RO-80-19:on 800124,during Equipment Qualification Review for IE Bulletin 79-01,qualification Discrepancy Discovered in Svc Water Radiation Pumps for Recirculation Spray Heat Exchangers.Cause Unknown
ML19270K264
Person / Time
Site: North Anna Dominion icon.png
Issue date: 01/25/1980
From:
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
References
IEB-79-01, IEB-79-1, NUDOCS 8002040544
Download: ML19270K264 (1)


Text

,

E%D/Ly gpw~

Us" = n Virginia Electric acd Pchar Ccgany U,%"

""L&w k  %

2;g 1larth Anna Pc;ar Statica, Unit il r 3 ?x DccletNo.50-338

.

m

} .,

-

24 Hour Repcrtable Evant ,

u &

WrittenFolltw4p .

.'

-

, Event: Radiation blificatica of Service Eter Radiatica Penitoring SaglePugs .

LER$0 80-1g/01T-0 Euring review of equiprent qualificatica for IE Bulletin 79-01, the service water radiatica ccnitoring puys for the recirculation spray heat exchangers (1-Sk'-P-5,6,7 and 8) were found not to te qualified for the integrated radiatian dose to which they cculd:te exposed to follcuing a postulated accident. -.

.

- '

The cause of'this discrepar.cy is not kr.ca at this time.

-

,. .

The feasibility of installing shielding arcund the pu ps is heing investigated. Passible prp relccation is also feing considered.

. -

. .

.

_

_

There has teen no effect on the cperatica of the plant as a result of this discrepancy. Continued operation is justified because the pups da not parfara an accidant nitigaticn'functica but act as a part of a

.

manitoring circuit.- :0ther radiatica ranitors :(Fit-SW108 and 109) are available to raattor activity in the service water systeri and by alternate-ly valving out recirculation spray heat exchangers they could te used to datemine kheiher a specific Eeat exchanger fs leaking. Inadditica, local sarples could'te taken at'each of thste ncaitors for analysis.

The present)lant status is 13% rated tEartal pcWer to acccalish a stean generatar secondary side scaE.

.

.

'

. (j Y6

\

.

-

3 8002040 [ y y