ML19209C442

From kanterella
Revision as of 11:16, 15 August 2019 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
LER 79-102/03L-0:on 790911,bistable for Containment high- Risk Pressure Channel I Actuated High Pressure Signal & Failed in Low Pressure State During Test.Caused by Bad Signal Comparator Card.Defective Card Replaced & Calibr
ML19209C442
Person / Time
Site: North Anna Dominion icon.png
Issue date: 10/11/1979
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19209C435 List:
References
LER-79-102-03L, LER-79-102-3L, NUDOCS 7910150568
Download: ML19209C442 (2)


Text

/C FORM 366 U. S. NUCLE AR REGULATORY COMMISSION r/.77)LICENSEE EVENT REPORT CONTROL atOCie l llllll@(PLE ASE PRINT OR TYPE ALL REQUIRED INFORMATION) lo lil l Vl ^l Nl Al Sl 1 l@l 0 l 0 l - l 0 l 0 l 0 l 0 l 0 l- l010 l@l4 l1 l1 l1 l1 l@l ll@7 8 9 LICENsis COaE 14 15 LICENSE NuvdeH 23 26 LectNSE TYPE JO 57 L A T bd CON'T ,g l L lg[ 0 l 5 l 0 l 0 l 0 l 3 l 3 l 5 l@l 0 l 9 l 1 l 1l7l9l@l1 ln l 111 17 lq l@

R O i/8 w 61 DOCKET NUYdEH f,d O'J LVENT DATE i .4 7')HEPOH T D AT E B0 EVEN T DESCP!PTION AND PROB ABLE CONSEQUENCES O'o l On September 11, 1979, the bistable for Containment High-High Pressure Channel I 1 O 2 i actuated on a high pressure signal and failed in tSc low pressure state during the lo 3[ perforcance of the monthly surveillance test. Since Containment High-High Pressure l0., Channels II, III, and IV remained operable to initiat.e a CDA if required, the health l0 s;O g i l and safety of the general public were not af fected . by this event.

Reportable lFOT77 l pursuant tO T.S. 6.9.1.9.b.

l!l.O<CE CODE SUSCO E COVPONENT CODE SUBC DE SU ODElO191 II I Bl@ dj@ LGj@ lI lN lS lT lR lU l@ O@ [Zj @

7 8 9 10 11 12 13 18 19 20,.SEQUE NTI AL OCCURRENCE REPORT REVISION LERRO EVENT YEAR REPORT NO.

CODE TYPE NO.@ sV,Pgr[7 l9 I l--- J l 11 0] 21 l/l 10 l3 lLll-ll0la6 ,21 22 23 24 26 21 28 29 JJ 31 J2 TAKEN A T N ON PL NT iT HOUHS 22 S$3YT'T D FO 95 8.SUPPLIE MAN FACTURER lClg g g Z lgl36 Zl@l0 l0 [0 lU l lYl@N l@lA l@l Wl l! 2 l 0l@

33 34 J 3/40 41 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h iiiO; l The bistable for Containment High-High Pressure Channel I failed because of a bad gisii signal comparator card. The channel was left in the blocked condition and the il defective comparator card was replaced. The new card was then calibrated, the loop , , i, 3i l functionally tested and the channel returned to the normal condition.

l11 1411*8 9 80 ST S% POWER OTHER STATUS iSCOV RY DISCOVERY DESCRIPTION li l5 l l El@ j 0 8l6l@

NAlBl@l Surveillance Test ACTIVITY CG TENT RELEASED OF RELE ASE AVOU.<T OF ACTIVITY LOCATION OF RELE ASE L.ZJ @ LZJ@i NA NA l i 6 7 8 9 10 It 44 45 80 PERSONNEL EXPOSURES NUVRE R TYPE D ESCR:PTION '

y 1010l Ol@l Zl@l NAl*'" ',ERSONNELmuns OESCRiPriON@

NoveERlfiTT1 10 0 Ol@l NA. .]}h ,-,lh]80 7 8 9 11 12 LOSS OF OR DAMAGE TO FACILITY Q TYPE DE SCRIP TION

%./l Zl@l NA i 9 7 8 9 10 80 PUBLICITY NRC USE ONLY

'e?7910150 5e#

l NAll1 I I I I I I I I I I :I l 2 l o l [_ N_j@DESCRIPI'iCN

'tsSUED 7 8 9 10 68 b9 80 ;W. R. Cartwright 703-894-5151 2 pa o ne.NAVE OF PR PAHER Virginia Electric and Power Company North Anna Power Station, Unit #1

Attachment:

Page 1 of 1 Docket No. 50-338 Report No. LER 79-102/03L-0 Descriction of Event On September 11, 1979, curing Mode 1 operation at 86L power, the bistable for Containment High-High Pressure Channel I actuated on a high pressure signal and failed in the low pressure stde during the performance of the monthly surveillance te:t.

The channel was left in the blocked condition and declared inoperable.

Probable Consequences of Occurrence The consequences of this event were limited because Contair. ment High-High Pressure Channels II, III and IV remained operable to initiate a Containment Depressurization Actuation if required. As a result, the public health and safety were not jeopardized by this event. This occurrence has no generic implications affecting Unit 1 and Unit 2 instrumentation.

_Cause of Occurrence The bistable for Containment High-High Pressure Channel I failed because the signal comparator card was defective. The failure was not the result of a W-104 component problem.

Immediate Corrective Action Containment High-High Pressure Channel I was left in the blocked condition and signal comparator card PS-LM100A-3 was replaced. The new card was then calibrated, the loop functionally tested, and the channel returned to the normal condition.

Scheduled Corrective Action No scheduled corrective action is required.

Actions Taken to Prevent Recurrence No further actions are required.

1145 355