C PS~G*

Public Service Electric and Gas Company Salem Generating Station P.O. Box #168 Hancocks Bridge, New Jersey 08038 Mr. Boyce Grier Director of USNRC March 2, 1978 Office of Inspections and Enforcements Region I 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Sir:

REPORTABLE OCCURRENCE 78-13/0lP DEGRADATION OF* SERVICE WATER SYSTEM This -letter serves to confirm our telephone *repo:rt;-of *March 1, 1978* _--

advising you of a reportable occurrence.in accordance--with~Technical.

Specification 6.9.1.8.i.

On January 11, 1978 four (4) service water pump strainers were lost within a one-half hour period.

This event prompted an investigation that was completed on February 28, 1978.

The results of this investigation show that corrective action will be required to prevent reoccurrence of an event similar to that experienced on January 11, 1978.

Preliminary results of the inves-

  • tigation indicate that the probable cause -'of the January lL, 1978 occurrence was a combination of frazil ice, relatively low tide, and silting=in.the~service_water intake bays.

A detailed rep0rtable occurrence report wi-11 be*.~ submi -tted =in the-*time __ _

period specified by Technical Specifications.

Very truly yours,

~/Jlk~

H. J. Heller Manager -

Salem Generating Station CC:

General Manager - Electric Production Manager - Quality Assurance ThP. FnPrnv PPrmlP.