05000247/LER-1981-011-01, /01T-0:on 810508,pits Observed on Exterior Surface of Svc Water Pump Discharge Piping.Caused by External Corrosion,Resulting in Local Areas Below Min Wall Thickness. Areas Sand Blasted,Patch Welded & Repainted

From kanterella
(Redirected from ML20004F374)
Jump to navigation Jump to search
/01T-0:on 810508,pits Observed on Exterior Surface of Svc Water Pump Discharge Piping.Caused by External Corrosion,Resulting in Local Areas Below Min Wall Thickness. Areas Sand Blasted,Patch Welded & Repainted
ML20004F374
Person / Time
Site: Indian Point 
Issue date: 05/22/1981
From:
CONSOLIDATED EDISON CO. OF NEW YORK, INC.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML093620883 List:
References
LER-81-011-01T, LER-81-11-1T, NUDOCS 8106180251
Download: ML20004F374 (2)


LER-1981-011, /01T-0:on 810508,pits Observed on Exterior Surface of Svc Water Pump Discharge Piping.Caused by External Corrosion,Resulting in Local Areas Below Min Wall Thickness. Areas Sand Blasted,Patch Welded & Repainted
Event date:
Report date:
2471981011R01 - NRC Website

text

_

LICENSEE EVENT REPORT cownot stocx: l l

t l

l 1

I@

(PLEASE PRINT OR TYPt ALL RLQUI ED INFORMATION!

i 6

loIil I n! y! il n!s ! 2l @l n I nl In I,!,1,I I e IO Iol@l.1'lilililil@l l@

t uCE m ECook i4 a

uC E Nm.v.e a

6 uCEsa n,E -

u sAi -

CON'T lolil C"J LtJ@l o f si > ln I o 12 1 : I vl@lo I s I oi s !a 11 l@l o I si 212 I a I il@

F 3

f,J 61 COC%ET NuYuta w

6J E% ENT DATE 14 4

REP 0HT DATE dJ EVENT OESCAtPT,4C*J AND ?PC0 ASLE CCf4 SEQUENCES h [TITl l Du r ing inspection of service watar nuno dischcir-e pi inc_-it-w e, n [o l 31 l observed on the exterior surface.

Ncn-destructive av i d u e 4 e e# "e I

j loidll pits indleated that the oice wall thickness under # cur em,'l

  • m ne I Isl lless than tne minimum wall thickness recuired to meet seismic desien l

ITTTII critoria, to.135 inchesi.

Possible consecuenecc could nave been ene i

l 017 l l eventual development of small pinhole leaks with no degradation in the I joi411 operability of the service water system.

I 60 r

ea ST E t !'.'

CAUSE

0 A ',11 CC"8 VAL % E COCE 00CE SLBCOCE C0YPCNENT COCE SL8C00E SLJCOCE 1o191 I w!n l@ le l@ l ol@ l"!r i oir I x! xf9 lo l@ l zi@

7 4

3 to ti 14 tJ 18 is 20 SE GUEN TI A L CCOUR"ENCE PE*AT A E V'CIC N

{

,_6%ENT vf aA utvC+ T NO.

COCE T*PE N o, ggs og

[,"!.'.h*

9!1

! I! I l

!O l7 I l '""-l

!O

,2'

.2

3 04
J 73
)

M il

  • w.'/80NEN?

CO ACT'ON servat Essg t 5 % T SC"4N AT*A >Y E N T No"8 0 4 821YE CTY8 ra.' v ta TA<!N a;? ;N 0. p.

  • .T YENO:

0LR$..

U.sYiTTE:

8 0.a Y 2,3 3, v. E :a lE

!2 lO U ! O!

l x!

lEl l.d k' ! O !7, 32 J4 3

.6 3t 4J 43 42 43 44 47 CAUSE CESCAlpitCN AND CCAAECTIVE ACTICNS h 11 lojl External corrosien esused four pits to be formed in the service water I

s Wl nur s discharce pipine waich resulted in Icesi arca telew ini.u- "211!

[,i,i l thickness.

The areas were sand

.-13.

ee, a patch was welded oter ca:n 1

area and the entire surfaces of the pipes recainted to crevent l

! [TT-l I pi t ted l

l til4 1] furtner cerrosion.

93 7

3 9 YETMCO CF F ACittTY STATUS

  • i p0V.E m OTHER STATLS O r 5C O'. E R Y 06SCOVERY OESCRt#TICN 32 lI I5l n! O !' Of n/A I

lCl ypeC131 test of de0th of piO3 l

7 8 3 to 12 11 44 45 46 to i

ACTIVITY CONTENT d'

I Af LE ASED OF#ELEASE AVCUNT CF ACT3VITY --

LOCATICN CF RELEASE l'istI d @ L:d@ln'^

l I n/a i

7 4 3 14 it 44 45 n

  • Ent?. EL E x803;aij
  • uvtif a Twig
g;;moTi;s l

l 3 l 7 l 1 r) a !

I*

l

'/*.

33 7

3 3 1;

'3 8E8450N*.E L %L* Ei P.LYPfa

  • E SCA
    P fiCN

!I k*l 0 0 M '3 33 7

8 9 11 12 LCt3CFCACAYACE?O8A0!utv/A mt

u
v?C U

i I

li I o I L.d@l

n 30 7

4 9 13 PL8pCf Y f W WE ONLY e

v sy E 0g D UC Ai* TION l 2 IO l h*'A l

lIl!lllI*I !ilj 64 6 ')

U 5 s a su o

fJf'.1E OF PREPARER PHONE:

2, 8106 7a o rot --.

4 t

ATTACllMENT 1 Docket No. 05000247 consolidated Edison company of New York, Inc.

LER 81-011/03L-0 Indian Point Unit No. 2 While in cold shutdown the service water piping in the pump pit was sand blasted to remove surface corrosion.

Visual inspection of the cleaned pipe showed a total of seven (7) pits had formed on three of six service water pump discharge lines.

The depth of the pits and. surrounding wall thickness were measured using a pipe pit gage and an ultrasonic meter respectively.

The remain-ing wall thickness under each pit was then calculated using the measured values.

Using an allowable wall thickness of 0.135 inches, which was based on seismic considerations, it was found that there were four pits which were below the value.

These wall thicknesses were:

Line No. 23, 0.060 inches; Line No. 24, 0.060, 0.105 and 0.125 inches.

The cause of the pitting is believed to have been e>:ternal corrosion resulting from the damp conditions fcund in the pump pit.

A patch was welded over each pitted area and the entire

- surfaces of the pipes repainted to prevent further c rr:sion.

The si::e and small number of pits did not reduce the ability of the piping to withstand a design basis seismic event.

Had one or more pits devolcped into through holes, the result would have been " pinhole" leaks which wculd not have significantly degraded the operability of the system.

- I e

k e

e

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - ^ ^ ' - ~ - - - ^ ^ ' ' ^ - - - - ' - ~ ~