OPS~G Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, N.J. 08038 609/339-1100 Leon R. Eliason Chief Nuclear Officer & President Nuclear Business Unit CERTIFIED MAIL RETURN RECEIPT REQUESTED ARTICLE NUMBER:

Z 217 970 197 Bureau of Discharge Prevention FEB o*s 1996 LR-E96019 New Jersey Department of Environmental Protection 401 East State Street CN-027 Trenton, New Jersey 08625-0027 Gentlemen:

PUBLIC SERVICE ELECTRIC AND GAS COMPANY SALEM GENERATING STATION CASE NO. 96-01-07-0049-18 DISCHARGE CONFIRMATION REPORT In accordance with NJAC 7:1E-5, Public Service Electric and Gas Company (PSE&G) has.prepared the attached report confirming the discharge of approximately 115 gallons of sodium hypochlorite to the Dela~are River at the Salem Generating Station.

The discharge occurred to the 13B circulating water pump bay at the Station's circulating water intake structure.

There were no personnel injuries resulting from this discharge.

The discharge was reported to the New Jersey Department of Environmental Protection (NJDEP) Hotline and assigned Case No. 96-01-07-0049-18 by Operator No. 18.

In addition, because 115 gallons exceeds the reportable quantity (RQ) for sodium hypochlorite in the Comprehensive Environmental Responsibility Cleanup Liabilities Act (CERCLA, 40 CFR 302), this discharge was also reported to the National Response Center and the Nuclear Regulatory Commission.

The National Response Center assigned Case No. 319-223.

In making this notification, PSE&G believes that it acted in accordance with the intent of NJAC 7:1E-5, which requires all major facilities to notify the NJDEP of discharges of petroleum and other potentially hazardous substances in any concentration.

Following a detailed investigation of this incident, PSE&G has identified the causes of this discharge and is developing measures to reduce the potential for future occurrences.

PSE&G shall provide the Department with these corrective measures in a supplemental report to be issued no later than March 1, 1996.

( - --9602130821--960206 PDR ADOCK 05000272 S

PDR The paw-er is in your hands.

ifJ!J I I 95-4924 REV. 10/94

I NJDEP LR-E96019

  • 2 FEB 0619!11 Should you have any questions concerning this information, or require additional information, please contact Mr. Patrick McCabe of Licensing and Regulation at (609) 339-1245.

Attachment (1)

Sincerely,

~a~e~

General Manager -

Salem Operations C

Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 US Coast Guard MSO/Group Philadelphia 1 Washington Avenue Philadelphia, PA 19147-4395 Attention:

Petty Officer Scott Roth Salem County Department of Health 98 Market Street Salem, NJ 08079 Attention:

Mr. James Warner

CERTIFICATION state of New Jersey:

SS County of Salem I certify under penalty of law that the information provided.in this document is true, accurate and complete.

I am aware that there are significant civil and criminal penalties, including fines or imprisonment or both, for submitting false, inaccurate or incomplete information.

Warren Gen al Manager -

Salem Operations Sworn and on this subscribed before me 0

day of Eetrw e 7

~LA.oLL/

' 1996.

Notary Public My commission expires BARBARA A. POWELL NOTARY PUBLIC OF NEW JERSEY My C<i*tl!TllHion Expires Dec. 2, 1998

. m # 2160323

DISCHARGE CONFIRMATION REPORT CASE NO. 96-01-07-0049-18 INDIVIDUAL REPORTING DISCHARGE:

S. Sauer Senior Nuclear Shift Supervisor Public Service Electric and Gas P. O. Box 236, M/C SOl Hancocks Bridge, New Jersey 08038 (609) 339-S200 INDIVIDUAL SUBMITTING CONFIRMATION REPORT:

c. c. Warren General Manager -

Salem Operations Public Service Electric and Gas P. O. Box 236, M/C SOS Hancocks Bridge, New Jersey 08038 (609) 339-2900 FACILITY OWNER/OPERATOR:

Public Service Electric and Gas Co.

P. O. Box S70-17G Newark, New Jersey 07101-0S70 (201) 430-S868 INDIVIDUAL(S) RESPONSIBLE FOR THE DISCHARGE:

c. c. Warren General Manager -

Salem Operations Public Service Electric and Gas P. O. Box 236, M/C SOS Hancocks Bridge, New Jersey 08038 (609) 339-2900 DISCHARGE SOURCE:

The discharge was caused by an operator closing a valve (1CL78) in the sodium hypochlorite injection system.

The valve closure resulted in an increase in the system pressure and the rupture of a filter gasket on the pump discharge strainer.

Sodium hypochlorite leaked from the strainer to the floor and drained to the inlet bay of the 13B circulating water pump.

The circulating water inlet bays are directly connected to the Delaware River.

The cause of the incident is attributed to human error involving inattention to detail in preparation of the tagging release by Work Control Center personnel.

Contributing causes include Operations personnel having overconfidence and misjudgment regarding the proper position of the valve, inadequate maintenance of the sodium hypochlorite pump recirculation system and inadequate design of the chlorine building sump.

DISCHARGE CONFIRMATION REPORT CASE NO. 96-01-07-0049-18 DISCHARGE LOCATION:

Salem Generating station End of Alloway Creek Neck Road Block No: 26 Lot No:

4.01 Municipality: Lower Alloways Creek Township County: Salem County Zip Code: 08038 Tax No: 22-1212-800 EPA ID No: NJD077070811 (Maps enclosed -

See Figures 1 & 2)

CHEMICAL DISCHARGED:

QUANTITY DISCHARGED:

DATE/TIME DISCHARGE BEGAN:

DATE/TIME DISCHARGE ENDED:

DATE/TIME DISCHARGE DISCOVERED:

DATE/TIME DISCHARGE REPORTED TO NJDEP HOTLINE:

Sodium Hypochlorite CAS Number:

007681-52-9 Approximately 115 gallons Unknown - last surveillance of area occurred at 4:25 p.m.

on January 6, 1996.

No discharge was observed.

January 7, 1996 12:35 a.m.

January 7, 1996 12:35 a.m.

January 7, 1996 12:49 a.m.

MEASURES TAKEN TO CONTAIN, CLEANUP AND REMOVE THE DISCHARGE:

Upon discovery, the discharge was terminated by turning off the sodium hypochlorite pump.

The sodium hypochlorite which discharged through the drain was allowed to disperse in the intake bay and River where it was quickly diluted by the tide and River current.

The residual chlorine concentration within the intake bay was diluted to 11.0 mg/l, as measured at approximately 2:00 a.m. by Chemistry personnel, and was expected to be

  • undetectable within the next tidal cycle.

DISCHARGE CONFIRMATION REPORT CASE NO. 96-01-07-0049-18 CORRECTIVE MEASURES:

Based upon the investigation conducted, PSE&G is developing measures to reduce the potential for future occurrences.

PSE&G shall provide the Department with these corrective measure~ in a supplemental report to be issued no later than March 1, 1996.

TYPE, QUANTITY, LOCATION AND DATE OF SAMPLES:

.As discussed above, a single grab sample was obtained at the 13B intake bay at approximately 2:00 a.m. on January 7.

INDIVIDUAL CONDUCTING ANALYSIS:

J. A. Zarin Chemistry Technician Public Service Electric and Gas P. o. Box 236, M/C S07 Hancocks Bridge, New *Jersey 08038 SAMPLE METHODOLOGY:

The sample was analyzed for Total Residual Chlorine via amperometric titration (EPA Method 330.1) at the Salem Generating station (NJ Lab No. 17327).

FINANCIAL RESPONSIBILITY:

PSE&G satisfies the requirements for self-insurance established by NJAC 7:1E-4.5(g) and has included appropriate documentation of this in its Discharge Cleanup and Removal (OCR) Plan as required by NJAC 7:1E-4.4(a)9.

\\

\\

DISCHARGE LOCATION I

'I

\\

)

a

x.-___

X SDI. ~TS n-.rJ EiEc

\\ ' 1' I

llOll

~,- - Pos1

\\

\\

\\

\\

CATION HARGE LO I

45" DISC 390 27 0"

Latitude 750 32" 0 gl.. tude Lon

-~

ROCkS FIGURE 2 TION REPORT DISCHARGE C~~~~~7-0049-1S CASE NO.