Proposed Tech Specs Reflecting Alternative Wording for Surveillance Which Address Only Clarification to Situational Testing Requirement
ML20202A796
Person / Time
Site: Fermi 
Issue date: 11/26/1997
From:
DETROIT EDISON CO.
To:
Shared Package
ML20202A727 List:
References
NUDOCS 9712020224
Download: ML20202A796 (2)


Text

..

Attachment I to NRC-97-0092 Page1

,t 7

ATTACilMENT PROPOSED TECllNICAL SPECIFICATION CIIANGES (ALTERNATIVE WORDING) 9712020224 971126 PDR ADOCK 05000341 P

PDR

4 h.

ELECTRICAL POWER !YSTEMS fiOTOR 0PERATED VALfES THERMAL OVERLOAD PROTECTION QHITINGCONDi'IONFOROPERATI0t*

3.8.4.3 The thermal overload protection of each valve used -in safety systems shall be OPERABLE.

APPLICABILITY: Whenever the motor-operated valve is required to be OPERABLE.

ACTION:

With the thermal overload protection for one or more of the above required 0-.ves inoperable, continuously bypass the inoperable thermal overload within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or declare the affected valve (s) inoperable and apply the appropriate ACTION statement (s) for the affected system (s).

, SURVEILLANCE RE0VIREMENTS 4.8.4.3 The thermal overload protection for the above required valves shall be demonstrated OPERABLE by the performance of a CHANNEL CALIBRATION of a j

representative sample of at least 25% of all thermal overloads for the above required valves at least once per 18 months, and by performance of a CHANNEL I

CALIBRATION of the affected thermal overload following any maintenance activity which could affect the performance of that thermal overload.

(

FERMI - UNIT 2 3/4 8-20 Amendment No. R2, l