ML18096A527

From kanterella
Jump to navigation Jump to search
NPDES Noncompliance Notification:On 920124,approx 500 Gallons of Oil,Contaminated W/Rainwater,Escaped from Spare Transformer Secondary Containment Area.Followup Investigation Underway.Affected Area Cleaned
ML18096A527
Person / Time
Site: Salem  PSEG icon.png
Issue date: 02/18/1992
From: Munzenmaier C
Public Service Enterprise Group
To:
NEW JERSEY, STATE OF
References
NLR-E92035, NUDOCS 9202250228
Download: ML18096A527 (12)


Text

J PS~G*

Public Service_ Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038 Nuclear Department CERTIFIED MAIL RETURN RECEIPT REQUESTED Article Number:

P632 876 228 FEB 1 8 1992

Discharge Confirmation Report

Dear Sirs:

DISCHARGE OF WATER/TRANSFORMER OIL PUBLIC SERVICE ELECTRIC AND GAS (PSE&G)

SALEM GENERATING STATION (CASE #92-01-24-1059-47) -

30 DAY CONFIRMATION REPORT As per the requirements of NJAC 7:1E-5.8, PSE&G has prepared the attached discharge confirmation report.

The discharge, which occurred at the above facility on January 24, 1992, occurred entirely within PSE&G property and no injuries resulted.

As there is no "Reportable Quantity" (RQ) for the discharged material, no notification of the release was reported to any agency other than the New Jersey Department of Environmental Protection and Energy (NJDEPE) and the Nuclear Regulatory Commission (NRC), as required under 10CFR50.72, Significant Events.

PSE&G believes it acted in accordance with the intent of NJAC 7:1E, Subchapter 5, which requires all major facilities to notify the NJDEPE of discharges of petroleum and other potentially hazardous substances in any concentration.

_:._c__-"-

0

' ~-2

-2

-':':-0

  • , -9=2~0;.:-;2~11.fa;---~\\

9~0225 05000272 PDR ADOCK PDR s

tY\\ I

\\

NJ DE PE NLR-E92035 2

FEB x 1992 As a result of this discharge, PSE&G has conducted a follow-up investigation of the incident and has cleaned the affected area and secondary containment involved.

Should you have any questions concerning the information contained herein, or require additional information, please contact Mr. Paul Behrens of Licensing and Regulation at (609) 339-1577.

Attachment Sincerely, fJ/lu~\\~v C. Munzenmaier General Manager -

Nuclear Services

NJ DE PE NLR-E92035 3

FEB I 8 1992 C

New Jersey Department of Environmental Protection and Energy Division of Environmental Quality Bureau of Communications and Support Services CN 411 Trenton, New Jersey 08625-0411 New Jersey Department of Environmental Protection and Energy Off ice of Enforcement Policy Southern Bureau of Water and Hazardous Waste 20 E. Clementon Road Gibbsboro, New Jersey 08026 Attention:

Mr. William Dunphee United States Nuclear Regulatory Commission Document Control Desk Washington, D.C., 20555 Salem County Department of Health 98 Market Street Salem, New Jersey 08079 Attention:

Mr. James Warner

ATTACHMENT 1 DISCHARGE CONFIRMATION REPORT -

SUPPLEMENTAL INFORMATION RELATED TO DISCHARGE OF OIL/WATER FROM ARTIFICIAL ISLAND -

CASE #92-01-24-1059-47 INDIVIDUAL REPORTING DISCHARGE:

Senior Nuclear Shift Supervisor Public service Electric and Gas Salem Generating Station P. O. Box 236, M/C SOl Hancocks Bridge, New Jersey 08038 (609) 339-5200 INDIVIDUAL SUBMITTING CONFIRMATION REPORT:

General Manager - Nuclear Services Public Service Electric and Gas Nuclear Department P. 0. Box 236, M/C N35 Hancocks Bridge,.New Jersey 08038 (609) 339-2300 FACILITY OWNER/OPERATOR:

Public Service Electric and Gas Co.

P. O. Box 570-17G Newark, New Jersey 07101-0570 INDIVIDUAL(S) RESPONSIBLE FOR THE DISCHARGE:

General Manager - Nuclear Services Public Service Electric and Gas Nuclear Department P. 0. Box 236, M/C N35 Hancocks Bridge, New Jersey 08038 DISCHARGE SOURCE:

Leak from spare transformer with subsequent discharge from secondary containment area.

Approximately 500 gallons of oil contaminated rainwater escaped from a spare transformer secondary containment area on to an area adjacent to and within the confines of the owner controlled area at this facility.

The event was discovered during a routine check of the area and appropriate response personnel notified.

ATTACHMENT 1 (continued)

DISCHARGE CONFIRMATION REPORT -

SUPPLEMENTAL INFORMATION RELATED TO DISCHARGE OF OIL/WATER FROM ARTIFICIAL ISLAND -

CASE #92-01-24-1059-47 This discharge occurred after approximately 500 gallons of a mixture of accumulated rainwater (3500 gallons) contaminated with a small amount of transformer oil (5 gallons) escaped from a spare transformer storage area.

The oil apparently leaked from one of the stored spare transformers when a thermocouple well cracked due to the freezing temperatures.

A maintenance technician making a routine inspection observed the water on the ground and noticed a film of oil in the secondary containment.

The technician informed the Senior Nuclear Shift Supervisor who requested that Environmental Licensing personnel make an on scene determination as to the possibility of a discharge.

The responding Licensing Engineer determined that a discharge had probably occurred and the notification that the discharge potentially contained trace amounts of transformer oil was appropriate.

This information was then reported as a discharge of approximately 500 gallons of an oil/water mixture.

ATTACHMENT 1 (continued)

DISCHARGE CONFIRMATION REPORT -

SUPPLEMENTAL INFORMATION RELATED TO DISCHARGE OF OIL/WATER FROM ARTIFICIAL ISLAND -

CASE #92-01-24-1059-47 DISCHARGE LOCATION:

Salem Generating Station End of Buttonwood Road Block#: 26 Lot#: 5 Municipality: Hancocks Bridge County: Salem County Zip Code: 08038 Tax #: 22-1212-800 EPA ID#: NJD077070811 (Map*Enclosed)

CHEMICAL DISCHARGED:

Oil/Water mixture containing trace amounts of transformer oil (Non-PCB)

  • QUANTITY DISCHARGED: Approximately 500 gallons DATE/TIME DISCHARGE BEGAN: Unknown DATE/TIME DISCHARGE ENDED: January 24, 1992 1030 Hours DATE/TIME DISCHARGE DISCOVERED: January 24, 1992 1000 Hours DATE/TIME DISCHARGE REPORTED:

January 24, 1992 1059 Hours To NJDEPE Hotline JUSTIFICATION FOR DELAY IN 15 MINUTE NOTIFICATION:

Personnel responded immediately to determine the status of the leak and upon determination, phoned the notification into the Nuclear Shift Supervisor from the field location.

,~.,--------~-----~-.~~-------.

ATTACHMENT 1 (continued)

DISCHARGE CONFIRMATION REPORT -

SUPPLEMENTAL INFORMATION RELATED TO DISCHARGE OF OIL/WATER FROM ARTIFICIAL ISLAND -

CASE #92-01-24-1059-47 MEASURES TAKEN TO CONTAIN, CLEANUP AND REMOVE THE DISCHARGE:

The time the discharge from the secondary containment began is unknown.

Upon discovery, immediate notification was made to on site emergency response personnel.

Initially believed to be non-reportable, efforts were undertaken to stop the discharge and mitigate any potential environmental impact.

Evidence of any discharge was masked by the fact that recent rains had made it impossible to distinguish between precipitation wetted areas and areas of potential discharge from the secondary containment.

Estimates of liquid discharged from the containment are based upon standing water down gradient of the containment rather than actual measured volumes.

As a result of the response, all liquid in the secondary containment was collected in a vacuum truck and any oily residue absorbed for disposal as solid spill debris.

The collected liquid was then discharged to an onsite facility oil/water separator (NJPDES permit NJ0005622, DSN 489B).

The top two (2) inches of soil in the area immediately adjacent to and down gradient (west) of the containment was physically removed and drummed for disposal to ensure that no traces of oil residue remained.

CORRECTIVE MEASURES:

This secondary containment is slated for upgrade as part of the DPCC/DCR regulatory implementation and has been assigned a high priority for funding as a result of this incident.

While a schedule for commencement of any modifications has not been published, it is anticipated that work will commence in 1992.

Additional engineering and design work must be completed prior to any schedule publication.

ATTACHMENT 1 (continued)

DISCHARGE CONFIRMATION REPORT -

SUPPLEMENTAL INFORMATION RELATED TO DISCHARGE OF OIL/WATER FROM ARTIFICIAL ISLAND -

CASE #92-01-24-1059-47 INDIVIDUAL INVOLVED IN CONTAINMENT/CLEANUP:

Cleanup activities were conducted associated with the discharge of the oil contaminated water.

On-site personnel with contaminated soil disposal responsibilities were consulted for this discharge cleanup.

These individual(s) are:

Yard Supervisor Site Services Maintenance Public Service Electric and Gas Nuclear Department P. 0. Box 236, M/C N34 Hancocks Bridge, New Jersey 08038 (609) 339-5338 Engineer Licensing and Regulation Public Service Electric and Gas Nuclear Department P. 0. Box 236, M/C N21 Hancocks Bridge, New Jersey 08038 (609) 339-1577 TYPE, QUANTITY, LOCATION AND DATE OF SAMPLES:

No laboratory data was collected for this discharge.

Information regarding the chemical nature of this material may be obtained from the following individuals:

Engineer Licensing and Regulation Public Service Electric and Gas Nuclear Department P. 0. Box 236, M/C N21 Hancocks Bridge, New Jersey 08038 (609) 339-1577

ATTACHMENT 1 (continued)

.DISCHARGE CONFIRMATION REPORT -

SUPPLEMENTAL INFORMATION RELATED TO DISCHARGE OF OIL/WATER FROM ARTIFICIAL ISLAND -

CASE #92-01-24-1059-47 INDIVIDUAL CONDUCTING ANALYSIS:

Not applicable to this discharge.

QUALITY ASSURANCE PROCEDURES:

Not applicable to this discharge.

SAMPLE METHODOLOGY:

Not applicable to this discharge.

RATIONALE FOR SAMPLING LOCATION:

Not applicable to this discharge.

FINANCIAL RESPONSIBILITY:

Financial responsibility is provided through Excess Liability Insurance.

This insurance is through the following carrier:

Associated Electric and Gas Services, Inc.

Harborside Financial Center 700 Plaza Two Jersey City, New Jersey 07311-3944 Policy #:

Effective Date:

X0015A1A91 8/1/91

CERTIFICATION State of New Jersey:

SS County of Salem I certify under penalty of law that the information provided in this document is true, accurate and complete.

I am aware that there are significant civil and criminal penalties, including fines or imprisonment or both, for submitting false, inaccurate or incomplete information.

Sworn and subscribed before me on this / (

day of ~ 41~ ' 1992.

ELiZABETH J. KIDD Notary Public of New Jersey My Commission Exoires April 25, 1995

ft PS~G Public Service

\\~.

li!l Elecirlc & G*a

"-!.'5" Company SURVEYS MAPPING ARTIFICIAL

~ISLAND

~o o a

a 0

  • -*~***--**--

~~~-::,-=..-::. -::.~'"'~\\.:-.:.:---.:-.::.:

II 1 ,,

11

~

\\ _

X17.2


~---;

~1 ll.6

\\ "

X1s.6 17.4 x

X17,2 16.8 x

\\

(

I

____________________________________ :_ Qigr,PILES,

  • v v x

16.9 c(T>J-...,._.1--.J see.. f"-?f-A~C\\.

X16.9 Xll.9 Xn.7

-12.s X15,1 IS

-~'"---- - - - -

--- ------- 12.5 IS