ML20206E333 | 28 April 1999 | Notice of Violation from Insp on 990105-022.Violation Noted: Between 981222 & 990105,low Temp Condition with Potential to Cause Freezing of Common Min Flow Line Was Not Identified Nor Cause Determined | Condition Adverse to Quality |
ML20207L121 | 10 March 1999 | Notice of Violation from Insp on 990105-0222.Violation Noted:As of 990129,Operations Manual 3.7, AOP & EOP Sets Use & Adherence, Rev 5,major Procedure Prescribing Activities Affecting Quality,Inappropriate for Circumstance | |
ML20199H562 | 15 January 1999 | Notice of Violation from Insp on 981121-990104.Violations Noted:As of 981015,adequate VT-2 Visual Exam of Pressure Retaining Boundary of Sfsp Common to Units 1 & 2 Not Performed During Each Code Insp Period | VT-2 |
ML20151Y257 | 11 September 1998 | Notice of Violations from Insp on 980608-12 & 0715-16. Violations Noted:Licensee Failed to Determine Lowest Voltages Available at Breaker Close & Trip Coils Since Original Installation of Breaker | |
ML20249C285 | 19 June 1998 | Notice of Violation from Insp on 980414-0523.Violation Noted:Licensee Did Not Test Some Refueling Sys Interlocks During Refueling Shutdowns from Time of Initial Plant Refueling Through 980422 | |
ML20249A062 | 11 June 1998 | Notice of Violation from Insp on 980518-22.Violation Noted: Two Emergency Plan SRDs Available for Use in Emergency Plan Sampling Kits,Not Calibrated in Dec 1997 | High Radiation Area Locked High Radiation Area |
ML20247D668 | 5 May 1998 | Notice of Violation from Insp on 971216-980309.Violations Noted:Weld Procedure Wps GT-SM/1.1-1 Pb,Rev 4,used to Fabricate SG Replacement Main Steam & Feedwater Welds,Did Not Meet Requirements of QW-409.1 | |
ML20217J452 | 1 April 1998 | Notice of Violation from Insp on 980310-18.Violation Noted: as of 980313,licensee Failed to Establish Measures to Assure That Conditions Adverse to Quality,Promptly Identified & Corrected | |
ML20217D345 | 21 March 1998 | Notice of Violation from Insp on 980120-0302.Violation Noted:Replacement of 10CFR50,App B,Criterion V,State,In Part,That Activities Affecting Quality Shall Be Prescribed by Documented Instructions | |
IR 07100020/2011007 | 19 February 1998 | Notice of Violation from Insp on 971020-1107.Violation Noted:Danger Tags 97-753 & 97-800 Were Installed on 971007 & 18,w/o Tag Sequence Numbers Being Assigned to Danger Tag Location Sheet | Operability Determination |
ML20202E964 | 10 February 1998 | NOV from Insp on 971201-980120.Violation Noted:From 980108- 09,operators Failed to Initiate Actions within 1 H to Place Unit in Hot Shutdown When Both Unit 1 safety-related 4,160- Volt Buses Were Powered from Standby Emergency Power Supply | |
IR 07100021/2011030 | 22 December 1997 | Notice of Violation from Insp on 971021-1130.Violation Noted:As of 971125,four Operability Determinations Prepared as Corrective Actions for Testing Nonconformance Documented in Condition Repts Failed to Justify Operability | Operability Determination |
IR 07100020/2012005 | 18 December 1997 | Notice of Violation from Insp on 971020-1205.Violation Noted:From 941031-970812,licensee Had Implemented Exemption from Biennial Written & Annual Operating Tests Required of Licensed Operators for 2 Individuals Assigned to Exam Team | |
ML20211P353 | 14 October 1997 | Notice of Violation from Insp on 970707-11.Violation Noted: as of 970711,surveillance Procedure E-M3-1, Emergency Lighting, Not Adequate & Did Not Include Data Sheet That Adequately Captured Emergency Lighting Battery | Emergency Lighting Fire Protection Program |
ML20211J883 | 4 October 1997 | NOV from Insp on 970825-29.Violation noted:11 Emergency Plan SRDs Not Calibr in June 1997 & Had Not Been Calibr Since Dec 1996 | |
ML20211B190 | 17 September 1997 | Notice of Violation from Insp on 970304-0805.Violation Noted:As of Feb 1997,test Program Did Not Ensure That Testing Required to Demonstrate Satisfactory Performance of CCW cross-connect valves,CC-722A & CC-722B Was Identified | Enforcement Discretion |
ML20217A261 | 15 September 1997 | Notice of Violation from Insp on 970519-0613.Violations Noted:Inspectors Identified on 970613 That Weld Procedure Wps GT-SM/3.3-2 Pb,Rev 1,did Not Meet Requirements of QW-409.1 | |
ML20217K287 | 8 August 1997 | Notice of Violations from Insp on 961202-970314.Violations Noted:Licensee Did Not Identify & Promptly Correct Condition Adverse to Quality Re Operation of Safety Injection Pump | Condition Adverse to Quality Operability Determination Operability Assessment Manual Operator Action |
ML20151K408 | 29 July 1997 | Notice of Violation from Insp on 970707-11.Violation Noted: Technician Performing Maint Removed Bypass Filters & Failed to Discard Them | |
ML20137M852 | 3 April 1997 | Notice of Violation from Insp on 970303-07.Violation Noted: on 970225,individual Signed in on Standing Radiation Permit 97-0004-1,entered Area Posted, High Radiation Area, Radiography in Progress | High Radiation Area |
ML20135E344 | 27 February 1997 | Notice of Violation from Insp on 961217-970127.Violation Noted:Licensee Identified That on 961216,auxiliary Operator Was Preparing Unit 2 Residual Heat Removal Sys for Fill & Vent Evolution & Did Not Open Valve 2RH-709A,as Required | |
ML20147A771 | 23 January 1997 | Notice of Violation from Insp on 961120-1127.Violation Noted:Battery Chargers D-107 & D-108 Would Not Function Properly If Aligned to DC Bus W/O Battery Also Conducted Due to Design | |
ML20133C433 | 2 January 1997 | Notice of Violation from Insp on 961028-0906.Violation Noted:Licensee Failed to Ensure That Byproduct Matl Was Possessed & Used,Iaw License Conditions 2.C,2.D or 2.E | Fuel cladding |
ML20129D994 | 18 October 1996 | Notice of Violation from Insp on 960826-0925.Violation Noted:On 960404,worker Present in C CVCS Hold Up Tank Cubicle Posted High Radiation Area,Rwp Required, W/O Being Signed on RWP | High Radiation Area |
ML20059A230 | 23 December 1993 | Notice of Violation from Insp on 931026-1206.Violation Noted:Licensee Did Not Rept Initiation of Nuclear Plant Shutdown Required by TS 15.3.0.A | |
ML20058C946 | 18 November 1993 | Notice of Violation from Insp on 930907-1025.Violation Noted:Work Instructions Were Not Appropriate Such as Replacing Bearings of Safety Injection Pump & Performing Electrical Distribution System Meter Calibrations | |
ML20057E817 | 6 October 1993 | Notice of Violation from Insp on 930802-0903.Violation Noted:Controlling Work Document Did Not Provide Quantitative Acceptance Criteria for Establishing Leak Tightness of Boundary Valves | |
ML20126B439 | 8 December 1992 | Notice of Violation from Insp on 921013-1122.Violation Noted:On 921026,maint Electrician Did Not Open Isolation Knife Switch as Required by Procedure Rmp 74 Prior to Depressing Relay Test Button | |
ML20125C748 | 8 December 1992 | Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $75,000.Violations Noted:While Reactor Made Critical on 911113,foreign Matl Exclusion Disk Left in Section of Sys Piping Leading to Suction of Injection Pump | |
ML20127D876 | 4 September 1992 | Notice of Violation from Insp on 920629-0823.Violation Noted:Battery Cable on G-501 Auxiliary Diesel Was Reconnected to Battery Prior to Danger Tag Location Sheet Authorizing Return to Svc of Equipment to Operations Group | |
ML20058H116 | 30 October 1990 | Notice of Violation from Insp on 900905-1015.Violation Noted:Inadvertent Actuation of RPS Occurred When Two of Three Containment Pressure Bistables Tripped & Was Not Reported Until 901011,over One Yr from Date of Occurrence | |
ML20055J375 | 8 June 1990 | Notice of Violation from Insp on 900525.Violation Noted: Failure to Make Adequate Surveys or Evaluations Necessary & Reasonable to Ensure Compliance W/Occupational Dose Limits After Health Physics Technologist Handled 142.5 Mci Fuel | High Radiation Area |
ML20245G776 | 21 June 1989 | Notice of Violation from Insp on 890301-0531.Violation Noted:On 890505,technician Failed to Install Analog Simulator for 1A Steam Generator Scheduled to Be Drained Below Low Level Setpoint to Facilitate Maint | |
ML20195B359 | 21 October 1988 | Notice of Violation from Insp on 880926-30.Violations Noted:Instructor Not Always Present During Exam Given to Students Having Completed General Employee Training | |
ML20155D553 | 19 May 1988 | Notice of Violation from Insp on 880418-22.Violation Noted: Failure to Use Flashing Red Light as Warning Device When Dose Rate Exceeded 1000 M/H & Radiation Surveys Performed While Fuel Element in Stationary Position | High Radiation Area |
ML20154H247 | 16 May 1988 | Notice of Violation from Insp on 880316-0430.Violation Noted:Instrument & Control Supervisor Submitted Request for Equipment Isolation to Duty Shift Supervisor W/O Specifying Time & Date of Planned Work Activity | |
IR 07100020/2012030 | 2 February 1988 | Notice of Violation from Insp on 871020-1230.Violations Noted:On 871114,during Plant Startup,Reactor Pressure Increased Above 150 Psig with RCIC Sys in Secured Status | |
IR 07100020/2011019 | 4 January 1988 | Notice of Violation from Insp on 871020-1119.Violations Noted:Emergency Diesel Generator 2J Electrically Overloaded Due to Inadequate Surveillance Procedure & Failure to Follow Procedures | |
ML20236G512 | 29 October 1987 | Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $25,000.Violation Noted:Msivs Could Not Close Because Dc Control Power Removed from Associated Solenoids & Event Not Reported within Required 4 H | Unanalyzed Condition Condition Adverse to Quality |
ML20236L716 | 29 July 1987 | Notice of Violation from Insp on 870217-20 & 0601-0715. Violations Noted:Licensee Disposed of Plant Sludge Onsite Contaminated W/Licensed Matl & Auxiliary Operator Failed to Reopen Air Start Isolation Valves While Performing TS-1 | |
ML20235Q723 | 14 July 1987 | Notice of Violation from Insp on 870428-0519.Violation Noted:Two Authorized Contractor Technicians Handled Container of Licensed Matl Containing Highly Radioactive Particles & Container Not Labeled or Identified | |
ML20215G865 | 7 April 1987 | Notice of Violation from Insp on 870201-0331 | |
ML20216J124 | 11 March 1987 | Partially Withheld Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $50,000 for Insp Repts 50-266/86-12 & 50-301/86-01 on 860718-0807 | |
ML20207L809 | 7 January 1987 | Notice of Violation from Insp on 860926-1211 | Integrated leak rate test |
ML20211K237 | 5 November 1986 | Notice of Violation from Insp on 860807-08 & 1016-17 | |
ML20212L239 | 8 August 1986 | Notice of Violation from Insp on 860601-0731 | |
ML20197H128 | 14 May 1986 | Notice of Violation from Insp on 850722-26.Violations Noted: File Did Not Demonstrate That Single Specimen of Rockbestos Coaxial Cable Used for Entire Test Sequence,Nor Was Analysis of Discrepancy Provided in Support of Qualification | Safe Shutdown |
IR 05000801/2009030 | 10 October 1985 | Notice of Violation from Insp on 850801-0930 | |
IR 05000301/2004030 | 21 August 1985 | Notice of Violation from Insp on 850301-0430 | |
ML20133F458 | 1 August 1985 | Notice of Violation from Insp on 850624-27,0703 & 18 |