UNITED STATES NUCLEAR REGULATORY COMMISSION
REGION II
101 MARIETTA ST., N.W., SUITE 3100 ATLANTA, GEORGIA 30303 MAY - 11980-Report Nos. 50-280/80-08 and 50-281/80-09 Licensee:
Virginia Electric and Power Company Richmond, VA 23261 Facility Name:
Surry Docket Nos. 50-280 and 50-281 License Nos. DPR-32 and DPR-27 Inspection at Surry site near Williamsburg, VA
-*-*1nspect~r=--~~~~--- *--P==-
W. H. Miller, Jr.*
.Approved by: ~
~
~~~
T. E. Conlon, Section Chief, RC&ES Branch SUMMARY Inspection on April 15-18, 1980 Areas Inspected
//-;5o-g'o Date Signed fL-3o-go Date Signed This special, unannounced inspection involved 30 inspector-hours on-site in the areas of fire protection/preventio Results Of the areas inspected, no items of deviations were identifie However, two items of noncompliance were found (Infraction-Nonfunctional fire door between Unit 2 emergency switchgear room and Unit 2 service building cable vault-Para-graph.3.d; and, Infraction-Failure to implement fire protection procedures for special processes involving ignition sources-Paragraph 6.a).
8006230 l~~
..
-...*
DETAILS Persons Contacted Licensee Employees
- J. L. Wilson, Station Manager
- R. F. Saunders, Superintendent Maintenance
- T. A. Peebles, Superintendent Technical Services
- M. R. Kansler, Supervisor, Engineering Services
- J. C. Moody, Fire Marshall
- M. S. O'Connell, SGRP Safety Coordinator
- R. G. Smith III, Staff Engineer (Corp.)
- D. A. Christian, Engineer Supervisor
- F. L. Rentz, Resident QC Engineer
- W.R. Runner, Jr., Supervisor Admin. Services
- R. K. MacManus, Assoc. Engineer (Corp.)
- E. P. DeWandel, Staff Assistant
- W. Davidson, Engineer H.J. VanDyke, Supervisor Security B. Anderson, QA/QC Records M. Kight, Welding Supervisor NRC Resident Inspector
- D. J. Burke
- Attended exit intervie.
Exit Interview The inspection scope and findings were summarized on April 18, 1980 with those persons indicated in Paragraph 1 abov.
Licensee Action on Previous Inspection Findings (Closed) Deviation Item (281/79-08-01), Failure to impl~ment the fire protection commitments of document entitled "Steam Generator Repair Program for Surry Units 1 and 2".
As previously reported in IE Report Nos. 50-280/79-61 and 50-281/79-80 corrective action was taken on the following two examples of this deviation:
(1) Temporary fire protection equipment for the Unit' __ 2 containment
~-1
'
~
~
are (2) Organization and training of construction site.fi£'e brigad *
--* During this inspection a tour was made of the Unit 2 containment and the installation of the standpipe system was found complet There-fore, the deviation is close (Closed) Inspector Followup Item (281/79-08-03), Sprinkler system installation discrepancies-Construction warehouse numbers 7 and The previously identified sprinkler system discrepancies have been corrected; therefore, this item is close (Closed) Inspector Followup Item (280/79-29-03 and 281/79-46-04),
Supervision of fire protection control valve All valves in the fire protection system are either electrically supervised or are locked in their normal position and a visual inspection of the position of the valves is made weekl This item is close (Closed) Noncompliance (Infraction) Item (280/79-61-01 and 281/79-80-01),
Inoperative fire door between Unit Nos. 1 and 2 emergency switchgear room The transformer blocking the fire doors has been removed; a memorandum has been sent to all plant superintendents and contractors to not block fire doors; and, areas adjacent to fire doors are checked periodically to ensure that doors are not obstructe This item is close However, during the plant tour on April 17, 1980, the fire door separating the Unit 2 emergency switchgear room from the Unit 2 cable vaule of the service building was found blocked in the open position by an electrical cable which was located in the doorwa A limiting condition of operation (LCO) consisting of a continuous fire watch had not been established on at least one side of the door as required by Technical Specification Section 3.2 This item is identified as Noncompliance (Infraction) Item 281/80-09-01), Nonfunc-tional fire door between Unit 2 emergency switchgear room and Unit 2 service building cable vaul (Open) Deviation Item (280/79-61-02 and 281/79-80-02), Substandard fire door This deviation identified several fire doors located throughout the plant which were not provided with positive type latching devices as required by National Fire Protection Association Standard No. 80 (NFPA-80), fire doors and window The correct type latching devices had been provided on the previously identified door However, during this inspection a number of additional doors were found which were not provided with the correct type latching hardware or the latching devices were inoperativ The licensee has committed to conduct an inspection of all fire doors installed at the plant and to repair or replace the latching devices as required to bring the doors up to the standards of NFPA-8 Therefore, this ite~ ~emains open.
.
- . -.
- -* (Closed) Deviation Item (280/79-61-03 and 281/79-80-02)~ Substandard carbon dioxide system for diesel tank room in the service water intake structur A design change has been submtted to modify the existing design to insure that the reserve supply of carbon dioxide for the system can be activated by the re~ote manual actuation device if the
- --'".-~i_.""*T*.-"7*"*--*~-.:--:-.. ~----"'="':*""C"-*"'<"""~7";"'.'",--;*s*-:,:="1:"":,;*<'<-:.~*,~-.....-*."!-~~-~\\~
\\..... TO
- -- * *
-
- .,.~: ~ <°;,
- ****
a
c
',*
., *"
,
.,_
,-. ?-
.
-** *
i
~'-,. '
main supply system is rendered inoperative. Until this design change can be accomplished the system will be normally supplied by.the main bank of cylinder However, if the main bank of cylinders are removed
- for recharge or repair, the reserve cylinders will be relo.cated and connected to the main cylinder discharge assembly to permit operation by the remote activato This item is close (Closed) Unresolved Item (280/79-61-04 and 281/79-80-04), Missing periodic test data on fire protection system The missing test data for PT-24.4B fire protection systems (electrical) was reviewed by the station Nuclear Safety and Operating Committee (NSOC).
The test data was listed on the electrical coordinators check sheet and the NSOC felt that these inspections were apparently accomplishe Therefore,
- no further action is necessar The missing test data for PT-24.4!
Fire Protection Systems (Warehouses) was not located and was apparently not reviewed by the NSOC since this inspection and test is not required by the Technical Specification. During this inspection a tour was made of the warehouses.and several inspection sign-off tags for various fire protection devices were reviewed. It appears that these items were inspected each month during 1979 and thus far in 1980 as required by PT-24.4 The licensee advised that appropriate action was to be
. taken to assure that future inspections of the fire protection systems and equipment would be properly documente Therefore, this item is close.
Unresolved Items Unresolved items were not identified during this inspectio.
Fire Protection/Prevention Modifications This. inspection evaluated the licensee's progress and corrective action on the fire protection modification and improvement commitments made to the NR The NRC Fire Protection Safety Evaluation Report (FPSER) for this facility dated September 19, 1979 (Amendment 54 to Operating License N DPR-32 and Amendment 53 to Operating License No. DPR-37) and the licensee's document entitled Fire Protection Systems Review (FPSR) for Surry Power Station dated July 1; 1977 were used.in this evaluatio These documents describe the fire protection modifications and target dates for implemen-tation of the modification The modifications and findings of this inspection are as follows:
-:;;
".:.. * a. *Number Location/Item
- Control Room Complex (1)
- Fire detectors/ adj a cent areas FPSER Commitment Paragraph.1.9(1)
- status 5/81
-4-
FPSER Commitment (Contd.) Number Location/Item Paragra:eh
- Status (2)
Fire hose/at existing hose 3.1.9(1)
7/80 station (3)
Fire hose nozzles 3.1.17(2)
Closed (4)
Fire doors/between 3.1.11(2)
-k"i',Open turbin building (5)
Fire extinguishers/CO2 3.1.13(1) and (2)
Closed and Water
(6)
Fire barrier/verification 3.1.24 8/80 (7)
Breathing apparatus/wall 3.1.3(6)
Closed mounted (8)
Trash receptacles with 3.1.6(1)
Closed cover (9)
Removal of Combustibles 3.1.6(3)
- Closed (10)
Smoke detectors/ceiling 3.1.9(2)
5/81 area (11)
Ventilation ducts and 3.1.12(5) and (6)
6/80 (12)
Smoke dampers
. 6/80 (13)
Security door.between 3.1.11(13)
6/80 control room and arinex/
cover louver
. (14)
Electrical circuit 3.1.5(1)
Unit 1 10/80 isolations Unit 2 5/81 (15)
Fixed battery lighting 3.1.8(2)
5/80 Unit
'~;'.'I; Emergency Switchgear and Relay Rooms 5.2.
. {16)
Charging.pumps.C+OSS 3.1.25 (1)
.11-S/81
~*;..... -
.
(1 !, ~
connected
.~-
. (17).
Alternate shutdown panel
. 3.1.23(1)
- ~
Unit 1 10/80
,-
Unit 2 5/81
. r
.
.
- ,
.
.
.
.
'
.
-~~~-,. ':*'
- . *.*
,~7 *:*
- ~**~*;
..
- .*** *. ~-:- ~
... _"/' :* ~----r..*. _,;.**? *:*
.
-.--.
.... --:--:7_=_**---~=~~~---....
.
~
....... _.. _____ - *---* --
---~
-5-FPSER Commitment (Contd.) Number Location/Item Paragra:eh
- Status (18)
Smoke detectors 3.1. 9 (7)
5/81 (19)
Ventilation ducts/fire 3.1.12(1)
6/80 dampers (20)
Fire doors-Replace existing 3.1.11(4)
6/80 doors (21)
Dry standpipe system 3.1.18(5)
7/80 (22)
Fire extinguisher 3.1.13(3)
Closed
. ---*-*--------*--- ~-----------------
(23)
Cable tray covers 3.1.4(1)
6/80 (24)
Cable tray fire stops 3.1.10(1)
9/80 (25)
Fire door between rooms 3.1.11(14)
6/80 (26)
Fixed battery lighting 3.1.8(2)
Closed units Outside Containment Penetration Vaults, Cable Tunnels, and Service Building Cable Vaults (27)
Charging systems-cross 3.1.25(1)
5/81 connected (28)
Monitor panel 3.1.23(1)
Unit 1 10/81 Unit 2 4/81 (29)
Sprinkler system (manual 3.1.26(3)
10/80 type)
(29A)
Vault/open head 3.1.26(3)
10/80
- .~;
(29B)
Tunnel/closed head 3.1.26(3)
10/80 over aisle (30)
Carbon dioxide system/add 3.1.16(3)
- _, '
~
10/80
. f.) ~- t nozzles
~~* ' ~
"
'ti
.-...
(31)
Fire barrier/verification 3.1. 24(a)
~
8/80 I
of adequacy
-6-
FPSER Commitment (Contd.) Number Location/Item Paragra:eh
- Status (32)
Fire extinguisher/Class C 3.1.13(1)
Closed (33)
Fire ladder 3.1.14(1)
- Closed (34)
Fixed battery lighting 3.1.8(2)
5/80 Units Battery Rooms (35)
Smoke detectors-exhaust 3.1.9(3)
5/81 ducts (36)
Air flow defectors
... ~----------. -.--.3~.L+/-Cl)
Open (37)
Fire doors (3 Hr)/Room 2B 3.1.11(5)
- Closed (38)
Fire barriers/verification 3.1.24(d)(a)
8/80 of adequacy
Cable *Tray Rooms (39)
Storage of combustibles 3.1.6(2)
Closed and Signs (40)
Enforce "No Smoking" 3.1.1(1)
Closed (41)
Fire hose station 3.1.18 (3)
7/80 (42)
Fire barrier pene-3.1.24(3)
8/80 trations/sealed (43)
Fire door into turbine 3.1.11(7)
Closed building (44)
Fire dampers 3.1.12(2)
6/80 (45)
Fire extinguisher 3. l.13(i)
Closed (46)
Cable tray covers 3. /80.
'*
(47)
Fire hose nozzles 3.1.17(1)
t; -~- -~
Closed u ' ~
'# '
Switchgear Rooms ~
-
(48)
Fire extinguisher 3.1.13(1)
Closed
- .
. -.. -
-7-FPSER Commitment (Contd.) Number Location/Item ParagraEh
- Status (49)
Fire hose verification 3.1.18(8)
- 7/80 (SO)
Fire hose nozzles 3.1.17(1)
Closed Motor Control* Center Rooms (51)
Storage of 3.1.6(3)
Closed combustibles Auxiliary Building - EL 2 Feet (52)
Smoke detectors-exhaust 3.1.9(4)
5/81 ducts (53)
Charging system-cross 3.1.25(1)
5/81
. connection (54)
Trash containers with 3, 1.6(1)
Closed covers (55)
Cable tray covers 3.1. 4(1)
10/80 (56)
Fire extinguishers 3.1.13 (1)
Closed (57)
Water shields/CCW pumps 3.1.29 7/80 Auxiliary Building - EL 13 Feet (58)
Smoke detectors - exhaust 3.1.9(4)
5/81 ducts (59)
Ventilation system/charging 3.1.27 10/80 pump area (60)
Smoke detectors/ charging..
3.1. 9 (12)
5/81
.pump exhaust
- ~
(61)
Charging pumps - cross 3.1.25(1)
5/81 connection
- ,
- (62)
Cable tray. covers **
3.1.4(1)
rr ****..-. 10/80
~}
'*
.
.. (~3)
Fire doors/cable vaults *.
3.1.11(8)
. -~
- 6/80
- ~
(64)
Hydrogen lines/identified 3.1.19
--
7/80
.,.
(Contd.) Number (65)
(66)
-8-Location/Item Fire barrier/verification of adequacy Fire extinguishers Auxiliary Building - EL 27'-6" (67)
(68)
(69)
(70)
(71)
(72)
(73)
(74)
Smoke detectors - exhaust ducts Smoke detectors/solid waste drumming Heat collectors/charcoal filters Cable tray covers Fire door/HP hallway Storage of combustibles Hydrogen lines/identifi-cation Fire barriers/verifica-tion of adequacy Auxiliary Building - EL 45' -10" (75)
(76)
(77)
(78)
(79)
(80)
Smoke detectors - exhaust ducts Cable tray covers Fire door/fuel building Fire barriers/verifica-tion of adequacy Storage of combustibles Sprinkler system/charcoal filters FPSER Commitment Paragraph 3.1.24(1)(6)
3.1.13(1)
5.10 3.1.9(4)
3.1.9(8)
3.1.7(1)
3..1.11(6)
3.1.6(4)
3.1.19 3.1.24(1) (c)
5.11 3.1.9(4)
3..1.11(9)
5.11..1.6(3)
3.1. 26(1)
1,
'
t;- *.. *
- 1 *. ;'
!(
- .~
-~**-*... '. -- -
- Status 8/80 Closed 5/81 5/81 Open 10/80 6/80 Closed 7/80 8/80 5/81 10/80 6/80 8/80 Closed 10/80
....... '...,...
~
,
-9-
FPSER Commitment (Contd.) Number Location/Item Paragraph
- Status Reactor Building - Unit 1 5.12 (81)
Standpipe system type)
(dry 3.1.18(6)
7/80 (82)
Oil collection system/RC 3.1.15 (4)
3/81 pumps (83)
Smoke detectors 3.1.9(10)
5/81 (83A)
Recircuition ventilation system (83B)
Cable penetration areas (84)
Monitor panel with 3.1.23(1)
10/80 secondary power Reactor Building - Unit 2 5.12 (85)
Standpipe system (dry 3.1.18(6)
Closed type)
(86)
Oil collection system/RC 3.1.15 (4)
3/81 pumps (87)
-Smoke detectors 3.1.9(10)
5/81 (87A)
Recirculation ventilation system (87B)
Cable penetration ar~as (88)
Monitor panel with 3.1.23(1)
4/81 secondary power -
Containment Spray Pump and Auxiliary
)';"
Feedwater Pump Buildings - Units 1 and 2 5.13 It,
.,
(89)
Smoke detectors -
3.1.9(9)
- lf-; ;* -
5/81 Ventilation ducts t.4-
~
(90)
Fire equipment/yard 3.1.18(15)
7/80 hose cabinet
r-..... --~~-**~=;,,~=:-;,'~.....--~"'1-:"";~-*-:-.,.---..,-.-... ~-r* *,-r,--_,..,.~~~----::-,
- -.
,-., ~,--:i-.~~-'.~-.. ~...-:--;:::;;- *.* -** * *""* " *, ** **"
- * r"'"*
-*
- *--
~
..
-10-(Contd.) Number Location/Item Fuel Building (91)
Fire detectors at ceiling Safeguards Equipment Buildings (92)
(93)
(94)
(95)
Smoke detectors/19 1 -6 11 ceiling level Fire barriers between cables Fire extinguishers/outside and inside Fire barriers/verification of adequacy Intake Structure (96)
(97)
(98)
(99)
Fire door (3 Hr)/Oil tank room Fire damper (3 Hr)/Oil tank room Storage of portable heaters Service water pumps/CO2 protection FPSER Commitment Paragraph 5.14 3,19(5)
5.15 3.1.9(6)
3.1.10(2)
3.1.13(1)
3.1.24(1)
5.16 3.1.11(1)
3.1.12(3)
3.1. 6(5)
5.1 Mechanical Equipment Room No. 3.
5.17 (100)
(101)
(102)
(103)
Smoke detectors/venti-lation exhaust Fire door/connecting Unit 2 switchgear Hose stations/turbine building Fire barriers/verification of adequacy 3.1. 9 (11)
- ~~
3.1.11(11)
3.1.18(1)
3.1.24
- Status 5/81 5/81 9/80 Closed 8/80 6/80
.Closed 10/80 5/81 6/80 -
,, u ;<
' /80 8/80
-11-FPSER Commitment (Contd.) Number Location/Item ParagraEh
- Status Turbine Building 5.18 (104)
Fire doors (3 Hr)
(104A)
Diesel generator 3. l.11(12)(a)
6/80 (104B)
Control Room 3.1.11(2)
- Open (104C)
Battery Room 2B 3.1.11(12) (a)
~'.-Closed (104D)
Emergency Switchgear _
_____ 3. l._ ll(12)JaJ_~-~--ClP_s_ed Room (104E)
Lube Oil storage 3.1.11 (12)(b)
6/80 (104F)
Sliding Fire door/replace 3.,1. 11 (12)( c)
Closed link (105)
Dike/lube oil conditioning 3.1.15 (1)
Closed units (106)
Hydrogen piping/
3.1.19 7/80 identification (107)
Fire hose placement 3.1.18(1)
7/80 analysis (108)
Sprinkler head/heat 3.1.26(2)
10/80 shields (109)
Fire damper/lube oil 3. 1. 12. 12 (b)
6/80 storage Diesel Generator Rooms-5.19 (110)
Dikes/day tank, floor 3.1.15("2)
Closed drains and entrance door (111)
Diesel fuel transfer 3.1.1(3)
.1;..
l Closed pumps/administration u;:
t~
~
procedures ff.-,
~
- -
-12-(Contd.) Number Location/Item Fire Pumphouse (112)
(113)
(114)
(115)
Fire door (3 Hr) between pump rooms Curb/fuel oil day tank Dike/floor drains Fire damper (3 Hr) in duct between rooms FPSER Commitment Paragraph 5.23 3.1.11(3)
3.1.15(3)
3.1.15(3)
3.1.12(4)
(116)
Fire detectors
. - :=-3.-1-.-9 (13)
General Plant Areas (117)
(118)
(119)
(120)
(121)
(122)
(123)
(124)
(125)
(126)
- (127)
Interim fire hose installations Fire hose inspection Fire hose house equipment Fire hose houses Fire Protection Valve Supervision Water supply connection/auxiliary building Foam/Hose Cart 3.1.18(2)
3.1.18(4)
3.1.18(9)
3.1.18(10)
3.1.18(11)
3.1.18(12)
3.1.18(13)
3.1.18(14)
3.1.22 3.1.18(16)
3.1.20 lJ f ft ; :
~
~
- Status
- Open. __ _
Closed
"'-'*Op nn en 6/80 5/81 7/80 7/80 7/80 7/80 7/80 7/80 7/80 7/80
- Closed 7/80 Closed
,.
- (Contd.) Number (128)
(128A)
-13-Location/Item Carbon dioxide systems Manual lock out/oil pump rooms FPSER Commitment Paragraph 3. 1.16 3.1.16(1)
(128B)
Monitoring device/pilot 3.1.16(2)
cylinder (129)
Hydrant valve for branch 3.1.21 line from Auxiliary Building Emergency Breathing Equipment (130)
Breathing apparatus and spare cylinders (131)
Air compressor relocated (132)
Cascade system-add cylinders (133)
Air compressor intake (134)
Cylinder water tank Emergency Lighting (136)
Portable lantern for fire brigade Fire Doors - Administrative Procedures (136)
(137)
Semi-annual inspection Electrical supervision or:
Locked closed and inspected weekly; Automatic release and inspected monthly; Self-closing and inspected daily 3.1.3(1)
3.1.3(2)
3.1.3(3)
3.1.3(4)
3.1.3(5)
3. LS(l)
3.1. 11 (l)(a)
3.1.11 (l)(b)
u~~~~
- '
- Status 10/80 10/80 10/80 Closed 6/80 6/80 6/80 6/80 6/80 Closed 6/80 6/80
- -
-14-(Contd.) Number Location/Item FPSER Commitment Paragraph
- Status Compressed Gas Storage Area (138)
(139)
(140)
(141)
(142)
Technical (143)
(144)
NOTES:
Control smoking and hot work Remove vegetation -
fuel oil tank area Replacement of penetration seals (procedure)
Alternates water supply for charging pump service water Fire detection systems emergency power supply Specifications Charging pumps/from other unit Auxiliary feedwater pumps/from other unit 3.1.1(2)
Closed 3.1.6(6)
Closed 3.1.24(2)
8/80 3.1.25(2)
5/81 3.1.28 8/80 3.1.30(1)
5/81 3.1.30(2)
Closed
- Dates indicate the scheduled date of completio Completed items are listed as close Items incompleted are listed as ope **Refer to Paragraph 5. b for comment Findings Additional information on the "Open" items and on the "Closed" items in Paragraph 5.a marked by"**" as listed belo Ths below listed numbers correspond to the numbered items in Paragraph (4)
The fire doors between the turbine building and the control room are security type doors and not fire doors as required by Sec-tion 3. 1.11 (2) of the FPSER and Section III. c (Fir*e Area SA) of the FPS The licensee advised that these doors:, have a three hour fire rating but documentation was not availa~le at the sit This d~ta will be obtained by the licensee and will be reviewed during a subsequent NRC inspectio This item remains ope *.,
.. -.....,.--........ e.**"~... ~
.. ~*~:7;*,......,.**.
- * **""' *,*
- '\\
~
- ,
- * :
"** *:
- '..* *
~
- *--
---
-15-(9)
The combustibles remaining in the control room appear to be required for normal operation of the plan Therefore, this item is close (33)
A short ladder has been provided for the cable tunne This ladder will not reach the top portion of the cable vaul However, since this does not appear feasible in the event of a fire situation and since a water suppression system is to be provided for this are This item is close (37)
The fire door is not provided with a closer but door is normally maintained closed and is provided with a security alarm to indicate when door is left ope This item is close (96) Fire door has been installed but hardware is not properly adjuste his item will be reinspecte (104A)
Refer to item No. (4).
(104C) Refer to item No. (37).
(112)
The fire doors have been installed but the hardware is not properly adjuste This item will be reinspecte (114)
The floor drains are not dike This item will be evaluated during a subsequent NRC inspectio (125) Refer to Paragraph Within the areas examined, no items of noncompliance or deviations were identifie.
Plant Tour A tour was made of the plant to review the completed fire protection modi-fications, to verify that the existing fire protection systems were in service and to review the licensee's compliance to the administrative procedures for the control of fire hazards within the plan The following discrepancies were noted: Cutting and Welding Operations At the two foot elevation of the auxiliary building welding operations were being accomplished without a "Welding and Flame Permit".
VEPCO procedure ADM-56 Special Processes Involving Ignition"Sources prohibits welding or cutting operations in all areas of plant except the welding shop unless a welding or Flame Permit is issue The ~elding foreman for the job in the auxiliary building advised that welding operations were also being conducted at other locations in the plant without an approved permi A review of the permits on file within the control
- >
-16-room appeared to confirm this statement. It appears that this problem existed primarily due to the fact that the existing procedure does not clearly describe the requirements to be followed in the preparation, posting and record retention of the permit However, the procedure clearly states that a welding and flame permit is required and lists the safety provisions which must be followe The performance of welding operations without the issuance of an approved Welding and Flame Permit is a failure to fully implement the facility fire protec-tion program as required by Section 6.4.J of the Technical Specifications and is identified as Noncompliance (Infraction) Item (280/80-08-02),
Failure to implement fire protection program procedures for special processes involving ignition source The licensee was advised that the existing procedure for special processes involving ignition sources should be reviewed and revised as necessary to assure that these operations are safely conducte Fire Doors A number of fire doors were noted in which the latching device was the wrong type or inoperativ Also, one fire door was found blocked in the open position by electrical cable in the doorwa For additional comments on these items, refer to above Paragraphs 3.d and Compressed Gas Cylinders Compressed gas cylinders were noted improperly stored throughout the plan Cylinders were not secured in the upright position to prevent being knocked ove Cylinders were stored without protective valve covers in place, fuel cylinders were stored adjacent to combustible materials in safety-related areas, and contaminated cylinders were stored within radiation areas of the plan The licensee agreed to evaluate the plant's current administrative procedures covering the use a~d storage of compressed gas cylinders and to establish a program to assure that cylinders will be properly stored while in the plant and for cylinders to be promptly removed from safety-related areas upon completion of work in these area This item is identified as Inspector Followup Item (280/80-08-03 and 281/80-09-03), Improper Storage of Compressed Gas Cylinders and will be reevaluated during a subsequent NRC inspectio t*:
~.
i