Forwards Rev 0 to App C Inservice Pump & Valve Testing Program for 1990-1999 Interval, QA Manual for Review & Approval.Program Reviewed to Positions Delineated in Generic Ltr 89-04
ML17251A521
Person / Time
Site: Ginna Constellation icon.png
Issue date: 05/23/1989
From: MECREDY R C
ROCHESTER GAS & ELECTRIC CORP.
To: JOHNSON A
Office of Nuclear Reactor Regulation
Shared Package
ML17251A522 List:
References
GL-89-04, GL-89-4, NUDOCS 8906050144
Download: ML17251A521 (5)


Text

'.A.C:CELERATEDDlgPBUTlONDEMONSTf+10NSYSTEM,E,'-'-tREGULATORYIANFORMATIONDISTRIBUTIONSYSTEM(RIDS)ACCESSIONNBR:8906050144'OC.DATE:89/05/23NOTARIZED:NODOCKETFACIL:50-244RobertEmmetGinnaNuclearPlant,Unit1,RochesterG05000244AUTH.NAMEAUTHORAFFILIATIONMECREDY,R.C.RochesterGas&ElectricCorp.RECIP.NAMERECIPIENTAFFILIATIONJOHNSON,A.ProjectDirectorateI-3

SUBJECT:

Forwards"QAManualGinnaStationRGEAppCInservicePump&RValveTestingProgramfor1990-99Interval."+/g7DISTRIBUTIONCODE:A047DCOPIESRECEIVED:LTRIENCLgSIZE:8TITLE:ORSubmittal:InserviceInspection/Testing/RelieffromASMECodeDNOTES:LicenseExpdateinaccordancewith10CFR2,2.109(9/19/72).050002448RECIPIENTIDCODE/NAMEPD1-3LAJOHNSON,AINTERNAL:AEOD/DSP/TPABNRR/DEST/MTB9HOC/LQMBEGFZX'1EXTERNAL:EG&GBROWN,BLPDRNRCPDRCOPIESLTTRENCL101111111011111111RECIPIENTIDCODE/NAMEPD1-3PDNRR/DEST/MEB9HNUDOCS-ABSTRACTOGC/HDS2RES/DSIR/EIBEG&GROCKHOLD,HNL007HEMMINGNSICCOPIESLTTRENCL11111011N111RISNOTE'IOALL"RIDS"RECIPIEMIS:PLEASEHELPUSIOREDUCEHASTECGNZACTTHEDXX3MEÃZCONTROLDESKIRXMPl-37(EZZ.20079)KOELIKBQQEYOURNAMEFRYDISTRIBUTIONLISTSFORDOCUMENZSYOUDONiTNEEDtTOTALNUMBEROFCOPIESREQUIRED:LTTR21ENCL SZZZrZZPIIIIIIIIL4ilOwl~IJIIZZSZruZ8K.::::ISROCHESTERGASANDELECTRICCORPORATIONo89EASTAVENUE,ROCHESTER,N.Y.14649.0001May23,1989TELEPHONCAscAcoom7ia546.2700U.S.NuclearRegulatoryCommissionDocumentControlDeskAttn:Mr.AllenJohnsonPWRProjectDirectorateI-3DivisionofReactorProjectsI/IIWashington,D.C.20555

SUBJECT:

InservicePumpandValveTestingProgramR.E.GinnaNuclearPowerPlantDocketNo.50-244

DearMr.Johnson:

Inaccordancewithrequirementsof10CFRPart50,Section50.55a,paragraph(g),wehaveenclosedtheGinnaStationInservicePumpandValveTesting(IST)ProgramfortheJanuary1,1990throughDecember31,1999intervalforyourreviewandapproval.ThisprogramwilldirectsurveillancerequirementsdelineatedinTechnicalSpecificationsSection4.2fortheInservicePumpand.ValveTestingProgram.Theenclosureisentitled"AppendixCInservicePumpandValveTestingProgramforthe1990-1999Interval."ThisprogramcloselyparallelstherecentlyrevisedRGGEISTprogramfor1989endorsedbyyourletterdatedMay3,1989.Inaccordancewith10CFR50.55aparagraph(g)(4)(ii),thisprogramisbasedonthe1986EditionofASMESectionXI".Theenclosed10yearsubmittalwasreviewedtopositionsdelineatedinAttachment1bfUSNRCGenericLetter89-04issued.onApril3,1989'.TheprogramcomplieswithpositionsofAttachment1withonepossibleexception.Position4ofAttachment1would.requiretwoseriescheckvalvesinEventVconfigurationstobeindividuallytested.TheGinna.configura-tionforSafetyInjectiontoeachReactorCoolantSystemHotLegcontainstwoseriescheckvalvesinserieswithalockedclosed,deenergizedmotoroperated.valve.Themotoroperatedvalveisleaktestedalongwithaleaktestconductedonthecheckvalvesinseries.Anevaluation.hasbeeninitiated.todetermineifthisisadiscrepancy.Theresolution,tobeprovided.priortoAugust.1,1989,willeitherinvolvefurtherclarificationtoTechnicalSpecifications,furtherclarificationofthissubmittaloracommitmenttoafuturemodification.39060501448'F0523PDRAGOCK05000244PPDC GenericLetter89-04,Attachment1-Position11identifiesexamplesofvalvesandpumpsorvalvegroupsthathavegenerallyanderroneouslybeenomittedfromISTprograms.SuchitemsareincludedintheprogramasManagementdirectedupgradesorfromagoodEngineeringpracticestandpoint,whentheyareapplicabletoRGGE'sSystemSelectionCriteria.ThefollowingEGGGresponsenumbersdocumentedinoursubmittaldatedDecember20,1988substantiatetheexclusionofsomeoftheseexamplesfromtheISTProgram.Position11referenceEG&GResponseNumberControlRoomChilledWaterAccumulatorMOVs/VentsAuxiliaryPrzrSprayBoricAcidTransferPumpsValvesinEmergencyBorateFlowpathH-2E-10B-1B-7;2-7B-7;2-7SinceourDecember20,1988responsetothe99EGGGquestionsprovidedinyourJune21,1988lettertoMr.R.W.Kober,achangeinourresponsetoQuestionsB-2,B-5,D-4,E-3,E-5,F-4,L-1,P-6andP-9hasoccurred.asfollows:TheB-2andB-5responsesindicatedthatvalves204A,427and820weretobetestedaseitherpressureorcontainmentisolationvalves.Withthereclassificationofletdownisolationvalves200A,200B,202toserveasbothpressureandcontainmentisolationfunctions,valves204A,427and820arenotrequiredtobeincluded.intheISTprogram.TheD-4responseindicatedthatfullstroke.exercisingflowratesforCCWvalves723AandBwas2500GPM.Subsequentevaluationindicatesthatthesevalveswillbepartialstroketested.to2500GPMquarterlyand.fullstroketested.to2980GPMatcoldshutdown.Thisisduetosystemconfigurationandtestmethodsavailableatpower.TheE-3responseindicatedfullstrokeexerciseforSIpumpdischargecheckvalves870A,870B,889A6889Bwouldoccurduringcoldshutdowns.Duetolowtemperatureoverpres-surizationconcernsforthereactorcoolantsystem,arefuelingfrequencyisnowproposedconsistentwithreliefrequestVR-11.TheE-5responseindicatedfullstrokeexerciseforsafetyinjectionsystempressureisolationvalves878Gand878Jwouldoccurduringcoldshutdowns.DuetolowtemperatureoverpressurizationconcernsforthereactorcoolantsystemarefuelingfrequencyisnowproposedconsistentwithreliefrequestVR-10.

TheF-4responseindicated.thatsafetyinjectionrecir-culationand,testlinereturnvalves897and898wouldbeexercisedatcoldshutdownastheywereblockedopenduringnormaloperation.Duringthe1989outagetheairoperatedvalveswerereplacedwithmotoroperatedvalvespermittingquarterlytestinginaccordancewiththeCode.~TheL-1responseprovidedatestmethodforclosureverificationofMainFeedwatercheckvalves3992and3993.Analternatemethod,hasbeendevelopedtotestthevalvesduringroutinecoldorrefuelingshutdownsinvolvingapressuredropverification.Thiswillbeusedinlieuofthemethodpreviouslydescribed.Forunscheduledshutdownsresultingfromaplanttrip,areliefrequestisprovided.toallowdeferraloftestingtothenextplannedcoldshutdownorrefueling.~TheP-6responseindicatedthatvalve857Cwasapassivevalvewhichiskeptlockedopenwithpowerremoved.Duringthe1989outagetheRHRtoSIsystemcross-connectvalveswereupgraded.Valve857Cisnowmaintainedclosedandisrequiredtoopenforhighheadsafetyinjectionre-circulation.Thisvalvehasbeenincludedintheprogramandwillbeexercised.inaccordancewiththeCode.~TheP-9responseindicatedthatvalve822Ahadasafetyfunctionandwouldbeadded,totherevisedISTprogramasaCategoryAClassboundaryvalve.Subsequentreviewhasdetermined.thatvalve822Aisnotacontainmentisolationvalve,thereforenegating,itsneedtobeincludedintheIST'rogram.Considerationwasgiventoevaluatingtimeandresourcesneededforanadequatepumpand.valvereviewtocurrentcriteriaandguidelinesestablishedinGenericLetter89-04.Itwasestimatedthatoneyearand,approximately2500man-hours,asaminimum,wouldberequired.forexistingprograms.Verytrulyyours,RobertC.MedyGeneralManager,NuclearProductionRCMhcemh114 0CII'