[Table view]NPDES Noncompliance Notification:On 980720,lightning Caused Relay Failure on Conventional Waste Sys Lift Station IW-6 Which Caused Pumps to Shut Off.Caused by OOS Alarm Sys.Pumps Were Manually Cycled Until Power Could Be Restored ML20210L1101997-05-15015 May 1997 NPDES Noncompliance Notification:On 970513,overflow of Industrial Waste-2 Lift Station Occurred.Caused by Ruptured Water Main Feeding in Basement of Bldg 7405.Secured Break in Water Line & Pumped Down Water in Subject Lift Station ML20210L1191997-05-12012 May 1997 NPDES Noncompliance Notification:On 970506,discovered Exceedance of Fecal Coliform.Caused by Insufficient Levels of Chlorine,Compounded by High Level of Nitrite.Increased Level of Chlorine & Performed Addl Monitoring ML20210L1471996-10-21021 October 1996 NPDES Noncompliance Notification:On 961015,exceedance of Fecal Coliform Limits Occurred.Caused by Elevated Nitrite Levels.Increased Chlorine Levels ML20210L1651996-10-14014 October 1996 NPDES Noncompliance Notification:On 961010,Wastewater Collection Basin,Outfall 005,experienced Failure of Chronic Toxicity. Caused by Fertilizer Placed in Close Proximity of Waste Water Collection Basin.Will Retest Discharge 005 ML20210L1921996-05-0202 May 1996 NPDES Noncompliance Notification:On 960430,sandfilter by-pass on WT Sanitary Treatment Sys Occurred.Caused by Personnel Performing Needed Repairs Due to Heavy Rains.Sys Returned to Operable Status on 960430 ML20106H0121996-03-13013 March 1996 NPDES Noncompliance Notification:On 960219,C02 Sys Failed to Perform & Automatic Shutoff Valve Out of Svc.Shuttoff Valve Repaired & Discharge of Settling Pond B Discontinued ML20072Q1021994-08-25025 August 1994 Follow-up Emergency Notice of Reportable Superfund Amends & Reauthorization Act Release:On 940726,approx 33 Lb of Hydrazine Released to Environ.Special Drum Hand Truck Ordered & Appropriate Personnel Trained on Proper Use ML20059E3831993-10-26026 October 1993 Follow-up to NPDES Noncompliance Notification:On 931006,12 & 19,fecal Coliform Exceedances Occurred at Outfall 003 Due to High Chlorine Demand from Nitrate Interference & Seasonal Turnover in Lagoon.Sandfilter Pumps Modified ML20046D2241993-08-0404 August 1993 Followup to NPDES Noncompliance Notification:On 930721, Notified of Failure of Chronic Toxicity Test on Combined Samples Collected from Waste Water Collection Basin,Outfall 005 on 930713 & 19.Unwatering Process Initiated on 930717 ML20045E9361993-06-25025 June 1993 NPDES Noncompliance Notification:On 930610 Discovered That Leaking Antifreeze Solution Had Reached Floor Drain at Plant Garage Facility,As Result of Pinhole Leak in Cracked Fitting of Ethylene Glycol Storage Tank ML20044H1811993-06-0101 June 1993 Corrected NPDES Noncompliance Notification Re Exceeding Chlorine Effluent Limitations on Outfall 001.No Chlorine Monitoring Equipment Violations Occurred at Outfall 003 for Sept 1992 ML20044C6131993-04-0101 April 1993 NPDES Noncompliance Notification:On 930322,discovered That Sanitary Sys Manway Overflowed Approx 100 Gallons of Sewage Onto Ground.On 930324 & 25,pumps Experienced Problems Keeping Up W/Vol of Influent.Sand Filter Bypassed ML20081F4461991-06-0303 June 1991 NPDES Noncompliance Notification:On 910521,soil Around Tank B,Outside Fence,Had Gasoline Odor.On 910522,soil Around Tank A,Inside Fense,Had Gasoline Odor.Soil Samples Will Be Obtained within Next 3 Wks ML20028H7231991-01-23023 January 1991 NPDES Noncompliance Notification:On 901108,water Containing Hydrazine Released to Floor Drain Discharging Into Station Wastewater Collection Basin.Problem Investigation/Station Problem Repts Initiated to Reroute Floor Drains ML19332G0541989-11-27027 November 1989 NPDES Noncompliance Notification Rept for Oct 1989.On Two Occasions,Total Residual Chlorine Exceeded 0.2 mg/1 Concentration Limitation at Outfall 001 & 2 H Time Limit for Discharging Chlorine Exceeded.Investigation Underway ML20155D2681988-06-0808 June 1988 NPDES Noncompliance Notification:On 880531,conventional Wastewater Treatment Sys Discharge Exceeded Std 9.3 Units. Caused by Malfunction of Addition Sys.Discharge Immediately Terminated & Ph Found Above Limitations ML20236N5291987-11-0909 November 1987 NPDES Noncompliance Notification:On 871016,solution Began Leaking Through Check Valve,During Process of Filling Steam Generator W/Water Containing Hydrazine.Caused by Clogged Floor Drain in Structure.Release Posed No Threat to Public ML20245C7651987-10-30030 October 1987 Noncompliance Notification:On 871007,daily Max BOD Limit of 45.0 Mg/L Exceeded at Sanitary Waste Treatment Sys (Outfall 003).Analysis Result 51.0 Mg/L.Cause Attributed to Cooler Weather.Corrective Action:Aeration Patterns Changed ML20128A6261985-06-24024 June 1985 NPDES Noncompliance Notification:On 850612-18,fecal Coliform in Sewage Treatment Sys Discharge Exceeded Weekly Average of 2000/ml.Caused by Chlorine Demand in Tertiary Treatment Pond.Chlorine Contact Chamber Planned to Replace Pond ML20125B5851985-06-0505 June 1985 NPDES Noncompliance Notification:On 850531,hydrazine & Ammonium Hydroxide Inadvertently Released to Collection Basin to Catawba River Via Turbine Bldg Sump.Turbine Bldg Sump Routed to Treatment Facility ML20106F3711985-02-0808 February 1985 NPDES Noncompliance Notification:On 850204,pH of Effluent Discharged from Conventional Wastewater Treatment Facility 5.6.Caused by Malfunctioning of Carbon Dioxide Addition Sys Allowing CO2 Addition.Flow to Ph Controller Reestablished ML20042C5071982-03-0505 March 1982 NPDES Noncompliance Notification:On 820302,unknown Amount from Wastewater Collection Basin Discharged Into Catawba River.Wastewater Exceeded 9.0 Std Units Ph.Monitoring Frequency Increased.Excursion Caused by Photosynthecism 1998-08-10 Category:TEXT-ENVIRONMENTAL REPORTS MONTHYEARML20212A8451999-09-14014 September 1999
[Table view]Environ Assessment & Finding of No Significant Impact. Proposed Action Would Exempt McGuire Nuclear Station from Certain Requirements of 10CFR50 ML20207C8241998-12-31031 December 1998 Annual Occupational Radiation Exposure Rept for 1998, for McGuire Nuclear Station ML20206F3381998-12-31031 December 1998 1998 Annual Radioactive Effluent Release Rept for McGuire Nuclear Station ML20206H9061998-12-31031 December 1998 Annual Radiological Environ Operating Rept for 1998. with ML20209G5381998-12-31031 December 1998 Amend to Annual Radioactive Effluent Release Rept for 1998 for McGuire Nuclear Station ML20237B5041998-08-10010 August 1998 NPDES Noncompliance Notification:On 980720,lightning Caused Relay Failure on Conventional Waste Sys Lift Station IW-6 Which Caused Pumps to Shut Off.Caused by OOS Alarm Sys.Pumps Were Manually Cycled Until Power Could Be Restored ML20217M6151997-12-31031 December 1997 Annual Radiological Environ Operating Rept for 1997, for McGuire Nuclear Station Units 1 & 2 ML20209G5221997-12-31031 December 1997 Amend to Annual Radioactive Effluent Release Rept for 1997 for McGuire Nuclear Station ML20199D0031997-12-31031 December 1997 Lake Norman:1997 Summary Maintenance Monitoring Program McGuire Nuclear Station:Npdes NC0024392, Dtd Dec 1998 ML20203J8761997-12-31031 December 1997 DPC - McGuire Nuclear Station Tabulation of Number of Personnel & Person-Rem by Work & Job Fuction for 1997 ML20198P0451997-12-31031 December 1997 Lake Norman Creel Survey ML20217N8481997-12-31031 December 1997 Annual Radioactive Effluent Release Rept for 1997 for McGuire Nuclear Station ML20198P0381997-12-31031 December 1997 Lake Norman:1996 Summary,Maintenance Monitoring Program McGuire Nuclear Station:Npdes NC0024392 ML20217J4811997-08-0808 August 1997 Environ Assessment & Finding of No Significant Impact Re Proposed Action Amending Licenses to Reflect Licensee Name Change from Duke Power Co to Duke Energy Corp ML20149J4241997-07-24024 July 1997 Environ Assessment & Finding of No Significant Impact Re Proposed Action to Exempt DPC from Requirements of 10CFR70.24,which Requires Monitoring Sys That Will Energize Audible Alarms If Accidental Criticality Occurs ML20210L1101997-05-15015 May 1997 NPDES Noncompliance Notification:On 970513,overflow of Industrial Waste-2 Lift Station Occurred.Caused by Ruptured Water Main Feeding in Basement of Bldg 7405.Secured Break in Water Line & Pumped Down Water in Subject Lift Station ML20210L1191997-05-12012 May 1997 NPDES Noncompliance Notification:On 970506,discovered Exceedance of Fecal Coliform.Caused by Insufficient Levels of Chlorine,Compounded by High Level of Nitrite.Increased Level of Chlorine & Performed Addl Monitoring ML20138H4111996-12-31031 December 1996 Annual Radiological Environ Operating Rept for 1996 ML20133F1861996-12-31031 December 1996 Lake Norman:1995 Summary Maint Monitoring Program McGuire Nuclear Station:Npdes NC0024392 ML20140G8271996-12-31031 December 1996 Annual Radioactive Effluent Release Rept for 1996 ML20135C3211996-12-31031 December 1996 Tabulation of Number of Personnel & Person-Rem by Work & Job Function for 1996 ML20210L1471996-10-21021 October 1996 NPDES Noncompliance Notification:On 961015,exceedance of Fecal Coliform Limits Occurred.Caused by Elevated Nitrite Levels.Increased Chlorine Levels ML20210L1651996-10-14014 October 1996 NPDES Noncompliance Notification:On 961010,Wastewater Collection Basin,Outfall 005,experienced Failure of Chronic Toxicity. Caused by Fertilizer Placed in Close Proximity of Waste Water Collection Basin.Will Retest Discharge 005 ML20115B5741996-07-0303 July 1996 Environ Assessment & Finding of No Significant Impact Re Issuance of Amends to Licenses NPF-9 & NPF-17 to Change FSAR That Would Delete Seismic Qualification Requirement for Containment Atmosphere Particulate Radiation Monitors ML20210L1921996-05-0202 May 1996 NPDES Noncompliance Notification:On 960430,sandfilter by-pass on WT Sanitary Treatment Sys Occurred.Caused by Personnel Performing Needed Repairs Due to Heavy Rains.Sys Returned to Operable Status on 960430 ML20106H0121996-03-13013 March 1996 NPDES Noncompliance Notification:On 960219,C02 Sys Failed to Perform & Automatic Shutoff Valve Out of Svc.Shuttoff Valve Repaired & Discharge of Settling Pond B Discontinued ML20107M0151995-12-31031 December 1995 Annual Radiological Environ Operating Rept 1995. W/ ML20100H5091995-12-31031 December 1995 DPC MNS Tabulation of Number of Personnel & Person-Rem by Work & Job Function for 1995 ML20101J1931995-12-31031 December 1995 Annual Radioactive Effluent Release Rept ML20087K1051995-08-17017 August 1995 Environ Assessment & Finding of No Significant Impact Re Proposed Action That Would Change TS to Allow Max Enrichment for Fuel Stored in Fuel Pools to Increase from Nominal Value of 4.0 to 5.0 Weight Percent U-235 ML20096E9301994-12-31031 December 1994 Lake Norman:1994 Summary Maint Monitoring Program McGuire Nuclear Station:Npdes NC0024392 ML20087J2071994-12-31031 December 1994 Annual Environ Operating Rept for CY94 ML20082Q8141994-12-31031 December 1994 Annual Radiological Environ Operating Rept 1994 ML20082L1911994-12-31031 December 1994 Annual Radioactive Effluent Release Rept 1994 ML20080H8471994-12-31031 December 1994 Personnel Monitoring Rept for CY94 ML20072Q1021994-08-25025 August 1994 Follow-up Emergency Notice of Reportable Superfund Amends & Reauthorization Act Release:On 940726,approx 33 Lb of Hydrazine Released to Environ.Special Drum Hand Truck Ordered & Appropriate Personnel Trained on Proper Use ML20096E9211994-03-0101 March 1994 Habitat Selection of Striped Bass in Lake Norman, Final Rept ML20078A1781993-12-31031 December 1993 Annual Lake Norman Environ Summary Rept for 1993 ML20029C7351993-12-31031 December 1993 Duke Power Company McGuire Nuclear Station Units 1 & 2 Annual Radiological Environ Operating Rept 1993 ML20059F0171993-12-31031 December 1993 Lake Norman 1992:Summary Maint Monitoring Program Rept ML20065E8961993-12-31031 December 1993 Radioactive Effluent Release Rept for 1993 ML20063L5361993-12-31031 December 1993 Tabulation of Number of Personnel & Person-Rem by Work & Job Function for 1993 ML20059E3831993-10-26026 October 1993 Follow-up to NPDES Noncompliance Notification:On 931006,12 & 19,fecal Coliform Exceedances Occurred at Outfall 003 Due to High Chlorine Demand from Nitrate Interference & Seasonal Turnover in Lagoon.Sandfilter Pumps Modified ML20046D2241993-08-0404 August 1993 Followup to NPDES Noncompliance Notification:On 930721, Notified of Failure of Chronic Toxicity Test on Combined Samples Collected from Waste Water Collection Basin,Outfall 005 on 930713 & 19.Unwatering Process Initiated on 930717 ML20045E9361993-06-25025 June 1993 NPDES Noncompliance Notification:On 930610 Discovered That Leaking Antifreeze Solution Had Reached Floor Drain at Plant Garage Facility,As Result of Pinhole Leak in Cracked Fitting of Ethylene Glycol Storage Tank ML20044H1811993-06-0101 June 1993 Corrected NPDES Noncompliance Notification Re Exceeding Chlorine Effluent Limitations on Outfall 001.No Chlorine Monitoring Equipment Violations Occurred at Outfall 003 for Sept 1992 ML20035H2881993-04-22022 April 1993 Annual Environ Operating Rept,1992, Including Summaries & Analyses of Results of Activities Required by Section 4.2 of Environ Protection Plan (Epp),List of EPP Noncompliances & C/As & List of Changes in Station Design or Operation ML20044C6131993-04-0101 April 1993 NPDES Noncompliance Notification:On 930322,discovered That Sanitary Sys Manway Overflowed Approx 100 Gallons of Sewage Onto Ground.On 930324 & 25,pumps Experienced Problems Keeping Up W/Vol of Influent.Sand Filter Bypassed ML20034F1821992-12-31031 December 1992 Semiannual Radioactive Effluent Release Rept ML20126H9581992-12-30030 December 1992 Environ Assessment & Finding of No Significant Impact Re Rev to TS Concerning Limitations on Concentrations of Radioactive Matl Released in Liquid Effluents 1999-09-14 |
Text
-
f DUKE POWER GOMPANY NUGLEAR PRODUGTION DEPARTMENT P.O. DOX 33180,422 MOUTH CIfURCII HTHEET CitARLOTTE, N.C. 28242 (704) 373-4011 June 24, 1985 i
Division of Environmental Management Water Quality Section P.O. Box 27687 Raleigh, NC 27611 J
SUdJECT: Noncompliance Notification McGuire Nuc1 car Station FILE: MC-704.20
Dear Sir:
This is to notify you of a noncompliance incident at McGuire Nuclear Station.
Information related to the incident is as follows:
Discharge The discharge was the sewage treatment system discharge (discharge 003).
Cause The fecal coliform exceeded weekly average of' 2000/ml.
Date Dates were the week of June 12-18, 1985.
Prevention The current tertiary treatment pond is to be replaced with an appropri-ately sized chlorine contact chamber.
Summary-The tertiary treatment pond (TTP) provides too long a residence fo the sewage treatment effluent. With the hot, sunny weather, algae has ' pro-liferated. The chlorine demand of the TTP has increased until a residual cannot be maintained in the effluent.
Consequently, the fecal coliform weekly average was 2400/ml. The new chlorine contact chamber should al-leviate these problems.
Sincerely, W. A. Ha!ler, Manager f
Nuclear Technical Services
/
t I E j
8507020734 850624 PDR ADOCK 05000369 S
Division of Environmental Management Water Quality Section
SUBJECT:
Noncompliance Notification June 24, 1985 Page 2 WTG/LPH/wmc cc: Rex Gleason Harold R. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, D.C.
20555