ULNRC-03289, Monthly Operating Rept for Oct 1995 for Callaway Plant Unit 1

From kanterella
Jump to navigation Jump to search
Monthly Operating Rept for Oct 1995 for Callaway Plant Unit 1
ML20094J658
Person / Time
Site: Callaway Ameren icon.png
Issue date: 10/31/1995
From: Affolter R, Holmes M
UNION ELECTRIC CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
ULNRC-03289, ULNRC-3289, NUDOCS 9511160001
Download: ML20094J658 (6)


Text

~

Cat:a..sy Plant

, Post Ofhce Box 620 fu; tan. M,ssoun 65251 l

l Union "*~"bc"5 i

Etscruic 53 U.S. Nuclear Regulatory Commission l Document Control Desk  !

Washington,DC 20555 l ULNRC-03289 l

l Gentlemen:

DOCKET NUMBER 50-483 CALLAWAY PLANT UNIT 1 l FACILITY OPERATING LICENSE NPF-30 MONTHLY OPERATING REPORT OCTOBER 1995

> The enclosed Monthly Operating Report for October 1995 is submitted pursuant to Section 6.9.1.8 of the Callaway Unit 1 Technical Specifications.

V b R. D. Affolter Manager, Callaway Plant RDA/HDB/MAH/cmw i Enclosure cc: Distribution attached e, ,- ....

U; i- ) 1 9511160001 951031 Y I PDR R

ADOCK 050004B3 PDR

/I i L

?

cc distribution for ULNRC-03289 J with enclosures Mr. L. Joe Callan  :

Regional Administrator  :

U.S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive Suite 400 Arlington, TX 76011 Ms. Kristine M. Thomas (2 copies)

Licensing Project Manager Office of Nuclear Reactor Regulation )

U.S. Nuclear Regulatory Commission 1 Mail Stop 13-E-21 l Washington, D.C. 20555 Manager, Electric Department Missouri Public Service Commission .

P. O. Box 360 '

Jefferson City, MO 65102 Mr. Thomas A. Baxter Shaw, Pittman, Potts & Trowbridge 2300 N. Street N.W.

Washington, D.C. 20037 NRC Resident Inspector l

l

.. - __ -. -.- - . . . - - - - -. - . ~ - - - . - . - . - -

1 DOCKET NO.: 50-483

  • UNIT NAME: CALLAWAY UNIT 1 DATE: 11/8/95 COMPIETED BY: M. A. Holmes

'IELEPHONE: 314/676-8842 FAX: 314/676-8562 PART A - OPERATIONS

SUMMARY

The plant operated at approximately 98.5% for the month of October due to steam generator low pressure limitations after chemical cleanir.g with the following exceptions:

On 10/02/95 at 08:00 CDT, the plant was shut down to repair a leak on the Excess Letdown line. This line comes off the 'D' loop cross-over line connecting the Reactor Coolant Pump (RCP) with the Steam Generator. The work continued until the leak was repaired. In addition boric acid crystals were identified on the 'B' and 'C' RCPs between the seal housing and casing The bolts on the housings had been replaced during the 1995 spring outage due to leaks in the same area. The cause was determined to be burrs in the bolts causing false elongation readings during the torquing process. The bolts were replaced with studs. On 10/11/95 at 14:26, the main breaker was closed.

On 10/13/95 at 23:01, power was reduced to 98.3% for the performance ofInstrument and Control (I&C) surveillances On 10/16/95 at 17:00, power was reduced to 98.3% for the performance ofI&C surveillances.

On 10/23/95 at 21:00, power was reduced to 98.3% for the performance ofI&C surveillances.

On 10/24/95 at 09:15, power was reduced to 98.1% to adjust the packing on a valve in the Chemical & Volume Control System, BGHV8152.

On 10/25/95 at 19:00, power was reduced to 98.3% for the performance ofI&C surveillances.

PART B - PORY AND SAFETY VALVE

SUMMARY

None.

Page 1 of 4

?^

^

PART C AVERAGE DAILY UNIT POWER LEVEL DOCKET NO: 50-483 l UNIT. Callaway Unit I  !

DATE: 11/8/95 COMPLETED BY: M. A. Holmes TELEPHONE: 314/676 4 842 FAX: 314/676-8562 MONTH: OCTOBER 1995 AVERAGE DAILY POWER AVERAGE DAILY POWER LEVEL LEVEL DAY (MWe-NeO M (MWe-NeO 1 1.148 17 1.144 2 912 18 1.146 ,

i 3 0 19 1.146 4 0 20 1.162 5 0 21 1.166 6 0 22 1.154 7 0 23 1.149 8 0 24 1.159 9 0 25 1.159 10 0 26 1.154 11 123 27 1.155 12 689 28 1.162 13 1.084 29 1.161 14 1.158 30 1.160 15 1.158 31 1.155 16 1.157 Page 2 of 4

.. '. PART D OPERATING DATA REPORT DOCKET NO.: 50-483 c - UNIT NAME:

CAllAWAY UNIT 1 DATE: 11/8/95 COMPLETED BY: M. A. Holmes TELEPHONE: 314/676-8842 FAX: 314/676-8562 l

OPERATING STATUS- l (OCT) (YTD) (CUM) )

1. REPORTING PERIOD:

GROSS HOURS IN REPORTING PERIOD: 744 7,295 95,220.5 2 CURRENTLY AUTHORIZED POWER LEVEL (MWt): 3565 MAX. DEPEND. CAPACITY (MWe-Net): 1125 DESIGN ELECTRICAL RATING (MWe-Net): 1171

3. POWER LEVEL TO WHICH RESTRICTED (IF ANY) (MWe-Net): 100 %
4. REASONS FOR RESTRICTION (IF ANY)

THIS MONTH YR TO DATE CUMULATIVE

5. NUMBER OF HOURS REACTOR WAS CRITICAL 525.2 5,953.8 83,660.5
6. REACTOR RESERVE SHUTDOWN HOURS 0 0 0
7. HOURS GENERATOR ON-LINE 525 5,894.6 82,176.4
8. UNIT RESERVE SHUTDOWN HOURS 0 0 0
9. GROSS THERMAL ENERGY GENERATED 1,784,097 20,249,075 277,805,838 (MWH)
10. GROSS ELECTRICAL ENERGY GENERATED 612,321 6.884,878 94,736,646 (MWH)
11. NET ELECTRICAL ENERGY GENERATED 578,403 6,547,774 90,118,316 (MWH)
12. REACTOR SERVICE FACTOR 70.6 81.6 87.9
13. REACTOR AVAILABILITY FACTOR 70.6 81.6 87.9
14. UNIT SERVICE FACTOR 70.6 80.8 86.3
15. UNIT AVAILABILITY FACTOR 70.6 80.8 86.3
16. UNIT CAPACITY FACTOR (Using MDC) 69.1 79.8 84.1
17. UNIT CAPACITY FACTOR (Using Design MWe) 66.4 76.6 80.8
18. UNrr FORCED OUTAGE RATE 29.39 4.10 2.39
19. SIRTTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH):

Refueling Date: 10/05/96 Duration: 42 days

20. IF SHUT DOWN AT END OF REPORTING PERIOD, ESTIMATE DATE OF STARTUP:

Page 3 of 4

. - . - . -. -. _ _ - . . - . _ . . - - . - . . . - - - - . - - . . - . ~ . _ . ..- - ..- - - - . . . - = - . . ~ - ~ . _ . . .

PART E UNIT SHUTDOWNS AND POWER REDUCTIONS ,

DOCKET NO.: 50-483 l, UNIT NAME. CALLAWAY UNIT 1 .

DATE: 11/5/95 COMPLETED BY: M. A.Hohnes j TELEPHONE- 314/676-8842 .

4 FAX: 314/676-8562 j t

REPORTMONTH: OC1DBER1995 METHOD OF TYPE SHUTTING DOWN F: FORCED DURATION THE REACIDR OR COPRECTIVE ML DATE S: SCHEDULED fBOURS) REASON REDUCING POWER ACTIONS /COMMEN15 6 951002 F 219 A 1 SEE

SUMMARY

BELOW. ,

SUMMARY

On 10/02/95 at 08:00 CDT, the plant was shut down to repair a leak on the Excess Letdown line. This line comes off the 'D' loop cross-over line connecting the Reactor Coolant Pump (RCP) with the Steam Generator. The work continued until the leak was repaired. In addition boric acid crystals were identified on the 'B' and 'C' RCPs between the seal housing and casing. The bolts on the housings had been replaced during the 1995 spring outage due to leaks in the same area. The cause was determined to be burrs in the bolts causing false elongation readings during the torquing process. The bolts were replaced with studs On 10/11/95 at 14:26, the main breaker was closed.

REASON METHOD A EQUIPMENTFAILURE(EXPLAIN) 1: MANUAL B. MAINT.ORTEST 2: MANUAL SCRAM C: REFUELING 3: AUTOMATICSCRAM D: REGULATORYRESTRICTION 4: DINER (EXPLAIN)

E: OPERATORTRAINING AND LICENSE EXAMINATION F: ADMINISTRATION G: OPERATIONALERROR(EXPLAIN)

H: 011IER(EXPLAIN)