ML19268C171

From kanterella
Jump to navigation Jump to search
Supplements RO 79-141/01T-0:while Reviewing Operation of Secondary Ventilation Sys,Sys Discovered to Operate in Manner Not in Keeping W/Accident Analyses.Cause Unknown. Matter Under Review
ML19268C171
Person / Time
Site: North Anna 
Issue date: 11/27/1979
From:
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
References
NUDOCS 8001030599
Download: ML19268C171 (1)


Text

_.

d "i

Virginia Electric ar.d Power Company i

North Anna Power Station, Unit fl. WPF-4

.n a n.,

l Docket No. 50-338

'.,'., " - l

~ ' '

jI 24 Hour Reportable Event 11 Written Policw-Up (supplament)

12.,/ 27 P d,' 4 9 Event:

ISF Systans Returuing to Non-Safety Mode Upon Reset of Actuation Signal 1.IR/E0 79-141/01T-0 While teviewing the operation of the secondary ventilation system, it was discovered that the system operates in a manner less conservative than that assured in the accident analyses in the uafety analysis report.

Specifically, following the receipt of a Hi-Hi radioactivity signal l

fron the air eject.or radiation s.onitor (RM-SV121) the air tasoval systen diverts air to the containzant (TV-SV102-1 and TV-SV103).

In this condition a containment isolation signal will close these valves.

When the contain ant isolation signal is roast, while the Hi-81 radiation signal is present, these l

valves will reopen, This is not consistant wi!.h FSAR Coc=ent 7.4.

The cause of this discrepancy is not known.

This discrepancy has

[

cet affected the plant and is under review by the engineering staff.

The ij plant is presently in a refueling shutdown.

This event is similar to l'

L12/R0 79-141.

An awndment to LER/RO 79-141 will be submitted within the 14 day reporting requirement of this report.

j i L P. 0 RtiLLY

'N

> ll, M. U tiGMT y R. D. CHENDtut 3, 4. KEANA

.E 3. LONG

& L NURPHY i'

T. SUTHERLAND h)SECLA,RL k

.?-

{$%*

cc 8001030