ML19290C683

From kanterella
Jump to navigation Jump to search
RO 80-02/01T-0:during Review Required by IE Bulletin 79-14, Stress Discovered Over Design Allowable on Pipe Hangers & Snubbers.Caused by Incorrect Valve Weights Used in Design Calculations.Hangers & Snubbers Will Be Modified
ML19290C683
Person / Time
Site: North Anna 
Issue date: 02/04/1980
From:
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
References
IEB-79-14, NUDOCS 8002040554
Download: ML19290C683 (1)


Text

  • i

__ -,m

_o.

--s--

.e.

I' f ] {1 Yirginia Electric and Pcwah Co:panyO ~ ?. 5 s n ~ t North Anna Pcher Statica. Unit 11. 'NPF-4 { Dccket No. 50-338 1' I 24 ifaur Reportable Event. k Eritten Fo11cw Up 1 Event: Nonconfornances in Pipe. Support' Design l 1.ER/R0 80-02/01T-0 ' l During the review. required by IE Bulletin 79-14. of sets.nic' analyses for as-built safety related piping systems. Stone & liebster discovered the stress an pipa hangers RH-R-19 and liS-R-316 and snubters SI-HSS-1018.101C. and 107A to he over design allevable. These nonconformances affect the suction and discharge of the'RRR pu::.ps the discharga of "B" SI accumula-tar, and the service watar makeup line from the screen wash ptaps. -s The pipa supports are o' erstressed because incorrect valve wights v w re used in the design calculations. There has been no affect on the plant as a result of these discrepancies. The hangers and sr.iJhhers will. ha modified or reinforced a,s required. The unit'is presently in Mode 5 folicwing a refueling shutdcwn. ,!.-g \\ a. a .t g, L ucRPtif

s

{ k T. SUTHEM g L N. W 3 ,s. k ai R l I k ~., 4 h r,c e. s m [ 4 .h y lf N 1 1 4 f i k '.4 00 ID } i 4

u I

2}}