LER 80-026/03L-0:on 801011,emergency Diesel Generator 1/2 Tripped.Caused by Short in Motor of Diesel Generator Cooling Water Pumps.Motor Replaced w/shop-tested,used Motor. Shorted Motor Will Be Repaired & Reinstalled
ML19340C121
Person / Time
Site: Quad Cities Constellation icon.png
Issue date: 10/29/1980
From: Steffes C
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML19340C117 List:
References
LER-80-026-03L-03, LER-80-26-3L-3, NUDOCS 8011140019
Download: ML19340C121 (2)


Text

. -- . _.

- . __ .

NRC FORS%8 U. S. NUCLEAR REGULATORY COMMISEION 1747b LICENSEE EVENT REPORT CONTROL BLOCK: l i

l l l l l lh e

(PLEASE PRINT OR TYPE ALL REQUIREO INFORMATIOM jo lij 8ll9l L l LICENSEE 7

Q l A CCDE lD l 1,14lgl15 0 l 0 l 0 l -LICENSE l 0 l NUMsER 0 l 0 l - l 0 l 0 l250 l@l 26 4lLICENSE 1l1 lITYPE l 1J0l@l$7 GAl T $dl@

CON'T

~ l ') I 1 1 g lL l@l 0l 5 l 0 l 0 l 0 l 2 l 5 l 4 l@l 1 l 0 l 1 l1 l 8 l 0 l@l 11 01 74 75 2l 91 8l Ol@

REPORT QATE 30

'

8 60 61 OOCKET NUYSER ed 6W EVENT CATE EVENT DESCRIPTION AND PROBABLE CONSECUENCES h I o 12 ] l The 1/2 Energency Olesel Generator tripped from high engine temperature af ter i l hoer and 50 minutes of testing because the 1/2 Diesel Cooling Water Pump tripped.

~

,o,3, l

, o i,; l The Consequences were minimal because the Unit I and Unit 2 Diesel Generators, Core g gg Spray and all modes of the RHR ystem were demonstrated ooerable as required by  ;

g a ;g y l Technical Specif! Cation 3 9.E. l 10171I I I

l o la l i 30 7 8 9

"

E CCCE SUSC E COMPONE NT CODE SL,9 C CE SU E lo19] lE lE l@ yh l A l@ lM l0 lT l0 lR lX lh W@ W @

9 10 11 12 13 id 19 20 7 6

,,. SE QUENTI AL OCCU R R E NCE RE*CRT REVISION EVENT YEAR REPORT NO. CODE TYPE NO.

O ,"gg" g*Tno u'i .3E R l8l0l l-l l0 l2 l6 l l/l l 0l 3 l lL l l-l l0l

_ 21 22 23 24 26 27 28 29 JJ 31 32

'

K N A ON C PL NT ME HOURS 22 SS if POR ! 8. S PP IE MAN F C RER IJJ A l@[0 jg .,,_

34 lZg 35 lZl@

08

[ 0 l0 l0 lU l 31 40 lYl@

41 l42Y l@ l43N l@ l44G l 0 l 8 l 047 l@

CAUSE OESCRIPTION AND CCRRECTIVE #CTIONS lt loll The motor for the 1/2 Diesel Generator Cooling Water Pumo was found to have a l li li j i short. The motor was replaced with a shoo tested used motor. The shorted motor I it i ,i l will be repaired and reinstalled. l L! j.J ] I I t i l41 1 I 7 a 2 ao ST U$  % POWER OTHER STATUS 015 O RY DISCOVERY DESCRIPTION 11 15l W Q l0l0l0lgl NA l l A lgl Operational Event l ACTIVITY CCPTENT REttAsEo oP RELEASE LOCATION OP =ELEASE @

L1_.[6 ] [ 0 J g [_Zjgl AMOUNT NA or ACriviTv l hl NA l 7 89_ tJ tt 4.4 45 80 PERSONNEL EXPOSURES NUMBER CESCRIPTION LiLJl01010l@l

' ' '

TYPE l

@l

  • I PEpsoNNEL is;u'4 Es Nu.m R oEsCRiPTiON@

f i j y l l 0 l 0 l 0 l@l NA l 7 8 9 11 12 80 LOSS OF OR nAMAGE TO FACILITY TvPE DESCRePfeON NA l l : l 94l >l Z l@lm

, .o

" * NRC USE CNLY ,

.ssu t-12 l a l l N [@oE[CRiPTiON@

l _

NA l Sa llllllllll 1! l}

.9 so. ;

7 g i11()01U Curt Steffes 309-654-2241, ext. 175 o NAME OF PREP AnEn PHONE: j

-, , .

.

o #

l. LER NUMBER: LER/R0 80-26/03L-0
11. LICENSEE NAME: Commonwealth Edison Company Quad-Cities Nuclear Power Station 111. FACILITY NAME: Unit One IV. DOCKET NUMBER: 050-254 V. EVENT DESCRIPTION:

On October 11, 1980, Unit One was in the REFUEL Mode and Unit Two was operating at 815 MWe and 2489 MWt. At 4:12 a.m. the 1/2 Diesel Gen-erator tripped from high engine temperature af ter running for one hour and fifty minutes. The 1/2 Diesel Generator Cooling Water Pump was found tripped. In acco.-dance with Technical Speci fication 3.9.E. ,

the Unit One and Unit Two Diesel Generators were tested immediately and all of the low pressure core cooling and both loops of the containment cooling mode of the RHR system associated with the Unit Two Diesel Gen-erator were demonstrated to be operable. The 1/2 Diesel Generator Cooling Water Pump motor was replaced. The 1/2 Diesel Generator was tested successfully and returned to service on October 12, 1980.

VI. PROBABLE CONSEQUENCES OF THE OCCURRENCE:

The 1/2 Diesel Generator provides a standby power supply to Bus 23-1 which feeds Core Spray Pump 2A and RHR Pumps 2A and 28. The Unit Two Diesel Generator was demonstrated to be operable as were the redundant 2B Core Spray Pump and 2C and 2D RHR Pumps. The requirements of Technical Specification 3.9.E. were satisfied, therefore, the con-sequences of the occurrence were minimal.

Vll. CAUSE:

The motor cn the 1/2 Diesel Generator Cooling Water Pump was found to have a short which caused the pump to trip. This led to high engine temperature in the Diesei Generator. The motor is manufactured by General Electric, Model No. SK365AK169 Vlli. CORRECTIVE ACTl0J1:

On October 12, 1980, the 1/2 Diesel Generator Cooling Water Pump motor was replaced temporarily with a like used motor that was shop tested prior to installation. The failed motor is to be rebuilt and re-installed.