IR 05000498/2019010

From kanterella
Jump to navigation Jump to search
NRC Design Bases Assurance Inspection (Teams) Report 05000498/2019010 and 05000499/2019010
ML19144A069
Person / Time
Site: South Texas  STP Nuclear Operating Company icon.png
Issue date: 05/23/2019
From: Vincent Gaddy
Region 4 Engineering Branch 1
To: Gerry Powell
South Texas
Gaddy V
References
IR 2019010
Download: ML19144A069 (22)


Text

May 23, 2019

SUBJECT:

SOUTH TEXAS PROJECT ELECTRIC GENERATING STATION, UNITS 1 AND 2 - NRC DESIGN BASES ASSURANCE INSPECTION (TEAMS),

INSPECTION REPORT 05000498/2019010 and 05000499/2019010

Dear Mr. Powell:

On April 11, 2019, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at your South Texas Project Electric Generating Station, Units 1 and 2, and discussed the results of this inspection with you and members of your staff. The results of this inspection are documented in the enclosed report.

NRC inspectors documented two findings of very low safety significance (Green) in this report.

These findings involved violations of NRC requirements. The NRC is treating these violations as non-cited violations (NCVs) consistent with Section 2.3.2 of the Enforcement Policy.

If you contest the violations or significance of these NCVs, you should provide a response within 30 days of the date of this inspection report, with the basis for your denial, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555-0001; with copies to the Regional Administrator, Region IV; the Director, Office of Enforcement; and the NRC resident inspector at the South Texas Project Electric Generating Station.

If you disagree with a cross-cutting aspect assignment in this report, you should provide a response within 30 days of the date of this inspection report, with the basis for your disagreement, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555-0001; with copies to the Regional Administrator, Region IV; and the NRC resident inspector at the South Texas Project Electric Generating Station. This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with 10 CFR 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely,

/RA/

Vincent G. Gaddy, Chief Engineering Branch 1 Division of Reactor Safety

Docket Nos. 50-498 and 50-499 License Nos. NPF-76 and NPF-80

Enclosure:

Inspection Report 05000498/2019010 and 05000499/2019010

Enclosure U.S. NUCLEAR REGULATORY COMMISSION

Inspection Report

Docket Numbers:

05000498, 05000499

License Numbers:

NPF-76, NPF-80

Report Numbers:

05000498/2019010, 05000499/2019010

Enterprise Identifier: I-2019-010-0038

Licensee:

STP Nuclear Operating Company

Facility:

South Texas Project Electric Generating Station, Units 1 and 2

Location:

Wadsworth, Texas

Inspection Dates:

March 25, 2019, to April 11, 2019

Inspectors:

W. Sifre, Senior Reactor Inspector, Team Lead

R. Smith, Nuclear Systems Engineer

W. Cullum, Reactor Inspector

S. Makor, Reactor Inspector

S. Kobylarz, Contractor

B. Sherbin, Contractor

Approved By:

Vincent G. Gaddy, Chief

Engineering Branch 1

Division of Reactor Safety

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a Design Bases Assurance Inspection at South Texas Project Electric Generating Station, Units 1 and 2 in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information. NRC-identified and self-revealed findings, violations, and additional items are summarized in the table below.

Licensee-identified non-cited violations are documented in the Inspection Results at the end of this report.

List of Findings and Violations

Inadequate Corrective Actions for Distribution Panel Molded Case Circuit Breaker Testing Cornerstone Significance Cross-cutting Aspect Inspection Procedure Mitigating Systems Green NCV 05000498/2019010-01;

NCV 05000499/2019010-01 Closed

[H.4] -

Teamwork 71111.21M The inspectors identified a Green non-cited violation for the failure to assure that conditions adverse to quality, such as failures, malfunctions, deficiencies, deviations, defective material and equipment, and nonconformances are promptly identified and corrected. Specifically, the licensee failed to completely correct a condition adverse to quality by performing electrical testing on the distribution panel molded case circuit breakers as documented in the engineering evaluation.

Failure to Incorporate Design Changes into Emergency Procedures and Design Documents Cornerstone Significance Cross-cutting Aspect Inspection Procedure Mitigating Systems Green NCV 05000498/2019010-02;

NCV 05000499/2019010-02 Closed

[H.4] -

Teamwork 71111.21M The inspectors identified a Green non-cited violation for failure to incorporate design changes into safety-related procedures and the updated final safety analysis report (UFSAR).

Specifically, the failure to incorporate these changes had a direct impact on operator actions associated with starting high-head safety injection (HHSI) pumps in the required time during a small-break loss-of-coolant accident (SBLOCA) while shutdown in Modes 3 and 4.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs)in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html.

Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

REACTOR SAFETY

===71111.21MDesign Bases Assurance Inspection (Teams)

The inspectors evaluated the following components and listed applicable attributes, permanent modifications, and operating experience:

Design Review - Risk-Significant/Low Design Margin Components (IP Section 02.02)

=

From March 25, 2019, to April 11, 2019, the inspectors reviewed the following components and listed applicable attributes.

(1) Emergency Diesel Generator Room Safety-Related Ventilation Fan Unit 1, Train B

a) Mechanical calculations for room heat generation and for fan sizing

b) Seismic qualification of fan and motor assembly

c) Fan and motor assembly vendor manual, airflow testing performed after equipment installation, and control scheme for fan starts and stops

d) Component walkdown to assess material condition, configuration, and consistency with drawings and calculations

e) Corrective action history and corrective/preventive maintenance records

f) Fan motor electrical thermal overload sizing

(2) Refueling Water Storage Tank, Unit 2

a) Seismic qualification of tank and tank foundation

b) Calculations, procedures, and analyses associated with the tank water capacity and boric acid requirements for LOCA mitigation

c) Calculations, procedures, and analyses associated with the suction swap-over of emergency core cooling system (ECCS) pumps from the tank to the containment sumps to verify concerns associated with air entrapment and vortexing were addressed

d) Component walkdown to assess material condition, configuration, and consistency with drawings and calculations

e) Records associated with operating experience and preventive and corrective maintenance

(3) 120/208 VAC Distribution Panel DPA (B)(C) 235

a) Component maintenance history and corrective action program reports to verify the monitoring of potential degradation

b) Calculations for electrical distribution, system load flow, voltage drop, short-circuit, and electrical protection to verify that bus capacity and voltages remained within minimum acceptable limits

c) Component walkdown and vendor document review to verify installed configuration, specifications and acceptance criteria, and design bases functions

d) Procedures for circuit breaker inspection and testing to compare maintenance practices against industry standards and vendor guidance

e) Design bases documents, updated final safety analysis report, technical specifications and bases to assure licensing bases match component capabilities

(4) Engineered Safety Features Load Sequencer Cabinet A, Unit 1

a) Component walkdown and visual inspection was performed to assess the material condition and configuration

b) Maintenance and testing procedures and performance history was reviewed to assure consistency with vendor and industry recommendations

c) Design bases documents, updated final safety analysis report, technical specifications and bases to assure licensing bases match component capabilities

(5) Auxiliary Feedwater Pump 11 Area Supply Fan Motor, Unit 1

a) Component walkdown and visual inspection was performed to assess the material condition and configuration

b) Component and area temperature requirements, alarm settings, and response procedures were reviewed and validated against vendor and plant design criteria

c) Component corrective actions and maintenance history was reviewed to validate continued operability and functionality

Design Review - Large Early Release Frequency (LERF) (IP Section 02.02) (1 Sample)

From March 25, 2019, to April 11, 2019, the inspectors reviewed the following large-early-release-frequency component.

High-Head Safety Injection Valves 4A, B, C

a) Specific component design basis including required safety functions

b) Calculations for maximum torque, thrust, differential pressure for opening and closing, and degraded voltage

c) Maintenance history including motor-operated valve (MOV) testing and surveillance procedure implementation

d) Manufacturer recommendations for maintenance and valve setup

e) Walkdown of components to assess physical condition

Evaluation of Operator Procedures and Actions Related to Components and Permanent

Modifications (6 Samples)

From March 25, 2019, to April 11, 2019, the inspectors observed the following operator actions associated with selected components and modifications.

(1) Control room operator actions resulting from a simulated small-break LOCA (SBLOCA) while the plant is in Mode 3, hot shutdown condition. From the receipt of associated alarms, actions to manually start both a low-head safety injection (LHSI)pump and high-head safety injection (HHSI) pump within 10 minutes. (Associated with the HHSI Valves 4A, B, C)
(2) Control room and a plant operator actions to provide sufficient channel 1 battery capacity for a 4-hour duration following a simulated loss of all alternating current (ac).

From the loss of all ac power, actions taken to shed loads from train A following an automatic load sequencing within 30 minutes of the event. (Associated with the Engineered Safety Features Load Sequencer Cabinet A, Unit 1)

(3) Control room operator actions to lowering all steam generator (SG) power-operated relief valves (PORVs) setpoint to at least 1000 psig during a simulated SBLOCA.

From the receipt of associated alarms, actions to manually reduce the setpoint of the all SG PORVs to less than 1000 psig within 45 minutes. (Associated with Modification DCP 08-9595-10)

(4) Control room operator actions to identify a simulated spuriously opened SG PORV during a SG tube rupture. From the receipt of the associated alarms, the crew will identify a spuriously opened PORV within 10 minutes. (Associated with Modification DCP 08-9595-10)
(5) Control room and plant operator actions to isolate a simulated spuriously opened SG PORV during a SG tube rupture. From receipt of the associated alarms, the crew attempts to isolate the spuriously opened PORV from the control room and when unsuccessful will direct a plant operator to shut the manual steam isolation valve to the PORV within 15 minutes after having identified the failed open PORV.

(Associated with Modification DCP 08-9595-10)

(6) Control room operator actions for a simulated large-break loss-of-coolant accident with a failure of one train of both low and HHSI valves to swap from the refueling water storage tank (RWST) to containment sump. From receipt of the associated alarms, the crew will act to secure the low and HHSI pumps in the associated train that failed to swap from the RWST to the containment sump before the tank empty alarm is received. The crew will then follow procedural direction to realign the suction source for this train from the RWST to the containment sump and reestablish injection to the reactor coolant system (RCS) from this train. (Associated with the Refueling Water Storage Tank, Unit 2)

Permanent Modification (6 Samples)

From March 25, 2019, to April 11, 2019, the inspectors reviewed the following permanent modifications.

(1) DCP 06-15147-40, Replace Essential Cooling Water Pump 2A
(2) DCP 08-9595-10, Steam Generator Power Operated Relief Valves Fail Closed Modification
(3) DCP 04-7140-45, Replace ESF E2B Agastat Relays and Load Cell Switch Contact
(4) DCP 09-809-27, Replace Obsolete RCS Wide Range Pressure Transmitters
(5) DCP 13-15128-5, RHR Low Flow Trip Energize to Actuate Modification
(6) DCPs 05-11049-1, 05-11049-2, Install Test Connections at Emergency Standby Diesel Generator Control Panels to Facilitate Surveillance Testing

Operating Experience (4 Samples)

From March 25, 2019, to April 11, 2019, the inspectors reviewed the following operating experience issues.

(1) NRC Generic Letter 96-05, Periodic Verification of Design Basis Capability of Safety-Related Motor-Operated Valves
(2) NRC Generic Letter 2006-02, Grid Reliability and the Impact on Plant Risk and the Operability of Offsite Power
(3) NRC Information Notice 2013-18, Refueling Water Storage Tank Degradation
(4) NRC Information Notice 2017-16, Battery and Battery Charger Short-Circuit Current Contributions to a Fault on the Direct Current Distribution System

INSPECTION RESULTS

Inadequate Corrective Actions for Distribution Panel Molded Case Circuit Breaker Testing Cornerstone Significance Cross-cutting Aspect Inspection Procedure Mitigating Systems Green NCV 05000498/2019010-01; NCV 05000499/2019010-01 Closed

[H.4] Teamwork 71111.21M The inspectors identified a Green non-cited violation for the failure to assure that conditions adverse to quality, such as failures, malfunctions, deficiencies, deviations, defective material and equipment, and nonconformances are promptly identified and corrected. Specifically, the licensee failed to completely correct a condition adverse to quality by performing electrical testing on the distribution panel molded case circuit breakers as documented in the engineering evaluation.

Description:

The 120/208 VAC Distribution Panel is a component in the Class 1E 120V vital ac system that is designed to provide a reliable source of 120 VAC control and instrument power to the engineered safety feature (ESF) equipment during all modes of reactor operation, including postulated design-basis events for a period of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> after a loss of all offsite and onsite power.

The inspectors reviewed calculations for the electrical distribution, system load flow/voltage drop, short-circuit, and electrical protection to verify that bus capacity and voltages remained within minimum acceptable limits, procedures for circuit breaker inspection and testing to compare maintenance practices against industry and vendor guidance.

During this review, the inspectors determined that the licensee failed to completely correct an adverse condition by failing to perform electrical testing on ten

(10) distribution panels on three trains DPA(B)(C)135 and DPA(B)(C)235. Specifically, in March 2016 inspectors identified that the licensee failed to demonstrate that the safety-related molded case circuit breakers would perform satisfactorily and within limits. In response, the licensee opened condition report engineering evaluation (CREE) 16-2166 to address the adequacy of molded case circuit breaker testing to include overcurrent testing to validate that the circuit breaker will open as expected during a downstream fault condition. This requirement was a corrective action from a previously identified performance deficiency for the molded case circuit breaker testing and methodology documentation.

During questions from this inspection, the licensee realized they had failed to completely correct the original adverse to quality condition. The electrical testing for the DC and upstream breakers were completed, but the condition report was closed before the recommended corrective actions in CREE 16-2166 were completed for all of the safety-related panels, ac breakers. Specifically, the licensee had failed to perform required testing on the distribution panel molded case circuit breakers.

Corrective Action: In response to this issue, the licensee entered the issue into the corrective action program to evaluate and correct this condition. The inspectors determined that this finding does not represent an immediate safety concern because the last maintenance performed on these circuit breakers that did not receive electrical testing was completed for Unit 1, on April 4, 2017, and for Unit 2, on October 23, 2016. Because of these activities, there is a high confidence in the performance of the affected circuit breakers.

Corrective Action Reference: Condition Report 19-3431

Performance Assessment:

Performance Deficiency: The failure to correct a condition adverse to quality by not performing electrical testing on the distribution panel molded case circuit breakers as documented in an engineering evaluation was a performance deficiency. Specifically, the licensee completed testing on all DC and upstream circuit breakers in accordance with CREE 16-2166, but closed the action without completing testing on all of the affected distribution panel circuit breakers.

Screening: The inspectors screened this performance deficiency using IMC 0612, Appendix B, Issue Screening, and determined that this performance deficiency was more than minor because it was associated with the design control attribute of the mitigating systems cornerstone and adversely affect the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the deficiency resulted in ten distribution panels not receiving the electrical testing as recommended in CREE 16-2166.

Significance: The inspectors determined this finding adversely affected the mitigating systems cornerstone in accordance with Inspection Manual Chapter 0609, Attachment 4, Initial Characterization of Findings. The inspectors reviewed the finding using the criteria specified in Figure 1 of IMC 0609, Significance Determination Process (SDP), Appendix A, Significance Determination of Reactor Inspection Findings for At-Power Situations.

Cross-Cutting Aspect: This finding has a cross-cutting aspect in human performance associated with teamwork because the licensee did not communicate and coordinate their activities within and across organizational boundaries to ensure nuclear safety is maintained.

In this instance, the licensee performed an engineering evaluation and documented the need to do electrical testing but closed the condition report prior to ensuring that all of the tests were performed as required [H.4].

Enforcement:

Violation: Title 10 CFR Part 50, Appendix B, Criterion XVI, Corrective Actions, requires, in part, that conditions adverse to quality, such as failures, malfunctions, deficiencies, deviations, defective material and equipment, and nonconformances are promptly identified and corrected.

Contrary to the above, from 2012 to April 11, 2019, the licensee failed to correct a condition adverse to quality by not performing electrical testing on the distribution panel molded case circuit breakers as documented in the CREE 16-2166.

Enforcement Action: This violation is being treated as a non-cited violation, consistent with Section 2.3.2 of the NRC Enforcement Policy.

NCV 05000498/2019010-01; 05000499/2019010-01, Inadequate Corrective Actions for Distribution Panel Molded Case Circuit Breaker Testing Failure to Incorporate Design Changes into Emergency Procedures and Design Documents Cornerstone Significance Cross-cutting Aspect Inspection Procedure Mitigating Systems Green NCV 05000498/2019010-02; NCV 05000499/2019010-02 Closed

[H.4] Teamwork 71111.21M The inspectors identified a Green, non-cited violation of 10 CFR Part 50, Appendix B, Criterion III, Design Control, for the licensees failure to incorporate design changes into the plant design bases documentation and associated operating procedures. Specifically, the failure to incorporate these changes had a direct impact on operator actions associated with starting the high-head safety injection (HHSI) pumps in the required time during a SBLOCA in shutdown Modes 3 and 4.

Description:

The inspectors identified a performance deficiency for the licensees failure to update the design basis documentation and associated procedures with design change information. Specifically, the Westinghouse owners group had performed analysis of a SBLOCA while plants were in shutdown Modes 3 and 4. This analysis was incorporated in WCAP-12476, Evaluation of LOCA During Mode 3 and Mode 4 Operation for Westinghouse NSSS, Revision 1, issued in November 2000. The analysis concluded that for a four loop Westinghouse pressurized water reactor, during a SBLOCA accident while the plant is in Modes 3 and 4 that to ensure the 10 CFR 50.46 limits would not be exceeded that operators establish flow from both a high-head and a low head safety injection (LHSI) pump within 10 minutes.

The inspectors reviewed task three of Procedure 0PGP03-ZO-0057, Operator Time Critical Action Program, Revision 3, which required operators to start one LHSI pump within 10 minutes and a subsequent HHSI pump within 30 minutes of the shutdown SBLOCA event.

While reviewing the bases documents for this task, the inspectors identified that there was a difference in the licensees bases document and the WCAP-12476. The inspectors questioned the licensee about this difference in the required times to start at least one HHSI pump within 10 minutes in the WCAP-12476 and within 30 minutes in the licensees bases document. The licensee determined they had failed to incorporate the change from the WCAP-12476 into their bases document. By failing to evaluate the WCAP for applicability when it was issued, the licensee missed an opportunity to incorporate the most up-to-date design information into their design basis documents and procedures.

Subsequently, the licensee had not incorporated this change into their shutdown SBLOCA Procedure 0POP04-RC-0006, Shutdown LOCA. In 2015 when the licensee was developing an operator time critical action (OTCA) procedure they failed to identify that their bases document was not properly updated with the correct times and, therefore, used 30 minutes to start a HHSI pump during a SBLOCA while in Mode 3 and 4. The licensee performed OTCA validation for this task in 2016 and had unacceptable results for some crews. The licensee performed training to improve performance of this task. The licensee again performed more OTCA validation for this task and still had unacceptable results for some crews.

Corrective Action: The licensee revised Procedure 0POP04-RC-0006, Shutdown LOCA, Revision 19, to include an action on their conditional information page to start at least one of each high-head and LHSI pumps when one of the following criteria is met: RCS subcooling less than 35°F, pressurizer level less than 8%, or containment pressure greater than 3 psig.

The licensee again performed OTCA validation for this task and all of the results were acceptable.

The inspectors observed two crews performing a shutdown SBLOCA in the simulator and both crews were able to start at least one high-head and one LHSI pump within the required time of 10 minutes. The licensee entered this issue into their corrective action program as Condition Report 19-4187. This action includes incorporating the WCAP-12476 analysis into their UFSAR for the shutdown SBLOCA and updating the 0POP03-ZO-0057, Operator Time Critical Action Program, changing the time limit to 10 minutes for starting a HHSI during a shutdown SBLOCA.

Corrective Action Reference: Condition Report 19-4187

Performance Assessment:

Performance Deficiency: The failure to evaluate for applicability and incorporate the most up-to-date design bases information into the licensees bases document and operating procedures was a performance deficiency. Specifically, the failure to incorporate the change in design could have resulted in not starting a HHSI pump within the required time limit to prevent exceeding peak cladding temperature of 2200°F.

Screening: The inspectors screened this performance deficiency using IMC 0612, Appendix B, Issue Screening, and determined that this performance deficiency was more than minor because it was associated with the design control attribute of the mitigating systems cornerstone and adversely affect the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences.

Significance: The inspectors determined this finding adversely affected the mitigating systems cornerstone in accordance with IMC 0609, Attachment 4, Initial Characterization of Findings. The inspectors reviewed the finding using the criteria specified in Exhibit 3 of IMC 0609, Significance Determination Process (SDP), Appendix G, Shutdown Operations.

Cross-cutting Aspect: This finding had a cross-cutting aspect in the area of human performance associated with teamwork in that individuals and work groups did not communicate and coordinate their activities within and across organizational boundaries to ensure nuclear safety is maintained. Specifically, the licensees engineering group failed to evaluate for applicability and implement a change to their design bases document based on the WCAP-12476 and the operation group performed a procedure change to their shutdown SBLOCA procedure in 2017, and the engineering review using the licensee-based document did not correct the incorrect time for starting the HHSI pump within 10 minutes [H.4].

Enforcement:

Violation: Title 10 CFR Part 50, Appendix B, Criterion III, Design Control, states, in part, Measures shall be established for selection and review for suitability of application of materials, parts, equipment, and processes that are essential to the safety-related functions of the structures, systems, and components.

Contrary to the above, from November of 2000 to April 11, 2019, the licensee failed to establish measures for selection and review for suitability of application of materials, parts, equipment, and processes that are essential to the safety-related functions of the structures, systems, and components. Specifically, in November 2000 Westinghouse issued WCAP-12476, Evaluation of LOCA During Mode 3 and Mode 4 Operation for Westinghouse NSSS, Revision 1. This analysis recommended that Westinghouse plants start HHSI pumps much sooner than what the licensee assumed in their analysis of record during certain accident conditions. However, the licensee failed to evaluate the guidance for suitability to their site and missed an opportunity to incorporate the most up-to-date design information into their design basis documents and procedures. The failure to incorporate this analysis in design could have resulted in not starting a HHSI pump within the required time limit to prevent exceeding peak cladding temperature 2200°F.

Enforcement Action: This violation is being treated as a non-cited violation, consistent with Section 2.3.2 of the NRC Enforcement Policy.

NCV 05000498/2019010-02; 05000499/2019010-02, Failure to Incorporate Design Changes into Emergency Procedures and Design Documents.

EXIT MEETINGS AND DEBRIEFS

On April 11, 2019, the inspectors presented the Design Bases Assurance (Teams) inspection results to Mr. G. Powell, Chief Executive Officer, and other members of the licensee staff. The inspectors confirmed that proprietary information was controlled to protect from public disclosure.

DOCUMENTS REVIEWED

71111.21MDesign Bases Assurance Inspection (Teams)

Calculations

Number

Title

Revision

or Date

MC-5174

DG Building HVAC System Pressure Drop

MC-5285

DG Building Emergency Cooling Load

CC-6120

Anchor Bolt Design

EC-5002

Motor Load Report

MC-5037A

Evaluation of RWST Vortex Breaker

MC-5037

RWST Volumes & Limits

ZC-7024

Loop Uncertainty Calculation for RWST Level

Monitoring Instrumentation

STI-512246

RWST Design Report (Seismic)

E

2N129MC5815

RWST Vacuum Potential

V-EC-908

Motor Operated Valve GNL 89-10

01/22/1991

V-EC-909

Motor Operated Valve GNL 89-10

01/22/1991

V-EC-910

Motor Operated Valve GNL 89-10

01/22/1991

MC-6472

DVAC Calculation AC Motor MOVs

MC-6460

Minimum Thrust for GL 89-10 Gate MOVs

MC-6426

IVC/AFW Cooling Load and Room Heat-up

5V140MC5876

MSIVC Heating Load

5N049EB01118

Station Blackout

5N049EB01118

Station Blackout (SUPP# 0)

13-DJ-006

25 VDC BATTERY 4-HOUR COPING ANALYSIS

13-DJ-006

25 VDC BATTERY 4-HOUR COPING ANALYSIS

(SUPP# 0)

NC-6034

Steam Generator Tube Rupture for UFSAR

Chapter 15.6.3

NC-7069

Steam Generator Tube Rupture Mass Releases

WCAP-12476

Evaluation of LOCA During Mode 3 and Mode 4

Operation for Westinghouse NSSS

WCAP-12476

Evaluation of LOCA During Mode 3 and Mode 4

Operation for Westinghouse NSSS (SUPP# 0)

ZC-7020

3.0 Functional Description

EC5052

Degraded and Undervoltage Protection and

20/208 VAC Panelboard Voltage Analysis

EC 5000

Voltage Regulation Study

EC5031

Protection 480V Load Centers

EC05033

Protection Non 1E 48 VDC, 125 VDC & 250 VDC, and

Class 1E 125 VDC Systems

Calculations

Number

Title

Revision

or Date

EC05018

Short Circuit Analysis Class 1E 125 VDC and Non-Class

1E 250, 125 and 48 VDC System

Drawings

Number

Title

Revision

5V139Z41621#1

Diesel Generator Building HVAC Emergency Vent Fans

Logic Diagram System: HG

JC1-1HG01-001

Johnson Controls-DG Building HVAC train A-Flow

Balance

5V139V00015#1

P&ID, HVAC Diesel Generator Building Normal and

Emergency System

5N129F05013#1

P&ID, Safety Injection System

77-0110015-1

RWST Vessel Drawing (Brown-Minneapolis Tank)

77-0110015-2

RWST Orientation Drawing (Brown-Minneapolis Tank)

5S109F00016#1

Piping and Instrumentation Drawing Main Steam

20-0100059WN Motor Operated Gate Valve MOD 06002GM87FHB2DO

D

13-DJ-006

25 VDC Battery 4-Hour Coping Analysis

13-DJ-006

25 VDC Battery 4-Hour Coping Analysis (SUPP# 0)

088004-WD12-

2

Wiring Diagram for MCC E2B2 CUB R3

088004-BM12-072 Bill of Materials for MCC E2B2 CUB R3

088004-WD11-

003

Wiring Diagram for MCC E1B2 CUB R3

088004-BM11-003 Bill of Materials for MCC E1B2 CUB R3

088004-WD10-

2

Wiring Diagram for MCC E2C2 CUB 01

08804-BM10-012

Bill of Materials for MCC E2C2 CUB D1

088004-WD9-032

Wiring Diagram for MCC E1A2 CUB L3

088004-WD9-032

Wiring Diagram for MCC E2A2 CUB L3

088004-BMB-032

Bill of Materials for MCC E2A2 CUB L3

08804-WD8-032

Wiring Diagram for MCC E2A2 CUB L3

088004-BM5-012

Bill of Materials for MCC E1C2 CUB D1

088004-WD5-012

Wiring Diagram for MCC E1C2 CUB D1

Drawings

Number

Title

Revision

00000E0AAAA

Single Line Diagram Main One Line Diagram

Unit No. 1 & 2

00009E0DG01#2

Elementary Diagram Standby Diesel Generator DG22

4.16KV Feeder Breaker

00009E0VFAB#1

Single Line Diagram Class 1E 120/208V Distribution

Panel DPA235, DPB235, DPC235

00009E0VFAB#2

Single Line Diagram Class 1E 120/208V Distribution

Panel DPA235, DPB235, DPC235

00009E0PK04

Elementary Diagram ESF Transformer & 4.16KV Bus

E2A, E2B, & E2C Protection and Metering

0363-0100

System Internal Diagram ESF Load Sequencer

N/A

9-E-PKAA-01#1

Single Line Diagram 4.16KV Class 1E Switchgear E1A

(EAB)

9E0PMAK#1,

Sht. 1

Single Line Diagram 480V Class 1E Motor Control

Center E1A4 (EAB)

9E0HC01#1,

Sht. 1

Elementary Diagram IVC AFW Pump Cubicle HVAC

Supply Fans FN001, FN002, & FN003

5V149V25008

Piping & Instrumentation Diagram - HVAC Main Steam

Ventilation System

9E0AF01, Sht. 1

Elementary Diagram Auxiliary Feedwater Pumps

No. 11, 12, & 13

9E0AAAB#1,

Sht. 1

Single Line Diagram Class 1E 125V DC & 120V Vital AC

Non-Class 1E 48V, V, 250V, DC & 120V Vital AC Non-

Class 1E Inverter Power for Computer 208V/120V AC

Regulated Power

G5-253-202

Control Schematic (Generator) (Protective Relaying and

Metering)

HC0

Procedures

Number

Title

Revision

or Date

OPSP03-SP-

0008C

SSPS Train C Quarterly Slave Relay Test

Completed

03/16/2019

0P0P02-HG-0001 Diesel Generator Building HVAC

0PSP05-SI-0931L RWST Level Loop Calibration

Completed

2/11/2019

0PGP03-ZE-0133 Boric Acid Corrosion Control Program

0PSP03-MS-0001 Main Steam System Valve Operability Test

Procedures

Number

Title

Revision

or Date

0PMP04-SG-0007 Steam Generator PORV Hydraulic Actuator

Maintenance

0PGP03-ZO-0057 Operator Time Critical Action Program

0POP04-RC-0006 Shutdown LOCA

0POP04-RC-0006 Shutdown LOCA

0POP04-RC-0006 Shutdown LOCA

0POP04-RC-0006 Shutdown LOCA

0POP04-ZO-0001 Control Room Evacuation

0POP05-EO-

EC00

Loss of all AC Power

0POP05-EO-

EC11

Loss of Emergency Coolant Recirculation

0POP05-EO-

EO00

Reactor Trip or Safety Injection

0POP05-EO-

EO10

Loss of Reactor or Secondary Coolant

0POP05-EO-

EO30

Steam Generator Tube Rupture

0POP05-EO-

ES12

Post LOCA Cooldown and Depressurization

0POP05-EO-

ES13

Transfer to Cold Leg Recirculation

0POP09-AN-

01M2

Annunciator Lampbox 1M02 Response Instructions

C-1 RWST LEVEL HI/LO

D-1 RWST LO-LO/EMPTY

0POP12-ZO-

FSG07

Loss of Vital Instruments or Control Power

0PMP04-SG-0007 Steam Generator PORV Hydraulic Actuator

Maintenance

0POP05-EO-

ES12

Post LOCA Cooldown and Depressurization

0POP10-ZO-

EDMG

Extensive Damage Mitigation Guideline

0POP09-AN-

06M3

Annunciator Lampbox 6M03 Response Instructions

SG PORV Not Close

0POP04-MS-0001 Excessive Steam Demand

Procedures

Number

Title

Revision

or Date

0POP03-ZO-0057 OTCA Validation Record Task #3, Manually Initiate

LHSI and HHSI Pumps (7 Time Validations)

11/29/2016, to

03/09/2017

0PSP03-ZQ-0028 Operator Logs

151

0PAP01-ZA-0102

Plant Procedures (Form 1, Rev 0 - Screening for

0POP04-RC-0006, Shutdown LOCA, Rev 19)

0POP04-AE-0005 Offsite Power System Degraded Voltage

0PGP04-ZA-0307 Preparation of Calculations

0POP03-ZG-0002 STP Coordinator Operations

0PGP03-ZO-0045 CenterPoint Energy Real Time Operations Emergency

Operations Plan

0PGP03-XS-0001 Switchyard Management

0PGP04-ZA-0108 Vendor Technical Information Revision Cover Sheet

0PMP05-PK-1001 4160 Volt Class 1E Switchgear Maintenance

0PGP05-ZE-0001 PRA Analyses/Assessment

0POP-AN-22M1

Annunciator Lampbox 22M01 Response Instructions

0PMP05-NA-0004 Molded Case Breaker Test

0POP09-AN-

03M3

Annunciator Lampbox 3M03 Response Instructions

0PSP03-DG-0007 Standby Diesel 11(21) LOOP Test

0PSP03-DG-0013 Standby Diesel 11(21) LOOP - ESF Actuation Test

0PSP02-SF-

0001A

Unit 1 ESF Diesel Sequencer Timing Test Train A

Performed

04/20/2011

0PSP02-SF-

0001A

Unit 1 ESF Diesel Sequencer Timing Test Train A

Performed

10/22/2015

0PSP02-SF-

0001B

Unit 1 ESF Diesel Sequencer Timing Test Train B

Performed

11/18/2012

0PSP02-SF-

0001C

Unit 1 ESF Diesel Sequencer Timing Test Train C

Performed

03/20/2014

0PSP02-SF-

0001C

Unit 1 ESF Diesel Sequencer Timing Test Train C

Performed

10/10/2018

0PSP02-SF-

0001A

Unit 2 ESF Diesel Sequencer Timing Test Train A

Performed

2/09/2013

0PSP02-SF-

0001A

Unit 2 ESF Diesel Sequencer Timing Test Train A

Performed

07/06/2016

Procedures

Number

Title

Revision

or Date

0PSP02-SF-

0001B

Unit 2 ESF Diesel Sequencer Timing Test Train B

Performed

11/17/2011

0PSP02-SF-

0001B

Unit 2 ESF Diesel Sequencer Timing Test Train B

Performed

10/26/2016

0PSP02-SF-

0001C

Unit 2 ESF Diesel Sequencer Timing Test Train C

Performed

04/18/2010

0PSP02-SF-

0001C

Unit 2 ESF Diesel Sequencer Timing Test Train C

Performed

04/21/2015

Vendor Manuals

and Documents

Number

Title

Revision

or Date

VTD-J127-0002

Vendor Manual, Joy Axial Fans, Adjustable Pitch

S-222

Vendor Seismic Report, Joy Axial Fans

07/20/1979

VTD-P095-0046

Installation, Operation & Maintenance Manual for (8)

Linear Valve Modulating Operator Assembly

VTD-R369-0014

Model 1153 Series D Alphaline Pressure Transmitters

for Nuclear Service

VTD-R369-0041

Rosemount Model 1154 Series H Alphaline Nuclear

Pressure Transmitter

VTD-A348-0014

Vendor Technical Document for Agastat Nuclear

Qualified Control Relays - Series EGP/EML/ETR

VTD-E945-0001

Seismic Qualification of Signal Isolator DEVAR P/N

18-119-M31 ESI-SR-06-158

VTD-P319-0003

Instruction Manual Three Phase Thyrister Controlled

from Power Conversion Products Model

No. 3SD-130-300

VTD-S345-0008

Square D Company 8501XDO80V62 Control Relay Data

Sheet

VTD-S637-0009

ESF Load Sequencer for South Texas Project Electric

Generating Station

JCI-IHZ11-001

Johnson Controls, Inc. MSIVC Building Emergency

Supply Air All Elevations

Engineering

Changes

Number

Title

Revision

or Date

DCP No.13-

15128-5

RHR Low Flow Trip Energize to Actuate Modification

Supplement 0

04-7140-45

Replace ESF E2B Agastat Relays and add Load Cell

Switch Contract

09/16/2014

09-809-27

Replace Obsolete RCS Wide Range Pressure

Transmitters

09/27/2010

DCP 05-11049-1

Install Test Connections at Standby Diesel Generator

Control Panels to Facilitate Surveillance Testing

Supplement 0

Other

Number

Title

Revision

or Date

EOPT-03.10

STPEGS EOP Technical Guidelines

4Q019MS1044

Seismic Floor Response Spectra (Bechtel Document)

3R289NS0012

Specification Essential Cooling Water Pumps

5E329ES1002

Specification for Valve Electric Motor Actuators

NLO 300.61

NLO-300 - Outside Design Bases Procedures

POR 182.07

Loss of all AC Power EC00/Station Blackout

POR 182.06

0POP10-ZO-EDMG, Extensive Damage Mitigation

Guideline

LOR175.06

Requiring Reading Completion Information Attendance

Record

11/14/2017, to

01/08/2018

POR182

POP-10-EDMG/Respond to Station Blackout, 2018-1

Training Attendance Records

05/08/2018, to

06/05/2018

LOR161.02

Emergency Core Cooling System (ECCS) Review

LOT201.10

Emergency Core Cooling Systems

NOC-AE-

07002109

Response to Request for Additional Information

Regarding Resolution of NRC Generic Letter 2006-02:

Grid Reliability and the Impact on Plant Risk and the

Operability of Offsite Power, (TAC Nos. MD1035 and

MD1036)

01/30/2007

NOC-AE-

06001979

60-Day Response to NRC Generic Letter 2006-02, Grid

Reliability and the Impact on Plant Risk and the

Operability of Offsite Power

03/30/2006

INT02-249A

South Texas Project Interconnection Agreement

08/15/2002

Amended and Restated South Texas Project Nuclear

Plant Interface Coordination Agreement

08/01/2018

Other

Number

Title

Revision

or Date

Owners Communication Plan (Rev. 1)

2/16/2014

NOC-AE-

10002532

Reactor Coolant System Pressure Transmitter

Replacement

05/18/2010

South Texas Project (STP) Steady-State Voltage, Short-

Circuit, and Stability Studies

2/05/2018

PRA-17-010

Evaluation pf Switchyard Maintenance Update to

Include the 2015 Annual STP Stability Assessments and

the CenterPoint Energy data 06/01/15 through

06/30/2017

PRA-17-009

Risk Management Actions for North and South Bus

Maintenance

20-00004DJA

Induction Motor Data Sheet 3V141VFN001,

3V141VFN002, & 3V141VFN003

06/12/1984

20-00030AJA

Joy Report No. X-1076, Performance and Sound Test

on Joy Series 1000 Axivane Fan

07/18/1984

Condition Reports (CRs)

96-11944

00-12147

03-14686

04-5149

04-5585

06-1696

16-2166

16-6008

18-7604-1

09-12490

08-9595

08-9382

08-12982

17-15954

17-16576

17-24605

18-12630

01-17582

07-16631

09-7179

2-6770

13-6461

13-11008

04-7140

06-15147

09-5680

09-809

13-15806

13-556

13-6869

13-6991

13-8784

14-13030

15-10558

15-16042

15-16559

15-24053

15-5477

15-5857

16-1127

16-1137

16-1201

16-1281

16-1293

16-1308

16-1381

16-1694

16-1794

16-1985

16-2117

16-2197

16-2214

16-2220

16-3944

16-6008

17-12447

17-21537

17-22052

17-22335

18-14470

18-14621

18-7604

Condition Reports (CRs) Generated during the Inspection

19-3431

19-3603

19-3604

19-4170

19-4187

19-4201

19-3497

19-3512

19-3569

19-3605

19-3607

19-3614

19-3422

19-4182

19-4201

Work Orders (WOs)

96014189

566224

26825

543585

359558

360514

9700667

8612181

419379

109650

209980

99000649

1300171

405613

370940

396888

468808

ML19144A069

SUNSI Review: ADAMS:

Non-Publicly Available Non-Sensitive Keyword: NRC-002

By: WCS Yes No

Publicly Available

Sensitive

OFFICE

RI:EB1

RI:EB2

NSE:RCB

SRI:EB1

C:PBB

C:EB1

NAME

WCullum

SMakor

RSmith

WSifre

NTaylor

VGaddy

SIGNATURE

/RA/

/RA/

/RA/

/RA/

/RA/

/RA/

DATE

05/16/2019

05/17/2019

05/15/2019

05/15/2019

05/23/2019

5/23/2019