ML20081D324

From kanterella
Revision as of 22:18, 20 April 2020 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Proposed Changes to Tech Spec 15.3.1.A Eliminating Provisions Beyond Basis for Required Operational RCS Components
ML20081D324
Person / Time
Site: Point Beach  NextEra Energy icon.png
Issue date: 10/25/1983
From:
WISCONSIN ELECTRIC POWER CO.
To:
Shared Package
ML20081D313 List:
References
TAC-52663, TAC-52664, NUDOCS 8311010140
Download: ML20081D324 (1)


Text

. . .-

15.3 LIMITING CONDITIONS FOR OPERATION 15.3.1 REACTOR COOLANT SYSTEM Applicability l Applies to the operating status of the Reactor Coolant System.

Obj ective To specify those limiting conditions for operation of the Reactor Coolant System which must be met to ensure safe reactor operation.

Specification A. OPERATIONAL COMPONENTS

1. Coolant Pumps *
a. At least one reactor coolant pump or the residual heat removal system shall be in operation when a reduction is made in the boron concentration of the reactor coolant.
b. When the reactor is critical and above 1% of rated power except for natural circulation tests, at least one reactor coolant pump shall be in operation.
c. (1) Reactor power shall not be maintained above 10% of rated power unless both reactor coolant pumps are in operation.

(2) If either reactor coolant pump ceases operating, immediate power reduction shall be initiated under administrative control as necessary to reduce power to less than 10% of rated power.

2. Steam Generator
  • a.

l One steam generator shall be operable whenever the average reactor coolant temperature is above 350*F.

3. Components required for Redundant Decay Heat Removal Capability *

' l

a. Reactor coolant temperature less than 350*F and greater than 140*F.

l (1) At least two of the decay heat removal methods listed shall be operable. I l

(a) Reactor Coolant Loop A, its associated steam generator and either reactor coolant pump (b) Reactor Coolant Loop B its associated steam generator and either reactor coolant pump Applicable only when one or more fuel assemblies are in the reactor vessel.

8311010140 831025 15.3.1-1 p DR ADOCK 05000266

PM i