Notice of Violation from Insp on 850509-0621
ML20132D680
Person / Time
Site: Braidwood, Satsop  Constellation icon.png
Issue date: 07/09/1985
From: Little W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML20132D670 List:
References
50-456-85-23, 50-457-85-24, NUDOCS 8508010333
Download: ML20132D680 (1)


See also: IR 05000509/2006021

Text

-

, o

i

Appendix

NOTICE OF VIOLATION

Comonwealth Edison Company Docket No. 50-456

Docket No. 50-457

As a result of the inspection conducted on May 9 through June 21, 1985, and in

accordance with the General Policy and Procedures for NRC Enforcement Actions

(10 CFR Part 2, Appendix C), the following violation was identified:

10 CFR 50, Appendix B, Criterion XIII, states in part, that measures shall

be established to control the storage and preservation of material and

equipment to prevent damage or deterioration. The Commonwealth Edison

Company Quality Assurance Program contains in Quality Requirement (QR)

2.0 a commitment to Regulatory Guide 1.39, Revision 2.

Regulatory Guide 1.39, Revision 2, endorses the requirements of ANSI

N45.2.3-1973, " Housekeeping During the Construction Phase of Nuclear

Power Plants". ANSI N45.2.3, Section 3.2.1, requires that scrap and

excess materials shall be collected and disposed of in accordance with

specified requirements. Such excess material shall not be allowed to

accumulate and create conditions that will adversely affect quality.

Contrary to the above:

a. Nails, washers, bolts, screws, wire, metal brackets and a grinding

wheel were found in cable trays which had installed cable,

b. The upper cable spreading room was noted as having debris in cable

trays and empty aerosol cans which had contained a highly flammable

liquid.

c. High strength bolting material, (A490 and A325 galvanized bolts,

which cannot be reused per the AISC Code) were found laying in

various work areas of the plant, not controlled or stored in a

material staging area.

This is a Severity Level IV Violation (Supplement II).

Pursuant to the provisions of 10 CFR 2.201, you are required to submit to this

office within thirty days of the date of this Notice a written statement or

explanation in reply, including for each item of noncompliance: (1) corrective

action taken and the results achieved; (2) corrective action to be taken to

avoid further noncompliance; and (3) the date when full compliance will be

achieved. Consideration may be given to extending your response time for good

cause shown.

1kbr

Datef~

ffMA

W. 5. Little( Director "

Braidwood Project

-

8508010333 850711

PDR ADOCK 05000456

G PDRs