ML20133A896

From kanterella
Jump to navigation Jump to search
Responds to 840227 Request for re-review of Selected Sections of Tech Specs Including Applicable Bases Section in Auxiliary Sys Branch Areas of Responsibility.Tech Specs Acceptable
ML20133A896
Person / Time
Site: Grand Gulf 
Issue date: 03/06/1984
From: Rubenstein L
Office of Nuclear Reactor Regulation
To: Mattson R
Office of Nuclear Reactor Regulation
Shared Package
ML19276B572 List: ... further results
References
FOIA-84-459 NUDOCS 8507200187
Download: ML20133A896 (5)


Text

.

..~ -.

  1. p@ ithjo,,

tsNITED STATES dQ yhe g

NUCLEAR REGULATORY COMMISSION

. 4,,7, 3.y WASHINGTON, D. C. 20555

,Y,. **

MAR 6 1984 10RAf1DUM FOR: Roger J. Mattson, Director, Division of Systems Integration FROM:

L. S. Rubenstein, Assistant Director for Core and Plant Systems, Division of Systems Integration

SUBJECT:

RE-REVIEW 0F GRAf10 GULF TECHilICAL SPECIFICATI0its As reouested by your memorandum dated February 27, 1984 we have re-reviewed the following sections of the Grand Gulf Technical Specifications, including the applicable bases section, which are in the Auxiliary Systems Branch (ASB) areas of primary responsibility.

1.18 - Identified Leakage 1.29 - Pressure Boundary Leakage 3/4

^t/3.7.4 - Remote Shutdown Monitoring Instrumentation 3/4.4.3 - Reactor Coolant System Leakage 3/4.6.1 - MSIV Leakage Control System 3/4.7.1.1 - Standby Service Water System 3/4.7.1.2 - High Pressure Core ' Spray Service Water System 3/4.7.1.3 - Ultimate Heat Sink 3/4.7.2 - Control Room Emergency Filtration System 3/4.7.8 - Arca Temperature Monitoring System 3/4.7.9 - Spent Fuel Storage Pool Temperature 3/4.9.7 - Crane Travel - Spent Fuel Flood Upper Containment Fuel Storage Pools

-3/4.9.9 - Water Level - Spent Fuel and Upper Containment Fuel Storage Pools 3/4.9.12 - Horizontal Fuel Transfer System 5. <,

-rua svo,%e

Contact:

J. Ridgely X29566 6

8507200187 850515 PDR FOIA BELLB4-459 PDR

.. MAR 6 By Based on our review, we conclude that the Grand Gulf Technical Specifications are accepta51e except for specifications 3/4.6.1, 3/4.7.1.1 and 3/4.7.1.2.

Enclosed are copies of those three specifications which have been marked with the appropriate corrections.

A s

E. S.ARubenstein, Asf stant Director for Core and Plant Systems Division of Systems Integration

Enclosure:

As Stated cc w/ enclosure:

R. Capra O. Parr J. Wilson J. Hermiel F. Clemenson J. Ridgely D. Hoffman O

CONTAINMENT SYSTEMS

' MSIV LEAKAGE CONTROL SYSTEM LIMITING CONDITION FOR OPERATION 3.6.1.4 Two independent MSIV leakage control system (LCS) subsystems shall be OPERABLE.

APPLICABILITY:

OPERATIONAL CONDITIONS 1, 2 and 3.

ACTION:

With one MSIV leakage control system subsystem inoperable, restore the inoperable subsystem to OPERABLE status within 30 days or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

SURVEILLANCE REOUIREMENTS 4.6.1.4 Each MSIV leakage control system subsystem shall be demonstrated OPERABLE:-

a.

At least once per 31 days by verifying:

1.

Blower OPERABILITY by starting the blowers from the control room and operating the blowers for at least 15 minutes.

caupMe-& A-edes %J v $gd*;-a em4 4 /.W 2.

Heater OPERABILITY by #.

~ * ~ ' '

"'- + '--' ---+

m s__.,__

u j m,

,o 9.')1,~ F :s i C < a k % + u.

. b.

During each COLD SHUTDOWN, if not performed within the previous 92 days, by cycling each motor operated valve through at least one complete cycle of full travel.

c.

At least once per 18 months by:

1.

Performance of a functional test which includes simulated actuation of the subsystem throughout.its operating sequence, and verifying that each automatic valve actuates to its correct position, the blowers start and the heater draws 7.8 to 9.5 amperes per phase.

2.

Verifying that the blower developed at least the below required vacuum at the rated capacity.

a)

Inboard valves, 15" 1 1" H O at 100 scfm.

2 b)

Outboard valves, 50" 1 2" H O at 200 scfm.

2 d.

By verifying the inboard flow, inboard and outboard pressure, and inboard temperature instrumentation to be OPERABLE by performance of a:

1.

CHANNEL CHECK at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, 2.

CHANNEL FUNCTIONAL TEST at least once per 31 days, and 3.

CHANNEL CALIBRATION at least once per 18 months.

GRAND GULF-UNIT 1 3/4 6-7 Amendment No. 9 L

3/4.7 PLANT SYSTEMS 3/4.7.1 SERVICE WATER SYSTEMS STANOBY SERVICE WATER SYSTEM

~

LIMITING CONDITION FOR OPERATION 3.7.1.1 Two independent standby service water (SSW) system subsystems shall be OPERABLE with each subsystem comprised oft a.

One OPERABLE SSW pump, and b.

An OPERABLE flow path capable of taking suction from the associated SSW cooling tower basin and transferring the water through the RHR heat exchangers, ECCS pump room seal coolers, and associated coolers and pump heat exchangers.

APPLICABILITY:

OPERATIONAL CONDITIONS 1, 2, 3, 4, 5 and *.

ACTION:

a.

In OPERATIONAL CONDITION 1, 2 or 3:

1.

With one SSW subsystem inoperable, restore the inoperable subsystem to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

2.

With both 35W subsystems inoperable, be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN ** within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

b.

In OPERATIONAL CONDITION 3 or 4 with the SSW subsystem, which is associated with an.RHR loop required OPERABLE by Specification 3.4.9.1 or 3.4.9.2, inoperable, declare the associated RHR loop inoperable and take the ACTION required by Specification 3.4.9.1 or 3.4.9.2, as~ applicable.

c.

In OPERATIONAL CONDITION 4 or 5 with the SSW subsystem, which is associated with an ECCS pump required OPERABLE by Specification 3.5.2, inoperable, declare the associated ECCS pump inoperable and take the ACTION required by Specification 3.5.2.

d.

In OPERATIONAL CONDITION 5 with the SSW subsystem, which is associated with an RHR system required OPERABLE by Specification 3.9.11.1 or 3.9.11.2, inoperable, declare the associated RHR system inoperable and take the ACTION required by Specification 3.9.11.1 or 3. 9.11.2, as applicable.

In 0perational Conditionsh,;.s & TSM rd ry r%

  • ..L:

+,

p t" +M Srd r""eytt::, ch.d. :s e.

3

- - ;,. :. w w.. Q = u:a el gere.etr re W red O'E.G5LE vy 5pecifica-

.medly t L. 0.C.1.2, inuper w M declare the associated diesel generator inoperable and take the ACTION required by Specification 3.8.1.2.

The provisions of Specification 3.0.3 are not applicable, nWhen handling irradiated fuel in the primary or secondary containment.

==Whenever both SSW subsystems are inoperable, if unable to attain COLD SHUTDOWN as required by this ACTION, maintain reactor coolant temperature as low as practical by use of alternate heat removal methods.

GRAND GULF-UNIT 1 3/4 7-1 Amencment No. 9

PLANT SYSTEMS 4

HIGH PRESSURE CORE SPRAY SERVICE WATER SYSTEM

l l

LIMITING CONDITION FOR OPERATION 3.7.1.2. The high pressure core spray (HPCS) service water system shall be OPERABLE with:

a.

.One OPERABLE HPCS service water pump, and b.

An OPERABLE flow path capable of taking suction from the associated SSW cooling tower basin and transferring the water through the HPCS service water system heat exchangers.

APPLICABILITY:

OPERATIONAL CONDITIONS 1, 2, 3,' 4*, and 5*.

ACTION:

With the HPCS service water system inoperable, declare the HPCS system inoperable and take the ACTION required by Specification 3.5.1 or 3.5.2, as applicable.

i 1

)

SURVEILLANCE REQUIREMENTS

)

a.

4.7.1.2 The HPCS service water system shall be demonstrated OPERABLE,at least once per 31 days by verifying that each valve, manual, power operated or auto-matic, servicing safety related equipment that is not locked, sealed or otherwise secured in position, is in its correct position.

de'n skh k Gy wtflQ O' Q j ksfr w p t S mv~~$$

r d h -) u t a d e p g 4 4.e b.. A c 4 i

A.h oJn rnovie.iuj

.h wre cY. 7. re b w w a.

r e o i e.<. M w ac. b M rw 4esk NJ I

When the HPSCS system is required to be OPERABLE.

GRAND GULF-UNIT 1 3/4 7-3 Amendment No. 9

'