Monthly Operating Repts for June 1983.W/830706 Ltr
ML20024C748
Person / Time
Site: Brunswick  Duke Energy icon.png
Issue date: 07/06/1983
From: Dietz C, Harrison F
CAROLINA POWER & LIGHT CO.
To: Deyoung R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
References
BSEP-83-2191, NUDOCS 8307130212
Download: ML20024C748 (12)


Text

.p APPENDIX D AVERAGE DAILY POWER LEVEL DOCKET NO. 050-032b LINIT BRUNSWICK UNIT 1 DATE 07/06/83 COMPLETED BY FRANCES HARRISON TELEPHONE (919)457-9521 JUNE 1983 DAY AVG. DAILY POWER LEVEL DAY AVG. DAILY POWER LEVEL (HWE-NET) (MWE-NET) 1 -4 17 -6 2 -4 18 -6 3 -5 19 -6 4 -5 20 -7 5 -5 21 -0 6 ~5 22 -- 7 7 -5 23 -7 8 -5 24 -9 9 -6 25 -10 10 -6 26 -12 11 ~5 27 -12 12 -6 28 -12 13 -6 29 -12 14 -6 30 -10 15 -7 16 -6 1.16 - O sot 8307130212$ 4 PDR ADOCK 0 PDR R

. ~ =- =

OPERATING DATA REPORT DOCKET NO. 050-0325 DATE 07/06/83 COMPLETED BY FRANCES HARRISON TELEPHONE (919)457-9521 OPERATING STATUS

1. UNIT NAME: BRUNSWICK UNIT 1 i NOTES I
2. REPORTING PERIOD: JUNE 83 . I I 2
3. LICENSED THERMAL POWER (MWT): 2436 I i
4. NAMEPLATE RATING-(GROSS MWE): 867.0 l I
5. DESIGN ELECTRICAL RATING (NET MWE): 821.0 I i

'6. MAX DEPENDABLE CAPACITY (GROSS MWE): 815.0 l I

7. MAX DEPENDABLE CAPACITY (NET MWE): 790.0 -------------------------------

- 8. IF' CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THRU 7) SINCE LAST REPORT, GIVE REASONS:

9. POWER' LEVEL TO WHICH RESTRICTED IF ANY (NET MWE):
10. REASONS FOR RESTRICTION IF ANY:

i THIS YR TO CUMUL HONTH DATE ATIVE 11.' HOURS IN REPORTING PERIOD 720.00 4343.00 55104.00

12, NUMBER OF HOURS REACTOR CRITICAL .00 .00 33888.47
13. REACTOR RESERVE SHUTDOWN HRS .00 .00 1647.10
14. HOURS GENERATOR ON LINE .00 .00 31970.03
15. UNIT RESERVE SHUTDOWN HOURS .00 .00 .00
16. GROSS THERMAL ENERGY GEN. (MWH) .00 .00 63896018.86 4
17. GROSS ELEC. ENERGY GEN. (MWH) .00 00 21062188.00

. 18, NET ElEC. ENERGY GENERATED (MWH) -4966.00 -22749.00 20202370.00

19. UNIT SERVICE FACTOR .00 .00 58.02
20. UNIT AVAILABILITY FACTOR .00. .00 50.02
21. UNIT CAP. FACTOR (USING HDC NET) .87 -.66 46.41
22. UNIT CAP. FACTOR (USING DER NET) .84 .64 44.66

- 23. UNIT FORCED OUTAGE RATE .00 .00 24.03

24. SHUTDOWNS SCHED. OVER NEXT 6 MONTHS'(TYPE, DATE, AND DURATION OF EACH):
25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF START UP: 07/22/83
26. UNITS IN TEST STATUS (PRIOR TO. COMMERCIAL OPERATION): FORCAST ACHEIVED INITIAL CRITICALITY -------- --~~~---

INITIAL ELECTRICITY -------- --------

COMMERCIAL CPERATION -------- --------

1.16 - 9'

r . . .

p

  • n .
n

,/ DOCKET NO. 050-19s UNIT S!!UTDOWNS AND POWER REDUCTIONS UNIT NAME arunswiek No. 1 j

DATE July 1983

. / Timo 14R1 COMPLETED BY Frances Harrison REPORT MONTH TELEPilONE (919)457-9521

-, i'E 'b .5 i Licensee E

% $, Cause & Corrective No. Date [:; 3g g ,g y 5 Event  :: ? 893 Action to H

$5 5 31 5 , Report # N0 50 Prevent Recurrence .

c  : o ,

D o~ -

e 83116 821211 S 720 C 4 NA RC FUELXX Refueling / Maintenance Outage t

9

' ~

i 1 2 3 8 4 -

F: Forced Reason: . Method: Exhibit G - Instructions S: Scheduled A liguipment Failure (Explain) . I Manual for Preparation of Daia B. Maintenance or Test 2 Manual Scram. Entry Sheets for Licensee C. Refueling 3 Automatic Scram. Event Report (LER) File (NUREG-D Regulatory Restriction 4 Continuations 0161)

E-Operator Training & License Examination 5-3oad Reductions '

F Administrative 3 6-Other G. Operational Error (Explain) . - Exhibit I Same Source

  • e)/77) li Other(Explain) -

APPENDIX {

DOCKET NO.: 050-325 UNIT: Brunswick No. 1 DATE: July 1983

-COMPLETED BY: Frances Harrison OPERATIONS

SUMMARY

BRUNSWICK UNIT NO. 1 Brunswick Unit No. I was shutdown the entire month of June for a refueling /

maintenance outage.

There are 656 BWR and 160 PWR spent fuel bundles in the Brunswick No. 1

. fuel pool.

1 J

f t

1 I"

.?

I i

1 1'

I l

l-o i,

3 APPENDIX B AVERAGE DAILY POWER LEVEL DOCKET NO. 050-0324 UNIT BRUNSWICK UNIT 2 DATE 07/05/83 COMPLETED BY FRANCES HARRISON TELEPHONE (919)457-9521

-JUNE 1983 DAY - AVG. DAILY POWER LEVEL DAY AVG. DAILY POWER LEVEL

'(MWE-NET) (MWE-NET) 1- -774 17 704 2 595 18 700 3 -15 19 750 4 -17 20 410 5 277 21 -13 6 193 22 -12 7 370 23 ^-11 8 464 24 -11 9 713 25 -14 10 736 26 243 1 1 -= 650 27 610 12 366 28 649 13 642 29 640 14- 724 30 482

15 ~725 16 726 1

.1.16 - 8

.i .i is

. s OPERATING DATA REPORT DOCKET NO. 050-0324 DATE 07/06/83 COMPLETED BY FRANCES HARRISON TELEPHONE (919)457-9521 OPERATING STATUS

1. UNIT NAME: BRUNSWICh UNIT 2 i NOTES I
2. REPORTING PERIOD: JUNE 83 i I
3. LICENSED THERMAL POWER (NWT): 2436 I I
4. NAMEPLATE RATIt4G (GROSS MWE): 867.0 l I
5. DESIGN ELECTRICAL RATING (NET MWE): 821.0 l I
6. MAX DEPENDABLE CAPACITY (GROSS MWE): 815.0 I i
7. MAX DEPENDABLE CAPACITY (NET MWE): 790.0 -------------------------------
8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THRU 7) SINCE LAST REPORT, GIVE REASONS:
9. POWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE):
10. REASONS FOR RESTRICTION IF ANY:

THIS YR TO CUMUL MONTH DATE ATIVE

11. HOURS IN REPORTING PERIOD 720.00 4343.00 67128.00
12. NUMBER OF HOURS REACTOR CRITICAL 568.41 3189.81 41965.93
13. REACTOR RESERVE SHUTDOWN HRS .00 .00 .00
14. HOURS GENERATOR ON LINE 531.02 3015.26 39166.00
15. UNIT RESERVE SHUTDOWN HOURS .00 .00 00
16. GROSS THERMAL ENERGY GEN. (MWH) 1000552.90 6345039.47 72642022.83
17. GROSS ELEC. ENERGY GEN. (MWH) 327173.00 2127839.00 24144531.00
18. NET ELEC. ENERGY GENERATED (MWH) 313526.00 2048847.00 23140773.00
19. UNIT SERVICE FACTOR 73.75 69.43 58.35
20. UNIT AVAILABILITY FACTOR 73.75 69.43 58.35
21. UNIT CAP. FACTOR (USING MDC NET) 55.12 59.72 43.64
22. UNIT CAP. FACTOR (USING DER NET) 53.04 57.46 41.99
23. UNIT FORCED OUTAGE RATE 26.25 8.44 16.22
24. SHUTDOWNS SCHED. OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH):

Maintenance / Condenser 9-3-83 22 Weeks

25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF START UP:
26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION): FORCAST ACHEIVED INITIAL CRITICALITY -------- --------

INITIAL ELECTRICITY -------- --------

COMMERCIAL OPERATION -------- --------

1.16 - 9 m,

4

o .

DOCKET NO. 050-325 UNIT SHUTDOWNS AND POWER REDUCTIONS UNIT NAME Brunswicic No. 2

  • DATE July 1983
  • COMPLETED BY Frances llarrison REPORT MONTil June 1983 TELEPHONE (919)457-9521 w.

,. .! E 3 Y Licensee E r, o Cause & Corrective No. Date g 5g s 2s5 Event gy go3 Action to H

$E 5 3 e dj =8 Repor # mO o v

Prevent Recurrence i ,

6 - 83-050 830602 F 54.1 A 3 NA HA GENERA Rx scram-power load unbalance was tested light didn't go out and turbine tripped on load reject.

I I 2 3 4 F: Forced Reason: Method: Exhibit G Instructions S: Scheduled A. Equipment Failure (Explain) 1-Manual for Preparation of Data .

B-Maintenance of Test 2 Manual Scram. Entry Sheets for Licensee C Refueling 3 Automatic Scram. Event Report (LER) File (NUREG.

D Regulatory Restriction

  • 0161)

E-Operator Training & Ucensc Examination 4-Continuations - .

F-Administrative 5-Load Reductions- ,5 G-Operational Error (Explain) (,-Other Exhibit I Same Source (9/77) ll-Other (Explain) ,

._____ _ _ - -- . _ _ _ _ - _ _ . _ 9 - - _ _ _ _ - _ _ . _ _ _ - _ . _ _ _ -

DOCKET NO.

050-325 UNIT SilUTDOWNS AND POWER REDUCTIONS UNIT NAME Brimnwick No. 2

. DATE T"1" 14M .

COMPLETED BY Frances Harrison REPORT MONTH . Time 1983 TELEPHONE (919)457-9521 w.

- E E

, .$ ? 3 yY5 Licensee ,E g Cause & Corrective No. Date g 5g s jg5 Event g' {p*u., Action to H $ 9, 5 j;gg Report # mO g Prevent Recurrence i O .83-052 830606 F .00 A 5 NA Cll PUMPXX Reduced power "A" rx feedpump escillating. ,

I i

s .

a .

'4 5 .

4 i

i, b

i . .e e ',

4

\

1 i

i

. I 2 3 4 F: Forced Reason: Method: Exhibit G-Instructions S: Scheduled .

A-Equipment Failure (Explain) 1-Manual for Preparation of Data .

1 B-Maintenance of Test 2-Manual Scram. Entry Sheets for Licensee C-Refueling 3-Automatic Scram. Event Report (LER) File (NUREG-

D-Regulatory Restriction 0161)

E-Operator Training & Licensc Examination l-Continuations i - .

F. Administrative 5-Load Reductlons - 5 i G-Operational Error (Explain) 6-Other Exhibit I- Same Source

  • l (9/77) li Other (Explain) ,

1 9 _ _ _ _ _ _ _ _ _ _

UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 050-325 UNIT NAME Brimwick No. 2 DATE July 1983

  • COMPLETED BY Frances Harrison REPORT MONTil June 1983 TELEPHONE (919)457-9521 ,

c C ra Y en 3 li'*"5CC 5t Cause & Corrective E3 No. Date E. $_$

B-0

?je E Event Report #

g,'7 mo

$"g.

gu gc,;g, ,,

O *$ 5ml g Prevent Recurrence 6 .83-055 830611 F .00 A 5 NA HC HTEXCH Reduced power for waterbox work.

o I 2 3 4 F: Forced Reason: Method: Exhibit G Instructions S: Scheduled A-Equipment Failure (Explain) 1-Manual for Preparation of Data .

B Maintenance of Test 2-Manual Scram. Entry Sheets for Licensee C-Refueling 3-Automatic Scram. Event Report (LER) File (NUREG-D-Regulatoiy Restriction 0161)

E-Operator Training & Ucensc Examination 4-Continuations - ,

l F Administrative 5-Load Reductions - ,5 G-Operational Error (Explain) 6-Other Exhibit t - Same Source (9/77) Il-Other (Explain)

  • n

1 UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 050-325 UNIT NAME Brunswick No. 2 i

DATE July 1983 '

COMPLETED BY Frances Harrison REPORTMONTil June 1983 TELEPHONE (919)457-9521 w.

C P$ 50 Li' "$# C""5' E C"""'IV' No. Date E.

k- o

=  ? $ oc

.c 3 U

Event sk-51 "o Action to {

$13 5 jisy Report # Nd U Prevent Recurrence d .

4 e

83-062 830620 F 134.6 A 3 NA ZZ ZZZZZZ Rx scram on hi water level. (Drywell dooler cleaning and EllC oil leak repaired while unit is down) t

.[

I i ,

d i 1 2 3 4 F: Forced Reason: Method: Exhibit G . Instructions S: Scheduled A-Equipment Failure (Explain) 1-Manual for Preparation of Data .

B-Maintenance of Test 2 Manual Scram. Entry Sheets for Licensee C Refueling 3 Automatic Scram. Event Report (LER) File (NUREG-D-Regulatory Restriction 0161)

E-Operator Training & License Examination 4-Continuations - .

~

F-Administrative 5-Load Reductions- ,5 l G-Operational Error (Explain). 6-Other Exhibit 1-Same Source (9/77) ,

li C:her (Explain) ,

3

- i.

., .o.-

APPENDIX DOCKET NO.: 050-324 UNIT: Brunswick No. 2 DATE: July 1983 COMPLETED BY: Frances Harrison OPERATIONS

SUMMARY

BRUNSWICK UNIT NO. 2 Brunswick Unit No. 2 operated at 73.75% availability factor for the month of June with a 55.12% capacity factor. There were two scrams and two power reductions this month. They are detailed in Appendix D, the unit shut-downs and power reduction log.

There are 424 BWR and 144 PWR spent fuel bundles in the Brunswick No. 2 fuel pool.

. . , o l

1 S/RV FAILURE / CHALLENGES REPORT UNIT 2 DATE: July 1983 TIME OF OCCURRENCE:

DETAILS OF S/RV's FAILURE: There were no challences to main nennm averem safetv/ relief valves for the scram in Mav or rho nn n e. in June 1983.

m 1

  • p

i Cp&L Carolina Power & Light Company teessmumm=amnememima Brunswick Steam Electric Plant P. O. Box 10429 Southport, NC 28461-0429 -

July 6, 1983 FILE: B09-13510C SERIAL: BSEP/83-2191 Mr. R. C. DeYoung - Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 BRUNSWlCK STEAM ELECTRIC PLANT, UNIT NOS.1 AND 2 LICENSE NOS. DPR-71 AND DPR-62 DOCKET N05. 50-325 AND 50-324 MONTHLY OPERATING REPORT

Dear Mr. DeYoung:

In accordance with Technical Specification 6.9.1.6 for the Brunswick Steam Electric Plant, Unit Nos. 1 and 2, Carolina Power & Light Company herewith submits the report of operating statistics and shutdown experience for the month of June 1983.

Very truly yours, ,

Ys}

C. R. Dietz, General Manager Brunswick Steam Electric Plant FH/ag Enclosure cc: Mr. J. P. O'Reilly Ms. J. C.' Baker Mr. S. L. Rosen Ms. Mary Hodges L

l $