ML20087E216

From kanterella
Jump to navigation Jump to search
Suppl 1 to Human Factors Control Room Design Review, Final Rept
ML20087E216
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 03/31/1984
From:
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
Shared Package
ML20087E208 List:
References
NUDOCS 8403160083
Download: ML20087E216 (122)


Text

- - - - -

l SUPPLEMENT NO. I i

l l .

I s

HUMAN FACTORS CONTROL ROOM DESIGN REVIEW 0F COMANCHE PEAK STEAM ELECTRIC STATION MARCH 1984 i

I t

8403160083 840308 PDR ADOCK 05000445 PDR A

l

t l

i ABSTRACT l

l l

Supplement I to the Human Factors Control Room Design Review of l

Comanche Peak Steam Electric Station (CPSES) provides resolution to

~

those issues open when the original report was issued in December 1982 and to the issues /HED's' identified during the Human Factors Engineering Branch audit of CPSES of fpril 4 to 8,1983, as documented in B. J. Youngblood's letter to R. J. Gary dated July 8, 1983.

f I

e i SUPPLEMENT 1

l l

TABLE OF CONTENTS

1.0 INTRODUCTION

1-1 1-1

1.3 SCOPE OF THE CRDR j 1.5 EXCEPTIONS TO NUREG-0700 GUIDELINES 1-1 1.5.1 Program Plan 1-1 1.5.2 System Function / Task Analysis 1-2 i l 3.0 HETH000 LOGY AND SCOPE 3-1 3.2 SCOPE 3-1 3.4 SURVEYS 3-1 3.4.1 Control Room Workspace 3-1 3.4.1.3 Scope 3-1
3. 4.1. 3. 4 Noise, Lighting and Environmental 3-1 6.0 INCOMPLETE TASKS 6-1

6.1 INTRODUCTION

6-1 6.2 NOISE, LIGHTING AND ENVIRONMENTAL SURVEYS 6-1 6.3 SYSTEMS ANALYSIS 6-1 APPENDIX A HED ORGANIZATION AND CROSS REFERENCES A-1, A-2 APPENDIX B HED SUMMARIES B-1 2.0 WORKSPACE HEDS HED 1 Revised HED 45 Revised HED 59 Revised HED 111 Revised HED 154 Revised HED 155 Revised HED 156 Revised HED 166 Revised HED 171 Revised HED 296 Revised HED 335 New HED 336 New HED 337 New HED 342 New HED 346 New HED 348 New HED 349 New HED 350 New HED 351 New HED 352 New HED 353 New 3.0 COMMUNICATIONS HEDS HED 71 Revised HED 118 Revised HED 119 Revised HED 120 Revised HED 347 New l

l 11 SUPPLEMENT 1 1

-. , , . .- ..n . --

4.0 ANNUNCIATOR HEDS HED 308 Revised HED 310 Revised HED 311 Revised HED 315 Revised HED 318 Revised HED 323 Revised l 5.0 CONTROLS HEDS I I Revised HED 27 HED 28 Revised HED 93 Revised HED 161 Revised HED 169 Revised HED 172 Revised HED 183 Revised HED 214 Revised HED 244 Revised HED 344 New 6.0 VISUAL DISPLAY HEDS HED 8 Revised HED 13 Revised HED 29 Revised lied 39 Revised HED 41 Revised HED 63 Revised HED 81 Revised HED 85 Revised HED 89 Revised

HED 94 Revised HED 102 Revised HED 126 Revised HED 260 Revised HED 267 Revised HED 269 Revised HED 298 Revised HED 338 New 7.0 LABELING & LOCATION AIDS HEDS HED 107 Revised HED 151 Revised HED 343 New 8.0 PROCESS COMPUTER HEDS HED 36 Revised HED 116 Revised HED 177 Revised HED 339 New HED 345 New iii SUPPLEMEh' 1

l 9.0 PANEL LAYOUT HEDS HED 25 Revised (Previously in Section 8.0)

HED 143 Revised HED 285 Revised New j HED 340 l

10.0 CONTROL DISPLAY INTEGRATION HEDS ,

I HED 140 Revised

' i HED 341 New

' APPENDIX C ANNUNCIATOR SYSTEM HUMAN ENGINEERING GUILDLINES C-1 4.0 GUIDELINES C-1 4.3 DETAILED GUILDINES C-1 APPENDIX D VERTICAL INDICATOR HUMAN ENGINEERING GUIDELINES D-1 5.0 GUIDELINES D-1 5.3 DESIGN RE0VIREMENTS D-1 APPENDIX E DEMARCATION, LABELING, AND MIMIC HUMAN ENGINEERING GUIDELINES E-1 5.0 GUIDELINES E.-1 APPENDIX G CODING HUMAN ENGINEERING GUIDELINES G-1 thru G-10 APPENDIX H NOISE AND LIGHTING SURVEYS METHODOLOGY H-1 thru H-8 APPENDIX I RESPONSE TO IN-PROGRESS AUDIT OF COMANCHE I-1 PEAK STEAM ELECTRIC STATION CONTROL ROOM thru DESIGN REVIEW I-3 t

l l

l f

SUPPLEMENT 1

-r , - g. - , -

1.0 INTRODUCTION

1.3 ' SCOPE OF THE CRDR

a. The initial scope of the CRDR was to perform an evaluation using the NUREG/CR-1580 (Draft) guidelines. After the issuance of NUREG-0700, the CRDR was restructured to follow NUREG-0700 guidelines.
b. All areas of the CPSES detailed CRDR have been addressed.

In addition, CPSES has agreed to perform noise, lighting and environmental surveys at the Hot Shutdown Panel. The results of these surveys will be addressed later.

1.5 EXCEPTIONS TO NUREG-0700 GUIDELINES CPSES CRDR does not take exception to the guidelines of NUREG-0700. Alternate methods of complying with two aspects of these guidelines, the Program Plan and the System Function / Task Analysis, are described below.

1.5.1 Program Plan At the time of issuance of NUREG-0700, the CPSES CRDR had already been started. At that time, CPSES chose not to submit a Program Plan. In lieu of this Program Plan, CPSES is submitting a historical account of the detailed methodology used in the CRDR. The following cross-reference is provided to assist in correlating the applicable NUREG-0700 Program Plan requirements to the appropriate sections of this report. j The cross-reference also addresses the program plan information requested by Generic Letter 82-33, Supplement 1 to NUREG-0737, as j tabulated in the CPSES In-Progress Audit Results (see Youngblood to Gary letter of July 8,1983).

SUPPLEMENT 1 l i

~ - - -- .- . . . , . , , - . _ .- _- ._ ,,1

1 l

NUREG In-Progress CPSES l

0700 Audit of Results CRDR Report 2.1 -- 1.2 2.2 9. 2.0 2.3 1. Table 1

-- 2. 1.5.2

-- 3. 1.5.2 2.4 -- 2.383.3.2

-- 4. 3.3.4.183.4

5. 3.3.4, 3.3.4.2 & 3.3.4.3
6. 3.3.483.3.4.3
7. 3.3.4.3
8. 3.3.4.3 2.5 -- 1.4 2.6 -- 1.4 1.5.2 System Function / Task Analysis When NUREG-0700 was issued, the CPSES control room was being design reviewed against the guidelines in NUREG/CR-1580. An engineering evaluStion was underway to group functionally related controls / displays on the CPSES control boards to facilitate mimicking and demarcation. This evaluation took into consideration system functions and operator tasks. The control board rearrangements that i

resulted were based on a balance of accepted human engineering practices, improved operability, and cost effectiveness. Although none of the thought processes used in the evaluation were documented, the resulting control board arrangement was a considerable improvement over i the original design and CPSES was confident that a SFTA would not result in any violations that would require further control board I modifications. At that point, the decision was made to begin implementing the proposed control board design so as not to impact the fuel load schedule. -

1-2 SUPPLEMENT 1 i

l

_s .. . , , , . - . . . , _ - - . - - , - - . _ - _ _ . . . . _ , . - . . _ . . . . -,. - , ~ . . . , , - ,

By the time Westinghouse had issued their generic guidelines, all of the proposed control board modifications had been completed.

These Westinghouse generic guidelines were converted into CPSES plant specific Emergency Response Guidelines (ERGS). These ERGS were then verified using the modified control board arrangement to satisfy NUREG-0899. To perform this verification CPSES contracted the services

! of licensed Senior Reactor Operators with previous experience in the operation of a Westinghouse four-loop PWR. The verification process, consisting of flow chart review, table top review, and control room walk-throughs, was structured to verify that each task defined in the procedures could be accomplished with the minimum shift complement and that all the controls / displays required to complete each step in the procedure were available at the main control board. Documentation of the results is on file with each emergency procedure generation package.

P I

1-3 SUPPLEMENT 1

3.0 METHODOLOGY AND SCOPE 3.2 SCOPE l

The overall scope of the CRDR was as follows:

f

a. Review the Unit 1 control boards to assess compliance with NUREG/CR-1580 guidelines.
b. Reassess control boards for compliance with NUREG-0700 guidelines.
c. Evaluate applicable SERs and LERs.
d. Develop corrections for all Unit 1 discrepancies.
e. Compare Unit 2 to Unit 1 to assess design differences.
f. Develop and implement design change packages such that Unit 2 will be identical to the corrected Unit 1.

The review was limited to those primary control panels with which the operator normally interfaces. In addition, the review was extended to cover the Hot Shutdown Panel. The noise, lighting and environmental surveys were performed in the Control Room. CPSES has also agreed to perform Dese surveys at the Hot Shutdown Panel.

3.4 SURVEYS 3.4.1 Control Room Workspace 3.4.1.3 Scope 3.4.1.3.4 Noise, Lighting and Environmental I

l 3-1 SUPPLEMENT 1

_ . . . ~ . _ - . . , . - . , . . . . , . . _ _ .

A final noise, lighting and environmental surveys have been perform 4d. The methodology used is contained in Appendix H. The noise, lighting and environmental surveys at the Hot Shutdown Panel will be addressed after they are completed.

~

e W

e 3-2 SUPPLEMENT 1

l 6.0 INCOMPLETE TASKS l

)

6.1 INTRODUCTION

l l

All portions of the CPSES detailed CRDR have been completed.

l 6.2 NOISE, LIGHTING AND ENVIRONMENTAL SURVEYS All required surveys have been completed. The agreed upon noise, lighting and environmental surveys at the Hot Shutdown Panel have been scheduled for the near future.

6.3 SYSTEM ANALYSIS The systems analysis is complete as discussed in Section 1.5.2.

a i

l l .

l 6-1 SUPPLEMENT l'

i I

i i

APPENDIX A HED ORGANIZATION AND CROSS REFERENCES SUPPLEMENT 1 A-1

APPENDIX A HED ORGANIZATION AND CROSS REFERENCES HED CONTROL APPENDIX B SECTION NO. 2.0 3.0 4.0 5.0 6.0 7.0- 8.0 9.0 10.0 25 25 335 335  ;

336 336 l

337 337 ;

338 .

338 339 , 339 l 340 ,  !

l 340 341 l  ! 341 1

l 342 342 .

343 l 343 344 344 l

345  ; j 345 ,

346 346 ' l 347 l347, I  !

348 l 348 ' l l 349 I 349 ,' I

! i 350 8 350l l 351 351 : l l l 352 352 - f  !

t 1 353 353 -

i.

SUPPLEMENT 1 g

e e

O O

9 APPENDIX B HED SLWiARIES t

B-1 SUPPLEMENT 1

l i

i 2.0 WORKSPACE HEDS A

6 O

SUPPLDfENT 1

i HED CONTROL NO. 1 A. HED DESCRIPTION j MLB lamp tests are not accessible to 50th percentile operators.

l l

B. GUIDELINE REFERENCE NUREG-0700: 6.1. 2.2.b. (1) .

C. LOCATION CB-01, CB-02, and CB-11 D. POTENTIAL SAFEIY CONSEQUENCES Inability to detect MLB failures.

i E. ASSESSMENT FROCESS

1. Feasibility of relocating lamp tests was examined.
2. Alternative locations were evaluated.

F. BACKFIT None.

! 1. JUSTIFICATION CPSES realizes the need to be able to test the MLB lamps from a location accessible to the fifth percentile operator, however, in view I

of.the possibility to compromise plant safety with such an extensive change, we do not feel ~it is justified. Furthermort, since the control room will be manned with a minimum of 5 operators at any given time, it is highly unlikely that at least one of those operators will-not be able to test the MLB lamps from their present test location.

i i

l I

i SUPPLEMENT 1

HED CONTROL NO. 45 A. HED DESCRIPTION The control room has several traffic obstructions (the PRODAC and drawing layout table) which obstruct traffic flow between portions of the control boards.

B. GUIDELINE REFERENCE NUREG-0700: 6.1.1.3.c.1.

C. LOCATION Control room.

D. POTENTIAL SAFETY CONSEQUENCES None.

E. ASSESSMENT PROCESS No assessment necessary.

F. BACKFIT The drawing layout table is temporary and will be replaced with permanent furniture. The PRODAC is essential to the operator for information retrieval and as such is located with similar readout devices. Location of the PRODAC does not significantly impede operator mobility.

e SUPPLEMENT 1

HED CONTROL NO. 59 l

l A. HED DESCRIPTION Temporary control room ventilation presents white noise, which could l degrade consnunications as well as mask alarms and communications signals.

B. GUIDELINE REFERENCE NUREG-0700: 6.1.5.5.

C. LOCATION Control room.

D. POTENTIAL SAFETY CCNSEQUENCES

1. Failure to respond to alarm condition.
2. Failure to acknowledge communications.

E. ASSESSMENT PROCESS Control room noise survey F. BACKFIT Ambient noise levels were found to be below 65 dBA as prescribed in the guidelines. Carpeting will be installed in, the control room to further reduce " white noise".

l l

l l

i f

l ..

I t

I SUPPLEMENT 1

. - - -., - .  : , :~- ., .a,_., . _. .

HED CONTROL NO. 111 A. HED DESCRIPTION Conclusive NRC sound level surveys were not performed.

B. GUIDELINE REFERENCE None C. LOCATION Control room.

D. POTENTIAL SAFETY CONSEQUENCES NA E. ASSESSMENT PROCESS None.

F. BACKFIT A sound level survey has been perfor=ed as detailed in Appendix H.

4 4

- SUPPLDIENT 1

2 HED CONTROL NO. 154 A. HED DESCRIPTION Recorder glass causes glare, thereby hampering readability of scale indicators B. GUIDELINE REFERENCE NUREG-0700: 6.1.5.3.1 C. LOCATION All panels except CB-11 and CB-12 D. POTENTIAL SAFETY CONSEQUENCES Delayed in or incorrect data interpretation.

E. ASSESSMENT PROCESS Source of glare was pinpointed during lighting survey.

F. BACKFIT The source of the glare on recorder glass was determined to be reflected light from the control room floor. The centrol room floor is being replaced with carpeting to reduce noise levels. We anticipate using a darker color to reduce reflected light which should correct the glare

~

problem on recorder glass. This will be re-evaluated after installation of the carpet in the control room.

O SUPPLDIENT 1

1 I

l IIED CONTROL NO. 155 A. HED DESCRIPTION Toggle switches located below recommended 34-inch minimum height.

B. GUIDELINE REFERENCE NUREG-0700
6.1.2.5.a. (1) .

C. LOCATION In-core instrumentation panel.

D. FOIENTIAL SAFETY CONSEQUENCES None.

E. ASSESSMENT PROCESS Situations requiring operator interface with these switches were reviewed.

F. BACKFIT These toggle switches were used to select an In-Core thermocouple for monitoring on the P2500 computer. With the new Core Cooling Monitoring (CCM) design, these coggle switches are bypassed and will be removed.

i SUPPLEMENT 1

HED CONTROL NO. 156 A. HED DESCRIPTION Infrequently operated controls located above 70-inches maximum height from floor.

B. GUIDELINE REFERENCE NUREG-0700: 6.1.2.5.a. (1) .

C. LOCATION 1 In-core instrumentation panel.

D. POTENTIAL SAFETY CONSEQUENCES None.

E. ASSESSMENT PROCESS Situations involving requiring interface with these switches were reviewed.

F. BACKFIT None.

1. JUSTIFICATION The In-Core Instrumentation Panel is not used by the operator for
plant operations. It is used by the plant reactor engineer to

~

periodically run flux maps on the reactor core to determine fuel burn-out. The operator may be called upon to assist the reactor engineer, however, this will not occur frequently enough to warrant rearrangement of the controls on this panel.

l .

I SUPPLEMENT 1

HED CONTROL NO. 166 A. HED DESCRIPTION i

Controls are too high (above 74 inches) and too low (24 inches) for easy access. Recorders are too low (below 41 inches) for easy visibility.

B. GUIDELINE REFERENCE NUREG-0700: 6.1.2.5.a. (1) and b. (1) .

C. LOCATION Radiation Monitoring Panel.

D. POTENTML SAFETY CONSEQUENCES None.

E. ASSESSMENT PROCESS No assessment necessary.

F. BACKFIT The Radiation Monitoring Panel has been redesigned to improve control and display location problems. Due to the density of controls / displays located on this panel, there are still some controls located below 24 inches.

However, in view of the operator's infrequent use of this panel during normal operations, this poses no threat to plant safety, t

a i

i

  • SUPPLEMENT 1 l

1

h HED CONTKOL EO.171 A. HED DESCRIPTION Glare hampers readability of PRODAC.

B. GUIDELINE REFERENCE NUREG-0700: 6.1.5.3.f.

C. LOCATION Printer console.

D. POTENTIAL SAFETT CONSEQUENCES Incorrect or delayed datt. interpretation.

E. ASSESSMENT PROCESS -

1. Determined source
2. Evaluated impact on readability of printed information.

F. BACKFIT None

1. JU5TIFICATION Glare on PRODAC does not impede the readability of the printed information.

f i

l e

SUPPLDfENT 1

. ., m.__,._. -

HED CONTROL NO. 296 A. HED DESCRIPTION Controls violate anthropometric maximum and minimum requirements of distance from the control board edge.

B. GUIDELINE REFERENCE NUREG-0700: 6.1.2.2.d. (1) and (2) .

C. LOCATION All panels.

D. POTENTIAL SAFETY CONSEQUENCES Inadvertent control actuation.

E. ASSESSMENT PROCESS Potential backfits were investigated.

F. BACKFIT -

None.

1. JUSTIFICATION An anthropometric study was conducted to evaluate the accessibility of controls. Contro.'.s located on the transition and vertical sections of the control boards were found to be out of the extended reach of the 5th. percentile female operator. Where feasible, controls were moved to where they are within reach. Where movement was not feasible, control functions were examined individually to determine the safety-related, consequences of misoperation, if any, due.to its inaccessibilty. The only controls that were found to have the potential for safety-related consequences due to misoperation were the Auxiliary Feedwater Flow controllers and the Turbine Driven Auxiliary Feedwater Pump speed controller located on the transition section of CB-09. These controls will be used in conjunction with the process l

indications located directly above them. Any misoperation which may

occur due to these controls being difficult to reach will be immediately apparent to the operator through the feedback provided by l

these indications.

SUPPLEMENT 1

.- =. a.-.=

HED CONTROL No. 335 A. HED DESCRIPTION The oblique angle from the operator's line of sight to the plane of the

^

outboard annunciators is less than 45* from several control stations. This contributes to poor readability, especially on panels CB-09, CB-11, and CV-01. In the case of CV-01, many annunciators cannot be read at all from the control station.

B. GUIDELINE REFERENCE NUREG-0700: 6.1.2.2.e.(2)

C. LOCATION ,

CB-09,11 CV-01 ,

D. POTENTIAL SAFETY CONSEQUENCES

1. Failure to respond to alarm
2. Possible equipment damage due to delayed response time.

E. ASSESSMENT PROCESS

1. Evaluated readability of far left/right annunciator tiles from annunciator control station.
2. Evaluated feasibility of relocating control stations to increase viewing angle.
3. Evalpated feasibility of adding control stations in an area such that viewing angle would be 45*.
4. Evaluated feasibility of moving annunciator tiles to a more readily viewable position.
F. BACKFIT l

JUSTIFICATION

1. CPSES realizes that the viewing angles are acute and that it affects the operators ability.to read the legends on the outboard columns of the annunciator matrices of the annunciators on CB-09, CB-11, and CV-01 from their respecitve annunciator control stations. -

i

The viewing angles on CB-09 and CB-11 were re-evaluated and, in particular, operators were consulted. It is our conclusion that the problem does not affect the operator's ability to respond to those alarms in a timely manner.

2. For CV-01, the annunciator control station will be moved from the end of the panel closest to the operator to a more central locatioa. The relocation of this control station will generally cause the operator to pass in front of the annunciators prior to reaching the control station. This backfit represents the most reasonable modification for ensuring that the operator knows which annunciators are affected by actions at the control station.

l i

l l

l O

hS - - , _ _

SUPPLEMENT 1

HED CONTROL NO. 336 1

A. HED DESCRIPTION l i

There is no scheme for rapid positive identification of Unit 1 and Unit 2 l procedures. <

B. GUIDELINE REFERENCE NUREG-0700: 6.1.3.1.d. -

C. LOCATION q

Control Room

, s D. POTENTIAL SAFETY CONSEQUENCES Incorrect operator response E. ASSESSMENT PROCESS None required eq.

O F. BACKFIT Procedures mantsals for Unit I and Unit 2 vill be uniquely identified.

\

5 ( 4-. _

s k h k b ,

4 l

b

\ 'N.

I \ . ,

I f \ .

i

~

~,g': . _ _

v N *.

'N / s ,

4 I

g - Y4

  • t

^

,fy

~

~, . -

.J { '

SUPPLEMENT 1

.m v _: _ .

HED CONTROL NO. 337 l

A. HED DESCRIPTION According to plant conventions for shared panels, Unit I controls and displays are located toward the Unit I control room and Unit 2 controls and displays are located toward the Unit 2 cuntrol room. This convention is violated on the Radiatior. Monitoring Panel.

B. GUIDELINE REFERENCE NUREG-0700: 6.1.3.1.e(4)

L C. LOCATION CV-13 D. POTENTIAL SAFETY CONSEQUENCES Misinterpretatic.' ;f displays E. ASSESSMENT PROCESS Evaluated feasibility of rearranging displays F. BACKFIT Displays for Unit 1 and Unit 2 Containment Radiation will be interchanged.

e SUPPLEMENT 1

HED CONTROL NO. 342 A. HED DESCRIPTION Human factors improvements have not been made to the NIS Panel, the Meteorological Panel, the In-Core Inscrumentation Panel, or the Recorder Panel.

B. CUIDELINE REFERENCE NUREG-0700: 6.1.2.5 -

C. LOCATION NIS Panel Meteorological Panel. In-Core Instrumentation Panel. Recorder Panel. ,

D. POTENTIAL SAFETY CONSEQUENCES

1. Inability to operate controls
2. Failure to read displays.

E. ASSESSMENT PROCESS Determine operator interface requirements at these panels.

F. BACKFIT None.

1. JUSTIFICATION Each of these panels was design reviewed for compliance with NUREG-0700 guidelines. Several HEDs were identified on each panel.

The HEDs written against the Meteorological Panel and against the Recorder Panel are covered in this report and will be dispositioned as 1 .

l described herein. The HEDs written against the NIS Panel and against ,

the In-Core Instrumentation Panel were not addressed since the operator very rarely interfaces with these panels.

O l

l SUPPLEMENT 1 )

1

HED CONTROL NO. 346 A. HED DESCRIPTION Ambient noise levels make verbal communications difficult at distances of

. over 16 feet.

B. GUIDELINE REFERENCE NUREG-0700: 6.1.5.5.a.

C. LOCATION Control Room D. POTENTIAL SAFETT CONSEQUENCES Failure to c2anunicate E. ASSESSMENT PROCESS None required F. BACKFIT Carpeting is being installed in the control room to reduce ambient noise.

'l O

e 4

4 SUPPLEMENT 1

l l

I '.

l HED CONTROL NO. 348 i

l l

A. HED DESCRIPTION Illumination levels are excessive.

B. GUIDELINE REFERENCE l NUREG-0700: 6.1.5.3.a C. LOCATION CB-04, 12 D. POTENTIAL SAFETY CONSEQUENCES None .

4 E. ASSESSMENT PROCESS Illumination survey.

F. BACKFIT Translucent diffusing panels will be installed to temper the illumination levels in these areas.

t I

I I

I l'

I SUrrtEnEnT t j

i HED CONTROL NO. 349 A. HED DESCRIPTION l Illumination levels are inadequate B. GUIDELINE REFERENCE NUREG-0700: 6.1.5.3.a C. LOCATION SRO desk D. POTENTIAL $AFETY CONSEQUENCES None .

E. ASSESSMENT PROCESS Illumination survey F. BACKFIT SRO desk will be provided with a desk lamp to improve workplace illumination.

6 3

e l

l SUPPLEMENT 1

.. , - ~ . .- . .. . . , . . .-

u.

!i HED CONTROL NO. 350 1

A. HED DESCRIPTION Reflectance of upper walls is excessive B. GUIDELINE REFERENCE NUREG-0700: 6.1.5.3 3 C. LOCATION Control room 4

j D. POTENTIAL SAFETY CONSEQUENCES None ,

E. ASSESSMENT PROCESS Reflectance calculations from illumination / luminance data.

F. BACKFIT None.

1. JUSTIFICATION The high reflectance of the upper walls in the control room does not degrade the overall lighting levels in the control room.

4

  • e SUPPLEMENT 1

1 HED CONTROL No. 351 A. HED DESCRIPTION Reflectance of consoles / panel surfaces is excessive.

B. GUIDELINE REFERENCE NUREG-0700: 6.1.5.3.g C. LOCATION Control room D. POTENTIAL SAFETY CONSEQUENCES None -

E. ASSESSMENT PROCESS Reflectance calculations from illumination / luminance data.

F. BACKFIT None.

1. JUSTIFICATION The high reflectance of the consoles / panel surfaces does not degrade the overall 1ighting levels in the control room.

O e

4

HED CONTROL No. 352 A. HED DESCRIPTION Illumination levels under Train A emergency lighting are insufficient.

B. GUIDELINE REFERENCE NUREG-0700: 6.1.5.3.c C. LOCATION CV-01, 03 ,

i D. POTENTIAL SAFETY CONSEQUENCES Inability to read E. ASSESSMENT PROCESS Emergency lighting Survey ,

l l

F. BACKFIT Perform a review of lighting system and evaluate the feasibility of adding Train B lighting at CV-01 and CV-03.

SUPPL 1 MENT 1

._- ._.. _-- - . _ _ ._-.m _

i HED CONTROL NO. 353 l

1 l

A. EED DESCRIPTION Control Room temperature was not maintained within comfort range.

B. GUIDELINE REFERENCE NUREG-0700: 0700: 6.1.5.1.a C. LOCATION Control Room D. POTENTIAL SAFETY CONSEOUENCES NONE ,

E. ASSESSMENT PROCESS Environmental Survey F. BACKFIT Control Room HVAC system is currently being modified. The survey will be repeated when the implementation is complete.

f l

l

  • l arrram~;u

1 1

l 1

l I 1 l

l

)

1 4

3.0 COMMUNICATIONS HEDS S 8 e

O SUPPLEMENT 1

HED CONTROL NO. 71 l A. HED DESCRIPTION Inadequate provisions for consnunication between HVAC panel and the main control room and between the In-Core Instrumentation panel and the main control room.

B. GUIDELINE REFERENCE NUREG-0700: 6.2.1.8.a.

C. LOCATION Control room.

D. POTENTIAL SAFETY CCNSEQUENCES Delay in or incorrect HVAC operation.

E. ASSESSMENT PROCESS No assessment necessary.

F. BACKFIT A page phone has been installed at the HVAC panels. Communications between the In-Core Instrumentation panel and the main control room are not requirad.

i i

i SUPPLEMENT 1

1 l

l HED CONTROL NO. 118 A. HED DESCRIPTION Presently, there is only one outside phone in the control room. There is no dedicated phone for NRC hotline, state or local authorities, or NRC operations center.

B. GUIDELINE REFERENCE NUREG-0700: 6.2.1.8.a.

  • C. LOCATION Control room.

D. POTENTIAL SAFETY CONSEQUENCES N/A E. ASSESSMENT PROCESS Requirements for communications in the control room were assessed.

F. BACKFIT All required communica. ion links to the control room will be provided.

These communication links include the following:

1. Dedicated link to NRC Incident Response Center over the Emergency Notification System.
2. Dedicated telephone links to the Technical Support Center (TSC),

Emergency Operations Facility (EOF), Operations Support Center (OSC). Dept. of Public Safety. Hood County EOC, Somervell County EOC, and the System dispatcher.

3. Two-way radio communication to the TSC, EOF, and OSC.
4. Normal telephone communications to all of the above.
5. Sound-powered telephor.e communications to various In-Plant areas.

SUPPLEMENT 1

_ . , _ . . - . _ . . . . . ~, __ ___. .

HED CONTROL NO. 119 A. HED DESCRIPTION No communication link between control room and Technical Support Cancer.

B. GUIDELINE REFERENCE NUREG-0700: 6.2.1.7.

C. LOCATION Control room.

D. FOTENTIAL SAFETY CONSEQUENCES N/A .

E. ASSESSMENT PROCESS No assessment necessary.

4 F. BACKFIT The following communication links will be provided between the control room and the Technical Support Center:

1. Dedicated telephone
2. Two-way radio
3. Normal telephone S

e e

SUPPLEMENT 1

l HED CONTROL NO. 120 i

l l

l A. HED DESCRIPTION j

Sound-powered jack communications are incomplete.

l B. GUIDELINE REpERENCE NUREG-0700: 6.2.1.3.b.(6)

C. LOCATION.

Control room and HSP D. POTENTIAL SAFETY CONSCOUENCES N/A E. ASSESSMENT PROCESS The sound-powered jack communications were re-evaluated.

F. BACKFII Sound-powered jack communications have been completed. Headsets will be provided in the control room and at the Hot Shutdown Panel.

C i

l SUPPLEMENT 1-

ll HED CONTROL NO. 347 A. HED DESCRIPTION Page speaker volume prevents detection of some auditory alarms.

B. GUIDELINE REFERENCE NUREG-0700: 6.2.1.6.3(1)

C. LOCATION Control room D. POTENTIAL SAFETY CONSEQUENCES Failure to respond to alarm E. ASSESSMENT PROCESS None required F. BACKFIT Page speaker volume will be adjusted to ensure that speaker communications do not cask auditory alarms.

{

1 o

O O

l l

I

)

4.0 ANNUNCIATOR HEDS

.O O

O e

1 SUPPLEMENT 1

1 .

l l  !

HED CONTROL NO. 308 l

l A. HED DESCRIPTION i Audible alarms are not discernible over ambient control room noise.

I B. GUIDELINE REFERENCE NUREG-0700: 6.3.2.1.a. ,

C.' LOCATION Control room.

D. POTENTIAL SAFETY CONSEQUENCES Failure to respond to alarm condition. ,

E. ASSESSMENT PROCESS Control room noise survey.

F. BACKFIT Audible alarm levels will be adjusted such that they are at least 10 dBA

, ever ambient noise levels as measured from any station where auditory l

recognition is required.

8 e a

~ SUPPLEMENT 1' I

HED CONTROL NO. 310 A. HED DESCRIPTION The ability of an alarm to capture the operator's attention could not be evaluated.

B. GUIDELINE REFERENCE NUREG-0700: 6.3.2.1.c.

l C. LOCATION I

Control room.

D. POTENTIAL SAFETY CONSEQUENCES Failure to respond to alarm condition.

E. ASSESSMENT PROCESS Control room noise survey.

F. BACKT!T Audible alarm levels will be adjusted such that they are at least 10 dBA 2 above ambient noise levels as measured from any station where auditory recognition is required.

e e

e

~ SUPPLEMENT 1

HED CONTROL NO. 311 A. HED DESCRIPTION Alar.a detection levels could not be evaluated.

2 B. GUIDELINE REFERENCE NUREG-0700: 6.3.2.1.d.

C. LOCATION Control room.

s D. POTENTIAL SAFETY CONSEQUENCES Failure to respond to alarm condition ,

E. ASSESSMENT PROCESS Control room noise survey.

F. BACKFIT Audible alarm levels will be adjusted such that they are at least 10 dBA chove ambient noise levels as measured from any station where auditory recognition is required.

e 4

9 O

e

. SUPPLEMENT 1-a

l l

l l HED CONTROL No. 315 l

l l

A. HED DESCRIPTION When the lamp drive transistor fails on the cards, the lamp box fails OFF.

If there is a failure in the control card (which controls the flash rate forindividualalarms),itwillalsofail0F[.

B. GUIDELINE REFERENCE NUREG-0700: 6.3.3.2.c.

C. LOCATION Control room.

D. POTENTIAL SAFETY CONSEQUENCES Failure to identify problems.

E. ASSESSMENT PROCESS No assessment necessary. ,

F. BACKFIT A full functional annunciator test will be performed per shif t and repairs made as required.

i SUPPLEMENT 1

I 1

1 HED CONTROL NO. 318 A. HED DESCRIPTION Annunciator tile legends are not specific.

B. GUIDELINE REFERENCE NURZG-0700: 6.3.3.4.a.

C. LOCATION Control room.

D. POTENTIAL SAFETY CONSEQUENCES Failure to understand or correct problem. .

E. ASSESSMENT PROCESS A readability survey was performed.

F. BACKFIT The legends have been reviewed and will be rewritten, as necessary, to make the message clear and understandable. An informal design change procedure has been instituted to assure that new annunciators are human factored in accordance with Appendix C before installation.

SUPPLEMENT 1

HED CONTROL NO. 323 A. HED DESCRIPTION Lack of strong administrative procedures governing testing of annunciators.

l B. GUIDELINE REFERENCE NUREG-0700: 6.3.4.1.d.(2) and 6.3.4.2.c.

C. LOCATION Control room.

D. POTENTIAL SAFETY CONSEQUENCES ,

Failure to detect alarm failure. .

E. ASSESSMENT PROCESS

1. The need to test annunciators was assessed.
2. The methods by which r.nnunciators could be tested were assessed.

F. BACKFIT Administrative procedures will be implemented for the testing of annunciators and replacement of defective bulbs, as required.

4 SUPPLEMENT 1

5.0 CONTROLS REDS 6

O SUPPLEMENT 1

g . .. . .
  • J HED CONTROL NO. 27 A. HED DESCRIPTION Control switches vioiste direction of movement convention (e.g., AUTO is counter-clockwise and CLOSE is clockwise) and control positions are inconsistent across controls.

B. GUIDELINE REFERENCE NUREG-0700: 6.4.2.1.

C. LOCATION CB-03 and CB-10.

D. POTENTIAL SAFETY CONSEQUENCES

1. Improper control operation.
2. Loss of sampling capacity.
3. Loss of main steam relief heating steam.

E. ASSESSMENT PROCESS Feasibility of modifying switch positions was assessed.

i F. BACKFIT Control switch positions will be changed to meet established human engineering stereotypes.

c..n n m .m,= .

- ,--nw-r- ---- ~ - * * ' ' - '

' ~ ' * ' - " ' * ' ' ' " ' ~~

l HED CONTROL NO. 28 i

A. HED DESCRIPTION Different switch types are used kr valve controls - different plant equipment (i.e., pumps, valves) operated by J-handles.

3. GUIDELINE REFERENCE NUREG-0700: 6.4.2.2.d.

C. LOCATION CB-08 and CB-09.

D. POTENTIAL SAFETY CONSEQUENCES

1. Incorrect system operation.
2. Loss of feedwater could result in possible plant shutdown.

E. ASSESSMENT PROCESS

1. Reviewed feasibility of shape coding.
2. Reviewed feasibility of symbol coding. -

F. BACKFIT J-handles valvs controls will.be coded with a valve symbol on the handle to differentiate them from J-handle pump controls.

m SUPPLDENT 1

i HED CONTROL NO.161 t i

A. HED DESCRIPTION -

Continuous adjustment rotary control knobs are uncomfortable and fatiguing if held in the contact position for a long time.

B. GUIDELINE REFERENCE NUREG/CR-1580: CON-37 C. LOCATION CB-03 i D. POTENTIAL SAFETY CONSEQUENCES Failure to open containment hydrogen purge dampers.

4 E. ASSESSMENT PROCESS

1. Function of switches were reviewed.
2. Electrical schematic drawings were reviewed to verify circuits.

F. BACK?lT Continuous adjustment rotary controls will be provided with extended handles to make them less fatiguing to operate.

9 O

O O

t SUPPLEMENT 1-c

  • * - w ~ m -w ---% ~ -en- wg, ~ T- -m- --n y e- v4 %v

HED CONTROL NO. 169 A. HED DESCRIPTION CMC switches stop between detented positions.

B. GUIDELINE REFERENCE NUREG-0700: 6.4.4.5.b.2.

C. LOCATION CB-02 and CB-04.

D. POTENTIAL SAFETY CONSEQUENCES

1. Incorrect SI valve alignment.

2

2. Loss of SI flow.

j E. ASSESSMENT PROCESS Incorrect positioning of these ruitches was investigated.

F. BACKFIT None.

1. JUSTIFICATION These CMC switches can only be stopped between positions with a concentrated effort to do so. If they are inadvertently stopped between positions, feedback is provided through the valve position lights located on the switch module. Furthermore, these valve controls are used very infrequently under strong administrative controls making misoperation very unlikely.

l 1

SUPPLEMENT 1

i l

l HED CONTROL NO. 172 l

l A. HED DESCRIPTION There is no coding or viru.s1 enhancement for controls.

B. GUIDELINE REFERENCE NUREG-0700: 6.4.2.2.

C. LOCATION--

All~ panels.

D. POTENTIAL SAFETY CONSEQUENCES

1. Incorrect control / display association.
2. Iuptcper control actuation.

E. ASSESS 11ENT PROCESS The applicability of various types of visual enhancements were examined.

F. BACKFIT -

Controls will be coded. and visually enhanced as outlined in Appendix G:

v I

i

\

1 , ,

' ~~~

~+ . , _ ,

/

'l # SUPPLEMENT 1. l s, ,

3 .... 1, , . . - . v ._ _

l HED CONTROL No. 183 A. HED DESCRIPTION The color coding of pushbuttons on the miniature turbine control panel and on the process controllers is indiscriminant.

B. GUIDELINE REFERENCE ,

NUREG-0700: 6.4.2.2.f.

C. LOCATION CB-04, CB-05, CB-06, CB-08, CB-09. CB-10, CV-01, and CV-03.

D. POTENTIAL SAFETY CONSEQUENCES None.

E. ASSESSMENT PROCESS No assessment necessary.

F. BACKFIT Color coding of process controller pushbuttons will be changed as follows:

Amber - manual White . auto Red - increase output Green - decrease output The pushbutton color coding on the miniature turbine control panel is clear and unambiguous.

I i

l l

SUPPLEMENT 1

1ED CONTROL NO. 214 i

l A. HED DESCRIPTION A rotary control with clockwise-counter clockwise movement is used to control a " lower" and " raise" function.

B. GUIDELINE REFERENCE NUREG-0700: 6.4.1.1.a. or 6.4.2.1.

C. LOCATION CB-11 D. POTENTIAL SAFETY CONSEQUENCES Diesel Generator shutdown from incorrect voltage control.

E. ASSESSMENT PROCESS No assessment necessary.

F. BACKFIT Switch configurations will be changed to ha7e " RAISE" in the clockwise position and " LOWER" in the counterclockwise position.

6 l SUPPLEMFNT 1

~

HED CONTROL NO. 244 l

l l

A. HED DESCRIPTION The association between controls and related display is not immediately apparent. i.e., the meaning of coding of selector switch and pointer on trend recorder is not obvious.

B. GUIDELINE REFERENCE NUREG-0700: 6.4.2.2.f.(2).

C. LOCATION CB-07 ,

D. POTENTIAL SAFETY CONSEQUENCES None.

E. ASSESS!ENT PROCESS Feasibility of colcr coding was reviewed.

F. BACKFIT Color coding will be added to key each selector switch to the appropriate recorder pen.

O SUPPLDfENT 1

HED CONTROL No. 344 A. HED DESCRIPTION Westinghouse controllers are used in the control room for the Steam Generator PORV'a. Leeds and Northrup controllers are used for the same function cn the Hot Shutdown Panel.

B. GUIDELINE REFERENCE NUREG-0700: 6.4.1.1 (2)

C. LOCATION RSP D. POTENTIAL SAFETY CONSEQUENCES Misoperation of controllers E. ASSESSMDIT PROCESS Determine what, if any, operational differences exist between these two controller types.

F. BACKFIT None.

1. JUSTIFICATION The Westinghouse controllers used for Steam Generator PORV control from the control room are setpoint controllers and operate automatically to maintain main steam line pressure at the setpoint l i

valve. The Leeds and Northrup controllers on the HSP are strictly manual loaders used to manually position the Steam Generator PORV's to regulate main steam line pressure. These operational differences dictated the use of the two different controller types.

l I

l SUPPLEMENT 1


-v -+-w-- , 7,- e-- e- 3- ,.--p - M +-- + .-p *

.- med.--.w.- .g -- - , - em -we ..,y. . . ,y --%e,e, y ,

l l

l 1

6.0 VISUAL DISPLAY HEDS l

l l

SUPPLDfENT 1

l l

HED CONTROL NO. 8 l

I l A. HED DESCRIPTION If rod control lever is held down, the step counters will continue to advance beyond 228 steps after the control rods are entirely out.

B. GUIDELINE REFERENCE NUREG-0700: 6.5.1.1.e.

C. LOCATION CB-07.

D. POTENTIAL SAFETY CONSEQUENCES Only applicable in bank control with no safety consequences.

E. ASSESSMENT PROCESS CPSES reviewed with Westinghouse, the supplier of this equipment, the criteria for control board interface as it relates to reactor operation and control rod manipulation.

F. BACKFIT The Westinghouse design for control rod control requires that these step counters continue to count past 228 steps if the operator inadvertently advances the control rods after they are entirely out. A recovery procedure will be provided for the operator in the event that this misoperation occurs.

I l

. l I

SUPPLEMENT 1

^

4 i

HED CONTROL NO. 13 i

N I

I A. HED DESCRIPTION j' Reactor Coolant Pump vibration levels are not displayed in startup area.

4 B. GUIDELINE REFERENCE i

! NUREG-0700: 6.5.1.1.

1 i

k C. LOCATION l CV-07 D. POTENTIAL SAFETY CONSEQUENCES

)

l Possible Reactor Coolant Pump damage.

E. ASSESSMENT PROCESS

! The cperational requirements to successful perfernance in situations involving this indication were reviewed.

F. BACKFIT

None.
1. JUSTIFICATION Section 7.5 of the CPSES FSAR details the "Information Systems l Important to Safety". The analyses and evaluations performed in i conjunction with the development of this section did not identify RCP
vibration as a parameter required to permit the operator to take

- action to mitigate design basis accident event scenarios.

)

I i

1

)

  • i 4

i SUPPLEMENT 1

n..

HED COUROL NO. 29 A. HED DESCRIPTION Reactor coolant drain tank level indication is not displayed in.the control room.

a B. GUIDELINE REFERENCE NUREG-0700: 6.5.1.1.b .

C. LOCATION Control room D. POTENTIAL SAFETY CONSEQUENCES None.

E. ASSESSMENT PROCESS No assessment necessary.

F. BACKFIT None.

1. JUSTIFICATION Section 7.5 of the CPSES FSAR details the "Information Systems Important to Safety". The analyses and evaluations performed in conjunction with the development of this section did not identify RCDT level as a parameter required to permit the operator to take action to mitigate design basis' accident event scenarios.

l SUPPLEMENT 1

HED CONTROL NO. 39 A. HED DESCRIPTION Inconsistent pointer positi8on in de-energized circular matars. I i

l B. GUIDELINE REFERENCE NUREG-0700: 6.5.1.1. ,

I l

C. LOCATION .

CB-11 l

l D. POTENTIAL SAFETY CONSEQUENCES .

Incorrect display interpretation.

E. ASSESSMENT PROCESS .

Each meter was examined to determine its proper pointer position when de-energized.

F. BACKFIT None.

I 1. JUSTIFICATION Redundant information exists to determine whether a meter has failed or whether it is reading zero. For vo'ltmeters, the redundant

'nformation is the position of the feeder breaker (s) for that bus. If one of the feeder breakers is closed then there should be voltage on the bus. Ammeter readings can be verified through the associated

. voltmeters. During normal operation, if there is voltage on a bus, then there should be current flow'from the bus (as measured at the feeder breaker). Amneter readings can be verified locally. This is i

done twice per shift as part of the operators daily routine. l Frequency meters should always read 60 Hz when energized. Wattmeters should read positive whenever there is voltage and current.

SUPPLEMENT 1 l

1 1

l HED CONTROL NO. 41 1

A. HED DESCRIPTION There is no test function for some LED displays.

B. GUIDELINE REFERENCE NUREG/CR-1580: VD-91.

C. LOCATION .

CB-08 CB-09. CB-10. CB-12.

D. POTENTIAL SAFETY CONSEQUENCES None E. ASSESSMENT PROCESS Assessed life span of LEDs.

F. BACKFIT None. -

1. JUSTIFICATION LEDs are highly reliable and typically long-lived displays. Should a segment on one of the digits fail, our evaluation identified six undetectable failures. These failures are illustrated below:

Y

-l Y Y

- - - ~

g

,g,-g -

g g g

Each of these failures was evaluated as it affected each digit of each digital display. The only significant failure was determined to be in the " hundreds" digit of the AFWPT SPEED display since this failuke-could go undetected for some time. Such a failure, however, would not affect system operation. Redundant AFW flow indications are provided to assure that the AFWPT is performing its safety function.

Furthermore, periodic surveillance tests will be performed to assure that each digital display is operating properly.

l SUPPLEMENT 1

HED CONTROL NO. 63 A. HED DESCRIPTION Brightness of indicater lights is variable, due to the use of different light covers.

B. GUIDELINE REFERENCE NUREG-0700: 6.5.3.1.

C. LOCATION All panels.

D. POTENTIAL SAFETY CONSEQUENCES None.

E. ASSESSMENT PROCESS Extent / magnitude of the variability was evaluated.

F. BACKFIT -

The existence of different intensities of red and green indicator lights caused by the use of d1fferent indicator light types does not, in CPSES's opinion, affect discrimination between priorities or the operator's color 4

sensitivity. The different intensities of red and green indicator lights that exists in the Master Specialtier Series 90K and 800K lights is caused by the fact that some have translucent diffusers and some do not. For Master Specialties Series 90K and 800K lights, all translucent diffusers will be removed.

O t

SUPPLEMENT 1

HED CONTROL NO. 81 l

J A. HED DESCRIPTION Scales on trend recorders obscure pen traces and other scales.

B. GUIDELINE REFERENCE NUREG/CR 1580: VD-10 and VD-78.

C. LOCATION CB-05 and CB-09.

D. POTENTIAL SAFETY CONSEQUENCES

1. Delayed or incorrect reading. .
2. Reactor trip.
3. Loss of seal flow.

E. ASSESSMENT PROCESS Alternative solutions were generated and evaluated.

F. BACKFIT None.

1. JUSTIFICATION -

These recorders are used to trend selected parameters. They are not used for indication. As such the visibility of the pen traces and scales from the normal operating position is not critical.

Indications of the parameters required for normal operation are l

provided on vertical meters .%cated in close proximity to these recorders.

SUPPLEMENT 1

HED CONTROL NO. 85 l

A. HED DESCRIPTION J-handle " target" colors are difficult to differentiate from each other.

B. GUIDELINE REFERENCE NUREG-0700: 6.5.1.6.3.2.

C. LOCATION All panels.

D. POTENTIAL SAFETY CONSEQUENCES Delay in control operation.

E. ASSESSMENT PROCESS Cause of poor differentiation between colored flag indicators was determined.

F. BACKFIT The " target" colors are difficult to differentiate between because the targets are dirty as a result of construction activity. The targets will be cleaned to make colors easy to differentiate.

l

HED CONTROL NO. 89 A. HED DESCRIPTION There is no lamp test provided to test indicator lights associated with control switches.

B. GUIDELINE REFERENCE NUREG-0700: 6.5.3.1.a.2.

C. LOCATION All panels.

D. POTENTIAL SAFETY CONSEQUENCES Delay in response to component failure, i E. ASSESSMENT PROCESS Functional modes of indicator lights were investigated.

F. BACKFIT Sufficient feedback exists for the operator to determine a lamp failure without the use of a lamp test feature. Administrative procedures will be written to require the operator to perform a check for and replace failed lamps at each shift turnover.

O SUPPLDiENT 1

- p FED CONTROL NO. 93 A. HED DESCRIPTION l No control coding is currently being used for:

a. Mechanical valves, pumps, breakern, motors, etc.

l

b. Throttle valves.
c. Emergency or critical controls.

B. GUIDELINE REFERENCE NUREG-0700: 6.4.2.2.

C. LOCATION CB-08 and CB-09.

D. POTENTIAL SAFETY CONSEQUENCES Improper control actuation.

E. ASSESSMENT PROCESS

1. Reviewed various forms of coding, including shape, size, and symbology -

coding.

2. Estimated effectiveness of using labeling to contain information, differentiating types of components.
3. Assessed symbology coding as the most effective and feasible means of denoting various types of components.

F. BACKFIT Control switches will be coded as specified in Appendix G.

1 I

l i I i

l SUPPLEMENT 1 l

HED CONTROL NO. 94 l

A. HED DESCRIPTION -

, Incomplete color coding of indicators.

l i

l B. GUIDELINE REFERENCE 1

6.5.1.6.

NUREG-0700:

C. LOCATION Control room.

D. POTENTIAL SAFETY CONSEQUENCES N/A -

E. ASSESSMENT PROCESS Effort to complete indicator color coding was assessed.

F. BACKFIT RG 1.97, Rev. 2 Category 1 indications will be color-coded as specified in Appendix G.

O i -

I l.

i I

l SUPPLEMENT'1

w& m a M M+*

HED CONTROL NO. 102 1

A. HED DESCRIPTION Overlapping pens on trend recorders cause other pens to be obscured.

B. GUIDELINE REFERENCE NUREG-0700: 6.5.4.2.b.

C. LOCATION CB-09. CB-05 D. POTENTIAL SAFETY CONSEQUENCES

1. Possible incorrect FW operation
2. Delay in operation of control.
3. Reactor trip.

E. ASSESSMENT PROCESS Alternative solutions were generated and evaluated.

F. BACKFIT None.

1. JUSTIFICATION These recorders are used to trend selected parameters. They are not used for indication. As such, the visibility of the pen traces and scales from the normal operating position is not critical.

Indications 'of the parameters required for normal operat'sn are provided on vertical meters located in close proximity to these recorders.

SUPPLEMENT 1

i HED CONTROL NO. 126 i

l A. HED DESCRIPTION There is no direct indication of percent flow bypassed. It must be determined by comparing letdown flow to CVCS return flow. These two indicators have different scales and are not adjacent to each other.

B. GUIDELINE REFERENCE NUREG-0700: 6.5.1.1.b.8.

C. LOCATION CB-06 D. POTENTIAL SAFETY CONSEQUENCES None.

E. ASSESSMENT PROCESS Feasibility of equipment modification was evaluated.

F. BACKFIT None.

1. JUSTIFICATION Indication of % BTRS bypass flow is not required. It is independent of charging and latdown flow. Indication is provided for BTRS demineralizer flow in gallon-per-minute.

SUPPLEMENT 1

i HED CONTROL NO. 260 l

1 l

l A. HED DESCRIPTION Indicator light lenses are subject to accidental interchange.

B. GUIDELINE REFERENCE NUREG-0700: 6.5.3.1.c.(2).

C. LOCATION All panels.

D. POTENTIAL SAFETY CONSEQUENCES Delay or improper equipment operation. -

E. ASSESSMENT PROCESS Examine all potential problem areas.

F. BACKFIT All potential problem areas were examined and it was determined that the only indicator light lenses that are subject to interchange are the indicator light lenses on the Safety System Inoperable Indicators (SSII).

These SSII boxes have been redesigned. New indicator lights are designed such that lenses need not be removed to change bulbs; thus, inadvertent interchange is not a problem.

O 4

9 k

HED CONTROL No. 267

A. HED DESCRIPTION

( Trend recorders use frosted glass.

B. GUIDELINE REFERENCE NUREG-0700: 6.5.4.1.k.

C. LOCATION ,

CB-10 D. POTENTIAL SAFETY CONSEQUENCES

., Possible turbine shutdown or damage.

E. ASSESSMENT PROCESS

! 1. Trend recorder glass was examined to determine effect on readability.

2. Replacement glass was examined.

, 3. Recorder operation was examined.

) >

i F. BACKFIT None.

1. JUSTIFICATION Recorders with frosted glass are equipped with display lighting mounted inside recorder doors. When the recorders are energized this display lighting shou'ld improve the readability of recorded data to acceptable levels.

t l

i 1 -l i \

I Ma .w.

i HED CONTROL NO. 269 i

l A. HED DESCRIPTION Trend recorder doors in the control room could swing down when unlatched and stride and obscura components located below them.

B. GUIDELINE REFERENCE NUREG-0700: 6.5.4.1.

C. LOCATION All panels.

D. POTENTIAL SAFETY CONSEQUENCES Inadvertent control actuation.

E. ASSESSMENT PROCESS

1. Effect on operations was evaluated.
2. Potential consequences of plant safety were examined.

F. BACKFIT Recorder doors that swing down and obscure components below them are missing rubber restraints on the door hinges. These restraints will be replaced.

I 2

I 1

SUPPLEMENT 1

. _ _ _ ~

HED CONTROL NO. 298 i

A. HED DESCRIPTION Indicator lights are used to indicate unfavorable status.

B. GUIDELINE REFERENCE NUREG-0700: 6.5.3.1.d.

C. LOCATION CB-08, CB-09. CB-10, and CV-01.

D. POTENTIAL SAFETY CONSEQUENCES Failure to detect problem.

E. ASSESSMENT PROCESS Examined enhancements to improve operator awareness.

F. BACKFIT These red lights will be changed to white lights to indicate which parameter in a multiple input annunciator window is out of limits as per the color coding detailed in Appendix G. Specific alarm response procedures will be written to define the operator interface with these indicator lights. ,

1 e

t SUPPLEMENT 1

i 1

l i

HED CONTROL No. 338 A. HED DESCRIPTION Some indicating lights do not follow the existing indicating light color code convention.

B. GUIDELINE REFERENCE

, NUREG-0700: 6. 5.1. 6. d . (1)

C. LOCATION CV-03, ESP D. POTENTIAL SAFETY CONSEQUENCES Misinterpretation of display E. ASSES $ MENT PROCESS

1. Determine intended meaning of indicating light.
2. Examine feasibility of changing color to conform to established color

~

code.

F. BACKFIT Indicating light colors will be changed to conform to the color code outlined in Appendix G.

O SUPPLEMENT 1

4 7.0 LABELING & LOCATION AIDS HEDS l

e e

SUPPLDfENT 1

l l

l HED CONTROL NO. 107 1 A. HED DESCRIPTION Train A and Train B color coding is not applied consistently and/or correctly.

B. CUIDELINE REFERENCE NUREG-0700: 6.6.1.1.

C. LOCATION All panels.

D. POTENTIAL SAFETY CONSEQUENCES ,

Improper control actuation.

E. ASSESSMENT PROCESS

1. Usefulness of color coding train designation was assessed.
2. Examined conspicuous train label inconsistencies.

l F. BACKFIT i

j None.

1. JUSTIFICATION Conspicuous train color coding inconsistencies were examined and no errors were found. All apparent errors in train designation were found to be correct as is.

l l

!~ SUPPLEMENT 1 1

HED CONTROL No. 151 A. HED DESC*-lPTION Control switc)s indicating lights, for controls with three indicating ligists, are not labeled.

,. B. GUIDELIKE-REFERENCE NfRF" O'90: 6.6.1.1.

C. LOCA! ION CB-01 D. POTENTIAL SAFETY CONSEQUENCIS ,

1. Loss cf instrument air.
2. Unic shutdown.

E. ASSESSMENT PROCESS The functicnal meaning of indicator lights were determined.

F. BACKFIT None.

1. JUSTIFICATION Control switch indicating lights, for controls with three indicating lights, conform to the iolor coding ...tandard given in Appendix G.

w

\

\

s e /

s s s 8

E

_d \

N SUPPLEMENT 1

HED CONTROL NO. 343 A. HED DESCRIPTION Remote / Local positions on HSP and STP transfer switches are confusing. It 1 is not clear whether the " Remote" position means remote from the control room or remote from the HSP.

B. GUIDELINE REFERENCE NUREG-0700: 6.6.3.2.d and 6.6.3.3.b C. LOCATION HSP, STP D. POTENTIAL SAFETY CONSEQUENCES Misoperation of control switches E. ASSESSMENT PROCESS

1. Determine proper meaning of " Remote".
2. Examine alternate labels that are clearer.

l F. BACKFIT Remote / Local positions on ESP and STP transfer switches will be changed to CR/HSP, respectively.

I 1

1 l

SUPPLEMENT 1

1

\

8.0 PROCESS COMPUTER HEDS e

O b

a G

e.

e s

.~

.)

g /

'N l

~

e

/

  1. 1 W

'\

~

, t

~.

SUPPLEMENT 1

r I

HED CONTROL NO. 36 l

4 A. HED DESCRIPTION There is no readily available index listing information contained in the process computer groups. Thus, the operator must search for desired information ot' memorize the information contained in each group.

B B. GUIDELINE REFERENCE NUREG-0700: 6.7.1.8.b.(2).

C. LOCATION CB-07 D. POTENTIAL SAFETY CONSEQUENCES Delay in finding information.

E. ASSESSMENT PROCESS No assessment necessary.

F. BACKFIT None.

1. JUSTIFICATION Process computer groups are prograr:mable by the operator to fit operating situations. Point nu:nber indeces would provide no assistance since they are subject to' frequent damage.

l i

I

. SUPPLEMENT _,1 _

-1

HED CONTROL NO. 116 A. HED DESCRIPTION There are no operating procedures for operator actions if total loss of the process computer system should occur.

B. GUIDELINE REFERENCE NUREG-0700: 6.7.1.8.a. 5 (b)

, C. LOCATION l

Process computer system.

D. POTENTIAL SAFETY CONSEQUENCES Delay in receiving and assessing information.

E. ASSESSMENT PROCESS No assessment necessary.

F. BACKFIT An operating procedure has been provided for use during total loss of the process computer system.

SUPPLEMENT 1

_ _ - _. - _ - . . . . _ . - - - . - . . ~ - - _-- . .

HED CONTROL NO. 177 A. HED DESCRIPTION

^

There is no color coding on the process computer CRT.

B. GUIDELINE REFFRENCE NUREC/CR-1580: VD-52 ,

C. LOCATION CB-07 D. POTENTIAL SAFETY CONSEQUENCES None.

E. ASSESSMENT PROCESS No assestment necessary.

F. BACKFIT None. -

1. JUSTIFICATION The process computer CRT is only used for alarm summary and therefore color coding provides no advantage. Color coding will be provided on the S.PDS CRT as outlined in Appendix G.

O I

.__ ~. -. -

SUPPLEMENT l' --

HED CONTROL NO. 339 A. HED DESCRIPTION Alarm legends on P2500 process computer do not match alarm legends on control board annunciators.

B. GUIDELINE REFERENCE NUREG-0700: 6. 7.3. 2. f. (1)

C. LOCATION Control Room l

D. POTENTIAL SAFETY CONSEQUENCES Failure to relate printed alarm message to illuminated annunciator tile.

E. ASSESSMENT PROCESS Examine feasibility of changing process computer alarm legends.

I F. BACKFIT P2500 process computer alarm legends will be changed to match the alarm legends on centrol board annunciator tiles.

+ 0 6 9

s SUPPLEMENT 1 y -

,y-. m em, =- -- -

l l

l l

HED CONTROL NO. 345 A. HED DESCRIPTION Abbreviations in con.puter displays do not conform to those in the Comanche P;ak Steam Electric Station " Dictionary of Acronyms and Abbreviations".

B. GUIDELINE REFERENCE NUREG-0700: 6.7.1.2.c C. LOCATION Process computer D. POTENTIAL SAFETY CONSEQUENCES ,

Misinterpretation of display E. ASSESSMENT PROCESS None required F. EACKFIT -

Abbreviations on computer displays will be changed to conform to those

, listed in the CPSES Dictionary of Acronyms and Abbreviations.

9 j

l SUPPLEMENT 1

9.0 PANEL LAYOUT HEDS

- h$ h1 $

HED CONTROL NO. 25 A. HED DESCRIPTION If operator fails to acknowledge a process computer alarm at printer console, subsequent process computer audio alarms will be inhibited when the main CRT flashes an alarm.

B. GUIDELINE REFERENCE NUREG-0700: 6.7.3.2.

C. LOCATION Printer console.

D. POTENTIAL SAFETY CONSEQUENCES Failure to receive CRT alam message.

E. ASSESSMENT PROCESS Feasibility of reprogramming computer was evaluated.

F. BACKFIT None

1. JUSTIFIttTION This is a desireable feature from the standpoint that it requires the operator to acknowledge each alarm individually as it is printed at the printer console.

9 9

SUPPLEMENT 1 l

_J

l l

HED CONTROL NO. 143 l

l A. HED DESCRIPTION The controls and displays on the Radiation Monitoring Panel are arranged by train and are mirror imaged.

B. GUIDELINE REFERENCE NUREG-0700: 6.8.3.3.

C. LOCATION Radiation Monitoring Panel.

D. POTENTIAL SAFETY CONSEQUENCES ,

None.

E. ASSESSMENT PROCESS Operational situations were reviewed.

F. BACKFIT -

The Radiation Monitoring Panel has been redesigned to correct mirror imaging.

SUPPLEMENT 1

k HED CONTROL No. 285 l

A. HED DESCRIPTION Layout of electrical distribution system controls / indicators is mirror-imaged.

B. GUIDELINE REFERENCE NUREG-0700: 6.8.2.3 C. LOCATION CB-11 D. POTENTIAL SAFETY CONSEQUENCES ,

Misoperation of Diesel Generator controls E. ASSESSMENT PROCESS

1. Reviewed feasibility of rearranging components.
2. Reviewed operability of panel in its present layout.

F. BACRFIT The electrical distribution system controls are best mimicked in a i

" mirror-image" layout. Demarcation and hierarchical labeling was added to the, electrical distribution system indicators to enhance their layout and improve control / display futegration.

Diesel Generator contrcls will be demarcated out of the mimic and rearranged such that the layout of the Diesel Generator 1 controls match the layout of the Diesel Generator 2 controls.

SUPPLEMENT 1

l HED CONTROL NO. 340 l

l A. HED DESCRIPTION Bottom-to-top orientation of Generator Ammeter Select Switches does not match left- to-right orientation of the corresponding displays.

B. GUIDELISE REFERENCE f NUREG-0700: 6.8.2.2.

C. LOCATION CB-11 D. POTENTIAL SAFETY CONSEQUENCES ,

Misinterpretation of display E. ASSESSMENT PROCESS

1. Examine feasibility of rearranging select switches.
2. Examine feasibility of rearranging displays.

F. BACKFIT i

The selector switches will be interchanged to match the left-to-right orientation of the corresponding displays.

6 9

s SUPPLEMENT 1

a b

10.0 CONTROL DISPLAY INTEGRATION HEDS 6

e 4

4 0

SUPPLEMENT 1

HED CONTROL NO. 140 l

A. HED DESCRIPTION Eistable (Reactor trip status) lights t -04 are remote from related Reactor control on CB-07.

B. CUIDELINE REFERENCE NUREG-0700: 6.9.1.2.a.

C. LOCATION CB-04 D. POTENTIAL SAFETY CONSEQUENCES Delay in responding to Reactor protection problems or failures.

E. ASSESSMENT PROCESS

1. Reviewed the feasibility of moving the permissive indicators to CB-07.
2. Analyzed the operator interface with these trip status lights.

l F. BACKFIT None.

4

1. JUSTIFICATION Reactor trip status lights are not required for Reactor control. They. j are used primarily to give the operator information on the status of l 1

reactor trip bistables during normal operation. Reactor control )

permissives/intericeks have been provided to the cperatcr through the l installation of a Permissive and Control Interlock Panel (PCIP) located directly above the reactor controls.

9 SUPPLEMENT 1

HED CONTROL NO. 341 A. HED DESCRIPTION On CB-04, the lef t-to-right arrangement of two pairs of valve controllers (controllers 1-HIC-606 and 1-FK-618 and controllers 1-HIC-607 and 1-FK-619) and the representation of those pairs of valves in a mimic are reversed.

4 B. GUIDELINE REFERENCE NUREG-0700: 6. 9. 2. 2. c (1)

C. LOCATION CB-04 D. POTENTIAL SAFETY CONSEQUENCES Misoperation of controllers E. ASSESSMENT PROCESS None required F. BACKFIT Mimic has been reversed to match controller layout.

O 5

SUPPLEMENT 1

l APPENDIX C - ANNUNCIATOR SYSTEM HUMAN ENGINEERING GUIDELINES l

4.0 GUIDELINES 4.3 DETAILED GUIDELINES The detailed human engineering guidelines as provided in the original report are modified to read as noted below:

C. LOCALIZATION OF ANNUNCIATOR ALARM SIGNALS AND CONTROL STATIONS - LOCALIZED

2. Annunciator Control Stations
c. Annunciator Control Stations should be coded to distinguish them from nearby associated controls as specified in Appendix G.

E. PRIORITIZATIOM OF ANNUNCIATOR ALARMS

3. If color is used to prioritize alarms, the color code should :enform to the guidelines set forth in Appendix G.

t I

SUPPLEMENT 1 C-1

APPENDIX D - VERTICAL INDICATOR HUMAN ENCINEERING CUIDELINES 5.0 GUIDELINES The design requiranents for the coding of vertical indicators has been expanded as noted below:

5.3 DESIGN REQUIREMENTS G. Coding - Both single and dual indicacors may be coded for normal operating range and setpoints. Coding schemes should conform to the guidelines set forth in Appendix G.

i I

D-1 SUPPLEMENT.1

l APPENDIX E - DEMARCATION, LABELING, AND MIMC HUMAN ENGINEERING GUIDELINES 5.0 GUIDELINES The guidelines for train indication on labels and the color coding of mimic have been modified as noted below:

E. Label Desian Reaufrements

4. Label Qualities
f. Train Indication - Train should be indicated on labels for train specific controls and displays.

Train color coding should conform to the guidelines set forth in Appendix G. The design should be selected for ease of recognition at the anticipated viewing distance at which train identification is required.

H. Mimics 9 Color Ceding - HLeic line color should conform to the

, ccior coding scheme set forth in Appendix G.

l E-1 SUPPLEMENT 1

APPENDIX G CODING HDfAN ENGINEERING GUIDELINES G-1 SUPPLEMENT 1

HUMAN ENGINEERING GUIDELINES

1.0 PLAhT

Comanche Peak Steam Electric 3.0 REV. NO. 0

Station REV. DATE _.

2.0 TITLE

CODING STANDARDS 4.0 GUIDELINES

4.1 INTRODUCTION

In the large interactive systems of a nuclear power plant, hundreds of controls and displays must be operated and monitored. Locating and operating the appropriate control or display can be crucial to safe operation of the plant, especially in transient or emergency situations. Operator aids can be useful to support efficient, safe, and expedient operations. One such operator cid that has been proven effective in the identification and processing of j

information is the use of coding schemes. The following sections set forth the r guidelines which should be followed when implementing coding schemes in the

Comanche Peak Ci.am Electric Station (CPSES) control room. .

4.2 BACKGROUND

These guidelines have been pre;i ed for the CPSES control room. Specific

! design requirements and criteria hava been selected based on NUREG-0700 t

guidelines, generally accepted and applied human engineering criteria, and

conventions currently employed in the existing CPSES control board design.

These guidelines were developed as part of the detailed control room design review. In several instances the constraints of the existing design preclude

. backfits which would be optimal in accordance with human engineering guidelines.

4.3 PURPOSE The purpore of these guidelines is to provide specific human engineering guidance and criteria for developing uniform, standardized, coding schemes in I- the CPSES control room. Application of these guidelinas to ths development of

! coding schemes should result in the following: ,

A. Reduced'sisinterpretation of displays B. Reduced visual search time for contrcls/ displays C. Reduced probability of control usage errors D. Esse in identifying functional relationships 4.4 'GEFr.KAL GUIDELINES Coding s-hemes selected for use in the CPSES control room should conform to the following general guidelines:

t A. The meaning assigned to a particular code or coding scheme should be consistent throughout all control room applications. ,

i B. The code or coding scheme should provide redundant information to more pertinent information contained in some other form (e.g. labels, l

scales, etc).

C. The meaning assigned to a particular code or coding scheme should be narrowly defined.

D. Use of codes and coding schemes should not be excessive so as to become confusing or distracting.

i SUPPLEMENT 1

_ __ -G-2 . ~ _ _ _ - _ _ _ _ _ _ ._.-u n.

1 4.5 DETAILED GUIDELINES A. Color Codina

1. Number of colors - The number of colors used for color coding should be kept to a minimum and should not exceed eleven (11).
2. Meaning of colors - The meaning of a particular color should remain the same whether applied to control board mounted devices or to CRTs.
3. Contrast of colors - Diff2 rent colors used in color coding shculd be easily distinguishable from one another.
4. Specific color codes
a. Indicating lights - Color coding used for simple indicating lights should conform to the following standcrds:
1. Red - pump / fan / breaker operating, valve /dampe.r open, process controller output at maximum.
2. Green - pump / fan / breaker not operating, valve / damper closed, process controller output at minimum.
3. Amber - pump / fan / breaker control switch mismatch, process controller in manual.

. 4. White gpump/ fan / breaker auto trip, process condition exists, process controller in auto.

5. Blue - permissive satisfied.
b. Mimic - Color coding used for mimic lines should conform to the following standards:
1. Blue - fluid lines
2. Grey - air lines
3. Green - Train B electrical bus
4. Orange - Train A electrical bus
5. Silver - Train C (non-train) electrical bus
6. White w/di.sgonal black stripes - 133kV alectrical distribetton
7. .White w/ lateral brown acrfpes - 22kV electrical distribucien

. 8. White w/ diagonal brcen stripas - 345kV electrical i distribution 1 I

White indicating lights should be used whenever it is necessary to supplement a multiple input alarm with redundant indications. For instance, consider a design where it is desired to alert the operator to a low priority condition cuch as a high level in one of seversi auxiliary steam'line drain pots. If each drain pot level were annunciated individually, it would use up valuable cnnunciator space. An alternate solution is to have a single multiple input cnnunciator that corresponds with several individual white indicating lights to pinpoint which drain pot level is out of limits.

G-3 SUPPLEMENT 1

1

c. Annunciator Prioritization - Color coding used for annunciator prioritization should conform to the follrwing standards (refer to Appendix C for definition of priorities):
1. Red - first priority
2. Amber - second priority J 3. White - third priority
d. Component labels - Color coding used for component labels should conform to the following standards:
1. White (black text) - component identification
2. Black (white text) - component identification for Reg.

Guide 1.97, Category 1 indications.

I

e. Train ID labels - Color coding used for tr'ain ID labels i should conform to the following standards:
1. Orange (white text) e Train A
2. Green (white text) - Train B
3. White (black text) - Train C (non-train)
f. Scale bands - Color coding used in conjunction with operating range and setpoint banding of indicator scales ,

i should conform to the following standards:

1. Red - reactor trip point ,
2. Amber - caution / marginal zone

, 3. Green - normal operating range

g. Control switches - Color coding applied to control switches shculd be as follows:
1. RaJ ~ autegency/ critical controls 4

~ 2. Tellow'- annunciator controls

h. CRT displays - Color coding used in conjunction with CRT 2IspI'ays should conform to the following standards:
1. Bar graphs
1. red - parameter in alarm state
11. green - parameter within limits iii. yellow - input invalid / unavailable iv. beige - static (borders, legends. .etc)

SUPPLEMENT 1-

._ ~ . .

2. P & ids
1. red - (pump /fon/ breaker) operating, (valve / damper) open.

ii. green - (pump / fan / breaker) not operating, (valve / damper) closed, iii. white - input valid iv. yellov - input invalid / unavailable ,

v. beige - static (piping, tanks, etc)

B. Size / Shape Coding

1. Size - No more than three different sizes of controls should be used for discrimination of absolute size.
2. Shape - Control shapes should be visually and tactually identifiable.
3. Consistency - Whenever practical; controls used for the same function on different items of equipment should be the same shape and size. When not practical, another coding method may be used to supplement the size / shape code.
4. Specific control switch size / shape codes - Size / shape coding of control switches should conform to the following standards:
a. J-handle controls - as a general rule, J-handle control switches should be used for all pump, fan, breaker, and emergency systems actuation controls and all other similar i applications.
b. T-handle controls - T-handle control suitenes should be used for selector functions.
c. Star-handle controls - Star-handle control switches should

- "be used for aII synchroscope switche?.

d. Thumb rocary contrcis - Thumb-rotary control switches should be used for valve and damper controls and all other similar applications.

In cases where application of the conventional size / shape code is precluded due to engineering constraints, unconventional applications should be supplemented by some other type of coding-

-(e.g. symbol coding).

O i

G-5 sUPPLDENT .1

C. Location codina - Controls should be located so as to be easily related to functions and functional groupings.

I 1. Consistency - Controls with similar functions should be in the same location from panel to panel or within panels.

2. Repeated functions - The layout of identical control or display sets should be consistent at all locations.
3. Mirror imanina - Layouts of repeated functions should not be mirror imaged.
4. Specific Location Codes l

l

a. Control switch layout - Control switches for process systems should be laid out with the suction side of the system at the bottom of the control board and the discharge side of the system at the top of the control board as depicted in Figure 1.
b. Vertical indicator layout - As a general rule, control board process indications should be laid out as depected in Figure 2.

D. Symbol Codina

1. Meanina - abstract symbols should be used only if they havs a commonly accepted meaning for all intended users.
2. Distinguishability - Symbols should be unique and distinguishable -

from one another.

3. Standard - A commonly accepted standard configuration should be i

used.

4. Specific swal:1 codes,
s. Valve control operation - Thumb-rocary con:rols used for valve /dssper control are generally either 2 position maintained or 3-position spring-returned to center. These two types of switches are easily differentiated from one another by the "at rest" orientation of the-respective

[ handles of each. The "at rest" orientation of the 2 position maintained control switch handle is either at 10 o' clock or at 2 o' clock. The "at rest" orientation of the 3-position spring-returned to center control switch handle is at 12 o' clock. Any deviations from these two types of control switch operations should have each discrete position coded using the following code (See illustration in Figure 3):

74> - Spring return from counterclockwise position 46 - Spring return from clockwise position

@ - maintained position -

- Throttling control.

G-6 SUPPLEMENT 1

_ . . _ . _ _ . _ ... ._ _ _ _ _ . . ~ _ _ _ _ _ _ _ _ _ - . . -_ _ _ _ .

l l

I i

l l

i i

b. J-handle valve controls - Whenever it is necessary to use a J-handle control switch for valve control, a valve symbol

(>4) should be engraved on the control switch handle to differentiate J-handle valve controls from the conventional l J-handle pump / fan / breaker controls.

i d

G I

i e

s 9

0 e

t G-7 SUPPLEMENT 1 l

I f

i Recirculation C Valve Dischatge

[ Valve U Pump

)

U

, Suction Valve ,

I FIGURE 1 Typical Bottom-to-Top Control Switch Layout .

Depicting Flow Path of Process G-g SUPPLEMENT 1

l t

I I Temperature Level Flow Pressure k

. FICLTI 2 Typical V*rtical' Indicatcr Layuut SUPPLEMENT 1 G-9

l l

1 J

F 3 AUTO -

@ +- 1 CLOSE OPEN f

FIGURE 3

- _ Typical. configuration of

'7 Valve Control Operation Symbol Cooling n' .<

r
  • k.

G-10; 7' .SUFPLEMENT-1

  • ,? '<

-s iI . e } '

3

_a_r

. , a ,

ADPENDIX H NOISE, LIGHTING AND ENVIRONMENTAL SURVEYS METHODOLOGY l

H-1 SUPPLEMENT 1

l l

j 4

, NOISE, LIGHTING AND ENV RONMENTAL SURVEYS 1.0 NOISE' 1.1 Objective - The objective of this survey was to measure the ambient noise

~

levels _in the control room from varicus operator positions and assess its impact on the operators ability co verbally communicate and/or discriminate audible signals. ' ,

1.2 Instrumentation - The performance of this study required the use of an appropriate scund Invel meter, selected to conform to the requirements established. -

J 1.3 Methodology - The performance of this evaluation required the consideration of not just normal control toom noise but any factors that could add to the'overall noise level. Included in this were the occasional noises of '

very short duration that caused high peak levels.  !

A. Noise Conditions - The noise survey started with a basal noise level; that is, the ambient noise without alarms, typers, or communications equipment contributing. Once this measurement had been taken, a measurement was taken with each potential source of added noise active. Once all potehtial noise sources had been-measured, a measurement was taken.with all these sources active simultaneously.

The following are potential noise. sources: ;

i

1. Audible alarms
2. Typers and printers
3. Communications ..quipment (ringing celephonai, pas, radios) 4.' Emergency or atypical environmental control systems (air conditioning, exhaust fans).

~

5.~ Loud conversation 2 6 .- Adjacent control room alarms

7. Open doors leading out of the control room.

E' ' Survey' Conduct - Noisa' measurements were taken at each operator position that requires verbal communication and/or auditory discrimination of a signal.- This includad.the Reactor Operator's

console, the Senior Reactor Operator's desk, a' point near the center of each panel /boardi~and 'any pcsition at back panels requiring

~ communications (e.g. EVAC). Three measurements were taken at each position, one with the microphone directed towards the major noise 1 source, one.with th's mihrophone directed towards the panel surface and

[ on%with thi microphone _ directed toward.s the farthest operator's l position that would, require communications. Nessurements were taken in decibels (dBA).J Any instances bf extreme peak values ,were noted j and the source located. '

~

1.4 Data Evaluation;- The,collectsd data was compared to the' appropriate guidelines contaitied in NUREGe0700. Values that excee'ded ths' established limits were documented on Human Engineering Discrepancy' Sunnary Sheets

~

contained in' Appendix B.

~

l' s +

, H-2:

_ . _ _ _ _ ._ _. _ _ _ - _ . _ _ , , ._ ~ . _ _ . _ _.

2.0 LIGHTING 2.1 Objectives - The objective of this survey was threefold. First, to measure the ambient illumination in the control room and assess its impact on the operator's ability to read and interpret displays, controls, labeling, and printed matter such as drawings and procedures. Second to measure the luminance of displays and calculate the luminance ratio values to determine the adequacy of display lighting. Third, to measure and calculatethe reflectance of surfaces to determine the level of reflected light in the control room.

2.2 Instrumentation - The ambient illumination was measured using a photometer and an illuminance probe. Ihe luminance measurements were taken with a photometer and a luminance probe. Reflectance was measured using a photometer in conjunction with illumination and luminance probes. All instruments conformed to the established requirements.

2.3 Methodology - The ambient illumination was performed under normal and emergency lighting. The luminance and reflectance surveys were performed under normal lighting.

A. Ambient Illumination - Measurements were taken at all operator positions. These included:

1. Reactor operator's ccnscle
2. Senior reactor operator's work desk
3. Each control panel, including back panel areas
4. Each point where reading of printed material might be required At each operator position a light meter was held at eye height and pointed first at the panel / desk; a second reading was taken with the meter pointed at the ceiling. If reading of printed material was required, it was in place when the measurement was taken.

j B. Luminance - Measurements were taken for the display types listed l below: .

1. Indicator lights 2 .' CRT (video) characters
3. LED light emitting diode characters .
4. Labels
5. Status / Monitor lights
6. Annunciator alarms The luminance probe was focused on the reflected or emitted light source and a reading was taken. The probe was then focused on the surface adjacent to the display and another reading was taken.

Measurements were taken from a wide selection of displays on the boards to provide an adequate sampling of the brightness of displays and ensure uniformity of illumination. All measurements were recorded on data sheets.

H-3

__ . . _ SUPPLEMENT 1

k C. Reflectance - Measurements were taken for the surfaces listed below:

1. Ceiling
2. Upper wall i
3. Floor
4. Operator's consola
5. Senior Reactor operator's work desk
6. Control panel surface
7. Visual displays Two measurements were taken for reflectance. First, surface luminance was measured as outlined in paragraph B. Second, surface illumination was measured as outlined in paragraph A. All measurements were recorded on data sheets.

2.4 Data Evaluation - The collected data wa's compared to the appropriate guidelines of NUREG-0700. The data from the luminance survey was, substituted in the following formula to calculate luminance ratio (LR).

LR = Lg/L2 where Lg = Bright area and L = Dark area 2

The data from the reflectance survey was substit stad into the following l formula to calculate rLflectance values (R):

i R = (L/I) x 100% where L = Luminance and I = Illumination.

The values udre compared to the appropriate guidelines in NUREG-0700. Any dsviations from the guidelines were reported on Human Engineering Discrepancy Summary Sheets contained in Appendix B.

l l

l l

i l I

l t

I l

i 1 .

l H-4 1

-~ _,-, SUPPLEMENT 1,_ ,_-, a

l 1

l 3.0 ENVIRONMENTAL 3.1 Objective - The objective of this survey was twofold. First, to measure the temperature and humidity in the control room. Second, to measure the temperature differential at floor level and at head level.

3.2 Instrumentation - The temperature and relative humidity were measured and recorded by two-pen temperature and humidity recorders.

3.3 Methodology - The temperature and relative humidity were recorded for a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> period at two locations in the control room. One recorder was placed at an elevation of approximately six feet. The second reccrder was at floor level.

3.4 Data Evaluation - The collected data was compared to the appropriate guidelines contained in NUREG-0700. Any deviations from the guidelines were reported on Human Engineering Discrepancy Summary Sheets contained in Appendix B.

W H-5

- SUPPLEMENT 1

TABLE 1 NOISE DATA ._ .

l PLANT: 'N .

DATE: ME-l m.

l t TEST CONDUCTED BY:

souw3 Lavat UTTER mooEL:

micRoewows moogL: CAtteRATm Daft: .

SERIAL NUMSER: SERIAL NUmstR:

OPERATOR POSmON dB(A)' agMARKs NOISE CONDmOw/SOURCL' DIRECTION OF MEASUREMENT e

e l

H-6 SUPPLEMENT 1

TABLE 2

. J.IGHUNG DATA DATE:

TIME:

PLANT:

TEST CONOUCTED SY:

PM37CMETER MODEL: CAllBRAT!ON DATE:

SETJAL NUMBER: .

UGHTING CONDITIONS EMERGENCY #EMARES OPERATORIMEASUREMENT POSITION NORMAL O

e e

e e

O 4

e 9

O O

9 e

SUPPLEMENT 1 .

9

,.- ,.ns,. am,, _ , - , , , ..,,--,-.--_,,,,m

.. . _ . . . . . . . . . . . . - . . . - . . . . . . ~ . - - - -

HUMIDITY / TEMPERATURE RECORD l

Plent Date: Time:

Measursments made by: Sheet of Equipment / Instrument used:

Sarici *: Calibration date:

Tite Height Temperature Humidity Remarks Floor 6 ft.

Floor ,

6 ft.

Floor 6 ft.

l Floor 6 ft.

Floor 6 ft.

Floor 6 ft.

Floor 6 ft.

H SUPPLEMENT 1

l l

I f

APPENDIX I: RESPONSE TO IN-PRCGRESS AUDIT OF COMANCHE PEAK STEAM ELECTRIC STATION CONTROL ROOM DESIGN REVIEW 6

SUPPLEMENT 1 7,

I RESPONSE TO IN-PROGRESS AUDIT OF COMANCHE PEAK STEAh ELECTRIC STATION CONTROL ROOM DESIGN REVIEW 1.0 DISCUSSION On Apr11,4 through April 8,1983, the Human Factors Engineering Branch conducted an on-site review of the CPSES detailed CRDR. Thi s review was documented in a July 8,1983, letter from B. J. Youngblood, Chief, Licensing Branch No.1, Division of Licensing to Mr. R. J. Gary, Executive Vice President and General Manager, Texas Utilities Generating Company and entitled, "Results of In-Progress Audit of Comanche Peak Steam Electric Station Control Room Design Review". This Appendix to supplement I responds to the conditions noted in that, report which must be satisifed pr.ior to licensing and to the concerns l relating to the detailed CRDR.

l 2.0 CONDITIONS WHICH MUST BE SATISFIED PRIOR TO LICENSING The audit report noted four conditions that must be satisfied prior to licensing CPSES Unit 1. The response to these four items is noted below:

1. Implementation of the identified HEDs continues. The identified corrective action for all HEDs will be completed prior to fuel load.
2. Revised HEDs are included in this supplement (supplement 1) for all HEDs specified in Appendix B of the audit report as requiring clarification.

l

3. HEDs are provided in this supplement (supplement 1) for the Human Engineering Discrepancies identified in Appendix C to the audit report (see HEDs 335 through 345). The HEDs describe the' corrective actions and all corrective actions will be completed prior to fuel load.

I-2 SUPPLEMENT 1

f

4. Final noise, lighting and environmental surveys have been completed. All HED's identified as a result of these surveys are addressed in this supplement. The guidance for the noise and lighting surveys are included in Appendix H to this supplement.

l CPSES has also agreed to perform noise, lighting and environmental surveys at the Hot Shutdown Panel.

3.0 CONCERNS RELATING TO THE DETAILED CRDR The audit report noted two concerns that related to the detailed CRDR. The first concern, pertaining a program plan, is addressed in Section 1.5.1 of this supplement. The second concern, which relates to a system function and task analysis, is addressed in Section 1.5.,2 of this supplement.

t j I-3 SUPPLEMENT 1

- - . , _ _ - .