i TABLE 15.3.5-5 .

INSTRUMENT OPERATING CONDITIONS FOR INDICATIONS 1 2 3 MINIMUM NO. OF OPERABLE OPERATOR ACTION IF CONDITIONS CHANNELS ((iANNELS OF COLUMN 2 CANNOT BE MET NO. FUNCTIONAL UNIT

1. PORY Position Indicator 1/ Valve 1/ Valve If the operability of the PORY position indicator cannot be restored within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />, shut the associated PORV Block Valve.

1/ Valve 1/ Valve If the operability of the PORV Block Valve Position l

2. PORY 8?ock Valve Position Indicator cannot tm restored within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />, shut and Indicator verify the Block Valve shut by direct observation or declare the Block Valve inoperable.

Safety Valve Position Indicator 1/ Valve 1/ Valve If the operability of the Safety Valve Position

3. Indicator cannot be restored within seven days, he in at least Hot Shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
4. Reactor Coolant System Subcooling 1 1 If the operability of a subcooling monitor cannot be restored or a backup monitor made fur.ctional within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />, be in at least Hot Shutdown within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
5. Auxiliary Feedwater Flow Rate
  • 1 1 If the cperability of the auxiliary feedwater flow rate indicator cannot be restored within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />, be in hot shutdown within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
6. Contro Rod Misalignment as 1 1 Log individual rod positions once/hr., after a l

Monitored by On-Lino load change >10% or after >30 inches 4 ,8!(yeij of control l rod motion, l Computer