LER 78-037/03L-0 on 781116:Unit 2 Reactor Bldg to Suppression Chamber Vacuum Breaker Valve 2-1601-20A Failed to Open.Caused by Failure of Air Line Solenoid Operator (Valve 2-1601-50A)
ML19305A113
Person / Time
Site: Quad Cities Constellation icon.png
Issue date: 12/08/1978
From: Reed M
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML19305A114 List:
References
LER-78-037-03L-01, LER-78-37-3L-1, NUDOCS 7901040143
Download: ML19305A113 (2)


Text

_

Il 'El)

LICENSEE EVENT REPORT p  ?;

V (PLEASE PRINT OR TYPE ALL REQUIRED INFORf/.ATION)

E CONT [d L DLOCO l i

l l l l l lh e

I O lil ! ! !Lj_QdAjD l 2 l@Lo l n l n l - l n l 0 l 0 l- l0 l0 l026l@l4l1lIl1l1}@! 2a LICENSE T)PE 40 l

bl t. A T Sa l@

a 9 LICCf4SLC 000E 14 15 LICENSE NUY3Ett CON'T f0'IIl 3$.3"c' [Ld@l Ol 5 l 0] O I o l 2 l 6 l c; l@l1 l1 II l6!7lRl@l1 l2 l0 l8 I7 l8 l@

EVENT DESCatPTION A DPROBA C JS ENCES lo 121 i While performing quarterly test procedure QOS 1600-9, Unit Two Reactor Buildina to I Suppression Chamber Vacuu.ti Breaker valve 2-1601-20A failed to open. The consequences (

g7s] l 10141 l of this occurrence were minimal since the redundant 100% flow capacity vacuum l IO1sl l breaker (2-1601-208) operated properly. l I

BTc 1 I l

l0 l7] l I

RTs 1 1 83 SYSTEM CAUSE CAuSE CO.'.t P. VALVE CODE CODE SUSCODE COMPONENT CODE SUBCODE SUSCODE 10191 IS lA lh l E lh l 8 l@ l V l A l L l V l 0 l P lh [_E_jh 20W @ 18 19 7 8 9 to 1i 12 13 OCCURRENCE REPORT REVISION

,. SEQUF NTI AL EVENT YE AR REPORT NO. CODE TYPE NO.

LE RfRo

@ yg.g I 718 l a

_ 28 22 l--J 24 10 13 17 I 24 2G Ld 2 .'

10 13 I 28 29 LLJ 30 I-I 31 LOJ 32 OJPL PT tE T HOURS SH iT ED FOR1 US. S PPLIE MAN FACTURER T KEN ACTC

[.A_j@lj@

33 34 lZl@

3a

[Z__j@

36 l Ol 0l 0l 0l 3/ 40 l41Y l@ [Y__j@

42 l Alh lV l0 l9l5l@

43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h I

li101l The 2-1601-20A valve did.not oDen due to the failure of the air line solenoid lilii l operator (valve 2-1601-50A). This was a mechanical failure of the fourway Versa i Fi I21 l solenoid valve. The Versa solenoid valve was reolaced and the 7-1601-?aA vacuum I l

le l 31 l breaker was retested and oroven ooerable.

I t i l41 1

  • 80 8 9 A $  % POWER OTHER STATUS IS O FY DISCOVERY DESCRIPTION I115I [E_j h l0l 9l8 l h l NA l l B l@l Routine Test l A TIVITY CO TENT PELEASE AMOUNT OF ACTIVITY LOCATION OF BELEASE

[1 l f> l l Z l @D OF RELEASE [Zj@l NA l l NA l 44 45 BJ

, 8 9 to 11 PERSONNE L EXPOSURES NUf/S E R TYPE DESCRIPflON -

l i li I il 10 l 0 l 0 ]@lZ l@l NA I PE RSONP.E L I?4 JURIES P.uveER DESCHIPTION

[1,[d l 0 l 0 l 0 lhl NA SJ I

B 9 11 12 L OF. OF CR DA*JAGE TO FACILITY h TvPE LESCRIP TION v l

[ 2191 [Zj@! HA E0 S 9 .0 "nc u~

, al"""USCH,P,,0N @ ?S0%040%3 .

I2101 LNjhl NA l lllliIIllIlIli M (.9 EG. 5

> 9 v3 NA*.t' OF PDEPAnE ft M. Reed PHONE 309-654-2241 Ext. 252 {

- t

1. LER NUMBER: LER/R0 78-37/03L-0 c II. LICENSE NAME: Commonw;alth Edison Company Quad-Cities Nuclear Power Station

, Ill. FACILITY NAME: Unit Two IV. DOCKET NAME: 050-265 V. EVENT DESCRIPTION:

On November 16, 1978, Unit Two Reactor Building to Suppression Chamber Vacuum Breaker Valve (2-1601-20A) failed to open while performing quarterly test procedure QOS 1600-9 Unit Two was in the RUN mode at a thermal power of 2460 MWt.

VI. PROBABLE CONSEQUENCES OF THE OCCURRENCE:

The consequencei of this occurrence were mininal since the reactor buildi' j to suppression chamber vacuum relief system consists of tw 100% flow capacity subsystems. Operation of either subsystem will maintain the pressure differential less than the external design of the primary containment. Redundancy of lir.es Justify reactor operation with one valve out of tertice for repairs, for a period of seven days. The redundant 2-1601-20B valve did operate properly when tested.

Vll. CAUSE:

The 2-1601-20A valve did not open due to the failure of the air line solenoid operated valve 2-1601-50A. When the solenoid coil was de-energized, the solenoid core failed to return to the de-energized position; thus, not allowing air to open the 2-1601-20A valve. This was a mechanical failure of the four-way Versa Model VGS-4422-V-10-31 solenoid valve.

Vill. CORRECTIVE ACTION:

Work request 5276-78 was written for electrical maintenance personnel to investigate the problem. The Versa solenoid valve was replaced, and the valve was again tested to be ope rab le.

4