02 3.2697E+00 1.0369E-01 1.3506E-01 Accumulated dose (rem) 4.1745E-02 3.9207E+00 1.2441E-01 1.6193E-01 Control Room Doses:

Time (h) = 2.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.4405E-02 4.0636E+01 2.5491E+00 1.2698E+00 Accumulated dose (rem) 2.9134E-02 5.9930E+01 3.0240E+00 1.8660E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 4.3833E-02 1.1172E-07 7.9154E+17 1.6218E+09 Kr-85m 1.7949E-04 2.1810E-14 1.5452E+11 6.6411E+06 Kr-88 5.5009E-06 4.3870E-16 3.0022E+09 2.0353E+05 Rb-86 9.0669E-03 1.1143E-10 7.8030E+14 3.3547E+08 I-131 1.1618E-02 9.3709E-11 4.3079E+14 4.2985E+08 I-132 7.8571E-03 7.6119E-13 3.4727E+12 2.9071E+08 I-133 3.2140E-03 2.8372E-12 1.2847E+13 1.1892E+08 I-135 8.2571E-05 2.3512E-14 1.0488E+11 3.0551E+06 Xe-133 3.4322E+00 1.8336E-08 8.3024E+16 1.2699E+11 Xe-135 3.8183E-01 1.4952E-10 6.6698E+14 1.4128E+10 Cs-134 1.0169E+00 7.8598E-07 3.5323E+18 3.7626E+10 Cs-136 2.6304E-01 3.5890E-09 1.5892E+16 9.7324E+09 Cs-137 5.5000E-01 6.3231E-06 2.7795E+19 2.0350E+10 I-130 2.5899E-05 1.3279E-14 6.1515E+10 9.5826E+05 Kr-83m 9.7674E-06 4.7341E-16 3.4349E+09 3.6139E+05 Xe-131m 3.0933E-02 3.6930E-10 1.6977E+15 1.1445E+09 Xe-133m 1.2323E-01 2.7463E-10 1.2435E+15 4.5595E+09 Xe-135m 1.5138E+00 1.6618E-11 7.4132E+13 5.6011E+10 Cs-134m 1.5878E-06 1.9689E-16 8.8487E+08 5.8750E+04 Rb-88 1.4723E-05 1.2266E-16 8.3937E+08 5.4476E+05 Ba-137m 1.6958E-01 3.1532E-13 1.3861E+12 6.2745E+09 Br-82 2.2540E-05 2.0819E-14 1.5290E+11 8.3397E+05

Numerical Applications Inc. Attachment 5 Page 189 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Br-83 5.6277E-10 3.5624E-20 2.5847E+05 2.0823E+01 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 2.0000 Atmosphere Sump Pool Noble gases (atoms) 8.7825E+17 0.0000E+00 0.0000E+00 Elemental I (atoms) 3.2456E+14 0.0000E+00 9.7465E+20 Organic I (atoms) 1.2287E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 7.1128E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 1.0820E+02 1.3298E-06 9.3121E+18 4.0036E+12 Cs-134 1.2136E+04 9.3799E-03 4.2154E+22 4.4903E+14 Cs-136 3.1391E+03 4.2831E-05 1.8966E+20 1.1615E+14 Cs-137 6.5637E+03 7.5460E-02 3.3170E+23 2.4286E+14 Cs-134m 1.8949E-02 2.3497E-12 1.0560E+13 7.0112E+08 Rb-88 4.1148E-02 3.4279E-13 2.3458E+12 1.5225E+09 Ba-137m 7.1125E+03 1.3225E-08 5.8134E+16 2.6316E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 8.4884E-02 Environment Integral Nuclide Release:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 1.0506E+03 2.6779E-03 1.8973E+22 3.8874E+13 Kr-85m 4.3022E+00 5.2278E-10 3.7038E+15 1.5918E+11 Kr-88 1.3185E-01 1.0515E-11 7.1960E+13 4.8786E+09 I-131 1.4746E+02 1.1894E-06 5.4679E+18 5.4561E+12 I-132 7.5715E+01 7.3352E-09 3.3465E+16 2.8014E+12 I-133 4.0801E+01 3.6017E-08 1.6308E+17 1.5096E+12 I-135 1.0482E+00 2.9847E-10 1.3314E+15 3.8783E+10 Xe-133 6.4279E+04 3.4341E-04 1.5549E+21 2.3783E+15 Xe-135 3.5728E+03 1.3990E-06 6.2409E+18 1.3219E+14 I-130 3.2877E-01 1.6857E-10 7.8090E+14 1.2165E+10 Kr-83m 1.0427E-02 5.0538E-13 3.6668E+12 3.8580E+08 Xe-131m 4.1399E+02 4.9425E-06 2.2721E+19 1.5318E+13 Xe-133m 1.6660E+03 3.7128E-06 1.6811E+19 6.1641E+13 Xe-135m 5.6580E+01 6.2112E-10 2.7707E+15 2.0934E+12 Rb-88 1.1594E-01 9.6588E-13 6.6099E+12 4.2899E+09 Br-82 2.8613E-01 2.6429E-10 1.9410E+15 1.0587E+10 Br-83 7.1442E-06 4.5223E-16 3.2812E+09 2.6433E+05 Environment Transport Group Inventory:

Present Release Integral Time (h) = 2.0000 Release Rate/s Release Noble gases (atoms) 2.0604E+20 2.8617E+18 2.0573E+22 Elemental I (atoms) 4.1252E+16 5.7295E+14 4.1119E+18 Organic I (atoms) 1.5617E+16 2.1690E+14 1.5566E+18 Aerosols (kg) 5.1878E-16 7.2053E-18 9.6588E-13 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 1.0820E+02 1.3298E-06 9.3121E+18 4.0036E+12 Cs-134 1.2136E+04 9.3799E-03 4.2154E+22 4.4903E+14

Numerical Applications Inc. Attachment 5 Page 190 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Cs-136 3.1391E+03 4.2831E-05 1.8966E+20 1.1615E+14 Cs-137 6.5637E+03 7.5460E-02 3.3170E+23 2.4286E+14 Cs-134m 1.8949E-02 2.3497E-12 1.0560E+13 7.0112E+08 Rb-88 4.1148E-02 3.4279E-13 2.3458E+12 1.5225E+09 Ba-137m 7.1125E+03 1.3225E-08 5.8134E+16 2.6316E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 8.4884E-02 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0000 Ci kg Atoms Bq I-131 5.9993E-02 4.8391E-10 2.2246E+15 2.2197E+09 I-132 3.2103E-02 3.1101E-12 1.4189E+13 1.1878E+09 I-133 1.6599E-02 1.4653E-11 6.6347E+13 6.1416E+08 I-135 4.2643E-04 1.2143E-13 5.4167E+11 1.5778E+07 I-130 1.3375E-04 6.8580E-14 3.1769E+11 4.9489E+06 Br-82 1.1641E-04 1.0752E-13 7.8963E+11 4.3070E+06 Br-83 2.9064E-09 1.8398E-19 1.3349E+06 1.0754E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.6733E+15 Organic I (atoms) 6.3345E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 1.0820E+02 1.3298E-06 9.3121E+18 4.0036E+12 I-131 1.3031E+02 1.0511E-06 4.8319E+18 4.8214E+12 I-132 6.6794E+01 6.4709E-09 2.9522E+16 2.4714E+12 I-133 3.6055E+01 3.1828E-08 1.4411E+17 1.3340E+12 I-135 9.2627E-01 2.6376E-10 1.1766E+15 3.4272E+10 Cs-134 1.2136E+04 9.3799E-03 4.2154E+22 4.4903E+14 Cs-136 3.1391E+03 4.2831E-05 1.8966E+20 1.1615E+14 Cs-137 6.5637E+03 7.5460E-02 3.3170E+23 2.4286E+14

Numerical Applications Inc. Attachment 5 Page 191 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 I-130 2.9053E-01 1.4897E-10 6.9007E+14 1.0750E+10 Cs-134m 1.8949E-02 2.3497E-12 1.0560E+13 7.0112E+08 Rb-88 4.1148E-02 3.4279E-13 2.3458E+12 1.5225E+09 Ba-137m 7.1125E+03 1.3225E-08 5.8134E+16 2.6316E+14 Br-82 2.5285E-01 2.3355E-10 1.7152E+15 9.3554E+09 Br-83 6.3132E-06 3.9963E-16 2.8995E+09 2.3359E+05 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.6336E+18 Organic I (atoms) 1.3756E+18 Aerosols (kg) 8.4884E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 2.0316E-01 5.1783E-07 3.6688E+18 7.5170E+09 Kr-85m 8.3193E-04 1.0109E-13 7.1621E+11 3.0781E+07 Kr-88 2.5497E-05 2.0334E-15 1.3915E+10 9.4338E+05 I-131 8.7943E-03 7.0936E-11 3.2610E+14 3.2539E+08 I-132 5.6209E-03 5.4455E-13 2.4844E+12 2.0797E+08 I-133 2.4330E-03 2.1478E-12 9.7250E+12 9.0022E+07 I-135 6.2506E-05 1.7799E-14 7.9397E+10 2.3127E+06 Xe-133 1.2446E+01 6.6493E-08 3.0108E+17 4.6051E+11 Xe-135 6.9644E-01 2.7272E-10 1.2165E+15 2.5768E+10 I-130 1.9606E-05 1.0052E-14 4.6567E+10 7.2541E+05 Kr-83m 2.2162E-06 1.0741E-16 7.7935E+08 8.1998E+04 Xe-131m 8.0354E-02 9.5932E-10 4.4101E+15 2.9731E+09 Xe-133m 3.2333E-01 7.2059E-10 3.2628E+15 1.1963E+10 Xe-135m 2.9635E-02 3.2533E-13 1.4512E+12 1.0965E+09 Rb-88 9.2730E-06 7.7250E-17 5.2865E+08 3.4310E+05 Br-82 1.7063E-05 1.5760E-14 1.1574E+11 6.3131E+05 Br-83 4.2602E-10 2.6967E-20 1.9566E+05 1.5763E+01 Control Room Transport Group Inventory:

Overlying Time (h) = 2.0000 Atmosphere Sump Pool Noble gases (atoms) 3.9787E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 2.4558E+14 0.0000E+00 0.0000E+00 Organic I (atoms) 9.2969E+13 0.0000E+00 0.0000E+00 Aerosols (kg) 7.7250E-17 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 2.0000 Ci kg Atoms Bq I-131 6.7201E-02 5.4205E-10 2.4918E+15 2.4864E+09 I-132 3.0459E-02 2.9508E-12 1.3462E+13 1.1270E+09 I-133 1.8595E-02 1.6415E-11 7.4324E+13 6.8800E+08 I-135 4.7771E-04 1.3603E-13 6.0679E+11 1.7675E+07 I-130 1.4984E-04 7.6826E-14 3.5589E+11 5.5440E+06 Rb-88 1.0288E-05 8.5705E-17 5.8651E+08 3.8065E+05 Br-82 1.3040E-04 1.2045E-13 8.8458E+11 4.8249E+06 Br-83 3.2559E-09 2.0610E-19 1.4954E+06 1.2047E+02 Deposition Recirculating Time (h) = 2.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 1.8726E+15 Organic I (atoms) 0.0000E+00 7.0890E+14 Aerosols (kg) 0.0000E+00 8.5705E-17 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 192 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0000 Ci kg Atoms Bq I-131 5.9993E-02 4.8391E-10 2.2246E+15 2.2197E+09 I-132 3.2103E-02 3.1101E-12 1.4189E+13 1.1878E+09 I-133 1.6599E-02 1.4653E-11 6.6347E+13 6.1416E+08 I-135 4.2643E-04 1.2143E-13 5.4167E+11 1.5778E+07 I-130 1.3375E-04 6.8580E-14 3.1769E+11 4.9489E+06 Br-82 1.1641E-04 1.0752E-13 7.8963E+11 4.3070E+06 Br-83 2.9064E-09 1.8398E-19 1.3349E+06 1.0754E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.6733E+15 Organic I (atoms) 6.3345E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq I-131 1.2719E-01 1.0260E-09 4.7164E+15 4.7062E+09 I-132 6.2561E-02 6.0609E-12 2.7651E+13 2.3148E+09 I-133 3.5194E-02 3.1067E-11 1.4067E+14 1.3022E+09 I-135 9.0414E-04 2.5745E-13 1.1485E+12 3.3453E+07 I-130 2.8359E-04 1.4541E-13 6.7358E+11 1.0493E+07 Rb-88 1.0288E-05 8.5705E-17 5.8651E+08 3.8065E+05 Br-82 2.4681E-04 2.2797E-13 1.6742E+12 9.1318E+06 Br-83 6.1623E-09 3.9008E-19 2.8302E+06 2.2801E+02 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0000 Ci kg Atoms Bq Kr-85 4.3833E-02 1.1172E-07 7.9154E+17 1.6218E+09 Kr-85m 1.7949E-04 2.1810E-14 1.5452E+11 6.6411E+06 Kr-88 5.5009E-06 4.3870E-16 3.0022E+09 2.0353E+05 Rb-86 9.0669E-03 1.1143E-10 7.8030E+14 3.3547E+08 I-131 1.1618E-02 9.3709E-11 4.3079E+14 4.2985E+08 I-132 7.8571E-03 7.6119E-13 3.4727E+12 2.9071E+08 I-133 3.2140E-03 2.8372E-12 1.2847E+13 1.1892E+08 I-135 8.2571E-05 2.3512E-14 1.0488E+11 3.0551E+06 Xe-133 3.4322E+00 1.8336E-08 8.3024E+16 1.2699E+11 Xe-135 3.8183E-01 1.4952E-10 6.6698E+14 1.4128E+10 Cs-134 1.0169E+00 7.8598E-07 3.5323E+18 3.7626E+10 Cs-136 2.6304E-01 3.5890E-09 1.5892E+16 9.7324E+09 Cs-137 5.5000E-01 6.3231E-06 2.7795E+19 2.0350E+10 I-130 2.5899E-05 1.3279E-14 6.1515E+10 9.5826E+05 Kr-83m 9.7674E-06 4.7341E-16 3.4349E+09 3.6139E+05 Xe-131m 3.0933E-02 3.6930E-10 1.6977E+15 1.1445E+09 Xe-133m 1.2323E-01 2.7463E-10 1.2435E+15 4.5595E+09 Xe-135m 1.5138E+00 1.6618E-11 7.4132E+13 5.6011E+10 Cs-134m 1.5878E-06 1.9689E-16 8.8487E+08 5.8750E+04

Numerical Applications Inc. Attachment 5 Page 193 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Rb-88 1.4723E-05 1.2266E-16 8.3937E+08 5.4476E+05 Ba-137m 1.6958E-01 3.1532E-13 1.3861E+12 6.2745E+09 Br-82 2.2540E-05 2.0819E-14 1.5290E+11 8.3397E+05 Br-83 5.6277E-10 3.5624E-20 2.5847E+05 2.0823E+01 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 2.0000 Atmosphere Sump Pool Noble gases (atoms) 8.7825E+17 0.0000E+00 0.0000E+00 Elemental I (atoms) 3.2456E+14 0.0000E+00 9.7465E+20 Organic I (atoms) 1.2287E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 7.1128E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 2.0000 Ci kg Atoms Bq Rb-86 1.0820E+02 1.3298E-06 9.3121E+18 4.0036E+12 I-131 1.3031E+02 1.0511E-06 4.8319E+18 4.8214E+12 I-132 6.6794E+01 6.4709E-09 2.9522E+16 2.4714E+12 I-133 3.6055E+01 3.1828E-08 1.4411E+17 1.3340E+12 I-135 9.2627E-01 2.6376E-10 1.1766E+15 3.4272E+10 Cs-134 1.2136E+04 9.3799E-03 4.2154E+22 4.4903E+14 Cs-136 3.1391E+03 4.2831E-05 1.8966E+20 1.1615E+14 Cs-137 6.5637E+03 7.5460E-02 3.3170E+23 2.4286E+14 I-130 2.9053E-01 1.4897E-10 6.9007E+14 1.0750E+10 Cs-134m 1.8949E-02 2.3497E-12 1.0560E+13 7.0112E+08 Rb-88 4.1148E-02 3.4279E-13 2.3458E+12 1.5225E+09 Ba-137m 7.1125E+03 1.3225E-08 5.8134E+16 2.6316E+14 Br-82 2.5285E-01 2.3355E-10 1.7152E+15 9.3554E+09 Br-83 6.3132E-06 3.9963E-16 2.8995E+09 2.3359E+05 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.6336E+18 Organic I (atoms) 1.3756E+18 Aerosols (kg) 8.4884E-02 Detailed model information at time (H) = 2.0020 EAB Doses:

Time (h) = 2.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 4.6224E-04 3.1621E-02 1.2015E-03 1.4315E-03 Accumulated dose (rem) 3.3831E-01 3.1762E+01 1.0080E+00 1.3120E+00 LPZ Doses:

Time (h) = 2.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.5985E-05 1.7776E-03 6.7545E-05 8.0472E-05 Accumulated dose (rem) 4.1771E-02 3.9225E+00 1.2447E-01 1.6202E-01 Control Room Doses:

Time (h) = 2.0020 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.2975E-05 2.4694E-02 2.4153E-03 7.7973E-04 Accumulated dose (rem) 2.9157E-02 5.9955E+01 3.0264E+00 1.8667E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 4.3833E-02 1.1172E-07 7.9154E+17 1.6218E+09 Kr-85m 1.7943E-04 2.1804E-14 1.5448E+11 6.6390E+06

Numerical Applications Inc. Attachment 5 Page 194 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Kr-88 5.4982E-06 4.3848E-16 3.0007E+09 2.0344E+05 Rb-86 9.0669E-03 1.1143E-10 7.8029E+14 3.3547E+08 I-131 1.1618E-02 9.3709E-11 4.3078E+14 4.2985E+08 I-132 7.8985E-03 7.6520E-13 3.4910E+12 2.9225E+08 I-133 3.2138E-03 2.8370E-12 1.2846E+13 1.1891E+08 I-135 8.2553E-05 2.3507E-14 1.0486E+11 3.0545E+06 Xe-133 2.7569E+00 1.4728E-08 6.6688E+16 1.0200E+11 Xe-135 1.7233E-01 6.7481E-11 3.0102E+14 6.3761E+09 Cs-134 1.0169E+00 7.8598E-07 3.5323E+18 3.7626E+10 Cs-136 2.6304E-01 3.5889E-09 1.5892E+16 9.7323E+09 Cs-137 5.5000E-01 6.3231E-06 2.7795E+19 2.0350E+10 I-130 2.5896E-05 1.3278E-14 6.1508E+10 9.5815E+05 Kr-83m 1.3667E-06 6.6243E-17 4.8063E+08 5.0569E+04 Xe-131m 1.8640E-02 2.2254E-10 1.0230E+15 6.8969E+08 Xe-133m 7.4883E-02 1.6689E-10 7.5565E+14 2.7707E+09 Xe-135m 1.5360E-01 1.6863E-12 7.5221E+12 5.6834E+09 Cs-134m 1.5871E-06 1.9680E-16 8.8445E+08 5.8721E+04 Rb-88 1.5039E-05 1.2529E-16 8.5739E+08 5.5646E+05 Ba-137m 1.6959E-02 3.1534E-14 1.3862E+11 6.2749E+08 Br-82 2.2539E-05 2.0818E-14 1.5289E+11 8.3393E+05 Br-83 5.6245E-10 3.5603E-20 2.5832E+05 2.0811E+01 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 2.0020 Atmosphere Sump Pool Noble gases (atoms) 8.6032E+17 0.0000E+00 0.0000E+00 Elemental I (atoms) 3.2457E+14 0.0000E+00 9.7561E+20 Organic I (atoms) 1.2287E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 7.1128E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 1.0831E+02 1.3312E-06 9.3214E+18 4.0076E+12 Cs-134 1.2148E+04 9.3893E-03 4.2197E+22 4.4948E+14 Cs-136 3.1422E+03 4.2873E-05 1.8985E+20 1.1626E+14 Cs-137 6.5703E+03 7.5536E-02 3.3204E+23 2.4310E+14 Cs-134m 1.8959E-02 2.3510E-12 1.0566E+13 7.0149E+08 Rb-88 4.1134E-02 3.4267E-13 2.3450E+12 1.5220E+09 Ba-137m 7.0880E+03 1.3180E-08 5.7934E+16 2.6226E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 8.4970E-02 Environment Integral Nuclide Release:

Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 1.0517E+03 2.6806E-03 1.8992E+22 3.8913E+13 Kr-85m 4.3052E+00 5.2314E-10 3.7064E+15 1.5929E+11 Kr-88 1.3192E-01 1.0521E-11 7.1997E+13 4.8811E+09 I-131 1.4761E+02 1.1906E-06 5.4734E+18 5.4615E+12 I-132 7.5769E+01 7.3405E-09 3.3489E+16 2.8035E+12 I-133 4.0839E+01 3.6051E-08 1.6324E+17 1.5110E+12 I-135 1.0490E+00 2.9871E-10 1.3325E+15 3.8814E+10 Xe-133 6.4344E+04 3.4375E-04 1.5565E+21 2.3807E+15 Xe-135 3.5763E+03 1.4004E-06 6.2470E+18 1.3232E+14 I-130 3.2907E-01 1.6872E-10 7.8160E+14 1.2175E+10 Kr-83m 1.0448E-02 5.0641E-13 3.6743E+12 3.8658E+08 Xe-131m 4.1443E+02 4.9478E-06 2.2745E+19 1.5334E+13

Numerical Applications Inc. Attachment 5 Page 195 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Xe-133m 1.6677E+03 3.7167E-06 1.6829E+19 6.1705E+13 Xe-135m 5.9338E+01 6.5140E-10 2.9058E+15 2.1955E+12 Rb-88 1.1602E-01 9.6652E-13 6.6142E+12 4.2927E+09 Br-82 2.8640E-01 2.6454E-10 1.9428E+15 1.0597E+10 Br-83 7.1472E-06 4.5242E-16 3.2825E+09 2.6444E+05 Environment Transport Group Inventory:

Present Release Integral Time (h) = 2.0020 Release Rate/s Release Noble gases (atoms) 2.0643E+19 2.8671E+17 2.0594E+22 Elemental I (atoms) 4.1262E+15 5.7308E+13 4.1160E+18 Organic I (atoms) 1.5620E+15 2.1695E+13 1.5582E+18 Aerosols (kg) 5.5260E-18 7.6750E-20 9.6652E-13 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 1.0831E+02 1.3312E-06 9.3214E+18 4.0076E+12 Cs-134 1.2148E+04 9.3893E-03 4.2197E+22 4.4948E+14 Cs-136 3.1422E+03 4.2873E-05 1.8985E+20 1.1626E+14 Cs-137 6.5703E+03 7.5536E-02 3.3204E+23 2.4310E+14 Cs-134m 1.8959E-02 2.3510E-12 1.0566E+13 7.0149E+08 Rb-88 4.1134E-02 3.4267E-13 2.3450E+12 1.5220E+09 Ba-137m 7.0880E+03 1.3180E-08 5.7934E+16 2.6226E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 8.4970E-02 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0020 Ci kg Atoms Bq I-131 6.0053E-02 4.8440E-10 2.2268E+15 2.2220E+09 I-132 3.2124E-02 3.1122E-12 1.4198E+13 1.1886E+09 I-133 1.6615E-02 1.4667E-11 6.6410E+13 6.1474E+08 I-135 4.2678E-04 1.2152E-13 5.4210E+11 1.5791E+07 I-130 1.3387E-04 6.8642E-14 3.1798E+11 4.9534E+06 Br-82 1.1652E-04 1.0762E-13 7.9040E+11 4.3112E+06 Br-83 2.9077E-09 1.8406E-19 1.3354E+06 1.0758E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.6750E+15 Organic I (atoms) 6.3409E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 196 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 1.0831E+02 1.3312E-06 9.3214E+18 4.0076E+12 I-131 1.3044E+02 1.0521E-06 4.8368E+18 4.8263E+12 I-132 6.6843E+01 6.4756E-09 2.9543E+16 2.4732E+12 I-133 3.6089E+01 3.1858E-08 1.4425E+17 1.3353E+12 I-135 9.2701E-01 2.6397E-10 1.1775E+15 3.4299E+10 Cs-134 1.2148E+04 9.3893E-03 4.2197E+22 4.4948E+14 Cs-136 3.1422E+03 4.2873E-05 1.8985E+20 1.1626E+14 Cs-137 6.5703E+03 7.5536E-02 3.3204E+23 2.4310E+14 I-130 2.9079E-01 1.4910E-10 6.9069E+14 1.0759E+10 Cs-134m 1.8959E-02 2.3510E-12 1.0566E+13 7.0149E+08 Rb-88 4.1134E-02 3.4267E-13 2.3450E+12 1.5220E+09 Ba-137m 7.0880E+03 1.3180E-08 5.7934E+16 2.6226E+14 Br-82 2.5309E-01 2.3377E-10 1.7169E+15 9.3644E+09 Br-83 6.3159E-06 3.9979E-16 2.9007E+09 2.3369E+05 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.6372E+18 Organic I (atoms) 1.3769E+18 Aerosols (kg) 8.4970E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 2.0297E-01 5.1735E-07 3.6653E+18 7.5100E+09 Kr-85m 8.3089E-04 1.0096E-13 7.1532E+11 3.0743E+07 Kr-88 2.5460E-05 2.0305E-15 1.3895E+10 9.4203E+05 I-131 8.7758E-03 7.0787E-11 3.2541E+14 3.2470E+08 I-132 5.6084E-03 5.4334E-13 2.4788E+12 2.0751E+08 I-133 2.4278E-03 2.1431E-12 9.7039E+12 8.9827E+07 I-135 6.2362E-05 1.7757E-14 7.9213E+10 2.3074E+06 Xe-133 1.2436E+01 6.6436E-08 3.0082E+17 4.6012E+11 Xe-135 6.9603E-01 2.7256E-10 1.2158E+15 2.5753E+10 I-130 1.9562E-05 1.0030E-14 4.6464E+10 7.2380E+05 Kr-83m 2.2264E-06 1.0791E-16 7.8294E+08 8.2376E+04 Xe-131m 8.0299E-02 9.5866E-10 4.4070E+15 2.9710E+09 Xe-133m 3.2310E-01 7.2008E-10 3.2605E+15 1.1955E+10 Xe-135m 3.1753E-02 3.4858E-13 1.5549E+12 1.1748E+09 Rb-88 9.2594E-06 7.7137E-17 5.2788E+08 3.4260E+05 Br-82 1.7026E-05 1.5726E-14 1.1550E+11 6.2996E+05 Br-83 4.2488E-10 2.6895E-20 1.9514E+05 1.5721E+01 Control Room Transport Group Inventory:

Overlying Time (h) = 2.0020 Atmosphere Sump Pool Noble gases (atoms) 3.9750E+18 0.0000E+00 0.0000E+00 Elemental I (atoms) 2.4506E+14 0.0000E+00 0.0000E+00 Organic I (atoms) 9.2772E+13 0.0000E+00 0.0000E+00 Aerosols (kg) 7.7137E-17 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 2.0020 Ci kg Atoms Bq I-131 6.7241E-02 5.4238E-10 2.4934E+15 2.4879E+09 I-132 3.0466E-02 2.9516E-12 1.3466E+13 1.1273E+09 I-133 1.8605E-02 1.6424E-11 7.4365E+13 6.8838E+08 I-135 4.7790E-04 1.3608E-13 6.0704E+11 1.7682E+07

Numerical Applications Inc. Attachment 5 Page 197 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 I-130 1.4991E-04 7.6864E-14 3.5607E+11 5.5467E+06 Rb-88 1.0283E-05 8.5663E-17 5.8622E+08 3.8047E+05 Br-82 1.3048E-04 1.2052E-13 8.8508E+11 4.8276E+06 Br-83 3.2560E-09 2.0610E-19 1.4954E+06 1.2047E+02 Deposition Recirculating Time (h) = 2.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 1.8737E+15 Organic I (atoms) 0.0000E+00 7.0932E+14 Aerosols (kg) 0.0000E+00 8.5663E-17 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 2.0020 Ci kg Atoms Bq I-131 6.0053E-02 4.8440E-10 2.2268E+15 2.2220E+09 I-132 3.2124E-02 3.1122E-12 1.4198E+13 1.1886E+09 I-133 1.6615E-02 1.4667E-11 6.6410E+13 6.1474E+08 I-135 4.2678E-04 1.2152E-13 5.4210E+11 1.5791E+07 I-130 1.3387E-04 6.8642E-14 3.1798E+11 4.9534E+06 Br-82 1.1652E-04 1.0762E-13 7.9040E+11 4.3112E+06 Br-83 2.9077E-09 1.8406E-19 1.3354E+06 1.0758E+02 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.6750E+15 Organic I (atoms) 6.3409E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 2.0020 Ci kg Atoms Bq I-131 1.2729E-01 1.0268E-09 4.7201E+15 4.7099E+09 I-132 6.2591E-02 6.0637E-12 2.7664E+13 2.3159E+09 I-133 3.5219E-02 3.1090E-11 1.4077E+14 1.3031E+09 I-135 9.0467E-04 2.5761E-13 1.1491E+12 3.3473E+07 I-130 2.8379E-04 1.4551E-13 6.7405E+11 1.0500E+07 Rb-88 1.0283E-05 8.5663E-17 5.8622E+08 3.8047E+05 Br-82 2.4699E-04 2.2814E-13 1.6755E+12 9.1388E+06 Br-83 6.1637E-09 3.9016E-19 2.8309E+06 2.2806E+02 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Numerical Applications Inc. Attachment 5 Page 198 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 2.0020 Ci kg Atoms Bq Kr-85 4.3833E-02 1.1172E-07 7.9154E+17 1.6218E+09 Kr-85m 1.7943E-04 2.1804E-14 1.5448E+11 6.6390E+06 Kr-88 5.4982E-06 4.3848E-16 3.0007E+09 2.0344E+05 Rb-86 9.0669E-03 1.1143E-10 7.8029E+14 3.3547E+08 I-131 1.1618E-02 9.3709E-11 4.3078E+14 4.2985E+08 I-132 7.8985E-03 7.6520E-13 3.4910E+12 2.9225E+08 I-133 3.2138E-03 2.8370E-12 1.2846E+13 1.1891E+08 I-135 8.2553E-05 2.3507E-14 1.0486E+11 3.0545E+06 Xe-133 2.7569E+00 1.4728E-08 6.6688E+16 1.0200E+11 Xe-135 1.7233E-01 6.7481E-11 3.0102E+14 6.3761E+09 Cs-134 1.0169E+00 7.8598E-07 3.5323E+18 3.7626E+10 Cs-136 2.6304E-01 3.5889E-09 1.5892E+16 9.7323E+09 Cs-137 5.5000E-01 6.3231E-06 2.7795E+19 2.0350E+10 I-130 2.5896E-05 1.3278E-14 6.1508E+10 9.5815E+05 Kr-83m 1.3667E-06 6.6243E-17 4.8063E+08 5.0569E+04 Xe-131m 1.8640E-02 2.2254E-10 1.0230E+15 6.8969E+08 Xe-133m 7.4883E-02 1.6689E-10 7.5565E+14 2.7707E+09 Xe-135m 1.5360E-01 1.6863E-12 7.5221E+12 5.6834E+09 Cs-134m 1.5871E-06 1.9680E-16 8.8445E+08 5.8721E+04 Rb-88 1.5039E-05 1.2529E-16 8.5739E+08 5.5646E+05 Ba-137m 1.6959E-02 3.1534E-14 1.3862E+11 6.2749E+08 Br-82 2.2539E-05 2.0818E-14 1.5289E+11 8.3393E+05 Br-83 5.6245E-10 3.5603E-20 2.5832E+05 2.0811E+01 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 2.0020 Atmosphere Sump Pool Noble gases (atoms) 8.6032E+17 0.0000E+00 0.0000E+00 Elemental I (atoms) 3.2457E+14 0.0000E+00 9.7561E+20 Organic I (atoms) 1.2287E+14 0.0000E+00 0.0000E+00 Aerosols (kg) 7.1128E-06 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 2.0020 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 2.0020 Ci kg Atoms Bq Rb-86 1.0831E+02 1.3312E-06 9.3214E+18 4.0076E+12 I-131 1.3044E+02 1.0521E-06 4.8368E+18 4.8263E+12 I-132 6.6843E+01 6.4756E-09 2.9543E+16 2.4732E+12 I-133 3.6089E+01 3.1858E-08 1.4425E+17 1.3353E+12 I-135 9.2701E-01 2.6397E-10 1.1775E+15 3.4299E+10 Cs-134 1.2148E+04 9.3893E-03 4.2197E+22 4.4948E+14 Cs-136 3.1422E+03 4.2873E-05 1.8985E+20 1.1626E+14 Cs-137 6.5703E+03 7.5536E-02 3.3204E+23 2.4310E+14 I-130 2.9079E-01 1.4910E-10 6.9069E+14 1.0759E+10 Cs-134m 1.8959E-02 2.3510E-12 1.0566E+13 7.0149E+08 Rb-88 4.1134E-02 3.4267E-13 2.3450E+12 1.5220E+09 Ba-137m 7.0880E+03 1.3180E-08 5.7934E+16 2.6226E+14 Br-82 2.5309E-01 2.3377E-10 1.7169E+15 9.3644E+09 Br-83 6.3159E-06 3.9979E-16 2.9007E+09 2.3369E+05 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 2.0020 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.6372E+18 Organic I (atoms) 1.3769E+18 Aerosols (kg) 8.4970E-02 Detailed model information at time (H) = 8.0000 EAB Doses:

Time (h) = 8.0000 Whole Body Thyroid Skin TEDE

Numerical Applications Inc. Attachment 5 Page 199 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Delta dose (rem) 3.4385E-02 2.8818E-01 6.0409E-02 4.3218E-02 Accumulated dose (rem) 3.7270E-01 3.2050E+01 1.0685E+00 1.3552E+00 LPZ Doses:

Time (h) = 8.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 1.9330E-03 1.6200E-02 3.3959E-03 2.4295E-03 Accumulated dose (rem) 4.3704E-02 3.9387E+00 1.2787E-01 1.6444E-01 Control Room Doses:

Time (h) = 8.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 5.5538E-03 2.7095E+00 5.4605E-01 8.8572E-02 Accumulated dose (rem) 3.4711E-02 6.2665E+01 3.5725E+00 1.9553E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq Xe-133 6.2058E-01 3.3154E-09 1.5012E+16 2.2961E+10 Xe-135 1.2532E-01 4.9072E-11 2.1890E+14 4.6367E+09 Kr-83m 1.6542E-06 8.0177E-17 5.8173E+08 6.1206E+04 Xe-131m 1.3504E-02 1.6122E-10 7.4113E+14 4.9964E+08 Xe-133m 4.4430E-02 9.9018E-11 4.4834E+14 1.6439E+09 Xe-135m 8.1371E-01 8.9328E-12 3.9848E+13 3.0107E+10 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 8.0000 Atmosphere Sump Pool Noble gases (atoms) 1.6460E+16 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 9.5399E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 8.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 8.0000 Ci kg Atoms Bq Rb-86 1.0882E+02 1.3374E-06 9.3651E+18 4.0264E+12 Cs-134 1.2316E+04 9.5192E-03 4.2780E+22 4.5570E+14 Cs-136 3.1446E+03 4.2905E-05 1.8999E+20 1.1635E+14 Cs-137 6.6626E+03 7.6597E-02 3.3670E+23 2.4651E+14 Cs-134m 4.5843E-03 5.6846E-13 2.5547E+12 1.6962E+08 Rb-88 3.5814E-08 2.9836E-19 2.0418E+06 1.3251E+03 Ba-137m 7.3856E+03 1.3733E-08 6.0366E+16 2.7327E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 8.6161E-02 Environment Integral Nuclide Release:

Time (h) = 8.0000 Ci kg Atoms Bq Kr-85 1.0614E+03 2.7054E-03 1.9167E+22 3.9272E+13 Xe-133 6.3291E+04 3.3812E-04 1.5310E+21 2.3418E+15 Xe-135 2.3824E+03 9.3292E-07 4.1616E+18 8.8149E+13 Kr-83m 1.8585E-03 9.0080E-14 6.5359E+11 6.8766E+07 Xe-131m 4.2038E+02 5.0188E-06 2.3072E+19 1.5554E+13 Xe-133m 1.5834E+03 3.5289E-06 1.5979E+19 5.8587E+13 Xe-135m 3.0472E+01 3.3452E-10 1.4922E+15 1.1275E+12 Environment Transport Group Inventory:

Numerical Applications Inc. Attachment 5 Page 200 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Present Release Integral Time (h) = 8.0000 Release Rate/s Release Noble gases (atoms) 3.2938E+16 4.5748E+14 2.0741E+22 Elemental I (atoms) 2.8607E+00 3.9733E-02 4.0252E+18 Organic I (atoms) 1.0830E+00 1.5041E-02 1.5238E+18 Aerosols (kg) 3.8753E-25 5.3824E-27 2.9327E-13 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 8.0000 Ci kg Atoms Bq Rb-86 1.0882E+02 1.3374E-06 9.3651E+18 4.0264E+12 Cs-134 1.2316E+04 9.5192E-03 4.2780E+22 4.5570E+14 Cs-136 3.1446E+03 4.2905E-05 1.8999E+20 1.1635E+14 Cs-137 6.6626E+03 7.6597E-02 3.3670E+23 2.4651E+14 Cs-134m 4.5843E-03 5.6846E-13 2.5547E+12 1.6962E+08 Rb-88 3.5814E-08 2.9836E-19 2.0418E+06 1.3251E+03 Ba-137m 7.3856E+03 1.3733E-08 6.0366E+16 2.7327E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 8.6161E-02 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 8.0000 Ci kg Atoms Bq I-131 5.9604E-02 4.8078E-10 2.2102E+15 2.2054E+09 I-132 5.3647E-03 5.1973E-13 2.3711E+12 1.9849E+08 I-133 1.3797E-02 1.2179E-11 5.5147E+13 5.1049E+08 I-135 2.3075E-04 6.5706E-14 2.9310E+11 8.5378E+06 I-130 9.6988E-05 4.9729E-14 2.3036E+11 3.5886E+06 Br-82 1.0504E-04 9.7020E-14 7.1252E+11 3.8864E+06 Br-83 5.1782E-10 3.2778E-20 2.3782E+05 1.9159E+01 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.6458E+15 Organic I (atoms) 6.2307E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 201 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 8.0000 Ci kg Atoms Bq Rb-86 1.0882E+02 1.3374E-06 9.3651E+18 4.0264E+12 I-131 1.2945E+02 1.0442E-06 4.8003E+18 4.7898E+12 I-132 1.1170E+01 1.0821E-09 4.9369E+15 4.1329E+11 I-133 2.9966E+01 2.6453E-08 1.1978E+17 1.1088E+12 I-135 5.0118E-01 1.4271E-10 6.3661E+14 1.8544E+10 Cs-134 1.2316E+04 9.5192E-03 4.2780E+22 4.5570E+14 Cs-136 3.1446E+03 4.2905E-05 1.8999E+20 1.1635E+14 Cs-137 6.6626E+03 7.6597E-02 3.3670E+23 2.4651E+14 I-130 2.1065E-01 1.0801E-10 5.0034E+14 7.7941E+09 Cs-134m 4.5843E-03 5.6846E-13 2.5547E+12 1.6962E+08 Rb-88 3.5814E-08 2.9836E-19 2.0418E+06 1.3251E+03 Ba-137m 7.3856E+03 1.3733E-08 6.0366E+16 2.7327E+14 Br-82 2.2814E-01 2.1072E-10 1.5476E+15 8.4411E+09 Br-83 1.1247E-06 7.1192E-17 5.1654E+08 4.1613E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.5745E+18 Organic I (atoms) 1.3532E+18 Aerosols (kg) 8.6161E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq Kr-85 5.4747E-08 1.3954E-13 9.8864E+11 2.0257E+03 Xe-133 1.9368E-02 1.0347E-10 4.6852E+14 7.1662E+08 Xe-135 4.2974E-03 1.6828E-12 7.5066E+12 1.5900E+08 Kr-83m 4.9255E-08 2.3873E-18 1.7321E+07 1.8224E+03 Xe-131m 4.1678E-04 4.9758E-12 2.2874E+13 1.5421E+07 Xe-133m 1.3819E-03 3.0798E-12 1.3945E+13 5.1131E+07 Xe-135m 1.2019E-02 1.3195E-13 5.8860E+11 4.4472E+08 Control Room Transport Group Inventory:

Overlying Time (h) = 8.0000 Atmosphere Sump Pool Noble gases (atoms) 5.1442E+14 0.0000E+00 0.0000E+00 Elemental I (atoms) 5.3871E+01 0.0000E+00 0.0000E+00 Organic I (atoms) 2.0394E+01 0.0000E+00 0.0000E+00 Aerosols (kg) 7.3122E-24 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 8.0000 Ci kg Atoms Bq I-131 7.0224E-02 5.6643E-10 2.6039E+15 2.5983E+09 I-132 5.4729E-03 5.3021E-13 2.4189E+12 2.0250E+08 I-133 1.6256E-02 1.4350E-11 6.4977E+13 6.0148E+08 I-135 2.7188E-04 7.7418E-14 3.4535E+11 1.0060E+07 I-130 1.1427E-04 5.8592E-14 2.7142E+11 4.2282E+06 Br-82 1.2376E-04 1.1431E-13 8.3952E+11 4.5791E+06 Br-83 6.1011E-10 3.8620E-20 2.8021E+05 2.2574E+01 Deposition Recirculating Time (h) = 8.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 1.9388E+15 Organic I (atoms) 0.0000E+00 7.3397E+14 Aerosols (kg) 0.0000E+00 5.2775E-22 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 202 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 8.0000 Ci kg Atoms Bq I-131 5.9604E-02 4.8078E-10 2.2102E+15 2.2054E+09 I-132 5.3647E-03 5.1973E-13 2.3711E+12 1.9849E+08 I-133 1.3797E-02 1.2179E-11 5.5147E+13 5.1049E+08 I-135 2.3075E-04 6.5706E-14 2.9310E+11 8.5378E+06 I-130 9.6988E-05 4.9729E-14 2.3036E+11 3.5886E+06 Br-82 1.0504E-04 9.7020E-14 7.1252E+11 3.8864E+06 Br-83 5.1782E-10 3.2778E-20 2.3782E+05 1.9159E+01 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.6458E+15 Organic I (atoms) 6.2307E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq I-131 1.2983E-01 1.0472E-09 4.8141E+15 4.8036E+09 I-132 1.0838E-02 1.0499E-12 4.7900E+12 4.0099E+08 I-133 3.0053E-02 2.6530E-11 1.2012E+14 1.1120E+09 I-135 5.0263E-04 1.4312E-13 6.3845E+11 1.8597E+07 I-130 2.1126E-04 1.0832E-13 5.0179E+11 7.8167E+06 Br-82 2.2880E-04 2.1133E-13 1.5520E+12 8.4655E+06 Br-83 1.1279E-09 7.1398E-20 5.1804E+05 4.1733E+01 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 8.0000 Ci kg Atoms Bq Xe-133 6.2058E-01 3.3154E-09 1.5012E+16 2.2961E+10 Xe-135 1.2532E-01 4.9072E-11 2.1890E+14 4.6367E+09 Kr-83m 1.6542E-06 8.0177E-17 5.8173E+08 6.1206E+04 Xe-131m 1.3504E-02 1.6122E-10 7.4113E+14 4.9964E+08 Xe-133m 4.4430E-02 9.9018E-11 4.4834E+14 1.6439E+09 Xe-135m 8.1371E-01 8.9328E-12 3.9848E+13 3.0107E+10 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 8.0000 Atmosphere Sump Pool Noble gases (atoms) 1.6460E+16 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 9.5399E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 8.0000 Surfaces Filter

Numerical Applications Inc. Attachment 5 Page 203 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 8.0000 Ci kg Atoms Bq Rb-86 1.0882E+02 1.3374E-06 9.3651E+18 4.0264E+12 I-131 1.2945E+02 1.0442E-06 4.8003E+18 4.7898E+12 I-132 1.1170E+01 1.0821E-09 4.9369E+15 4.1329E+11 I-133 2.9966E+01 2.6453E-08 1.1978E+17 1.1088E+12 I-135 5.0118E-01 1.4271E-10 6.3661E+14 1.8544E+10 Cs-134 1.2316E+04 9.5192E-03 4.2780E+22 4.5570E+14 Cs-136 3.1446E+03 4.2905E-05 1.8999E+20 1.1635E+14 Cs-137 6.6626E+03 7.6597E-02 3.3670E+23 2.4651E+14 I-130 2.1065E-01 1.0801E-10 5.0034E+14 7.7941E+09 Cs-134m 4.5843E-03 5.6846E-13 2.5547E+12 1.6962E+08 Rb-88 3.5814E-08 2.9836E-19 2.0418E+06 1.3251E+03 Ba-137m 7.3856E+03 1.3733E-08 6.0366E+16 2.7327E+14 Br-82 2.2814E-01 2.1072E-10 1.5476E+15 8.4411E+09 Br-83 1.1247E-06 7.1192E-17 5.1654E+08 4.1613E+04 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 8.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.5745E+18 Organic I (atoms) 1.3532E+18 Aerosols (kg) 8.6161E-02 Detailed model information at time (H) = 24.0000 EAB Doses:

Time (h) = 24.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 3.0567E-02 1.1070E-16 5.2440E-02 3.0567E-02 Accumulated dose (rem) 4.0326E-01 3.2050E+01 1.1209E+00 1.3858E+00 LPZ Doses:

Time (h) = 24.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 1.1569E-03 4.1897E-18 1.9847E-03 1.1569E-03 Accumulated dose (rem) 4.4861E-02 3.9387E+00 1.2986E-01 1.6560E-01 Control Room Doses:

Time (h) = 24.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 4.2631E-04 5.5948E-13 2.7830E-02 4.2631E-04 Accumulated dose (rem) 3.5137E-02 6.2665E+01 3.6003E+00 1.9557E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 3.6411E-01 1.9452E-09 8.8079E+15 1.3472E+10 Xe-135 2.3407E-02 9.1658E-12 4.0887E+13 8.6606E+08 Kr-83m 1.5971E-08 7.7408E-19 5.6164E+06 5.9092E+02 Xe-131m 1.2750E-02 1.5221E-10 6.9973E+14 4.7173E+08 Xe-133m 2.6068E-02 5.8097E-11 2.6306E+14 9.6453E+08 Xe-135m 1.5199E-01 1.6685E-12 7.4428E+12 5.6235E+09 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 24.0000 Atmosphere Sump Pool Noble gases (atoms) 9.8190E+15 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 8.9131E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 24.0000 Surfaces Filter

Numerical Applications Inc. Attachment 5 Page 204 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 1.0616E+02 1.3047E-06 9.1361E+18 3.9279E+12 Cs-134 1.2309E+04 9.5133E-03 4.2754E+22 4.5542E+14 Cs-136 3.0356E+03 4.1418E-05 1.8340E+20 1.1232E+14 Cs-137 6.6623E+03 7.6594E-02 3.3669E+23 2.4650E+14 Cs-134m 1.0010E-04 1.2412E-14 5.5782E+10 3.7035E+06 Ba-137m 7.3853E+03 1.3732E-08 6.0364E+16 2.7326E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 8.6150E-02 Environment Integral Nuclide Release:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 5.8814E+04 3.1421E-04 1.4227E+21 2.1761E+15 Xe-135 7.6014E+02 2.9766E-07 1.3278E+18 2.8125E+13 Kr-83m 1.8046E-05 8.7465E-16 6.3461E+09 6.6770E+05 Xe-131m 4.2507E+02 5.0748E-06 2.3329E+19 1.5728E+13 Xe-133m 1.3315E+03 2.9674E-06 1.3436E+19 4.9264E+13 Xe-135m 5.6930E+00 6.2497E-11 2.7879E+14 2.1064E+11 Environment Transport Group Inventory:

Present Release Integral Time (h) = 24.0000 Release Rate/s Release Noble gases (atoms) 1.9648E+16 2.7289E+14 2.0626E+22 Elemental I (atoms) 4.1477E-34 5.7607E-36 3.7608E+18 Organic I (atoms) 1.5702E-34 2.1808E-36 1.4237E+18 Aerosols (kg) 2.1019E-44 2.9194E-46 5.9065E-15 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 1.0616E+02 1.3047E-06 9.1361E+18 3.9279E+12 Cs-134 1.2309E+04 9.5133E-03 4.2754E+22 4.5542E+14 Cs-136 3.0356E+03 4.1418E-05 1.8340E+20 1.1232E+14 Cs-137 6.6623E+03 7.6594E-02 3.3669E+23 2.4650E+14 Cs-134m 1.0010E-04 1.2412E-14 5.5782E+10 3.7035E+06 Ba-137m 7.3853E+03 1.3732E-08 6.0364E+16 2.7326E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 8.6150E-02 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup

Numerical Applications Inc. Attachment 5 Page 205 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 24.0000 Ci kg Atoms Bq I-131 5.6275E-02 4.5392E-10 2.0867E+15 2.0822E+09 I-132 4.3194E-05 4.1846E-15 1.9091E+10 1.5982E+06 I-133 8.0951E-03 7.1460E-12 3.2357E+13 2.9952E+08 I-135 4.3100E-05 1.2273E-14 5.4747E+10 1.5947E+06 I-130 3.9540E-05 2.0273E-14 9.3914E+10 1.4630E+06 Br-82 7.6719E-05 7.0863E-14 5.2042E+11 2.8386E+06 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.5377E+15 Organic I (atoms) 5.8211E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 1.0616E+02 1.3047E-06 9.1361E+18 3.9279E+12 I-131 1.2222E+02 9.8588E-07 4.5321E+18 4.5223E+12 I-132 8.9935E-02 8.7128E-12 3.9750E+13 3.3276E+09 I-133 1.7582E+01 1.5521E-08 7.0277E+16 6.5054E+11 I-135 9.3611E-02 2.6656E-11 1.1891E+14 3.4636E+09 Cs-134 1.2309E+04 9.5133E-03 4.2754E+22 4.5542E+14 Cs-136 3.0356E+03 4.1418E-05 1.8340E+20 1.1232E+14 Cs-137 6.6623E+03 7.6594E-02 3.3669E+23 2.4650E+14 I-130 8.5878E-02 4.4033E-11 2.0398E+14 3.1775E+09 Cs-134m 1.0010E-04 1.2412E-14 5.5782E+10 3.7035E+06 Ba-137m 7.3853E+03 1.3732E-08 6.0364E+16 2.7326E+14 Br-82 1.6663E-01 1.5391E-10 1.1303E+15 6.1653E+09 Br-83 1.0858E-08 6.8733E-19 4.9870E+06 4.0176E+02 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.3396E+18 Organic I (atoms) 1.2643E+18 Aerosols (kg) 8.6150E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 4.3459E-03 2.3217E-11 1.0513E+14 1.6080E+08 Xe-135 3.0700E-04 1.2022E-13 5.3626E+11 1.1359E+07 Xe-131m 1.5050E-04 1.7968E-12 8.2601E+12 5.5686E+06 Xe-133m 3.1011E-04 6.9112E-13 3.1294E+12 1.1474E+07 Xe-135m 8.5895E-04 9.4294E-15 4.2063E+10 3.1781E+07 Control Room Transport Group Inventory:

Overlying

Numerical Applications Inc. Attachment 5 Page 206 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 24.0000 Atmosphere Sump Pool Noble gases (atoms) 1.1709E+14 0.0000E+00 0.0000E+00 Elemental I (atoms) 7.8107E-33 0.0000E+00 0.0000E+00 Organic I (atoms) 2.9569E-33 0.0000E+00 0.0000E+00 Aerosols (kg) 3.9937E-43 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 24.0000 Ci kg Atoms Bq I-131 6.6301E-02 5.3480E-10 2.4585E+15 2.4531E+09 I-132 4.4065E-05 4.2690E-15 1.9476E+10 1.6304E+06 I-133 9.5379E-03 8.4197E-12 3.8124E+13 3.5290E+08 I-135 5.0782E-05 1.4460E-14 6.4505E+10 1.8789E+06 I-130 4.6587E-05 2.3887E-14 1.1065E+11 1.7237E+06 Br-82 9.0393E-05 8.3493E-14 6.1318E+11 3.3445E+06 Deposition Recirculating Time (h) = 24.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 1.8116E+15 Organic I (atoms) 0.0000E+00 6.8581E+14 Aerosols (kg) 0.0000E+00 3.2881E-38 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 24.0000 Ci kg Atoms Bq I-131 5.6275E-02 4.5392E-10 2.0867E+15 2.0822E+09 I-132 4.3194E-05 4.1846E-15 1.9091E+10 1.5982E+06 I-133 8.0951E-03 7.1460E-12 3.2357E+13 2.9952E+08 I-135 4.3100E-05 1.2273E-14 5.4747E+10 1.5947E+06 I-130 3.9540E-05 2.0273E-14 9.3914E+10 1.4630E+06 Br-82 7.6719E-05 7.0863E-14 5.2042E+11 2.8386E+06 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.5377E+15 Organic I (atoms) 5.8211E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq I-131 1.2258E-01 9.8872E-10 4.5452E+15 4.5353E+09

Numerical Applications Inc. Attachment 5 Page 207 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 I-132 8.7259E-05 8.4536E-15 3.8567E+10 3.2286E+06 I-133 1.7633E-02 1.5566E-11 7.0481E+13 6.5242E+08 I-135 9.3882E-05 2.6733E-14 1.1925E+11 3.4736E+06 I-130 8.6127E-05 4.4160E-14 2.0457E+11 3.1867E+06 Br-82 1.6711E-04 1.5436E-13 1.1336E+12 6.1831E+06 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 24.0000 Ci kg Atoms Bq Xe-133 3.6411E-01 1.9452E-09 8.8079E+15 1.3472E+10 Xe-135 2.3407E-02 9.1658E-12 4.0887E+13 8.6606E+08 Kr-83m 1.5971E-08 7.7408E-19 5.6164E+06 5.9092E+02 Xe-131m 1.2750E-02 1.5221E-10 6.9973E+14 4.7173E+08 Xe-133m 2.6068E-02 5.8097E-11 2.6306E+14 9.6453E+08 Xe-135m 1.5199E-01 1.6685E-12 7.4428E+12 5.6235E+09 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 24.0000 Atmosphere Sump Pool Noble gases (atoms) 9.8190E+15 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 8.9131E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 24.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 24.0000 Ci kg Atoms Bq Rb-86 1.0616E+02 1.3047E-06 9.1361E+18 3.9279E+12 I-131 1.2222E+02 9.8588E-07 4.5321E+18 4.5223E+12 I-132 8.9935E-02 8.7128E-12 3.9750E+13 3.3276E+09 I-133 1.7582E+01 1.5521E-08 7.0277E+16 6.5054E+11 I-135 9.3611E-02 2.6656E-11 1.1891E+14 3.4636E+09 Cs-134 1.2309E+04 9.5133E-03 4.2754E+22 4.5542E+14 Cs-136 3.0356E+03 4.1418E-05 1.8340E+20 1.1232E+14 Cs-137 6.6623E+03 7.6594E-02 3.3669E+23 2.4650E+14 I-130 8.5878E-02 4.4033E-11 2.0398E+14 3.1775E+09 Cs-134m 1.0010E-04 1.2412E-14 5.5782E+10 3.7035E+06 Ba-137m 7.3853E+03 1.3732E-08 6.0364E+16 2.7326E+14 Br-82 1.6663E-01 1.5391E-10 1.1303E+15 6.1653E+09 Br-83 1.0858E-08 6.8733E-19 4.9870E+06 4.0176E+02 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 24.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 3.3396E+18 Organic I (atoms) 1.2643E+18 Aerosols (kg) 8.6150E-02 Detailed model information at time (H) = 96.0000 EAB Doses:

Time (h) = 96.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 9.7780E-03 2.6903E-38 2.2081E-02 9.7780E-03 Accumulated dose (rem) 4.1304E-01 3.2050E+01 1.1430E+00 1.3955E+00 LPZ Doses:

Time (h) = 96.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 1.5728E-04 4.3275E-40 3.5518E-04 1.5728E-04 Accumulated dose (rem) 4.5018E-02 3.9387E+00 1.3021E-01 1.6576E-01 Control Room Doses:

Numerical Applications Inc. Attachment 5 Page 208 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 96.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 7.1654E-05 6.3848E-35 6.3460E-03 7.1654E-05 Accumulated dose (rem) 3.5209E-02 6.2665E+01 3.6066E+00 1.9558E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 3.3053E-02 1.7658E-10 7.9955E+14 1.2230E+09 Xe-135 1.2313E-05 4.8214E-15 2.1508E+10 4.5557E+05 Xe-131m 9.8440E-03 1.1752E-10 5.4027E+14 3.6423E+08 Xe-133m 2.3664E-03 5.2738E-12 2.3879E+13 8.7556E+07 Xe-135m 7.9948E-05 8.7766E-16 3.9151E+09 2.9581E+06 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 96.0000 Atmosphere Sump Pool Noble gases (atoms) 1.3637E+15 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 6.7874E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 96.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 9.4964E+01 1.1671E-06 8.1726E+18 3.5137E+12 Cs-134 1.2275E+04 9.4871E-03 4.2636E+22 4.5416E+14 Cs-136 2.5900E+03 3.5339E-05 1.5648E+20 9.5831E+13 Cs-137 6.6610E+03 7.6579E-02 3.3662E+23 2.4646E+14 Ba-137m 7.3839E+03 1.3730E-08 6.0352E+16 2.7320E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 8.6103E-02 Environment Integral Nuclide Release:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 4.0614E+04 2.1698E-04 9.8246E+20 1.5027E+15 Xe-135 3.4893E+00 1.3663E-09 6.0951E+15 1.2910E+11 Xe-131m 4.3126E+02 5.1488E-06 2.3669E+19 1.5957E+13 Xe-133m 5.5327E+02 1.2330E-06 5.5831E+18 2.0471E+13 Xe-135m 2.9948E-03 3.2876E-14 1.4666E+11 1.1081E+08 Environment Transport Group Inventory:

Present Release Integral Time (h) = 96.0000 Release Rate/s Release Noble gases (atoms) 2.7284E+15 3.7894E+13 2.0166E+22 Elemental I (atoms) 0.0000E+00 0.0000E+00 2.8639E+18 Organic I (atoms) 0.0000E+00 0.0000E+00 1.0842E+18 Aerosols (kg) 0.0000E+00 0.0000E+00 1.3791E-22 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 9.4964E+01 1.1671E-06 8.1726E+18 3.5137E+12 Cs-134 1.2275E+04 9.4871E-03 4.2636E+22 4.5416E+14 Cs-136 2.5900E+03 3.5339E-05 1.5648E+20 9.5831E+13 Cs-137 6.6610E+03 7.6579E-02 3.3662E+23 2.4646E+14

Numerical Applications Inc. Attachment 5 Page 209 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Ba-137m 7.3839E+03 1.3730E-08 6.0352E+16 2.7320E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 8.6103E-02 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 96.0000 Ci kg Atoms Bq I-131 4.3450E-02 3.5048E-10 1.6112E+15 1.6077E+09 I-133 7.3484E-04 6.4869E-13 2.9372E+12 2.7189E+07 I-135 2.2672E-08 6.4557E-18 2.8798E+07 8.3885E+02 I-130 6.9737E-07 3.5756E-16 1.6564E+09 2.5803E+04 Br-82 1.8660E-05 1.7235E-14 1.2658E+11 6.9041E+05 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.1709E+15 Organic I (atoms) 4.4328E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 9.4964E+01 1.1671E-06 8.1726E+18 3.5137E+12 I-131 9.4370E+01 7.6120E-07 3.4993E+18 3.4917E+12 I-133 1.5960E+00 1.4089E-09 6.3795E+15 5.9053E+10 I-135 4.9241E-05 1.4021E-14 6.2548E+10 1.8219E+06 Cs-134 1.2275E+04 9.4871E-03 4.2636E+22 4.5416E+14 Cs-136 2.5900E+03 3.5339E-05 1.5648E+20 9.5831E+13 Cs-137 6.6610E+03 7.6579E-02 3.3662E+23 2.4646E+14 I-130 1.5146E-03 7.7661E-13 3.5976E+12 5.6042E+07 Ba-137m 7.3839E+03 1.3730E-08 6.0352E+16 2.7320E+14 Br-82 4.0528E-02 3.7434E-11 2.7492E+14 1.4995E+09 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway

Numerical Applications Inc. Attachment 5 Page 210 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.5432E+18 Organic I (atoms) 9.6276E+17 Aerosols (kg) 8.6103E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 2.9775E-04 1.5907E-12 7.2026E+12 1.1017E+07 Xe-135 1.2188E-07 4.7727E-17 2.1290E+08 4.5096E+03 Xe-131m 8.7706E-05 1.0471E-12 4.8135E+12 3.2451E+06 Xe-133m 2.1247E-05 4.7351E-14 2.1440E+11 7.8613E+05 Xe-135m 3.4107E-07 3.7442E-18 1.6702E+07 1.2620E+04 Control Room Transport Group Inventory:

Overlying Time (h) = 96.0000 Atmosphere Sump Pool Noble gases (atoms) 1.2231E+13 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 96.0000 Ci kg Atoms Bq I-131 5.1191E-02 4.1292E-10 1.8982E+15 1.8941E+09 I-133 8.6582E-04 7.6431E-13 3.4607E+12 3.2035E+07 I-135 2.6713E-08 7.6064E-18 3.3931E+07 9.8836E+02 I-130 8.2167E-07 4.2129E-16 1.9516E+09 3.0402E+04 Br-82 2.1985E-05 2.0307E-14 1.4914E+11 8.1346E+05 Deposition Recirculating Time (h) = 96.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 1.3796E+15 Organic I (atoms) 0.0000E+00 5.2226E+14 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 96.0000 Ci kg Atoms Bq I-131 4.3450E-02 3.5048E-10 1.6112E+15 1.6077E+09 I-133 7.3484E-04 6.4869E-13 2.9372E+12 2.7189E+07 I-135 2.2672E-08 6.4557E-18 2.8798E+07 8.3885E+02 I-130 6.9737E-07 3.5756E-16 1.6564E+09 2.5803E+04 Br-82 1.8660E-05 1.7235E-14 1.2658E+11 6.9041E+05 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.1709E+15 Organic I (atoms) 4.4328E+14 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 211 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq I-131 9.4642E-02 7.6339E-10 3.5094E+15 3.5017E+09 I-133 1.6007E-03 1.4130E-12 6.3980E+12 5.9225E+07 I-135 4.9384E-08 1.4062E-17 6.2729E+07 1.8272E+03 I-130 1.5190E-06 7.7886E-16 3.6080E+09 5.6204E+04 Br-82 4.0645E-05 3.7543E-14 2.7572E+11 1.5039E+06 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 96.0000 Ci kg Atoms Bq Xe-133 3.3053E-02 1.7658E-10 7.9955E+14 1.2230E+09 Xe-135 1.2313E-05 4.8214E-15 2.1508E+10 4.5557E+05 Xe-131m 9.8440E-03 1.1752E-10 5.4027E+14 3.6423E+08 Xe-133m 2.3664E-03 5.2738E-12 2.3879E+13 8.7556E+07 Xe-135m 7.9948E-05 8.7766E-16 3.9151E+09 2.9581E+06 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 96.0000 Atmosphere Sump Pool Noble gases (atoms) 1.3637E+15 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 6.7874E+20 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 96.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 96.0000 Ci kg Atoms Bq Rb-86 9.4964E+01 1.1671E-06 8.1726E+18 3.5137E+12 I-131 9.4370E+01 7.6120E-07 3.4993E+18 3.4917E+12 I-133 1.5960E+00 1.4089E-09 6.3795E+15 5.9053E+10 I-135 4.9241E-05 1.4021E-14 6.2548E+10 1.8219E+06 Cs-134 1.2275E+04 9.4871E-03 4.2636E+22 4.5416E+14 Cs-136 2.5900E+03 3.5339E-05 1.5648E+20 9.5831E+13 Cs-137 6.6610E+03 7.6579E-02 3.3662E+23 2.4646E+14 I-130 1.5146E-03 7.7661E-13 3.5976E+12 5.6042E+07 Ba-137m 7.3839E+03 1.3730E-08 6.0352E+16 2.7320E+14 Br-82 4.0528E-02 3.7434E-11 2.7492E+14 1.4995E+09 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 96.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.5432E+18 Organic I (atoms) 9.6276E+17 Aerosols (kg) 8.6103E-02 Detailed model information at time (H) = 720.0000 EAB Doses:

Numerical Applications Inc. Attachment 5 Page 212 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 720.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 5.2148E-04 5.5873-125 3.4903E-03 5.2148E-04 Accumulated dose (rem) 4.1356E-01 3.2050E+01 1.1465E+00 1.3961E+00 LPZ Doses:

Time (h) = 720.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.4574E-06 2.6330-127 1.6448E-05 2.4574E-06 Accumulated dose (rem) 4.5021E-02 3.9387E+00 1.3023E-01 1.6576E-01 Control Room Doses:

Time (h) = 720.0000 Whole Body Thyroid Skin TEDE Delta dose (rem) 2.7563E-06 8.8400-122 6.2322E-04 2.7563E-06 Accumulated dose (rem) 3.5212E-02 6.2665E+01 3.6073E+00 1.9558E+00 Fuel Pool-Unfiltered Compartment Atmosphere Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-133 3.0783E-11 1.6445E-19 7.4464E+05 1.1390E+00 Xe-131m 1.0464E-03 1.2492E-11 5.7429E+13 3.8716E+07 Fuel Pool-Unfiltered Transport Group Inventory:

Overlying Time (h) = 720.0000 Atmosphere Sump Pool Noble gases (atoms) 5.7429E+13 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 7.2011E+19 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 720.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered Time (h) = 720.0000 Ci kg Atoms Bq Rb-86 3.6151E+01 4.4429E-07 3.1111E+18 1.3376E+12 Cs-134 1.1984E+04 9.2628E-03 4.1628E+22 4.4342E+14 Cs-136 6.5439E+02 8.9287E-06 3.9537E+19 2.4213E+13 Cs-137 6.6501E+03 7.6454E-02 3.3607E+23 2.4605E+14 Ba-137m 7.3718E+03 1.3707E-08 6.0253E+16 2.7276E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 8.5726E-02 Environment Integral Nuclide Release:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-133 1.3242E+03 7.0744E-06 3.2032E+19 4.8995E+13 Xe-131m 1.9138E+02 2.2848E-06 1.0503E+19 7.0811E+12 Environment Transport Group Inventory:

Present Release Integral Time (h) = 720.0000 Release Rate/s Release Noble gases (atoms) 1.1486E+14 1.5953E+12 1.9109E+22 Elemental I (atoms) 0.0000E+00 0.0000E+00 3.0384E+17 Organic I (atoms) 0.0000E+00 0.0000E+00 1.1502E+17 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Unfiltered

Numerical Applications Inc. Attachment 5 Page 213 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 720.0000 Ci kg Atoms Bq Rb-86 3.6151E+01 4.4429E-07 3.1111E+18 1.3376E+12 Cs-134 1.1984E+04 9.2628E-03 4.1628E+22 4.4342E+14 Cs-136 6.5439E+02 8.9287E-06 3.9537E+19 2.4213E+13 Cs-137 6.6501E+03 7.6454E-02 3.3607E+23 2.4605E+14 Ba-137m 7.3718E+03 1.3707E-08 6.0253E+16 2.7276E+14 Fuel Pool Release-Unfiltered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 8.5726E-02 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 720.0000 Ci kg Atoms Bq I-131 4.6186E-03 3.7255E-11 1.7126E+14 1.7089E+08 Br-82 8.9039E-11 8.2243E-20 6.0399E+05 3.2944E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.2423E+14 Organic I (atoms) 4.7030E+13 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 720.0000 Ci kg Atoms Bq Rb-86 3.6151E+01 4.4429E-07 3.1111E+18 1.3376E+12 I-131 1.0031E+01 8.0913E-08 3.7196E+17 3.7115E+11 I-133 1.4864E-09 1.3122E-18 5.9414E+06 5.4998E+01 Cs-134 1.1984E+04 9.2628E-03 4.1628E+22 4.4342E+14 Cs-136 6.5439E+02 8.9287E-06 3.9537E+19 2.4213E+13 Cs-137 6.6501E+03 7.6454E-02 3.3607E+23 2.4605E+14 Ba-137m 7.3718E+03 1.3707E-08 6.0253E+16 2.7276E+14 Br-82 1.9339E-07 1.7863E-16 1.3118E+09 7.1553E+03 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway

Numerical Applications Inc. Attachment 5 Page 214 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.6982E+17 Organic I (atoms) 1.0214E+17 Aerosols (kg) 8.5726E-02 Control Room Compartment Atmosphere Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-131m 7.0858E-06 8.4595E-14 3.8889E+11 2.6217E+05 Control Room Transport Group Inventory:

Overlying Time (h) = 720.0000 Atmosphere Sump Pool Noble gases (atoms) 3.8889E+11 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Recirculating Filter Inventory Time (h) = 720.0000 Ci kg Atoms Bq I-131 5.4415E-03 4.3892E-11 2.0177E+14 2.0133E+08 Br-82 1.0491E-10 9.6901E-20 7.1165E+05 3.8816E+00 Deposition Recirculating Time (h) = 720.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 1.4636E+14 Organic I (atoms) 0.0000E+00 5.5409E+13 Aerosols (kg) 0.0000E+00 0.0000E+00 Control Room Unfiltered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Filter Pathway Nuclide Inventory for Control Room Filtered Makeup Time (h) = 720.0000 Ci kg Atoms Bq I-131 4.6186E-03 3.7255E-11 1.7126E+14 1.7089E+08 Br-82 8.9039E-11 8.2243E-20 6.0399E+05 3.2944E+00 Control Room Filtered Makeup Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 1.2423E+14 Organic I (atoms) 4.7030E+13 Aerosols (kg) 0.0000E+00 Control Room Unfiltered Inleakage Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00 Aerosols (kg) 0.0000E+00 Control Room Exhaust Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 0.0000E+00 Organic I (atoms) 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 215 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Aerosols (kg) 0.0000E+00 Control Room Total Filter Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq I-131 1.0060E-02 8.1146E-11 3.7303E+14 3.7222E+08 Br-82 1.9395E-10 1.7914E-19 1.3156E+06 7.1761E+00 Fuel Pool-Filtered Compartment Atmosphere Nuclide Inventory:

Time (h) = 720.0000 Ci kg Atoms Bq Xe-133 3.0783E-11 1.6445E-19 7.4464E+05 1.1390E+00 Xe-131m 1.0464E-03 1.2492E-11 5.7429E+13 3.8716E+07 Fuel Pool-Filtered Transport Group Inventory:

Overlying Time (h) = 720.0000 Atmosphere Sump Pool Noble gases (atoms) 5.7429E+13 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 7.2011E+19 Organic I (atoms) 0.0000E+00 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 0.0000E+00 Deposition Recirculating Time (h) = 720.0000 Surfaces Filter Noble gases (atoms) 0.0000E+00 0.0000E+00 Elemental I (atoms) 0.0000E+00 0.0000E+00 Organic I (atoms) 0.0000E+00 0.0000E+00 Aerosols (kg) 0.0000E+00 0.0000E+00 Filter Pathway Nuclide Inventory for Fuel Pool Release-Filtered Time (h) = 720.0000 Ci kg Atoms Bq Rb-86 3.6151E+01 4.4429E-07 3.1111E+18 1.3376E+12 I-131 1.0031E+01 8.0913E-08 3.7196E+17 3.7115E+11 I-133 1.4864E-09 1.3122E-18 5.9414E+06 5.4998E+01 Cs-134 1.1984E+04 9.2628E-03 4.1628E+22 4.4342E+14 Cs-136 6.5439E+02 8.9287E-06 3.9537E+19 2.4213E+13 Cs-137 6.6501E+03 7.6454E-02 3.3607E+23 2.4605E+14 Ba-137m 7.3718E+03 1.3707E-08 6.0253E+16 2.7276E+14 Br-82 1.9339E-07 1.7863E-16 1.3118E+09 7.1553E+03 Fuel Pool Release-Filtered Transport Group Inventory:

Pathway Time (h) = 720.0000 Filter Noble gases (atoms) 0.0000E+00 Elemental I (atoms) 2.6982E+17 Organic I (atoms) 1.0214E+17 Aerosols (kg) 8.5726E-02 Transport Group Totals in Model:

Noble Gases (atoms) 1.9109E+22 Elemental I (atoms) 1.4460E+20 Organic I (atoms) 2.1727E+17 Aerosols (kg) 1.7145E-01 37004 I-131 Summary Fuel Pool-Unfiltered Environment Control Room Time (hr) I-131 (Curies) I-131 (Curies) I-131 (Curies) 0.000 0.0000E+00 0.0000E+00 0.0000E+00 0.001 0.0000E+00 0.0000E+00 0.0000E+00 0.002 0.0000E+00 0.0000E+00 0.0000E+00 0.280 1.1687E-02 2.0584E+01 6.7252E-02 0.333 1.1685E-02 2.4530E+01 7.7946E-02

Numerical Applications Inc. Attachment 5 Page 216 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 0.600 1.1674E-02 4.4319E+01 2.7681E-02 0.860 1.1664E-02 6.3556E+01 1.4128E-02 1.120 1.1653E-02 8.2754E+01 1.0300E-02 1.380 1.1643E-02 1.0191E+02 9.2154E-03 1.640 1.1632E-02 1.2104E+02 8.9039E-03 1.900 1.1622E-02 1.4013E+02 8.8103E-03 2.000 1.1618E-02 1.4746E+02 8.7943E-03 2.002 1.1618E-02 1.4761E+02 8.7758E-03 2.280 0.0000E+00 1.4880E+02 2.4312E-03 2.540 0.0000E+00 1.4867E+02 6.8551E-04 2.800 0.0000E+00 1.4853E+02 1.9329E-04 3.060 0.0000E+00 1.4839E+02 5.4501E-05 3.320 0.0000E+00 1.4825E+02 1.5368E-05 3.580 0.0000E+00 1.4811E+02 4.3331E-06 3.840 0.0000E+00 1.4797E+02 1.2218E-06 4.100 0.0000E+00 1.4784E+02 3.4451E-07 4.360 0.0000E+00 1.4770E+02 9.7139E-08 4.620 0.0000E+00 1.4756E+02 2.7390E-08 4.880 0.0000E+00 1.4742E+02 7.7231E-09 5.140 0.0000E+00 1.4728E+02 2.1776E-09 5.400 0.0000E+00 1.4715E+02 6.1402E-10 5.660 0.0000E+00 1.4701E+02 1.7313E-10 5.920 0.0000E+00 1.4687E+02 4.8818E-11 6.180 0.0000E+00 1.4674E+02 1.3765E-11 6.440 0.0000E+00 1.4660E+02 3.8813E-12 6.700 0.0000E+00 1.4646E+02 1.0944E-12 6.960 0.0000E+00 1.4632E+02 3.0858E-13 7.220 0.0000E+00 1.4619E+02 8.7009E-14 7.480 0.0000E+00 1.4605E+02 2.4534E-14 7.740 0.0000E+00 1.4592E+02 6.9177E-15 8.000 0.0000E+00 1.4578E+02 1.9505E-15 8.260 0.0000E+00 1.4564E+02 5.4999E-16 8.520 0.0000E+00 1.4551E+02 1.5508E-16 8.780 0.0000E+00 1.4537E+02 4.3727E-17 9.040 0.0000E+00 1.4524E+02 1.2330E-17 9.300 0.0000E+00 1.4510E+02 3.4765E-18 9.560 0.0000E+00 1.4496E+02 9.8026E-19 9.820 0.0000E+00 1.4483E+02 2.7640E-19 10.080 0.0000E+00 1.4469E+02 7.7936E-20 24.000 0.0000E+00 1.3764E+02 2.8585E-49 96.000 0.0000E+00 1.0627E+02 1.5962-201 720.000 0.0000E+00 1.1296E+01 0.0000E+00 Fuel Pool-Filtered Time (hr) I-131 (Curies) 0.000 0.0000E+00 0.001 0.0000E+00 0.002 0.0000E+00 0.280 1.1687E-02 0.333 1.1685E-02 0.600 1.1674E-02 0.860 1.1664E-02 1.120 1.1653E-02 1.380 1.1643E-02 1.640 1.1632E-02 1.900 1.1622E-02 2.000 1.1618E-02 2.002 1.1618E-02 2.280 0.0000E+00 2.540 0.0000E+00 2.800 0.0000E+00 3.060 0.0000E+00 3.320 0.0000E+00 3.580 0.0000E+00 3.840 0.0000E+00 4.100 0.0000E+00 4.360 0.0000E+00 4.620 0.0000E+00 4.880 0.0000E+00 5.140 0.0000E+00 5.400 0.0000E+00 5.660 0.0000E+00 5.920 0.0000E+00

Numerical Applications Inc. Attachment 5 Page 217 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 6.180 0.0000E+00 6.440 0.0000E+00 6.700 0.0000E+00 6.960 0.0000E+00 7.220 0.0000E+00 7.480 0.0000E+00 7.740 0.0000E+00 8.000 0.0000E+00 8.260 0.0000E+00 8.520 0.0000E+00 8.780 0.0000E+00 9.040 0.0000E+00 9.300 0.0000E+00 9.560 0.0000E+00 9.820 0.0000E+00 10.080 0.0000E+00 24.000 0.0000E+00 96.000 0.0000E+00 720.000 0.0000E+00 Cumulative Dose Summary EAB LPZ Control Room Time Thyroid TEDE Thyroid TEDE Thyroid TEDE (hr) (rem) (rem) (rem) (rem) (rem) (rem) 0.000 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.001 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.002 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.0000E+00 0.280 4.4208E+00 1.8246E-01 5.4625E-01 2.2545E-02 1.3839E+01 4.2762E-01 0.333 5.2687E+00 2.1747E-01 6.5102E-01 2.6871E-02 1.9294E+01 5.9618E-01 0.600 9.5219E+00 3.9305E-01 1.1765E+00 4.8566E-02 3.7157E+01 1.1495E+00 0.860 1.3659E+01 5.6392E-01 1.6877E+00 6.9679E-02 4.4302E+01 1.3728E+00 1.120 1.7790E+01 7.3455E-01 2.1981E+00 9.0763E-02 4.8628E+01 1.5090E+00 1.380 2.1915E+01 9.0498E-01 2.7078E+00 1.1182E-01 5.2157E+01 1.6204E+00 1.640 2.6035E+01 1.0752E+00 3.2169E+00 1.3286E-01 5.5459E+01 1.7247E+00 1.900 3.0149E+01 1.2452E+00 3.7253E+00 1.5386E-01 5.8693E+01 1.8269E+00 2.000 3.1731E+01 1.3106E+00 3.9207E+00 1.6193E-01 5.9930E+01 1.8660E+00 2.002 3.1762E+01 1.3120E+00 3.9225E+00 1.6202E-01 5.9955E+01 1.8667E+00 2.280 3.2050E+01 1.3256E+00 3.9387E+00 1.6278E-01 6.1963E+01 1.9306E+00 2.540 3.2050E+01 1.3273E+00 3.9387E+00 1.6288E-01 6.2467E+01 1.9472E+00 2.800 3.2050E+01 1.3291E+00 3.9387E+00 1.6298E-01 6.2609E+01 1.9522E+00 3.060 3.2050E+01 1.3307E+00 3.9387E+00 1.6307E-01 6.2649E+01 1.9537E+00 3.320 3.2050E+01 1.3323E+00 3.9387E+00 1.6316E-01 6.2660E+01 1.9543E+00 3.580 3.2050E+01 1.3339E+00 3.9387E+00 1.6325E-01 6.2663E+01 1.9545E+00 3.840 3.2050E+01 1.3355E+00 3.9387E+00 1.6333E-01 6.2664E+01 1.9546E+00 4.100 3.2050E+01 1.3369E+00 3.9387E+00 1.6342E-01 6.2664E+01 1.9547E+00 4.360 3.2050E+01 1.3384E+00 3.9387E+00 1.6350E-01 6.2665E+01 1.9547E+00 4.620 3.2050E+01 1.3398E+00 3.9387E+00 1.6358E-01 6.2665E+01 1.9548E+00 4.880 3.2050E+01 1.3412E+00 3.9387E+00 1.6366E-01 6.2665E+01 1.9548E+00 5.140 3.2050E+01 1.3425E+00 3.9387E+00 1.6373E-01 6.2665E+01 1.9549E+00 5.400 3.2050E+01 1.3439E+00 3.9387E+00 1.6381E-01 6.2665E+01 1.9549E+00 5.660 3.2050E+01 1.3451E+00 3.9387E+00 1.6388E-01 6.2665E+01 1.9550E+00 5.920 3.2050E+01 1.3464E+00 3.9387E+00 1.6395E-01 6.2665E+01 1.9550E+00 6.180 3.2050E+01 1.3476E+00 3.9387E+00 1.6402E-01 6.2665E+01 1.9551E+00 6.440 3.2050E+01 1.3488E+00 3.9387E+00 1.6408E-01 6.2665E+01 1.9551E+00 6.700 3.2050E+01 1.3499E+00 3.9387E+00 1.6415E-01 6.2665E+01 1.9551E+00 6.960 3.2050E+01 1.3510E+00 3.9387E+00 1.6421E-01 6.2665E+01 1.9552E+00 7.220 3.2050E+01 1.3521E+00 3.9387E+00 1.6427E-01 6.2665E+01 1.9552E+00 7.480 3.2050E+01 1.3532E+00 3.9387E+00 1.6433E-01 6.2665E+01 1.9552E+00 7.740 3.2050E+01 1.3542E+00 3.9387E+00 1.6439E-01 6.2665E+01 1.9553E+00 8.000 3.2050E+01 1.3552E+00 3.9387E+00 1.6444E-01 6.2665E+01 1.9553E+00 8.260 3.2050E+01 1.3562E+00 3.9387E+00 1.6448E-01 6.2665E+01 1.9553E+00 8.520 3.2050E+01 1.3571E+00 3.9387E+00 1.6452E-01 6.2665E+01 1.9554E+00 8.780 3.2050E+01 1.3581E+00 3.9387E+00 1.6455E-01 6.2665E+01 1.9554E+00 9.040 3.2050E+01 1.3590E+00 3.9387E+00 1.6459E-01 6.2665E+01 1.9554E+00 9.300 3.2050E+01 1.3599E+00 3.9387E+00 1.6462E-01 6.2665E+01 1.9554E+00 9.560 3.2050E+01 1.3607E+00 3.9387E+00 1.6465E-01 6.2665E+01 1.9554E+00 9.820 3.2050E+01 1.3616E+00 3.9387E+00 1.6469E-01 6.2665E+01 1.9554E+00 10.080 3.2050E+01 1.3624E+00 3.9387E+00 1.6472E-01 6.2665E+01 1.9554E+00 24.000 3.2050E+01 1.3858E+00 3.9387E+00 1.6560E-01 6.2665E+01 1.9557E+00 96.000 3.2050E+01 1.3955E+00 3.9387E+00 1.6576E-01 6.2665E+01 1.9558E+00

Numerical Applications Inc. Attachment 5 Page 218 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 720.000 3.2050E+01 1.3961E+00 3.9387E+00 1.6576E-01 6.2665E+01 1.9558E+00 Worst Two-Hour Dose (Provided for Dose Location 1)

EAB Time Whole Body Thyroid Skin TEDE (hr) (rem) (rem) (rem) (rem) 0.0 3.3785E-01 3.1731E+01 1.0068E+00 1.3106E+00 30 Day Control Room Skin Dose Control Room Time Skin (hr) (rem) 720.0 3.6073E+00

Numerical Applications Inc. Attachment 6 Page 219 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Attachment 6 FHA Nuclide Inventory File Nuclide Inventory Name:

Palisades AST Design Basis FHA source term Adjusted Power Level:

0.2703E+04 Nuclides:

107 Nuclide 001:

Co-58 7

0.6117120000E+07 0.5800E+02 0.0000E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 002:

Co-60 7

0.1663401096E+09 0.6000E+02 0.0000E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 003:

Kr-85 1

0.3382974720E+09 0.8500E+02 0.2104E+05 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 004:

Kr-85m 1

0.1612800000E+05 0.8500E+02 0.1174E+03 Kr-85 0.2110E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 005:

Kr-87 1

0.4578000000E+04 0.8700E+02 0.1647E-05 Rb-87 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 006:

Kr-88 1

0.1022400000E+05 0.8800E+02 0.4302E+01 Rb-88 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 007:

Rb-86 3

0.1612224000E+07 0.8600E+02 0.1819E+04 none 0.0000E+00

Numerical Applications Inc. Attachment 6 Page 220 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 none 0.0000E+00 none 0.0000E+00 Nuclide 008:

Sr-89 5

0.4363200000E+07 0.8900E+02 0.7020E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 009:

Sr-90 5

0.9189573120E+09 0.9000E+02 0.8456E+05 Y-90 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 010:

Sr-91 5

0.3420000000E+05 0.9100E+02 0.2679E+05 Y-91m 0.5780E+00 Y-91 0.4220E+00 none 0.0000E+00 Nuclide 011:

Sr-92 5

0.9756000000E+04 0.9200E+02 0.4453E+01 Y-92 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 012:

Y-90 9

0.2304000000E+06 0.9000E+02 0.8623E+05 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 013:

Y-91 9

0.5055264000E+07 0.9100E+02 0.9107E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 014:

Y-92 9

0.1274400000E+05 0.9200E+02 0.3229E+03 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 015:

Y-93 9

0.3636000000E+05 0.9300E+02 0.4137E+05 Zr-93 0.1000E+01 none 0.0000E+00

Numerical Applications Inc. Attachment 6 Page 221 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 none 0.0000E+00 Nuclide 016:

Zr-95 9

0.5527872000E+07 0.9500E+02 0.1210E+07 Nb-95m 0.7000E-02 Nb-95 0.9930E+00 none 0.0000E+00 Nuclide 017:

Zr-97 9

0.6084000000E+05 0.9700E+02 0.1684E+06 Nb-97m 0.9470E+00 Nb-97 0.5300E-01 none 0.0000E+00 Nuclide 018:

Nb-95 9

0.3036960000E+07 0.9500E+02 0.1248E+07 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 019:

Mo-99 7

0.2376000000E+06 0.9900E+02 0.8264E+06 Tc-99m 0.8760E+00 Tc-99 0.1240E+00 none 0.0000E+00 Nuclide 020:

Tc-99m 7

0.2167200000E+05 0.9900E+02 0.7956E+06 Tc-99 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 021:

Ru-103 7

0.3393792000E+07 0.1030E+03 0.1216E+07 Rh-103m 0.9970E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 022:

Ru-105 7

0.1598400000E+05 0.1050E+03 0.5426E+03 Rh-105 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 023:

Ru-106 7

0.3181248000E+08 0.1060E+03 0.5771E+06 Rh-106 0.1000E+01 none 0.0000E+00 none 0.0000E+00

Numerical Applications Inc. Attachment 6 Page 222 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Nuclide 024:

Rh-105 7

0.1272960000E+06 0.1050E+03 0.3958E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 025:

Sb-127 4

0.3326400000E+06 0.1270E+03 0.6450E+05 Te-127m 0.1760E+00 Te-127 0.8240E+00 none 0.0000E+00 Nuclide 026:

Sb-129 4

0.1555200000E+05 0.1290E+03 0.1176E+03 Te-129m 0.2250E+00 Te-129 0.7750E+00 none 0.0000E+00 Nuclide 027:

Te-127 4

0.3366000000E+05 0.1270E+03 0.7344E+05 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 028:

Te-127m 4

0.9417600000E+07 0.1270E+03 0.1222E+05 Te-127 0.9760E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 029:

Te-129 4

0.4176000000E+04 0.1290E+03 0.2383E+05 I-129 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 030:

Te-129m 4

0.2903040000E+07 0.1290E+03 0.3637E+05 Te-129 0.6500E+00 I-129 0.3500E+00 none 0.0000E+00 Nuclide 031:

Te-131m 4

0.1080000000E+06 0.1310E+03 0.3690E+05 Te-131 0.2220E+00 I-131 0.7780E+00 none 0.0000E+00 Nuclide 032:

Numerical Applications Inc. Attachment 6 Page 223 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Te-132 4

0.2815200000E+06 0.1320E+03 0.6852E+06 I-132 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 033:

I-131 2

0.6946560000E+06 0.1310E+03 0.1028E+07 Xe-131m 0.1110E-01 none 0.0000E+00 none 0.0000E+00 Nuclide 034:

I-132 2

0.8280000000E+04 0.1320E+03 0.7060E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 035:

I-133 2

0.7488000000E+05 0.1330E+03 0.3019E+06 Xe-133m 0.2900E-01 Xe-133 0.9710E+00 none 0.0000E+00 Nuclide 036:

I-134 2

0.3156000000E+04 0.1340E+03 0.2087E-09 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 037:

I-135 2

0.2379600000E+05 0.1350E+03 0.8949E+04 Xe-135m 0.1540E+00 Xe-135 0.8460E+00 none 0.0000E+00 Nuclide 038:

Xe-133 1

0.4531680000E+06 0.1330E+03 0.1298E+07 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 039:

Xe-135 1

0.3272400000E+05 0.1350E+03 0.8201E+05 Cs-135 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 040:

Cs-134

Numerical Applications Inc. Attachment 6 Page 224 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 3

0.6507177120E+08 0.1340E+03 0.2034E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 041:

Cs-136 3

0.1131840000E+07 0.1360E+03 0.5284E+05 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 042:

Cs-137 3

0.9467280000E+09 0.1370E+03 0.1100E+06 Ba-137m 0.9460E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 043:

Ba-139 6

0.4962000000E+04 0.1390E+03 0.4861E-04 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 044:

Ba-140 6

0.1100736000E+07 0.1400E+03 0.1130E+07 La-140 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 045:

La-140 9

0.1449792000E+06 0.1400E+03 0.1235E+07 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 046:

La-141 9

0.1414800000E+05 0.1410E+03 0.2730E+03 Ce-141 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 047:

La-142 9

0.5550000000E+04 0.1420E+03 0.5794E-03 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 048:

Ce-141 8

Numerical Applications Inc. Attachment 6 Page 225 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 0.2808086400E+07 0.1410E+03 0.1168E+07 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 049:

Ce-143 8

0.1188000000E+06 0.1430E+03 0.4100E+06 Pr-143 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 050:

Ce-144 8

0.2456352000E+08 0.1440E+03 0.1014E+07 Pr-144m 0.1780E-01 Pr-144 0.9822E+00 none 0.0000E+00 Nuclide 051:

Pr-143 9

0.1171584000E+07 0.1430E+03 0.1071E+07 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 052:

Nd-147 9

0.9486720000E+06 0.1470E+03 0.4211E+06 Pm-147 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 053:

Np-239 8

0.2034720000E+06 0.2390E+03 0.1023E+08 Pu-239 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 054:

Pu-238 8

0.2768863824E+10 0.2380E+03 0.4494E+04 U-234 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 055:

Pu-239 8

0.7594336440E+12 0.2390E+03 0.3578E+03 U-235 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 056:

Pu-240 8

0.2062920312E+12

Numerical Applications Inc. Attachment 6 Page 226 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 0.2400E+03 0.5406E+03 U-236 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 057:

Pu-241 8

0.4544294400E+09 0.2410E+03 0.1522E+06 U-237 0.2450E-04 Am-241 0.1000E+01 none 0.0000E+00 Nuclide 058:

Am-241 9

0.1363919472E+11 0.2410E+03 0.1897E+03 Np-237 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 059:

Cm-242 9

0.1406592000E+08 0.2420E+03 0.5649E+05 Pu-238 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 060:

Cm-244 9

0.5715081360E+09 0.2440E+03 0.1339E+05 Pu-240 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 061:

I-130 2

0.4449600000E+05 0.1300E+03 0.2546E+04 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 062:

Kr-83m 1

0.6588000000E+04 0.8300E+02 0.3727E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 063:

Xe-138 1

0.8502000000E+03 0.1380E+03 0.0000E+00 Cs-138 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 064:

Xe-131m 1

0.1028160000E+07 0.1310E+03

Numerical Applications Inc. Attachment 6 Page 227 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 0.8276E+04 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 065:

Xe-133m 1

0.1890432000E+06 0.1330E+03 0.3403E+05 Xe-133 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 066:

Xe-135m 1

0.9174000000E+03 0.1350E+03 0.1434E+04 Xe-135 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 067:

Cs-138 3

0.1932000000E+04 0.1380E+03 0.0000E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 068:

Cs-134m 3

0.1044000000E+05 0.1340E+03 0.5122E+00 Cs-134 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 069:

Rb-88 3

0.1068000000E+04 0.8800E+02 0.4804E+01 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 070:

Rb-89 3

0.9120000000E+03 0.8900E+02 0.0000E+00 Sr-89 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 071:

Sb-124 4

0.5201280000E+07 0.1240E+03 0.1663E+04 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 072:

Sb-125 4

0.8741455200E+08 0.1250E+03 0.1566E+05

Numerical Applications Inc. Attachment 6 Page 228 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Te-125m 0.2280E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 073:

Sb-126 4

0.1071360000E+07 0.1260E+03 0.9900E+03 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 074:

Te-131 4

0.1500000000E+04 0.1310E+03 0.8307E+04 I-131 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 075:

Te-133 4

0.7470000000E+03 0.1330E+03 0.2034E-10 I-133 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 076:

Te-134 4

0.2508000000E+04 0.1340E+03 0.2217E-14 I-134 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 077:

Te-125m 4

0.5011200000E+07 0.1250E+03 0.3417E+04 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 078:

Te-133m 4

0.3324000000E+04 0.1330E+03 0.1213E-09 I-133 0.8700E+00 Te-133 0.1300E+00 none 0.0000E+00 Nuclide 079:

Ba-141 6

0.1096200000E+04 0.1410E+03 0.0000E+00 La-141 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 080:

Ba-137m 6

0.1531200000E+03 0.1370E+03 0.1041E+06 none 0.0000E+00

Numerical Applications Inc. Attachment 6 Page 229 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 none 0.0000E+00 none 0.0000E+00 Nuclide 081:

Pd-109 7

0.4833720000E+05 0.1090E+03 0.2825E+05 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 082:

Rh-106 7

0.2990000000E+02 0.1060E+03 0.5771E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 083:

Rh-103m 7

0.3367200000E+04 0.1030E+03 0.1097E+07 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 084:

Tc-101 7

0.8520000000E+03 0.1010E+03 0.0000E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 085:

Eu-154 9

0.2777068800E+09 0.1540E+03 0.1246E+05 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 086:

Eu-155 9

0.1565256960E+09 0.1550E+03 0.8442E+04 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 087:

Eu-156 9

0.1312416000E+07 0.1560E+03 0.1935E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 088:

La-143 9

0.8538000000E+03 0.1430E+03 0.0000E+00 Ce-143 0.1000E+01 none 0.0000E+00

Numerical Applications Inc. Attachment 6 Page 230 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 none 0.0000E+00 Nuclide 089:

Nb-97 9

0.4326000000E+04 0.9700E+02 0.1692E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 090:

Nb-95m 9

0.3117600000E+06 0.9500E+02 0.8748E+04 Nb-95 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 091:

Pm-147 9

0.8278820780E+08 0.1470E+03 0.1296E+06 Sm-147 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 092:

Pm-148 9

0.4639680000E+06 0.1480E+03 0.1659E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 093:

Pm-149 9

0.1910880000E+06 0.1490E+03 0.2481E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 094:

Pm-151 9

0.1022400000E+06 0.1510E+03 0.5012E+05 Sm-151 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 095:

Pm-148m 9

0.3568320000E+07 0.1480E+03 0.2899E+05 Pm-148 0.4600E-01 none 0.0000E+00 none 0.0000E+00 Nuclide 096:

Pr-144 9

0.1036800000E+04 0.1440E+03 0.1015E+07 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00

Numerical Applications Inc. Attachment 6 Page 231 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Nuclide 097:

Pr-144m 9

0.4320000000E+03 0.1440E+03 0.1217E+05 Pr-144 0.9990E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 098:

Sm-153 9

0.1681200000E+06 0.1530E+03 0.2171E+06 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 099:

Y-94 9

0.1146000000E+04 0.9400E+02 0.0000E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 100:

Y-95 9

0.6420000000E+03 0.9500E+02 0.0000E+00 Zr-95 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 101:

Y-91m 9

0.2982600000E+04 0.9100E+02 0.1702E+05 Y-91 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 102:

Br-82 2

0.1270800000E+06 0.8200E+02 0.2060E+04 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 103:

Br-83 2

0.8604000000E+04 0.8300E+02 0.8833E-01 Kr-83m 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 104:

Br-84 2

0.1908000000E+04 0.8400E+02 0.0000E+00 none 0.0000E+00 none 0.0000E+00 none 0.0000E+00 Nuclide 105:

Numerical Applications Inc. Attachment 6 Page 232 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Am-242 9

0.5767200000E+05 0.2420E+03 0.1138E+05 Cm-242 0.8270E+00 Pu-242 0.1730E+00 none 0.0000E+00 Nuclide 106:

Np-238 8

0.1829088000E+06 0.2380E+03 0.2238E+06 Pu-238 0.1000E+01 none 0.0000E+00 none 0.0000E+00 Nuclide 107:

Pu-243 8

0.1784160000E+05 0.2430E+03 0.5681E+03 Am-243 0.1000E+01 none 0.0000E+00 none 0.0000E+00 End of Nuclear Inventory File

Numerical Applications Inc. Attachment 7 Page 233 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Attachment 7 RADTRAD-NAI Dose Conversion Factor File NAI-1101-001rev0.DCF Includes 107 istopes 9 ORGANS DEFINED IN THIS FILE:

GONADS BREAST LUNGS RED MARR BONE SUR THYROID REMAINDER EFFECTIVE SKIN(FGR) 107 NUCLIDES DEFINED IN THIS FILE:

Co-58 Y Co-60 Y Kr-85 Kr-85m Kr-87 Kr-88 Rb-86 D Sr-89 Y Sr-90 Y Sr-91 Y Sr-92 Y Y-90 Y Y-91 Y Y-92 Y Y-93 Y Zr-95 D Zr-97 Y Nb-95 Y Mo-99 Y Tc-99m D Ru-103 Y Ru-105 Y Ru-106 Y Rh-105 Y Sb-127 W Sb-129 W Te-127 W Te-127m W Te-129 D Te-129m W Te-131m W Te-132 W I-131 D I-132 D I-133 D I-134 D I-135 D Xe-133 Xe-135 Cs-134 D Cs-136 D Cs-137 D Ba-139 D Ba-140 D La-140 W La-141 D La-142 D Ce-141 Y Ce-143 Y Ce-144 Y Pr-143 Y Nd-147 Y Np-239 W Pu-238 W Pu-239 W Pu-240 W Pu-241 W Am-241 W

Numerical Applications Inc. Attachment 7 Page 234 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 Cm-242 W Cm-244 W I-130 D Kr-83m Xe-138 Xe-131m Xe-133m Xe-135m Cs-138 D Cs-134m D Rb-88 D Rb-89 D Sb-124 W Sb-125 W Sb-126 W Te-131 D Te-133 D Te-134 D Te-125m W Te-133m D Ba-141 D Ba-137m Pd-109 Y Rh-106 Rh-103m D Tc-101 D Eu-154 W Eu-155 W Eu-156 W La-143 W Nb-97 Y Nb-95m Y Pm-147 Y Pm-148 Y Pm-149 Y Pm-151 Y Pm-148m Y Pr-144 Y Pr-144m Sm-153 W Y-94 Y Y-95 Y Y-91m Y Br-82 W Br-83 W Br-84 D Am-242 W Np-238 W Pu-243 Y CLOUDSHINE GROUND GROUND GROUND INHALED INHALED INGESTION SHINE 8HR SHINE 7DAY SHINE RATE ACUTE CHRONIC Co-58 GONADS 4.660E-14 2.867E-11 5.828E-10 9.970E-16-1.000E+00 6.170E-10 1.040E-09 BREAST 5.300E-14 2.737E-11 5.565E-10 9.520E-16-1.000E+00 9.370E-10 1.790E-10 LUNGS 4.640E-14 2.617E-11 5.319E-10 9.100E-16-1.000E+00 1.600E-08 8.530E-11 RED MARR 4.530E-14 2.671E-11 5.430E-10 9.290E-16-1.000E+00 9.230E-10 2.600E-10 BONE SUR 7.410E-14 3.795E-11 7.716E-10 1.320E-15-1.000E+00 6.930E-10 1.250E-10 THYROID 4.770E-14 2.720E-11 5.530E-10 9.460E-16-1.000E+00 8.720E-10 6.310E-11 REMAINDER 4.440E-14 2.585E-11 5.255E-10 8.990E-16-1.000E+00 1.890E-09 1.580E-09 EFFECTIVE 4.760E-14 2.732E-11 5.553E-10 9.500E-16-1.000E+00 2.940E-09 8.090E-10 SKIN(FGR) 5.580E-14 3.278E-11 6.664E-10 1.140E-15-1.000E+00 0.000E+00 0.000E+00 Co-60 GONADS 1.230E-13 7.056E-11 1.480E-09 2.450E-15-1.000E+00 4.760E-09 3.190E-09 BREAST 1.390E-13 6.739E-11 1.413E-09 2.340E-15-1.000E+00 1.840E-08 1.100E-09 LUNGS 1.240E-13 6.537E-11 1.371E-09 2.270E-15-1.000E+00 3.450E-07 8.770E-10 RED MARR 1.230E-13 6.710E-11 1.407E-09 2.330E-15-1.000E+00 1.720E-08 1.320E-09 BONE SUR 1.780E-13 8.956E-11 1.879E-09 3.110E-15-1.000E+00 1.350E-08 9.390E-10 THYROID 1.270E-13 6.480E-11 1.359E-09 2.250E-15-1.000E+00 1.620E-08 7.880E-10 REMAINDER 1.200E-13 6.508E-11 1.365E-09 2.260E-15-1.000E+00 3.600E-08 4.970E-09 EFFECTIVE 1.260E-13 6.768E-11 1.419E-09 2.350E-15-1.000E+00 5.910E-08 2.770E-09 SKIN(FGR) 1.450E-13 7.948E-11 1.667E-09 2.760E-15-1.000E+00 0.000E+00 0.000E+00 Kr-85 GONADS 1.170E-16 8.121E-14 1.704E-12 2.820E-18-1.000E+00 0.000E+00 0.000E+00

Numerical Applications Inc. Attachment 7 Page 235 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 BREAST 1.340E-16 7.891E-14 1.656E-12 2.740E-18-1.000E+00 0.000E+00 0.000E+00 LUNGS 1.140E-16 7.056E-14 1.481E-12 2.450E-18-1.000E+00 0.000E+00 0.000E+00 RED MARR 1.090E-16 6.998E-14 1.469E-12 2.430E-18-1.000E+00 0.000E+00 0.000E+00 BONE SUR 2.200E-16 1.287E-13 2.702E-12 4.470E-18-1.000E+00 0.000E+00 0.000E+00 THYROID 1.180E-16 7.459E-14 1.565E-12 2.590E-18-1.000E+00 0.000E+00 0.000E+00 REMAINDER 1.090E-16 6.941E-14 1.457E-12 2.410E-18-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 1.190E-16 7.603E-14 1.596E-12 2.640E-18-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 1.320E-14 2.304E-11 4.835E-10 8.000E-16-1.000E+00 0.000E+00 0.000E+00 Kr-85m GONADS 7.310E-15 2.594E-12 3.653E-12 1.570E-16-1.000E+00 0.000E+00 0.000E+00 BREAST 8.410E-15 2.527E-12 3.560E-12 1.530E-16-1.000E+00 0.000E+00 0.000E+00 LUNGS 7.040E-15 2.379E-12 3.351E-12 1.440E-16-1.000E+00 0.000E+00 0.000E+00 RED MARR 6.430E-15 2.346E-12 3.304E-12 1.420E-16-1.000E+00 0.000E+00 0.000E+00 BONE SUR 1.880E-14 5.286E-12 7.446E-12 3.200E-16-1.000E+00 0.000E+00 0.000E+00 THYROID 7.330E-15 2.395E-12 3.374E-12 1.450E-16-1.000E+00 0.000E+00 0.000E+00 REMAINDER 6.640E-15 2.313E-12 3.257E-12 1.400E-16-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 7.480E-15 2.511E-12 3.537E-12 1.520E-16-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 2.240E-14 2.247E-11 3.164E-11 1.360E-15-1.000E+00 0.000E+00 0.000E+00 Kr-87 GONADS 4.000E-14 4.962E-12 5.026E-12 7.610E-16-1.000E+00 0.000E+00 0.000E+00 BREAST 4.500E-14 4.740E-12 4.802E-12 7.270E-16-1.000E+00 0.000E+00 0.000E+00 LUNGS 4.040E-14 4.603E-12 4.663E-12 7.060E-16-1.000E+00 0.000E+00 0.000E+00 RED MARR 4.000E-14 4.708E-12 4.769E-12 7.220E-16-1.000E+00 0.000E+00 0.000E+00 BONE SUR 6.020E-14 6.514E-12 6.598E-12 9.990E-16-1.000E+00 0.000E+00 0.000E+00 THYROID 4.130E-14 4.473E-12 4.531E-12 6.860E-16-1.000E+00 0.000E+00 0.000E+00 REMAINDER 3.910E-14 4.590E-12 4.650E-12 7.040E-16-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 4.120E-14 4.773E-12 4.835E-12 7.320E-16-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 1.370E-13 8.802E-11 8.916E-11 1.350E-14-1.000E+00 0.000E+00 0.000E+00 Kr-88 GONADS 9.900E-14 2.278E-11 2.655E-11 1.800E-15-1.000E+00 0.000E+00 0.000E+00 BREAST 1.110E-13 2.177E-11 2.537E-11 1.720E-15-1.000E+00 0.000E+00 0.000E+00 LUNGS 1.010E-13 2.139E-11 2.493E-11 1.690E-15-1.000E+00 0.000E+00 0.000E+00 RED MARR 1.000E-13 2.190E-11 2.552E-11 1.730E-15-1.000E+00 0.000E+00 0.000E+00 BONE SUR 1.390E-13 2.886E-11 3.363E-11 2.280E-15-1.000E+00 0.000E+00 0.000E+00 THYROID 1.030E-13 2.012E-11 2.345E-11 1.590E-15-1.000E+00 0.000E+00 0.000E+00 REMAINDER 9.790E-14 2.139E-11 2.493E-11 1.690E-15-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 1.020E-13 2.202E-11 2.567E-11 1.740E-15-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 1.350E-13 5.607E-11 6.534E-11 4.430E-15-1.000E+00 0.000E+00 0.000E+00 Rb-86 GONADS 4.710E-15 2.788E-12 5.187E-11 9.740E-17-1.000E+00 1.340E-09 2.150E-09 BREAST 5.340E-15 2.662E-12 4.953E-11 9.300E-17-1.000E+00 1.330E-09 2.140E-09 LUNGS 4.710E-15 2.553E-12 4.750E-11 8.920E-17-1.000E+00 3.300E-09 2.140E-09 RED MARR 4.640E-15 2.619E-12 4.873E-11 9.150E-17-1.000E+00 2.320E-09 3.720E-09 BONE SUR 7.050E-15 3.635E-12 6.764E-11 1.270E-16-1.000E+00 4.270E-09 6.860E-09 THYROID 4.840E-15 2.599E-12 4.836E-11 9.080E-17-1.000E+00 1.330E-09 2.140E-09 REMAINDER 4.520E-15 2.542E-12 4.729E-11 8.880E-17-1.000E+00 1.380E-09 2.330E-09 EFFECTIVE 4.810E-15 2.665E-12 4.958E-11 9.310E-17-1.000E+00 1.790E-09 2.530E-09 SKIN(FGR) 4.850E-14 2.210E-10 4.111E-09 7.720E-15-1.000E+00 0.000E+00 0.000E+00 Sr-89 GONADS 7.730E-17 7.155E-14 1.436E-12 2.490E-18-1.000E+00 7.950E-12 8.050E-12 BREAST 9.080E-17 7.212E-14 1.447E-12 2.510E-18-1.000E+00 7.960E-12 7.980E-12 LUNGS 7.080E-17 5.689E-14 1.142E-12 1.980E-18-1.000E+00 8.350E-08 7.970E-12 RED MARR 6.390E-17 5.345E-14 1.073E-12 1.860E-18-1.000E+00 1.070E-10 1.080E-10 BONE SUR 1.940E-16 1.560E-13 3.131E-12 5.430E-18-1.000E+00 1.590E-10 1.610E-10 THYROID 7.600E-17 6.063E-14 1.217E-12 2.110E-18-1.000E+00 7.960E-12 7.970E-12 REMAINDER 6.710E-17 5.603E-14 1.124E-12 1.950E-18-1.000E+00 3.970E-09 8.250E-09 EFFECTIVE 7.730E-17 6.523E-14 1.309E-12 2.270E-18-1.000E+00 1.120E-08 2.500E-09 SKIN(FGR) 3.690E-14 1.914E-10 3.841E-09 6.660E-15-1.000E+00 0.000E+00 0.000E+00 Sr-90 GONADS 7.780E-18 9.590E-15 2.014E-13 3.330E-19-1.000E+00 2.690E-10 5.040E-11 BREAST 9.490E-18 1.008E-14 2.116E-13 3.500E-19-1.000E+00 2.690E-10 5.040E-11 LUNGS 6.440E-18 6.307E-15 1.324E-13 2.190E-19-1.000E+00 2.860E-06 5.040E-11 RED MARR 5.440E-18 5.558E-15 1.167E-13 1.930E-19-1.000E+00 3.280E-08 6.450E-09 BONE SUR 2.280E-17 2.393E-14 5.025E-13 8.310E-19-1.000E+00 7.090E-08 1.390E-08 THYROID 7.330E-18 7.171E-15 1.506E-13 2.490E-19-1.000E+00 2.690E-10 5.040E-11 REMAINDER 6.110E-18 6.422E-15 1.348E-13 2.230E-19-1.000E+00 5.730E-09 6.700E-09 EFFECTIVE 7.530E-18 8.179E-15 1.717E-13 2.840E-19-1.000E+00 3.510E-07 3.230E-09 SKIN(FGR) 9.200E-15 4.032E-12 8.465E-11 1.400E-16-1.000E+00 0.000E+00 0.000E+00 Sr-91 GONADS 3.380E-14 2.155E-11 5.062E-11 1.026E-15-1.000E+00 5.650E-11 2.520E-10 BREAST 3.830E-14 2.059E-11 4.838E-11 9.806E-16-1.000E+00 1.740E-11 3.676E-11 LUNGS 3.370E-14 1.970E-11 4.626E-11 9.376E-16-1.000E+00 2.130E-09 1.055E-11 RED MARR 3.310E-14 2.011E-11 4.722E-11 9.570E-16-1.000E+00 2.230E-11 5.659E-11

Numerical Applications Inc. Attachment 7 Page 236 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 BONE SUR 5.200E-14 2.852E-11 6.709E-11 1.360E-15-1.000E+00 1.270E-11 2.070E-11 THYROID 3.470E-14 2.035E-11 4.782E-11 9.693E-16-1.000E+00 9.640E-12 1.968E-12 REMAINDER 3.240E-14 1.948E-11 4.573E-11 9.268E-16-1.000E+00 5.780E-10 2.557E-09 EFFECTIVE 3.450E-14 2.057E-11 4.832E-11 9.793E-16-1.000E+00 4.490E-10 8.455E-10 SKIN(FGR) 8.140E-14 1.748E-10 3.987E-10 8.080E-15-1.000E+00 0.000E+00 0.000E+00 Sr-92 GONADS 6.610E-14 1.593E-11 1.830E-11 1.300E-15-1.000E+00 1.020E-11 8.180E-11 BREAST 7.480E-14 1.520E-11 1.745E-11 1.240E-15-1.000E+00 6.490E-12 1.700E-11 LUNGS 6.670E-14 1.483E-11 1.703E-11 1.210E-15-1.000E+00 1.050E-09 7.220E-12 RED MARR 6.620E-14 1.520E-11 1.745E-11 1.240E-15-1.000E+00 6.980E-12 2.290E-11 BONE SUR 9.490E-14 2.010E-11 2.308E-11 1.640E-15-1.000E+00 4.360E-12 8.490E-12 THYROID 6.820E-14 1.446E-11 1.661E-11 1.180E-15-1.000E+00 3.920E-12 1.300E-12 REMAINDER 6.450E-14 1.471E-11 1.689E-11 1.200E-15-1.000E+00 2.900E-10 1.720E-09 EFFECTIVE 6.790E-14 1.532E-11 1.759E-11 1.250E-15-1.000E+00 2.180E-10 5.430E-10 SKIN(FGR) 8.560E-14 2.280E-11 2.618E-11 1.860E-15-1.000E+00 0.000E+00 0.000E+00 Y-90 GONADS 1.890E-16 1.586E-13 1.601E-12 5.750E-18-1.000E+00 5.170E-13 1.430E-14 BREAST 2.200E-16 1.578E-13 1.593E-12 5.720E-18-1.000E+00 5.170E-13 1.270E-14 LUNGS 1.770E-16 1.313E-13 1.326E-12 4.760E-18-1.000E+00 9.310E-09 1.260E-14 RED MARR 1.620E-16 1.261E-13 1.273E-12 4.570E-18-1.000E+00 1.520E-11 3.700E-13 BONE SUR 4.440E-16 3.228E-13 3.259E-12 1.170E-17-1.000E+00 1.510E-11 3.670E-13 THYROID 1.870E-16 1.385E-13 1.398E-12 5.020E-18-1.000E+00 5.170E-13 1.260E-14 REMAINDER 1.680E-16 1.291E-13 1.303E-12 4.680E-18-1.000E+00 3.870E-09 9.680E-09 EFFECTIVE 1.900E-16 1.468E-13 1.482E-12 5.320E-18-1.000E+00 2.280E-09 2.910E-09 SKIN(FGR) 6.240E-14 2.897E-10 2.924E-09 1.050E-14-1.000E+00 0.000E+00 0.000E+00 Y-91 GONADS 2.560E-16 1.756E-13 3.546E-12 6.110E-18-1.000E+00 8.200E-12 3.540E-12 BREAST 2.930E-16 1.713E-13 3.459E-12 5.960E-18-1.000E+00 8.920E-12 5.540E-13 LUNGS 2.500E-16 1.526E-13 3.082E-12 5.310E-18-1.000E+00 9.870E-08 2.020E-13 RED MARR 2.410E-16 1.521E-13 3.070E-12 5.290E-18-1.000E+00 3.190E-10 6.590E-12 BONE SUR 4.560E-16 2.903E-13 5.862E-12 1.010E-17-1.000E+00 3.180E-10 6.130E-12 THYROID 2.600E-16 1.564E-13 3.157E-12 5.440E-18-1.000E+00 8.500E-12 1.290E-13 REMAINDER 2.390E-16 1.509E-13 3.047E-12 5.250E-18-1.000E+00 4.200E-09 8.570E-09 EFFECTIVE 2.600E-16 1.650E-13 3.332E-12 5.740E-18-1.000E+00 1.320E-08 2.570E-09 SKIN(FGR) 3.850E-14 1.989E-10 4.016E-09 6.920E-15-1.000E+00 0.000E+00 0.000E+00 Y-92 GONADS 1.270E-14 3.855E-12 4.872E-12 2.650E-16-1.000E+00 2.610E-12 1.960E-11 BREAST 1.440E-14 3.680E-12 4.652E-12 2.530E-16-1.000E+00 1.500E-12 3.550E-12 LUNGS 1.270E-14 3.535E-12 4.468E-12 2.430E-16-1.000E+00 1.240E-09 1.390E-12 RED MARR 1.250E-14 3.608E-12 4.560E-12 2.480E-16-1.000E+00 2.070E-12 4.910E-12 BONE SUR 1.950E-14 5.091E-12 6.435E-12 3.500E-16-1.000E+00 1.510E-12 1.750E-12 THYROID 1.300E-14 3.579E-12 4.523E-12 2.460E-16-1.000E+00 1.050E-12 1.770E-13 REMAINDER 1.220E-14 3.506E-12 4.431E-12 2.410E-16-1.000E+00 2.030E-10 1.700E-09 EFFECTIVE 1.300E-14 3.680E-12 4.652E-12 2.530E-16-1.000E+00 2.110E-10 5.150E-10 SKIN(FGR) 1.140E-13 2.022E-10 2.556E-10 1.390E-14-1.000E+00 0.000E+00 0.000E+00 Y-93 GONADS 4.670E-15 2.108E-12 4.989E-12 9.510E-17-1.000E+00 5.310E-12 2.200E-11 BREAST 5.300E-15 2.026E-12 4.794E-12 9.140E-17-1.000E+00 1.740E-12 3.130E-12 LUNGS 4.680E-15 1.937E-12 4.585E-12 8.740E-17-1.000E+00 2.520E-09 8.670E-13 RED MARR 4.580E-15 1.972E-12 4.669E-12 8.900E-17-1.000E+00 4.040E-12 4.930E-12 BONE SUR 7.580E-15 2.948E-12 6.977E-12 1.330E-16-1.000E+00 3.140E-12 1.730E-12 THYROID 4.790E-15 1.908E-12 4.516E-12 8.610E-17-1.000E+00 9.260E-13 1.260E-13 REMAINDER 4.510E-15 1.919E-12 4.543E-12 8.660E-17-1.000E+00 9.250E-10 4.090E-09 EFFECTIVE 4.800E-15 2.021E-12 4.784E-12 9.120E-17-1.000E+00 5.820E-10 1.230E-09 SKIN(FGR) 8.500E-14 2.726E-10 6.452E-10 1.230E-14-1.000E+00 0.000E+00 0.000E+00 Zr-95 GONADS 3.530E-14 2.182E-11 4.421E-10 7.590E-16-1.000E+00 1.880E-09 8.160E-10 BREAST 4.010E-14 2.084E-11 4.223E-10 7.250E-16-1.000E+00 1.910E-09 1.050E-10 LUNGS 3.510E-14 1.989E-11 4.030E-10 6.920E-16-1.000E+00 2.170E-09 2.340E-11 RED MARR 3.430E-14 2.030E-11 4.112E-10 7.060E-16-1.000E+00 1.300E-08 2.140E-10 BONE SUR 5.620E-14 2.875E-11 5.824E-10 1.000E-15-1.000E+00 1.030E-07 4.860E-10 THYROID 3.610E-14 2.076E-11 4.205E-10 7.220E-16-1.000E+00 1.440E-09 8.270E-12 REMAINDER 3.360E-14 1.963E-11 3.978E-10 6.830E-16-1.000E+00 2.280E-09 2.530E-09 EFFECTIVE 3.600E-14 2.078E-11 4.211E-10 7.230E-16-1.000E+00 6.390E-09 1.020E-09 SKIN(FGR) 4.500E-14 2.561E-11 5.190E-10 8.910E-16-1.000E+00 0.000E+00 0.000E+00 Zr-97 GONADS 8.800E-15 2.179E-11 7.799E-11 9.253E-16-1.000E+00 1.840E-10 6.228E-10 BREAST 9.990E-15 2.083E-11 7.455E-11 8.846E-16-1.000E+00 4.700E-11 8.137E-11 LUNGS 8.810E-15 1.992E-11 7.127E-11 8.456E-16-1.000E+00 4.100E-09 1.770E-11 RED MARR 8.640E-15 2.034E-11 7.279E-11 8.634E-16-1.000E+00 6.370E-11 1.302E-10 BONE SUR 1.380E-14 2.881E-11 1.031E-10 1.224E-15-1.000E+00 3.500E-11 4.558E-11 THYROID 9.030E-15 2.061E-11 7.377E-11 8.755E-16-1.000E+00 2.310E-11 2.671E-12 REMAINDER 8.480E-15 1.966E-11 7.035E-11 8.345E-16-1.000E+00 2.040E-09 6.990E-09

Numerical Applications Inc. Attachment 7 Page 237 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 EFFECTIVE 9.020E-15 2.078E-11 7.438E-11 8.824E-16-1.000E+00 1.170E-09 2.283E-09 SKIN(FGR) 5.550E-14 2.281E-10 8.148E-10 9.587E-15-1.000E+00 0.000E+00 0.000E+00 Nb-95 GONADS 3.660E-14 2.253E-11 4.435E-10 7.850E-16-1.000E+00 4.320E-10 8.050E-10 BREAST 4.160E-14 2.150E-11 4.231E-10 7.490E-16-1.000E+00 4.070E-10 1.070E-10 LUNGS 3.650E-14 2.055E-11 4.045E-10 7.160E-16-1.000E+00 8.320E-09 2.740E-11 RED MARR 3.560E-14 2.101E-11 4.135E-10 7.320E-16-1.000E+00 4.420E-10 1.990E-10 BONE SUR 5.790E-14 2.957E-11 5.819E-10 1.030E-15-1.000E+00 5.130E-10 2.940E-10 THYROID 3.750E-14 2.144E-11 4.220E-10 7.470E-16-1.000E+00 3.580E-10 1.180E-11 REMAINDER 3.490E-14 2.032E-11 4.000E-10 7.080E-16-1.000E+00 1.070E-09 1.470E-09 EFFECTIVE 3.740E-14 2.147E-11 4.226E-10 7.480E-16-1.000E+00 1.570E-09 6.950E-10 SKIN(FGR) 4.300E-14 2.598E-11 5.112E-10 9.050E-16-1.000E+00 0.000E+00 0.000E+00 Mo-99 GONADS 7.130E-15 4.282E-12 4.403E-11 1.550E-16-1.000E+00 9.510E-11 2.180E-10 BREAST 8.130E-15 4.116E-12 4.233E-11 1.490E-16-1.000E+00 2.750E-11 3.430E-11 LUNGS 7.060E-15 3.867E-12 3.977E-11 1.400E-16-1.000E+00 4.290E-09 1.510E-11 RED MARR 6.820E-15 3.923E-12 4.034E-11 1.420E-16-1.000E+00 5.240E-11 8.320E-11 BONE SUR 1.240E-14 6.105E-12 6.278E-11 2.210E-16-1.000E+00 4.130E-11 6.320E-11 THYROID 7.270E-15 4.033E-12 4.147E-11 1.460E-16-1.000E+00 1.520E-11 1.030E-11 REMAINDER 6.740E-15 3.812E-12 3.920E-11 1.380E-16-1.000E+00 1.740E-09 4.280E-09 EFFECTIVE 7.280E-15 4.061E-12 4.176E-11 1.470E-16-1.000E+00 1.070E-09 1.360E-09 SKIN(FGR) 3.140E-14 1.039E-10 1.068E-09 3.760E-15-1.000E+00 0.000E+00 0.000E+00 Tc-99m GONADS 5.750E-15 2.334E-12 3.877E-12 1.240E-16-1.000E+00 2.770E-12 9.750E-12 BREAST 6.650E-15 2.258E-12 3.752E-12 1.200E-16-1.000E+00 2.150E-12 3.570E-12 LUNGS 5.490E-15 2.127E-12 3.533E-12 1.130E-16-1.000E+00 2.280E-11 3.140E-12 RED MARR 4.910E-15 2.070E-12 3.439E-12 1.100E-16-1.000E+00 3.360E-12 6.290E-12 BONE SUR 1.630E-14 5.383E-12 8.942E-12 2.860E-16-1.000E+00 2.620E-12 4.060E-12 THYROID 5.750E-15 2.145E-12 3.564E-12 1.140E-16-1.000E+00 5.010E-11 8.460E-11 REMAINDER 5.150E-15 2.070E-12 3.439E-12 1.100E-16-1.000E+00 1.020E-11 3.340E-11 EFFECTIVE 5.890E-15 2.277E-12 3.783E-12 1.210E-16-1.000E+00 8.800E-12 1.680E-11 SKIN(FGR) 7.140E-15 2.710E-12 4.502E-12 1.440E-16-1.000E+00 0.000E+00 0.000E+00 Ru-103 GONADS 2.190E-14 1.404E-11 2.783E-10 4.892E-16-1.000E+00 3.070E-10 5.720E-10 BREAST 2.510E-14 1.350E-11 2.677E-10 4.705E-16-1.000E+00 3.110E-10 1.200E-10 LUNGS 2.180E-14 1.273E-11 2.522E-10 4.432E-16-1.000E+00 1.560E-08 7.310E-11 RED MARR 2.100E-14 1.287E-11 2.551E-10 4.483E-16-1.000E+00 3.190E-10 1.660E-10 BONE SUR 3.890E-14 1.958E-11 3.882E-10 6.823E-16-1.000E+00 2.370E-10 9.631E-11 THYROID 2.240E-14 1.331E-11 2.639E-10 4.638E-16-1.000E+00 2.570E-10 6.250E-11 REMAINDER 2.080E-14 1.248E-11 2.472E-10 4.346E-16-1.000E+00 1.250E-09 2.110E-09 EFFECTIVE 2.250E-14 1.332E-11 2.641E-10 4.642E-16-1.000E+00 2.420E-09 8.271E-10 SKIN(FGR) 2.770E-14 1.785E-11 3.543E-10 6.229E-16-1.000E+00 0.000E+00 0.000E+00 Ru-105 GONADS 3.720E-14 1.327E-11 1.861E-11 8.070E-16-1.000E+00 1.590E-11 9.670E-11 BREAST 4.240E-14 1.271E-11 1.783E-11 7.730E-16-1.000E+00 6.610E-12 1.590E-11 LUNGS 3.700E-14 1.210E-11 1.697E-11 7.360E-16-1.000E+00 5.730E-10 6.210E-12 RED MARR 3.590E-14 1.230E-11 1.725E-11 7.480E-16-1.000E+00 7.700E-12 2.350E-11 BONE SUR 6.280E-14 1.809E-11 2.537E-11 1.100E-15-1.000E+00 4.620E-12 8.890E-12 THYROID 3.800E-14 1.260E-11 1.766E-11 7.660E-16-1.000E+00 4.150E-12 1.820E-12 REMAINDER 3.540E-14 1.189E-11 1.667E-11 7.230E-16-1.000E+00 1.610E-10 8.540E-10 EFFECTIVE 3.810E-14 1.265E-11 1.773E-11 7.690E-16-1.000E+00 1.230E-10 2.870E-10 SKIN(FGR) 6.730E-14 7.368E-11 1.033E-10 4.480E-15-1.000E+00 0.000E+00 0.000E+00 Ru-106 GONADS 0.000E+00 6.411E-12 1.340E-10 2.230E-16-1.000E+00 1.300E-09 1.640E-09 BREAST 0.000E+00 6.152E-12 1.286E-10 2.140E-16-1.000E+00 1.780E-09 1.440E-09 LUNGS 0.000E+00 5.836E-12 1.220E-10 2.030E-16-1.000E+00 1.040E-06 1.420E-09 RED MARR 0.000E+00 5.893E-12 1.232E-10 2.050E-16-1.000E+00 1.760E-09 1.460E-09 BONE SUR 0.000E+00 8.883E-12 1.856E-10 3.090E-16-1.000E+00 1.610E-09 1.430E-09 THYROID 0.000E+00 6.066E-12 1.268E-10 2.110E-16-1.000E+00 1.720E-09 1.410E-09 REMAINDER 0.000E+00 5.721E-12 1.196E-10 1.990E-16-1.000E+00 1.200E-08 2.110E-08 EFFECTIVE 0.000E+00 6.095E-12 1.274E-10 2.120E-16-1.000E+00 1.290E-07 7.400E-09 SKIN(FGR) 0.000E+00 4.082E-10 8.531E-09 1.420E-14-1.000E+00 0.000E+00 0.000E+00 Rh-105 GONADS 3.640E-15 2.127E-12 1.411E-11 7.980E-17-1.000E+00 2.110E-11 5.800E-11 BREAST 4.160E-15 2.063E-12 1.369E-11 7.740E-17-1.000E+00 5.610E-12 8.970E-12 LUNGS 3.570E-15 1.935E-12 1.284E-11 7.260E-17-1.000E+00 9.580E-10 3.860E-12 RED MARR 3.380E-15 1.946E-12 1.291E-11 7.300E-17-1.000E+00 7.770E-12 1.470E-11 BONE SUR 7.530E-15 3.332E-12 2.210E-11 1.250E-16-1.000E+00 4.460E-12 6.750E-12 THYROID 3.680E-15 1.983E-12 1.316E-11 7.440E-17-1.000E+00 2.880E-12 2.910E-12 REMAINDER 3.390E-15 1.885E-12 1.250E-11 7.070E-17-1.000E+00 4.530E-10 1.270E-09 EFFECTIVE 3.720E-15 2.031E-12 1.347E-11 7.620E-17-1.000E+00 2.580E-10 3.990E-10 SKIN(FGR) 1.070E-14 4.691E-12 3.112E-11 1.760E-16-1.000E+00 0.000E+00 0.000E+00 Sb-127

Numerical Applications Inc. Attachment 7 Page 238 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 GONADS 3.260E-14 1.985E-11 2.441E-10 7.100E-16-1.000E+00 2.520E-10 6.140E-10 BREAST 3.720E-14 1.904E-11 2.341E-10 6.810E-16-1.000E+00 9.120E-11 7.600E-11 LUNGS 3.240E-14 1.809E-11 2.224E-10 6.470E-16-1.000E+00 6.940E-09 1.570E-11 RED MARR 3.140E-14 1.834E-11 2.255E-10 6.560E-16-1.000E+00 1.610E-10 1.330E-10 BONE SUR 5.520E-14 2.720E-11 3.345E-10 9.730E-16-1.000E+00 1.340E-10 5.240E-11 THYROID 3.330E-14 1.884E-11 2.317E-10 6.740E-16-1.000E+00 6.150E-11 4.640E-12 REMAINDER 3.090E-14 1.775E-11 2.183E-10 6.350E-16-1.000E+00 2.330E-09 5.870E-09 EFFECTIVE 3.330E-14 1.890E-11 2.324E-10 6.760E-16-1.000E+00 1.630E-09 1.950E-09 SKIN(FGR) 5.580E-14 7.967E-11 9.799E-10 2.850E-15-1.000E+00 0.000E+00 0.000E+00 Sb-129 GONADS 6.970E-14 2.336E-11 3.231E-11 1.440E-15-1.000E+00 2.150E-11 1.510E-10 BREAST 7.910E-14 2.222E-11 3.074E-11 1.370E-15-1.000E+00 1.280E-11 2.560E-11 LUNGS 6.980E-14 2.141E-11 2.962E-11 1.320E-15-1.000E+00 8.980E-10 9.390E-12 RED MARR 6.860E-14 2.190E-11 3.029E-11 1.350E-15-1.000E+00 1.700E-11 3.670E-11 BONE SUR 1.070E-13 3.033E-11 4.196E-11 1.870E-15-1.000E+00 1.460E-11 1.340E-11 THYROID 7.160E-14 2.174E-11 3.007E-11 1.340E-15-1.000E+00 9.720E-12 1.470E-12 REMAINDER 6.710E-14 2.125E-11 2.939E-11 1.310E-15-1.000E+00 1.870E-10 1.450E-09 EFFECTIVE 7.140E-14 2.238E-11 3.096E-11 1.380E-15-1.000E+00 1.740E-10 4.840E-10 SKIN(FGR) 1.050E-13 8.273E-11 1.144E-10 5.100E-15-1.000E+00 0.000E+00 0.000E+00 Te-127 GONADS 2.370E-16 1.191E-13 2.661E-13 5.480E-18-1.000E+00 2.020E-12 4.020E-12 BREAST 2.730E-16 1.158E-13 2.588E-13 5.330E-18-1.000E+00 1.880E-12 3.000E-12 LUNGS 2.320E-16 1.060E-13 2.370E-13 4.880E-18-1.000E+00 4.270E-10 2.890E-12 RED MARR 2.210E-16 1.058E-13 2.365E-13 4.870E-18-1.000E+00 4.090E-12 6.570E-12 BONE SUR 4.650E-16 1.862E-13 4.162E-13 8.570E-18-1.000E+00 4.090E-12 6.460E-12 THYROID 2.400E-16 1.106E-13 2.472E-13 5.090E-18-1.000E+00 1.840E-12 2.860E-12 REMAINDER 2.210E-16 1.036E-13 2.316E-13 4.770E-18-1.000E+00 1.110E-10 6.130E-10 EFFECTIVE 2.420E-16 1.125E-13 2.515E-13 5.180E-18-1.000E+00 8.600E-11 1.870E-10 SKIN(FGR) 1.140E-14 1.173E-11 2.622E-11 5.400E-16-1.000E+00 0.000E+00 0.000E+00 Te-127m GONADS 1.900E-16 4.689E-13 9.642E-12 1.630E-17-1.000E+00 1.100E-10 1.250E-10 BREAST 2.690E-16 5.150E-13 1.059E-11 1.790E-17-1.000E+00 1.100E-10 9.740E-11 LUNGS 7.620E-17 1.602E-13 3.295E-12 5.570E-18-1.000E+00 3.340E-08 9.620E-11 RED MARR 6.430E-17 1.249E-13 2.567E-12 4.340E-18-1.000E+00 5.360E-09 5.430E-09 BONE SUR 3.940E-16 9.005E-13 1.852E-11 3.130E-17-1.000E+00 2.040E-08 2.070E-08 THYROID 1.500E-16 2.779E-13 5.714E-12 9.660E-18-1.000E+00 9.660E-11 9.430E-11 REMAINDER 8.640E-17 1.999E-13 4.111E-12 6.950E-18-1.000E+00 1.660E-09 2.980E-09 EFFECTIVE 1.470E-16 3.251E-13 6.684E-12 1.130E-17-1.000E+00 5.810E-09 2.230E-09 SKIN(FGR) 8.490E-16 1.496E-12 3.076E-11 5.200E-17-1.000E+00 0.000E+00 0.000E+00 Te-129 GONADS 2.710E-15 3.889E-13 3.922E-13 6.510E-17-1.000E+00 1.750E-12 1.590E-12 BREAST 3.120E-15 3.800E-13 3.832E-13 6.360E-17-1.000E+00 1.680E-12 6.050E-13 LUNGS 2.640E-15 3.298E-13 3.326E-13 5.520E-17-1.000E+00 1.330E-10 4.910E-13 RED MARR 2.540E-15 3.298E-13 3.326E-13 5.520E-17-1.000E+00 1.970E-12 7.640E-13 BONE SUR 4.880E-15 5.753E-13 5.802E-13 9.630E-17-1.000E+00 2.030E-12 5.400E-13 THYROID 2.740E-15 3.525E-13 3.555E-13 5.900E-17-1.000E+00 1.630E-12 3.360E-13 REMAINDER 2.520E-15 3.262E-13 3.289E-13 5.460E-17-1.000E+00 2.400E-11 1.790E-10 EFFECTIVE 2.750E-15 3.590E-13 3.621E-13 6.010E-17-1.000E+00 2.420E-11 5.450E-11 SKIN(FGR) 3.570E-14 3.429E-11 3.458E-11 5.740E-15-1.000E+00 0.000E+00 0.000E+00 Te-129m GONADS 1.560E-15 2.206E-12 4.799E-11 8.561E-17-1.000E+00 1.780E-10 2.420E-10 BREAST 1.810E-15 2.181E-12 4.739E-11 8.454E-17-1.000E+00 1.690E-10 1.664E-10 LUNGS 1.460E-15 1.741E-12 3.815E-11 6.808E-17-1.000E+00 4.030E-08 1.593E-10 RED MARR 1.420E-15 1.729E-12 3.793E-11 6.768E-17-1.000E+00 3.100E-09 3.500E-09 BONE SUR 2.600E-15 3.287E-12 7.147E-11 1.275E-16-1.000E+00 7.050E-09 7.990E-09 THYROID 1.560E-15 1.923E-12 4.201E-11 7.495E-17-1.000E+00 1.560E-10 1.572E-10 REMAINDER 1.410E-15 1.746E-12 3.822E-11 6.819E-17-1.000E+00 3.270E-09 7.196E-09 EFFECTIVE 1.550E-15 1.974E-12 4.308E-11 7.686E-17-1.000E+00 6.470E-09 2.925E-09 SKIN(FGR) 1.490E-14 1.501E-10 3.360E-09 6.001E-15-1.000E+00 0.000E+00 0.000E+00 Te-131m GONADS 6.850E-14 4.020E-11 2.343E-10 1.535E-15-1.000E+00 2.340E-10 7.415E-10 BREAST 7.780E-14 3.853E-11 2.246E-10 1.472E-15-1.000E+00 9.250E-11 1.361E-10 LUNGS 6.830E-14 3.657E-11 2.131E-10 1.397E-15-1.000E+00 2.230E-09 6.335E-11 RED MARR 6.680E-14 3.736E-11 2.178E-10 1.427E-15-1.000E+00 1.410E-10 2.435E-10 BONE SUR 1.090E-13 5.467E-11 3.189E-10 2.090E-15-1.000E+00 2.270E-10 3.248E-10 THYROID 7.020E-14 3.741E-11 2.181E-10 1.429E-15-1.000E+00 3.610E-08 4.383E-08 REMAINDER 6.550E-14 3.626E-11 2.113E-10 1.385E-15-1.000E+00 9.460E-10 3.153E-09 EFFECTIVE 7.010E-14 3.825E-11 2.229E-10 1.461E-15-1.000E+00 1.730E-09 2.514E-09 SKIN(FGR) 8.850E-14 1.033E-10 6.188E-10 4.056E-15-1.000E+00 0.000E+00 0.000E+00 Te-132 GONADS 1.020E-14 6.812E-12 7.706E-11 2.450E-16-1.000E+00 4.150E-10 5.410E-10 BREAST 1.180E-14 6.756E-12 7.643E-11 2.430E-16-1.000E+00 3.630E-10 3.500E-10 LUNGS 9.650E-15 5.727E-12 6.479E-11 2.060E-16-1.000E+00 1.670E-09 3.300E-10

Numerical Applications Inc. Attachment 7 Page 239 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 RED MARR 8.950E-15 5.588E-12 6.322E-11 2.010E-16-1.000E+00 4.270E-10 4.440E-10 BONE SUR 2.420E-14 1.273E-11 1.441E-10 4.580E-16-1.000E+00 7.120E-10 8.300E-10 THYROID 1.020E-14 5.978E-12 6.762E-11 2.150E-16-1.000E+00 6.280E-08 5.950E-08 REMAINDER 9.160E-15 5.644E-12 6.385E-11 2.030E-16-1.000E+00 7.890E-10 1.490E-09 EFFECTIVE 1.030E-14 6.339E-12 7.171E-11 2.280E-16-1.000E+00 2.550E-09 2.540E-09 SKIN(FGR) 1.390E-14 8.313E-12 9.405E-11 2.990E-16-1.000E+00 0.000E+00 0.000E+00 I-131 GONADS 1.780E-14 1.119E-11 1.789E-10 3.940E-16-1.000E+00 2.530E-11 4.070E-11 BREAST 2.040E-14 1.082E-11 1.730E-10 3.810E-16-1.000E+00 7.880E-11 1.210E-10 LUNGS 1.760E-14 1.016E-11 1.626E-10 3.580E-16-1.000E+00 6.570E-10 1.020E-10 RED MARR 1.680E-14 1.022E-11 1.635E-10 3.600E-16-1.000E+00 6.260E-11 9.440E-11 BONE SUR 3.450E-14 1.675E-11 2.679E-10 5.900E-16-1.000E+00 5.730E-11 8.720E-11 THYROID 1.810E-14 1.053E-11 1.685E-10 3.710E-16-1.000E+00 2.920E-07 4.760E-07 REMAINDER 1.670E-14 9.908E-12 1.585E-10 3.490E-16-1.000E+00 8.030E-11 1.570E-10 EFFECTIVE 1.820E-14 1.067E-11 1.707E-10 3.760E-16-1.000E+00 8.890E-09 1.440E-08 SKIN(FGR) 2.980E-14 1.825E-11 2.920E-10 6.430E-16-1.000E+00 0.000E+00 0.000E+00 I-132 GONADS 1.090E-13 2.523E-11 2.771E-11 2.320E-15-1.000E+00 9.950E-12 2.330E-11 BREAST 1.240E-13 2.414E-11 2.652E-11 2.220E-15-1.000E+00 1.410E-11 2.520E-11 LUNGS 1.090E-13 2.305E-11 2.532E-11 2.120E-15-1.000E+00 2.710E-10 2.640E-11 RED MARR 1.070E-13 2.360E-11 2.592E-11 2.170E-15-1.000E+00 1.400E-11 2.460E-11 BONE SUR 1.730E-13 3.327E-11 3.655E-11 3.060E-15-1.000E+00 1.240E-11 2.190E-11 THYROID 1.120E-13 2.381E-11 2.616E-11 2.190E-15-1.000E+00 1.740E-09 3.870E-09 REMAINDER 1.050E-13 2.283E-11 2.509E-11 2.100E-15-1.000E+00 3.780E-11 1.650E-10 EFFECTIVE 1.120E-13 2.403E-11 2.640E-11 2.210E-15-1.000E+00 1.030E-10 1.820E-10 SKIN(FGR) 1.580E-13 8.199E-11 9.007E-11 7.540E-15-1.000E+00 0.000E+00 0.000E+00 I-133 GONADS 2.870E-14 1.585E-11 6.748E-11 6.270E-16-1.000E+00 1.950E-11 3.630E-11 BREAST 3.280E-14 1.519E-11 6.468E-11 6.010E-16-1.000E+00 2.940E-11 4.680E-11 LUNGS 2.860E-14 1.446E-11 6.156E-11 5.720E-16-1.000E+00 8.200E-10 4.530E-11 RED MARR 2.770E-14 1.466E-11 6.242E-11 5.800E-16-1.000E+00 2.720E-11 4.300E-11 BONE SUR 4.870E-14 2.161E-11 9.202E-11 8.550E-16-1.000E+00 2.520E-11 4.070E-11 THYROID 2.930E-14 1.502E-11 6.393E-11 5.940E-16-1.000E+00 4.860E-08 9.100E-08 REMAINDER 2.730E-14 1.418E-11 6.038E-11 5.610E-16-1.000E+00 5.000E-11 1.550E-10 EFFECTIVE 2.940E-14 1.509E-11 6.425E-11 5.970E-16-1.000E+00 1.580E-09 2.800E-09 SKIN(FGR) 5.830E-14 1.150E-10 4.897E-10 4.550E-15-1.000E+00 0.000E+00 0.000E+00 I-134 GONADS 1.270E-13 1.200E-11 1.202E-11 2.640E-15-1.000E+00 4.250E-12 1.100E-11 BREAST 1.440E-13 1.145E-11 1.147E-11 2.520E-15-1.000E+00 6.170E-12 1.170E-11 LUNGS 1.270E-13 1.100E-11 1.102E-11 2.420E-15-1.000E+00 1.430E-10 1.260E-11 RED MARR 1.250E-13 1.127E-11 1.129E-11 2.480E-15-1.000E+00 6.080E-12 1.090E-11 BONE SUR 1.960E-13 1.568E-11 1.571E-11 3.450E-15-1.000E+00 5.310E-12 9.320E-12 THYROID 1.300E-13 1.127E-11 1.129E-11 2.480E-15-1.000E+00 2.880E-10 6.210E-10 REMAINDER 1.220E-13 1.091E-11 1.093E-11 2.400E-15-1.000E+00 2.270E-11 1.340E-10 EFFECTIVE 1.300E-13 1.150E-11 1.152E-11 2.530E-15-1.000E+00 3.550E-11 6.660E-11 SKIN(FGR) 1.870E-13 4.477E-11 4.485E-11 9.850E-15-1.000E+00 0.000E+00 0.000E+00 I-135 GONADS 7.770E-14 3.113E-11 5.489E-11 1.599E-15-1.000E+00 1.700E-11 3.610E-11 BREAST 8.790E-14 2.971E-11 5.240E-11 1.526E-15-1.000E+00 2.340E-11 3.850E-11 LUNGS 7.840E-14 2.886E-11 5.089E-11 1.482E-15-1.000E+00 4.410E-10 3.750E-11 RED MARR 7.760E-14 2.965E-11 5.228E-11 1.523E-15-1.000E+00 2.240E-11 3.650E-11 BONE SUR 1.130E-13 3.983E-11 7.024E-11 2.046E-15-1.000E+00 2.010E-11 3.360E-11 THYROID 8.010E-14 2.852E-11 5.030E-11 1.465E-15-1.000E+00 8.460E-09 1.790E-08 REMAINDER 7.570E-14 2.883E-11 5.084E-11 1.481E-15-1.000E+00 4.700E-11 1.540E-10 EFFECTIVE 7.980E-14 2.989E-11 5.271E-11 1.535E-15-1.000E+00 3.320E-10 6.080E-10 SKIN(FGR) 1.110E-13 9.826E-11 1.733E-10 5.047E-15-1.000E+00 0.000E+00 0.000E+00 Xe-133 GONADS 1.610E-15 1.465E-12 2.052E-11 5.200E-17-1.000E+00 0.000E+00 0.000E+00 BREAST 1.960E-15 1.505E-12 2.107E-11 5.340E-17-1.000E+00 0.000E+00 0.000E+00 LUNGS 1.320E-15 1.045E-12 1.464E-11 3.710E-17-1.000E+00 0.000E+00 0.000E+00 RED MARR 1.070E-15 8.791E-13 1.231E-11 3.120E-17-1.000E+00 0.000E+00 0.000E+00 BONE SUR 5.130E-15 4.254E-12 5.958E-11 1.510E-16-1.000E+00 0.000E+00 0.000E+00 THYROID 1.510E-15 1.181E-12 1.653E-11 4.190E-17-1.000E+00 0.000E+00 0.000E+00 REMAINDER 1.240E-15 1.042E-12 1.460E-11 3.700E-17-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 1.560E-15 1.299E-12 1.819E-11 4.610E-17-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 4.970E-15 1.953E-12 2.734E-11 6.930E-17-1.000E+00 0.000E+00 0.000E+00 Xe-135 GONADS 1.170E-14 5.455E-12 1.194E-11 2.530E-16-1.000E+00 0.000E+00 0.000E+00 BREAST 1.330E-14 5.325E-12 1.166E-11 2.470E-16-1.000E+00 0.000E+00 0.000E+00 LUNGS 1.130E-14 4.959E-12 1.086E-11 2.300E-16-1.000E+00 0.000E+00 0.000E+00 RED MARR 1.070E-14 4.959E-12 1.086E-11 2.300E-16-1.000E+00 0.000E+00 0.000E+00 BONE SUR 2.570E-14 9.120E-12 1.997E-11 4.230E-16-1.000E+00 0.000E+00 0.000E+00 THYROID 1.180E-14 5.023E-12 1.100E-11 2.330E-16-1.000E+00 0.000E+00 0.000E+00

Numerical Applications Inc. Attachment 7 Page 240 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 REMAINDER 1.080E-14 4.829E-12 1.058E-11 2.240E-16-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 1.190E-14 5.217E-12 1.142E-11 2.420E-16-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 3.120E-14 4.506E-11 9.867E-11 2.090E-15-1.000E+00 0.000E+00 0.000E+00 Cs-134 GONADS 7.400E-14 4.607E-11 9.646E-10 1.600E-15-1.000E+00 1.300E-08 2.060E-08 BREAST 8.430E-14 4.406E-11 9.224E-10 1.530E-15-1.000E+00 1.080E-08 1.720E-08 LUNGS 7.370E-14 4.204E-11 8.802E-10 1.460E-15-1.000E+00 1.180E-08 1.760E-08 RED MARR 7.190E-14 4.262E-11 8.922E-10 1.480E-15-1.000E+00 1.180E-08 1.870E-08 BONE SUR 1.200E-13 6.105E-11 1.278E-09 2.120E-15-1.000E+00 1.100E-08 1.740E-08 THYROID 7.570E-14 4.377E-11 9.163E-10 1.520E-15-1.000E+00 1.110E-08 1.760E-08 REMAINDER 7.060E-14 4.147E-11 8.681E-10 1.440E-15-1.000E+00 1.390E-08 2.210E-08 EFFECTIVE 7.570E-14 4.377E-11 9.163E-10 1.520E-15-1.000E+00 1.250E-08 1.980E-08 SKIN(FGR) 9.450E-14 6.249E-11 1.308E-09 2.170E-15-1.000E+00 0.000E+00 0.000E+00 Cs-136 GONADS 1.040E-13 6.223E-11 1.102E-09 2.180E-15-1.000E+00 1.880E-09 3.040E-09 BREAST 1.180E-13 5.966E-11 1.056E-09 2.090E-15-1.000E+00 1.670E-09 2.650E-09 LUNGS 1.040E-13 5.710E-11 1.011E-09 2.000E-15-1.000E+00 2.320E-09 2.620E-09 RED MARR 1.010E-13 5.824E-11 1.031E-09 2.040E-15-1.000E+00 1.860E-09 2.950E-09 BONE SUR 1.660E-13 8.422E-11 1.491E-09 2.950E-15-1.000E+00 1.700E-09 2.710E-09 THYROID 1.070E-13 5.852E-11 1.036E-09 2.050E-15-1.000E+00 1.730E-09 2.740E-09 REMAINDER 9.950E-14 5.652E-11 1.001E-09 1.980E-15-1.000E+00 2.190E-09 3.520E-09 EFFECTIVE 1.060E-13 5.966E-11 1.056E-09 2.090E-15-1.000E+00 1.980E-09 3.040E-09 SKIN(FGR) 1.250E-13 7.251E-11 1.284E-09 2.540E-15-1.000E+00 0.000E+00 0.000E+00 Cs-137 GONADS 7.960E-18 1.669E-11 3.530E-10 5.840E-16-1.000E+00 8.760E-09 1.390E-08 BREAST 9.670E-18 1.596E-11 3.376E-10 5.585E-16-1.000E+00 7.840E-09 1.240E-08 LUNGS 6.680E-18 1.517E-11 3.209E-10 5.309E-16-1.000E+00 8.820E-09 1.270E-08 RED MARR 5.700E-18 1.542E-11 3.260E-10 5.394E-16-1.000E+00 8.300E-09 1.320E-08 BONE SUR 2.290E-17 2.238E-11 4.734E-10 7.832E-16-1.000E+00 7.940E-09 1.260E-08 THYROID 7.550E-18 1.588E-11 3.358E-10 5.556E-16-1.000E+00 7.930E-09 1.260E-08 REMAINDER 6.340E-18 1.490E-11 3.152E-10 5.215E-16-1.000E+00 9.120E-09 1.450E-08 EFFECTIVE 7.740E-18 1.585E-11 3.353E-10 5.546E-16-1.000E+00 8.630E-09 1.350E-08 SKIN(FGR) 8.630E-15 5.253E-11 1.110E-09 1.836E-15-1.000E+00 0.000E+00 0.000E+00 Ba-139 GONADS 2.130E-15 3.368E-13 3.429E-13 4.790E-17-1.000E+00 2.560E-12 1.560E-12 BREAST 2.450E-15 3.297E-13 3.357E-13 4.690E-17-1.000E+00 2.460E-12 5.170E-13 LUNGS 2.030E-15 3.002E-13 3.057E-13 4.270E-17-1.000E+00 2.530E-10 3.890E-13 RED MARR 1.870E-15 2.932E-13 2.985E-13 4.170E-17-1.000E+00 3.410E-12 8.590E-13 BONE SUR 5.290E-15 6.841E-13 6.965E-13 9.730E-17-1.000E+00 2.490E-12 4.380E-13 THYROID 2.130E-15 3.044E-13 3.100E-13 4.330E-17-1.000E+00 2.400E-12 2.660E-13 REMAINDER 1.920E-15 2.932E-13 2.985E-13 4.170E-17-1.000E+00 4.820E-11 3.570E-10 EFFECTIVE 2.170E-15 3.227E-13 3.286E-13 4.590E-17-1.000E+00 4.640E-11 1.080E-10 SKIN(FGR) 6.160E-14 7.241E-11 7.373E-11 1.030E-14-1.000E+00 0.000E+00 0.000E+00 Ba-140 GONADS 8.410E-15 5.451E-12 9.607E-11 1.910E-16-1.000E+00 4.300E-10 9.960E-10 BREAST 9.640E-15 5.280E-12 9.305E-11 1.850E-16-1.000E+00 2.870E-10 1.590E-10 LUNGS 8.270E-15 4.852E-12 8.550E-11 1.700E-16-1.000E+00 1.660E-09 6.630E-11 RED MARR 7.930E-15 4.880E-12 8.601E-11 1.710E-16-1.000E+00 1.290E-09 4.390E-10 BONE SUR 1.550E-14 8.020E-12 1.413E-10 2.810E-16-1.000E+00 2.410E-09 5.530E-10 THYROID 8.530E-15 5.109E-12 9.003E-11 1.790E-16-1.000E+00 2.560E-10 5.250E-11 REMAINDER 7.890E-15 4.766E-12 8.399E-11 1.670E-16-1.000E+00 1.410E-09 7.370E-09 EFFECTIVE 8.580E-15 5.137E-12 9.053E-11 1.800E-16-1.000E+00 1.010E-09 2.560E-09 SKIN(FGR) 2.520E-14 5.565E-11 9.808E-10 1.950E-15-1.000E+00 0.000E+00 0.000E+00 La-140 GONADS 1.140E-13 6.027E-11 4.425E-10 2.240E-15-1.000E+00 4.540E-10 1.340E-09 BREAST 1.290E-13 5.758E-11 4.228E-10 2.140E-15-1.000E+00 1.450E-10 1.800E-10 LUNGS 1.150E-13 5.596E-11 4.109E-10 2.080E-15-1.000E+00 4.210E-09 4.010E-11 RED MARR 1.140E-13 5.731E-11 4.208E-10 2.130E-15-1.000E+00 2.140E-10 2.810E-10 BONE SUR 1.690E-13 7.776E-11 5.709E-10 2.890E-15-1.000E+00 1.410E-10 9.770E-11 THYROID 1.180E-13 5.462E-11 4.010E-10 2.030E-15-1.000E+00 6.870E-11 6.400E-12 REMAINDER 1.110E-13 5.569E-11 4.089E-10 2.070E-15-1.000E+00 2.120E-09 6.260E-09 EFFECTIVE 1.170E-13 5.812E-11 4.267E-10 2.160E-15-1.000E+00 1.310E-09 2.280E-09 SKIN(FGR) 1.660E-13 2.217E-10 1.628E-09 8.240E-15-1.000E+00 0.000E+00 0.000E+00 La-141 GONADS 2.330E-15 7.315E-13 9.675E-13 4.740E-17-1.000E+00 1.010E-11 3.770E-12 BREAST 2.640E-15 7.007E-13 9.267E-13 4.540E-17-1.000E+00 9.840E-12 7.070E-13 LUNGS 2.340E-15 6.713E-13 8.879E-13 4.350E-17-1.000E+00 6.460E-10 2.720E-13 RED MARR 2.310E-15 6.852E-13 9.063E-13 4.440E-17-1.000E+00 2.930E-11 1.070E-12 BONE SUR 3.490E-15 9.923E-13 1.312E-12 6.430E-17-1.000E+00 1.200E-10 6.060E-13 THYROID 2.390E-15 6.590E-13 8.716E-13 4.270E-17-1.000E+00 9.400E-12 5.290E-14 REMAINDER 2.260E-15 6.682E-13 8.838E-13 4.330E-17-1.000E+00 2.280E-10 1.240E-09 EFFECTIVE 2.390E-15 7.007E-13 9.267E-13 4.540E-17-1.000E+00 1.570E-10 3.740E-10 SKIN(FGR) 6.580E-14 1.667E-10 2.204E-10 1.080E-14-1.000E+00 0.000E+00 0.000E+00

Numerical Applications Inc. Attachment 7 Page 241 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 La-142 GONADS 1.400E-13 1.978E-11 2.034E-11 2.540E-15-1.000E+00 1.660E-11 6.990E-11 BREAST 1.570E-13 1.885E-11 1.938E-11 2.420E-15-1.000E+00 1.130E-11 1.540E-11 LUNGS 1.420E-13 1.846E-11 1.898E-11 2.370E-15-1.000E+00 3.010E-10 8.400E-12 RED MARR 1.420E-13 1.900E-11 1.954E-11 2.440E-15-1.000E+00 1.360E-11 1.930E-11 BONE SUR 1.950E-13 2.484E-11 2.554E-11 3.190E-15-1.000E+00 1.110E-11 7.400E-12 THYROID 1.450E-13 1.768E-11 1.818E-11 2.270E-15-1.000E+00 8.740E-12 1.160E-12 REMAINDER 1.380E-13 1.853E-11 1.906E-11 2.380E-15-1.000E+00 8.070E-11 5.200E-10 EFFECTIVE 1.440E-13 1.916E-11 1.970E-11 2.460E-15-1.000E+00 6.840E-11 1.790E-10 SKIN(FGR) 2.160E-13 9.111E-11 9.368E-11 1.170E-14-1.000E+00 0.000E+00 0.000E+00 Ce-141 GONADS 3.380E-15 2.213E-12 4.332E-11 7.710E-17-1.000E+00 5.540E-11 1.080E-10 BREAST 3.930E-15 2.170E-12 4.247E-11 7.560E-17-1.000E+00 4.460E-11 1.110E-11 LUNGS 3.170E-15 1.951E-12 3.820E-11 6.800E-17-1.000E+00 1.670E-08 1.430E-12 RED MARR 2.830E-15 1.860E-12 3.641E-11 6.480E-17-1.000E+00 8.960E-11 3.390E-11 BONE SUR 9.410E-15 5.166E-12 1.011E-10 1.800E-16-1.000E+00 2.540E-10 2.300E-11 THYROID 3.350E-15 2.003E-12 3.922E-11 6.980E-17-1.000E+00 2.550E-11 1.800E-13 REMAINDER 2.980E-15 1.894E-12 3.708E-11 6.600E-17-1.000E+00 1.260E-09 2.500E-09 EFFECTIVE 3.430E-15 2.118E-12 4.146E-11 7.380E-17-1.000E+00 2.420E-09 7.830E-10 SKIN(FGR) 1.020E-14 3.788E-12 7.416E-11 1.320E-16-1.000E+00 0.000E+00 0.000E+00 Ce-143 GONADS 1.280E-14 7.900E-12 4.958E-11 2.980E-16-1.000E+00 7.530E-11 2.120E-10 BREAST 1.470E-14 7.688E-12 4.825E-11 2.900E-16-1.000E+00 1.660E-11 2.320E-11 LUNGS 1.230E-14 6.893E-12 4.325E-11 2.600E-16-1.000E+00 3.880E-09 3.820E-12 RED MARR 1.170E-14 6.787E-12 4.259E-11 2.560E-16-1.000E+00 2.960E-11 5.070E-11 BONE SUR 2.520E-14 1.323E-11 8.302E-11 4.990E-16-1.000E+00 1.640E-11 1.610E-11 THYROID 1.280E-14 7.211E-12 4.525E-11 2.720E-16-1.000E+00 6.230E-12 4.350E-13 REMAINDER 1.170E-14 6.734E-12 4.226E-11 2.540E-16-1.000E+00 1.420E-09 3.890E-09 EFFECTIVE 1.290E-14 7.396E-12 4.642E-11 2.790E-16-1.000E+00 9.160E-10 1.230E-09 SKIN(FGR) 3.960E-14 1.058E-10 6.638E-10 3.990E-15-1.000E+00 0.000E+00 0.000E+00 Ce-144 GONADS 8.530E-16 6.328E-13 1.319E-11 6.088E-17-1.000E+00 2.390E-10 6.987E-11 BREAST 1.010E-15 6.274E-13 1.307E-11 5.922E-17-1.000E+00 3.480E-10 1.223E-11 LUNGS 7.690E-16 5.228E-13 1.089E-11 5.362E-17-1.000E+00 7.910E-07 6.551E-12 RED MARR 6.680E-16 4.755E-13 9.907E-12 5.247E-17-1.000E+00 2.880E-09 8.923E-11 BONE SUR 2.490E-15 1.646E-12 3.429E-11 1.127E-16-1.000E+00 4.720E-09 1.280E-10 THYROID 8.330E-16 5.529E-13 1.152E-11 5.418E-17-1.000E+00 2.920E-10 5.154E-12 REMAINDER 7.230E-16 5.086E-13 1.060E-11 5.283E-17-1.000E+00 1.910E-08 1.890E-08 EFFECTIVE 8.530E-16 5.909E-13 1.231E-11 5.766E-17-1.000E+00 1.010E-07 5.711E-09 SKIN(FGR) 2.930E-15 7.648E-13 1.594E-11 1.250E-14-1.000E+00 0.000E+00 0.000E+00 Pr-143 GONADS 2.130E-17 2.264E-14 4.032E-13 7.930E-19-1.000E+00 4.370E-18 8.990E-18 BREAST 2.550E-17 2.330E-14 4.149E-13 8.160E-19-1.000E+00 2.220E-18 1.090E-18 LUNGS 1.860E-17 1.642E-14 2.923E-13 5.750E-19-1.000E+00 1.330E-08 1.910E-19 RED MARR 1.620E-17 1.493E-14 2.659E-13 5.230E-19-1.000E+00 1.480E-11 1.030E-12 BONE SUR 5.930E-17 5.454E-14 9.711E-13 1.910E-18-1.000E+00 1.490E-11 1.030E-12 THYROID 2.050E-17 1.802E-14 3.208E-13 6.310E-19-1.000E+00 1.680E-18 2.660E-20 REMAINDER 1.760E-17 1.642E-14 2.923E-13 5.750E-19-1.000E+00 1.970E-09 4.220E-09 EFFECTIVE 2.100E-17 2.002E-14 3.564E-13 7.010E-19-1.000E+00 2.190E-09 1.270E-09 SKIN(FGR) 1.760E-14 5.711E-11 1.017E-09 2.000E-15-1.000E+00 0.000E+00 0.000E+00 Nd-147 GONADS 6.130E-15 4.218E-12 7.235E-11 1.480E-16-1.000E+00 8.410E-11 1.790E-10 BREAST 7.120E-15 4.132E-12 7.088E-11 1.450E-16-1.000E+00 3.450E-11 1.870E-11 LUNGS 5.820E-15 3.648E-12 6.257E-11 1.280E-16-1.000E+00 1.060E-08 2.440E-12 RED MARR 5.400E-15 3.505E-12 6.013E-11 1.230E-16-1.000E+00 9.190E-11 5.050E-11 BONE SUR 1.320E-14 8.265E-12 1.418E-10 2.900E-16-1.000E+00 3.260E-10 2.220E-11 THYROID 6.120E-15 3.876E-12 6.648E-11 1.360E-16-1.000E+00 1.820E-11 2.640E-13 REMAINDER 5.530E-15 3.562E-12 6.111E-11 1.250E-16-1.000E+00 1.760E-09 3.760E-09 EFFECTIVE 6.190E-15 3.961E-12 6.795E-11 1.390E-16-1.000E+00 1.850E-09 1.180E-09 SKIN(FGR) 1.950E-14 3.135E-11 5.377E-10 1.100E-15-1.000E+00 0.000E+00 0.000E+00 Np-239 GONADS 7.530E-15 4.691E-12 4.380E-11 1.710E-16-1.000E+00 7.450E-11 1.620E-10 BREAST 8.730E-15 4.636E-12 4.329E-11 1.690E-16-1.000E+00 1.630E-11 1.720E-11 LUNGS 7.180E-15 4.115E-12 3.842E-11 1.500E-16-1.000E+00 2.360E-09 2.400E-12 RED MARR 6.500E-15 4.005E-12 3.740E-11 1.460E-16-1.000E+00 2.080E-10 4.660E-11 BONE SUR 2.000E-14 1.001E-11 9.349E-11 3.650E-16-1.000E+00 2.030E-09 3.590E-11 THYROID 7.520E-15 4.197E-12 3.919E-11 1.530E-16-1.000E+00 7.620E-12 2.070E-13 REMAINDER 6.760E-15 4.005E-12 3.740E-11 1.460E-16-1.000E+00 9.590E-10 2.770E-09 EFFECTIVE 7.690E-15 4.471E-12 4.175E-11 1.630E-16-1.000E+00 6.780E-10 8.820E-10 SKIN(FGR) 1.600E-14 7.215E-12 6.737E-11 2.630E-16-1.000E+00 0.000E+00 0.000E+00 Pu-238 GONADS 6.560E-18 4.291E-14 9.011E-13 1.490E-18-1.000E+00 2.800E-05 2.330E-09 BREAST 1.270E-17 5.558E-14 1.167E-12 1.930E-18-1.000E+00 1.000E-09 1.800E-13

Numerical Applications Inc. Attachment 7 Page 242 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 LUNGS 1.060E-18 2.267E-15 4.759E-14 7.870E-20-1.000E+00 1.840E-05 8.640E-14 RED MARR 1.680E-18 5.587E-15 1.173E-13 1.940E-19-1.000E+00 1.520E-04 1.270E-08 BONE SUR 9.300E-18 3.514E-14 7.378E-13 1.220E-18-1.000E+00 1.900E-03 1.580E-07 THYROID 4.010E-18 9.792E-15 2.056E-13 3.400E-19-1.000E+00 9.620E-10 7.990E-14 REMAINDER 1.990E-18 9.216E-15 1.935E-13 3.200E-19-1.000E+00 7.020E-05 2.180E-08 EFFECTIVE 4.880E-18 2.413E-14 5.068E-13 8.380E-19-1.000E+00 1.060E-04 1.340E-08 SKIN(FGR) 4.090E-17 2.776E-13 5.830E-12 9.640E-18-1.000E+00 0.000E+00 0.000E+00 Pu-239 GONADS 4.840E-18 1.768E-14 3.713E-13 6.140E-19-1.000E+00 3.180E-05 2.640E-09 BREAST 7.550E-18 2.238E-14 4.699E-13 7.770E-19-1.000E+00 9.220E-10 1.210E-13 LUNGS 2.650E-18 2.267E-15 4.760E-14 7.870E-20-1.000E+00 1.730E-05 7.890E-14 RED MARR 2.670E-18 3.456E-15 7.258E-14 1.200E-19-1.000E+00 1.690E-04 1.410E-08 BONE SUR 9.470E-18 1.673E-14 3.514E-13 5.810E-19-1.000E+00 2.110E-03 1.760E-07 THYROID 3.880E-18 5.126E-15 1.077E-13 1.780E-19-1.000E+00 9.030E-10 7.500E-14 REMAINDER 2.860E-18 4.838E-15 1.016E-13 1.680E-19-1.000E+00 7.560E-05 2.120E-08 EFFECTIVE 4.240E-18 1.057E-14 2.220E-13 3.670E-19-1.000E+00 1.160E-05 1.400E-08 SKIN(FGR) 1.860E-17 1.057E-13 2.220E-12 3.670E-18-1.000E+00 0.000E+00 0.000E+00 Pu-240 GONADS 6.360E-18 4.118E-14 8.649E-13 1.430E-18-1.000E+00 3.180E-05 2.640E-09 BREAST 1.230E-17 5.328E-14 1.119E-12 1.850E-18-1.000E+00 9.510E-10 1.730E-13 LUNGS 1.090E-18 2.249E-15 4.723E-14 7.810E-20-1.000E+00 1.730E-05 8.220E-14 RED MARR 1.650E-18 5.386E-15 1.131E-13 1.870E-19-1.000E+00 1.690E-04 1.410E-08 BONE SUR 9.260E-18 3.398E-14 7.137E-13 1.180E-18-1.000E+00 2.110E-03 1.760E-07 THYROID 3.920E-18 9.446E-15 1.984E-13 3.280E-19-1.000E+00 9.050E-10 7.510E-14 REMAINDER 1.960E-18 8.870E-15 1.863E-13 3.080E-19-1.000E+00 7.560E-05 2.130E-08 EFFECTIVE 4.750E-18 2.313E-14 4.857E-13 8.030E-19-1.000E+00 1.160E-04 1.400E-08 SKIN(FGR) 3.920E-17 2.644E-13 5.552E-12 9.180E-18-1.000E+00 0.000E+00 0.000E+00 Pu-241 GONADS 7.190E-20 6.653E-17 1.396E-15 2.310E-21-1.000E+00 6.820E-07 5.660E-11 BREAST 8.670E-20 7.229E-17 1.517E-15 2.510E-21-1.000E+00 3.060E-11 2.790E-15 LUNGS 6.480E-20 4.090E-17 8.584E-16 1.420E-21-1.000E+00 7.420E-09 4.480E-15 RED MARR 5.630E-20 4.003E-17 8.403E-16 1.390E-21-1.000E+00 3.360E-06 2.780E-10 BONE SUR 2.190E-19 1.385E-16 2.908E-15 4.810E-21-1.000E+00 4.200E-05 3.480E-09 THYROID 6.980E-20 4.522E-17 9.491E-16 1.570E-21-1.000E+00 1.240E-11 1.010E-15 REMAINDER 6.090E-20 4.291E-17 9.007E-16 1.490E-21-1.000E+00 1.310E-06 1.850E-10 EFFECTIVE 7.250E-20 5.558E-17 1.167E-15 1.930E-21-1.000E+00 2.230E-06 2.070E-10 SKIN(FGR) 1.170E-19 2.033E-16 4.268E-15 7.060E-21-1.000E+00 0.000E+00 0.000E+00 Am-241 GONADS 8.580E-16 9.360E-13 1.966E-11 3.250E-17-1.000E+00 3.250E-05 2.700E-07 BREAST 1.070E-15 1.014E-12 2.129E-11 3.520E-17-1.000E+00 2.670E-09 2.620E-11 LUNGS 6.740E-16 5.789E-13 1.216E-11 2.010E-17-1.000E+00 1.840E-05 3.360E-11 RED MARR 5.210E-16 4.838E-13 1.016E-11 1.680E-17-1.000E+00 1.740E-04 1.450E-06 BONE SUR 2.870E-15 2.678E-12 5.625E-11 9.300E-17-1.000E+00 2.170E-03 1.810E-05 THYROID 7.830E-16 6.365E-13 1.337E-11 2.210E-17-1.000E+00 1.600E-09 1.320E-11 REMAINDER 6.340E-16 5.933E-13 1.246E-11 2.060E-17-1.000E+00 7.820E-05 6.660E-07 EFFECTIVE 8.180E-16 7.920E-13 1.663E-11 2.750E-17-1.000E+00 1.200E-04 9.840E-07 SKIN(FGR) 1.280E-15 2.396E-12 5.032E-11 8.320E-17-1.000E+00 0.000E+00 0.000E+00 Cm-242 GONADS 7.830E-18 4.893E-14 1.013E-12 1.700E-18-1.000E+00 5.700E-07 5.200E-09 BREAST 1.480E-17 6.159E-14 1.275E-12 2.140E-18-1.000E+00 9.440E-10 8.950E-12 LUNGS 1.130E-18 3.022E-15 6.257E-14 1.050E-19-1.000E+00 1.550E-05 8.840E-12 RED MARR 1.890E-18 6.562E-15 1.359E-13 2.280E-19-1.000E+00 3.900E-06 3.570E-08 BONE SUR 1.060E-17 4.231E-14 8.759E-13 1.470E-18-1.000E+00 4.870E-05 4.460E-07 THYROID 4.910E-18 1.261E-14 2.610E-13 4.380E-19-1.000E+00 9.410E-10 8.820E-12 REMAINDER 2.270E-18 1.079E-14 2.235E-13 3.750E-19-1.000E+00 2.450E-06 4.020E-08 EFFECTIVE 5.690E-18 2.751E-14 5.697E-13 9.560E-19-1.000E+00 4.670E-06 3.100E-08 SKIN(FGR) 4.290E-17 2.700E-13 5.589E-12 9.380E-18-1.000E+00 0.000E+00 0.000E+00 Cm-244 GONADS 6.900E-18 4.522E-14 9.492E-13 1.570E-18-1.000E+00 1.590E-05 1.330E-07 BREAST 1.330E-17 5.702E-14 1.197E-12 1.980E-18-1.000E+00 1.040E-09 8.820E-12 LUNGS 7.080E-19 2.592E-15 5.441E-14 9.000E-20-1.000E+00 1.930E-05 8.810E-12 RED MARR 1.460E-18 5.875E-15 1.233E-13 2.040E-19-1.000E+00 9.380E-05 7.820E-07 BONE SUR 8.820E-18 3.859E-14 8.101E-13 1.340E-18-1.000E+00 1.170E-03 9.770E-06 THYROID 4.190E-18 1.146E-14 2.406E-13 3.980E-19-1.000E+00 1.010E-09 8.440E-12 REMAINDER 1.810E-18 9.821E-15 2.062E-13 3.410E-19-1.000E+00 4.780E-05 4.150E-07 EFFECTIVE 4.910E-18 2.529E-14 5.308E-13 8.780E-19-1.000E+00 6.700E-05 5.450E-07 SKIN(FGR) 3.910E-17 2.506E-13 5.260E-12 8.700E-18-1.000E+00 0.000E+00 0.000E+00 I-130 GONADS 1.010E-13 2.867E-11 5.828E-10 9.970E-16-1.000E+00 2.810E-11 1.040E-09 BREAST 1.160E-13 2.737E-11 5.565E-10 9.520E-16-1.000E+00 4.870E-11 1.790E-10 LUNGS 1.010E-13 2.617E-11 5.319E-10 9.100E-16-1.000E+00 6.030E-10 8.530E-11 RED MARR 9.820E-14 2.671E-11 5.430E-10 9.290E-16-1.000E+00 4.550E-11 2.600E-10 BONE SUR 1.680E-13 3.795E-11 7.716E-10 1.320E-15-1.000E+00 4.030E-11 1.250E-10

Numerical Applications Inc. Attachment 7 Page 243 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 THYROID 1.040E-13 2.720E-11 5.530E-10 9.460E-16-1.000E+00 1.990E-08 6.310E-11 REMAINDER 9.660E-14 2.585E-11 5.255E-10 8.990E-16-1.000E+00 8.020E-11 1.580E-09 EFFECTIVE 1.040E-13 2.732E-11 5.553E-10 9.500E-16-1.000E+00 7.140E-10 8.090E-10 SKIN(FGR) 1.360E-13 3.278E-11 6.664E-10 1.140E-15-1.000E+00 0.000E+00 0.000E+00 Kr-83m GONADS 1.710E-18 7.056E-11 1.480E-09 2.450E-15-1.000E+00 0.000E+00 3.190E-09 BREAST 5.050E-18 6.739E-11 1.413E-09 2.340E-15-1.000E+00 0.000E+00 1.100E-09 LUNGS 1.640E-19 6.537E-11 1.371E-09 2.270E-15-1.000E+00 0.000E+00 8.770E-10 RED MARR 3.830E-19 6.710E-11 1.407E-09 2.330E-15-1.000E+00 0.000E+00 1.320E-09 BONE SUR 2.250E-18 8.956E-11 1.879E-09 3.110E-15-1.000E+00 0.000E+00 9.390E-10 THYROID 6.430E-19 6.480E-11 1.359E-09 2.250E-15-1.000E+00 0.000E+00 7.880E-10 REMAINDER 5.300E-19 6.508E-11 1.365E-09 2.260E-15-1.000E+00 0.000E+00 4.970E-09 EFFECTIVE 1.500E-18 6.768E-11 1.419E-09 2.350E-15-1.000E+00 0.000E+00 2.770E-09 SKIN(FGR) 3.560E-17 7.948E-11 1.667E-09 2.760E-15-1.000E+00 0.000E+00 0.000E+00 Xe-138 GONADS 5.590E-14 8.121E-14 1.704E-12 2.820E-18-1.000E+00 0.000E+00 0.000E+00 BREAST 6.320E-14 7.891E-14 1.656E-12 2.740E-18-1.000E+00 0.000E+00 0.000E+00 LUNGS 5.660E-14 7.056E-14 1.481E-12 2.450E-18-1.000E+00 0.000E+00 0.000E+00 RED MARR 5.600E-14 6.998E-14 1.469E-12 2.430E-18-1.000E+00 0.000E+00 0.000E+00 BONE SUR 8.460E-14 1.287E-13 2.702E-12 4.470E-18-1.000E+00 0.000E+00 0.000E+00 THYROID 5.770E-14 7.459E-14 1.565E-12 2.590E-18-1.000E+00 0.000E+00 0.000E+00 REMAINDER 5.490E-14 6.941E-14 1.457E-12 2.410E-18-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 5.770E-14 7.603E-14 1.596E-12 2.640E-18-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 1.070E-13 2.304E-11 4.835E-10 8.000E-16-1.000E+00 0.000E+00 0.000E+00 Xe-131m GONADS 4.570E-16 2.594E-12 3.653E-12 1.570E-16-1.000E+00 0.000E+00 0.000E+00 BREAST 6.020E-16 2.527E-12 3.560E-12 1.530E-16-1.000E+00 0.000E+00 0.000E+00 LUNGS 2.670E-16 2.379E-12 3.351E-12 1.440E-16-1.000E+00 0.000E+00 0.000E+00 RED MARR 2.270E-16 2.346E-12 3.304E-12 1.420E-16-1.000E+00 0.000E+00 0.000E+00 BONE SUR 1.060E-15 5.286E-12 7.446E-12 3.200E-16-1.000E+00 0.000E+00 0.000E+00 THYROID 3.910E-16 2.395E-12 3.374E-12 1.450E-16-1.000E+00 0.000E+00 0.000E+00 REMAINDER 2.710E-16 2.313E-12 3.257E-12 1.400E-16-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 3.890E-16 2.511E-12 3.537E-12 1.520E-16-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 4.820E-15 2.247E-11 3.164E-11 1.360E-15-1.000E+00 0.000E+00 0.000E+00 Xe-133m GONADS 1.420E-15 4.962E-12 5.026E-12 7.610E-16-1.000E+00 0.000E+00 0.000E+00 BREAST 1.700E-15 4.740E-12 4.802E-12 7.270E-16-1.000E+00 0.000E+00 0.000E+00 LUNGS 1.190E-15 4.603E-12 4.663E-12 7.060E-16-1.000E+00 0.000E+00 0.000E+00 RED MARR 1.100E-15 4.708E-12 4.769E-12 7.220E-16-1.000E+00 0.000E+00 0.000E+00 BONE SUR 3.230E-15 6.514E-12 6.598E-12 9.990E-16-1.000E+00 0.000E+00 0.000E+00 THYROID 1.360E-15 4.473E-12 4.531E-12 6.860E-16-1.000E+00 0.000E+00 0.000E+00 REMAINDER 1.150E-15 4.590E-12 4.650E-12 7.040E-16-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 1.370E-15 4.773E-12 4.835E-12 7.320E-16-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 1.040E-14 8.802E-11 8.916E-11 1.350E-14-1.000E+00 0.000E+00 0.000E+00 Xe-135m GONADS 2.000E-14 2.278E-11 2.655E-11 1.800E-15-1.000E+00 0.000E+00 0.000E+00 BREAST 2.290E-14 2.177E-11 2.537E-11 1.720E-15-1.000E+00 0.000E+00 0.000E+00 LUNGS 1.980E-14 2.139E-11 2.493E-11 1.690E-15-1.000E+00 0.000E+00 0.000E+00 RED MARR 1.910E-14 2.190E-11 2.552E-11 1.730E-15-1.000E+00 0.000E+00 0.000E+00 BONE SUR 3.500E-14 2.886E-11 3.363E-11 2.280E-15-1.000E+00 0.000E+00 0.000E+00 THYROID 2.040E-14 2.012E-11 2.345E-11 1.590E-15-1.000E+00 0.000E+00 0.000E+00 REMAINDER 1.890E-14 2.139E-11 2.493E-11 1.690E-15-1.000E+00 0.000E+00 0.000E+00 EFFECTIVE 2.040E-14 2.202E-11 2.567E-11 1.740E-15-1.000E+00 0.000E+00 0.000E+00 SKIN(FGR) 2.970E-14 5.607E-11 6.534E-11 4.430E-15-1.000E+00 0.000E+00 0.000E+00 Cs-138 GONADS 1.170E-13 2.788E-12 5.187E-11 9.740E-17-1.000E+00 3.280E-12 2.150E-09 BREAST 1.330E-13 2.662E-12 4.953E-11 9.300E-17-1.000E+00 4.020E-12 2.140E-09 LUNGS 1.190E-13 2.553E-12 4.750E-11 8.920E-17-1.000E+00 1.590E-10 2.140E-09 RED MARR 1.180E-13 2.619E-12 4.873E-11 9.150E-17-1.000E+00 3.950E-12 3.720E-09 BONE SUR 1.700E-13 3.635E-12 6.764E-11 1.270E-16-1.000E+00 3.550E-12 6.860E-09 THYROID 1.210E-13 2.599E-12 4.836E-11 9.080E-17-1.000E+00 3.570E-12 2.140E-09 REMAINDER 1.150E-13 2.542E-12 4.729E-11 8.880E-17-1.000E+00 2.060E-11 2.330E-09 EFFECTIVE 1.210E-13 2.665E-12 4.958E-11 9.310E-17-1.000E+00 2.740E-11 2.530E-09 SKIN(FGR) 2.170E-13 2.210E-10 4.111E-09 7.720E-15-1.000E+00 0.000E+00 0.000E+00 Cs-134m GONADS 9.300E-16 7.155E-14 1.436E-12 2.490E-18-1.000E+00 3.610E-12 8.050E-12 BREAST 1.120E-15 7.212E-14 1.447E-12 2.510E-18-1.000E+00 3.390E-12 7.980E-12 LUNGS 7.840E-16 5.689E-14 1.142E-12 1.980E-18-1.000E+00 6.400E-11 7.970E-12 RED MARR 6.810E-16 5.345E-14 1.073E-12 1.860E-18-1.000E+00 3.760E-12 1.080E-10 BONE SUR 2.610E-15 1.560E-13 3.131E-12 5.430E-18-1.000E+00 3.550E-12 1.610E-10 THYROID 8.880E-16 6.063E-14 1.217E-12 2.110E-18-1.000E+00 3.340E-12 7.970E-12 REMAINDER 7.450E-16 5.603E-14 1.124E-12 1.950E-18-1.000E+00 6.900E-12 8.250E-09 EFFECTIVE 9.050E-16 6.523E-14 1.309E-12 2.270E-18-1.000E+00 1.180E-11 2.500E-09

Numerical Applications Inc. Attachment 7 Page 244 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 SKIN(FGR) 2.880E-15 1.914E-10 3.841E-09 6.660E-15-1.000E+00 0.000E+00 0.000E+00 Rb-88 GONADS 3.260E-14 9.590E-15 2.014E-13 3.330E-19-1.000E+00 1.310E-12 5.040E-11 BREAST 3.670E-14 1.008E-14 2.116E-13 3.500E-19-1.000E+00 1.430E-12 5.040E-11 LUNGS 3.310E-14 6.307E-15 1.324E-13 2.190E-19-1.000E+00 1.470E-10 5.040E-11 RED MARR 3.300E-14 5.558E-15 1.167E-13 1.930E-19-1.000E+00 1.450E-12 6.450E-09 BONE SUR 4.620E-14 2.393E-14 5.025E-13 8.310E-19-1.000E+00 1.470E-12 1.390E-08 THYROID 3.370E-14 7.171E-15 1.506E-13 2.490E-19-1.000E+00 1.370E-12 5.040E-11 REMAINDER 3.210E-14 6.422E-15 1.348E-13 2.230E-19-1.000E+00 1.380E-11 6.700E-09 EFFECTIVE 3.360E-14 8.179E-15 1.717E-13 2.840E-19-1.000E+00 2.260E-11 3.230E-09 SKIN(FGR) 1.830E-13 4.032E-12 8.465E-11 1.400E-16-1.000E+00 0.000E+00 0.000E+00 Rb-89 GONADS 1.030E-13 2.155E-11 5.062E-11 1.026E-15-1.000E+00 1.340E-12 2.520E-10 BREAST 1.170E-13 2.059E-11 4.838E-11 9.806E-16-1.000E+00 1.730E-12 3.676E-11 LUNGS 1.040E-13 1.970E-11 4.626E-11 9.376E-16-1.000E+00 6.800E-11 1.055E-11 RED MARR 1.040E-13 2.011E-11 4.722E-11 9.570E-16-1.000E+00 2.020E-12 5.659E-11 BONE SUR 1.480E-13 2.852E-11 6.709E-11 1.360E-15-1.000E+00 2.540E-12 2.070E-11 THYROID 1.070E-13 2.035E-11 4.782E-11 9.693E-16-1.000E+00 1.610E-12 1.968E-12 REMAINDER 1.010E-13 1.948E-11 4.573E-11 9.268E-16-1.000E+00 8.140E-12 2.557E-09 EFFECTIVE 1.060E-13 2.057E-11 4.832E-11 9.793E-16-1.000E+00 1.160E-11 8.455E-10 SKIN(FGR) 1.870E-13 1.748E-10 3.987E-10 8.080E-15-1.000E+00 0.000E+00 0.000E+00 Sb-124 GONADS 8.890E-14 1.593E-11 1.830E-11 1.300E-15-1.000E+00 1.040E-09 8.180E-11 BREAST 1.010E-13 1.520E-11 1.745E-11 1.240E-15-1.000E+00 8.940E-10 1.700E-11 LUNGS 8.970E-14 1.483E-11 1.703E-11 1.210E-15-1.000E+00 4.140E-08 7.220E-12 RED MARR 8.850E-14 1.520E-11 1.745E-11 1.240E-15-1.000E+00 1.090E-09 2.290E-11 BONE SUR 1.340E-13 2.010E-11 2.308E-11 1.640E-15-1.000E+00 1.240E-09 8.490E-12 THYROID 9.150E-14 1.446E-11 1.661E-11 1.180E-15-1.000E+00 6.740E-10 1.300E-12 REMAINDER 8.660E-14 1.471E-11 1.689E-11 1.200E-15-1.000E+00 4.180E-09 1.720E-09 EFFECTIVE 9.150E-14 1.532E-11 1.759E-11 1.250E-15-1.000E+00 6.800E-09 5.430E-10 SKIN(FGR) 1.260E-13 2.280E-11 2.618E-11 1.860E-15-1.000E+00 0.000E+00 0.000E+00 Sb-125 GONADS 1.980E-14 1.586E-13 1.601E-12 5.750E-18-1.000E+00 3.600E-10 1.430E-14 BREAST 2.270E-14 1.578E-13 1.593E-12 5.720E-18-1.000E+00 4.160E-10 1.270E-14 LUNGS 1.950E-14 1.313E-13 1.326E-12 4.760E-18-1.000E+00 2.170E-08 1.260E-14 RED MARR 1.870E-14 1.261E-13 1.273E-12 4.570E-18-1.000E+00 5.350E-10 3.700E-13 BONE SUR 3.530E-14 3.228E-13 3.259E-12 1.170E-17-1.000E+00 9.780E-10 3.670E-13 THYROID 2.010E-14 1.385E-13 1.398E-12 5.020E-18-1.000E+00 3.240E-10 1.260E-14 REMAINDER 1.860E-14 1.291E-13 1.303E-12 4.680E-18-1.000E+00 1.450E-09 9.680E-09 EFFECTIVE 2.020E-14 1.468E-13 1.482E-12 5.320E-18-1.000E+00 3.300E-09 2.910E-09 SKIN(FGR) 2.650E-14 2.897E-10 2.924E-09 1.050E-14-1.000E+00 0.000E+00 0.000E+00 Sb-126 GONADS 1.350E-13 1.756E-13 3.546E-12 6.110E-18-1.000E+00 1.320E-09 3.540E-12 BREAST 1.530E-13 1.713E-13 3.459E-12 5.960E-18-1.000E+00 6.440E-10 5.540E-13 LUNGS 1.340E-13 1.526E-13 3.082E-12 5.310E-18-1.000E+00 1.380E-08 2.020E-13 RED MARR 1.300E-13 1.521E-13 3.070E-12 5.290E-18-1.000E+00 7.970E-10 6.590E-12 BONE SUR 2.220E-13 2.903E-13 5.862E-12 1.010E-17-1.000E+00 6.750E-10 6.130E-12 THYROID 1.370E-13 1.564E-13 3.157E-12 5.440E-18-1.000E+00 4.800E-10 1.290E-13 REMAINDER 1.280E-13 1.509E-13 3.047E-12 5.250E-18-1.000E+00 3.190E-09 8.570E-09 EFFECTIVE 1.370E-13 1.650E-13 3.332E-12 5.740E-18-1.000E+00 3.170E-09 2.570E-09 SKIN(FGR) 1.730E-13 1.989E-10 4.016E-09 6.920E-15-1.000E+00 0.000E+00 0.000E+00 Te-131 GONADS 1.990E-14 3.855E-12 4.872E-12 2.650E-16-1.000E+00 6.140E-12 1.960E-11 BREAST 2.280E-14 3.680E-12 4.652E-12 2.530E-16-1.000E+00 5.530E-12 3.550E-12 LUNGS 1.960E-14 3.535E-12 4.468E-12 2.430E-16-1.000E+00 2.540E-10 1.390E-12 RED MARR 1.880E-14 3.608E-12 4.560E-12 2.480E-16-1.000E+00 6.640E-12 4.910E-12 BONE SUR 3.800E-14 5.091E-12 6.435E-12 3.500E-16-1.000E+00 6.210E-12 1.750E-12 THYROID 2.030E-14 3.579E-12 4.523E-12 2.460E-16-1.000E+00 2.630E-09 1.770E-13 REMAINDER 1.870E-14 3.506E-12 4.431E-12 2.410E-16-1.000E+00 5.420E-11 1.700E-09 EFFECTIVE 2.040E-14 3.680E-12 4.652E-12 2.530E-16-1.000E+00 1.290E-10 5.150E-10 SKIN(FGR) 6.890E-14 2.022E-10 2.556E-10 1.390E-14-1.000E+00 0.000E+00 0.000E+00 Te-133 GONADS 4.490E-14 2.108E-12 4.989E-12 9.510E-17-1.000E+00 6.700E-13 2.200E-11 BREAST 5.100E-14 2.026E-12 4.794E-12 9.140E-17-1.000E+00 8.480E-13 3.130E-12 LUNGS 4.470E-14 1.937E-12 4.585E-12 8.740E-17-1.000E+00 4.390E-11 8.670E-13 RED MARR 4.360E-14 1.972E-12 4.669E-12 8.900E-17-1.000E+00 8.390E-13 4.930E-12 BONE SUR 7.500E-14 2.948E-12 6.977E-12 1.330E-16-1.000E+00 7.490E-13 1.730E-12 THYROID 4.590E-14 1.908E-12 4.516E-12 8.610E-17-1.000E+00 5.910E-10 1.260E-13 REMAINDER 4.290E-14 1.919E-12 4.543E-12 8.660E-17-1.000E+00 5.020E-12 4.090E-09 EFFECTIVE 4.600E-14 2.021E-12 4.784E-12 9.120E-17-1.000E+00 2.490E-11 1.230E-09 SKIN(FGR) 1.060E-13 2.726E-10 6.452E-10 1.230E-14-1.000E+00 0.000E+00 0.000E+00 Te-134 GONADS 4.160E-14 2.182E-11 4.421E-10 7.590E-16-1.000E+00 9.000E-12 8.160E-10

Numerical Applications Inc. Attachment 7 Page 245 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 BREAST 4.750E-14 2.084E-11 4.223E-10 7.250E-16-1.000E+00 8.720E-12 1.050E-10 LUNGS 4.100E-14 1.989E-11 4.030E-10 6.920E-16-1.000E+00 6.020E-11 2.340E-11 RED MARR 3.940E-14 2.030E-11 4.112E-10 7.060E-16-1.000E+00 9.300E-12 2.140E-10 BONE SUR 7.560E-14 2.875E-11 5.824E-10 1.000E-15-1.000E+00 8.580E-12 4.860E-10 THYROID 4.230E-14 2.076E-11 4.205E-10 7.220E-16-1.000E+00 5.540E-10 8.270E-12 REMAINDER 3.910E-14 1.963E-11 3.978E-10 6.830E-16-1.000E+00 1.880E-11 2.530E-09 EFFECTIVE 4.240E-14 2.078E-11 4.211E-10 7.230E-16-1.000E+00 3.440E-11 1.020E-09 SKIN(FGR) 6.350E-14 2.561E-11 5.190E-10 8.910E-16-1.000E+00 0.000E+00 0.000E+00 Te-125m GONADS 5.960E-16 2.179E-11 7.799E-11 9.253E-16-1.000E+00 7.930E-11 6.228E-10 BREAST 8.480E-16 2.083E-11 7.455E-11 8.846E-16-1.000E+00 7.080E-11 8.137E-11 LUNGS 2.230E-16 1.992E-11 7.127E-11 8.456E-16-1.000E+00 1.040E-08 1.770E-11 RED MARR 1.860E-16 2.034E-11 7.279E-11 8.634E-16-1.000E+00 1.150E-09 1.302E-10 BONE SUR 1.220E-15 2.881E-11 1.031E-10 1.224E-15-1.000E+00 1.180E-08 4.558E-11 THYROID 4.640E-16 2.061E-11 7.377E-11 8.755E-16-1.000E+00 3.870E-11 2.671E-12 REMAINDER 2.590E-16 1.966E-11 7.035E-11 8.345E-16-1.000E+00 6.750E-10 6.990E-09 EFFECTIVE 4.530E-16 2.078E-11 7.438E-11 8.824E-16-1.000E+00 1.970E-09 2.283E-09 SKIN(FGR) 1.940E-15 2.281E-10 8.148E-10 9.587E-15-1.000E+00 0.000E+00 0.000E+00 Te-133m GONADS 1.120E-13 2.253E-11 4.435E-10 7.850E-16-1.000E+00 8.970E-12 8.050E-10 BREAST 1.270E-13 2.150E-11 4.231E-10 7.490E-16-1.000E+00 7.820E-12 1.070E-10 LUNGS 1.120E-13 2.055E-11 4.045E-10 7.160E-16-1.000E+00 1.820E-10 2.740E-11 RED MARR 1.090E-13 2.101E-11 4.135E-10 7.320E-16-1.000E+00 8.320E-12 1.990E-10 BONE SUR 1.750E-13 2.957E-11 5.819E-10 1.030E-15-1.000E+00 6.940E-12 2.940E-10 THYROID 1.150E-13 2.144E-11 4.220E-10 7.470E-16-1.000E+00 2.610E-09 1.180E-11 REMAINDER 1.070E-13 2.032E-11 4.000E-10 7.080E-16-1.000E+00 4.140E-11 1.470E-09 EFFECTIVE 1.140E-13 2.147E-11 4.226E-10 7.480E-16-1.000E+00 1.170E-10 6.950E-10 SKIN(FGR) 1.740E-13 2.598E-11 5.112E-10 9.050E-16-1.000E+00 0.000E+00 0.000E+00 Ba-141 GONADS 4.060E-14 4.282E-12 4.403E-11 1.550E-16-1.000E+00 1.410E-12 2.180E-10 BREAST 4.630E-14 4.116E-12 4.233E-11 1.490E-16-1.000E+00 1.470E-12 3.430E-11 LUNGS 4.030E-14 3.867E-12 3.977E-11 1.400E-16-1.000E+00 1.160E-10 1.510E-11 RED MARR 3.910E-14 3.923E-12 4.034E-11 1.420E-16-1.000E+00 2.490E-12 8.320E-11 BONE SUR 7.170E-14 6.105E-12 6.278E-11 2.210E-16-1.000E+00 4.730E-12 6.320E-11 THYROID 4.150E-14 4.033E-12 4.147E-11 1.460E-16-1.000E+00 1.330E-12 1.030E-11 REMAINDER 3.870E-14 3.812E-12 3.920E-11 1.380E-16-1.000E+00 2.270E-11 4.280E-09 EFFECTIVE 4.160E-14 4.061E-12 4.176E-11 1.470E-16-1.000E+00 2.180E-11 1.360E-09 SKIN(FGR) 1.070E-13 1.039E-10 1.068E-09 3.760E-15-1.000E+00 0.000E+00 0.000E+00 Ba-137m GONADS 2.820E-14 2.334E-12 3.877E-12 1.240E-16-1.000E+00 0.000E+00 9.750E-12 BREAST 3.220E-14 2.258E-12 3.752E-12 1.200E-16-1.000E+00 0.000E+00 3.570E-12 LUNGS 2.800E-14 2.127E-12 3.533E-12 1.130E-16-1.000E+00 0.000E+00 3.140E-12 RED MARR 2.730E-14 2.070E-12 3.439E-12 1.100E-16-1.000E+00 0.000E+00 6.290E-12 BONE SUR 4.630E-14 5.383E-12 8.942E-12 2.860E-16-1.000E+00 0.000E+00 4.060E-12 THYROID 2.880E-14 2.145E-12 3.564E-12 1.140E-16-1.000E+00 0.000E+00 8.460E-11 REMAINDER 2.680E-14 2.070E-12 3.439E-12 1.100E-16-1.000E+00 0.000E+00 3.340E-11 EFFECTIVE 2.880E-14 2.277E-12 3.783E-12 1.210E-16-1.000E+00 0.000E+00 1.680E-11 SKIN(FGR) 3.730E-14 2.710E-12 4.502E-12 1.440E-16-1.000E+00 0.000E+00 0.000E+00 Pd-109 GONADS 2.710E-16 1.404E-11 2.783E-10 4.892E-16-1.000E+00 2.130E-12 5.720E-10 BREAST 3.520E-16 1.350E-11 2.677E-10 4.705E-16-1.000E+00 5.110E-13 1.200E-10 LUNGS 1.940E-16 1.273E-11 2.522E-10 4.432E-16-1.000E+00 1.200E-09 7.310E-11 RED MARR 1.740E-16 1.287E-11 2.551E-10 4.483E-16-1.000E+00 9.820E-13 1.660E-10 BONE SUR 7.020E-16 1.958E-11 3.882E-10 6.823E-16-1.000E+00 9.580E-13 9.631E-11 THYROID 2.460E-16 1.331E-11 2.639E-10 4.638E-16-1.000E+00 1.550E-13 6.250E-11 REMAINDER 1.920E-16 1.248E-11 2.472E-10 4.346E-16-1.000E+00 5.040E-10 2.110E-09 EFFECTIVE 2.510E-16 1.332E-11 2.641E-10 4.642E-16-1.000E+00 2.960E-10 8.271E-10 SKIN(FGR) 2.150E-14 1.785E-11 3.543E-10 6.229E-16-1.000E+00 0.000E+00 0.000E+00 Rh-106 GONADS 1.010E-14 1.327E-11 1.861E-11 8.070E-16-1.000E+00 0.000E+00 9.670E-11 BREAST 1.160E-14 1.271E-11 1.783E-11 7.730E-16-1.000E+00 0.000E+00 1.590E-11 LUNGS 1.010E-14 1.210E-11 1.697E-11 7.360E-16-1.000E+00 0.000E+00 6.210E-12 RED MARR 9.750E-15 1.230E-11 1.725E-11 7.480E-16-1.000E+00 0.000E+00 2.350E-11 BONE SUR 1.720E-14 1.809E-11 2.537E-11 1.100E-15-1.000E+00 0.000E+00 8.890E-12 THYROID 1.030E-14 1.260E-11 1.766E-11 7.660E-16-1.000E+00 0.000E+00 1.820E-12 REMAINDER 9.630E-15 1.189E-11 1.667E-11 7.230E-16-1.000E+00 0.000E+00 8.540E-10 EFFECTIVE 1.040E-14 1.265E-11 1.773E-11 7.690E-16-1.000E+00 0.000E+00 2.870E-10 SKIN(FGR) 1.090E-13 7.368E-11 1.033E-10 4.480E-15-1.000E+00 0.000E+00 0.000E+00 Rh-103m GONADS 1.250E-17 6.411E-12 1.340E-10 2.230E-16-1.000E+00 8.910E-14 1.640E-09 BREAST 2.150E-17 6.152E-12 1.286E-10 2.140E-16-1.000E+00 8.800E-14 1.440E-09 LUNGS 1.870E-18 5.836E-12 1.220E-10 2.030E-16-1.000E+00 7.750E-12 1.420E-09 RED MARR 2.820E-18 5.893E-12 1.232E-10 2.050E-16-1.000E+00 8.840E-14 1.460E-09

Numerical Applications Inc. Attachment 7 Page 246 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 BONE SUR 1.760E-17 8.883E-12 1.856E-10 3.090E-16-1.000E+00 8.730E-14 1.430E-09 THYROID 8.550E-18 6.066E-12 1.268E-10 2.110E-16-1.000E+00 8.490E-14 1.410E-09 REMAINDER 3.680E-18 5.721E-12 1.196E-10 1.990E-16-1.000E+00 1.340E-12 2.110E-08 EFFECTIVE 8.800E-18 6.095E-12 1.274E-10 2.120E-16-1.000E+00 1.380E-12 7.400E-09 SKIN(FGR) 4.490E-17 4.082E-10 8.531E-09 1.420E-14-1.000E+00 0.000E+00 0.000E+00 Tc-101 GONADS 1.570E-14 2.127E-12 1.411E-11 7.980E-17-1.000E+00 2.500E-13 5.800E-11 BREAST 1.800E-14 2.063E-12 1.369E-11 7.740E-17-1.000E+00 3.030E-13 8.970E-12 LUNGS 1.540E-14 1.935E-12 1.284E-11 7.260E-17-1.000E+00 2.830E-11 3.860E-12 RED MARR 1.460E-14 1.946E-12 1.291E-11 7.300E-17-1.000E+00 3.190E-13 1.470E-11 BONE SUR 3.210E-14 3.332E-12 2.210E-11 1.250E-16-1.000E+00 2.800E-13 6.750E-12 THYROID 1.590E-14 1.983E-12 1.316E-11 7.440E-17-1.000E+00 7.720E-12 2.910E-12 REMAINDER 1.470E-14 1.885E-12 1.250E-11 7.070E-17-1.000E+00 3.520E-12 1.270E-09 EFFECTIVE 1.610E-14 2.031E-12 1.347E-11 7.620E-17-1.000E+00 4.840E-12 3.990E-10 SKIN(FGR) 4.770E-14 4.691E-12 3.112E-11 1.760E-16-1.000E+00 0.000E+00 0.000E+00 Eu-154 GONADS 6.000E-14 1.985E-11 2.441E-10 7.100E-16-1.000E+00 1.170E-08 6.140E-10 BREAST 6.810E-14 1.904E-11 2.341E-10 6.810E-16-1.000E+00 1.550E-08 7.600E-11 LUNGS 5.990E-14 1.809E-11 2.224E-10 6.470E-16-1.000E+00 7.920E-08 1.570E-11 RED MARR 5.870E-14 1.834E-11 2.255E-10 6.560E-16-1.000E+00 1.060E-07 1.330E-10 BONE SUR 9.430E-14 2.720E-11 3.345E-10 9.730E-16-1.000E+00 5.230E-07 5.240E-11 THYROID 6.150E-14 1.884E-11 2.317E-10 6.740E-16-1.000E+00 7.140E-09 4.640E-12 REMAINDER 5.750E-14 1.775E-11 2.183E-10 6.350E-16-1.000E+00 1.130E-07 5.870E-09 EFFECTIVE 6.140E-14 1.890E-11 2.324E-10 6.760E-16-1.000E+00 7.730E-08 1.950E-09 SKIN(FGR) 8.290E-14 7.967E-11 9.799E-10 2.850E-15-1.000E+00 0.000E+00 0.000E+00 Eu-155 GONADS 2.490E-15 2.336E-11 3.231E-11 1.440E-15-1.000E+00 3.560E-10 1.510E-10 BREAST 2.950E-15 2.222E-11 3.074E-11 1.370E-15-1.000E+00 6.140E-10 2.560E-11 LUNGS 2.220E-15 2.141E-11 2.962E-11 1.320E-15-1.000E+00 1.190E-08 9.390E-12 RED MARR 1.850E-15 2.190E-11 3.029E-11 1.350E-15-1.000E+00 1.430E-08 3.670E-11 BONE SUR 8.090E-15 3.033E-11 4.196E-11 1.870E-15-1.000E+00 1.520E-07 1.340E-11 THYROID 2.410E-15 2.174E-11 3.007E-11 1.340E-15-1.000E+00 2.400E-10 1.470E-12 REMAINDER 2.070E-15 2.125E-11 2.939E-11 1.310E-15-1.000E+00 1.110E-08 1.450E-09 EFFECTIVE 2.490E-15 2.238E-11 3.096E-11 1.380E-15-1.000E+00 1.120E-08 4.840E-10 SKIN(FGR) 3.390E-15 8.273E-11 1.144E-10 5.100E-15-1.000E+00 0.000E+00 0.000E+00 Eu-156 GONADS 6.570E-14 1.191E-13 2.661E-13 5.480E-18-1.000E+00 6.120E-10 4.020E-12 BREAST 7.420E-14 1.158E-13 2.588E-13 5.330E-18-1.000E+00 3.640E-10 3.000E-12 LUNGS 6.630E-14 1.060E-13 2.370E-13 4.880E-18-1.000E+00 1.840E-08 2.890E-12 RED MARR 6.560E-14 1.058E-13 2.365E-13 4.870E-18-1.000E+00 1.140E-09 6.570E-12 BONE SUR 9.580E-14 1.862E-13 4.162E-13 8.570E-18-1.000E+00 2.760E-09 6.460E-12 THYROID 6.780E-14 1.106E-13 2.472E-13 5.090E-18-1.000E+00 2.160E-10 2.860E-12 REMAINDER 6.410E-14 1.036E-13 2.316E-13 4.770E-18-1.000E+00 3.910E-09 6.130E-10 EFFECTIVE 6.750E-14 1.125E-13 2.515E-13 5.180E-18-1.000E+00 3.820E-09 1.870E-10 SKIN(FGR) 9.980E-14 1.173E-11 2.622E-11 5.400E-16-1.000E+00 0.000E+00 0.000E+00 La-143 GONADS 5.040E-15 4.689E-13 9.642E-12 1.630E-17-1.000E+00 6.530E-13 1.250E-10 BREAST 5.700E-15 5.150E-13 1.059E-11 1.790E-17-1.000E+00 3.200E-13 9.740E-11 LUNGS 5.070E-15 1.602E-13 3.295E-12 5.570E-18-1.000E+00 1.060E-10 9.620E-11 RED MARR 5.010E-15 1.249E-13 2.567E-12 4.340E-18-1.000E+00 7.300E-13 5.430E-09 BONE SUR 7.590E-15 9.005E-13 1.852E-11 3.130E-17-1.000E+00 7.290E-13 2.070E-08 THYROID 5.190E-15 2.779E-13 5.714E-12 9.660E-18-1.000E+00 2.440E-13 9.430E-11 REMAINDER 4.900E-15 1.999E-13 4.111E-12 6.950E-18-1.000E+00 1.050E-11 2.980E-09 EFFECTIVE 5.180E-15 3.251E-13 6.684E-12 1.130E-17-1.000E+00 1.620E-11 2.230E-09 SKIN(FGR) 9.640E-14 1.496E-12 3.076E-11 5.200E-17-1.000E+00 0.000E+00 0.000E+00 Nb-97 GONADS 3.110E-14 3.889E-13 3.922E-13 6.510E-17-1.000E+00 8.650E-13 1.590E-12 BREAST 3.550E-14 3.800E-13 3.832E-13 6.360E-17-1.000E+00 1.120E-12 6.050E-13 LUNGS 3.100E-14 3.298E-13 3.326E-13 5.520E-17-1.000E+00 1.560E-10 4.910E-13 RED MARR 3.010E-14 3.298E-13 3.326E-13 5.520E-17-1.000E+00 1.140E-12 7.640E-13 BONE SUR 5.110E-14 5.753E-13 5.802E-13 9.630E-17-1.000E+00 8.260E-13 5.400E-13 THYROID 3.180E-14 3.525E-13 3.555E-13 5.900E-17-1.000E+00 9.200E-13 3.360E-13 REMAINDER 2.960E-14 3.262E-13 3.289E-13 5.460E-17-1.000E+00 1.050E-11 1.790E-10 EFFECTIVE 3.180E-14 3.590E-13 3.621E-13 6.010E-17-1.000E+00 2.240E-11 5.450E-11 SKIN(FGR) 6.510E-14 3.429E-11 3.458E-11 5.740E-15-1.000E+00 0.000E+00 0.000E+00 Nb-95m GONADS 2.880E-15 2.206E-12 4.799E-11 8.561E-17-1.000E+00 4.960E-11 2.420E-10 BREAST 3.310E-15 2.181E-12 4.739E-11 8.454E-17-1.000E+00 4.530E-11 1.664E-10 LUNGS 2.770E-15 1.741E-12 3.815E-11 6.808E-17-1.000E+00 3.070E-09 1.593E-10 RED MARR 2.590E-15 1.729E-12 3.793E-11 6.768E-17-1.000E+00 5.870E-11 3.500E-09 BONE SUR 6.600E-15 3.287E-12 7.147E-11 1.275E-16-1.000E+00 6.610E-11 7.990E-09 THYROID 2.890E-15 1.923E-12 4.201E-11 7.495E-17-1.000E+00 3.860E-11 1.572E-10 REMAINDER 2.630E-15 1.746E-12 3.822E-11 6.819E-17-1.000E+00 8.690E-10 7.196E-09

Numerical Applications Inc. Attachment 7 Page 247 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 EFFECTIVE 2.930E-15 1.974E-12 4.308E-11 7.686E-17-1.000E+00 6.590E-10 2.925E-09 SKIN(FGR) 1.120E-14 1.501E-10 3.360E-09 6.001E-15-1.000E+00 0.000E+00 0.000E+00 Pm-147 GONADS 7.480E-19 4.020E-11 2.343E-10 1.535E-15-1.000E+00 8.250E-15 7.415E-10 BREAST 9.560E-19 3.853E-11 2.246E-10 1.472E-15-1.000E+00 3.600E-14 1.361E-10 LUNGS 5.450E-19 3.657E-11 2.131E-10 1.397E-15-1.000E+00 7.740E-08 6.335E-11 RED MARR 4.460E-19 3.736E-11 2.178E-10 1.427E-15-1.000E+00 1.610E-09 2.435E-10 BONE SUR 2.180E-18 5.467E-11 3.189E-10 2.090E-15-1.000E+00 2.010E-08 3.248E-10 THYROID 6.750E-19 3.741E-11 2.181E-10 1.429E-15-1.000E+00 1.980E-14 4.383E-08 REMAINDER 5.260E-19 3.626E-11 2.113E-10 1.385E-15-1.000E+00 1.560E-09 3.153E-09 EFFECTIVE 6.930E-19 3.825E-11 2.229E-10 1.461E-15-1.000E+00 1.060E-08 2.514E-09 SKIN(FGR) 8.110E-16 1.033E-10 6.188E-10 4.056E-15-1.000E+00 0.000E+00 0.000E+00 Pm-148 GONADS 2.810E-14 6.812E-12 7.706E-11 2.450E-16-1.000E+00 2.120E-10 5.410E-10 BREAST 3.190E-14 6.756E-12 7.643E-11 2.430E-16-1.000E+00 7.190E-11 3.500E-10 LUNGS 2.830E-14 5.727E-12 6.479E-11 2.060E-16-1.000E+00 1.370E-08 3.300E-10 RED MARR 2.790E-14 5.588E-12 6.322E-11 2.010E-16-1.000E+00 1.070E-10 4.440E-10 BONE SUR 4.240E-14 1.273E-11 1.441E-10 4.580E-16-1.000E+00 7.080E-11 8.300E-10 THYROID 2.890E-14 5.978E-12 6.762E-11 2.150E-16-1.000E+00 3.820E-11 5.950E-08 REMAINDER 2.730E-14 5.644E-12 6.385E-11 2.030E-16-1.000E+00 4.100E-09 1.490E-09 EFFECTIVE 2.890E-14 6.339E-12 7.171E-11 2.280E-16-1.000E+00 2.950E-09 2.540E-09 SKIN(FGR) 7.970E-14 8.313E-12 9.405E-11 2.990E-16-1.000E+00 0.000E+00 0.000E+00 Pm-149 GONADS 5.300E-16 1.119E-11 1.789E-10 3.940E-16-1.000E+00 3.610E-12 4.070E-11 BREAST 6.070E-16 1.082E-11 1.730E-10 3.810E-16-1.000E+00 8.200E-13 1.210E-10 LUNGS 5.170E-16 1.016E-11 1.626E-10 3.580E-16-1.000E+00 3.120E-09 1.020E-10 RED MARR 4.890E-16 1.022E-11 1.635E-10 3.600E-16-1.000E+00 5.530E-12 9.440E-11 BONE SUR 1.100E-15 1.675E-11 2.679E-10 5.900E-16-1.000E+00 5.010E-12 8.720E-11 THYROID 5.360E-16 1.053E-11 1.685E-10 3.710E-16-1.000E+00 3.310E-13 4.760E-07 REMAINDER 4.910E-16 9.908E-12 1.585E-10 3.490E-16-1.000E+00 1.390E-09 1.570E-10 EFFECTIVE 5.410E-16 1.067E-11 1.707E-10 3.760E-16-1.000E+00 7.930E-10 1.440E-08 SKIN(FGR) 2.190E-14 1.825E-11 2.920E-10 6.430E-16-1.000E+00 0.000E+00 0.000E+00 Pm-151 GONADS 1.480E-14 2.523E-11 2.771E-11 2.320E-15-1.000E+00 7.170E-11 2.330E-11 BREAST 1.700E-14 2.414E-11 2.652E-11 2.220E-15-1.000E+00 1.590E-11 2.520E-11 LUNGS 1.440E-14 2.305E-11 2.532E-11 2.120E-15-1.000E+00 1.640E-09 2.640E-11 RED MARR 1.370E-14 2.360E-11 2.592E-11 2.170E-15-1.000E+00 2.720E-11 2.460E-11 BONE SUR 2.990E-14 3.327E-11 3.655E-11 3.060E-15-1.000E+00 1.860E-11 2.190E-11 THYROID 1.500E-14 2.381E-11 2.616E-11 2.190E-15-1.000E+00 6.180E-12 3.870E-09 REMAINDER 1.370E-14 2.283E-11 2.509E-11 2.100E-15-1.000E+00 8.390E-10 1.650E-10 EFFECTIVE 1.510E-14 2.403E-11 2.640E-11 2.210E-15-1.000E+00 4.730E-10 1.820E-10 SKIN(FGR) 3.320E-14 8.199E-11 9.007E-11 7.540E-15-1.000E+00 0.000E+00 0.000E+00 Pm-148m GONADS 9.470E-14 1.585E-11 6.748E-11 6.270E-16-1.000E+00 1.190E-09 3.630E-11 BREAST 1.080E-13 1.519E-11 6.468E-11 6.010E-16-1.000E+00 1.240E-09 4.680E-11 LUNGS 9.420E-14 1.446E-11 6.156E-11 5.720E-16-1.000E+00 3.590E-08 4.530E-11 RED MARR 9.140E-14 1.466E-11 6.242E-11 5.800E-16-1.000E+00 1.360E-09 4.300E-11 BONE SUR 1.580E-13 2.161E-11 9.202E-11 8.550E-16-1.000E+00 1.360E-09 4.070E-11 THYROID 9.680E-14 1.502E-11 6.393E-11 5.940E-16-1.000E+00 1.050E-09 9.100E-08 REMAINDER 9.010E-14 1.418E-11 6.038E-11 5.610E-16-1.000E+00 3.580E-09 1.550E-10 EFFECTIVE 9.680E-14 1.509E-11 6.425E-11 5.970E-16-1.000E+00 6.100E-09 2.800E-09 SKIN(FGR) 1.180E-13 1.150E-10 4.897E-10 4.550E-15-1.000E+00 0.000E+00 0.000E+00 Pr-144 GONADS 1.900E-15 1.200E-11 1.202E-11 2.640E-15-1.000E+00 2.410E-15 1.100E-11 BREAST 2.150E-15 1.145E-11 1.147E-11 2.520E-15-1.000E+00 1.050E-14 1.170E-11 LUNGS 1.900E-15 1.100E-11 1.102E-11 2.420E-15-1.000E+00 9.400E-11 1.260E-11 RED MARR 1.870E-15 1.127E-11 1.129E-11 2.480E-15-1.000E+00 1.380E-14 1.090E-11 BONE SUR 2.990E-15 1.568E-11 1.571E-11 3.450E-15-1.000E+00 1.470E-14 9.320E-12 THYROID 1.950E-15 1.127E-11 1.129E-11 2.480E-15-1.000E+00 8.470E-15 6.210E-10 REMAINDER 1.840E-15 1.091E-11 1.093E-11 2.400E-15-1.000E+00 1.400E-12 1.340E-10 EFFECTIVE 1.950E-15 1.150E-11 1.152E-11 2.530E-15-1.000E+00 1.170E-11 6.660E-11 SKIN(FGR) 8.430E-14 4.477E-11 4.485E-11 9.850E-15-1.000E+00 0.000E+00 0.000E+00 Pr-144m GONADS 3.250E-16 3.113E-11 5.489E-11 1.599E-15-1.000E+00 0.000E+00 3.610E-11 BREAST 4.200E-16 2.971E-11 5.240E-11 1.526E-15-1.000E+00 0.000E+00 3.850E-11 LUNGS 2.000E-16 2.886E-11 5.089E-11 1.482E-15-1.000E+00 0.000E+00 3.750E-11 RED MARR 1.560E-16 2.965E-11 5.228E-11 1.523E-15-1.000E+00 0.000E+00 3.650E-11 BONE SUR 8.160E-16 3.983E-11 7.024E-11 2.046E-15-1.000E+00 0.000E+00 3.360E-11 THYROID 2.810E-16 2.852E-11 5.030E-11 1.465E-15-1.000E+00 0.000E+00 1.790E-08 REMAINDER 1.980E-16 2.883E-11 5.084E-11 1.481E-15-1.000E+00 0.000E+00 1.540E-10 EFFECTIVE 2.790E-16 2.989E-11 5.271E-11 1.535E-15-1.000E+00 0.000E+00 6.080E-10 SKIN(FGR) 5.080E-16 9.826E-11 1.733E-10 5.047E-15-1.000E+00 0.000E+00 0.000E+00 Sm-153

Numerical Applications Inc. Attachment 7 Page 248 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 GONADS 2.330E-15 1.465E-12 2.052E-11 5.200E-17-1.000E+00 2.360E-11 0.000E+00 BREAST 2.820E-15 1.505E-12 2.107E-11 5.340E-17-1.000E+00 5.670E-12 0.000E+00 LUNGS 1.970E-15 1.045E-12 1.464E-11 3.710E-17-1.000E+00 2.050E-09 0.000E+00 RED MARR 1.620E-15 8.791E-13 1.231E-11 3.120E-17-1.000E+00 6.660E-11 0.000E+00 BONE SUR 7.290E-15 4.254E-12 5.958E-11 1.510E-16-1.000E+00 1.570E-10 0.000E+00 THYROID 2.220E-15 1.181E-12 1.653E-11 4.190E-17-1.000E+00 1.510E-12 0.000E+00 REMAINDER 1.850E-15 1.042E-12 1.460E-11 3.700E-17-1.000E+00 8.840E-10 0.000E+00 EFFECTIVE 2.280E-15 1.299E-12 1.819E-11 4.610E-17-1.000E+00 5.310E-10 0.000E+00 SKIN(FGR) 1.450E-14 1.953E-12 2.734E-11 6.930E-17-1.000E+00 0.000E+00 0.000E+00 Y-94 GONADS 5.490E-14 5.455E-12 1.194E-11 2.530E-16-1.000E+00 1.230E-13 0.000E+00 BREAST 6.210E-14 5.325E-12 1.166E-11 2.470E-16-1.000E+00 4.400E-13 0.000E+00 LUNGS 5.500E-14 4.959E-12 1.086E-11 2.300E-16-1.000E+00 1.480E-10 0.000E+00 RED MARR 5.420E-14 4.959E-12 1.086E-11 2.300E-16-1.000E+00 4.180E-13 0.000E+00 BONE SUR 8.220E-14 9.120E-12 1.997E-11 4.230E-16-1.000E+00 3.280E-13 0.000E+00 THYROID 5.650E-14 5.023E-12 1.100E-11 2.330E-16-1.000E+00 4.120E-13 0.000E+00 REMAINDER 5.300E-14 4.829E-12 1.058E-11 2.240E-16-1.000E+00 3.080E-12 0.000E+00 EFFECTIVE 5.620E-14 5.217E-12 1.142E-11 2.420E-16-1.000E+00 1.890E-11 0.000E+00 SKIN(FGR) 1.800E-13 4.506E-11 9.867E-11 2.090E-15-1.000E+00 0.000E+00 0.000E+00 Y-95 GONADS 4.650E-14 4.607E-11 9.646E-10 1.600E-15-1.000E+00 1.070E-13 2.060E-08 BREAST 5.190E-14 4.406E-11 9.224E-10 1.530E-15-1.000E+00 3.170E-13 1.720E-08 LUNGS 4.720E-14 4.204E-11 8.802E-10 1.460E-15-1.000E+00 8.040E-11 1.760E-08 RED MARR 4.730E-14 4.262E-11 8.922E-10 1.480E-15-1.000E+00 3.200E-13 1.870E-08 BONE SUR 6.410E-14 6.105E-11 1.278E-09 2.120E-15-1.000E+00 3.790E-13 1.740E-08 THYROID 4.840E-14 4.377E-11 9.163E-10 1.520E-15-1.000E+00 2.790E-13 1.760E-08 REMAINDER 4.590E-14 4.147E-11 8.681E-10 1.440E-15-1.000E+00 1.250E-12 2.210E-08 EFFECTIVE 4.790E-14 4.377E-11 9.163E-10 1.520E-15-1.000E+00 1.020E-11 1.980E-08 SKIN(FGR) 1.590E-13 6.249E-11 1.308E-09 2.170E-15-1.000E+00 0.000E+00 0.000E+00 Y-91m GONADS 2.490E-14 6.223E-11 1.102E-09 2.180E-15-1.000E+00 3.210E-13 3.040E-09 BREAST 2.850E-14 5.966E-11 1.056E-09 2.090E-15-1.000E+00 6.080E-13 2.650E-09 LUNGS 2.480E-14 5.710E-11 1.011E-09 2.000E-15-1.000E+00 7.000E-11 2.620E-09 RED MARR 2.390E-14 5.824E-11 1.031E-09 2.040E-15-1.000E+00 7.740E-13 2.950E-09 BONE SUR 4.280E-14 8.422E-11 1.491E-09 2.950E-15-1.000E+00 6.210E-13 2.710E-09 THYROID 2.540E-14 5.852E-11 1.036E-09 2.050E-15-1.000E+00 5.020E-13 2.740E-09 REMAINDER 2.370E-14 5.652E-11 1.001E-09 1.980E-15-1.000E+00 3.740E-12 3.520E-09 EFFECTIVE 2.550E-14 5.966E-11 1.056E-09 2.090E-15-1.000E+00 9.820E-12 3.040E-09 SKIN(FGR) 3.110E-14 7.251E-11 1.284E-09 2.540E-15-1.000E+00 0.000E+00 0.000E+00 Br-82 GONADS 1.270E-13 1.669E-11 3.530E-10 5.840E-16-1.000E+00 1.690E-10 1.390E-08 BREAST 1.440E-13 1.596E-11 3.376E-10 5.585E-16-1.000E+00 2.100E-10 1.240E-08 LUNGS 1.270E-13 1.517E-11 3.209E-10 5.309E-16-1.000E+00 1.680E-09 1.270E-08 RED MARR 1.240E-13 1.542E-11 3.260E-10 5.394E-16-1.000E+00 2.180E-10 1.320E-08 BONE SUR 1.990E-13 2.238E-11 4.734E-10 7.832E-16-1.000E+00 1.920E-10 1.260E-08 THYROID 1.300E-13 1.588E-11 3.358E-10 5.556E-16-1.000E+00 2.060E-10 1.260E-08 REMAINDER 1.220E-13 1.490E-11 3.152E-10 5.215E-16-1.000E+00 3.310E-10 1.450E-08 EFFECTIVE 1.300E-13 1.585E-11 3.353E-10 5.546E-16-1.000E+00 4.130E-10 1.350E-08 SKIN(FGR) 1.540E-13 5.253E-11 1.110E-09 1.836E-15-1.000E+00 0.000E+00 0.000E+00 Br-83 GONADS 3.740E-16 3.368E-13 3.429E-13 4.790E-17-1.000E+00 1.130E-12 1.560E-12 BREAST 4.290E-16 3.297E-13 3.357E-13 4.690E-17-1.000E+00 1.140E-12 5.170E-13 LUNGS 3.690E-16 3.002E-13 3.057E-13 4.270E-17-1.000E+00 1.820E-10 3.890E-13 RED MARR 3.540E-16 2.932E-13 2.985E-13 4.170E-17-1.000E+00 1.140E-12 8.590E-13 BONE SUR 6.750E-16 6.841E-13 6.965E-13 9.730E-17-1.000E+00 1.140E-12 4.380E-13 THYROID 3.800E-16 3.044E-13 3.100E-13 4.330E-17-1.000E+00 1.140E-12 2.660E-13 REMAINDER 3.520E-16 2.932E-13 2.985E-13 4.170E-17-1.000E+00 5.310E-12 3.570E-10 EFFECTIVE 3.820E-16 3.227E-13 3.286E-13 4.590E-17-1.000E+00 2.410E-11 1.080E-10 SKIN(FGR) 1.850E-14 7.241E-11 7.373E-11 1.030E-14-1.000E+00 0.000E+00 0.000E+00 Br-84 GONADS 9.160E-14 5.451E-12 9.607E-11 1.910E-16-1.000E+00 2.840E-12 9.960E-10 BREAST 1.020E-13 5.280E-12 9.305E-11 1.850E-16-1.000E+00 3.310E-12 1.590E-10 LUNGS 9.270E-14 4.852E-12 8.550E-11 1.700E-16-1.000E+00 1.560E-10 6.630E-11 RED MARR 9.260E-14 4.880E-12 8.601E-11 1.710E-16-1.000E+00 3.270E-12 4.390E-10 BONE SUR 1.280E-13 8.020E-12 1.413E-10 2.810E-16-1.000E+00 2.990E-12 5.530E-10 THYROID 9.500E-14 5.109E-12 9.003E-11 1.790E-16-1.000E+00 3.120E-12 5.250E-11 REMAINDER 8.990E-14 4.766E-12 8.399E-11 1.670E-16-1.000E+00 1.870E-11 7.370E-09 EFFECTIVE 9.410E-14 5.137E-12 9.053E-11 1.800E-16-1.000E+00 2.610E-11 2.560E-09 SKIN(FGR) 1.880E-13 5.565E-11 9.808E-10 1.950E-15-1.000E+00 0.000E+00 0.000E+00 Am-242 GONADS 6.090E-16 6.027E-11 4.425E-10 2.240E-15-1.000E+00 1.940E-09 1.340E-09 BREAST 7.300E-16 5.758E-11 4.228E-10 2.140E-15-1.000E+00 2.940E-12 1.800E-10 LUNGS 5.510E-16 5.596E-11 4.109E-10 2.080E-15-1.000E+00 5.200E-08 4.010E-11

Numerical Applications Inc. Attachment 7 Page 249 of 249 Palisades Design Basis Fuel Handling Accident AST Radiological Analysis Calculation Number: NAI-1149-016 Rev. 1 RED MARR 4.770E-16 5.731E-11 4.208E-10 2.130E-15-1.000E+00 1.320E-08 2.810E-10 BONE SUR 1.880E-15 7.776E-11 5.709E-10 2.890E-15-1.000E+00 1.650E-07 9.770E-11 THYROID 5.940E-16 5.462E-11 4.010E-10 2.030E-15-1.000E+00 2.520E-12 6.400E-12 REMAINDER 5.180E-16 5.569E-11 4.089E-10 2.070E-15-1.000E+00 8.540E-09 6.260E-09 EFFECTIVE 6.150E-16 5.812E-11 4.267E-10 2.160E-15-1.000E+00 1.580E-08 2.280E-09 SKIN(FGR) 8.200E-15 2.217E-10 1.628E-09 8.240E-15-1.000E+00 0.000E+00 0.000E+00 Np-238 GONADS 2.660E-14 7.315E-13 9.675E-13 4.740E-17-1.000E+00 1.990E-09 3.770E-12 BREAST 3.020E-14 7.007E-13 9.267E-13 4.540E-17-1.000E+00 4.180E-11 7.070E-13 LUNGS 2.650E-14 6.713E-13 8.879E-13 4.350E-17-1.000E+00 3.470E-09 2.720E-13 RED MARR 2.610E-14 6.852E-13 9.063E-13 4.440E-17-1.000E+00 1.690E-08 1.070E-12 BONE SUR 3.990E-14 9.923E-13 1.312E-12 6.430E-17-1.000E+00 2.100E-07 6.060E-13 THYROID 2.730E-14 6.590E-13 8.716E-13 4.270E-17-1.000E+00 2.450E-11 5.290E-14 REMAINDER 2.550E-14 6.682E-13 8.838E-13 4.330E-17-1.000E+00 2.550E-09 1.240E-09 EFFECTIVE 2.720E-14 7.007E-13 9.267E-13 4.540E-17-1.000E+00 1.000E-08 3.740E-10 SKIN(FGR) 4.310E-14 1.667E-10 2.204E-10 1.080E-14-1.000E+00 0.000E+00 0.000E+00 Pu-243 GONADS 1.020E-15 1.978E-11 2.034E-11 2.540E-15-1.000E+00 1.670E-12 6.990E-11 BREAST 1.210E-15 1.885E-11 1.938E-11 2.420E-15-1.000E+00 2.750E-13 1.540E-11 LUNGS 9.280E-16 1.846E-11 1.898E-11 2.370E-15-1.000E+00 2.270E-10 8.400E-12 RED MARR 7.840E-16 1.900E-11 1.954E-11 2.440E-15-1.000E+00 5.770E-12 1.930E-11 BONE SUR 3.230E-15 2.484E-11 2.554E-11 3.190E-15-1.000E+00 6.530E-11 7.400E-12 THYROID 9.910E-16 1.768E-11 1.818E-11 2.270E-15-1.000E+00 1.130E-13 1.160E-12 REMAINDER 8.660E-16 1.853E-11 1.906E-11 2.380E-15-1.000E+00 4.690E-11 5.200E-10 EFFECTIVE 1.030E-15 1.916E-11 1.970E-11 2.460E-15-1.000E+00 4.440E-11 1.790E-10 SKIN(FGR) 8.150E-15 9.111E-11 9.368E-11 1.170E-14-1.000E+00 0.000E+00 0.000E+00