Docket No. 50-423 Bf7376 Attachment I '

Millstone Nuclear Power Station, Unit No. 3 Proposed Revision to Technical Specifications 1

i 4

8612290223 861218 PDR ADOCK 05000423 P PDR

INSTRUMENTATION 3/4.3.3 MONITORING INSTRUMENTATION RADIATION MONITORING FOR PLANT OPERATIONS LIMITING CONDITION FOR OPERATION 3.3.3.1 The radiation monitoring instrumentation channels for plant operations shown in Table 3.3-6 shall be OPERABLE with their Alarm / Trip Setpoints within the specified limits.

APPLICABILITY: As shown in Table 3.3-6.

ACTION:

a. With a radiation monitoring channel Alarm / Trip Setpoint for plant operations exceeding the value shown in Table 3.3-6, adjust the Setpoint to within the limit within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or declare the channel inoperable.
b. With one or more radiation monitoring channels for plant operations inoperable, take the ACTION shown in Table 3.3-6.
c. ' The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.3.3.1 Each radiation monitoring instrumentation channel for plant operations shall be demonstrated OPERABLE by the performance of the CHANNEL CHECK, CHANNEL CALIBRATION and ANALOG CHANNEL OPERATIONAL TEST for the MODES and at the frequencies shown in Table 4.3-3.

MILLSTONE - UNIT 3 3/4 3-42 l i

2

?

F TABLE 3.3-6

{t

@ RADIATION MONITORING INSTRUMENTATION FOR PLANT OPERATIONS rn i

i C

h CHANNELS MINIMUM ALARM /

u TO TRIP / CHANNELS APPLICABLE TRIP FUNCTIONAL UNIT ALARM OPERABLE MO'.25 SETPOINT ACTION

1. Containment
a. Containment Area Purge 1 2 All <1R/h 26 w and Exhaust Isolation i

l ',d b. RCS Leakage Detection i O

1) Particulate Radioactivity N/A 1 1,2,3,4 N/A 29' i 2) Gaseous Radioactivity N/A 1 1,2,3,4 N/A 29
2. Fuel Storage Pool Areas
a. Criticality-Radiation Level 1 2 *

$ 15 mR/h 28 l

TABLE 3.3-6 (Continued)

TABLE NOTATIONS

  • With fuelin the fuel storage pool areas.

ACTION STATEMENTS ACTION 26 - With less _ than the Minimum Channels OPERABLE requirement, operation may continue provided the containment purge and exhaust valves are maintained closed.

ACTION 27 - Not used.

ACTION 28 - With less than the Minimum Channels OPERABLE requirement, operation may continue for up to 30 days provided an appropriate portable continuous monitor with the same Alarm Setpoint is provided in the fuel storage pool area.

Restore the inoperable monitors to OPERABLE status within 30 days or suspend all operations involving fuel movement in the fuel storage pool areas.

ACTION 29 - With the number of OPERABLE Channels less than the Minimum Channels OPERABLE requirement, comply with the ACTION requirements of Specification 3.4.6.1.

MILLSTONE - UNIT 3 3/4 3-44

=,

E:

F

[ TABLE 4.3-3

-t O RADIATION MONITORING INSTRUMENTATION FOR PLANT m OPERATIONS SURVEILLANCE REQUIREMENTS C

z Q ANALOG MODES FOR w CHANNEL CHANNEL WHICH SUR-CHANNEL CALI- OPERATIONAL VEILLANCE FUNCTIONAL UNIT ALARM BRATION TEST IS REQUIRED

1. Containment
a. Containment Area Purge S R M All R and Exhaust Isolation e-
b. RCS Leakage Detection
1) Particulate Radioactivity S R M 1,2,3,4
2) Gaseous Radioactivity S R M 1,2,3,4
2. Fuel Storage Pool Areas
a. Criticality-Radiation Level S R M
  • TABLE NOTATIONS
  • With fuelin the fuel storage pool area.

1