CNE Carchna Power & Light Company -
,SEP 2 21992 SERIAL: NLS-92-210 10 CFR 50, Appendix E United States Nuclear Regulatory Commission ATTENTION: Document Control Desk Washington, DC 20555 H. B. ROBINSON STEAM ELECTRIC PLANT, UNIT NO.-2 DOCRET NO, 50-261/ LICENSE NO. DPR-23 EMERGENCY RESPONSE DATA SYSTEM - DATA POINT LIBRARY Gentlemen:
The purpose of this letter is to provide Carolina Power & Light Company's Data
-Point Library (DPL) for the H. B, Robinson Steam Electric Plant, Unit No. 2 (HBR2), This DPL submittal completes the Emergency Response Data System information requirements for HBR2 contained in NUREG-1394, Revision 1.
Should you have any questions regarding this subject, please contact Mr. Fred Emerson at (919) 546-7573.
Yours very truly, David C. McCarthy Manager Nuclear Licensing Section DBB/jbw Enclosure cc: Mr. S. D. Ebneter Mr. L W. Garner Ms. B. L Mozafari b2b LOO .
mmm-s - ---=mm - thhI 4 ,
ns e---....- + Street = P . O Box 1551 e h e e q *, N C ; 70c?
. N N Or m Z1M U21 E N ECC4 (1720cLU) hhk y
kDoh 0 0 61 PDR t- - -. _
~
4 u e. . A R A 4W f ' k EMERGENCY RESPONSE DATA SYSTEM (ERDS) IMPLEMENTATION HHBGEG-1394 REVISION 1 CRITICAL SAFETY FUNCTION PARAMETERS EDE H. B. ROBINSON NUCLEAR PROJECT DEPARTMENT ROBINSON UNIT 2 9
2
~
<lEg < - .= g e;.p g..
" - f w.
CRITICAL SAFETY FUNCTION _PARAMELERS FOR PRESSURIZED WATER REACTORS -
Safety Ennetion Parameter DescriDtion Pace Nuclear Instruments Nuclear Instruments, Power Range 1 Nuclear' Instruments, Intermediate Range 2 Nuclear Instruments, Soutce Range 3 Core Cooling Reactor Vessel Water Level 4 Highest Temperature at Core Exit 8 Saturation Temperature - Highest CET 9 Total Reactor Coolant Flow 10 Steara Generators Steam Generator A Water Level 13 Steam Generator B Water Level 14 Steam Generator C Water Level 15 Steam Generator A Pressure 16 Steam Generator B Pressure 17-Steam Generator C Pressure 18 Stm Gen A Main Feedwater Flow 19 Stm Gen B-Main Feedwater Flow 20 Stm Gen C-Main Feedwater Flow 21 Stm Gen A Auxiliary FW Flow 22 Stm Gen B Auxiliary FW Flow 23 Stm Gen C Auxiliary FW Flow- 24 Stm Gen A Inlet Temperature 25 Stm Gen B Inlet Temperature 26 Stm Gen C. Inlet Temperature 27 Stm Gen A Outlet Temperature 20 Stm Gen- B Outlet Tenperature 29 Stm Gen C Outlet Temperature 30 RCS Integrity Reactor Coolant System Pressure 31 Primary System Pressurizer Level 32 Primary System Charging or Makeup Flow 33 High Pressure Safety Injection Flow 35 Low Pressure Safety Injection Flow 37 Containment Sump Narrow Range-Level 38 Containment Sump Wide Range Level 39
(' .4 CRITICAL SAFETY FUNCTION PARAMETERS FOR PRESSURIZED WATER REACTORS Safety Function Parameter Description- Page Radioactivity. Radioactivity of Released Gases 40 Control Radioactivity of Released Liquids 50 Condenser Air Ejector Radioactivity 51 Radiation Level in the Containment 52 Rad Level of the RCS Letdown Line 54 Stm Gen A Steam Line Rad Level 55 Stm Gen B Steam Line Rad Level 56 Stm Gen C Steam Line Rad Level 57-Stm Gen A Blowdown Rad Level 58 Stm Gen.B Blowdown Rad Level 59 Stm Gen C Blowdown Rad Level 60 Containment Containment Pressure 61 Conditions Containment' Temperature 62 Containment Hydrogen Concentration 63 Miscellaneous Borated Water Storage Tank Level 64 Parameters Wind Speed at the Reactor Site 65 Wind Direction at the Reactor Site 67 Air Stability at the Reactor Site 69-
8 &
DATA POINT LIBRARY REFERENCE FILE Date: __f.,_f___
Reactor Unit: R02 Data Feeder: __ERFIS NRC ERDS Parameter: NI POVER RNC Point ID: NIN0001 Plant Spec Point Desc.: SPDS POVER RANGE AVEPAGE PERCENT POWER Generic /Cond Dese.: _b'UCLEAR INSTRUMENT POVER RANCE Analeg/ Digital: A Engr Units / Dig States: %
Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 120 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 4 How Processed: AVEPAGE Sensor Locations: REACTOR CORE Alarm / Trip Set Points: SEE UNIQUE SYSTEM DESCRIPTION NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: LO POVER RANGE HI FLUX - 24%
HIGH POWER RANGE HIGH FLUX - 108%
PVR RANGE OVERPOWER ROD VDRL STOP - 103%
PVR RANGE SINGLE CH HI RGE ALERT - 108%
92-1103A (1)
DATA POINT LIBRARY REFERENCE FILE Date: _.)._]_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: NI INTR RNC Point ID: NIN0004 Plant Spec Point Desc.: AVC INTERMEDIATE RANCE FLUX Generic /Cond Dese,: NUCLEAR INSTRUMENTATION. INTERMEDIATE RANGE Analog / Digital: A Engr Units / Dig States: AMP _
Engr Units Conversion: N/A Minimum Instr Range: .100E.10 Maximum Instr Range: .100E-02 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2
~
How Processed: AVERACE Sensor Locations: REACTOR CORE. MID PLANE Alarm / Trip Set Points: SEE UNIOUE SYSTEM DESCRIPTION NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Irstrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.; BLOCK IR TRIP VHEN PWR >10% (P-10)
IR TRIP CURRENT EOUIVALENT TO 25% FULL POWER IR HI FLUX LVL ROD VDRL STOP CURRENT EQUIVALENT TO 20%
t d
92-1103A (2)
DATA POINT LIBRARY REFERENCE FILE Date: JJ_
Reactor Unit: xv2 Data Feeder: ERFIS NRC ERDS Parameter: NI SOURC RNC Point ID: NIN0005 Plant Spec Point Dese.: AVG SOURCE PANGE FLUX Ceneric/Cond Desc.: NUCLEAR INSTRUMENT. SOURCE PANGE Analog / Digital: A Engr Units / Dig States: CPS Engr Units Conversion: N/A Minimum Instr Range: .100E+01 Maximum Instr Range: .100E+07 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: J How Processed: AVERACE Sensor Locations: REACTOR CORF. LOVER 1/3 CORE Alarm / Trip Set Points: SR HI FLUX TRIP 105 CPS NI Detector Power Supply Cut-off Power Level: _10% POWER RANGE NI Detector Power Supply Turn-on Power Level: 1040 AMPS INTERMEDIATE RANGE l Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER l Temperature Compensation For DP Transmitters.: N/A l Level Reference Leg: N/A Unique System Desc.:
1 92-1103A (3)
DATA POINT LIBRARY REFERENCE FILE Date: _/_/_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: REAC VES LEV Point ID: RCLO487 Plant Spec Point Dese.: RVLIS FULL RANCE A Generic /Cond Dese.: REACTOR VESSEL VATER LEVEL Analog / Digital: A Engr Units / Dig States: )
Engr Units Conversion:
Minimum Instr Range: 0 Maximum Instr Range: 120 Zero Point
Reference:
BOTTOM OF REACTOR VESSEL Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: AUXILIARY BUILDING Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: __F/A NI Detector Power Supply Turn on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: YES Level Reference Leg: WET Unique System Desc.: THIS DATA PROVIDES TO ERFIS VIA DATA LINK VITH P,EACTOR VESSEL-LEVEL INSTRUMENTATION SYSTEM 92-1103A (4)
DATA POINT LIBRARY REFERENCE FILE Date: ,__/_/_
Reactor Unit: R02 Data Peeder: ERFIS NRC ERDS Parameter: REAC VES LEV Point ID: RCLO490 Plant Spec Point Dese.: RVLIS FULL PANGE F Generic /Cond Dese,: REACTOR VESSEL VATER D. VEL Analog / Digital: A Engr Units / Dig States: 1 Engr Units Conversion:
Minimum Instr Range: 0 Maximum Instr Range: 120 Zero Point
Reference:
BOTTOM OF REACTOR VESSEL Reference Point Notes: N/A
~
PROC or SENS: P Number of Sensors: 1 How Processed: DIFJCT READING Sensor Locations: AUXILIARY BUILDING Alarm / Trip Set Points: N/A NI Detector Power Supply cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Te=perature Compensation For DP Transmitters: YES Level Reference Leg: VET Unique System Desc.: THIS DATA PROVIDED TO ERFIS VIA DATA LINK VITH REACTOR VESSEL LEVEL INSTRUMENTATION SYSTEM.
92-1103A (5)
DATA POINT LIBRARY REFERENCE FILE Date: __/ _/
Reactor Unit: _ _ . _
R02 Data Ferder: ERFIS NRC ERDS Parameter: REAC VES LEV Point ID: RCLO488 Plant Spec Point Dese.: RVLIS DYNAMIC HEAD A Generic /Cond Desc.: REACTOR VESSEL VATER LEVEL Analog / Digital: A Engr Units / Dig States: 1 Engr Units Conversion:
Minimum Instr Range: 0 Maximum Instr Range: 120 Zero Point
Reference:
COMPLX Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: AUXILIARY BUILDING Alarm / Trip Set Points: N/A NI Detector Power Supply cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: YES Level Reference Leg: WET Unique System Desc.* MEASURES PRESSURE DROP ACROSS THE CORE WITH RCPs RUNNING. THIS DATA INVALID VITH NO RCPs R_UNNING. THIS DATA PROVIDED TO , , BY DATA LINK VITH l REACTOR VESSEL LEVEL INSTRUMENTATION
- SYSTEM.
92-1103A (6)
DATA POINT LIBRARY REFERENCE FILE Date: JJ_
Reactor Unit: R02 _.
Data Feeder: ERFIS NRC ERDS Parameter: REAC VES LEV Point ID: RCLO491 Plant Spec Point Desc.: RVLIS DYNAMIC HEAD B _
Ceneric/Cond Desc.: REACTOR VESSEL VATER LEVEL Analog / Digital: A Engr Units / Dig States: %
Engr Units Conversion:
Minimum Instr Range: 0 Maximum Instr Range: 120 D ro Point
Reference:
COMPLX ,
Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: AUXILIARY BUILDING Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = PAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: YES Level Reference Leg: _k" T Unique System Desc.: MEASURES PRESSURE DROP ACROSS THE CORE VITH RCPs RUNNINC. THIS DATA INVALID WHEN NO RCPs RUNNING. THIS DATA PROVIDED TO ERFIS VIA DATA LINK WITU REACIOR VESSEL LEVEL INSTRUMENTATION SYSTEM.
92-1103A (7)
DATA POINT LIBRARY REFERENCE FILE Date: __)_ ]._
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: TEMP CORE EX Point ID: P_XT0v01 Plant Spec Point Desc.: AVG OF 5 HOTTEST THERMOCOUPLES Generic /Cond Desc.: HIGHEST TEMPERATURE AT CORE EXIT Analog / Digital: A Engr Units / Dig States: DEGF Engr Units Conversion: N/A Minimum Instr Range: 32 Maximum Instr Range: 1500 Zero Point
Reference:
N/A _
Reference Point Notes: N/A PPOC or SENS: P Number of Sensors: 5 How Processed: AVEPAGE OF 5 HIGHEST INCORE THERMOCOUPLES -
Sensor Locations: CORE EXIT larm/ Trip Set Points: N/A NI Detector Power Supply cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: QUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitecrs: N/A Level Reference Leg: N/A Unique System Desc.: CORE EXIT THERMOCOUPLE DATA IS PROVIDED TO ERFIS VIA DATA LINK TO INADEOUATE CORE COOLING MONITOR (ICCM).
i 92-1103A _ _ _ _ _ _ _ _ _ _ _ _
(8)
Date: ,,_,/_,,_/,,,,,,
Reactor Unit: R02 Data Feeder: ERFIS ENRC ERDS Parameter: SUB MARCIN Point ID: RCT0003 Plant Spec Point Desc.: RCS SUBC00 LING
' Generic /Cond Desc.: SATURATION TEMPERATURI - HICHEST CET-Analog /bigital: A Engr Units / Dig , States: DECF Engr Units Conversion: N/A Minimum Instr Range: -100 Maximum Instr Range: +100 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 6 How Processed: SEE UNIOUE SY3 TEM DESC.
Sensor Locations: SEE UNIOUE SYSTEM DESC. .
Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply
. Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Dese.: THE FOLLOVING INPUTS ARE USED AVERACE TEMF OF 5 HIGHEST CORE EXIT THERMOCOUPLE. RCS VIDE RANCE PRESSURE TRANS. THOT FROM VIDE RANCE HOT LEG RTD'S.
92-1103A (9)
DATA. POINT LIBRARY REFERENCE FILE Date: _ _/__/__.
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: CORE FLOW Point ID: _RCF0400A Plant Spec Point Desc.: FT-414 RC LOOP 1 FLOW Generic /Cond Desc.: TOTAL REACTOR COOLANT FLOW Analog / Digital: A Engr Units / Dig States: %
Engr Units Conversion:
Minimum Instr Range: 0 Maximum Instr Range: 120 Zero Point
Reference:
N/A Reference Point Notes: dyA PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: A LOOP COLD LEG AT DISCHARGE OF SG Alarm / Trip Set Points: 91% OF FULL FLOW NI Detector Power Supply Cut-off Power Level: N/J NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY - BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.:
92-1103A (10)
. . DATA POINT LIBRARY REFERENCE FILE Date: _/_/_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: CORE FLOW Point ID: RCF0420A Plant Spec Point Desc.. FT-424 RC LOOP 2 FLOV Ceneric/Cond Desc.* TOTAL REACTOR COOLANT FLOW Analog /Digita A __
Engr Units / Dig States: %
Engr Units Converr. ion:
Minimum Instr Range: 0 _
Maximum Instr Range: 120 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 llow Processed: DIRECT READING Sensor Locations: B LOOP COLD LEG AT DISCHARGE OF S/G Alarm / Trip Set Points: 91% OF FULL FLOW NI Detector Power Supply Cut-off Power Level: __N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.
92-1103A (11)
j DATA POIllT LIBRARY REFEREllCE FILE Date: J_f_
Reactor Unit: R02 Data Feeder: _EPFIS NRC ERDS Parameter: CORE FLOV Point ID: RCF0440A Plant Spec Point Desc.: FT-434 RC LOOP 3 FLOW Generic /Cond Desc.: TOTAL REACTOR COOLANT FLOW Analog / Digital: A Engr Units / Dig States: %
Engr Units Conversior:
Minimum Instr Range- O _
Maximum Instr Range: 120 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Seasor Locations: C LOOP COLD TEG AT DISCHARGE OF S/G Alarm / Trip Set Points: 91% OF FULL FLOW NI Detector Power Supply Cut-of f Power Lenl: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: _ _0UALITY == BAD 09 o JAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc..
92-1103A (12)
DATA POINT LIBRARY REFERENCE FILE Date: _/J_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: SC LEVEL A Point ID: FVLO403A Plant Spec Point Desc.: LT-477 S/G A VIDE RANGE _ LEVEL Generic /Cond Desc., STEAM CENERATOR A VATER LEVEL ,
Analog / Digital: A Engr Units / Dig States: %
Engr Units Conversion: N/A Minimum Instr Range: 0 Maximam Inser Range: 100 Zero Point
Reference:
TUBSHT Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: ALONG SIDE A STM GEN, IN CV Alarm / Trip Set Points: HI LVL ALARM - 88%. LO LVL ALARM 67%
NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Lovel: N/A .
Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: WET Unique System Desc.' LO LVL ALARM BLOCKED IF SC PRESS
>614 PSIC.
92-1103A (13)
DATA POINT LIB;'ARY REFERENCE FILE Date: _ /___/ _ l l
Reacto Jnit : R02 )
I Data Feeder: ERFIS __.
NRC ERDS Parameter: SC LE'TEL B _
Point ID: FWLO423A Plant Spec Point Desc.: LT-487 S/G B VIDE RANCE LEVEL Generic /Cond Desc.: STEAM CENERATOR B UA_TER LEVEL Analog / Digital: A Engr Units / Dig States: %
Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 100 Zero Point
Reference:
TUBSHT Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: ALONG SIDE B STM CEN. IN CV Alarm / Trip Set Points: HI LVL ALARM - 88%. LO LVL ALAPJi 67%
NI Detector Power Supply Cut-off Power Level: N/A _
NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY - BAD OR NCAL OR RDER Temperature Compensation For DP Transmittecs: N/A Level Reference Leg: WET Unique System Desc.: LO LVL ALARM BLOCKED IF SG PRESS
___F14 PSIG.
92-1103A (14)
DATA POINT LIBRARY REFERENCE FILE Date: JJ_ \
Reactor Unit: R02 Data Feeder: EFFIS.
NRC ERDS Parameter: SG 1.EVEL C Point ID: FVIA443A Plant Spec Point Desc.: LT-497 S/0 C VIDE RANGE LEVEL Generic /Cond Dese.: S UAM CERERATOR C VATER Analog / Digital: A _ _
Engr Units / Dig States: 1 Engr Units Conversion: N/A Minimum Instr Range: 0 _
Maxime. Instr Range: 100 Zero Point
Reference:
TUBSHT _
Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 llow Processed: _ DIRECT READING _
Sen_. Locations: _ ALONG SIDE C STM CEN. IN CV Alarm / Trip Set Points: HI LVL AIARM 88%. LO LVL ALARM 67C NI D..tector Power Svpply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Trans=itters: N/A Level Reference Leg: VET Unique System Desc.: LO LVL AIARM BLOCKED IF S/C PRESS
>614 PSIC. ,
92-1103A (15) .
_. _ _ . .. __ = - . . -. . _ _ - - ._. .. .
DATA POINT LIBRARY REFERENCE FILE Date: JJ_
l Reactor Unit: R02 Data Peeder: ERFIS NRC EkDS Parameter: SC PRESS A Point ID: MSP0007 Plant Spec Point Dese.: AVG STM GEN A STEAM PRESSURE I Generic /Cond Dese.: STEAM CENERATOR A PRESSURE Analog / Digital: A Engr Units / Dig States: PSIG Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 1400 Zero Poi..
Reference:
N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 3 ,
P'v Processed: AVERACE Gensor Locations: 2ND LEVEL TURBINE BLDC.
Alarm / Trip Set Points: N/A l
NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply l Turn-on Power Level: N/A ,
l- Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A _
Level Reference Leg: N/A Unique System Dese.: SUPPLIED BY pts 474. 475. 476 l THESE HAVE INPUT TO STRAM PRESSUPl INDICATION. S/G LEVEL CONTROL.
RFACTOR PROTECTION.
G2-1103A (16) . .
DATA POINT LIBRARY REFERENCE FILE Date: __/ J ._
. Reactor Unit: R02 Data Feeder: ERLIS NRC ERDS Parameter: SC PRESS B Point ID: MSP0008 Plant Spec Point Desc.: AVG STM GEN B STEAM PRESSURE Generic /Cond Desc.: STEAM CENERATOR B PRESSURE Analog / Digital: A Engr Units / Dig States: PSIG Engr Units Con *Srsion: N/A Minimum Instr Range: 0 Maximum Instr Range: 1400 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 3 How Processed: AVERAGE Sensor Locations: 2NB IIVEL _ TURBINE BLDC.
Alarm / Trip Set Points: N/A i NI Dermeter Power Supply Cut orf Powee Level: N/A NI Detector Power Supply l Turn on Power Level: OUALITY = BAD.OR NCAL OR RDER Instrument Failure Mode: N/A l Temperature Compensation l For DP Transmitters: N/A Level Reference Leg: SUPPLIED BY pts 484. 485. 486 !
Unique System Desc.: THESE RAVE INPUT TO STEAM PRESSURE INDICATION, S/C L7, VEL CONTRQL, REACTOR-PwoTECTION.
l 92-1103A -_. -
(17) -. . _
DATA POINT LIBRARY REFERENCE FILE Date: ,_/,_/,,,,,
Reactor Unit: R02 Data Feeder: ___EPFIS P.C ERDS Parameter: _SG PRESS C Point ID: MSP0009 Plant Spec Point Dese.: AVG STM CEN C STEAM PRESSURE Generic /Cond Desc.: ,_ STEAM CENERATOR C PRESSURE Analog / Digital: .. A Engr Units / Dig States: PSIG Engr Units Conversion > N/A Minimum lastr Range: 0 Maximum Instr Range: 1400 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 3 How Processed: _ y. ]tAGE Sensor Locations: 2ND LEVEL TURB BLDG, Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Coaipensation For DP Transmitters: N/A' Level Reference Leg: N/A Unique System Desc.: SUPPLIED BY PT'S 494 495. 496 THESE HAVE INPUT TO STEAM PRESSURE INDIC_ATION. S/G LEVEL CONTROL PIACTOR PROTECTION 92-1103A (18)
DATA POINT LIBRARY REFERENCE FILE i
i Date: _f._.]_
Reactor Unit: R02 Data. Feeder: ERFIS NRC ERDS Parameter: MN FD FL A Point ID: TVPM03A Plant Spec Point Dese.: FT 476 S/G A FEEDVATER FLOV Generic /Cond Desc.: STM GFJ A MAIN FEEDVATER FLOV Analog / Digital: A Engr Units / Dig States: MLBH Engr Units Conversion: N/A Minimum Instr Range: 0.000 Maximum Instr Range: 4.000 Zero Point
Reference:
N/A Reference Point Notes: N/A
. PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING ,
Sensor Locations: 2ND LEVEL, TURBINE BLDO, Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: NO Level Reference Leg: N/A Unique System Desc.:
9?-1103A (19)
DATA POINT LIBRARY REFERENCE FILE Datc: _JJ_
Reactor Unit: _ R02 l
Data Feeder: _ ERFIS I
)
NRC ERDS Parameter: MN FD FL B Point ID: FVT0423A __
Plant Spec Point Desc.: FT-486 S/c B FEFDVATER m FLOV Cener;c/Cond Desc.: STM CEN B MAIN FEEDVAIER FLOV Analog / Digital: A Engr Units / Dig States: MLBH Engr Units Conversion: N/A Minimum Instr Range: _0.000 Maximum Instr Range: 4,000 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 llow Processed: DIRECT READING Sensor Locations: 2ND LEVEL TURBINE BLDC.
Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: NO Level Reference Leg: N/A Unique System Dese.:
I l
92-1103A (20)
DATA POINT LIBRARY REFERENCE FILE Date: J _/,_,
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: MN FD FL C Point ID: TVF0443A Plant Spec Point Desc.: FT.496 S/G C FEEDWATER TLOV Ceneric/Cond Desc.: STM CEN C MAIN FEEDVATER FLOV Analog / Digital: _A Engr Units / Dig States: MLBH Engr Units Conversion: N/A Minimum Instr Range: 0.000 Maximum Instr Range: 4.000 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: 2ND LEVEL TURBINE BLDC.
Alarm / Trip Se. Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: NO Level Reference Leg: N/A Unique System Desc.:
92-1103A s21)
DATA POINT LIBRARY REFERENCE FILE Date: .__/._f.__
Reactor Unit: R02 Data Feeder: J.R FIS _
URC ERDS Parameter: AX_FD FL A Point ID: .AFF0002 Plant Spec Point Dese : TOTAL AFV FLOW TO S/G A Generic /Cond Desc.: STM CEN A AUXILIARY FW FLOV Analog / Digital: A Engr Units / Dig ates: CPM Engr Units Conversion: N/A Minimum Instr Range: 0 .
Maximum Instr Range: _,1000 Zero Point
Reference:
N/A .
Reference Point Notes:
^
PROC or SENS: P Number of Sensors: 2 How Processed: _ ADD Sensor Locations: TURBINE BLDG Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY - BAD OR NOAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: . yf A Unique System Desc.: SUPPLIED BY FT-1425A AND FT-1426A.
92 1103A (22)
DATA POINT LIBRARY REFERENCE FILE Date: / ,_/_,
Reactor Unit: R02 Esta Feeder: ERFIS KRC ERDS Parameter: AX FD FL B Point ID: AFF0003 Plant Spec Point Desc.: TOTAL AFV FLOV TO S/G B Generic /Cond Desc.: STM GEN B AUXIIIARY FV FLOV Analog / Digital: A Engr Units / Dig States: .GPM Engr Units Conversion: N/A Minimum Instr Range: 0 Maximue Instr Range: 1000 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: ADD Sensor Locations: _lURBINE BLDG Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALIII - BAD OR NCAL QR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: SUPPLIED BY FT-1425B AND FT-1426B.
92-1103A (23)
DATA P0 INT LIBRARY REFERENCE FILE Date: }_ J.,_.
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: AX FD FL C Point ID: AFF0003 Plant Spec Point Desc.: . TOTAL AFV FLOV TO S/C C Generic /Cond Dese.: STM GEN C AUXILTARY FV FI4V Analog / Digital: A Engr Units / Dig States: GPM ,
Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 1000 Zero Point
Reference:
_N/A _
Reference Point Hotes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: ADD Sensor Locations: TURBINE BLDG -
Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Dese.: SUPPLIED BY FT-1425C AND FT-1426C.
92-1103A (24)
DATA POINT LIBRARY REFERENCE FILE Date: /J_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERLS Parameter: lit TEMP A ,
Point ID: RCT0419A Plant Spec Point Desc.: TE 413 LOOP 1 V/R 110T LEG TEMP Generic /Cond Desc.: STM GEN A INLET TEMPERATURE _.
Analog / Digital: A Engr Units / Dig States: DECF Engr Units Conversion: N/A Mitgmum Instr Range: 0 Maximum Instr Range: 700 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 llow Processed: DIPICT READING Sensor Locations: LOOP A 110T LEC. !NSIDE CV Alarm / Trip Set Points: , N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.:
92-1103A (25)
DATA POINT LIBRARY REFERENCE FILE Date: ,,,__/J_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: IIL TEMP B Point ID: RCT0439A' Plant Spec Point Desc.: TE-423 LOOP 2 V/R HOT LEG TEMP Ceneric/Cond Dese.: STM CEN B INLET TEEPERATURE Analog / Digital: A Engr Units / Dig States: DECF Engr Units Conversion: - N/A Minimum Instr Range: ,
O Maximum Instr Range: 700 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 llow Processed: DIRECT READING Sensor Locations: LOOP B 110T I.EC. INSIDE CV Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: . N/A .
NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY - BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.:
92-1103A (26) _
i i
DATA POINT LIBRARY REFERENCE FILE Date: JJ_ l Reactor Unit: R02 Data Feeder: EPFIS NRC ERDS Parameter: HL TEMP C Point ID: RCT0459A Plant Spec Point Desc.: TE-433 LOOP 3 V/R HOT IIG TEMP ,
Generic /Cond Desc.: STM GEN C W/T, HOT LEG TEMPERATURE Analog / Digital: A Engr Units / Dig States: DEGF Engr Units Convqrsion: N/A Minimum Instr Range: 0 Maximum Instr Range: 700 Zero Point
Reference:
__N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READINO Sensor Locations: LOOP C HOT LEG, INSIDE CV '
Alarm / Trip Set Points: N/A i
NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A l Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER 1
1 Temperature Compensation For DP Transmitters: N/A l Level Reference Leg: N/A l Unique System Dese.:
1 i
92-1103A (27)
DATA POINT LIBRARY REFERENCE FILE Date: _]_]_
Reactor Unit: R02 Data Feeder: EFFIS NRC ERDS Parameter: CL TEMP A Point ID: _RCT0406A Plant Spec Point Desc.: TE-410 LOOP 1 V/R COLD LEG TEMP.
Generic /Cond Desc.: STM GEN A OUTLET TEMPERATURE Analog / Digital: A Engr Units / Dig States: DEGF Engr Units Conversion: N/A Minic:um Instr Range : 0 Maximum Instr Range: 700 Zero Point
Reference:
N/A-Reference Point Notes: N/A _
PROC or SENS: S Number of Sensors: 1 _
1;;v Processed: DIRECT READING i Sensor Locations: LOOP A COLD. LEG. INSIDE CV l
Alarm / Trip Set Fointa: N/A NI Detector Power Supply Cut-off Power Level: N/A j NI Detector Power Supply Turn-on Power Level: N/A _
- Instrument Failure Mode
- OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference '*g: N/A Unique Syst'm De ..:
1 l
92-1103A ( 2 0, ) .
DATA POINT LIBRARY REFERENCE FILE Date: _/J_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: CL TEMP B Point ID: RCT0426A Plant Spec Point Dese.: TE-420 LOOP 2 V/R COLD LEC TEMP Ceneric/Cond Desc.: STM GEN B OUTLET TEMPERATURE Analog / Digital: A Engr Units / Dig States: DECF Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 700 Zero roint
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: LOOP B COLD LEC. INSIDE CV Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER j Temperature Compensation l For DP Transmitters: N/A Level Reference Leg: N/A l
Unique System Dese.:
92-1103A (29)
DATA POINT LIBRARY REFERENCE FILE Date: JJ_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: CL TEMP C Point ID: RCT0446A Plant Spec Point Desc.: TE-430 LOOP 3 V/R COLD LEC TEMP Ceneric/Cond Desc.: STM CEN C OUTLET TEMPERA *[URE _
Analog / Digital: A Engr Units / Dig States: DECF Engr Units Conversion: P/A Minimum Instr Range: 0 Maximum Instr Range: 700 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: LOOP C COLD LEC. INSIDE CV '
Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY - BAD OR NCAL OR PSER Temperature Compensation For DP Transmitters: 14/A Level Reference Leg: N/A Unique System Dese.:
92-1103A (30) _ _ _ _ _ _ _ - .
DATA POINT LIBRARY REFERENCE FILE Date: J_f_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: RCS PRESSURE Point ID: RCPO493A Plant Spec Point Desc.: PT-500 PRESSURIZER PRESURE Generic /Cond Desc,- REACTOR COOLANT SYSTEM PRESSURE Analog / Digital: _A Engr Units / Dig States: ____ PS IC Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 3000 Zero Point
Reference:
N/A Reference Point Notes: F/A ,
PROC or SENS: S Number of Sensors: 1
~
How Processed: . DIJ_ECT READING Sensor locations: ALONG PZR, INSIDE CV Alarm / Trip Set Points: SEE UNIOUE SYSTEM DESC NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mod : OUALITY - BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.' THIS PT FEEDS TO LOW TEMP - HI PRESS PROTECTION WHICH OPEN A PZR PORV AT 400 PSIG VHEN SELECTED 92-1103A (31)
DATA POINT LIBRARY REFERENCE FILE Date: ,_) _)._
Reactor Unit: R02 Data Feeder: EBFIS NRC ERDS Parameter: PRZR LEVEL Point ID: P.CL0006 _
Plant Spec Point Desc.: AVERACE PRESSURIZFR LEVEL Ceneric/Cond Dese,: PRIMARY SYSTEM PRESURIZER 12 VEL Analog / Digital: A Engr Units / Dig States: %
Engr Units Conversion: . N/A Minimum Instr Range: 0 Maximum Instr Range: 100 Zero Point
Reference:
BOTTOM OF PRESSURIZER Reference Point Notes: N/A __
PROC or SENS: P Number of Sensors: 3 How Processed: SEE UNIOUE SYSTEM DESC.
Sensor Locations: ALONG PZR. INSIDE CV l Alarm / Trip Set Points: SEE UNIOUE SYSTEM DESC.
NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply
, Turn-on Power Level N/A 1
Instrument Failure Modo: OUALITY = BAD OR NCAL OR RDER Temperature Compensation i
For DP Transmitters: N/A Level Reference Leg: VET Unique System Desc.: PRESS LEVEL IS CALIBRATED FOR HOT l
OPERATION. THE THREE PRESSURIZER LEVEL SIONALS ARE COMBINED IN A 2 OF 3 LOGIC. ANY SIGNALS OF " BAD" OUALITY
. WILL BE USED. IN THE RCS INVENTORY CSE_
92-1103A (32)
Unique System Dese.:(Continued) JREE. THERE ARE TUO SETPOINTS FOR
,JJESSURIZER IIVEL. A HICH LEVEL SETPOINT.
(75D AND A LOV LEVEL SETPOINT (14.40.
. THE 111011 LEVEL SETPOINT REPRESENTS THE VORST CASE. IF TVO OR MOPI LEVELS
__ARE ESYOND EITHER SETPOINTS. THE CURRENT
- VALUE WILL BE CALCULATED FROM THOSE
. LEVELS V}lICH ARE BEYOND TilAT SETPOINT.
IN THE UNLIKEJ,Y EVENT TilAT ONE SIGNAL IS ABOVE THE IIICH LEVEL ONE SIGNAL IS BELOW
..THE LOV LEVEL. A,_ lid ONE SIGNAL IS OF BAD ,
OUALITY (REDUCING THE LOGIC TO 1 TO 2). --
. PRIORITY IS CIVEN To Tile HICll VALUE.
9 4
92-1103A (33)
. -. _ = - - _ _ .
I 1
DATA POINT LIBRARY REFERENCE FILE l Date: ,_f,_/_
Reactor Unit: R02 Data Feeder: __ERFIS NRC ERDS Parameter: RCS CHG/MU Point ID: CilF0128 A Plant Spec Point Desc.: FT-122 RCS CHAPGING FLOW Generic /Cond Dese.: PRIMARY SYSTEM CHARGING OR__M&KIUP FLOV Analog / Digital: A Engr Units / Dig States: CPM Engr Units Conversion _ t!/A Minimum Ir.str Range: _0 Maximum Instr Range: _ 150 Zero Point
Reference:
N/A Reference Point Notes: N/A FROC or SENS: S tc.mber of Sensors: 1 How Processed: DIRECT READING Sensor Locations: CRARGING PUMP DISCHARGE -
Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: ,
N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: _ N/A Unique System Desc.: _
I I
92-1103A (34)
DATA POINT LIBRARY REFERENCE FILE Date: J )_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: RCS CHG/MU Point ID: CHF0193A Plant Spoc Point Desc.: FT-114 PRIMARY MAKEUP VATER FLOV Ceneric/Cond Dese.: PRIMARY SYSTEM CHARGING OR MAKEUP FLOV Analog / Digital: A Engr Units / Dig States: CPM Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: _Q0 Zero Point
Reference:
N/A Reference Point Notes: - N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: PV DISCH EIPING PRIOR TO BLENDER Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUAI.ITY = EAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Dese.:
92-1103A (35)
DATE POINT REFERENCE F' t Date: J_f_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: _ HP SI FLOW Point ID: __SIF5303A Plant Spec Point Desc.: FT-940 $1 HOT 1E0 INJECTION FLOW Ceneric/Cond Dese.: HICH PRESSURE SAFETY INJECTION FLOW Analog / Digital: A Engr Units / Dig States: CPM Engr Units Conversion: _ N/A Minimum Instr Range: 0 Maximum Instr Range: 1000 Zero Point
Reference:
N/A Reference Point ~ Notes: N/A PROC or SENS: S Number of Sensorn: 1 How Processed: DIRECT READING Sensor Locations: COMMON PUMP DISCHARCE EBIOR TO NOT IICS Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Le"el: N/A NI Detector Power Supply -
Turn-on Power Level: N/A Instrument Failure Mode: .0UALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A ,
Unique System Dese.:
l 92-1103A -
(36)
DATE POINT REFERENCE FILE Date: .__/.__/-
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: IIP SI FLOV Point ID: SIF5304A Plant Spec Point Desc.: FT 943 SI COLD LEC INJECTI0tl FLOV -
Generic /Cond Dese.: llIGH PPESStTPE SAFETY INJECTION FLOV Analog / Digital: A
=
Engr Units / Dig States: CPM Engr Units Conversion: N/A Minimum Instr Range: 0 E
Maximum Instr Range: 1000 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 llow ProcesJed: DIRECT READING Sensor Locations: COMMON PtTMP DISCHAPGE PRIOR TO COLD LECS Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A
- NI Detector Power Supply Turn-on Power Level: N/A _
Instmn.ent Failure Mode: QUALITY - BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Dese.:
1 92-1103A (37)
DATE POINT REFERENCE' FILE ~ "
Date: JJ_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: LP SI FLOV Point ID: RHF0626A Plant Spec Point Desc.: FT-60$_RitR SYSTEM FLOV Generic /Cond Desc.: LOV PRESSURE SAFETY INJECTION FLOV Analog / Digital: A Engr Units / Dig States: CPM Engr Units Conversion: N/A Minimus Instr Range. O Maximum Instr Range: _8500 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: COMMON PUMP DISCRARGE PRIOR TO COLD IICS Alarm / Trip Set Points: LO FLOV 3000 CPM NI Detector Power Supply Cut-off Power Level: N/A
- NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A __ _
Unique System Desc.:
92-1103A (38)
l l
. DATE POINT REFERENCE FILE Date: JJ_
Reactor Unit: R02 Data Feeder: _ E P.FIS NRC ERDS Parameter: CT.01T SMP NR Point ID: - NONE ON ERFIS -
Plant Spec Point Desc.:
Generic /Cond Dese.: CONTb1NMENT SUMP N&RROV PANGE LEVEL Analog / Digital:
Engr Units / Dig States:
Engr Units Conversion:
Hinimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Locations: _
Alarm / Trip Set Points:
NI Detector Power Supply '
Cut-off Power Level: __
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensa?. ion For DP Transmitters:
Level Reference Leg:
Unique System Dese.: THIS DATA POINT IS NOT CURRENTLY ,
AVAILABLE FOR ERDS TRANSMISSION.
I 92-1103A (39)
- eB88 i' ' ,-(',# .,-r 9 DATE POINT' REFERENCE FILE Date: ,_ /,,_/_ l Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: CTMNT SMP VR Point ID: SILOOO2 Plant Spec Point Dese.: AVEPAGE CONTAINMENT SlTMP LEVEL Ceneric/Cond Desc.: CONTAINMENT SUMP WIDE RANGE LEVEL Analog / Digital: A Engr Units / Dig States: INCH Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum' Instr Range: $00 Zero Point
Reference:
CV SUMP FLOOR ,
Reference Point Notes: N/A ,
PROC or SENS: P __
Number of Sensors: 2 How Processed: AVERAGE Sensor Locations: CONTf UiKENT SUMP Alarm / Trip Set Points: JfA NI Detector Power Supply Cut-off Power Level: N/A NI Detector Powmr Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Dese,:
92-1103A (40)
. DATE POINT REFERENCE FILE Date: _/J_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: EFF CAS RAD Point ID: PER0002A Plant Spec Point Desc.: R-2 CV LO RANCE AREA MONITOR Generic /Cond Desc.: RADIOACTIVITY OF RELEASED CASES Analog / Digital: A Engr Units / Dig States: MRHR Engr Units Conversion: N/A Minimum Instr Range: .100E+00 Maximum Instr Range: .10bn05 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: ENTRANCE TO CV Alarm / Trip Set Points: 100 MR/HR NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N /t.
Inbcrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.:
92-1103A (41)
DATE POINT REFERENCE FILE Date: ._)J_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: EFF CAS RAD Point ID: RMR0007A Plant Spec Point Desc.: R 7 SEAL TABli RM. ARIA MONITOR Generic /Cond Desc.: __2 api 0 ACTIVITY OF RELEASED CASES Analog /DiEital: A Engr Units / Dig States: MRHR Engr Units Conversion: N/A Minimus Instr Karae: .100E+00 Maximum Instr Range: .100E+05 Zero Point
Reference:
N/A Reference Point Notesi N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Fensor LecationJ: CV SEAL TAB 15. ROOM Alarm / Trip Set Points: 200 MR/HR NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A ,,
j Level Reference Leg: N/A Unique System Dese.:
l l
l l 92-1103A (42)
DATE POINT REFERENCE FILE Date: _/ f_
Reactor Unit: _ R02 Data Feeder: ERFIS NRC ERDS Parameter: EFF GAS RAD Point ID: PER0051A Plant Spec Point Desc.: R-14A PLT VENT EFL PARTICULATE Ceneric/Cond Desc.: RADIOACTIVITY OF RELEASED CASES
'nalog/ Digital: A O.iits/ Dig tates: CFM Engr Units Conversion: N/A Minimum Instr Range: .100E+02 Maximum Instr Range: , .100E+07 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 ,
Mov Processed: DIRECT READING Sensor Locations: PLANT VENT STACK Alarm / Trip Set Points: SEE UNIQUE SYSTEM DESC NI Detector Power Supply Cut-off Power Level: N/A -
NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY - BAD OR NCAL OR EDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.* SETPOINT IS BASED ON THE MOST RESTRICTIVE DOSE RATE OF 10CFR20 __
VARIABLE SETPOINT.
92-1103A (43)
DATE POINT REFERENCE FILE Date: J _)_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: EFF GAT, RAD Foint ID: RMR0050A Plant Spec Point Desc.: R-14B PLT VENT EFL IODINE Ceneric/Cond Desc.: RADI0 ACTIVITY OF RELEASED GASES Analog / Digital: A 1
l Engr Units / Dig States: CPM Engr Units Conversion: N/A Minimum Instr Range: .100E+02 ,
Maximum Instr Range: .100E+07 {
Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: PLANT VENT STACK Alarm / Trip Set Points: SEE UNIOUE SYSTEM DESC NI Detector Power Suppl-
- Cut-off Power Level: N/A NI Detector Fover Supply Turn-on Fover Level: N/A Instrument Failure Mode: QUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.. SETPOINT IS BASED ON THE MOST RESTRICTIVE DOSE RATE OF ICCFR20 VARIABLE SETPOINT.
92-1103A (44)
Date: j._f Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: EFF CAS RAD Point ID: RMR0049A Plant Spec Point Dese.: R-14C PLT VEb'I EFL NOBLE CAS LO 09neric/Cond Dese.: RADI0 ACTIVITY OF RElIASED CASES Analog / Digital: A R Engr Units / Dig Sta as: CPM Engr Units Consersion: N/A g
Minimum Instr Range; .100E+02 Maximum Instr Range: .100E+07 i
iQ"P "ero Point
Reference:
N/A n ps
- hf Y
c~
Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING q Sensor Locations: PLANT VENT STACK Alarm / Trip Set Points: SEE UNIOUE SYSTEM DESC NI Eetector Power Supply ,
Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.* SETPOINT IS BASED ON THE MOST RESTRICTIVE D SE RATE OF 10CFR20 ALARM SHUTS RCV-014. VARIABLE SETPOINT A HI-NI ALARM SWITCHER SAMPLE FLOV TO R-14D & E.
92-1103A (45)
DATE POINT REFERENCE FILE Date: __/J_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: EFF CAS RAD Point ID: PER0045A Plant Spec Point Dese.: R-14D PLT VENT EFL NOBLE CAS MID Ceneric/Cond Desc., RADIOACTIVITY OF RELRASED CASES Analog / Digital: A Engr Units / Dig States: CPM Engr Units Conversion: N/A Minimum Instr Range: .100E+02 Maximum Instr Range: .100E+07 Zero Point
Reference:
N/A Reference Point NoteL: N/A PROC or SENS: S Number of Sensors: 1 -
Mov Processed: DIRECT READING Sensor Locations: PIANT VENT STACK Alarm / Trip Set Points: 3.85 E-02 MCI /CC NI Detector Power Supply Cut-off Power Level: N/A -
NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY - BAD OR NCAL OR RDER -
Tamperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: ATARM CORRESPONDS TO 50 MREM AT THE SITE B0JDARY:
92-1103A (46)
DATE POINT REFERENCE FILE Date: ,_/J_ l l
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: EFF GAS RAD Point ID: RMR0046A Plant Spec Point Desc.: R-14E PLT VENT EFL NOBLE CAS HI Ceneric/Cond Desc.: RADIOACTIVITY OF RELEASED CASES Analog / Digital: A Engr Units / Dig States: CFM Engr Units Conversion: N/A Minimum Instr Range: .100E+02 Maximum Instr Range: .100E+07 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: PLANT VENT STACK Alarm / Trip Set Points: 125 CCPM NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Dese.:
92-1103A (47)
DATE POINT REFERENCE FILE Date: J_/_
Reactor Unit: R02 Data Feeder: _ERFIS NRC ERDS Parameter: EFF CAS RAD Point ID: P3R0020A Plant Spec Point D c.: R 20 LOVER LEVEL FHB RAD MONITOR Ceneric/Cond Desc.: RADIOACTIVITY OF RELEASED CASES _
Analog / Digital: A Engr Units / Dig States: CPM Engr Units Conversion: N/A Minimum Instr Range: ,100E+02 Maximum Instr Range: .100E+08 Zero Point
Reference:
N/A P.eference Point Notes: N/A PROC or SENS: S Number of Sensors:
1 How Processed: DIRECT READINC Sensor Locations: DISCRARGE OF HVE-14 Alarm / Trip Set Points: SEE UNIOUE SYSTEM DESC NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation Fcr DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.* SETPOINT IS BASED ON THE MOST RESTRICTIVE DOSE RATE OF 10CFR20 SETPOINT IS VARIABLE, 92-1103A (48)
DATE POINT REFERENCE FILE Date: ._/._/__
Reactor Unit: R02 Data Feeder: _ERFIS NRC ERDS Parameter: EFF CAS PAD Point ID: kMR0021A Plant Spec Point Desc.: R-21 UPPER LEVEL FEB RAD MONITOR Generic /Cond Desc.: RADIOACTIVITY OF RELEASED CASES Analog / Digital: A Engr Units / Dig States: CPM Engr Units Conversion: N/A Minimum Instr Range: .100E+02 Maximum Instr Range: .100E+08 Zero Point
Reference:
N/A Reference Point Notes: N/A _
PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT PIADINC Sensor Locations: DISCHARCE OF HVE-15 Alarm / Trip Set Points: SEE UNIOUE SYSTEM DESC NI Detector Power Supply ,
cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Lsvel: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: SE1 POINT IS BASED ON 10% OF THE MFC F09 UASEOUS ACTIVITY AT THE SITE BOUNDIRY.
92-1103A (49)
. DATE POINT REFERENCE FILE Date: JJ_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: EFF GAS RAD Point ID: PER0030A Plant Spec Point Dese,: R-30 HI PANGE FHB PAD MONITOR Ceneric/Cond Desc.: RADIOACTIVITY OF RELEASED CASES Analog / Digital: A Engr Units / Dig States: MRHR Engr Units Conversion: N/A Minimum Instr Rcnge: .100E+01 Maximum Instr Range: .100E+06 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: DISCHARGE OF HVE-14 Alarm / Trip Set Points: , 9 MR/HR + BACKCROUND NI Detector Power Supply '
Cut-off Power Level N/A ,
NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY - BAD OR N_ CAL OR RDER Temperature Compensation For DP Transmitters: _ N/A Level Reference Leg: N/A Unique System Dese.:
92-1103A (50)
-. DAYE POINT REFERENCE FILE Date: J._,,J_
^
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: EFF LIO RAD Point ID: RMR0018A Plant Spec Point Desc.: R-18 LIO VASTE DISPOSAL MONITOR Ceneric/Cond Dese,: RADI0 ACTIVITY OF RELEASED LIOUIDS Analog / Digital: A Engr Units / Dig States: CPM Engr Units Conversion: N/A Minimum Instr Range: .iO0E+02 Maximum Instr Range: .100E+07 Zero Point
Reference:
N/A Refei'ence Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: _ DIRECT READING Sensor Locations: DISCRARGE PIPING OF VASTE PUMP Alarm / Trip Set Points: SEE UNIOUE SYSTEM DESC.
- NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique Systen Desc.: SET POINT IS CALCULATED PRIOR TO EACH
_ RELEASE.
92-1103A (51) l
DATE POINT REFERENCE FILE Date: _/_/_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: COND A/E RAD Point ID: RMR0015A Plant Spec Point Desc.: R-15 COND AIR EIHAUST MONITOR Generic /Cond Desc.: CONDENSER AIR EJECTOR RADI0 ACTIVITY Analog / Digital: A Engr Units / Dig States: CPM Engr Units Conversion: N/A Minimum Instr Range: .100E+02 Maximum Instr Range: .100E+07 Zero Point
Reference:
__N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 Uov Processed: DIRECT READING Sensor Locations: DISCRARCE OF VACUUM PUMPS Alarm / Trip Set Points: _ SEE UNIOUE SYSTEM DESC.
I NI Detector Power Supply
- 1 Cet-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Lag: N/A Unique System Desc.: ALARM SET POINT IS BASED ON THE MOSI l
RESTRICTIVE DOSE RATE OF 10CFR20.
l t
92-1103A (52) l
DATE POINT REFERENCE FILE Date: JJ_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: CNTMNT PAD Point ID: RXR0043A Plant Spec Point Desc.: R-32A CV HI PANGE AREA MONITOR Ceneric/Cond Dese.' PADIATION LEVEL IN CONTAIN4ENT Analog / Digital: A _
Engr Units / Dig States: R/HR Engr Units Conversion: N/A Minituum Instr Range: .100E+01 Maximum Instr Range: .100E+08 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: 3RD LEVEL CONTAIFMENT Alarm / Trip Set Points: SEE UNIQUE SYSTEM DESC.
NI Detector Power Supply Cut-off Power Level: _NZA NI Detector Power Supply Turt-on Power Level: N/A Instrument Failure Mode: OUALITY - BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: 2 ALARMS ALERT AT 10 R/HR HIGH AT,l000 R/WR 92-1103A (53)
. . DATE POINT REFERENCE FILE Date: ,,_/j_
Reactor Unic: R02 Data Feeder: ._ERFIS NRC ERDS Parameter: CNTMNT PAD Point ID: RMR0044A Plant Spec Point Desc.: R-32B CV HI PANGE AREA MONITOR Generic /Cond Desc.* KADIATION LEVEL IN CONTAINMENT Analog / Digital: A Engr Unit.s/ Dig States: R/HR Engr Units Conversion: N/A Minimum Instr Range: .100E+01 Maximum Instr hange: .100E+08 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S ,
Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: 3RD LEVE1; CONTAINMENT Alarm / Trip Set Points: SEE UNIOUE SYSTEM DESC.
NI Detector Power Supply Cut-off Power Level: N/A_
NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD ,
Temperature Compensation For DP Transmitters. N/A l
Level Reference Leg: N/A Unique System Desc. 2 ALARMS ALERT AT 10 R/RR HICH AT 1000 R/MR l
92-1103A (54) l
DATE POINT REFERENCE FILE Date: ,_/__/,_,,
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: RCS LTDN RAD __
Point ID: RKR0009A Plant Spec Point Desc.: R-9 RCS LETDOWN LINE RAD MONITOR Ceneric/Cond Dese,: RAD LEVEL OF THE RCS LETDOWN LINE Annlog/ Digital: A Engr Units / Dig States: MRRR Engr Units Conversion:
Minimum Instr Range: .100E+01 u
Maximum Instr Range: .100E+06 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: LETDOWN PIPING Alarm / Trip Set Points: 3000 MR/RR NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply -
Turn-oa Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A _
Unique System Desc.,
92-1103A (55)
. DATE POINT REFERENCE FILE Date: /._.J._.
Reactor Unit: R02 _
Data Feederi ERFIS NRC ERDS Parameter: MAIN SL A Point ID: RMR0040A Plant Spec Point Dese.: R-31A STM LINE A RAD MONITOR Generie/Cond Desc.: STM GEN A STEAM LINE RAD LEVEL Analog / Digital: A Engr Units / Dig States: MRRR Engr Units Conversion: N/A Minimum Instr Range: .100E+01 Maximum Instr Range: .100E+06 Zero Point Rererence: N/A ,
Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIPECT READING Sensor Locations: "A" STEAM LINE TURBINE DECK Alar:p/'* rip Set Toin'cc : 12 MR/HR NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER _
Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique ; estem Desc.:
92-1103A (56)
I
DATE POINT REFERENCE FILE Date: _/__/__
Reactor Unit: R02 Data Feeder: ERFIS NRC ERD 3 Parameter: MAIN SL B Point ID: RMR0041A Plant Spec Point Desc.; R-31E STM LINE B RAD MONITOP _
Generic /Cond Desc.: STM CEN B STEAM LINE RAD LEVEL Analog / Digital: A _
Engr Units /Lis States: MRRR Engr Units Conversion: N/A Minic.us Instr Range: .100E+01 _
Maximum Instr Range: .100E+06 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: "B" STEAM LINE TUREINE DECK Alarm / Trip 5et Points: 12. hR/HR NI Detector Power Supply cut-off Power Level: N/A
- NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: ,, OUALITY = BAD OR NCAL OR RDFR Temperature compensation
! For DP Tranrmitters: N/A Level Reference Leg: N/A Unique System Desc.- .
92-1103A (57) l
DATE POINT REFERENCE FILE Date: _f__/._,
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: MAIN SL C Point ID- RER0042A Plant Spec Point Desc.. K-310 STM LINE C FA' ' lNITOR Ceneric/Cond Dese.: STM CEN C STEAM LINE KAD LEVE1 Analog / Digital: A _
Engr Units / Dig States: __MRHR Engr Units Conversion: N/A _
Minimum Instr Range: .100E+01 Maximum Instr Range: .100E+06 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sansors: 1 ,
How Processed: DIREC'. READINO
~
- ! Sensor Locations
- "C" STEAM LINE TURBINE DECK Alarm / Trip set foints: 12 MR/MR ,
NI Detector Power Supply '
Cut-off Iower Level: N/A NI 9etector Power Supply Turn on Power Level: N/A __ _
Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.:
92-1103A (58)
DATE POINT REFERENCE FILE Date: ,_f._j _
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: SG BD RAD A Point ID: RMR0019A Plant Spec Point Desc. R-19A S/G A BLO7DOWN PAD MONITOR Generic /Cond Desc.: STM GEN A BLOVDOWN RAD LEVEL Analog / Digital: ._f.
Engr Units / Dig States: CPM Engr Units Conversion: N/A Minimum Instr Range: .100E+02 Maximus Instr Range: .100E+0B Zero Point
Reference:
_ !!/A Reference Point Notes: N/A PROC or SENS: S Numi er of Sensors : 1 5 Hou Processed: DIREat RFADING Sensor Locations: IST LEVEL AUX BLDG, Alerm/ Trip Set Points: SEE UNIOUE SYSTO' DESC. _ __
NI Detector Power Supply Cut-off Power Level: N/A N'i Detector Power Supply
,. Turn-on Power Level: _h/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A ,
Level Reference Leg: N/A Unique System Dest.: AIARM SET POINT BASED ON 10CFR20 LIMITS.
92-1103A (59)
, , DATE POINT REFERENCE FILE D4te: ___/j_
Reactor Unit: 302 Data Feeder: ERFIS NRC ERDS Parameter: SG BD RAD B Point ID: RMR0047A Plant Spec Point Dese,: R-19B S/G B BLOVDOWN RAD MONITOR Ceneric/Cond Dese.: STM CEN B BLOVDOWN RAD LEVEL _
Analog / Digital: A Engr Units / Dig States: _ CPM Engr Units Conversion: N/A Minimum Instr Range: .100E+02 Maximum Instr Range: ,100E+08 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: DIRECT READING Sensor Locations: IST LEVEL AUX BLDG.
Alara/ Trip Set Points: SEE UNIQUE SYSTEM DESC.
NI Detector Power Supply Cut-off Power Level: N/A ___ . , _ ,
N1 Letector a over Supply Turn-on Power Level N/A Instrument Failute Mode: _ QUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Dese.: ALARM SET POINT BASED ON 10CWR20 LIMITS.
92-7.103A (60)
DATE POINT REFERENCE FILE Date: __.)__)._,
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: SG BD RAD C Poittt ID: RMR004BA Plant Spec Point Dese.: R-19C S/G C BLOVDOWN RAD MONITOR Generic /Cond Desc.: STM GEN C BLOVDOWN RAD LEVEL Analog / Digital: A Engr Units / Dig States: CPM Engr Units Conversion: N/A Minimum Instr Range: ,100E+02 Maximum Instr Range: .100E+08 Zero Point
Reference:
N/A _
Reference Point Notes: N/A PROC or SENS: S
~
Number of Sensors: 1 How Processed: DIRECT READIbG u
Sensor Locations: IS_T_ LEVEL AU1 BLLG, Alarm / Trip -ct Feints: SEE UNIQUE SJSJ_EM S _DESC , , , _ , _ _.
NI Detector Pover Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensatien For DF Transmitters: N/A Level P.cference Leg: N/A Unique System Desc. . ALARM SET POINT BASE'.D ON 10CFR20 LIMITS.
92-1103A (61)
. . DATE POINT REFERENCE FILE Date: _)_/,_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Paraceter: CTMNT PRESS Point ID: CVP0001 Plant Spec Point Desc.: AVERAGE CONTAINMENT PRESSURE Generic /Cond Dese.: CONTAINMENT PRESSUPI Analog / Digital: A .
Engr Units / Dig States: PSIG Engr Units Conversion: N/A Minimum Instr Range: -5.0 Maximum Instr Range: 135.0 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 6 How Processed: SEE UNIOUE SYSTEM DESC.
Sensor Locations: AUXILIARY BLDG. __,
Alarm / Trip Set Points: SEE UNIOUE SYSTEM DESC.
NI Detector Power Supply cut-off Power Level: N/A NI Detector Power Supply Turn-or. Power Level: N/A Instrument Failure Mode: QUAQTY alA_D ,0J_NCAL Ok RD{R Temperature Compensation For DP Transmitters: N /A Level Reference Leg: N/A Unique System Desc.. 2 OUT OF 3 EI (4 PSIG) CIVES A SI SICNAL 2 OUT OF 3 PLUS 2 OUT OF 3 HI/HI (20 PSIG) GIVES A CV SPRAY SIGNAL.
92-1103A (62)
. DATE POINT REFERENCE FILE Unique System Desc.:(Continued) THE SIX SIGNALS ARE COMBINED IN A 2 OUT OF SIX LOGIC. IN THE CONTAINMENT TREE THERE ARE TWO SETPOINTS FOR CONTAINMENT PPISSURE. A HIGH PRESSURE (4 PSIG) AND A HIGH-HIGH PRESSURE SETPOINT (20 PSIG.)
THE HIGH-HIGH PRESSURE SETPOINT PIPRESENTS THE WORST CASE. PRIORITY IS GIVEN TO T}lE HIGH-HICH VALUES WHEN THERE API TWO OR MORE SIGNALS ABOVE EAC11_ SET- _
POINT.
IF ONE SIGNAL IS AB0VE THE HIGH-HIGH PPIFSURE. ONE SIGNAL IS ABOVE Ot?LY THE HIGH PRESSURE. AND THE OTHER SIGNALS ARE IN THE NORMAL RANGE. THE VALUE WHICH IS ,
ABOVE THE HIGH PRESSURZ IS USED. IN THI_S UNLIKELY CASE. 2 0F 6 SIGNALS ARE ABOVE THE HIGH PRESSURE BUT ONLY l 0F 6 IS ABOVE THE HIGH-HIGH PRESSURE, IN THE CASE OF BAD OUALITY SIGNALS. THE LOGIC IS REDUCED TO 2 0F 5. AND THEN 2 0F 4 THEN 2 0F 3, IF THF.PI ARLJ'EVER THAN, 3 GOOD OVALITL,E;I_G_NhTS . THE CALCULATION __
VILL BE CONSIDERED NON-VALIDATED.
92-1103A (63)
DATA POINT LIBRARY REFERENCE FILE Date: _JJ_
i Reactor Unit: R02 Data Feeder: ERFIS NRC EPSS Parameter: CTMNT TEMP Point ID: CVT0001 Plant Spec Point Desc.: AVERACE CV /. . TEMPERATUPI Generic /Cond Desc.: CONTAINMENT TEMPERATUPI Analog / Digital: A Engr Units / Dig States: DEGF Engr Units Conversion: N/A Minimum Instr Range: 0.0 Mar.imum Instr Range: 600.0 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: _5 .
liav Processed: A7 EPJ.GP Sensor Locations: IST LEVEL CV Alaic/ Trip 5et Poin'cs: ,,,33 NI Detector Power Supply Cut-off Power Level: ,_E/L _
NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY - BAD Temperature Compensation Fcr DP Transmitters: N/A Level Refe:6nce Leg: N/A Unique System Desc.:
and-92-1103A (64)
DATA POINT LIBRARY REFERENCE FILE Date: )._f Reactor Unit: R02 Data Feeder: ERFIS
] NRC ERDS Parameter: H2 CONC Point ID: SSC0001 Plant Spec Point Dese.: AVERAGE CV H2 CONCENTRATION Ceneric/Cond-Dese.: CONTAINMENT HYDROCEN CONCENTRATION Analog / Digital: A Engr Units / Dig States: % ,
l Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 100 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: E Number of Sensors: 2 How Processed: AVERAGE Sensor Locations: 3RD LEVEL CV -
Alarm / Trip Set Points: 3.5%
NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY = BAD OR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.,
92-1103A , (65)
DATA POINT LIBRARY REFERENCE FILE Da:e: .,_./_ f._
F.e t :::: Unit: R02 Data 7eeder: ERFIS NIO ELDS Parameter: RWST LEVEL F e in: ID: SILOOO1 Plant Spec Point Dese.: AVERAGE RWST LEVEL Generic /Cond Dese.: BORATED WATER STORAGE TANK LEVEL Ar.a' : g/ Digital:
A Eng: Units / Dig States: %
Eng: Units Conversion: N/A Mini::= Instr Range: 0 Maxirum Instr Range: 160 Zerc Point
Reference:
TNK BOT Reference Point Notes: N/A PROC or SENS: P S :':er of Sensors: 2 Eev Frocessed: , *~' RAGE Sens:: Locations: ALONG SIDE THE TANK
.Ca--/ Trip Se t Points: SEE UNIQUE SYSTEM DEjiC.
5: :e:ector Power Supply C :-:ff Power Level: N/A _,
S: 2etector Power Supply Tur -en Power Level: N/A Instrument Failure Mode: QUALITY - B AD OR NCAL OR RDER Te: erature Compensation
?: P Transmitters: N/A Le e'. Reference Leg: WET Cri:ne System Desc.:
HI ALARM AT 95%
LO ALARM AT 27%
LO/LO ALARM AT 9%
92 *103A (66)
. . DATA POINT LIBRARY REFERENCE FILE Date: J_/_
Reactor Unit: _ R02 Data Feeder: ERFIS NRC ERDS Parameter: VIND SPEED Point ID: EMT0007S Plant Spec Point Dese.: LOVER VIND SPEED (11.0M)
Generic /Cond Desc.: VIND SPEED AT REACTOR SITE Analog / Digital: A Engr Units / Dig States: MPH Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 100 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: 15 MINUTE AVERACE Sensor Locations: ROBINSON MET TOWER Alarm / Trip Set Points: N/A
- NI Detector Power Supply '
Cut-off Power Level: N /A
(
, NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: OUALITY= BAD Olt NCAL. OR VALUE--999 OR 999 Temperature Compensation For DP Transmitters: N/A .
Level Reference Leg: N/A Unique System Dese.:
I 1
I l
92-1103A (67)
e DATA POINT-LIBRARY REFERENCE FILE Date: ,_/,_/_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: VIND SPEED Point ID: EMT0002S Plant Spec Point Desc.: UPPER VIND SPEED (62.3M)
Generic /Cond Dese.: VIND '3 PEED AT RE*.CTOR SITE Analog / Dip!,tal: A Engr Units / Dig States: MPH Engr Units Conversion: N/A hinimum Instr Range: 0 Maximum Instr Range: 100 Zero Point
Reference:
N/A Reference Point Notes: N/A ,
PROC or SENS: S Number of Sensors: 1 Hov 1rocnssed: 15 MINUTE AVERAGE Sensor Lc cations: ROBINSON MET TOVER _
Alarm / Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A -
NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: QUALITY-BAD OR NCAL. OR VALUE--999 OR 999 Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.-
92-1103A (68)
DATA POINT LIBRARY REFERENCE FILE Date: ,_) _j_
Reactor Unit: R02 Data Feeder: ERFIS tiRC ERDS Parameter: VIND DIR Point ID: EMT0005D Plant Spee Point Desc.: LOWER WIND DIRICTION (11.0M)
Generic /Cond Desc.: VIND. DIRECTION AT REACTOR SITE Analog / Digital: __A Engr Units / Dig States: DEG Engr Units Conversion: N/A Minimum Instr Range: __0 Maximum Instr Range: 360.0 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: 15 MINUTE AVERAGE Sensor Locations: ROBINSON MET TOVER Alarm / Trip Set Points: N/A NI Detector Pow-r Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Fa.ilure Mode: OUALITY-BAD OR NCAL. OR VALUE--999 OR 999 Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.-
92-1103A (69)
P~ l DATA POINT LIBRARY REFERENCE FILE Date: _/J,,_
Reactor Unit: R02 Data Feeder: ERFIS NRC ERDS Parameter: VIND DIR Point ID: EMT0004D Plant Spec Point Desc.: UPPER VIND DIRECTION (62.3M)
Generic /Cond Desc.: VIND DIRECTIOP AT REACTOR S7.TE Analog / Digital: A ,
Engr Units / Dig States: DEG Engr Units Conversion: N/A Minimum Instr Rr ,e : 0 Maximum Instr Range: 360.0 Zero Point
Reference:
N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: _1 How Processed: 15 MINUTE AVERACE Sensor Locations: ROBINSON MET TOWER Alarm / Trip Set Points: N/A NI Detector Power Supply ~
Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Le' vel: N/A Instrument Failure Mode: QUALITY-BAD OR NCAL. OF VALUE=-999 OR 999 Temperature Compensation For DP Transmitters: N/A -
Level Reference Leg: N/A Unique System Desc.:
92-1103A (70)
e DATA POINT LIBRARY REFERENCE FILE
, nate: _j_f_
Reactor Unit: K02 Data Tecder: ERFIS NRC ERDS Parameter: STAB C1. ASS Point ID: EMT0016 Plant Spec Point Desc.. ._fASQUAL STAHLITY CIASSIFICATION Generic /Cond Desc.: ,_MP2STABJJ.ITY AT PEACTOR SITE Analog / Digital: _A Engr Units / Dig States: STABI Engr Units Conversion: N/A _
Minimum Instr Range: 1 _
Maximum Instr Range: 7 Zero Point
Reference:
N/A ,
Reference Point Notes: _N/A PROC or SENS: P Number of Sensors: 2 How Processed: SEE UN.IQ11E SYSTEM DESCRIPTION Sensor Locations: SEE UNT=UE SYSTEM DESCRIPTION Alarm / Trip Set Points: _NONE NI Detector Power Supply Cut-off Power Level: N/A N' Detector Power Supply
'lurn on Power Level: __E/L Instrument Failure Mode: OUALITY = BAD GR NCAL OR RDER Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N /A Unique System Desc.: MEASU MD USINC DIFFERENLIAL TEMPERATURE (FROM ROBINSON MET TOVER) BETVEEN UfPER AND LOVER TEM,f]RATURE. THE STABILITY
_ CIASSIFICATION IS PER_ REG. CUIDE 1.21.
_TABM _4B.
92-1103A (71)