BSEP-96-0204, Monthly Operating Repts for April 1996 for BSEP

From kanterella
(Redirected from ML20117F825)
Jump to navigation Jump to search
Monthly Operating Repts for April 1996 for BSEP
ML20117F825
Person / Time
Site: Brunswick  Duke energy icon.png
Issue date: 04/30/1996
From: Harrison F, Hicks G
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
BSEP-96-0204, BSEP-96-204, NUDOCS 9605200261
Download: ML20117F825 (11)


Text

- - - _ - _ _ _ _ - _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ - _ _ _ - - _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - . _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ __

CP&L Carolina Power & Light Company P.O. Box 1o429 Southport, NC 28461-o429 May 14,1996 SERIAL: BSEP 96-0204 FILE: B09-13510C U. S. Nuclear Regulatory Commission ATTENTION: Document Control Desk Washington, DC 20555 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS.1 AND 2 DOCKET NOS. 50-325 AND 50-324 i LICENSE NOS. DPR-71 AND DPR-62 MONTHLY OPERATING REPORT Gentlemen:

l In accordance with Technical Specification 6.9.1.11 for the Brunswick Steam Electric Plant, Units 1 and 2, Carolina Power & Light Company (CP&L) submits the enclosed report of operating statistics and shutdown experience for the month of April 1996. Also in accordance with Technical Specification 6.9.1.11, this report is being submitted to the NRC by the 15th day of the month following the calendar month covered by the report.

Please refer any questions regarding this submittal to Mr. Mark Turkal at (910) 457-3066.

elv: w-Q

, u. D. HicG/

Manager- Regulatory Affairs Brunswick Nuclear Plant WRM/wrm Enclosures 9605200261 960430 200tw '

PDR ADOCK 05000324 / l'I R PDR / I

I Document Control Desk BSEP 96-0204 / Page 2

\

{ cc: U. S. Nuclear Regulatory Commissiori l ATTN.: Mr. Stewart D. Ebneter, Regional Administrator 101 Marietta Street, N.W., Suite 2900 Atlanta, GA 30323-0199 Mr. C. A. Patterson '

NRC Senior Resident inspector - Brunswick Units 1 and 2:

U. S. Nuclear Regulatory Commission ATTN.: Mr. David C. Trimble, Jr. (Mail Stop OWFN 14H22)  ;

l 11555 Rockville Pike Rockville, MD 20852-2738 ,

t l

The Honorable H. Wells Chairman - North Carolina Utilities Commission t P.O. Box 29510 Raleigh, NC 27626-0510 l

l e

l l

I s

l ENCLOSURE 1 BRUNSWICK STEAM ELECTRIC PLANT, UNITS NOS.1 AND 2 I

- DOCKET NOS. 50-325 & 50-324 LICENSE NOS. DPR-71 & DPR-62 l l

PLANT PERFORMANCE DATA SYSTEM l OPERATING DATA REPORT i

l i

1

/

I i

I i

i i-

I CP&L. CO PLANT PERFORMANCE DATA SYSTEM PAGE 1 RUN DATE 05/09/96 APPENDIX B - AVERAGE DAILY POWER LEVEL RPD39-000 RUN TIME 08:09:48 BRUNSWICK UNIT 1 DOCKET NO. 050-0325 COMPLETED BY FRANCES HARRISON TELEPHONE (910)457-2756 l

APRIL 1996 DAY AVG. DAILY POWER LEVEL DAY AVG. DAILY POWER LEVEL l (MWE-NET) (MWE-NET) 1 804 17 803 2 804 18 803 3 805 19 802 l

4 804 20 801 5 804 21 801 6 804 22 801 7 805 23 800 8 806 24 801 l

9 805 25 801 10 806 26 800

, 11 806 27 797 12 801 28 801 13 715 29 800 14 804 30 800 15 803

l. 16 803 i

1.16 - 8 l

l l

t

CP&L CO PLANT PERFORMANCE DATA SYSTEM PAGE 1 RUN DATE 05/09/96 OPERATING DATA REPORT RPD36-000 RUN TIME 08:09:49 BRUNSWICK UNIT 1 DOCKET NO. 050-0325 COMPLETED BY FRANCES HARRISON OPERATING STATUS TELEPHONE (910)457-2756

1. UNIT NAME: BRUNSWICK UNIT 1 NOTES
2. REPORTING PERIOD: APRIL 96 l 3. LICENSED THERMAL POWER (MWT): 2436 l 4. NAMEPLATE RATING (GROSS MWE) : 867.0
5. DESIGN ELECTRICAL RATING (NET MWE): 821.0 l 6. MAX DEPENDABLE CAPACITY (GROSS MWE) : 791.0
7. MAX DEPENDABLE CAPACITY (NET MWE) : 767.0 -------------------------------
8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THRU 7) SINCE LAST REPORT, GIVE REASONS:

l 1

9. POWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE) :

I 10. REASONS FOR RESTRICTION IF ANY: ,

THIS YR TO CUMUL MONTH DATE ATIVE

11. HOURS IN REPORTING PERIOD 719.00 2903.00 167615.00
12. WUMBER OF HOURS REACTOR CRITICAL 719.00 2737.46 106130.20
13. REACTOR RESERVE SHUTDOWN HRS .00 .00 1647.10
14. HOURS GENERATOR ON LINE 719.00 2701.31 102052.48
15. UNIT RESERVE SHUTDOWN HOURS .00 .00 .00
16. GROSS THERMAL ENERGY GEN. (MWH) 1745963.05 6381614.54 225740185.37
17. GROSS ELEC. ENERGY GEN. (MWH) 589770.00 2137390.00 74244170.00
18. NET ELEC. ENERGY GENERATED (MWH) 574927.00 2082505.00 71459223.00
19. UNIT SERVICE FACTOR 100.00 93.05 60.89
20. UNIT AVAILABILITY FACTOR 100.00 93.05 60.89
21. UNIT CAP. FACTOR (USING MDC NET) 104.25 93.53 54.41
22. UNIT CAP. FACTOR (USING DER NET) 97.40 87.38 51.93
23. UNIT FORCED OUTAGE RATE .00 6.95 13.92
24. SHUTDOWNS SCHED. OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH):
25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF START UP:
26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION) : FORECAST ACHIEVED INITIAL CRITICALITY -------- --------

INITIAL ELECTRICITY -------- --------

COMMERCIAL OPERATION -------- --------

l 1.16 - 9

CP&k CO ' PLAli!T PERFORMANCE DATA SYSTEM PAGE 2 RUN DATE 05/09/96 APPENDIX B - AVERAGE DAILY POWER LEVEL RPD39-000 RUN TIME 08:09:48 BRUNSWICK UNIT 2 DOCKET NO. 050-0324 COMPLETED BY FRANCES HARRISON TELEPHONE (910)457-2756 APRIL 1996 DAY AVG. DAILY POWER LEVEL DAY AVG. DAILY POWER LEVEL

-(MWE-NET) (MWE-NET) 1 791 17 746 2 791 -18 772 l

3 790 19 762 4 789 20 771 5 789 21 771 6 788- 22 771 l 7 789 23 770 8 789 24 771 9 789 25 771 10 788 26 747 11 788 27 39 12 788 28 446 13 788 29 699 14 786 30 779 15 788

, 16 787 1.16 - 8 l

l

CP&I4 CO PLANT PERFORMANCE DATA SYSTEM PAGE 2 RUN DATE 05/09/96 OPERATING DATA REPORT RPD36-000 RUN TIME 08:09:49 BRUNSWICK UNIT 2 DOCKET NO. 050-0324 COMPLETED BY FRANCES HARRISON l OPERATING STATUS TELEPHONE (910)457-2756 l

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . . . . i

1. UNIT NAME: BRUNSWICK UNIT 2 NOTES l
2. REPORTING PERIOD: APRIL 96
3. LICENSED THERMAL POWER (MWT) : 2436
4. WAMEPLATE RATING (GROSS MWE) : 867.0
5. DESIGN ELECTRICAL RATING (NET MWE) : 821.0
6. MAX DEPENDABLE CAPACITY (GROSS MWE) : 782.0 7.. FiAX DEPENDABLE CAPACITY (NET MWE): 754.0 -------------------------------
8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THRU 7) SINCE LAST REPORT, GIVE REASONS:
9. POWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE) :
10. REASONS FOR RESTRICTION IF ANY:

THIS YR TO CUMUL MONTH DATE ATIVE

11. HOURS IN REPORTING PERIOD 719.00 2903.00 179639.00
12. NUMBER OF HOURS REACTOR CRITICAL 719.00 1905.92 115221.62
13. REACTOR RESERVE SHUTDOWN HRS .00 .00 .00
14. HOURS GENERATOR ON LINE 695.72 1793.53 109671.24
15. UNIT RESERVE SHUTDOWN HOURS .00 .00 .00
16. GROSS THERMAL ENERGY GEN. (MWH) 1672637.50 3423429.68 235608435.05
17. GROSS ELEC. ENERGY GEN. (MWH) 549630.00 1115570.00 76184291.00
18. WET ELEC. ENERGY GENERATED (MWH) 532809.00 1067084.00 73116301.00
19. UNIT SERVICE FACTOR 96.76 61.78 61.05
20. UNIT AVAILABILITY FACTOR 96.76 61.78 61.05 ,
21. UNIT CAP. FACTOR (USING MDC NET) 98.28 48.75 52.14
22. UNIT CAP. FACTOR (USING DER NET) 90.26 44.77 49.58
23. UNIT FORCED OUTAGE RATE 3.24 3.57 11.16
24. SHUTDOWNS SCHED. OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH) :
25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF START UP:
26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION): FORECAST ACHIEVED INITIAL CRITICALITY -------- --------

)

INITIAL ELECTRICITY -------- --------

COMMERCIAL OPERATION -------- --------

1.16 - 9 l

ENCLOSURE 2 l BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS.1 AND 2 '

DOCKET NOS. 50-325 & 50-324 LICENSE NOS. DPR-71 & DPR-62 UNIT SHUTDOWN AND POWER REDUCTION 3 REPORT -APRIL 1996 .

l l

l t

l l

l 4

m l

l

DOCKET NO. 050-0325 ,

UNIT NAME Brunswick I DATE May 1996 CCNPLETED BY Frances Harrison TELEPHONE 910-457-27 L .

UNIT SHUTDOWNS AND POWER REDUCTIONS REPORT MDNTH Aoril 1996 METM)0 0F LICENSEE DURATION SHUTTING EVENT SYSTEM COMPONENT CAUSE & CORRECTIVE ACTION TO NO. DATE TYPE (1) (HOURS) REASON (2) DOWN REACTOR REPORT NO. CODE (4) CODE (5) PREVENT RECURRENCE (3)96-013 960413 5 .00 B 5 NA HA VALVEX Downpower for valve testing and hotside maintenance.

1: hag 2: Reason 3: Method 4: Systen Code- 5. Comoonent code F - Forced A- Equipment Failure 1- Manual Instructions for Instructions for S - Scheduled (explain) 2- Manual Scram preparation of data entry preparation of data B- Maintenance or test 3- Autanatic scram sheets for Licensee Event entry sheets for LER C- Reft.eling 4- Continuations Report (LER) file from file fran IEEE D- Regulatory 5- Load reductions IEEE Standard 805-1983. Standard 803A-1983, t restriction 6- Other per NUREG-1022. per NUREG-1022.

E- Operator Training & Section VI. Item 13.b Section VI. Item 13.c License Examinatic' F- Adninistrative  ;

G- Operational error (explain)

H- Other (explain)

DOCKET NO. 050-03?4 ,

UNIT NAME Brunswick II DATE May 1996 COMPLETED BY Frances Harris 5 TELEPHONE 910-457-2756 UNIT SHUTDOWNS AND POWER RED'JCTIONS REPORT K) NTH Aoril 1996 METHOD OF LICENSEE DURATION SHUTTING EVENT SYSTEM COMPONENT CAUSE & CORRECTIVE ACTION TO NO. DATE TYPE (1) (HOURS) REASON (2) DOWN REACTOR REPORT NO. COGd (4) CODE (5) PREVENT RECURRENCE (3)96-018 960417 F 00 A 5 NA CH VALVEX Reduced power to 881 and isolated 4A and SA Feedwater Heaters.96-019 960419 F 00 A 5 NA CH VALVEX Reduced power to 90% to troubleshoot possible tube leak in the 4A/5A Feedwater Heaters.96-020 960426 F 00 A 5 NA CH VALVEX Power reduction in preparation for removing unit fra service to repair 4A Fee &ater Heater Level Control Valve.96-021 960327 F 23 hrs. A 1 NA CH VALVEX Turbine removed fra service 17 min. to repair Fee &ater Heater Level Control Valve.96-016 960331 F 00 A 5 NA CH VALVEX Rod Improvement 1: Img 2: Reason 3: Method 4: System Code- 5. Comoonent code F - Forced A- Equipment Failure 1- Manual Instructions for Instructions for 5 - Scheduled (explain) 2- Manual Scram preparation of data entry preparation of data B- Maintenance or test 3- Autmatic scram sheets for Licensee Event entry sheets for LER C- Refueling 4- Continuations Report (LER) file frm file fra IEEE D- Regulatory 5- Load reductions IEEE Standard 805-1983. Standard 803A-1983.

restriction 6- Other per NUREG-1022. per NUREG-1022.

E- Operator Training & Section VI. Item 13.b Section VI. Item 13.c License Examination F- Adninistrative

ENCLOSURE 3 BRUNSWlCK STEAM ELECTRIC PLANT, UNIT NOS.1 AND 2 NRC DOCKET NOS. 50-325 AND 50-324 OPERATING LICENSE NOS. DPR-71 AND DPR-62 MONTHLY OPERATING REPORT LIST OF REGULATORY COMMITMENTS The following table identifies those actions committed to by Carolina Power & Light Company in this document. Any other actions discussed in the submittal represent intended or planned actions by Carolina Power & Light Company. They are described to the NRC for the NRC's information and are not regulatory commitments. Please notify the Manager-Regulatory Affairs at the Brunswick Nuclear Plant of any questions regarding this document or any associated regulatory commitments.

Committed Commitment date or outage *

1. None N/A l

I E3-1

_ _.