April 15, 2021 Mr. G. T. Powell President and Chief Executive Officer STP Nuclear Operating Company P.O. Box 289 Wadsworth, TX 77483
SUBJECT:
SOUTH TEXAS PROJECT, UNIT 1 - REVIEW OF THE SPRING 2020 STEAM GENERATOR TUBE INSPECTION REPORT (EPID L-2020-LRO-0062)
Dear Mr. Powell:
By letter dated October 7, 2020 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML20281A854), as supplemented by letter dated March 8, 2021 (ADAMS Accession No. ML21067A772), STP Nuclear Operating Company (STPNOC, the licensee), submitted information summarizing the results of the spring 2020 steam generator inspections at South Texas Project, Unit 1. These inspections were performed during the 22nd refueling outage.
The U.S. Nuclear Regulatory Commission (NRC) staff has completed its review of the STPNOC submittals and concludes that the licensee provided the information required by the South Texas Project, Unit 1 technical specifications. The NRC staff did not identify additional issues that warrant followup actions. The NRC staffs review summary is enclosed.
If you have any questions, please contact me at 301-415-6256 or Dennis.Galvin@nrc.gov.
Sincerely,
/RA/
Dennis J. Galvin, Project Manager Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-498
Enclosure:
Review of Steam Generator Tube Inspection Report cc: Listserv
Enclosure REVIEW OF THE SPRING 2020 STEAM GENERATOR TUBE INSPECTION REPORT STP NUCLEAR OPERATING COMPANY SOUTH TEXAS PROJECT, UNIT 1 DOCKET NO. 50-498 By letter dated October 7, 2020 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML20281A854), as supplemented by letter dated March 8, 2021 (ADAMS Accession No. ML21067A772), STP Nuclear Operating Company (the licensee),
submitted information summarizing the results of the spring 2020 steam generator (SG) inspections at South Texas Project, Unit 1. The inspections were performed during refueling outage 22 (1RE22).
South Texas Project, Unit 1 is a four-loop pressurized-water reactor with Westinghouse Model Delta 94 SGs. Each recirculating SG contains 7,585 thermally treated Alloy 690 tubes with a nominal outside diameter of 0.688 inches and a nominal wall thickness of 0.040 inches. The tubes are supported by a number of stainless steel tube support plates and anti-vibration bars.
The tubes were hydraulically expanded at both ends for the full depth of the tubesheet. In addition, the U-bend region of the low row tubes was stress relieved prior to operation.
The licensee provided the scope, extent, methods, and results of the SG tube inspections in the letters referenced above. In addition, the licensee described corrective actions (e.g., tube plugging), if any were taken in response to the inspection findings.
Based on the review of the information provided, the U.S. Nuclear Regulatory Commission (NRC) staff has the following observations:
The licensee clarified that no tubes were plugged during 1RE22.
No crack like indications, no new volumetric indications under the hard sludge region, no new tube support plate wear indications, and no new foreign object wear indications were identified during 1RE22.
The licensee discontinued the use of the Dent (DNT) indication code and prior cycle DNT indications are associated with the Ding (DNG) indication code (also referred to in the submittal as a three-letter code).
Based on a review of the information provided, the NRC staff concludes that the licensee provided the information required by its technical specifications. In addition, the NRC staff concludes that there are no technical issues that warrant additional followup action at this time, since the inspections appear to be consistent with the objective of detecting potential tube degradation and the inspection results appear to be consistent with industry operating experience at similarly designed and operated units.