{{#Wiki_filter:/C FORM 366 U. S. NUCLE AR REGULATORY COMMISSION r/.77)LICENSEE EVENT REPORT CONTROL atOCie l llllll@(PLE ASE PRINT OR TYPE ALL REQUIRED INFORMATION) lo lil l Vl ^l Nl Al Sl 1 l@l 0 l 0 l - l 0 l 0 l 0 l 0 l 0 l- l010 l@l4 l1 l1 l1 l1 l@l ll@7 8 9 LICENsis COaE 14 15 LICENSE NuvdeH 23 26 LectNSE TYPE JO 57 L A T bd CON'T ,g l L lg[ 0 l 5 l 0 l 0 l 0 l 3 l 3 l 5 l@l 0 l 9 l 1 l 1l7l9l@l1 ln l 111 17 lq l@
{{#Wiki_filter:U. S. NUCLE AR REGULATORY COMMISSION
R O i/8 w 61 DOCKET NUYdEH f,d O'J LVENT DATE i .4 7')HEPOH T D AT E B0 EVEN T DESCP!PTION AND PROB ABLE CONSEQUENCES O'o l On September 11, 1979, the bistable for Containment High-High Pressure Channel I 1 O 2 i actuated on a high pressure signal and failed in tSc low pressure state during the lo 3[ perforcance of the monthly surveillance test. Since Containment High-High Pressure l0., Channels II, III, and IV remained operable to initiat.e a CDA if required, the health l0 s;O g i l and safety of the general public were not af fected . by this event.
  /C FORM 366 r/.77)
Reportable lFOT77 l pursuant tO T.S. 6.9.1.9.b.
LICENSEE EVENT REPORT CONTROL atOCie l                 l      l      l    l  l    l@                   (PLE ASE PRINT OR TYPE ALL REQUIRED INFORMATION) lo lil8 l9 Vl ^lLICENsis 7
l!l.O<CE CODE SUSCO E COVPONENT CODE SUBC DE SU ODElO191 II I Bl@ dj@ LGj@ lI lN lS lT lR lU l@ O@ [Zj @
Nl AlCOaE      Sl 1 l@l 0 l 0 l - l 0 LICENSE 14      15 l 0 l 0NuvdeH  l 0 l 0 l- l01023 l@l4       26      l1LectNSE l1 l1TYPE    l1JOl@l57 L Al T bdl@
7 8 9 10 11 12 13 18 19 20,.SEQUE NTI AL OCCURRENCE REPORT REVISION LERRO EVENT YEAR REPORT NO.
CON'T O    i          ,g l L lg[ 0 l 5 l 0 l 0 l 0 l 3 l 3 l 5 l@l 0 l 9 l 1 l 1l7l9l@l1 ln l 111 17 lqB0l@
CODE TYPE NO.@ sV,Pgr[7 l9 I l--- J l 11 0] 21 l/l 10 l3 lLll-ll0la6 ,21 22 23 24 26 21 28 29 JJ 31 J2 TAKEN A T N ON PL NT iT HOUHS 22 S$3YT'T D FO 95 8.SUPPLIE MAN FACTURER lClg g g Z lgl36 Zl@l0 l0 [0 lU l lYl@N l@lA l@l Wl l! 2 l 0l@
R i .4      7')        HEPOH T D AT E
33 34 J 3/40 41 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h iiiO; l The bistable for Containment High-High Pressure Channel I failed because of a bad gisii signal comparator card. The channel was left in the blocked condition and the il defective comparator card was replaced. The new card was then calibrated, the loop , , i, 3i l functionally tested and the channel returned to the normal condition.
/         8                     w             61               DOCKET NUYdEH               f,d     O'J       LVENT DATE EVEN T DESCP!PTION AND PROB ABLE CONSEQUENCES O'o O 2        l On September 11, 1979, the bistable for Containment High-High Pressure Channel I                                                                                       1 o  3      i actuated on a high pressure signal and failed in tSc low pressure state during the                                                                                     l 0  .,    [ perforcance of the monthly surveillance test. Since Containment High-High Pressure                                                                                     l 0  s Channels II, III, and IV remained operable to initiat.e a CDA if required, the health                                                                                 l
l11 1411*8 9 80 ST S% POWER OTHER STATUS iSCOV RY DISCOVERY DESCRIPTION li l5 l l El@ j 0 8l6l@
;O g i l and safety of the general public were not af fected . by this event.                                                                                   Reportable               l FOT77 l pursuant tO T.S. 6.9.1.9.b.                                                                                                                                                     l
NAlBl@l Surveillance Test ACTIVITY CG TENT RELEASED OF RELE ASE AVOU.<T OF ACTIVITY LOCATION OF RELE ASE L.ZJ @ LZJ@i NA NA l i 6 7 8 9 10 It 44 45 80 PERSONNEL EXPOSURES NUVRE R TYPE D ESCR:PTION '
                                                                                                                                                                                        !
y 1010l Ol@l Zl@l NAl'''*'" ',ERSONNELmuns OESCRiPriON@
O  <
NoveERlfiTT1 10 0 Ol@l NA. .]}h ,-,lh]80 7 8 9 11 12 LOSS OF OR DAMAGE TO FACILITY Q TYPE DE SCRIP TION
l.
%./l Zl@l NA i 9 7 8 9 10 80 PUBLICITY NRC USE ONLY
CE               CODE       SUSCO E                   COVPONENT CODE                 SUBC DE               SU ODE lO191                              II I Bl@ dj@ LGj@ lI lN lS lT lR lU l@ O@ [Zj 10                                                                        18            19                20,.
'e?7910150 5e#
                                                                                                                                                                  @
l NAll1 I I I I I I I I I I :I l 2 l o l [_ N_j@DESCRIPI'iCN
7         8                       9                         11           12             13 SEQUE NTI AL                         OCCURRENCE           REPORT                           REVISION EVENT YEAR                                 REPORT NO.                               CODE                 TYPE                           NO.
'tsSUED 7 8 9 10 68 b9 80 ;W. R. Cartwright 703-894-5151 2 pa o ne.NAVE OF PR PAHER Virginia Electric and Power Company North Anna Power Station, Unit #1
LERRO
              @     a6 sV,Pgr           [7 l9 22I                l--- J       l 11 0] 21                 l/l           10 l3 l                    Ll            l-l        l0l
                                    ,21                       23           24             26         21           28       29           JJ                 31         J2 TAKEN A T N                 ON PL NT               iT                     HOUHS 22           S$3YT'T D     FO 95 8.             SUPPLIE                 MAN FACTURER lClg 33          34 g g             J Z lg              l36 Zl@
l0 l0 [0 lU l 3/                      40 lYl@
41 N l@
42 lA 43 l@       l44 Wl l! 2 l 0l@
47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h iiiO; l The bistable for Containment High-High Pressure Channel I failed because of a bad gisii             signal comparator card. The channel was left in the blocked condition and the                                                                                           i
    , ,        l defective comparator card was replaced. The new card was then calibrated, the loop i, 3i l functionally tested and the channel returned to the normal condition.                                                                                                           l 11 1411
* 8 9                                                                                                                                                                         80 ST     S           % POWER                           OTHER STATUS                 iSCOV RY                             DISCOVERY DESCRIPTION li l5 l l El@ j 0 8l6l@                                           NA                      l        Bl@l             Surveillance Test ACTIVITY CG TENT RELEASED OF RELE ASE                           AVOU.<T OF ACTIVITY                                                     LOCATION OF RELE ASE i 6                                            NA                                                        NA                                                                          l 7        8 9 L.ZJ @ LZJ@i   10           It                                           44             45                                                                           80 PERSONNEL EXPOSURES NUVRE R             TYPE           D ESCR:PTION '
y 1010l Ol@l Zl@l                                               NA
* l
'         " '                 ''
                  ,ERSONNELmuns
                                                      '
NoveER              OESCRiPriON@
fiTT1 10 0 Ol@l                                     NA                                                                                                     . .     ,-,
80 l
7         8 9                 11       12 lh]        ]}h LOSS OF OR DAMAGE TO FACILITY Q TYPE     DE SCRIP TION                     %./
i 9 8 9 l Zl@l10                            NA 80 7
PUBLICITY                                                                                                                                       NRC USE ONLY tsSUED l 2 l o l [_ N_j@DESCRIPI'iCN l
                                              '
                                              'e?
NA 7910150 5e#                           l     l1      I I I I I I I I I 80I :I; 7         8 9           10                                                                                                                       68 b9 NAVE OF PR PAHER                        W. R. Cartwright                                             pa o ne.            703-894-5151                         2
 
Virginia Electric and Power Company North Anna Power Station, Unit #1                      


==Attachment:==
==Attachment:==
 
Page 1 of 1 Docket No. 50-338 Report No. LER 79-102/03L-0 Descriction of Event On September 11, 1979, curing Mode 1 operation at 86L power, the bistable for Containment High-High Pressure Channel I actuated on a high pressure signal and failed in the low pressure stde during the performance of the monthly surveillance te:t. The channel was left in the blocked condition and declared inoperable.
Page 1 of 1 Docket No. 50-338 Report No. LER 79-102/03L-0 Descriction of Event On September 11, 1979, curing Mode 1 operation at 86L power, the bistable for Containment High-High Pressure Channel I actuated on a high pressure signal and failed in the low pressure stde during the performance of the monthly surveillance te:t.
The channel was left in the blocked condition and declared inoperable.
Probable Consequences of Occurrence The consequences of this event were limited because Contair. ment High-High Pressure Channels II, III and IV remained operable to initiate a Containment Depressurization Actuation if required. As a result, the public health and safety were not jeopardized by this event. This occurrence has no generic implications affecting Unit 1 and Unit 2 instrumentation.
Probable Consequences of Occurrence The consequences of this event were limited because Contair. ment High-High Pressure Channels II, III and IV remained operable to initiate a Containment Depressurization Actuation if required. As a result, the public health and safety were not jeopardized by this event. This occurrence has no generic implications affecting Unit 1 and Unit 2 instrumentation.
_Cause of Occurrence The bistable for Containment High-High Pressure Channel I failed because the signal comparator card was defective. The failure was not the result of a W-104 component problem.
_Cause of Occurrence The bistable for Containment High-High Pressure Channel I failed because the signal comparator card was defective. The failure was not the result of a W-104 component problem.

Revision as of 14:34, 19 October 2019

LER 79-102/03L-0:on 790911,bistable for Containment high- Risk Pressure Channel I Actuated High Pressure Signal & Failed in Low Pressure State During Test.Caused by Bad Signal Comparator Card.Defective Card Replaced & Calibr
ML19209C442
Person / Time
Site: North Anna Dominion icon.png
Issue date: 10/11/1979
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19209C435 List:
References
LER-79-102-03L, LER-79-102-3L, NUDOCS 7910150568
Download: ML19209C442 (2)


Text

U. S. NUCLE AR REGULATORY COMMISSION

/C FORM 366 r/.77)

LICENSEE EVENT REPORT CONTROL atOCie l l l l l l l@ (PLE ASE PRINT OR TYPE ALL REQUIRED INFORMATION) lo lil8 l9 Vl ^lLICENsis 7

Nl AlCOaE Sl 1 l@l 0 l 0 l - l 0 LICENSE 14 15 l 0 l 0NuvdeH l 0 l 0 l- l01023 l@l4 26 l1LectNSE l1 l1TYPE l1JOl@l57 L Al T bdl@

CON'T O i ,g l L lg[ 0 l 5 l 0 l 0 l 0 l 3 l 3 l 5 l@l 0 l 9 l 1 l 1l7l9l@l1 ln l 111 17 lqB0l@

R i .4 7') HEPOH T D AT E

/ 8 w 61 DOCKET NUYdEH f,d O'J LVENT DATE EVEN T DESCP!PTION AND PROB ABLE CONSEQUENCES O'o O 2 l On September 11, 1979, the bistable for Containment High-High Pressure Channel I 1 o 3 i actuated on a high pressure signal and failed in tSc low pressure state during the l 0 ., [ perforcance of the monthly surveillance test. Since Containment High-High Pressure l 0 s Channels II, III, and IV remained operable to initiat.e a CDA if required, the health l

O g i l and safety of the general public were not af fected . by this event. Reportable l FOT77 l pursuant tO T.S. 6.9.1.9.b. l

!

O <

l.

CE CODE SUSCO E COVPONENT CODE SUBC DE SU ODE lO191 II I Bl@ dj@ LGj@ lI lN lS lT lR lU l@ O@ [Zj 10 18 19 20,.

@

7 8 9 11 12 13 SEQUE NTI AL OCCURRENCE REPORT REVISION EVENT YEAR REPORT NO. CODE TYPE NO.

LERRO

@ a6 sV,Pgr [7 l9 22I l--- J l 11 0] 21 l/l 10 l3 l Ll l-l l0l

,21 23 24 26 21 28 29 JJ 31 J2 TAKEN A T N ON PL NT iT HOUHS 22 S$3YT'T D FO 95 8. SUPPLIE MAN FACTURER lClg 33 34 g g J Z lg l36 Zl@

l0 l0 [0 lU l 3/ 40 lYl@

41 N l@

42 lA 43 l@ l44 Wl l! 2 l 0l@

47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h iiiO; l The bistable for Containment High-High Pressure Channel I failed because of a bad gisii signal comparator card. The channel was left in the blocked condition and the i

, , l defective comparator card was replaced. The new card was then calibrated, the loop i, 3i l functionally tested and the channel returned to the normal condition. l 11 1411

  • 8 9 80 ST S  % POWER OTHER STATUS iSCOV RY DISCOVERY DESCRIPTION li l5 l l El@ j 0 8l6l@ NA l Bl@l Surveillance Test ACTIVITY CG TENT RELEASED OF RELE ASE AVOU.<T OF ACTIVITY LOCATION OF RELE ASE i 6 NA NA l 7 8 9 L.ZJ @ LZJ@i 10 It 44 45 80 PERSONNEL EXPOSURES NUVRE R TYPE D ESCR:PTION '

y 1010l Ol@l Zl@l NA

  • l

' " '

,ERSONNELmuns

'

NoveER OESCRiPriON@

fiTT1 10 0 Ol@l NA . . ,-,

80 l

7 8 9 11 12 lh] ]}h LOSS OF OR DAMAGE TO FACILITY Q TYPE DE SCRIP TION  %./

i 9 8 9 l Zl@l10 NA 80 7

PUBLICITY NRC USE ONLY tsSUED l 2 l o l [_ N_j@DESCRIPI'iCN l

'

'e?

NA 7910150 5e# l l1 I I I I I I I I I 80I :I; 7 8 9 10 68 b9 NAVE OF PR PAHER W. R. Cartwright pa o ne. 703-894-5151 2

Virginia Electric and Power Company North Anna Power Station, Unit #1

Attachment:

Page 1 of 1 Docket No. 50-338 Report No. LER 79-102/03L-0 Descriction of Event On September 11, 1979, curing Mode 1 operation at 86L power, the bistable for Containment High-High Pressure Channel I actuated on a high pressure signal and failed in the low pressure stde during the performance of the monthly surveillance te:t. The channel was left in the blocked condition and declared inoperable.

Probable Consequences of Occurrence The consequences of this event were limited because Contair. ment High-High Pressure Channels II, III and IV remained operable to initiate a Containment Depressurization Actuation if required. As a result, the public health and safety were not jeopardized by this event. This occurrence has no generic implications affecting Unit 1 and Unit 2 instrumentation.

_Cause of Occurrence The bistable for Containment High-High Pressure Channel I failed because the signal comparator card was defective. The failure was not the result of a W-104 component problem.

Immediate Corrective Action Containment High-High Pressure Channel I was left in the blocked condition and signal comparator card PS-LM100A-3 was replaced. The new card was then calibrated, the loop functionally tested, and the channel returned to the normal condition.

Scheduled Corrective Action No scheduled corrective action is required.

Actions Taken to Prevent Recurrence No further actions are required.

1145 355