ML15016A439: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(StriderTol Bot change)
 
Line 2: Line 2:
| number = ML15016A439
| number = ML15016A439
| issue date = 01/20/2015
| issue date = 01/20/2015
| title = Draft Request for Additional Information (TAC Nos. MF2942 and MF2943)
| title = Draft Request for Additional Information
| author name = Whited J
| author name = Whited J
| author affiliation = NRC/NRR/DORL/LPLI-2
| author affiliation = NRC/NRR/DORL/LPLI-2

Latest revision as of 15:46, 19 March 2020

Draft Request for Additional Information
ML15016A439
Person / Time
Site: Beaver Valley
Issue date: 01/20/2015
From: Jeffrey Whited
Plant Licensing Branch 1
To: Meena Khanna
Plant Licensing Branch 1
Whited J
References
TAC MF2942, TAC MF2943
Download: ML15016A439 (4)


Text

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 January 20, 2015 MEMORANDUM TO: Meena K. Khanna, Chief Plant Licensing Branch 1-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation FROM: Jeffrey A. Whited, Project Manager ~-/ UPr)

Plant Licensing Branch 1-2  :?"'"7"

  • Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation

SUBJECT:

BEAVER VALLEY POWER STATION, UNITS 1 AND 2, DRAFT REQUEST FOR ADDITIONAL INFORMATION (TAG NOS. MF2942 AND MF2943)

The enclosed draft request for additional information (RAI) was transmitted on December 12, 2014, to Mr. Phil Lashley of FirstEnergy Nuclear Operating Company (FENOC, the licensee).

This information was transmitted to facilitate a conference call in order to clarify the licensee's amendment request for Beaver Valley Power Station (BVPS), Units 1 and 2 dated October 18, 2013. The proposed amendment would modify the BVPS Technical Specifications by relocating specific surveillance frequencies to a licensee controlled program with the implementation of Nuclear Energy Institute (NEI) 04-10, "Risk-Informed Technical Specifications Initiative Sb, Risk-Informed Method for Control of Surveillance Frequencies."

The draft RAI was sent to FENOC to ensure that the questions are understandable, the regulatory basis for the questions is clear, and to determine if the information was previously docketed. This memorandum and the enclosure do not convey or represent an NRC staff position regarding the licensee's request.

Docket Nos. 50-334 and 50-412

Enclosure:

Draft RAI cc w/encl: Distribution via Listserv

DRAFT REQUEST FOR ADDITIONAL INFORMATION OFFICE OF NUCLEAR REACTOR REGULATION REQUEST FOR ADDITIONAL INFORMATION RELATED TO AN AMENDMENT TO ADOPT TECHNICAL SPECIFICATIONS TASK FORCE TRAVELER TSTF-425 TO RELOCATE SPECIFIC SURVEILLANCE FREQUENCIES TO A LICENSEE CONTROLLED PROGRAM BEAVER VALLEY POWER STATION- UNITS 1 AND 2 DOCKET NO. 50-344 AND 50-412 By letter dated October 18, 2013, 1 as supplemented by letters dated June 26, 2014, 2 and September 21, 2014, 3 FirstEnergy Nuclear Operating Company (the licensee) submitted a license amendment request for Beaver Valley Power Station (BVPS) Units 1 and 2. The proposed amendment would modify the BVPS Technical Specifications by relocating specific surveillance frequencies to a licensee controlled program with the implementation of Nuclear Energy Institute (NEI) 04-10, "Risk-Informed Technical Specifications Initiative 5b, Risk-Informed Method for Control of Surveillance Frequencies," (TSTF-425). To complete its review, the Nuclear Regulatory Commission staff requests a response to the question below.

BACKGROUND The licensee's current TS SR 3.3.2.6 is associated with the Engineered Safety Features Actuation System (ESFAS) instrumentation. The surveillance requires that Slave Relay Test shall be performed once every 18 months for Unit 1 and once every 92 days for Unit 2 operations, OR for Unit 2 only once every 12 months per a NOTE in the surveillance frequency which states, "Only applicable to Unit 2 provided a satisfactory contact loading analysis has been completed, and a satisfactory slave relay service life has been established, for the slave relay being tested."

The licensee's proposed change as shown on TS page 3.3.2-6 in Attachment 2 of the application relocates the SR 3.3.2.6 frequency to the licensee's SFCP.

1 Agencywide Documents Access and Management System (ADAMS) Accession No. ML13295A006.

2 ADAMS Accession No. ML14177A514.

3 ADAMS Accession No. ML14265A158.

Enclosure

DISCUSSION The staff noticed that NOTE in SR 3.3.2.6 frequency is a specific condition to BVPS Unit 2 operations only. It is a frequency that is related to specific conditions or conditions for the performance of the surveillance requirement. As such, it is an exception to the SFCP.

Therefore, the surveillance frequencies and associated NOTE for Unit 2 operations need to be retained in TSs.

RAI8:

Please submit revised TS page for SR 3.3.2.6 change, otherwise submit a request for NRC permission to remove the condition with applicable justification for the NRC staff's review and approval.

Regulatory Basis The regulations under 10 CFR 50.36 (c)(2)(i) state that Limiting Conditions for Operation are the lowest functional capability or performance levels of equipment required for safe operation of the facility (emphasis added). When a limiting condition for operation of a nuclear reactor is not met, the licensee shall shut down the reactor or follow any remedial action permitted by the TSs until the condition can be met.

January 20, 2015 MEMORANDUM TO: Meena K. Khanna, Chief Plant Licensing Branch 1-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation FROM: Jeffrey A. Whited, Project Manager IRA/

Plant Licensing Branch 1-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation

SUBJECT:

BEAVER VALLEY POWER STATION, UNITS 1 AND 2, DRAFT REQUEST FOR ADDITIONAL INFORMATION (TAC NOS. MF2942 AND MF2943)

The enclosed draft request for additional information (RAI) was transmitted on December 12, 2014, to Mr. Phil Lashley of FirstEnergy Nuclear Operating Company (FENOC, the licensee).

This information was transmitted to facilitate a conference call in order to clarify the licensee's amendment request for Beaver Valley Power Station (BVPS), Units 1 and 2 dated October 18, 2013. The proposed amendment would modify the BVPS Technical Specifications by relocating specific surveillance frequencies to a licensee controlled program with the implementation of Nuclear Energy Institute (NEI) 04-10, "Risk-Informed Technical Specifications Initiative 5b, Risk-Informed Method for Control of Surveillance Frequencies."

The draft RAI was sent to FENOC to ensure that the questions are understandable, the regulatory basis for the questions is clear, and to determine if the information was previously docketed. This memorandum and the enclosure do not convey or represent an NRC staff position regarding the licensee's request.

Docket Nos. 50-334 and 50-412

Enclosure:

Draft RAI cc w/encl: Distribution via Listserv DISTRIBUTION:

PUBLIC SGursharan, NRR/DE/EICB LPL 1-2 R/F RGrover, NRR/DSS/STSB RidsNrrDoriLpl1-2 Resource RidsNrrDoriDpr Resource RidsNrrPMSusquehanna Resource ACCESSION NO.: ML15016A439 OFFICE LPL 1-2/PM NAME JWhited DATE 01/20/2015 OFFICIAL RECORD COPY