ML20101B103

From kanterella
Revision as of 05:56, 29 April 2020 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Rev 1 to Final Deficiency Rept DER 84-21 Re Rosemount Transmitters Not Torqued to Specified Value.Initially Reported on 840430.Units 1 & 2 Mounting Hardware Replaced to Conform W/Matl & Installation Requirements
ML20101B103
Person / Time
Site: Palo Verde  Arizona Public Service icon.png
Issue date: 12/08/1984
From: Van Brunt E
ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR
To: Kirsch D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
ANPP-31386-TDS, DER-84-21, NUDOCS 8412200105
Download: ML20101B103 (6)


Text

_ _ _ _ _ _ _

1 Arizona Nuclear Power Project P.O. BOX 52034 e PHOENIX. ARIZONA 85072-2034 December 8,1984 ANPP-31386-TDS/TRB U. S. Nuclear Regulatory Commission Region V 1450 Maria Lane - Suite 210 Walaut Creek, California 94596-5368 Attention: Mr. D. F. Kirsch, Acting Director Division of Reactor Safety and Projects

Subject:

Final Report, Revision 1 - DER 84-21 A 50.55(e) Reportable Condition Relating To Rost. mount Transmitters Not Torqued To Specified Value.

File: 84-019-026; D.4.33.2

Reference:

A) Telephone Conversation between T. Young and J. Cook on April 31, 1984 B) ANPP-29530, dated May 17, 1984 (Interim Report)

C) ANPP-30353, dated August 29, 1984 (Time Extension)

D) ANPP-30532, dated September 27, 1984 (Time Extension)

El ANPP-30980, dated October 26, 1984 (Time Extension)

F.. A.NPP-31033, dated November 5,1984 (Final Report)

Dear 'Jir:

Attached is Revision 1 of our final written report of the Reportable Deficiency under 10CFR50.55(e) referenced above. This Revision provides clarification of the Condition Description and Corrective Action aa requested by your office in the November 30, 1984 Exit Meeting held at Palo Verde.

Very Truly Yours, CCJLL

&Ltd_(

0105 841200 E.E. Van Brunt, Jr.

h S

OCK 05000 APS Vice President Nuclear Pr'oduction 1 ANPP Project Director I EEVB/TRB/nj 3; , y l l [g] tg Attachment j l

cc: See Page Two Ou

"?!J30i) b h

. . s ,

1 Mr. D. F. Kirsch DER 84-21

'Page Two ec:. - Richard DeYoung, Director Office of Inspection and Enforcement-U. S. Nuclear Regulatory Commission Washington, D. C. 20555

. T. G. Woods, Jr.

D. B. Karner W. E. Ide D. B. Fasnacht A. C. Rogers L. A. Souza D. E. Fowler T. D. Shriver C. N. Russo B. S. Kaplan J. R. Bynum

J. M. Allen A. C. Gehr i W. J. Stubblefield W. G. Bingham i R. L. Patterson R. W. Welcher H. D. Foster D. R. Hawkinson R. P. Zimmerman L. Clyde 1 M. Matt-j T. J. Bloom D. N. Stover

. J. D. Houchen J. E. Kirby D. Canady i ~

Records Center Institute of Nuclear Power Operations ,

c' 1100 Circle 75 Parkway, Suite 1500; Atlanta, GA 30339

~

t l

l l

i a 4- , . , . . -n, ,- --,- .a,-

s 4

- FINAL REPORT - DER '84-21 .

DEFICIENCY EVALUATION 50.55(e)= .l ARIZONA PUBLIC SERVICE COMPANY (APS)-

PVNGS UNITS 1, 2,'3- i 1

I. Description ~of Deficiency During a routine site audit,'the following discrepancies'between design drawings and "as-built" configurations were noted:

j; A. Combustion Engineering '(C-E) Drawings N001-13.01-727 and -728

. specify 300 series stainless steel instrument-to-bracket mounting hardware for Rosemount/Barton transmitters supplied by C-E.E NCR l SJ-3712 documents the use in Unit 1 of numerous carbon steel nuts and bolts having no' grade markings andl strong magnetic properties.

B. Bechtel Drawings 13-J-ZZS-161, -162, -165, -166, -167, -168,

-174, and -178 specify ASTM A193, CL2 and GRB8 bracket-to panel mounting nuts and bolts'for certain Rosemount/Barton l o transmitters. fNCR SJ-3713 documents nuts without proper marking.

. on many transmitter installations in Unit 1.

Following the initial routine site audit,'an extensive walkdown was j done in Units 1 and 2.

, Evaluation l The subject transmitters measure pressure, level, and flow rates in several safety-related systems. (LPSI pump A discharge flow, reactor coolant system pressure, steam generator level and MSIV hydraulic accumulator pressure). Specific tag numbers for transmitters'are

, identified in referenced SFRs and NCRs.

These instruments require mounting hardware of specific grade i- material, along with proper documentation and identification mark t'o i permit traceability. Also, the installation of these' transmitters should strictly adhere to mounting procedures and detail inspection and acceptance codes.

]

In the event of a DBE, instruments not properly mounted could become disengaged and not perform their intended safety function.

The root cause for the deficiencies described herein is the craf tsmen's failure to properly install the instruments and the l failure of field engineers and quality control to identify the use of

- improper materials.

l

! II. ' Analysis of Safety Implications Based upon the above, this condition is evaluated as reportable under.

j.

-10CFR50.55(e); since, if left uncorrected, it could represent a significant safety hazard.

L-This condition is evaluated as not reportable under.10CFR Part 21 -

, - since it.does not constitute a defect in a basic component.

.,,w-- y.-+= * ,e rv- m-w-- -

e- w-e-y--- 't,-~w-v- - - - - - - -+ -,e-- - -- - w-w-, -

3- -ww, -- = rwem - - e w--e-

1 4

i Final Report ,

DER 84-21 Page Two-i.

3 ' III. Corrective Action In Units 1 and 2 mounting hardware (bolts and nuts) were replaced to

~

' conform with material and installation requiremetits. In certain cases, the vendor (C-E) advised that specific installed hardware were an acceptable . substitute (e.g. , carbon steel in lieu of 300 series stainless steel). Where this occurred, the vendor prints were revised (see referenced FCR) .to reflect the alternate acceptable material. The above corrective action will be implemented and' documented by referenced SFRs/NCRa 1ist in Section IV.' - A definitive

~

list of the affected Rosemount/Barton transmitters is given in

Section IV. ,

Specific instructions (IOM-E-11465) have been issued to Construction to assure proper installation and preclude recurrence of this deficiency in Unit 3. - Also, a walkdown of 26 sample Q-class installations per unit is being done per Project Valide.cion of Q '

Instrument Procedure No. 5.26-08 to further assure that other Q-class installations are installed per the requirements of the design documents.

Recognizing the need to address the generic implications of improper

Q-Class instrumentation installations, the ANPP has initiated a l comprehensive review of Q-Class instrumentation deficiencies. This
review will evaluate Q-Class instrumentation installations to provide
assurance that Q-Class instruments are installed per the requirements
of applicable design documents. The scope of the evaluation and the results, including the sample walkdown conducted above, will be included in the final report for DER 84-27.

IV. References (1) SFRs/NCRs

- NCR No. SJ-3712 3713 4618 4619 SFR 2SE-3082/NCR SJ4688 SFR 2EC-3083/NCR SJ4689 SFR 2SB-3084 -

SFR 2SB-3085 -

l l

l

=

= ,s+- w.

9- p- - ,.- --W-3..,. we, =p.g- - g . -c.p-+ e,- + q m,.g,,-.w.. m , 4 .-,m -

-- - N

e.< (.g. ,

i Final Report DER 84-21 v

Page Three (1) SFRs/NCRs (continued)

SFR 2SB-3086 -

SFR 2RC-3087/NCR SJ4690 SFR 2CH-3088 -

SFR 2CH-3089/NCR SJ4691 S FR' 2RC-3090/NCR SJ4692 SFR 2RC-3091 -

SFR 2RC-3092/NCR SJ4693 SFR 2SI-3093 -

SFR 2EW-3094/NCR SJ4694 SFR 2SB-3095/NCR SJ4695 SFR 2NC-3096/NCR SJ4696 SFR 2CT-3097/NCR SJ4697 SFR 2EG-3098/NCR SJ4698 SFR 2AF-3099/NCR SJ4699 (2) Correspondence C-E Letter IV-CE-30018 April 2,1984 IOM E-11465 September 19, 1984 MOC #333342 Letter B/ANPP-E-122970 October 12, 1984 (3) FCRs 78,677N 82,609N (4) Rosemount/Barton Transmitter Listings

- (A) Rosemount/Barton Transmitter Listings HPB FT-502 AFB FT-041A HCA PT-353A SGA PT-229 AFB FT-041B HCB PT-353B SGB PT-230 CHA LT-200 SGA PT-308 SGA PT-231 CHB LT-201 SGA PT-315 SGB PT-232 CHA LT-203A SGB PT-321 SGB PT-234 CHB LT-203B AFB PT-017 SGA PT-235 CHC LT-203C AFB PT-018- '

SGB PT-236 CTA LT-035 CHA PT-212 ECA LT-015 CTB LT-036 RCB PT-138 ECB LT-016 FWA FT-013 RCA PT-190A SIB FT-309 FWB FT-014 RCB PT-190B ECA FT-533 FWA FT-151 RCC PT-105 ECB FT-534 FWA FT-152 RCD PT-106 EWA LT-091 SIA FT-306 RCA PT-199A EWB LT-092 SIB FT-307 RCB PT-199B NCA FT-474 SIA FT-308 RCC PT-199C NCA FT-475 SIB ~FT-348 RCD PT-199D NCA FT-476 SIA LT-704 CHB FT-212

eo' ;e, d

Final Report DER 84-21 Page Four 4

(A) .Rosemount Transmitters (continued)

NCA FT-477 SIB LT-705 - SIB FT-311 NCB FT-494 HCA PY-351A SIB FT-321 NCB FT-495 HCB PT-351B SIA FT-331-

- NCB FT-496 HCC PT-351C SIA FT-341 NCB FT-497 HCD PT-351D SIA FT-390 SIB LT-344 HCA PT-352A SIB FT-391 SIA LT-345 HCB PT-352B SIB LT-348 HCC PT-352C SIA LT-349 HCD PT-352D SPA FT-005 PCA PT-009 SPB FT-006 PCB PT-010 AFA FT-040A SGB PT-306 AFA FT-040B SGA PT-313 (B) Barton Transmitters CHA PT-268 RCA PDT-125A RCA PT-101A RCB PDT-125B RCB PT-101B RCC PDT-125C RCC PT-101C RCD PDT-125D RCD PT-101D SGA LT-1113A RCA PT-102A SGB LT-1113B RCB PT-102B SGC LT-1113C RCC PT-102C SGD LT-1113D RCD PT-102D SGA LT-1114A SGA PT-1013A SGB LT-1114B SGB PT-1013B SGC LT-1114C SGC PT-1013C SGD LT-1114D SGD PT-1013D SGA LT-1123A SGA PT-1023A SGB LT-1123B SGB PT-1023B SGC LT-1123C SGC PT-1023C SGD LT-1123D SGD PT-1023D SGA LT-1124A SIB PT-311 SGB LT-1124B SIB PT-313 SGC LT-1124C SIB PT-321 SGD LT-1124D SIB PT-323 SIB LT-311  ;

SIA PT-331 SIB LT-321 SIA PT-333 SIA LT-331 SIB PT-341 SIA LT-341 SIA PT-343 j RCA LT-110X  :

RCB LT-110Y RCA PDT-115A RCB PDT-115B i RCC PDT-115C RCD'PDT-115D