PS~Ge Public Service Electric and Gas Company 80 Park Place Newark, N.J. 07101 Phone 201/622-7000
Dear Mr. O'Reilly:
LICENSE NO. DPR-70 DOCKET NO. 50-272 June 2, 1977 REPORTABLE OCCURRENCE 77-36/03L Pursuant to the requirements of Salem Generating Station Unit No. 1 Technical Specifications, Section 6.9.1, we are submitting Licensee Event Report for Reportable Occurrence,77-36/03L.
This report is required within thirty (30) days of the occurrence.
Sincerely yours, J.
- Y.' f~L-YY' Frank P. Librizzi General Manager -
Electric Production CC Director, Office of Inspection and Enforcement (30 copies}
Director, Office of Management Information and Program Control
(.3 copies}
The Energy People 95-2001 300M 8-75
Report Number:,
" Report Date:
- Occurrence Date:
Facility
- - e36/03L 5/16/77 5/12/77 Salem Generating Station Public Service Electric & Gas Company Hancocks Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:
DNB Parameter Outside Technical Specification Limits (Pressurizer Pressure)
CONDITIONS PRIOR TO OCCURRENCE:
Mode 1, Reactor Power 90%
DESCRIPTION OF OCCURRENCE:
At 0830 hours0.00961 days <br />0.231 hours <br />0.00137 weeks <br />3.15815e-4 months <br />, pressurizer pressure decreased to 2150 psig.
Technical Specification Action Statement 3.2.5 was implemented by the Shift Super-visor.
At 1230 hours0.0142 days <br />0.342 hours <br />0.00203 weeks <br />4.68015e-4 months <br />, valve 1PS3 (Pressurizer Spray Valve) was isolated.
The pressurizer pressure returned to normal and the action statement was terminated.
DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:
A pneumatic valve operator adjustment problem caused 1PS3 to remain off of its closed seat.
Continuous spray flow through the valve caused the pressurizer pressure to decrease below the 2220 psia allowed by Technical Specification 3.2.5.
ANALYSIS OF OCCURRENCE:
Technical Specification 3.2.5 states that with any DNB parameter ex-ceeding its limit, restore the parameter to within its limit within two (2) hours or reduce thermal power to less than 5% of rated thermal power within the next four (4) hours.
The pressurizer pressure was restored to within its DNB limit within the time allowed by the Techni-cal Specification, therefore, the LCO was not violated.
At no time was there any danger to the health and safety of the general public or site personnel.
CORRECTIVE ACTION
The "zero" position (fully closed) on the pneumatic valve operator was reset.
The valve was restroked with satisfactory results.
The valve leakage terminated. and valve 1PS3 was returned to service.
- - 5/16/77 FAILURE DATA:
Valve 1PS3 Size:
4-inch, Air Operated Type:
Dl00-160-2.5 Manufacturer:
Copes-Vulcan Prepared by T. L. Spencer Manager -
Sal~m Generating Station SORC Meeting No.
54-77
e LICENSEE EVENT REPORT e I
LER 77-36/03L
- 5/16/77 CONTROL BLOC~
LICENSES:
NAME:
6 LICENSE NUM6E!'I LICENSE TYPE EVENT TYPE
@E4N I JI SIG IS I ~1 J5o IO 1-1 o IO Io IO IO 1-1. O I qJ Js 41 11 11 11 l.Jo. ~
REPORT REPORT C:ATEGORY T'l'll'E SOURCE OOCl<C:T NUMBER EVENT OATE REPORT CATE l'Ol1lccN'TlPIOI lLJ
~ 1015101-101217121
\\015\\11217171 101s111617171
~
57
. ;a 5S 00 61 6a 69 74 75 86 operation, pressurizer pressure decreased to below the DNB I
EVENT OESCRIPTlON
@li} I. Dur in*g *Mode 1 7
8 9 II§] limit of LCO 3.2.5.
so Valve 1PS3 was found leaking through and was isolated.
7 8 9
@E] I Valve lPSl was operable throughout this event.
7 8 9 Valve 1PS3 was restroked J
@J§JI and tested satisfactorily.
This is the first occurrence of this type.
7 8 9 ao
~
7 8~9~~~~~~~~~~~~~~~~~P-R-IM-E~~~~~~~~~~~~--,~~~__,~~__,~-80~
(77-36/03L)
SYSTEM
CAUSE
COMPONENT COMPONENT cooe:
cooe:
COMPONENT COOE SUPPLIER MANUFACTURER
@El1CIJI ~ IV!AILJVIOL.J
~
lCJ6j315J VIOLATlON lliJ 7
8 9 10 11 12 17 43 44 47 48 CAUSc DESCRIPTION
~
9 Valve operator adjustment problem caused leakage through spray valve. which J
~I decreased pressurizer nressure.
4-inch. Type Dl00-160-2.5, Copes-Vulcan.
I 7
89
~
[D£l 7
8~9~~~~~~~~~~--,,.-~~~~~~~~~~~~~~~~~~~--,~~~~~~~~90~
FACll..ITY STATUS [ili]
w.
7 a
9 FORM OF
""POWER IO I 91 01 10 l:Z ACTIVITY CONTENT METMOO OF OTMl::R STATUS OISCOVERY OISCOVS:RY OS:SCfllPTION l~_N.!U..,L.._;/A...___--11 LaJ 13 44 45 N/A REL£ASEO CF REL.EASE AMOUNT CF ACTIVITY [ili]
~ lEJ I
N/A 1
a 9
10 11 LOCATION OF REL.EASE I
\\~------N~/A
_________ -=1!
44 45 80 PSASONNEL EXPOSURES NUMBE.R TYPE OESC.RIPTION [ili]tO 1010 l ~
NA 1
a s 11 12
~lJ,-~~~-=-:..L-;:..::....~~~~~~~~~~~~~~~~~~~~~~~~--.30
~
PERSONNEL INJURIES NUMBER OESC.RIPTION GEJlO!O!OI 1
a 9 11 N A 12 OFFSIT<! CONScQUENC::s M
N A LOSS OR CAM AGE TO FA Cl LITY TY"P"E OC:SC!'llPTlON i,jslt;J
~~o----------~N~/=A ______________________________ _,..,JJ
~";;--~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~--1 7
89
~
NAME: _____
T_. __
L_._.;;;:S...... P_e=n:....:c""e=r'----------
PHONE; (609) 365-7000 Ext.Salem--52