Text
,
E%D/Ly gpw~
Us"
=
n U ""L&w k
Virginia Electric acd Pchar Ccgany 3
2;g 1larth Anna Pc;ar Statica, Unit il r
?x DccletNo.50-338
}
24 Hour Repcrtable Evant m
u WrittenFolltw4p Event:
Radiation blificatica of Service Eter Radiatica Penitoring SaglePugs LER$0 80-1g/01T-0 Euring review of equiprent qualificatica for IE Bulletin 79-01, the service water radiatica ccnitoring puys for the recirculation spray heat exchangers (1-Sk'-P-5,6,7 and 8) were found not to te qualified for the integrated radiatian dose to which they cculd:te exposed to follcuing a postulated accident.
The cause of'this discrepar.cy is not kr.ca at this time.
The feasibility of installing shielding arcund the pu ps is heing investigated.
Passible prp relccation is also feing considered.
There has teen no effect on the cperatica of the plant as a result of this discrepancy. Continued operation is justified because the pups da not parfara an accidant nitigaticn'functica but act as a part of a manitoring circuit.- :0ther radiatica ranitors :(Fit-SW108 and 109) are available to raattor activity in the service water systeri and by alternate-ly valving out recirculation spray heat exchangers they could te used to datemine kheiher a specific Eeat exchanger fs leaking.
Inadditica, local sarples could'te taken at'each of thste ncaitors for analysis.
The present)lant status is 13% rated tEartal pcWer to acccalish a stean generatar secondary side scaE.
(j Y6
\\