ML18096B177
ML18096B177 | |
Person / Time | |
---|---|
Site: | Salem ![]() |
Issue date: | 12/22/1992 |
From: | Thomson F Public Service Enterprise Group |
To: | Kugler S NEW JERSEY, STATE OF |
References | |
NLR-E92370, NUDOCS 9212300174 | |
Download: ML18096B177 (2) | |
Similar Documents at Salem | |
---|---|
Category:NPDES NONCOMPLIANCE NOTIFICATION
MONTHYEARML18107A2571999-04-29029 April 1999
[Table view]NPDES Noncompliance Notification:On 990331,shortnose Sturgeon Was Removed from Circulating Water Sys (CWS) Intake Trash Racks at Salem Generating Station.Environ Licensing Responded & Confirmed Identification of Sturgeon ML18106A7811998-07-23023 July 1998 NPDES Noncompliance Notification:On 980727,dead Sea Turtle Was Removed from Circulating Water Sys Intake Trash Racks. Based on Turtle Being Badly Decomposed,Licensee Disposed of Turtle in Trash Dumpster ML18102B2691997-04-29029 April 1997 Supplemental Discharge Confirmation Rept #2 Re Discharge of Fuel Oil to Delaware River.Maintenance Svcs Now Inspects & Documents All vendor-supplied Tanks Used for Fuel & Master List of Tanks & Locations Is Kept by Maintenance Svcs ML18102A8891997-02-27027 February 1997 NPDES Noncompliance Notification,Submitting Suppl Rept on Corrective Measures to Be Taken to Reduce Potential of Future Occurrences Re Discharge of Fuel Oil Into Delaware River ML18102A7591997-01-13013 January 1997 NPDES Noncompliance Notification,Confirming Discharge of Less than One Gallon of No 2 Fuel Oil to Delaware River at Plant.Measures Are Being Developed to Reduce Potential for Future Occurrences ML18101B2201996-02-0606 February 1996 Discharge Confirmation Rept:On 960107,discovered That Approx 115 Gallons of Sodium Hypochlorite Discharged to Delaware River.Caused by Human Error.Pse&G Developing Measures to Reduce Potential for Future Occurrences ML18101A8501995-07-21021 July 1995 Notification of Nonroutine Event:On 950702,one Dead logger- Head Sea Turtle Recovered from Trash Rack of CWS Intake. Cause of Death Appeared to Be Severe Propeller Cut on Remaining Carapace.Turtle Disposed of in Landfill ML18100B2341994-07-22022 July 1994 NPDES Noncompliance Notification:On 940624,loggerhead Sea Turtle Recovered from Trash Rack 11A of CWS Intake Trash Racks at Plant.Between June 1 & Oct 15,trash Racks Observed Every Two h,24 H a Day & Cleaned at Least Once Per Day ML18100B0301994-04-18018 April 1994 NPDES Noncompliance Notification:On 940414,noticed That Hydrazine Monitor in Influent Equalization Basin Indicated Presence of Hydrazine,Resulting from Residual Amount of SG Waste.Sys Operator Oversight Being Expanded ML18100A4681993-07-0202 July 1993 NPDES Noncompliance Notification:On 930513,discharge of Oil to Delaware River from West Yard Drain 488 Reported.Caused by Washing Oil from Walls of Collection Sys Piping During Precipitation events.One-inch Drain Valve Installed ML18100A3941993-05-28028 May 1993 NPDES Noncompliance Notification:On 930424 & 29,approx 1/2 Gallons of Ethylene Glycol Discharged to Delaware River Through Circulating Water Sys Outfall Dsn 481.Caused by Leaking Expansion Tank.Drip Bag Placed Under Leak ML18100A3811993-05-18018 May 1993 NPDES Noncompliance Notification:On 930513,less than One Gallon of Oil Discharged to Delaware River from Salem Generating Station.Absorbant Boom Being Maintained in Min of Three Manholes.Root Cause Investigation to Be Conducted ML18100A3741993-05-0707 May 1993 NPDES Noncompliance Notification:On 930504,lubricating Oil Discharged from Traveling Screen at Svc Water Intake Structure.Tarry Substance Probably Drawn in from Delaware River & Not as Result of Facility Discharge ML18100A2811993-03-30030 March 1993 NPDES Noncompliance Notification:On 930325,discharge of Hydrazine from Nonradiological Liquid Waste Disposal Sys Occurred & Hydrazine Detected in Final Clarifier.Caused by Failure to Open Valve.Hydrazine Addition Procedure Revised ML18096B3351993-03-0808 March 1993 NPDES Noncompliance Notification:On 930303,oil Sheen Entered Delaware River from South Yard Drain Dsn 489 & Extended Approx 80 Ft Along Shoreline.Caused by Operation of Unit 2 Skim Tank.Absorbant Boom Maintained in Manholes ML18096B2771993-02-17017 February 1993 NPDES Noncompliance Notification:On 930212,oil Sheen Entered Delaware River Through Stormwater Outfall Dsn 488.Probably Caused by Oil Washed from Sys During Precipitation Event. Bids Under Review for Vacuum Cleaning Yard Drain Sys ML18096B2141993-01-18018 January 1993 NPDES Noncompliance Notification:On 921118,reported Discharge of Hydrazine in Area of Acid/Caustic Truck Unloading Station at Facility.Ltr Serves as Clarification of Info Provided in Original Retraction of Discharge ML18096B2121993-01-15015 January 1993 NPDES Noncompliance Notification:On 930106,reported Violation of Petroleum Hydrocarbons Limit.Licensee Intends to Perform Weekly Petroleum Hydrocarbons Sampling for Remainder of Month ML18096B1881993-01-0505 January 1993 NPDES Noncompliance Notification:On 921230,oil Sheen Entered Delaware River Through Stormwater Outfall,Dsn 488.Discharge Effectively Terminated Upon Placement of Boom in River ML18096B1771992-12-22022 December 1992 NPDES Noncompliance Notification:On 921203,discharge of Approx 350 Gallons of Industrial Wastewater to Stone Covered Area Occurred.Discharge Originated from Industrial Wastewater Sys & Exempt from Permit Reporting Requirements ML18096B1761992-12-18018 December 1992 Suppl to 921206 Noncompliance Notification Re Discharge of Approx 1 Liter of Transformer Oil from Main Power Transformer to stone-filled Concrete Containment.Event Exempt from Reporting Requirements ML18096B1361992-12-0202 December 1992 NPDES Noncompliance Notification:On 921102,approx 1 Gallon of Lubricating Oil Released Due to Overfilling of Traveling Screen 21B Drain Bath.Discharge Terminated & Oil Wiped Up W/ Absorbant Pads.Permanent Containments Will Be Installed ML18096B1201992-11-27027 November 1992 NPDES Noncompliance Notification:On 911102 & 06,two Shortnose Sturgeon Removed from Circulating Water Racks During Cleaning of Trash Racks.Both Sturgeon Dead Upon Recovery.Trash Racks Inspected Daily for Debris Load ML18096B0471992-10-16016 October 1992 NPDES Noncompliance Notification:On 920919,20 & 22,three Loggerhead Sea Turtles & One Kemp Ridley Sea Turtle Recovered on Intake Trash Racks.On 921002,addl Turtle Recovered.Caused by Summer Migration.Turtles Released ML18096B0611992-10-14014 October 1992 NPDES Noncompliance Notification:On 920914,discovered That Approx 3 Gallons of Lubricating Oil Discharged to Ground in Scaffold Storage Area.Discharge Remained Entirely on Util Property.Environ Control Procedure Will Be Revised ML18096B0231992-09-25025 September 1992 NPDES Noncompliance Notification:On 920828,0901,09,11 & 12, Longerheads Retrieved from CWS Intake Trash Screens.On 920901 & 04,two Kemp Ridleys Recovered.On 920831,green Sea Turtle Recovered Dead.Caused by Summer Migration of Turtles ML18096A9831992-09-11011 September 1992 NPDES Noncompliance Notification:On 920821,approx 2 Gallons of Transformer Oil Discharged to Concrete Containment Filled W/Stone.Oil Cleaned Up Immediately Prior to Escape to Waters or Lands of State of Nj ML18096A9711992-09-0909 September 1992 NPDES Noncompliance Notification:On 920903,approx 1 Gallon of Oil Discharged to stone-surfaced Area Adjacent to Skim Tank 1.Oil Cleaned Up Immediately & Removed Prior to Escape Into Waters or Lands of State of Nj ML18096A9661992-08-28028 August 1992 NPDES Noncompliance Notification:On 920730,approx 5 Gallons of Lubricating Oil Discharged to Delaware River Through Circulating Water Sys at Outfall Dsn 485.Circulator Removed from Svc & Absorbant Pads Placed on Floor in Spill Area ML18096A9171992-08-17017 August 1992 NPDES Noncompliance Notification:On 920729,one Loggerhead Sea Turtle Recovered from Circulating Water Sys Intake Trash Racks.Caused by Turtle Migration During Summer Months. Turtle Tagged & Released Approx 3 1/2 Miles from Plant ML18096A9061992-08-14014 August 1992 NPDES Noncompliance Notification:On 920518,approx 5 Gallons of Diesel Fuel Oil Discharged to Ground at Well Pump 5 Temporary Diesel Fuel Tank.Caused by Tank Overflowing to Pump Skid.Measuring Gauge Repaired.Repts Encl ML18096A9001992-08-14014 August 1992 NPDES Noncompliance Notification:On 920715,20 Gallons of Diesel Fuel Discharged from 80-ton Crane Between Salem & Hope Creek Stations.Caused by Broken Fuel Line.Soil Around Discharge Excavated & Placed in Drums for Disposal ML18096A8831992-08-0707 August 1992 NPDES Noncompliance Notification:On 920708 & 09,discharges of Fuel Oil from Fuel Filter House at Plant Main Fuel Oil Storage Tank Occurred.Caused by Fuel Oil Dripping from Filter House Vent.Oil Sent to Lab for Waste Classification ML18096A8731992-08-0505 August 1992 NPDES Noncompliance Notification:On 920706,approx 3,500 Gallons of Water,Containing 5.75 mg/1 Hydrazine,Discharged to Delaware River.Caused by Tank Fill Valve Left Open Longer than Necessary.Hose Reattached to Vent Line ML18096A8601992-07-27027 July 1992 NPDES Noncompliance Notification:On 920510,discharge of Approx 2 Gallons of Diesel Fuel Oil to Ground North of Plant Svc Water Intake Structure Occurred.Caused by Faulty Fill Nozzle on Tanker Truck.Nozzle Replaced ML18096A8531992-07-24024 July 1992 NPDES Noncompliance Notification:On 920619,util Reported Oil Sheen on Delaware River in Area Between Svc Water Intake Structure & Circulating Water Sys Intake.Sheen Did Not Result from Plant Operations.Discharge Rept Retracted ML18096A8341992-07-14014 July 1992 NPDES Noncompliance Notification:On 920618,loggerhead Sea Turtle Recovered from Circulating Water Sys Intake Trash Screens.Turtle Placed in 800 Gallon Holding Tank for Observation.Turtle flipper-tagged & Released ML18096A7741992-06-0606 June 1992 NPDES Noncompliance Notification:On 920506,approx 500 Gallons of Water,Containing Hydrazine,Discharged to Ground. Caused by Overflow of Auxiliary Feedwater Storage Tank 2. Fill Valve Closed & Extension Added to Overflow Line ML18096A7731992-06-0606 June 1992 NPDES Noncompliance Notification:On 920507,lubricating Oil from Ancillary Equipment of Generator Became Entrained in Hydrogen Vent Stream.Caused by Misaligned Valve.Oil Absorbent Pads Placed on Ground Surrounding Crane ML18096A6191992-04-0202 April 1992 NPDES Noncompliance Notification:On 920304,sodium Hypochlorite Discharged from Svc Water Intake Structure. Caused by Util Tanker Backing Into Line & Shearing Off Drain Valve.Addl Instruction Added for Site Svcs Personnel ML18096A5981992-03-24024 March 1992 NPDES Noncompliance Notification:On 920227,discharge of Two Gallons of Number 2 Fuel Oil from Gas Turbine to Ground Occurred.Personnel Applied Absorbent to Affected Area to Collect Matl.Remediation Plan Being Developed ML18096A5841992-03-19019 March 1992 Suppl to 920305 NPDES Noncompliance Notification Re Discharge of Oil Contaminated Water at Laydown Yard.Approx 135 Cubic Ft of Soil & Gravel Removed from Discharge Area & Placed Into Drums.No Lab Data Collected for Discharge ML18096A5281992-02-19019 February 1992 NPDES Noncompliance Notification:On 920120 & 28,lubricating Oil Was Discharged to Ground Adjacent to Circulating Water Sys Bldg.Work Order Mod Included Placement of Impermeable Catch Basin Under Chain Guard Reservoir ML18096A5291992-02-18018 February 1992 NPDES Noncompliance Notification:On 920124,two Gallons of Hydraulic Fluid Spilled from Ruptured Hydraulic Line.All Fluid Contained within Paved Area Surrounding Crane ML18096A5271992-02-18018 February 1992 NPDES Noncompliance Notification:On 920124,approx 500 Gallons of Oil,Contaminated W/Rainwater,Escaped from Spare Transformer Secondary Containment Area.Followup Investigation Underway.Affected Area Cleaned ML18096A4251992-01-0303 January 1992 NPDES Noncompliance Notification:On 911230,approx 20 to 30 Gallons of Unknown Liquid Discharged at Facility.Caused by Sewage Leaking from Broken Sewer Line.Discharge Terminated & Area Disinfected W/Sodium Hypochlorite ML18096A4071991-12-24024 December 1991 Corrects 910706 NPDES Noncompliance Notification:On 910623 & 24,sea Turtles Discovered in Trash Rack 23b of Recirculating Water Sys.Turtles Tagged & Released 3 1/2 Miles from Plant ML18096A4051991-12-20020 December 1991 NPDES Noncompliance Notification:On 911121,water Discharged from Oil/Water Separator Discharge Piping.Caused by Excavation Activity.Adjacent Potential Joint Leak on Piping Unearthed & Hot Patch Applied ML18096A3691991-12-0303 December 1991 NPDES Noncompliance Notification:On 911103,approx 5 Gallons of Lubricating Oil Discharged to Delaware River Through Circulating Water Sys Outfall Dsn 484.Caused by Leaking Valve.Valve Tightened & Discharge Terminated ML18096A3681991-12-0303 December 1991 Resubmitted NPDES Noncompliance Notification,Containing Notary Seal & Correcting Date to 911104.Certification Should Be Replaced W/Encl Certification 1999-04-29 Category:TEXT-ENVIRONMENTAL REPORTS MONTHYEARML18107A5441999-08-31031 August 1999
[Table view]NPDES Discharge Monitoring Rept for Aug 1999 for Salem Generating Station. ML18107A4891999-07-31031 July 1999 NPDES Discharge Monitoring Rept, for Salem Generating Station for Jul 1999 ML18107A5251999-06-30030 June 1999 Semiannual Radioactive Effluent Release Rept for Jan-June 1999. ML18107A4571999-06-30030 June 1999 NPDES Discharge Monitoring Rept for June 1999 for Salem Generating Station. ML18107A4111999-05-31031 May 1999 NPDES Discharge Monitoring Rept, for Salem Generating Station for May 1999 ML18107A3391999-04-30030 April 1999 NPDES Discharge Monitoring Rept for Salem Generating Station for Apr 1999. ML18107A2571999-04-29029 April 1999 NPDES Noncompliance Notification:On 990331,shortnose Sturgeon Was Removed from Circulating Water Sys (CWS) Intake Trash Racks at Salem Generating Station.Environ Licensing Responded & Confirmed Identification of Sturgeon ML18107A2291999-03-31031 March 1999 NPDES Discharge Monitoring Repts for Mar 1999 for Salem Generating Station. ML18106B1401999-02-28028 February 1999 NPDES Discharge Monitoring Rept, for Salem Generating Station for Feb 1999 ML18106B0851999-01-31031 January 1999 Discharge Monitoring Rept for Salem Generating Station, for Jan 1999 ML18107A2581998-12-31031 December 1998 1998 Annual Environ Operating Rept (Non-Radiological) for Salem Generating Station,Units 1 & 2. with 990429 Ltr ML18107A2531998-12-31031 December 1998 Radiological Environ Monitoring Program for Salem & Hope Creek Generating Station for 1998. ML18106B0891998-12-31031 December 1998 Semiannual Radioactive Effluent Release Rept for Jul-Dec 1998. ML18106B0311998-12-31031 December 1998 NPDES Discharge Monitoring Rept, for Dec 1998 ML18106A9881998-11-30030 November 1998 NPDES Discharge Monitoring Rept for Nov 1998 ML18106A9711998-10-31031 October 1998 NPDES Discharge Monitoring Rept for Oct 1998 for Salem Generating Station,Units 1 & 2. ML18106A9401998-09-30030 September 1998 Discharge Monitoring Rept for Sgs for Sept 1998. ML20154B2281998-08-31031 August 1998 NPDES Discharge Monitoring Rept for Aug 1998 for Salem Generating Station ML18106A8231998-07-31031 July 1998 NPDES Discharge Monitoring Rept for July 1998 for Salem Generating Station. ML18106A7811998-07-23023 July 1998 NPDES Noncompliance Notification:On 980727,dead Sea Turtle Was Removed from Circulating Water Sys Intake Trash Racks. Based on Turtle Being Badly Decomposed,Licensee Disposed of Turtle in Trash Dumpster ML18106A7891998-06-30030 June 1998 NPDES Discharge Monitoring Rept for June 1998 for Sgs. ML18106A6761998-05-31031 May 1998 Discharge Monitoring Rept for Salem Generating Station for May 1998. ML18106A6211998-04-30030 April 1998 NPDES Discharge Monitoring Rept for Apr 1998 for Salem Generating Station. ML18106A5651998-03-31031 March 1998 New Jersey Pollutant Discharge Elimination Sys Discharge Monitoring Rept, for Salem Generating Station ML18106A4101998-02-28028 February 1998 NPDES Discharge Monitoring Rept for Salem Generating Station for Month of Feb 1998. ML18106A3461998-01-31031 January 1998 NPDES Monitoring Rept for Salem Generating Station, for Jan 1998 ML18106A3611997-12-31031 December 1997 Station,Radioactive Effluent Release Rept for Period Jul-Dec 1997. ML18106A2771997-12-31031 December 1997 NPDES Discharge Monitoring Repts for Dec 1997 for Salem Generating Station. ML18106A3521997-12-31031 December 1997 Std Format for Reporting Number of Personnel & Man-Rem by Work & Job Function for Period from 970101-1231. ML18106A5801997-12-31031 December 1997 1997 Annual Environ Operating Rept (Non-Radiological) for 970101-1231, for Salem Generating Station,Units 1 & 2. W/980428 Ltr ML18106A5891997-12-31031 December 1997 1997 Annual Radiological Environ Operating Rept for Salem & Hope Creek Generating Stations. ML18106A2301997-11-30030 November 1997 New Jersey NPDES Discharge Monitoring Rept for Salem Generating Station for Month of Nov,1997. ML20216F5301997-11-30030 November 1997 NPDES Discharge Monitoring Rept for Nov 1997 for Salem Generating Station ML18106A1751997-10-31031 October 1997 New Jersey NPDES Discharge Monitoring Repts, for Oct 1997 for Salem Generating Station ML20216F5231997-10-31031 October 1997 NPDES Discharge Monitoring Rept for Oct 1997 for Salem Generating Station ML18102B6241997-09-30030 September 1997 New Jersey NPDES Discharge Monitoring Repts for Salem Generating Station for Sept 1997. ML18102B5861997-08-31031 August 1997 NPDES Discharge Monitoring Rept for Salem Generating Station for Aug 1997. W/970925 Ltr ML18102B5261997-07-31031 July 1997 Discharge Monitoring Rept for Salem Nuclear Generating Station for July. ML18102B5541997-06-30030 June 1997 Semi-Annual Radioactive Effluent Release Rept. ML18102B4601997-06-30030 June 1997 NPDES Discharge Monitoring Rept for June 1997 for Salem Generating Station. W/970723 Ltr ML18102B4041997-05-31031 May 1997 NPDES Discharge Monitoring Rept for May 1997. ML18102B3371997-04-30030 April 1997 NPDES Discharge Monitoring Repts for Apr 1997 for Salem Generating Station. W/970523 Ltr ML18102B2691997-04-29029 April 1997 Supplemental Discharge Confirmation Rept #2 Re Discharge of Fuel Oil to Delaware River.Maintenance Svcs Now Inspects & Documents All vendor-supplied Tanks Used for Fuel & Master List of Tanks & Locations Is Kept by Maintenance Svcs ML18102B2501997-03-31031 March 1997 New Jersey Pollutant Discharge Elimination Sys Discharge Monitoring Repts for March 1997. W/970423 Ltr ML18102B3601997-02-28028 February 1997 Corrected Discharge Monitoring Rept for Feb 1997 for Salem Generating Station. ML18102A9421997-02-28028 February 1997 NPDES Discharge Monitoring Rept for Salem Generating Station Units 1 & 2 for Feb 1997. W/970324 Ltr ML18102A8891997-02-27027 February 1997 NPDES Noncompliance Notification,Submitting Suppl Rept on Corrective Measures to Be Taken to Reduce Potential of Future Occurrences Re Discharge of Fuel Oil Into Delaware River ML18102B3581997-01-31031 January 1997 Corrected Discharge Monitoring Rept for Jan 1997 for Salem Generating Station. ML18102A8771997-01-31031 January 1997 Discharge Monitoring Rept for Jan 1997 for Salem Generating Station. W/970220 Ltr ML18102A7591997-01-13013 January 1997 NPDES Noncompliance Notification,Confirming Discharge of Less than One Gallon of No 2 Fuel Oil to Delaware River at Plant.Measures Are Being Developed to Reduce Potential for Future Occurrences 1999-08-31 |
Text
Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038 Nuclear Department CERTIFIED MAIL RETURN RECEIPT REQUESTED ARTICLE NUMBER: P 708 711 285 DEC 2 21992 NLR-E92370 Bureau of Discharge Prevention NJ Department of Environmental Protection and Energy 401 East State Street CN-027 Trenton, NJ 08625-0027 Attention: Ms. Shelly Kugler
Dear Ms. Kugler:
RETRACTION OF DISCHARGE REPORT PUBLIC SERVICE.ELECTRIC AND GAS (PSE&G) COMPANY SALEM GENERATING STATION CASE NO. 92-12-03,:..2216-29 On December 3, 1992, PSE&G reported a discharge of approximately three hundred and fifty (350) gallons of industrial wastewater containing approximately 0.4 mg/l of hydrazine (CAS No. 302-01-2) and 30 mg/l of ammonia (CAS No. 766-441-7) to a stone covered area. The discharge was assigned Case No. 92-12-03-2216-29 by Operator 23.
Upon investigation of the discharge and review of applicable regulations and NJDEPE guidance (Questions & Answers An Aid to DPCC/DCR Planning) , PSE&G has determined that this discJ;1arge originated from an industrial wastewater treatment system regulated under a NJPDES permit, (NJ0005622). The wastewater was collected and returned to the industrial wastewater treatment system for treatment. It is PSE&G's interpretation of the regulations that as this incident involved industrial wastewater that is regulated under a NJPDES permit, it is*exempt from this reporting requirement.
PSE&G believes and maintains that it acted in accordance with the
- f .. ... .intent of NJAC 7: 1E-5. 3 which requires all major facilities to
" 1~/)notify NJDEPE of discharges of potentially hazardous substances
- .. ;\~";!!n any concentration.
- i . :~,;~~-~'r<
L
DEC 2 2 1992 NJ DE PE 2 NLR-E92370 Should you have any questions on this issue, please feel free to contact Mr. David Hurka of my staff at (609) 339-1275.
Sincerely,
~---// ;/
, 7 /k".....-,..... -4~- /
""F. X. Thomson,' Jr.
Manager -
Licensing and Regulation c NJ Department of Environmental Protection and Energy Southern Regional Enforcement 20 E. Clementon Road Gibbsboro, New Jersey 08026 Attention: Mr. Armand Minardi United States Nuclear Regulatory Commission Document Control Desk Washi~gton, D.C. 20555 Salem County Department of Health 98 Market Street Salem, New Jersey 08079 Attention: Mr. James Warner NJ Department of Environmental Protection and Energy Division of Responsible Party Site Remediation Site Assessment CN-407 Trenton, N.J. 08625