ML18100A394

From kanterella
Jump to navigation Jump to search
NPDES Noncompliance Notification:On 930424 & 29,approx 1/2 Gallons of Ethylene Glycol Discharged to Delaware River Through Circulating Water Sys Outfall Dsn 481.Caused by Leaking Expansion Tank.Drip Bag Placed Under Leak
ML18100A394
Person / Time
Site: Salem  
Issue date: 05/28/1993
From: Vondra C
Public Service Enterprise Group
To: Horsley J
NEW JERSEY, STATE OF
References
NLR-E93160, NUDOCS 9306040262
Download: ML18100A394 (16)


Text

.

~,

  • O.Ps~*

Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038 Nuclear Department CERTIFIED MAIL RETURN RECEIPT REQUESTED ARTICLE NUMBER: P 346 404 414 Bureau of -Discharge Prevention MAY 2 8 1993 NLR-E93160 NJ Department of Environmental Protection and Energy 401 East State Street CN-027 Trenton, New Jersey 08625-0027 Attention:

Mr. James T. Horsley Dear Mr. Horsley PUBLIC SERVICE ELECTRIC AND GAS (PSE&G) COMPANY SALEM GENERATING STATION CASE NO. 93-04-24-2203-21 AND CASE NO. 93-04-29-0837-37 As per the requirements of NJAC 7:1E-5.8, PSE&G has prepared confirmation reports for two separate discharges of ethylene glycol to the Delaware River through circulating water system outfall, DSN 481.

The confirmation reports for the April 24 and 29, 1993 discharges are included as Attachment 1 and Attachment 2, respectively. No injuries resulted due to these discharges.

l As the discharge of ethlyene glycol is not regulated under 40 CFR 302.4, no notification of the release was reported to any agency other than the New Jersey Department of Environmental Protection and Energy and the Nuclear Regulatory Commission (NRC), as required under 10 CFR 50.72, Significant.Events.

PSE&G, in making this notification, believes that it acted in accordance with the intent of NJAC 7:1E, Subchapter 5, which requires all major facilities to notify the NJDEPE of discharges of petroleum and other potentially hazardous substances in any concentration.

PSE&G has investigated-each incident, cleaned up the affected areas and is awaiting parts to repair the equipment responsible for the discharge.

The power is 4!_your hands.

,,-----9306040262 930528 PDR ADOCK 05000272 S

PDR df}_!}

)P\\\\

95-2168 REV. 11/91

NJDEPE NLR-E93160 2

MAY 2 8 1993 Should you have any questions concerning the information contained herein, or require additional information, please contact Mr. David Hurka of Licensing and Regulation at (609) 339-1275.

Attachments (2)

NJDEPE NLR-E93160 3

MAY 2 8 1993 c

NJ Department of Environmental Protection and Energy Southern Bureau of Regional Enforcement 20 E. Clementon Road Gibbsboro, New Jersey 08026 United States Nuclear Regulatory Commission Document Control Desk Washington, D.C.

20555 Salem County Department of Health 98 Market Street Salem, New Jersey 08079 Attention:

Mr. James Warner

ATTACHMENT 1 DISCHARGE CONFIRMATION REPORT CASE No. 93-04-24-2203-21 INDIVIDUAL REPORTING DISCHARGE:

M. c. Kafantaris Senior Nuclear Shift Supervisor Public Service Electric and Gas Company Salem Generating Station P. o. Box 236, M/C SOl Hancocks Bridge, New Jersey 08038 (609) 339-5200 INDIVIDUAL SUBMITTING CONFIRMATION REPORT:

c. A. Vondra General Manager - Salem Operations Public Service Electric and Gas Company Salem Generating Station P *. o. Box 2 3 6, M/ c so 5 Hancocks Bridge, New Jersey 08038 (609) 339-2900 FACILITY OWNER/OPERATOR:

Public Service Electric and Gas Company P. O. Box 570-17G Newark, New Jersey 07101-0570 (201) 430-5868 INDIVIDUAL(S) RESPONSIBLE FOR THE DISCHARGE:

c. A. Vondra General Manager - Salem Operations Public Service Electric and Gas Salem Generating Station P. o. Box 236, M/C sos Hancocks Bridge, New Jersey 08038 (609) 339-2900

ATTACHMENT 1 (continued)

DISCHARGE CONFIRMATION REPORT CASE No. 93-04-24-2203-21 DISCHARGE SOURCE:

Salem Generating Station Circulating Water Intake Structure Heating System Expansion Tank An estimated one-half (1/2) gallon of ethylene glycol/water mixture was released due to a leak in the expansion tank associated with the circulating water intake structure heating system. The mixture dripped to the floor and subsequently into a floor drain which drains to one of the six circulating water intake bays.

Circulating water is pumped from each intake bay to the facility's once-through non-contact cooling water system at a rate o~ approximately 370,000 gallons per minute before being returned to the Delaware River approximately SOOfeet offshore.

The discharge occurred through DSN 481 which is one of the six circulating water system outfalls regulated under the facility's New Jersey Pollutant Discharge Elimination System (NJPDES) Permit No. NJ0005622.

The leaking expansion tank was discovered during a routine system walkdown at 2147 hours0.0248 days <br />0.596 hours <br />0.00355 weeks <br />8.169335e-4 months <br />.

While the exact cause of the leak could not be determined, it was apparently the result of damage to the tank and associated piping during previous activities in the area.

I

DISCHARGE LOCATION:

ATTACHMENT 1 (continued)

DISCHARGE CONFIRMATION REPORT CASE No. 93-04-24-2203-21 Salem Generating station End of Buttonwood Road Block #: 26 Lot #: 4.01 Municipality: Hancocks Bridge County: Salem Zip Code: 08038 Tax #: 22-1212-800 EPA ID #: NJD077070811 (Map Enclosed -

See Figure 1)

CHEMICAL DISCHARGED:

Ethylene Glycol CAS Number: 107-21-1 QUANTITY DISCHARGED:

Approximately 1/2 gallon of ethylene glycol was discharged.

This value is a conservative estimate based on

_the residual quantity of ethylene glycol observed on the floor.

DATE/TIME DISCHARGE BEGAN:

Unknown.

However, Operations personnel are stationed at the intake structure around the clock and periodically walk by the area of the spill.

DATE/TIME DISCHARGE ENDED:

April 24, 1993 2147 Hours DATE/TIME DISCHARGE DISCOVERED:

April 24, 1993 2147 Hours DATE/TIME DISCHARGE REPORTED:

April 24, 1993 2201 Hours (To NJDEPE Hotline)

MEASURES TAKEN TO CONTAIN, CLEANUP AND REMOVE THE DISCHARGE:

Upon discovery, Operations personnel removed the system from service and cleaned up the affected area with absorbent material.

The used absorbent will be disposed of in accordance with Federal, State and Local regulations. The cleanup and disposal costs associated with this discharge were approximately $400.00 dollars

  • J ATTACHMENT 1 (continued)

DISCHARGE CONFIRMATION REPORT CASE No. 93-04-24-2203-21 CORRECTIVE MEASURES:

The Operations Department, responsible for operation of the intake structure and equipment, initiated a work order, No.

930427205, to the Maintenance Department to repair the leaking expansion tank.

The Maintenance Department has ordered and is awaiting delivery of the new tank.

The system will not be returned to service until the repairs have been completed.

INDIVIDUAL INVOLVED IN CONTAINMENT/CLEANUP:

Cleanup activities associated with the release of the ethylene glycol, consisting of removing the heating system from service service and cleaning up the residual ethylene glycol, were conducted by Operations personnel *. Site Services personnel are responsible for disposal of the used absorbant as hazardous waste.

These individual(s) are:

M. c. Kafantaris Senior Nuclear Shift Supervisor Public Service Electric and Gas Company Salem Generating Station P. o. Box 236, M/C SOl Hancocks Bridge, New Jersey 08038 (609) 339-5200 J. G. Sterner Yard Supervisor Site Services Maintenance Public Service Electric and Gas Company Nuclear Department P. o. Box 236, M/C N34 Hancocks Bridge, New Jersey 08038 (609) 339-5338

ATTACHMENT 1 (continued)

DISCHARGE CONFIRMATION REPORT CASE No. 93-04-24-2203-21 TYPE, QUANTITY, LOCATION AND DATE OF SAMPLES:

No samples were collected of this discharge.

However, based upon a worst case scenario in which all the ethylene glycol observed leaked to the intake within five (5) minutes, and was dispersed through only one outfall, the estimated concentration of ethylene glycol in the discharge is 0.24 mg/l. Information on this characterization may be obtained from:

D. Hurka -

Lead Engineer Licensing and Regulation Public,Service Electric and Gas Nuclear Department P. o. Box 236, M/C N21 Hancocks Bridge, New Jersey 08038 (609) 339-1275 INDIVIDUAL CONDUCTING ANALYSIS:

Not applicable to this discharge.

QUALITY ASSURANCE PROCEDURES:

Not applicable to this discharge.

SAMPLE METHODOLOGY:

Not applicable to this discharge.

RATIONALE FOR SAMPLING LOCATION:

Not applicable to this discharge.

FINANCIAL RESPONSIBILITY:

PSE&G satisfies the requirements for self-insurance established by N.J.A.C. 7:1E-4.5(g) and included appropriate documentation of this in its Discharge Cleanup and Removal (OCR) Plan as required by N.J.A.C. 7:1E-4.4(a)9

  • CERTIFICATION state of New Jersey:

SS County of Salem I certify under penalty of law that the information provided in this document is true, accurate and complete.

I am aware that there are significant civil and criminal penalties, including fines or imprisonment or both, for submitting false, inaccurate or incomplete information.

sworn and subscribed before me On thisag'f-~ day Of 'y?Jtu-g:>

I 199J *

~~~~~*

N ary 1

KIMBERLY JO BROWN NOTARY PUBUC OF NEW JERSEY My Commission &pires April 21, 1998

ATTACHMENT 2 DISCHARGE CONFIRMATION REPORT CASE No. 93-04-29-0837-37 INDIVIDUAL REPORTING DISCHARGE:

M. D. Gwirtz Senior Nuclear Shift Supervisor Public Service Electric and Gas Company Salem Generating Station P. 0. Box 236, M/C SOl Hancocks Bridge, New Jersey 08038 (609) 339-5200 INDIVIDUAL SUBMITTING CONFIRMATION REPORT:

c. A. Vondra General Manager -

Salem Operations Public Service Electric and Gas Company Salem Generating Station P. O. Box 236, M/C SOS Hancocks Bridge, New Jersey 08038 (609) 339-2900 FACILITY OWNER/OPERATOR:

Public Service Electric and Gas Company P. o. Box 570-17G Newark, New Jersey 07101-0570 (201) 430-5868 INDIVIDUAL(S) RESPONSIBLE FOR THE DISCHARGE:

c. A. Vondra General Manager -

Salem Operations Public Service Electric and Gas Salem Generating Station P. O. Box 236, M/C SOS Hancocks Bridge, New Jersey 08038 (609) 339-2900

DISCHARGE SOURCE:

ATTACHMENT 2 (continued)

DISCHARGE CONFIRMATION REPORT CASE No. 93-04-29-0837-37 Salem Generating Station Circulating Water Intake Structure Heating System Expansion Tank An estimated one pint of ethylene glycol/water mixture was released due to a leak in the expansion tank associated with the circulating water intake structure heating system. The mixture dripped to the floor and subsequently into a floor drain which drains to one of the six circulating water intake bays.

Circulating water is pumped from each intake bay to the facility's once-through non-contact cooling water system at a rate of approximately 370,000 gallons per minute before being returned to the Delaware River approximately 500 feet offshore.

The discharge occurred through DSN 481 which is one of the six circulating water system outfalls regulated under the facility's New Jersey Pollutant Discharge Elimination System (NJPDES) Permit No. NJ0005622.

The leaking expansion tank was discovered during a routine system walkdown at 0830 hours0.00961 days <br />0.231 hours <br />0.00137 weeks <br />3.15815e-4 months <br />.

The source of this leak was the same expansion tank discussed in the confirmation report for Case No.

93-04-24-2203-21, (see Attachment 1).

Apparently the make-up valve, which was isolated after the first leak, leaked through causing the system to ref ill to the point where the expansion tank leaked again

  • ATTACHMENT 2 (continued)

DISCHARGE CONFIRMATION REPORT CASE No. 93-04-29-0837-37 DISCHARGE LOCATION:

Salem Generating Station End of Buttonwood Road Block #: 26 Lot #: 4.01 Municipality: Hancocks Bridge County: Salem Zip Code: 08038 Tax #: 22-1212-800 EPA ID #: NJD077070811 (Map Enclosed - See Figure 1)

CHEMICAL DISCHARGED:

Ethylene Glycol CAS Number: 107-21-1 QUANTITY DISCHARGED:

Approximately 1 pint of ethylene glycol was discharged.

This value is a conservative estimate based on the residual quantity of ethylene glycol observed on the floor.

DATE/TIME DISCHARGE BEGAN:

Unknown.

However, Operations personnel are stationed at the intake structure around the clock and periodically walk by the area of the spill.

DATE/TIME DISCHARGE ENDED:

April 29, 1993 0830 Hours DATE/TIME DISCHARGE DISCOVERED:

April 29, 1993 0830 Hours DATE/TIME DISCHARGE REPORTED:

April 29, 1993 0837 Hours

{To NJDEPE Hotline)

MEASURES TAKEN TO CONTAIN, CLEANUP AND REMOVE THE DISCHARGE:

Upon discovery, operations personnel placed a drip bag under the leak to route any additional leakage to a 55 gallon drum until the system could be drained to prevent further leaks.

Site Services personnel cleaned up the affected area with absorbent material.

The used absorbent will be disposed of in accordance with Federal, State and Local regulations. The cleanup and disposal costs associated with this discharge were approximately

$400.00 dollars.*

ATTACHMENT 2 (continued)

DISCHARGE CONFIRMATION REPORT CASE No. 93-04-29-0837-37 CORRECTIVE MEASURES:

The Operations Department, responsible for operation of the intake structure and equipment, isolated and drained the system, and applied blocking tags to the appropriate equipment to prevent additional leakage.

Work order, No. 930427205, has been issued to the Maintenance Department to repair the leaking expansion tank.

The Maintenance Department has ordered and is awaiting delivery of the new tank.

The system will not be r~turned to service until the repairs to the expansion tank and the leaking valve have been ~ompleted.

INDIVIDUAL INVOLVED IN CONTAINMENT/CLEANUP:

Cleanup activities associated with the release of the ethylene glycol, consisting of installation of the drip bag and draining the system, were conducted by Operations personnel.

Site Services personnel are responsible for cleaning up the residual ethylene glycol and disposal of the used pads.

These individual(s) are:

M. D. Gwirtz Senior Nuclear Shift Supervisor Public Service Electric and Gas Company Salem Generating Station P. o. Box 236, M/C SOl Hancocks Bridge, New Jersey 08038 (609) 339-5200 J. G. sterner Yard Supervisor Site Services Maintenance Public Service Electric and Gas Company Nuclear Department P. o. Box 236, M/C N34 Hancocks Bridge, New Jersey 08038 (609) 339-5338

ATTACHMENT 2 (continued)

DISCHARGE CONFIRMATION REPORT CASE No. 93-04-29-0837-37 TYPE, QUANTITY, LOCATION AND DATE OF SAMPLES:

No samples were collected of this discharge.

However, based upon a worst case scenario in which all ethylene glycol observed leaked to the intake within five (5) minutes, and was dispersed through only one outfall, the estimated concentration of ethylene glycol in the discharge is 0.06 mg/l. Information on this characterization may be obtained from:

D. Hurka -

Lead Engineer Licensing and Regulation Public Service Electric and Gas Nuclear Department P. o. Box 236, M/C N21 Hancocks Bridge, New Jersey 08038 (609) 339-1275 INDIVIDUAL CONDUCTING ANALYSIS:

Not applicable to this discharge.

QUALITY ASSURANCE PROCEDURES:

Not applicable to this discharge.

SAMPLE METHODOLOGY:

Not applicable to this discharge.

RATIONALE FOR SAMPLING LOCATION:

Not applicable to this discharge.

FINANCIAL RESPONSIBILITY:

PSE&G satisfies the requirements for self-insurance established by N.J.A.C. 7:1E-4.5(g) and included appropriate documentation of this in its Discharge Cleanup and Removal (DCR) Plan as required by N.J.A.C. 7:1E-4.4(a)9

  • _J

CERTIFICATION State of New Jersey:

SS County of Salem I certify under penalty of law that the information provided in this document is true, accurate and complete.

I am aware that there are significant civil and criminal penalties, including fines or imprisonment or both, for submitting false, inaccurate or incomplete information.

sworn a~ subscribed before me on thisa ~ i:A day of YnC1.A#'

~Lw~aiM-NOaz:y Pil' KIMBERLY JO BROWN NOTARY. P~BllC.OF NEW JERSEY My Comm;ss1on Expires April 21, 199&

I 199J.

FIGURE 1

OPS~G~~~~

SURVEYS Comp.1ny MAPPING ARTIFICIAL ISLAND

--...,................ _j a --ii i

==a a

a 0

a I

/

-=----*.. J (

I~

/-...,

r-......

I

/

."'-/ '

. /

(

. /

I I

J /

,,,',\\

~~-=--:,-:.-:.':.' ~~--,:,:.;:-..r.::.;.

)I I

~ * * * * " " * " " * * * * * * * * "

~

/

\\,

1*