ti C F011M 356 Y LICENSEE EVENT REPORT CONTROL BLOCK: I l l l l l (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION) fiTil 8IN9 I vi LICENSEE 1191CODE Si 21@l o15 f o l -l o l oLICENSE l o fNWSER olnl I n I 25o l@l 41, I, I, I, l@l$7 CAT I 58 l@

i 14 26 LICENSE TYPE JQ CON'T b "

5 uRC IL@l0l5 10 101012 l 417 @l o l 4 l 2 l 2 ! 8 l i l@ln 74 I c; REPORT 75 l ? I ?QATE l n 1780l@

7 8 60 61 DOCK ET NuYSER 6a 63 EVENT DATE EVENT DESCRIPTION AND PROB ABLE CONSEQUENCES OiO g; A plant shutdown comenced when tee binding of valve No.1870 could not be l corrected within the time period allowed in Technical Specification 3.6.A.5a. l Valve No.1870 is one of two in series non-autcmatic containment isolation valves l on the RHR test and minimum flow recirculation line. The health and safety of the l

, ,, public were unaffected. There were no similar pervious events. l 0 7 l O is l C 0 CODE SUSCO E COMPONENT CODE SUS dE SU E 8 l cl Fl@ LE_jh l B lh I VI Al L! V! Ol Plh W@ W h 12 13 18 19 20 7 8 9 10 11 SEQUENTIAL OCCURRENCE REPORT REVISION EVENT YEAR REPORT NO. CODE TYPE NO.

LER

@ ,ag/RO l813 l l-l 10 11 18 l l/l 10l3l l Ll L-J LtJ 32

_ 21 22 23 24 26 27 28 29 30 31 KN AC ON PL NT Y HOURS 22 SB 1 FOR 8. SUPPLI MANUFACTURER

@33[Zj@ 34_ lBl@

35 l36Al@ l0 l0 l0 l1 l 3/ 40

[N_j @

46 lYl@

42 lNl@ lXl9l9l9l@

43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS i O l The binding of valve No. 1870 was alleviated by lubricating the valve stem and the_I

, , l universal joints between the actuator and the valve. The valve was stroked _

j satisfactorily and returned to service. Mfr. Data: Limitorque hbdel SMB-000 l l attached to a 2" Conval Globe Valve Fig. 2-12G-316. l i a I l

I t 4 I 80 7 8 9

'OWER OTH ER STATUS IS O Y DISCOVERY DESCRIPTION ST S Surveillance Test i s @l l 0l 0lgl NA l { gl l A TlVITY CO TENT AMOUNT OF ACTIVITY LOCATION OF RELEASE 1 6 r.Eg ASEo@OP rey ASE l M l l NA l PERSONNEL EXPOS ES

, , i 0"i"'tf'i"0 [g]gi "E " O l PERSON ~E L INau'!!ES NUMBER DESCRIPTION l

i a 10 l0 P l@l NA ti 12 83 f.Mf Od D AMAuE TO FACILITY 8306170410 830522 TYPE DESCHiPTION PDR ADOCK 05000247 I 9 ggl NA g PDR l 80 7 8 9 10 DESCRl* TION 2 -

L isTf81 "^ l 111111111111180 ;

f- e 3 10 68 69 *

- r.YL/LJ2SyL.pRAfh  !

g - s John D. C'Toole p- Vice Pres, dent I

Consobdated Edison Company of New York. Inc 4 Irving Place. New York. NY 10003 Te!ephone (212) 460-2533 May 22, 1983 Re: Indian Point Unit No. 2 Docket No. 50-247 LER-83-018/03L-0 Mr. James M. Allan, Acting Regional Administrator-Region I U. S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, Pa. 19406

Dear Mr. Allan:

The attached Licensee Event Report LER-83-018/03L-0 is hereby submitted in accordance with the requirements of Technical Specification 6.9.1.7.

This event is of the type described in Technical Specification 6.9.1.7.2.b.

Three copies of this letter and attachment are enclosed as required.

Ve truly yours,,

$ Y p' .

/ /y n+ - ,

attach.

cc: Mr. Richard DeYoung, Director (30 copies)

Office of Inspection and Enforcement c/o Distribution Services Branch, DDC, ADM U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Mr. William G. Mcdonald, Director (3 copies)

Office of Management Information and Program Control c/o Distribution Services Branch, DDC, ADM U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Mr. Thomas Foley, Senior Resident Inspector U. S. Nuclear Regulatory Commission P. O. Box 38 Buchanan, New York 10511 n

o

/ '

I