APPENDIX Docket No: 050-325 Unit: Brunswick No. 1 Date: May 1982 Completed by: Frances Harrison OPERATIONS

SUMMARY

BRUNSWICK UNIT NO. 1 Brunswick Unit No. 1 operated at 96.6 percent availability factor for the month of May with a 53.1 percent capacity factor. There was one off-line outage this month. The unit operated at reduced power because of fuel conservation. It is detailed in Appendix D, the unit shutdowns and power reduction log.

There are 476 BWR and 160 PWR spent fuel bundles in the Brunswick No. 1 fuel pool.

BPO6150238 820604 PDR ADOCK 05000324 R PDR

O o o .

1 DOCKET NO. 050-017s UNIT SifUTDOWNS AND POWER REDUC 110NS ,

UNIT N AME Brunwick I DATE May 1982 REPORT MONTil May 1982 COMPLETED BY Frnnces Hnrrison TELEPHONE (919) 457-9521 e.

- E E

, .5 g 3j $Y5 Licensee ,Eg $wt Cause & Corrective No. Date g 3g ji5 Event gi g3 Action to H jE 5 Ji dj =

e.

' Report # mV oo O Prevent Recurrence g

o e

82-057 820505 F 25.7 A 3 N/A XX CKTBRK Low condenser vacuum switch D failed.

Replaced low condenser vacuum switch

  1. 56D with a new switch, f

j  !

i i I a

1 I

I 2 3 4  :'

F: Forced Reason: Method: Exhibit G-Instructions S: Scheduled A Equipment Failure (Explain) 1-Manual for Preparation of Data B-Mab.:enance of Test 2-Manual Scram. Entry Sheets for Licensec

! C. Refueling 3 Automatic Scram. Event Report (LER) File (NUREG.

D Regulatory Restriction 0161) -

E Operator Training & Ucense Examination 4-Continuations 1 F-Administrative 5-Load Reductions 5 G-Operational Error (Explain) 6-Other Exhibit I Same Souree -i

('s/77) Il-Other (Explain)

) '

DOCKET NO. 050-0325 UNITSilUTDOWNS AND POWER REDUCTIONS .

UNIT NAME Brunswick I ,

DATE Mnv 1987 ,

May 1982 COMPLETED BY Frances Harrison REPORT MONTil i TELEPHONE (919) 457- M i

--o .5 E 3g .$ Licensee 5%  !" Cause & Corrective No. D.ste g 3g ,3 g 5 Event u? 8.% Action to N0

  • $5 v$b l E .5 e di F Report # Prevent Recurrence C

{

82-058 820501 5 0 F 4 N/A RC Fuel XX Fuel Conservation Maintain present power level to extend core life.

i l

I 4

i l I 2 3 4

, F: Forced Reason: Method: Exhibit G-Instructions i i

S: Scheduled A. Equipment Failure (Explain) 1-Manual for Preparation of Data

, B-Maintenance of Test 2-Manual Scram. Entry Sheets for Licensee C Refueling 3 Automatic Scram. Event Repor:(LER) File (NUREG-D Regulatory Restriction 0161)

E-Operator Training & License Examination 4-Continuat.ons 4 F-Adninist rative 5-Load Reductions 5 G-Operational Error (Explain) 6-Other Exhibit I Same Source (9/77) li-Other (Explain)

I i

M

APPENDIX B

' AVERAGE DAILY ~ POWER LEVEL:

-1 DOCKET _NO.<050-0325-UNIT BRUNSWICK ONIT,1

-DATE 06/01/82.

COMPLETED'BY FRANCES HARRISON r

TELEPHONE 919-457-9521

['<- MAY 82 '

I D Y' AVG. DAILY-POWER LEVEL' DAY AVG. DAILY POWER LEVEL l (MWE-NET) (MWE-NET) 2

! 1 446. -17 438. '

4

! 2 440. 18 439.

i

! 3 434' . .

19 438.

4' 434. 20 ~433.

5 126. -- 21 431.

6 206. 22 430.-

7 418. 23 434.

S 433. 24 -

422.

)  ;

! 9 439. .25 426. ~j i

10~ 440. 26 429. i

11 439. 27 425.

12 438. 28 424.

i 13 438. 29 425.

i, 14 436. 30 424 .

15 436. 31 544

! i 1

16 440. ,

i I

n 1.16 - e  ;

t i

, ~ . .- - -. - .. - - - . .-. . - - . _ -. - _ . . ..

i 1 F-

)

OPERATING DATA REPORT I

I DOCKET NO. 650-0325 '

I

! DATE 06/01/82 COMPLETEDBYFRANCESHARRISONl l TELEPHONE 919-457-9521 j j OPERATING STATUS

1. UNIT NAME: BRUNSWICK UNIT 1 I NOTES I
2. REPORTING PERIOD: MAY 82 I I '

i

5. LICENSED THERMAL POWER (MWT): 4436 I I f
4. NAMEPLATE RATING (GROSS MWE): 867.0 I I '

i 5. DESIGN ELECTRICAL RATING (NET MWE): 821.0 I I l 6. HAX DEPENDADLE CAPACITY (GROSS MWE): 815.0 I I

, 7. MAX DEPENDABLE CAPACITY (NET MWE): 790.0 -------------------------------

! 8. IF CHANGE 5 OCCUR IN CAPACITY RATINGS (ITEMS 3 THRU 7) SINCE LAST REPORT, i GIVE REASONS:

i

! 9. POWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE): NONE

10. REASON 5 FOR RESTRICTION IF ANY:

l L

3

>HIS YR TO CUMUL MONTH DATE ATIVE

11. HOUR 5 IN REPORTING PERIOD 744.0 3623.0 45624.0
12. NUMBER OF HOURS REACTOR WAS CRITICAL 724.6 3384.2 31649.5

! 13. REACTOR RESERVE SHUTDOWN HOURS 0.0 0.0 1647.1 i 14 HOURS GENERATOR ON LINE 718.4 3320.9 29860.5

15. UNIT RE9ERVE SHUTDOWN HOURS 0.0 0.0 0.0
16. GROS $ THERMAL ENERGY GENERATED (MWH) 1035129.9 5955418.0 60373222.6 ,
17. GRO55 ELECTRICAL ENERGY GENERATED (MWH) 324659.0 1921672.0 19922880.0
18. NET ELECTRICIAL ENERGY GENERATED (MWH) 312131.0 1854689.0 19158180.0
19. UNIT SERVICE FACTOR 96.6 91.7 65.4
20. UNIT AVAILABILITY FACTOR 96.o 91.7 65.4
21. Utili CAPACITY FACTOR (USING MDC NET) 53.1 64.8 53.2 i 22. UNIT CAFACITi 4CTOR (USING DER NET) 51.1 62.4 51.1

! 23. UNIT FORLED 00~ AGE HATE 3.4 4.4 20.3

24. SHUTDOWNS 50HEDULED OVER NEXT a NONTHS (TYPE, DATER AND DURATION OF EACH):

Refueling 820917 22 weeks

25. IF 5H01 DOWPJ AT END OF REPCRT PERIOD, ESTIMATED DATE OF START UP: 0/ w 0
26. UNITE IN TEST STATUS (FRIOR TO COMMERICIAL OPERATION): FORCAST ACHEIVED INITJAL ERITICALITY -------- --------

l INITIAL ELECTRIC!Ti -------- --------

COMMERICIAL OPERATION -------- --------

1.16 - 9 l

_ n-~w-m m wwww-ww ,www -

1. .

APPENDIX B AVERAGE. DAILY POWER LEVEL DOCKET NO. 05si-0324

, UNIT BRUNSWICK UNIT:2' l DATE 06/01/82 . .

! COMPLETED'BY FRANCES HARRISON TELEPHONE 919-457-9525 MAY 82 i

l DAY AVG. DAILY POWER LEVEL DAY . AVG. DAILY POWER LEVEL (MWE-NET) (MWE-NET) 1- -10. 17 -5.

2 -10. 18 -6,

3. -10. 19 -6.

t

! 4 -10. 20 -6, 5 -11. 21- -6.

6 -10. 22 -7.

7 -10. 23 -6.

8 -10. 24 -6.

9 -10. 25 -6.

! 10 -10. 26 -6.

11 -8. 27 -7.

12 -5. 28 -7.

13 -5. 29 -6.

14 -5. 30 -7.

15 -5. -31 -6.

16 -6.

1.16 - 8

~

-OPERATING DATA REPORT DOCKET-NO.-050-0324 DATE 06/01/82 COMPLETED BYLFRANCES HARRISON TELEFHONE 919-457-9521

' OPERATING STATUS

1. UNIT.NAME: BRUNSWICK UNIT 2 I NOTES I 2.-REPORTING PERIOD: MAY 82 I I
3. LICENSED THERMAL POWER (MWT): 2436' I I
4. NAMEPLATE RATING (GROSS MWE).:~867.0 I I
5. DESIGN' ELECTRICAL RATING ~(NET MWE): 821.0 I I
6. MAX DEPENDABLE CAPACITY-(GROSS MWE): 815.0 I- .I
7. MAX DEPENDABLE CAPACITY (NET ~MWE): 790.0 -------------------------------
8. IF CHANGES OCCUR IN CAPACITY RATINGS: (ITEMS 3 THRU 7)'SINCE LAST REPORT,.

CIVE REASONS:

l

9. POWER LEVEL TO WHICH RESTRICTED IF ANY '(NET MWE): NONE
10. REASONS FOR RESTRICTION IF ANY:

THIS YR TO CUMUL MONTH .DATE ATIVE l

l 11. HOURS IN REPORTING PERIOD _

744.0 3623.0 ~57648.0

12. NUMBER OF HOURS REACTOR WAS CRITICAL 0.0 2465.2 37632.1
13. REACTOR RESERVE SHUTDOWN-HOURS. 0.0 0.0 0.0 l 14. HOURS GENERATOR ON LINE 0.0 2384.6 '35153.9
15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0 0.0
16. GROSS THERMAL ENERGY GENERATED (MWH) 0.0 4467965.8 64465503.4-

, 17. GROSS ELECTRICAL ENERGY GENERATED (MWH) - 0. 0 1415289.0 21409226.0

! 18. NET ELECTRICIAL ENERGY GENERATED (MWH) -5454.0 1356517.0 20545930.6 19.-UNIT SERVICE FACTOR 0.0 65.8 '61.0 l 20. UNIT AVAILABILITY FACTOR 0.0 65.8 61.0' l 21. UNIT CAPACITY FACTOR (USING MDC NET) -0.9 47.4 45.1

22. UNIT CAPACITY FACTOR (USING DER NET) -0.9 45.6 43.4
23. UNIT FORCED OUTAGE RATE 0.0 17.1 17.1 l
24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPEr DATE, AND DURATION OF.EACH):

l l

25. IF SHUTDOWN AT END OF REPORT PERIOD ESTIMATED DATE OF START UP: 7/18/82'
26. UNITS IN TEST STATUS (PRIOR TO COMMERICIAL OPERATION): FORCAST ACHEIVED i INITIAL CRITICALITY -------- --------

l INITIAL ELECTRICITY -------- --------

COMMERICIAL OPFR4 TION -------- --------

l 1.16 - 9 l

i l

APPENDIX Docket No: 050-324 Unit: Brunswick No. 2 Date: May 1982 Completed By: Frances Harrison OPERATIONS

SUMMARY

BRUNSWICK UNIT NO. 2 Unit No. 2 was shut down the entire month of May for a refueling outage.

Estimated startup date July 18, 1982.

There are 914* BWR and 144 PWR spent fuel bundles in the Brunswick Unit No. 2 fuel pool.

  • There are 90 new reload bundles in the pool plus a 560 bundio fuel core discharge. One hundred sixty discharge bundles will remain in the pool af ter core reload.

, , . _ , . _ . ,