Responds to IE Bulletin 83-01, Failure of Reactor Trip Breakers (Westinghouse DB-50) to Open on Automatic Trip Signal. Preventive Maint Performed Each Refueling Outage & Bulletin Is Required Reading for Operators
ML20071D531
Person / Time
Site: Ginna Constellation icon.png
Issue date: 03/04/1983
From: Maier J
ROCHESTER GAS & ELECTRIC CORP.
To: Haynes R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
REF-SSINS-6820 IEB-83-01, IEB-83-1, NUDOCS 8303110217
Download: ML20071D531 (2)


Text

-

e :s

\

]

' p n ?; "!

n:7-'

"l gy;. n.a .

R6F ll 3 - ..

'wni ROCHESTER GAS AND ELECTRIC CORPCRATION

  • 89 EAST AVENUE, ROCHESTER, N.Y.14649 JOHN E MAIER ve t t aw ow
w. ruwwre aae 4 coes me 5-16-2700 March 4, 1983 Mr. Ronald C. Haynes, Regional Administrator U. S. Nuclear Regulatory Commission Region I 631 park Avenue King of Prussia, PA 19406

Subject:

IE Bulletin No. M b.3L - . .

Failure of Reactor Trip Breakers (Westinghouse DB-50)

To Open on Automatic Trip Signal.

R. E. Ginna Nuclear Power Plant, Unit No. 1 Docket No. 50-244

Dear Mr. Haynes:

8 3 -@J.

In response to NRC IE Bulletin No. AbEftT, Failure of Reactor Trio Breakers (Westinghouse DB-50) to open on Automatic Trip Signal, for item 4a, the undervoltage trip function, independent of the shunt trip, for the reactor trip breakers was successfully tested on 2/26/83. Proper breaker operation also occurred on

12/11/82 when breakers were intentionally tripped during NBFD relay testing, and again on 1/17/83 when a reactor trip occurred as a result of Low S/G Level and Steam Flow > Feedwater Flow mismatch.

In response to item 4b of the subject bulletin, Ginna Station l Maintenance performs preventive maintenance on the Reactor Trip

( Breakers each refueling outage. This maintenance conforms to l the Westinghouse recommended program with the exception of lubricat-ion. Ginna maintenance supervision is f amiliar with DB-50 breaker failures that led to Westinghouse 1974 policy change on the use of lubricants, and has concluded that the frequency of operation of our breakers does not warrant the use of lubricants that could attract dust and dirt, and prevent the breakers from operating properly. The current Ginna Station Breaker Maintenance program has orevented the oroblems that some other plants have experienced.

l 0303110217 830304 ~~ '.

PDR ADOCK 05000244 0

i

' f6 PDR / V-

3 In response to item 4c of the subject bulletin, each licensed operator upon his arrival on shift is being required to read IE Bulletin No. 83-01, In addition, all non-licensed operating personnel and licensed plant staff are being asked to read IE Bulletin No. 83-01 and acknowledge on a separate signoff sheet.

Very truly yours,

'rk,tAMrn t

T E. Maier Document Control Desk (1)

Subscribed and sworn to me on this 4th day of March 1983.