NPDES Noncompliance Notification:On 911103,approx 5 Gallons of Lubricating Oil Discharged to Delaware River Through Circulating Water Sys Outfall Dsn 484.Caused by Leaking Valve.Valve Tightened & Discharge Terminated
ML18096A369
Person / Time
Site: Salem  
Issue date: 12/03/1991
From: Vondra C
Public Service Enterprise Group
To:
NEW JERSEY, STATE OF
References
NLR-E91294, NUDOCS 9112100240
Download: ML18096A369 (10)


Text

Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038 Nuclear Department CERTIFIED MAIL RETURN RECEIPT REQUESTED Bureau of Discharge Prevention OE C o 3 1991 NLR-E91294 NJ Department of Environmental Protection and Energy 401 East State Street CN-027 Trenton, New Jersey 08625-0027

Dear sirs:

OIL DISCHARGE CONFIRMATION REPORT PUBLIC SERVICE ELECTRIC AND GAS (PSE&G) COMPANY SALEM GENERATING *STATION CASE #91-11-03-1734-02 As per the requirements of NJAC 7:1E-5.8, PSE&G has prepared the attached report confirming the discharge of approximately five (5) gallons of lubricating oil to the Delaware River through a circulating water system outfall, DSN 484.

The discharge, which occurred at the above facility on November 3, 1991, did not cause any injuries.

The discharge was reported to the New Jersey Department of Environmental Protection and Energy (NJDEPE) Hotline (Operator No. 23) and the National Response Center (Case No. 94844).

In addition, the Nuclear Regulatory Commission (NRC), was notified as required under 10 CFR 50.72, Significant Events.

PSE&G, in making this notification, believes that it acted in accordance with the intent of NJAC 7:1E, Subchapter 5, which requires all major facilities to notify the NJDEPE of discharges of petroleum and other potentially hazardous substances in any concentration.

As a result of this discharge, PSE&G has conducted a follow-up investigation of the incident, has repaired the equipment responsible for the discharge and has taken measures to prevent similar discharges in the future.

CSC:i15

,*~iT-(2 f. c~~:i2~1~:,_,~i+2~:~~: ----~

'PDR ADOCK 05000272 S

PDR

NJ DE PE NLR-E91294 2

Should you have any questions concerning the information contained herein, or require additional information, please contact Mr. Patrick McCabe of Licensing and Regulation at (609) jJ9-124*5.

Attachment

~ndr~

General Manager -

Salem Operations

/

  • \\;,9]

NJ DE PE NLR-E91294 3

c NJ Department of Environmental Protection and Energy Southern Bureau of Regional Enforcement 20 E. Clementon Road Gibbsboro, New Jersey 08026 Attention:

Mr. William Dunphee United States Nuclear Regulatory Commission Document Control Desk Washington, D.C.

20555 Salem County Department of Health 98 Market Street Salem, New Jersey 08079 Attention:

Mr. James Warner United States Coast Guard 1 Washington Avenue Philadelphia, PA 19147

  • ...,9\\

ATTACHMENT 1 DISCHARGE CONFIRMATION REPORT -

SUPPLEMENTAL INFORMATION RELATED TO DISCHARGE OF LUBRICATING OIL FROM SALEM GENERATING STATION -

CASE # 91-11-03-1734-02 INDIVIDUAL REPORTING DISCHARGE:

Senior Nuclear Shift Supervisor Public Service Electric and Gas Company Salem Generating Station P. 0. Box 236, M/C SOl Hancocks Bridge, New Jersey 08038 (609) 339-S200 INDIVIDUAL SUBMITTING CONFIRMATION REPORT:

General Manager -

Salem Operations Public Service Electric and Gas Company Salem Generating Station P. 0. Box 236, M/C SOS Hancocks Bridge, New Jersey 08038 (609) 339-2900 FACILITY OWNER/OPERATOR:

Public Service Electric and Gas Company P. 0. Box S70-17G Newark, New Jersey 07101-0S70 (201) 430-S868 INDIVIDUAL(S) RESPONSIBLE FOR THE DISCHARGE:

General Manager -

Salem Operations Public Service Electric and Gas Salem Generating station P. o. Box 236, M/C sos Hancocks Bridge, New Jersey 08038 (609) 339-2900 DISCHARGE SOURCE:

Salem Generating Station Circulating Water Intake Structure Traveling Screen (21A) Oil Bath Drain Valve Approximately S gallons of lubricating oil was released through a drain valve on an oil bath used to lubricate the 21A traveling screen at the circulating water system intake structure.

The oil dripped to the floor and subsequently into one of the six circulating water intake bays.

Circulating water is pumped from each intake bay to the facility's once-through non-contact cooling water system at

ATTACHMENT 1 (continued)

DISCHARGE CONFIRMATION REPORT -

SUPPLEMENTAL INFORMATION RELATED TO DISCHARGE OF LUBRICATING OIL FROM SALEM GENERATING STATION -

CASE # 91-11-03-1734-02 a rate of approximately 370,000 gallons per minute before being returned to the Delaware River approximately 500 feet offshore.

The discharge occurred through DSN 484 which is one of the six circulating water system outfalls regulated under the facility's New Jersey Pollutant Discharge Elimination System (NJPDES) Permit No. NJ0005622.

The leaking valve was discovered during a routine system walkdown at 1725 hours0.02 days <br />0.479 hours <br />0.00285 weeks <br />6.563625e-4 months <br />.

The valve was tightened, terminating the discharge at 1728 hours0.02 days <br />0.48 hours <br />0.00286 weeks <br />6.57504e-4 months <br />.

The cause of the leaking valve appeared to be vibration caused by operation of the traveling screens.

DISCHARGE LOCATION:

Salem Generating Station End of Buttonwood Road Block #: 26 Lot #: 4.01 Municipality: Hancocks Bridge County: Salem Zip Code: 08038 Tax #: 22-1212-800*

EPA ID #: NJD077070811 (Map Enclosed -

See Figures 1 and 2)

CHEMICAL DISCHARGED:

Lubricating Oil CAS Number: 8002-05-9 (Per New Jersey Worker and Community Right To Know)

QUANTITY DISCHARGED:

Approximately 5 gallons.

This value is a conservative estimate based on the quantity of oil needed to refill the bath.

This value does not account for oil recovered from the floor or applied to the traveling screen chain.

DATE/TIME DISCHARGE BEGAN:

Unknown.

However, Operations personnel are stationed at the intake structure around the clock and periodically walk by the area of the spill.

DATE/TIME DISCHARGE ENDED:

November 3, 1991 1728 Hours DATE/TIME DISCHARGE DISCOVERED:

November 3, 1991 1725 Hours DATE/TIME DISCHARGE REPORTED:

November 3, 1991 1734 Hours (To NJDEPE Hotline)

ATTACHMENT 1 (continued)

DISCHARGE CONFIRMATION REPORT -

SUPPLEMENTAL INFORMATION RELATED TO DISCHARGE OF LUBRICATING OIL FROM SALEM GENERATING STATION -

CASE # 91-11-03-1734-02 MEASURES TAKEN TO CONTAIN, CLEANUP AND REMOVE THE DISCHARGE:

Upon discovery, the leaking valve was tightened, terminating the discharge.

Absorbant pads were immediately placed on the floor in the spill area to recover any remaining oil.

The pads were then placed into a 55 gallon drum for disposal as hazardous waste.

CORRECTIVE MEASURES:

The Operations Department, responsible for operation and maintenance of the intake structure and equipment, has placed caps on the drain valves for each of the traveling screen oil baths to prevent future leaks.

INDIVIDUAL INVOLVED IN CONTAINMENT/CLEANUP:

Cleanup activities associated with the release of the lubricating oil, consisting of tightening the drain valve and placing absorbant pads on the floor in the area of the spill, were conducted by Operations personnel.

Site Services personnel were responsible for disposal of the used pads as hazardous waste.

These individual(s) are:

Senior Nuclear Shift Supervisor Public Service Electric and Gas Company Salem Generating Station P. O. Box 236, M/C SOl Hancocks Bridge, New Jersey 08038 (609) 339-5200 Yard Supervisor Site Services Maintenance Public Service Electric and Gas Company Nuclear Department P. O. Box 236, M/C N34 Hancocks Bridge, New Jersey 08038 (609) 339-5338

ATTACHMENT 1 (continued)

DISCHARGE CONFIRMATION REPORT -

SUPPLEMENTAL INFORMATION RELATED TO DISCHARGE OF LUBRICATING OIL FROM SALEM GENERATING STATION -

CASE # 91-11-03-1734-02 TYPE, QUANTITY, LOCATION AND DATE OF SAMPLES:

No samples were collected of this discharge.

However, based upon a worst case scenario in which all oil leaked from the drain valve to, the intake bay within one (1) minute, and the oil was dispersed through only one outfall, the estimated concentration of petroleum hydrocarbons in the discharge is 13.5 mg/l.

This is below the maximum daily discharge limitation of 15 mg/l imposed by the NJDEPE for similar discharges.

Information on this characterization may be obtained from:

Engineer Licensing and Regulation Public Service Electric and Gas Nuclear Department P. O. Box 236, M/C N21 Hancocks Bridge, New Jersey 08038 (609) 339-1245 INDIVIDUAL CONDUCTING ANALYSIS*:

Not applicable to this discharge.

QUALITY ASSURANCE PROCEDURES:

Not applicable to this discharge.

SAMPLE METHODOLOGY:

Not applicable to this discharge.

RATIONALE FOR SAMPLING LOCATION:

Not applicable to this discharge.

FINANCIAL RESPONSIBILITY:

Financial responsibility is provided through Excess Liability Insurance.

This insurance is through the following carrier:

Associated Electric and Gas Services, Inc.

Harborside Financial Center 700 Plaza Two Jersey City, New Jersey 07311-3944 Policy #:

Effective Date:

X0015A1A91 8/1/91

  • ---J l _____ ~

.. --::=====-=-==*-*~*

\\

oJl

\\..,

\\

D

\\

\\

  • O D
  • O DISCHARGE LOCATION H

ra 0

0 0.

O*

a

  • D O*

O*

O*

r l !

~-

l l [*-

1 l!I

,/,~:

FIGURE 1 SALEM GENERATING STATION GENERAL SITE MAP

llCI. I ----+.--- llCI. 8 SECTION DISCHARGE LOCATION FIGURE 2 SALEM GENERATING STATION CIRCULATING WATER SYSTEM INTAKE STRUCTURE DETAILS

CERTIFICATION State of New Jersey:

SS County of Salem I certify under penalty of law that the information provided J

in this document is true, accurate and complete.

I 1 am aware that there are significant *civil and criminal penalties, including fines or imprisonment or both, for submitting false, inaccurate or incomplete information.

Sworn and subscribed b~ore m~