BSEP-96-0295, Monthly Operating Repts for July 1996 for Brunswick Steam Electric Plant,Units 1 & 2

From kanterella
Jump to navigation Jump to search
Monthly Operating Repts for July 1996 for Brunswick Steam Electric Plant,Units 1 & 2
ML20116M139
Person / Time
Site: Brunswick  Duke energy icon.png
Issue date: 07/31/1996
From: Harrison F, Hicks C
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
BSEP-96-0295, BSEP-96-295, NUDOCS 9608200044
Download: ML20116M139 (11)


Text

(. .

Carolina Power & Light Company

, P.O. Box 10429 Southport, NC 28461-0429

'AUG 131996 SERIAL: BSEP 96-0295 FILE: B09-13510C U. S. Nuclear Regulatory Commission ATTENTION: Document Control Desk l Washington, DC 20555 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS.1 AND 2 DOCKET NOS. 50-325 AND 50-324 LICENSE NOS. DPR-71 AND DPR-62 MONTHLY OPERATING REPORT Gentlemen:

In accordance with Technical Specification 6.9.1.11 for the Brunswick Steam Electric Plant, Units 1 and 2, Carolina Power & Light Company (CP&L) submits the enclosed report of operating statistics and shutdown experience for the month of July 1996. Also, in accordance with Technical Specification 6.9.1.11, this report is being submitted to the NRC by the 15th day of the month followin0 the calendar month covered by the report.

Please refer any questions regarding this submittal to Mr. Mark Turkal at (910) 457-3066.

Sincerely,n f, --

~j v.

n .

u. s_,

Manager- Regulatory Affairs Brunswick Nuclear Plant  !

l WRM/wrm j Enclosures l 2000M

- /

1 9608200044 960731 PDR ADOCK 05000324 R PDR

]

Document Control Desk BSEP 96-0295 / Page 2 ,

l cc: U. S. Nuclear Regulatory Commission l ATTN.: Mr. Stewart D. Ebneter, Regional Administrator 101 Marietta Street, N.W., Suite 2900 Atlanta, GA 30323-0199 I Mr. C. A. Patterson I NRC Senior Resident inspector - Brunswick Units 1 and 2:  ;

U.S. Nuclear Regulatory Commission ATTN.: Mr. David C. Trimble, Jr. (Mail Stop OWFN 14H22) j 11555 Rockville Pike l Rockville, MD 20852-2738 '

The Honorable H. Wells Chairman - North Carolina Utilities Commission i P.O. Box 29510 l Raleigh, NC 27626-0510 l

1 l

)

i l

  • 9 .

e-4 ENCLOSURE 1 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS.1 AND 2 DOCKET NOS. 50-325 AND 50-324 LICENSE NOS. DPR-71 AND DPR-62 MONTHLY OPERATING REPORT I

PLANT PERFORMANCE DATA SYSTEM l OPERATING DATA REPORT l

I i

1

. -- . . ~

?

! CP&L CO PLANT PERFORMANCE DATA SYSTEM PAGE 1 i R N DATE 08/03/96 APPENDIX B - AVERAGE DAILY POWER LEVEL RPD39-000 RUN TIME 10:10:48 BRUNSWICK UNIT 1 DOCKET NO. 050-0325 COMPLETED BY FRANCES HARr(ISON TELEPHONE (910)457-2756 JULY 1996 DAY AVG. DAILY POWER LEVEL DAY AVG. DAILY POWER LEVEL (MWE-NET) (MWE-NET) 1 738 17 7 2 784 18 526 3 781 19 690 4 781 20 682 5 772 21 569 6 636 22 744 7 783 23 760 8 786 24 722 9 784 25 678 10 758 26 787 '

11 1 27 787 12 -12 28 784 i

13 -11 29 785 14 -9 30 785 15 -9 31 728 l

16 -9 I

l

)

1.16 - 8 l l

i

i CP&L CO PLANT PERFORMANCE DATA SYSTEM PAGE 1 I ROM DATE 08/03/95 OPERATING DATA REPORT RPD36-000 )

RUN TIME 10:10:49 BRUNSWICK UNIT 1 i

' ~

DOCKET NO. 050-0325 COMPLETED BY FRANCES HARRISON OPERATING STATUS TELEPHONE (910)457-2756

1. UNIT NAME: BRUNSWICK UNIT 1 NOTES
2. REPORTING PERIOD: JULY 96
3. LICENSED THERMAL POWER (MWT) : 2436
4. NAMEDLATE RATING (GROSS MWE) : 867.0
5. DESIGN ELECTRICAL RATING (NET MWE): 821.0
6. MAX DEPENDABLE CAPACITY (GROSS MWE): 791.0
7. MAX DEPENDABLE CAPACITY (NET MWE): 767.0 -------------------------------
8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THRU 7) SINCE LAST REPORT, 1 GIVE REASONS:
9. POWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE) :  :
10. REASONS FOR RESTRICTION IF ANY: l THIS YR TO CUMUL MONTH DATE ATIVE
11. HOURS IN REPORTING PERIOD 744.00 5111.00 169823.00
12. NUMBER OF HOURS REACTOR CRITICAL 602.85 4804.31 108197.05
13. REACTOR RESERVE SHUTDOWN HRS .00 .00 1647.10
14. HOURS GENERATOR ON LINE 580.52 4745.83 104097.00
15. UNIT RESERVE SHUTDOWN HOURS .00 .00 .00
36. GROSS THERMAL ENERGY GEN. (MWH) 1320994.08 11189547.74 230548118.57
17. GROSS ELEC. ENERGY GEN. (MWH) 437115.00 3739315.00 75846095.00
18. NET ELEC. ENERGY GENERATED (MWH) 422116.00 3637754.00 73014472.00
19. UNIT SERVICE FACTOR 78.03 92.86 61.30
20. UNIT AVAILABILITY FACTOR 78.03 92.86 61.30
21. UNIT CAP. FACTOR (USING MDC NET) 73.97 92.80 54.88
22. UNIT CAP. FACTOR (USING DER NET) 69.11 86.69 52.37
23. UNIT FORCED OUTAGE RATE .00 4.08 13.68 1
24. SHUTDOWNS SCHED. OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH) : '

Refueling Outage 10-5-96 for 35 days l

25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF START UP: j
26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION) : FORECAST ACHIEVED >

INITIAL CRITICALITY -------- --------

INITIAI ELECTRICITY -------- --------

COMMERCIAL OPERATION -------- --------

l 1.16 - 9 l

i

f. - .

I CP&L CO PLANT PERFORMANCE DATA SYSTEM- PAGE 2 l-RUNDATE 08/03/96 APPENDIX B - AVERAGE DAILY POWER LEVEL RPD39-000 .

l RUN TIME 10:10:48 BRUNSWICK UNIT 2 1

! l l

DOCKET NO. 050-0324 COMPLETED BY FRANCES HARRISON TELEPHONE (910)457-2756

'JOLY 1996 l I

' DAY AVG. DAILY POWER LEVEL DAY AVG. DAILY POWER LEVEL (MWE-NET) (MWE-NET) l l- ,

i- 1 778 17 65 .

! 2 715 18 458 1

3 722 19 731 i k

l i

4 777 20 750 5 776 21 748 6 778 22 757  :

7 777 23 757

! 8 777 24 756 l

9 776 25 755 I 10 776 26 582 i 11- 101 27 -15 l 12 -11 28 53 1

13 -10 29 645 14- -11 30 704 f 15 -11 31 621 l

, 16 -12

)

l I

l 1.16 - 8 l

lI I

t I '

l CP&L CO PLANT PERFORMANCE DATA SYSTEM PAGE 2 l RUN DATE 08/03/96 OPERATING DATA REPORT RPD36-000 i

RUN TIME 10:10:49 BRUNSWICK UNIT 2 l

DOCKET NO. 050-0324 COMPLETED BY FRANCES HARRISON OPERATING STATUS TELEPHONE (910)457-2756

1. UNIT NAME: BRUNSWICK UNIT 2 NOTES
2. REPORTING PERIOD: JULY 96
3. LICENSED THERMAL POWER (MWT) : 2436
4. NAMEPLATE RATING (GROSS MWE) - 867.0
5. DESIGN ELECTRICAL RATING (NET MWE) : 821.0
6. MAX DEPENDABLE CAPACITY (GROSS MWE): 782.0
7. MAX DEPENDABLE CAPACITY (NET MWE) : 754.0 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THRU 7) SINCE LAST REPORT, GIVE REASONS:
9. FOWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE) :
10. REASONS FOR RESTRICTION IF ANY:

THIS YR TO CUMUL MONTH DATU ATIVE ,

1

11. HOURS IN REPORTING PERIOD 744.00 5111.00 181847.00
12. HUMBER OF HOURS REAC'IOR CRITICAL 585.77 3955.69 117271.39
13. REACTOR RESERVE SHUTDOWN HRS .00 .00 .00
14. HOURS GENERATOR ON LINE 546.80 3804.33 111682.04
15. UNIT RESERVE SHUTDOWN HOURS .00 .00 .00
16. GROSS THERMAL ENERGY GEN. (MWH) 1245540.44 8225843.87 240410849.24 ,
17. GROSS ELEC. ENERGY GEN. (MWH) 400820.00 2689965.00 77758686.00 J
18. NET ELEC. ENERGY GENERATED (MWH) 385524.00 2592100.00 74642317.00 )
19. UNIT SERVICE FACTOR 73.49 74.43 61.42
20. UNIT AVAILABILITY FACTOR 73.49 74.43 61.42
21. UNIT CAP. FACTOR (USING MDC NET) 68.72 67.29 52.60
22. UNIT CAP. FACTOR (USING DER NET) 63.12 61.80 50.00
23. UNIT FORCED OUTAGE RATE 7.36 5.27 11.01
24. SHUTDOWNS SCHED. OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH):
25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF START UP:
26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION): FORECAST ACHIEVED INITIAL CRITICALITY ------__ ________

INITIAL ELECTRICITY _----___ ________

COMMERCIAL OPERATION --___--- ________

1.16 - 9 l

i

ENCLOSURE 2 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS.1 AND 2 DOCKET NOS. 50-325 AND 50 324  ;

LICENSE NOS. DPR-71 AND DPR-62 l MONTHLY OPERATING REPORT

.i UNIT SHUTDOWN AND POWER REDUCTION REPORT-JULY 1996 l

~

)

+ , , , ~. -

l DOCKET to. 050-0325 UNIT NAME _ Brunswick I DATE Aucust 1996 COMPLETED BY Frances Harrison TELEPHONE 910-457-2756 -

UNIT SHUTDOWNS AND POWER REDUCTIONS REPORT MDNTH Julv 1996 METHOD OF LICENSEE DURATION SHUTTING EVENT SYSTEM CCNPONENT CAUSE & CORPICTIVE ACTION TO NO. DATE TYPE (HOURS) REASON (2) DOWN REACTOR REPORT NO. CODE (4) CODE (5) PPIVENT RECURRINCE (1) (3)96-022 960705 5 .00 B 5 NA RC CONROD Rod Impre W 96-024 960710 5 163 hrs. H 2 NA ZZ ZZZZZZ Outage due to Hurricane 29 min Bertha 96-026 960720 5 .00 B 5 NA RC _) CONROD Rod Improvement 96-027 960723 5 .00 B 5 NA RC CONROD Losses due to rod pattern being such that the unit can't attain full rx thennal pcwer 96-028 960724 5 .00 ,,,J 5 NA RC CONROD Rod Improvement 96-030 960731 F .00 H 5 NA HF FILTER 7 P power due to three out

, of four CWIPs tripping due to high screen dP.

1: J.mg 2: Eecian 3: Method 4: system Code: 5. Comoonat Code F - Forced A- r ,ipment Failure 1- Manual Instructions for Instructions for 2

5 - Scheduled .xplain) 2- Manual Scram preparation of data entry preparation of data B- naintenence or test 3- Autmatic scram sheets for Licensee Event entry sheets forLER C- Refueling 4- Continuations Report (LER) file from file from IEEE D- Regulatory 5- Load redtetions IEEE Standard 805-1983. Standard 803A 1983.

restriction 6- Other per NUPIG-1022. per NUREG- d 2.

E- Operstor Training & Section VI. Item 13.b Section VI. Item 13.c License Exarination F- Adninistrative G- Operational error (explain)

H- Other (explain)

DOCKET to. 050-0324 UNIT NAME Brunswick II -

DATE Auoust 1996 COMPLETED BY Frances Harrison TELEPHONE 910-457-2756 .

UNIT SHUTDWNS AND POWER REDUCTIONS REPORT FONTH July 1996 METHOD OF LICENSEE DURATION SHUTTING EVENT SYSTEM CCt4PONENT CAUSE & CORRECTIVE ACTION T0 to. CATE TYPF (1) (HOURS) REASON (2) DOWN REACTOR REPORT NO. CODE (4) CODE (5) PREVENT RECURRENCE (3)96-026 960702 F .00 H 5 NA ZZ ZZZZZZ Red pwr to-700 rrwe at dispatcher's request due to tripped Castle Hayne line 96-028 960711 5 153 hrs. H 2 NA ZZ ZZZZZZ Outage - Hurricane Bertha.

44 min.96-030 960719 F 00 A 5 NA CH VALVEX Losses due to 4A/5A heaters being isolated due to HD-LV-75 prtbl es.96-032 960726 F 43 hrs. A 2 NA CH VALVEX forced Outage to repair HD-29 min. LV-75.96-034 ../30 F 00 A 5 NA CB MOTORX Red pwr due to 2A recirc pump motor imp hiah.96-035 960731 5 .00 B 5 NA RC CONROD Rod Improvenent.

1. Igg 2: Peason 3: Methos1 4: System Code: 5. Canoonent Code F - Forced A- Equipment Failure 1- Manual Instructions for Instructions for 5 Scheduled (explain) 2- Manual Scram preparation of data entry preparation of data B- Maintenance or test 3- Automatic scram sheets for Licensee Event entry sheets for LER C- Refueling 4- Continuations Report (LER) file from file frm IEEE D- Regulatory 5- Load reductions IEEE Standard 805-1983. Standard 803A-1983.

restriction 6- Other per NUREG-1022. per NUREG-1022.

E- Operator Training & Section VI. Item 13.b Section VI. Iten 13.c License Examination F- Adninistrative G- Operational error (explain)

H- Other (e 91ain)

ENCLOSURES l

l BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS.1 AND 2 NRC DOCKET NOS. 50-325 AND 50-324 OPERATING LICENSE NOS. DPR-71 AND DPR-62 l MONTHLY OPERATING REPORT l l

l l LIST OF REGULATORY COMMITMENTS The following table identifies those actions committed to by Carolina Power & Light Company in l this document. Any other actions discussed in the submittal represent intended or planned actions by Carolina Power & Light Company. They are described to the NRC for the NRC's information and are not regulatory commitments. Please notify the Manager-Regulatory Affairs at the Brunswick Nuclear Plant of any questions regarding this document or any associated

( regulatory commitments.

l Committed l Commitment date or*

i outage

1. None N/A 1

I l

l i

I 1

a 4

m