MPR-4153, Rev. 1, Seabrook Station - Approach for Estimating through-Thickness Expansion from Alkali-Silica Reaction
ML15183A020
Person / Time
Site: Seabrook 
Issue date: 06/30/2015
From: Bagley C
MPR Associates
To:
NextEra Energy Seabrook, Office of Nuclear Reactor Regulation
References
SBK-L-15107, TAC ME4028 MPR-4153, Rev. 1
Download: ML15183A020 (93)


Text

Enclosure 3 to SBK-L-15107 MPR-4153 Seabrook Station Approach for Estimating Through-Thickness Expansion from Alkali-Silica Reaction MPR Associates, Inc., Alexandria, VA, 2015 (Non-Proprietary)

W MPR MPR-4153 Revision 1 (Seabrook FP # 100918)

June 2015 Seabrook Station - Approach for Determining Through-Thickness Expansion from Alkali-Silica Reaction QUALITY ASSURANCE DOCUMENT This document has been prepared, reviewed, and approved in accordance with the Quality Assurance requirements of 10CFR50 Appendix B and/or ASME NQA-1, as specified in the MPR Nuclear Quality Assurance Program.

Prepared for NextEra Energy Seabrook, LLC P.O. Box 300, Lafayette Rd., Seabrook, NH 03874 Page 1 of 88

  • MPR Seabrook Station - Approach for Determining Through-Thickness Expansion from Alkali-Silica Reaction NPR-4153 Revision 1 (Seabrook FP # 100918)

June 2015 QUALITY ASSURANCE DOCUMENT This document has been prepared, reviewed, and approved in accordance with the Quality Assurance requirements of 1 OCFR50 Appendix B and/or ASME NQA-1, as specified in the MPR Nuclear Quality Assurance Program.

Prepared by: C.WL. B C. W. Baglef' Reviewed by: 2 U1&w2 J6hn W. Simons Approved by: Ja!Z-

-oney Additional Contributors K. Mulvaney D. Bergquist A. Card M. Saitta R. Vayda Prepared for NextEra Energy Seabrook, LLC P.O. Box 300, Lafayette Rd., Seabrook, NH 03874 320 KING STREET ALEXANDRIA, VA 22314-3230 703-519-0200 FAX: 703-519-0224 www.mpr.com Page 2 of 88

RECORD OF REVISIONS Revision Affected Pages Description 0

1 All Body of Report, Appendix A Initial Issue Included corrected data for expansion of FSEL test specimens in the through-thickness direction. Also made minor editorial changes throughout the body of the report.

MPR-4153 Revision 1 iii Page 3 of 88

Executive Summary This report recommends a methodology for determining the extent of through-thickness expansion of reinforced concrete structural members at Seabrook Station. Quantifying through-thickness expansion will enable NextEra Energy to apply the results of the ongoing structural testing programs to Seabrook Station based on the condition of existing plant structures.

Data from the structural testing programs have shown that expansion in the in-plane direction plateaus at low expansion levels, while expansion in the through-thickness direction continues to increase. Accordingly, the test programs will provide results correlating structural performance to expansion in the through-thickness direction.

NextEra plans to install instruments in concrete structures at Seabrook Station to measure expansion in the through-thickness direction (i.e., extensometers). This approach will enable measuring expansion for a given concrete structural member from the time the extensometer is installed. To calculate total expansion, NextEra will need to determine expansion from original construction until the time the extensometer is installed.

MPR recommends the following approach for determining total ASR-induced through-thickness expansion at each instrumented location at Seabrook Station. The recommended method determines the pre-instrument expansion based on the reduction in modulus of elasticity.

1.

Determine the current elastic modulus of the concrete by material property testing of cores removed from the structure. Elastic modulus testing requires companion compressive strength testing, so MPR recommends obtaining a minimum of four test specimens at each proposed monitoring location. Two test specimens are for compressive strength testing and two test specimens are for subsequent elastic modulus testing.

2.

Establish the original elastic modulus of the concrete by either (1) using the ACI 318-71 correlation to calculate elastic modulus from 28-day compressive strength records or (2) obtaining cores from representative ASR-free locations and testing for elastic modulus.

3.

Calculate the reduction in elastic modulus by taking the ratio of the test result from the ASR-affected area to the original elastic modulus.

4.

Determine through-thickness expansion from original construction to the time the extensometer is installed using the correlation developed in this report. The correlation relates reduction in elastic modulus with measured expansion from beam specimens used during the large-scale ASR structural testing programs.

5.

Calculate total expansion levels by adding the extensometer measurements to the expansion at the time of instrument installation.

MPR-4153 iv Revision 1 Page 4 of 88

Contents Title Page..........................................................................................................................................

i Signature Page.................................................................................................................................

ii Record of Revisions........................................................................................................................

iii Executive Summ ary........................................................................................................................

iv Contents...........................................................................................................................................

v Figures............................................................................................................................................

vi 1

Introduction.....................................................................................................

1-1 1.1 Purpose.....................................................................................................................

1-1 1.2 Background...............................................................................................................

1-1 2

Expansion Behavior in Test Specimens....................................................

2-1 2.1 Overview of Test Specim ens....................................................................................

2-1 2.2 Expansion in Reinforced Concrete...........................................................................

2-3 2.3 Implications for M onitoring A SR at Seabrook.........................................................

2-5 3

Determining Pre-instrument Expansion from Elastic Modulus.................

3-1 3.1 M aterial Properties of Test Specim ens.....................................................................

3-1 3.2 Development of Correlation between Modulus and Expansion...............................

3-3 3.3 Establishing Original Elastic M odulus at Seabrook.................................................

3-5 4

Recom m ended Approach.............................................................................

4-1 4.1 Overview of Approach.............................................................................................

4-1 4.2 Uncertainty...............................................................................................................

4-1 5

References..........................................................

5-1 A

Correlation Between Expansion and Elastic Modulus..............................

A-1 B

Evaluation of ACI Equation for Elastic Modulus.........................................

B-1 C

Compressive Strength of Concrete at Seabrook Station...........................

C-1 MPR-4153 v

Revision 1 Page 5 of 88

Figures Figure 1-1. A SR Expansion M echanism....................................................................................

1-1 Figure 2-1. Example Reinforcement Pattern in Shear Test Specimen (Reference 7.3)......

2-1 Figure 2-2. Plan View of Embedded Rods (Reference 7.6)

(Embedded Reinforcement with Terminators also Shown)......................................

2-2 Figure 2-3. Elevation View of Embedded Expansion Rods (Reference 7.6)

(Embedded Reinforcement with Terminators also Shown)......................................

2-2 Figure 2-4. Expansion Trends in Example Test Specimen.........................................................

2-3 Figure 2-5. Crack in Through-Thickness Direction of Example Test Specimen........................ 2-4 Figure 3-1. Material Properties as a Function of Expansion from Test Data (Reference 13)..... 3-2 Figure 3-2. Splitting Tensile Strength as a Function of Expansion from Test Data (R eference 13) 3-3 Figure 3-3. Elastic Modulus as a Function of Expansion from Test Data (Reference 13).......... 3-4 Figure 3-4. Comparison of Derived Relationship with Literature Data (Reference 13)............. 3-5 Figure 3-5. Comparison of Test Data to ACT Equation (Reference 18)......................................

3-6 TPR-4153 vi Revision 1 Page 6 of 88

1 Introduction 1.1 PURPOSE This report recommends a methodology for determining the extent of through-thickness expansion of reinforced concrete structural members that are affected by alkali-silica reaction (ASR) at Seabrook Station. Quantifying through-thickness expansion of existing plant structures is necessary to relate the extent of ASR in a given structure to the results of the structural testing programs at Ferguson Structural Engineering Laboratory (FSEL).

1.2 BACKGROUND

1.2.1 Overview of Alkali-Silica Reaction ASR occurs in concrete when reactive silica in the aggregate combines with alkali ions (Na+, K+)

in the pore solution. The reaction produces a gel that expands as it absorbs moisture, exerting tensile stress on the surrounding concrete and resulting in cracking. Typical cracking caused by ASR is described as "pattern" or "map" cracking and is usually accompanied by dark staining adjacent to the cracks. Figure 1-1 provides an illustration of this process.

alkali cement +

expansive gel cracking of the reactive aggregate aggregate and paste Figure 1-1. ASR Expansion Mechanism Several publications indicate that the cracking may degrade the material properties of the concrete (References 1, 2, and 3). The concrete properties most rapidly and severely affected are the elastic modulus and tensile strength. Compressive strength is also affected, but less rapidly and less severely.

MPR-4153 Revision I 1-1 Page 7 of 88

While development of ASR causes a reduction in material properties, there is not necessarily a corresponding decrease in structural performance. As discussed in previous MPR reports on ASR at Seabrook Station and the approach for the FSEL test program (References 4 and 5),

cores removed from a reinforced ASR-affected structure are no longer confined by the reinforcement and do not represent the structural context of the in-situ condition. Therefore, material properties obtained from cores have limited applicability for evaluating the capacity of a structure.

1.2.2 ASR at Seabrook Station NextEra Energy has identified ASR in multiple safety-related, reinforced concrete structures at Seabrook Station (Reference 6). To evaluate this condition, MPR performed a structural assessment (Reference 4) of selected ASR-affected structures. Based on the low level of observed cracking and the apparent slow rate of change, MPR concluded that these structures are suitable for continued service for at least an interim period (i.e., at least several years).

A follow-up evaluation will assess the long-term adequacy of the concrete structures at Seabrook Station. This evaluation will incorporate the results of large-scale test programs currently being performed at FSEL using test specimens that were specifically designed and fabricated to represent reinforced concrete at Seabrook Station.

1.2.3 Test Programs at FSEL MPR is sponsoring four test programs at FSEL to support NextEra's efforts to resolve the ASR issue at Seabrook Station. Three of the test programs focus on the structural performance data necessary to complete the final structural assessment of ASR-affected structures. The fourth test program evaluates instruments for monitoring expansion of Seabrook Station. A brief overview of each program is provided below.

Anchor Test Program-This program evaluates the impact of ASR on performance of anchors installed in the concrete. Tests will be performed at multiple levels of ASR degradation.

Shear Test Program-This program evaluates the impact of ASR on shear performance of reinforced concrete beams. The test scope includes tests at multiple levels of ASR degradation and, if necessary, tests of retrofits for restoring the shear capacity.

Reinforcement Anchorage Test Program--This program evaluates the impact of ASR on reinforcement anchorage using beams that have reinforcement lap splices. The test scope includes tests at multiple levels of ASR degradation and, if necessary, tests of retrofits.

Instrumentation Test Program-This program evaluates instruments for the measurement of through-thickness expansion. Insights gained from this program will be used to select which instrument to use at Seabrook Station and refine installation procedures.

As part of the test programs, FSEL monitors development of ASR. For the shear, reinforcement anchorage, and instrumentation test programs, FSEL both measures expansion of the test specimens and determines the effect on material properties of concrete, which are related to ASR MPR-4153 1-2 Revision I Page 8 of 88

development. Using this information, this report recommends a methodology for determining the extent of ASR-induced expansion at Seabrook Station. (Similar data were not obtained as part of the Anchor Test Program, so this report does not utilize expansion data from the Anchor Test Program.) Quantifying the extent of ASR development will enable comparison of the test data to the condition of existing structures at Seabrook Station.

Testing is being conducted under FSEL's project-specific quality system manual with quality assurance oversight from MPR. MPR is commercially dedicating the testing services performed by FSEL. Commercial grade dedication of services from the test program relevant for this report is documented in References 22, 23, and 24.

MPR-4153 1-3 Revision I Page 9 of 88

2 Expansion Behavior in Test Specimens This section discusses expansion behavior observed in the test specimens thus far in the test program and the implications for monitoring ASR development in structures at Seabrook Station.

An overview of test specimen design is included to provide context for understanding the observed expansion behavior.

2.1 OVERVIEW OF TEST SPECIMENS 2.1.1 Reinforcement Pattern

-The-test program specimens are large, reinforced-concrete beams. -Most test specimens are

  • feetj inches long,fl inches wide, andfS inches thick (References 7.1 and 7.2). The test specimens were designed to represent the configuration of reinforced concrete structural members at Seabrook Station. In particular, the test area of each specimen includes two-dimensional reinforcement mats on two opposite faces, which is the same reinforcement detailing used for most reinforced concrete buildings at Seabrook Station (e.g., walls that have reinforcement mats on the interior and exterior faces). Figure 2-1 provides a schematic of the reinforcement pattern in an example shear test specimen (Reference 7.3). The reinforcement anchorage and instrumentation test specimens have some design differences (e.g.,

but all test specimens contain two-dimensional reinforcement mats consistent with the example in Figure 2-1 (References 7.4 and 7.5).

Figure 2-1. Example Reinforcement Pattern in Shear Test Specimen (Reference 7.3)

MPR-4153 2-1 Revision 1 Page 10 of 88

2.1.2 Embedded Rods FSEL tracks the progression of ASR by measuring the distance between rods that were embedded in the concrete during specimen fabrication. Each specimen contains

ýrods perpendicular to the reinforcement mats and

ýrods parallel to the reinforcement mats.

As ASR occurs, the concrete between a given set of rods expands, which increases the distance between the rods.

FSEL measures the distance between each set of expansion rods shortly after fabrication to provide an initial value. The cumulative expansion at a given point in time is the difference between the initial value and the measurement at a given time (Reference 8). Figure 2-2 and Figure 2-3 show the configuration of the embedded rods.

Figure 2-2. Plan View of Embedded Rods (Reference 7.6)

(Embedded Reinforcement also Shown)

Figure 2-3. Elevation View of Embedded Expansion Rods (Reference 7.6)

(Embedded Reinforcement also Shown)

The instrumentation specimen has

ý rods perpendicular to the reinforcement mats, but does not have rods parallel to the reinforcement mats. For this specimen, through-thickness expansion is monitored using a depth gage inserted into small bore holes that go completely through the specimen.

MPR-4153 Revision I 2-2 Page 11 of 88

2.2 EXPANSION IN REINFORCED CONCRETE 2.2.1 Test Specimens Expansion of the test specimens is significantly more pronounced in the through-thickness direction (i.e., perpendicular to the reinforcement mats) than the in-plane direction (i.e., on the faces of the specimens parallel to the reinforcement mats). Expansion in the in-plane direction plateaus at low levels, while expansion in the through-thickness direction continues to increase.

This behavior can be seen in Figure 2-4, which is a plot of expansion for Specimen f based on monitoring the distance between the embedded rods1. Expansion behavior in this test specimen is representative of other test specimens.

Figure 2-4. Expansion Trends in Example Test Specimen The difference between in-plane expansion and through-thickness expansion is due to the reinforcement detailing and the resulting difference in confinement between the in-plane and through-thickness directions. The reinforcement mats confine expansion in the in-plane direction. Through-thickness expansion, on the other hand, is not confined because there is no

'Figure 2-4 is for illustrative purposes only. Periodic monitoring of expansion is considered for information only, whereas the measurements at the time of testing are formal test measurements.

MPR-4153 Revision 1 2-3 Page 12 of 88

reinforcement in that direction. Therefore, expansion occurs preferentially in the through-thickness direction.

For specimens with higher ASR levels, a large crack on the concrete surface formed on each specimen face that is between the reinforcement mats, as shown in Figure 2-5. This crack was also between the embedded pins used to measure through-thickness expansion. 2 m-gure z-b. uracK in I nrougn-I niCKness uirection OT exampie I est 6pecimen Once the large crack forms, expansion measured using the embedded rods is governed by the increase in crack width. Expansion in the regions outside of the embedded rods remains relatively unchanged. Therefore, expansion must be calculated based on the total width of the beam, rather than the distance between the embedded rods, to appropriately characterize expansion of the specimen. FSEL provided a correlation to relate expansion measurements from the embedded rods to through-thickness expansion over the total beam width. (Reference 21) 2.2.2 Literature Review The observed preferential expansion in the through-thickness direction is consistent with literature on expansion caused by ASR (References 2, 9, and 10). Literature suggests that when reinforcement is present to restrain the tensile force exerted by ASR expansion, an equivalent compressive force develops in the concrete, which creates a prestressing effect. If tensile loads 2 Concentration of expansion in the large crack is believed to be an edge effect of the test specimens that is not representative of Seabrook Station, where the concrete is in its full structural context. There is no evidence of this type of cracking at Seabrook Station at this time.

MPR-4153 Revision 1 2-4 Page 13 of 88

are applied to the structure, the compressive stresses in the concrete from prestressing must be overcome before there is a net tensile stress. Cracking in confined concrete would not occur until a net tensile stress is applied.

2.3 IMPLICATIONS FOR MONITORING ASR AT SEABROOK Based on the expansion behavior observed in the test specimens, expansion in the through-thickness direction is the best indicator of ASR development in the test specimens and at Seabrook Station. In-plane expansion is a readily available parameter that can be used to assist with diagnosis of ASR-affected reinforced concrete. However, the test data suggest that through-thickness measurement is a more sensitive parameter for characterizing ASR-induced expansion at Seabrook Station in the long term. Accordingly, the results of the structural testing program will be correlated to expansion in the through-thickness direction.

NextEra is expanding its ASR monitoring efforts to include through-thickness expansion.

Specifically, NextEra plans to install instruments (i.e., extensometers) in concrete structures at Seabrook Station to monitor expansion in the through-thickness direction. The current plan includes installing instruments in ASR-affected areas and some areas unaffected by ASR. The instruments in areas unaffected by ASR will provide a reference measurement to gauge effects, such as thermal expansion, that could influence the ASR expansion measurements.

The instruments measure through-thickness expansion that occurs after the instrument is installed. To determine the cumulative expansion since original construction, this expansion measurement must be added to the expansion up to the time the instrument is installed. The subsequent sections of this report provide a methodology for determining the pre-instrument expansion.

MPR-4153 2-5 Revision 1 Page 14 of 88

3 Determining Pre-Instrument Expansion from Elastic Modulus This section describes the technical basis and methodology for using the reduction in elastic modulus to determine the total ASR-induced expansion in the through-thickness direction prior to instrument installation. The methodology depends on determining the elastic modulus at the time of instrument installation from cores and establishing the original elastic modulus to provide a point of reference. The original elastic modulus may be determined by testing reference cores from concrete without symptoms of ASR or by using original construction data with an ACI correlation that relates compressive strength to elastic modulus.

Specific topics discussed in this section include:

Evaluation of changes in material properties to indicate ASR-induced expansion, Development of the correlation between expansion and elastic modulus based on test data from the large-scale ASR testing programs, and Determination of the original elastic modulus at Seabrook Station, which is used as the point of reference for determining reduction in elastic modulus.

The discussion in this section relies on test results obtained to date from the ongoing large-scale ASR testing programs at FSEL. After all test data are available, MPR will revisit this evaluation and provide updates, as appropriate.

3.1 MATERIAL PROPERTIES OF TEST SPECIMENS As part of the large-scale structural testing programs, FSEL has been obtaining material property data on the beam specimens at different levels of ASR expansion. The difference between the 28-day material property result and the material property result at the time of testing may be used to quantify development of ASRk.

3.1.1 Material Property Testing during FSEL Structural Testing Programs During fabrication of the beam specimens, FSEL prepares cylinders (approximately 8 inches in height and 4 inches in diameter) using the same batch of concrete as the specimens (Reference 11). A subset of these cylinders are tested 28 days after fabrication to provide initial values for the material properties of the specimen, including compressive strength, elastic

' The FSEL test results on elastic modulus are material tests of removed cores that no longer exhibit the structural context of the beam specimen. Load test results of beam specimens show that the reduction in elastic modulus of the cores does not correlate to a corresponding reduction in stiffness of the beam from which the cores were taken.

MPR-4153 3-1 Revision 1 Page 15 of 88

modulus, and splitting tensile strength (Reference 12). At the time of load testing a shear or reinforcement anchorage specimen, FSEL obtains cores from the specimen and performs testing for material properties. For the instrumentation specimen, FSEL obtains cores and performs material property testing at selected expansion levels.

3.1.2 Compressive Strength and Elastic Modulus Figure 3-1 is a plot showing the normalized values for compressive strength and elastic modulus as a function of expansion (Reference 13). A normalized material property is the ratio of the property at the time FSEL obtained the expansion measurement divided by the material property obtained from testing a cylinder 28 days after fabrication.

Figure 3-1. Material Properties as a Function of Expansion from Test Data (Reference 13)

Key observations from Figure 3-1 include the following:

Normalized elastic modulus follows a trend where elastic modulus decreases sharply at expansion levels less than aboutf%. The trend indicates a more gradual decrease at higher expansion levels.

Normalized compressive strength shows a general decreasing trend with increasing expansion levels; however, compared to elastic modulus, there is lower sensitivity with expansion (i.e., the slope is shallower) and there is more data scatter.

Literature data indicate that trends for normalized material properties are consistent with the material property results from the test programs (References 1 and 2). In particular, the literature concludes that reduction in elastic modulus is more sensitive to ASR development than compressive strength.

MPR-4153 3-2 Revision 1 Page 16 of 88

3.1.3 Splitting Tensile Strength Figure 3-2 is a plot showing the splitting tensile strength values as a function of expansion.

Normalized splitting tensile strength results (which require a 28-day value) are not currently available because the test program did not start obtaining these results until after FSEL had fabricated many of the specimens.

Figure 3-2. Splitting Tensile Strength as a Function of Expansion from Test Data (Reference 13)

Data from higher expansion levels have approximately the same splitting tensile strength values as data from low expansion levels. Even if normalized data were available, sensitivity with expansion would be low (i.e., shallow slope). Accordingly, MPR concludes that a correlation to expansion using normalized tensile strength is unlikely to be more sensitive than a correlation using normalized elastic modulus.

3.2 DEVELOPMENT OF CORRELATION BETWEEN MODULUS AND EXPANSION 3.2.1 Data from Test Program Figure 3-3 includes a plot of the test data for reduction in modulus of elasticity and the corresponding expansion measurements (Reference 13; Appendix A). The plot uses a normalized modulus value that is the ratio of the elastic modulus at the time the expansion measurement was obtained (Et) divided by the 28-day elastic modulus (Eo).

MPR-4153 3-3 Revision 1 Page 17 of 88

Figure 3-3. Elastic Modulus as a Function of Expansion from Test Data (Reference 13)

Results of calculations using the data from Figure 3-3 include the following:

The correlation shown in Figure 3-3 has the following equation determined by least-squares regression (Reference 13):

W

[Equation 1]

The correlation fits well with the data and therefore supports use of a=

formulation.

The coefficient of determination (R2) is M (Reference 13). MPR performed scoping evaluations of several different forms of the equation for the correlation and determined that a=

formulatior provided the best fit.

3.2.2 Data from Literature As part of the Reference 13 calculation, MPR compared the relationship developed from the FSEL test data against data available in literature (References 14, 15, and 16). The literature data reflect small specimens that were cast and cured as unconfined concrete.

MPR-4153 3-4 Revision I Page 18 of 88

Figure 3-4. Comparison of Derived Relationship with Literature Data (Reference 13)

Overall, the trend from the literature data compares favorably with the correlation generated from the FSEL data. Accordingly, the comparison to literature data corroborates application of the experimentally-determined correlation at Seabrook Station.

3.2.3 Applicability of Correlation to Seabrook Station The correlation developed from the FSEL data relating expansion to reduction in elastic modulus is applicable to reinforced concrete structures at Seabrook Station. The test data used to generate the correlation were obtained from test specimens that were designed to be as representative as practical of the concrete at Seabrook Station, including the reinforcement detailing.

Additionally, comparison against literature data shows that the correlation follows a trend that is consistent with other published studies which cover a range of concrete mixtures.

3.3 ESTABLISHING ORIGINAL ELASTIC MODULUS AT SEABROOK The correlation shown in Figure 3-3 and provided in Equation 1 uses the 28-day elastic modulus as an input for determining expansion. However, consistent with typical construction practices, material property testing of concrete used at Seabrook Station verified only the 28-day compressive strength; the elastic modulus was not measured. This section describes two approaches for establishing the 28-day elastic modulus for concrete at Seabrook Station.

MPR-4153 3-5 Revision 1 Page 19 of 88

3.3.1 Approach 1: Code Equation Based on Compressive Strength ACI 318-71 (Reference 17) provides the following equation for the elastic modulus of concrete (Eo) calculated based on compressive strength (f,') and the density of concrete in lb/ft3 (W,):

E, = 33 x w,1.5 X A(f 0 ')

[Equation 2]

The equation presented in ACI 318-71 is based on fitting a curve to publicly available information on compressive strength and elastic modulus of various concrete specimens. The data used cover a range of concrete mixtures from lightweight concrete to normal weight concrete.

Confirmation of Code Equation for FSEL-Generated Data Using data from the test program for 28-day compressive strength and elastic modulus for a concrete mix design that represented Seabrook Station, MPR confirmed that the ACI equation is applicable (Reference 18; Appendix B). ACI 318-71 states that the actual elastic modulus is expected to be within +/-20% of the calculated value. As shown in Figure 3-4, flofs data points a%) obtained from the test program met this criterion.

Figure 3-5. Comparison of Test Data to ACI Equation (Reference 18)

MPR concludes that the ACI 318-71 equation is applicable for concrete at Seabrook Station for the following reasons:

MPR-4153 Revision 1 3-6 Page 20 of 88

The FSEL data are consistent with the equation from ACI 318-71 and the stated variance of +/-20%.

The concrete test specimens fabricated by FSEL are designed to be representative of the concrete used at Seabrook Station and therefore better represent the concrete at Seabrook than the range of mixtures used to generate the code equation.

Original Compressive Strength Using original construction records for compressive strength tests and the ACI 318-71 correlation, NextEra could establish the 28-day elastic modulus.

NextEra has retrieved records for concrete fabrication from original construction for selected buildings. For convenience, MPR Calculation 0326-0062-CLC-02 (Reference 19; Appendix C) summarizes the currently-available 28-day compressive strength test results and the buildings associated with those results. For structural assessment of particular concrete members, application of values from Reference 19 will need to be evaluated on a case-by-case basis to determine whether the available data are sufficiently representative of the concrete being evaluated. NextEra may need to retrieve additional original construction records to implement this approach.

In addition, NextEra has statistical analysis of over 5,000 compressive strength specimens representing 12 mix classes used during original construction (Reference 20). These data could be applied if NextEra can identify the mix class used for a particular concrete surface.

3.3.2Approach 2: Reference Cores An alternative approach for determining the original elastic modulus is to obtain and test reference cores for elastic modulus from concrete at Seabrook Station that is not affected by ASR. The elastic modulus determined using the reference cores would then be applied as equivalent to the 28-day elastic modulus.

NextEra plans to install through-thickness expansion monitoring instrumentation in "control" locations where ASR has not affected the concrete. NextEra would test the cores obtained during installation to obtain elastic modulus results.

To implement this approach, NextEra would need to justify that the reference cores were representative of original construction concrete for the location in question. Petrographic examination of the cores (potentially after elastic modulus testing) would conclusively determine that the reference core is not affected by ASR. The original construction data discussed in Appendix C indicate that there are differences in material properties among the buildings at Seabrook Station. NextEra should evaluate selection of a representative reference core on a case-by-case basis.

3.3.3 Selection of an Approach for Determining Original Elastic Modulus Approach 1 and Approach 2 are both valid approaches. The approach should be selected based on specific considerations of the area being evaluated. If both approaches are feasible, both approaches may be used to validate the results using two independent means.

NPR-4153 3-7 Revision 1 Page 21 of 88

4 Recommended Approach 4.1 OVERVIEW OF APPROACH MPR recommends the following approach for determining ASR-induced through-thickness expansion for instrumented locations at Seabrook Station.

1.

Determine the current elastic modulus of the concrete by testing of cores removed from the structure. Elastic modulus testing requires companion compressive strength testing, so MPR recommends obtaining a minimum of four specimens. Two test specimens are for compressive strength testing and two test specimens are for subsequent elastic modulus testing.

2.

Establish the original elastic modulus of the concrete by one of the following methods:

Using the ACI 318-71 correlation to calculate elastic modulus from 28-day compressive strength test results.

Obtaining cores from ASR-free locations and testing for elastic modulus.

3.

Calculate the reduction in elastic modulus by finding the ratio of the test result from the ASR-affected area to the original elastic modulus.

4.

Determine through-thickness expansion from original construction to the time the extensometer is installed using the correlation developed in this report. The correlation relates reduction in elastic modulus with measured expansion from beam specimens used during the large-scale ASR structural testing program.

5.

Calculate the total expansion by adding the extensometer measurement to the expansion at the time of instrument installation.

4.2 UNCERTAINTY The recommended methodology relies on the correlation between through-thickness expansion and normalized elastic modulus. For normalized elastic modulus greater thanfl, the correlation indicates a relatively narrow range of expansion values from f% tol%. For normalized elastic modulus values less than f, the expansion values increase sharply. Uncertain with the methodology is more impactful for normalized elastic modulus values less thari.

NextEra previously tested cores from ASR-affected areas for elastic modulus as part of the original diagnosis of ASR at Seabrook Station. Using these test results and Approach 1 for establishing the original elastic modulus, MPR performed a scoping calculation that concluded MPR-4153 4-1 Revision 1 Page 22 of 88

that the minimum normalized elastic modulus currently at Seabrook Station is higher than fl.

Uncertainty associated with determining the normalized elastic modulus may result in a potential value for elastic modulus that is less than f and therefore in the range of high sensitivity for determining expansion.

MPR will conduct a more specific treatment of uncertainty and the associated consequences for determining structural performance when all test data are available.

MPR-4153 4-2 Revision 1 Page 23 of 88

5 References

1.

Institution of Structural Engineers, Structural Effects ofAlkali-Silica Reaction: Technical Guidance on the Appraisal of Existing Structures, London, UK, 1992.

2.

Bayrak, 0., "Structural Implications of ASR: State of the Art," July 2014.

(Seabrook FP # 100697)

3.

Fournier, B. et al, FHWA-HIF-09-004, Report on the Diagnosis, Prognosis, and Mitigation ofAlkali-Silica Reaction in Transportation Structures, January 2010.

4.

MPR-3727, Seabrook Station: Impact ofAlkali-Silica Reaction on Concrete Structures and Attachments, Rev. 1, May 2012. (Seabrook FP # 100716.)

5.

MPR-3 848, Seabrook Station - Approach for Shear and Reinforcement Anchorage Testing of Concrete Affected by Alkali-Silica Reaction, Rev. 0, April 2013.

(Seabrook FP # 100818)

6.

United States Nuclear Regulatory Commission, NRC Information Notice 2011-20, "Concrete Degradation by Alkali-Silica Reaction," November 18, 2011. (ADAMS Accession No. ML112241029)

7.

Test Program Drawings 7.1. FSEL Drawing DWG 0326-0063-0S-G, fl-Inch Shear Specimen Geometry, Revision 1.

7.2. FSEL Drawing DWG_0326-0063_JA-G, f-Inch Anchorage Specimen Geometry, Revision 3.

7.3. FSEL Drawing DWG_0326-0063-S-RI, f-Inch Shear Specimen Reinforcement, Revision 1.

7.4. FSEL Drawing DWG 0326-0063_MA-R1, l-Inch Anchorage Specimen Reinforcement, Revision 3.

7.5. FSEL Drawing DWG 0326-0063-01-R2, f-Inch Instrumentation Specimen Reinforcement - Assembly, Revision 0.

7.6 FSEL Drawing DWG 0326-0063-ES-I, N-Inch Shear Specimen Instrumentation, Revision 1.

8.

FSEL Procedure 4-3, Periodic Monitoring of Concrete Expansions, Revision 6.

MPR-4153 5-1 Revision 1 Page 24 of 88

9.

Deschenes, D., Bayrak, 0., and Folliard, K., ASR/DEF-Damaged Bent Caps. Shear Tests and Field Implications, Technical Report IAC-12-8XXIA006, Center for Transportation Research, Bureau of Engineering Research, University of Texas at Austin, August 2009.

10.

Miyagawa, T. et al, Fracture of Reinforcing Steels in Concrete Structures Damaged by Alkali-Silica Reaction - Field Survey, Mechanism, and Maintenance, Journal of Advanced Concrete Technology, Vol. 4 No. 3, October 2006.

11.

FSEL Procedure 1-5, Placement and Curing of Materials Testing Samples, Revision 3.

12.

MPR Test Specification 0326-0062-05, Revision 9, "Specification for Shear and Reinforcement Anchorage Testing of ASR-Affected Reinforced Concrete."

(Seabrook FP # 100759)

13.

MPR Calculation 0326-0062-CLC-03, Correlation Between Through-Thickness Expansion and Elastic Modulus in Concrete Test Specimens Affected by Alkali-Silica Reaction (ASR),

Revision 1.

14.

Clark, L., Critical Review of the Structural Implications of the Alkali Silica Reaction in Concrete, Transport and Road Research Laboratory Contractor Report 169, July 1989.

15.

Smaoui, N. et al, Mechanical Properties of ASR-Affected Concrete Containing Fine or Coarse Reactive Aggregates, Journal of ASTM International, Vol. 3, No. 3, March 2006.

16.

Ahmed, T. et al, The Effect ofAlkali Reactivity on the Mechanical Properties of Concrete, Construction and Building Materials, 17 (2003) 123-144, January 9, 2002.

17.

ACI 318-71, Building Code Requirements for Reinforced Concrete, 1971 Edition, Fourth Printing.

18.

MPR Calculation 0326-0062-CLC-01, Evaluation of ACI Equation for Elastic Modulus, Revision 0.

19.

MPR Calculation 0326-0062-CLC-02, Compressive Strength Values for Concrete at Seabrook Station, Revision 0.

20.

Pittsburgh Testing Laboratory letter dated January 25, 1986, "Seabrook Nuclear Station Spec. 9763.006-5-1 Statistical Analysis -- Concrete Compression Test Data January 1986."

(Seabrook FP # 100348)

21.

Letter from FSEL (Bayrak) to MPR (Simons) dated June 23, 2015, "Measurement of Z-Direction Expansion of A-and S-Series Specimens."

22.

MPR Commercial Grade Acceptance Record CGAR-0326-0062-43-1, Revision 1.

23.

MPR Commercial Grade Acceptance Record CGAR-0326-0062-43-2, Revision 0.

24.

MPR Commercial Grade Acceptance Record CGAR-0326-0062-43-3, Revision 0.

MPR-4153 5-2 Revision I Page 25 of 88

A Correlation Between Expansion and Elastic Modulus This appendix includes MPR Calculation 0326-0062-CLC-03, Correlation Between Through-Thickness Expansion and Elastic Modulus in Concrete Test Specimens Affected by Alkali-Silica Reaction (ASR), Revision 1.

MPR-4153 A-i Revision 1 Page 26 of 88

MPR Associates, Inc.

UM PR 320 King Street Alexandria, VA 22314 CALCULATION TITLE PAGE Client:

Page 1 of 12 +

NextEra Energy Seabrook Appendices A-C (28 pages total)

Project:

Task No.

Approach for Estimating Through-Wall Expansion from Alkali-Silica Reaction at Seabrook Station 0326-1405-0074

Title:

Calculation No.

Correlation Between Through-Thickness Expansion and Elastic Modulus in Concrete Test Specimens Affected by Alkali-Silica Reaction (ASR) 03260062CLC03 Preparer / Date Checker I Date Reviewer & Approver / Date Rev. No.

0 Michael Saitta Vaibhav Bhide John W. Simons February 2, 2015 February 2, 2015 February 2, 2015 Michael Saitta Kathleen Mulvaney John W. Simons June 23, 2015 June 23, 2015 June 23, 2015 QUALITY ASSURANCE DOCUMENT This document has been prepared, checked, and reviewed/approved in accordance with the QA requirements of 10CFR50 Appendix B and/or ASME NQA-1, as specified in the MPR Nuclear Quality Assurance Program.

MPR-QA Form QA-3.1-1, Rev. 2 Page 27 of 88

MPR Associates, Inc.

  • M P R 320 King Street Alexandria, VA 22314 RECORD OF REVISIONS Calculation No.

Prepared By Checked By Page:

2 0326-0062-CLC-03 Ae4'*ý gAboW*

tV1l Revision [ Affected Pages Description 0

1 All All Initial Issue Added correction factor for through-thickness expansion values to account for influence of mid-plane cracks on the expansion measured using embedded rods. (See new Section 5.2)

Note:

The revision number found on each individual page of the calculation carries the revision level of the calculation in effect at the time that page was last revised.

MPR QA Form QA-3.1-2, Rev. 0 Page 28 of 88

MPR Associates, Inc.

WMPR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: 3 0326-0062-CLC-03

ý PWwm fliv~vi Revis ion:

1 Table of Contents 1.0 Purpose..........................................................................................................

4 2.0 Sum m ary of Results.........................................................................................

4 3.0 Background.......................................................................................................

5 4.0 Assum ptions.....................................................................................................

5 4.1 Assumptions with a Basis.......................................................................................

5 4.2 Unverified Assumptions.........................................................................................

5 5.0 Discussion.........................................................................................................

5 5.1 Test Data.............................................................................................................

5 5.2 Expansion M easurement Correction Factor..........................................................

6 5.3 Selection of Elastic M odulus as the Property for the Correlation...........................

6 5.4 Elastic M odulus Correlation...................................................................................

8 5.5 Comparison to Published Values...........................................................................

9 6.0 References.......................................................................................................

11 A

Test Data......................................................................................................

A-1 B

Least Squares Regression...........................................................................

B-1 C

Reference 6..................................................................................................

C-1 MPR QA Form: QA-3.1-3, Rev. 0 Page 29 of 88

MPR Associates, Inc.

WMPR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: 4 0326-0062-CLC-03 A

_vh4' 14vý4L Revision: 1 1.0 PURPOSE This calculation determines a correlation between through-thickness expansion and elastic modulus of concrete test specimens affectedby Alkali-Silica Reaction (ASR). The correlation is based on data from test programs that MPR is sponsoring at Ferguson Structural Engineering Laboratory (FSEL). The correlation is compared to published data.

2.0

SUMMARY

OF RESULTS There is a strong correlation between elastic modulus and through-thickness expansion of concrete test specimens that are affected by ASR. The data were fit with a least squares regression using a form. Figure 2-1 below shows the FSEL test data and the least squares fit. The least squares fit compares favorably with the trend observed in the data. The R2 value of the correlation is Figure 2-1 also shows data found in the literature for free expansion of ASR-affected concrete specimens. These data are consistent with the FSEL data.

Figure 2-1. Strong Correlations Between Elastic Modulus and Expansion MPR QA Form: QA-3.1-3, Rev. 0 Page 30 of 88

MPR Associates, Inc.

  • M PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: 5 0326-0062-CLC-03

$vW

?Lw 1

Revision: 1

3.0 BACKGROUND

Published data show that the material properties of ASR-affected concrete change with increasing levels of ASR expansion. MPR intends to use the relationship between material properties and ASR expansion to develop a methodology to determine the through-thickness expansion of concrete structures at Seabrook Station. This relationship will be defined using data from test programs that MPR is sponsoring at FSEL to investigate ASR in reinforced concrete elements. The test specimens are consistent with structures at Seabrook Station in terms of reinforcement details, depth of cover and overall depth. In addition, the concrete used in the specimens is representative of the concrete used at Seabrook Station, with some deviations to produce significant ASR expansion in a short timeframe.

4.0 ASSUMPTIONS 4.1 Assumptions with a Basis There are no assumptions with a basis.

4.2 Unverified Assumptions There are no unverified assumptions.

5.0 DISCUSSION 5.1 Test Data The test data used herein are for specimens from the Shear Test Program and the Reinforcement Anchorage Test Program, as well as the Instrument Beam. Combining data from these programs is appropriate as the same concrete mix was used in all specimens and specimen configurations and reinforcement details are similar.

Test data on m concrete specimens are used in this calculation. The baseline material properties are the 28-day tests performed on cylinders molded at the time of concrete placement.

The material properties at various levels of ASR expansion are based on tests of cores removed from the specimen. The available data include the following:

  • 28 days after concrete placement o Three compressive strength values o Three elastic modulus values o

Three splitting tensile strength values (note that this test was only performed form of the I specimens, a total of I tests)

  • After ASR had occurred o Three compressive strength values MPR QA Form: QA-3.1-3, Rev. 0 Page 31 of 88

MPR Associates, Inc.

UM PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: 6 0326-0062-CLC-03

K5hu4ý41uv Revision
1 o Three elastic modulus values o

Three splitting tensile strength values o

Through-thickness expansion at the time the cores were removed These values are taken from Reference 1 and are summarized in Appendix A.

5.2 Expansion Measurement Correction Factor The test specimens have developed large cracks on the concrete surface in the through-thickness direction between the reinforcement mats. The large cracks concentrate though-thickness expansion between the embedded rods. Therefore, the expansion measurement taken at the rods was significantly higher than the average expansion of the specimen along its width. FSEL developed a correlation to correct the expansion measured using the embedded rods, yielding an estimate of the average through-thickness expansion (Reference 6, See Appendix C; Reference 7 and Reference 8). This correlation is:

Where:

Epin is the expansion measured using the rods, measured in percent, and E is the corrected expansion, measured in percent.

This correction is applied to all of the expansion data, and the corrected data are used throughout the remainder of the calculation. The results of the correction are presented in Appendix A.

5.3 Selection of Elastic Modulus as the Property for the Correlation To allow for more valid comparisons, the material properties of each specimen from the post-ASR testing were normalized against its average value from the 28-day test. Therefore, a sample that had seen very little change in a material property would have a normalized value of approximately 1, whereas one that had experienced a 25% reduction in a material property would have a normalized value of 0.75.

Figure 5-1 plots the normalized compressive strength and the normalized elastic modulus versus expansion. From the plot, it appears that there is a strong correlation between modulus and expansion. There also appears to be a weak correlation between compressive strength and expansion.

There were insufficient data to normalize the splitting tensile strength. Therefore, the splitting tensile strength was plotted against expansion in Figure 5-2. There does not appear to be a MPR QA Form: QA-3.1-3, Rev. 0 Page 32 of 88

MPR Associates, Inc.

320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: 7 0326-0062-CLC-03 K6lThýu44

{4444t4L1V Revision: 1 correlation between splitting tensile strength and expansion. Therefore, it is determined that elastic modulus is the best choice to correlate against expansion.

Figure 5-1. Normalized Strengths/Stiffness vs Expansion MPR QA Form: QA-3.1-3, Rev. 0 Page 33 of 88

320 King Street Alexandria, VA 22314 Calculation No.

0326-0062-CLC-03 Prepared By Checked By Page: 8

ývw'n ýj*

Revision:

1 Figure 5-2. Splitting Tensile Strength vs Expansion 5.4 Elastic Modulus Correlation Non-linear least squares regression was used to fit a curve for the relationship between normalized modulus and expansion. Based on scoping analysis of several types of equations, it was determined that the best-fit curve would take the form of:

Least squares fitting was used to determine the constants A and B. The process of least squares is described in detail in Appendix B. This resulted in a final correlation of:

Where:

expansion is the relative through-thickness expansion of the concrete specimen (0.02 implies a 2% expansion) modulus is the normalized modulus of the concrete specimen after ASR This correlation is shown in Figure 5-3. The least squares fit compares favorably with the observed data. The R2 value for the correlation is M.

MPR QA Form: QA-3.1-3, Rev. 0 Page 34 of 88

MPR Associates, Inc.

320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page:

9 0326-0062-CLC-03 y

  • ttvI 1

Revision:

1 Figure 5-3. Correlation between Expansion and Normalized Modulus 5.5 Comparison to Published Values Data on the elastic modulus as a function of ASR expansion are available in the literature. These data are for free expansion of small concrete specimens. Table 5-1 lists data from the sources considered in Reference 2.

Table 5-1. Existing Data Showing Expansion (%) and Corresponding Elastic Modulus Expansion (%)

Normalized Elastic Reference Modulus 0.05 100 3, Table 2.1 0.10 70 3, Table 2.1 0.25 50 3, Table 2.1 0.50 35 3, Table 2.1 1.00 30 3, Table 2.1 1.50 20 3, Table 2.1 MPR QA Form: QA-3.1-3, Rev. 0 Page 35 of 88

320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page:

10 0326-0062-CLC-03 b

4I 1

.Revision:

1 Table 5-1. Existing Data Showing Expansion (%) and Corresponding Elastic Modulus Normalized Elastic Expansion (%)

Modulus Reference 0.002 100 4

0.039 66.0 4

0.114 65.2 4

0.210 54.7 4

0.328 50.2 4

0.392 46.7 4

0.007 100 4

0.020 97.7 4

0.038 91.2 4

0.095 78.3 4

0.128 75.8 4

0.291 86.52 5

1.2531 13.92 5

0.431 70.22 5

1.5731 13.72 5

0.431 39.72 5

1.6561 10.32 5

0.431 32.82 5

1.686' 8.12 5

Note 1: Longitudinal prism expansion was selected as the most representative Note 2: Taken as elastic modulus at testing divided by elastic modulus at 28 days Figure 5-4 plots these data and compares them to the FSEL data and to the correlation based on the FSEL data.

MPR QA Form: QA-3.1-3, Rev. 0 Page 36 of 88

320 King Street Alexandria, VA 22314 Calculation No.

0326-0062-CLC-03 Prepared By Checked By Page: 11 VAh'tý gwr Revision: i Figure 5-4. Modulus vs Expansion From Published Literature As shown in Figure 5-4, the data from published literature follow a trend that is consistent with the FSEL test data and the correlation determined using these data.

6.0 REFERENCES

1.

FSEL Special Test and Inspection Reports (STIRs) as accepted by CGAR-0326-0062-43-1 Revision 1 and CGAR-0326-0062-43-2 Revision 0 a) STIR-24-21, Revision 0 n) STIR-24-64, Revision 0 b) STIR-24-23, Revision 0 o) STIR-24-67, Revision 0 c) STIR-24-24, Revision 0 p) STIR-24-68, Revision 0 d) STIR-24-26, Revision 0 q) STIR-24-69, Revision 0 e) STIR-24-34, Revision 0 r) STIR-24-70, Revision 0 fj STIR-24-35, Revision 0 s) STIR-24-71, Revision 0 g) STIR-24-56, Revision 1 t) STIR-24-72, Revision 0 h) STIR-24-58, Revision 0 u) STIR-24-79, Revision 1 i) STIR-24-59, Revision 0 v) STIR-24-81, Revision 1 j) STIR-24-60, Revision 0 w) STIR-24-86, Revision 0 k) STIR-24-61, Revision 0 x) STIR-24-88, Revision 0

1) STIR-24-62, Revision 0 y) STIR-24-89, Revision 0 m) STIR-24-63, Revision 0 z) STIR-24-103, Revision 0 MPR QA Form: QA-3.1-3, Rev. 0 Page 37 of 88

MPR Associates, Inc.

320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page:

12 0326-0062-CLC-03 Revision: 1 aa)

STIR-24-104, Revision 0 ii)

STIR-24-116, Revision 0 bb) STIR-24-105, Revision 0 jj)

STIR-24-120, Revision 0 cc)

STIR-24-106, Revision 0 kk) STIR-24-132, Revision 0 dd) STIR-24-107, Revision 0

11)

STIR-24-133, Revision 0 ee)

STIR-24-108, Revision 0 mm) STIR-24-134, Revision 0 ffj STIR-24-1 10, Revision 0 nn) STIR-24-140, Revision 0 gg) STIR-24-114, Revision 0 oo)

STIR-24-147, Revision 0 hh)

STIR-24-115, Revision 0

2.

Bayrak, Oguzhan, Structural Implications of ASR: State of the Art, July 28, 2014, transmitted to Seabrook Station in MPR Letter 0326-0058-200, dated July 29, 2014.

3.

Clark, L.A., Critical Review of the Structural Implications of the Alkali Silica Reaction in Concrete, Transport and Road Research Laboratory Contractor Report 169, July 1989.

4.

Smaoui, N. et al., Mechanical Properties of ASR-Affected Concrete Containing Fine or Coarse Reactive Aggregates, Journal of ASTM International, Vol. 3, No. 3, March 2006.

5.

Ahmed, T. et al., The effect ofAlkali Reactivity on the Mechanical Properties of Concrete, Construction and Building Materials, 17 (2003) 123-144, January 9, 2002.

6.

Letter from Oguzhan Bayrak (FSEL) to John Simons (MPR), "Measurement of Z-Direction Expansion of A-and S-Series Specimens", dated June 23, 2015. (Included as Appendix C)

7.

STIR-0326-0062-24-171, Revision 0.

8.

CGAR-0326-0062-43-3, Revision 0.

MPR QA Form: QA-3.1-3, Rev. 0 Page 38 of 88

MPR Associates, Inc.

  • M PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: A-i 0326-0062-CLC-03 r ]4uw Revision:

1 A

Test Data This Appendix includes tables of summarized test data originally from FSEL. Table A-I contains data from tests conducted 28 days after casting. The data are used to normalize the post-ASR data. Table A-2 contains data from tests that were conducted after ASR had occurred.

Table A-3 contains expansion values measured using the specimen rods and the corrected expansion determined using the correlation discussed in Section 5.2. Test data are taken from Reference 1 of the main body of this calculation.

MPR QA Form: QA-3.1-3, Rev. 0 Page 39 of 88

MPR Associates, Inc.

320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: A-2 0326-0062-CLC-03

,,wm Revision:

1 Table A-I. FSEL 28-Day Compressive Strength, Elastic Modulus, and Splitting Tensile Strength Test Data MPR QA Form: QA-3.1-3, Rev. 0 Page 40 of 88

MPR Associates, Inc.

320 King Street UIM PR Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: A-3 0326-0062-CLC-03

,;X-Ch4AA4Wvw ju.14i" Revision:

1 Table A-2. FSEL Average Expansion, Compressive Strength, and Elastic Modulus Test Data After ASR MPR QA Form: QA-3.1-3, Rev. 0 Page 41 of 88

MPR Associates, Inc.

  • M PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: A-4 0326-0062-CLC-03

,Th4Lb/M g

4 Revision:

1 Table A-3. FSEL Expansion Test Data With Correction Factor MPR QA Form: QA-3.1-3, Rev. 0 Page 42 of 88

MPR Associates, Inc.

UMPR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: B-i 0326-0062-CLC-03 Vdv{.A,4 Revision:

I B

Least Squares Regression Purpose This appendix explains the methodology used to perform the Least Squares Regression Analysis.

A brief description of the fit statistic R2 is also given. After the method of Least Squares is explained, the method is applied to the correlation between the FSEL test data for compressive strength and corrected through thickness expansion.

Discussion Least Squares Regression is a commonly accepted method of fitting a curve to a set of scattered data. This is done by minimizing the sum of squares error term. This is a common statistical method that is documented in textbooks such as "Applied Data Analysis and Modeling for Energy Engineers and Scientists" by T.A. Reddy. The sum of squares is given by:

m Sj=

r2 i=1 Where:

S is the error term, m is the number of known values, and rm is the residual of the mth value, as given by:

rm = Yi - f(xi, C)

Where:

yj and xi are a known value pair, f is the regressed or fit function, and C is the set of constants used to fit the model.

By combining the above equations with a known set of values, S is minimized by varying C. In some cases, this can be accomplished analytically, but is often accomplished numerically. The values of C that minimize S are said to be the fitting parameters, and the function f(xi, C) is the curve of best fit in the least squares sense.

MPR QA Form: QA-3.1-3, Rev. 0 Page 43 of 88

MPR Associates, Inc.

IIM PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: B-2 0326-0062-CLC-03

ýWt ThA4(

i Revision: 1 It is often desirable to determine how well a given curve fits a set of data. A commonly used statistic to determine this is the coefficient of determination, R2. R2 is defined as:

R

=

2 1

-SS_

sstot m

SSre (y - f(x,, C)) 2 = S 1=1 m

SStot (y -

iy 2

1=1 Example The least squares regression performed in the main body of this calculation is described in detail below. The set of points is listed in Table B-1 and plotted in Figure B-1.

MPR QA Form: QA-3.1-3, Rev. 0 Page 44 of 88

MPR Associates, Inc.

320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: B-3 0326-0062-CLC-03 Vý%vtai'

?ý-jv Revision: 1 Figure B-I. Plot of Known Values It appears that a power fit is reasonable. Therefore, it can be fit to an equation of form:

Where:

x is the set of values of X as shown in Table B-1.

A and B are a set of constants (C) used to fit the model.

To begin, we will guess at the values of A and B. In this example, our first guess will be that A = 1 and B = -0.01.

Using the model given above, we compute a value for y at each given x.

For each computed value, the residual is also computed. These values are shown in Table B-2.

MPR QA Form: QA-3.1-3, Rev. 0 Page 45 of 88

MPR Associates, Inc.

SM PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: B-4 0326-0062-CLC-03

ýWPVlýai

&wAý 1

Revision:

1 Taking the sum of squares of the residuals, we find a value of=.

However, this can be improved on. To do so, we iteratively adjust the values A and B to minimize S.

Values of A =

and B =

ý result in S being minimal and provide a good estimate of the solution. The fitted curve is plotted against the data in Figure B-2. The newly computed values are shown in Table B-3. The regressed equation is:

MPR QA Form: QA-3.1-3, Rev. 0 Page 46 of 88

MPR Associates, Inc.

SM PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: B-5 0326-0062-CLC-03

ýVýýRevision:

1 Table B-3. Eyamole Values With ComnL Residuals-Undated MPR QA Form: QA-3.1-3, Rev. 0 Page 47 of 88

320 King Street Alexandria, VA 22314 Calculation No.

0326-0062-CLC-03 Prepared By Checked By Page: B-6 Revision:

1 Figure B-2. Regressed Curve R2 can now be computed using the regressed curve. The sum of squared residuals i (SSres). The mean of y isM. Therefore, the sum of squared totals is M (SStot). R can now be computed.

R2 = 1 - SSr/SStot MPR QA Form: QA-3.1-3, Rev. 0 Page 48 of 88

MPR Associates, Inc.

  • M PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page:

C-1 0326-0062-CLC-03

K 44-2 0-Revision

I C

Reference 6 This appendix includes a copy of Reference 6: Letter from Oguzhan Bayrak (FSEL) to John Simons (MPR), "Measurement of Z-Direction Expansion of A-and S-Series Specimens", dated June 23, 2015.

Note that Reference 6 is accepted by References 7 and 8 (5 pages follow)

MPR QA Form: QA-3.1-3, Rev. 0 Page 49 of 88

PHIL M. FERGUSON STRUCTURAL ENGINEERING LABORATORY

}THE UNIVERSITY OF TEXAS AT AUSTIN 10100 Burnet Road, Building 177, Austin, Texas 78758-4497 (512) 471-3062 -Fax (512) 471-1944 June 15, 2015; Revised June 23, 2015 Mr. John W. Simons MPR Associates Inc.

320 King Street Alexandria, VA 22314-3230

Subject:

Measurement of Z-Direction Expansion of A-and S-Series Specimens

Dear Mr. Simons,

Over the past few years, Ferguson Structural Engineering Laboratory (FSEL) has been using embedded pins to measure expansion in the through-thickness, or Z-direction, of beam specimens in the MPR-sponsored test programs. A general view of a test specimen and directional definitions are provided in Figure 1. Measurement pins are located within the structural core of the test specimens, I in. from the face with Iin. of concrete cover and Iin. from the face with §in. of concrete cover (Figure 2). This arrangement places the pins Min. apart, and this distance forms the gage length for any pin-based expansion measurements.

Over time, most specimens have developed large mid-plane cracks. Investigation of past specimens with such cracks indicates that these mid-plane cracks are localized near the exposed surfaces of the specimens, and do not traverse the entire perpendicular dimension of Min. These large cracks occur between the pins mentioned above and cause significant displacement between measurement points.

Thus, expansions measured using these pins are heavily influenced by the width of this crack and may not be representative of Z-direction expansion of the entire specimen including areas outside the embedded pins. In an effort to address this edge effect and to examine expansion of the entire specimen, a new measurement frame has been designed and fabricated by FSEL.

Annotated views of the frame and specimen cross section are shown in Figure 2. The frame contacts the specimen at three points on formed concrete surfaces and aligns to both ends of both embedded pins. Once aligned, a total of fmeasurements can be taken at the locations shown in the figure using a calibrated depth micrometer. These measurements allow thickness of expanded specimens to be calculated in a repeatable manner and precisely at N locations. However, the initial through-thickness dimensions of the specimens are not known precisely at this time. To enable expansion calculations, initial through-thickness dimensions of the specimens have been taken equal to the width of the bottom portion of the steel forms used to cast the specimens. The forms were measured at five locations (Figure 3) using calibrated calipers and averaged to determine an initial width of Min.

for the specimens. All expansion calculations compare the average width measurement of the bottom form with subsequent through-thickness measurements taken on the specimens.

Page C-2 Page 50 of 88 MPR Calculation 0326-0062-CLC-03 Revision I

Figure 1 - Direction Definitions for A-and S-Series Specimens Figure 2 - Schematic View of the Measurement Frame to Measure Expansions in Z-direction 2

Page C-3 Page 51 of 88 MPR Calculation 0326-0062-CLC-03 Revision 1

Figure 3 - Plan View of Steel Form Bottom Panel with Width Measurements Through-thickness expansions can be determined by using the measurement frame, and these expansion values can be compared with those determined using the embedded pins. A summary of those data are plotted in Figure 4. It is important to note that in addition to the average expansions calculated using lmeasurements per specimen per cycle of measurement, the minimum and the maximum values are also shown to provide context. The plot also includes a

=

best-fit line through the data. Further, this figure includes both the official data and the data collected on an information-only basis. However, conclusions and recommendations presented in this letter are based only on the official data.

eIaIIonsnIp DeIween zxpanslon ivieasurements j~aseu on External Frame 3

Page C-4 MPR Calculation 0326-0062-CLC-03 Revision I Page 52 of 88

Based on the plotted comparison, an equation for through-thickness expansion based on pin measurements can be established as:

Equation I Where:

Ez,pin

= Z-direction expansion based on embedded pins in percent, and Ezfrare

= Z-direction expansion based on the measurement frame in percent.

Equation 1 is based on a combination of physical parameters related to the specimens and measurements alongside additional parameters developed based on a statistical best-fit linear regression. A detailed explanation for the derivation of Equation 1 is provided below.

4 Page C-5 MPR Calculation 0326-0062-CLC-03 Revision 1 Page 53 of 88

Equation 1 represents a combination of terms based on both engineering mechanics and statistical regression analysis.

Over upcoming months, additional data will be taken for expansion measurements using both the embedded pins and the external frame. Since specimens continue to expand with time, additional data will be plotted, primarily populating the right-hand side of Figure 4.

Within the existing test programs, no new data will be available to place points within the lower left portion of the figure. When additional data are available, the coefficients within Equation 1 may evolve, though significant changes are not expected due to the basis of the equation in structural mechanics. If changes should be warranted, the form of the equation and the methodology used for its development should remain unchanged.

Please contact me if you have any questions or comments.

Regards, Oguzhan Bayrak, Ph.D., P.E.

Director, Phil M. Ferguson Structural Engineering Laboratory Professor, Civil, Architectural and Environmental Engineering Charles Elmer Rowe Fellow, Cockrell School of Engineering The University of Texas at Austin 5

Page C-6 MPR Calculation 0326-0062-CLC-03 Revision 1 Page 54 of 88

B Evaluation of ACI Equation for Elastic Modulus This appendix includes MPR Calculation 0326-0062-CLC-01, Evaluation ofACI Equation for Elastic Modulus, Revision 0.

MPR-4153 B-i Revision I Page 55 of 88

MPR Associates, Inc.

UM PR 320 King Street Alexandria, VA 22314 CALCULATION TITLE PAGE Client:

NextEra Energy Seabrook, LLC Page 1 of 12+

Appendix A and B Project:

Task No.

Approach for Estimating Through-Wall Expansion from Alkali-Silica Reaction at Seabrook Station 0326-1405-0074

Title:

Calculation No.

Evaluation of ACI Equation for Elastic Modulus 0326-0062-CLC-0 1 Preparer / Date Checker / Date Reviewer & Approver I Date Rev. No.

Amanda Card David H. Bergquist John W. Simons 0A/29A 215 01/2/201 W0&/2 0 01/29/2015 01/29/2015 01/29/2015 0

QUALITY ASSURANCE DOCUMENT This document has been prepared, checked, and reviewed/approved in accordance with the QA requirements of 1 OCFR50 Appendix B and/or ASME NQA-1, as specified in the MPR Nuclear Quality Assurance Program.

MPR-QA Form QA-3.1-1, Rev. 2 Page 56 of 88

320 King Street Alexandria, VA 22314 RECORD OF REVISIONS Calculation No.

0326-0062-CLC-01 Revision Affected Pages 0

All Initial Issue Note:

The revision number found on each individual page of the calculation carries the revision level of the calculation in effect at the time that page was last revised.

MPR QA Form QA-3.1-2, Rev. 0 Page 57 of 88

MPR Associates, Inc.

  • M PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: 3 0326-0062-CLC-01 A

Revision: 0 Table of Contents 1.0 Introduction.......................................................................................................

4 1.1 P u rp o se.........................................................................................................................

4 1.2 Background.............................................................................................................

4 2.0 Sum m ary of Results and Conclusions...........................................................

4 3.0 Approach........................................................................................................

4 4.0 Inputs.....................................................................................................................

5 5.0 Calculation.........................................................................................................

6 5.1 Concrete Density Verification................................................................................

6 5.2 Elastic M odulus Determination.............................................................................

7 6.0 Results and Conclusions................................................................................

7 7.0 References......................................................................................................

11 A

Sam ple Concrete Density Calculation........................................................

A-1 B

Test Data and Calculations.........................................................................

B-1 MPR QA Form: QA-3.1-3, Rev. 0 Page 58 of 88

MPR Associates, Inc.

I M

P R 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: 4 0326-0062-CLC-01 (I*A't c/jk Revision:(

1.0 INTRODUCTION

1.1 Purpose This calculation evaluates the applicability of the elastic modulus equation provided in Section 8.5.1 of ACI 318-71 (Reference 2) to the concrete mix used in the Beam Test Programs that MPR is sponsoring at Ferguson Structural Engineering Laboratory (FSEL).

1.2 Background

MPR is developing a methodology to determine the through-thickness expansion of concrete structures at Seabrook Station due to Alkali-Silica Reaction (ASR). The through-thickness expansion results in a reduction in the elastic modulus. One approach for estimating the original elastic modulus (i.e., the elastic modulus before ASR expansion occurs) is to calculate it using the 28-day compressive strength of the concrete and the equation provided in ACT 318-71.

2.0

SUMMARY

OF RESULTS AND CONCLUSIONS Based on the results of this calculation, the relationship between the measured 28-day compressive strength and the elastic modulus for the test specimens within the Beam Test Programs at FSEL is consistent with the ACI equation. The measured data and calculated results show a similar trend. Measured and calculated elastic modulus values for all but three data sets were within the variability range stated in Reference 2, 20%.

3.0 APPROACH Section 8.5.1 of ACI 318-71 (Reference 2) states that the 28-day elastic modulus (E,) of concrete can be calculated based on the density of concrete in lb/ft3 (w.) and the 28-day compressive strength of concrete (fV'). This relationship is expressed using Equation 1.

E, = 33wc'S'V ]c (1)

Section R8.5.1 of ACT 318 (Reference 2) also states that measured values for elastic modulus range from 80% to 120% of the calculated value.

Reference 3 provides the basis for Equation 1 and supports Reference 2. Equation 1 is based on light weight and normal weight concrete test data from various published articles and unpublished reports from the Expanded Shale, Clay, and Slate Institute.

The elastic modulus for normal weight concrete (approximate density of 144 ) can be calculated using Equation 2, a simplified version of Equation 1. (Reference 2)

MPR QA Form: QA-3.1-3, Rev. 0 Page 59 of 88

MPR Associates, Inc.

FIM PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page:

5 0326-0062-CLC-01

(/

4 n

/

Revision: 0 EC = 57,0O olT-,

(2)

As part of the Shear and Reinforcement Anchorage Test Programs and Instrumentation Specimen Testing, FSEL has determined the 28-day concrete elastic modulus and compressive strength for each beam specimen fabricated to date. These tests use cylinders molded at the time of concrete placement. In addition to the 28-day data, data are also available from cores removed from the test specimens used for control tests (i.e., tests performed shortly after 28 days, before the onset of deleterious ASR expansion). The results of the FSEL elastic modulus and compressive strength tests are compared to Equation 2 (and therefore Equation 1) in this calculation to confirm that the ACI equation is applicable to the concrete mix used in the Beam Test Programs.

4.0 INPUTS As stated in Section 3.0, the 28-day elastic modulus and the 28-day compressive strength of twenty beams, collected by FSEL, were used to confirm the applicability of Equations 1 and 2.

A total of ddata sets were evaluated.

The data were taken from the Special Test and Inspection Records (STIRs) listed in Table 1.

(Reference 5 through Reference 40)

Table 1. References for Test Data MPR QA Form: QA-3.1-3, Rev. 0 Page 60 of 88

MPR Associates, Inc.

QM PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: 6 0326-0062-CLC-01

/

Revision: 0 Table 1. References for Test Data 5.0 CALCULATION 5.1 Concrete Density Verification It is important to note that the density of concrete varies slightly among the beams that were tested. However, all test beams are composed of normal weight concrete (144b).

The simplified equation for normal weight concrete, Equation 2, is therefore applicable and was used to calculate the elastic moduli reported in this calculation.

The relevance of Equation 2 was verified by calculating the density of a beam and comparing it to the density of normal weight concrete. The two values agreed.

A sample density calculation is provided in Appendix A.

MPR QA Form: QA-3.1-3, Rev. 0 Page 61 of 88

MPR Associates, Inc.

320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page:

0326-0062-CLC-01 (IA/1 l

Oijr Revision:

5.2 Elastic Modulus Determination The average 28-day compressive nths and Equation 2 were used to calculate the 28-day elastic modulus for each of the -

data sets listed in Table 1. The percent error is calculated between the measured and calculated elastic modulus values.

The calculation is provided in Appendix B.

6.0 RESULTS AND CONCLUSIONS The measured elastic modulus values for the data sets collected at FSEL align well with the calculated elastic modulus values (from Equation 2). All but Wof the measured elastic modulus values are within 80% to 120% of the calculated value.

Figure 1 compares the FSEL data to the trendline for Equation 2.

Figure 2 and Figure 3 illustrate that nearly all of the FSEL data falls within 80% and 120% of the calculated elastic modulus value, which is consistent with the statement in Section R8.5.1 of ACI 318 (Reference 2) regarding the accuracy of the equation.

It is important to note that the measured elastic modulus is plotted and compared to the trendline associated with Equation 2 in Figure 1 and Figure 2. The percent difference between measured elastic modulus and calculated elastic modulus (per Equation 2) is plotted in Figure 3. All three figures support the conclusion that Equation 2 (and therefore Equation 1) applies to the FSEL data.

The calculations required to generate Figure 1, Figure 2, and Figure 3 are also provided in Appendix B. Cylinders are depicted in blue. Cores are depicted in green.

Based on the results of this calculation, the elastic modulus equation, provided in Section 8.5.1 of ACI 318-71, is validated.

MPR QA Form: QA-3.1-3, Rev. 0 Page 62 of 88

320 King Street Alexandria, VA 22314 Calculation No.

0326-0062-CLC-01 Prepared By at~4Goa Checked By Page: 8 Revision: 0 Figure 1. Comparison of FSEL Elastic Modulus Test Data with Equation 2 MPR QA Form: QA-3.1-3, Rev. 0 Page 63 of 88

320 King Street Alexandria, VA 22314 Calculation No.

0326-0062-CLC-01 Prepared By Checked By Page: 9 Revision: 0 Figure 2. Range of FSEL Elastic Modulus Test Data MPR QA Form: QA-3.1-3, Rev. 0 Page 64 of 88

320 King Street Alexandria, VA 22314 Calculation No.

0326-0062-CLC-01 Prepared By a4WMbA& *3ko Checked By Page:

Revision:

10 0

Figure 3. Percent Error: FSEL Elastic Modulus Test Data vs. Equation 2 Elastic Modulus MPR QA Form: QA-3.1-3, Rev. 0 Page 65 of 88

MPR Associates, Inc.

  • M P

R 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page:

1 0326-0062-CLC-01

(

Revision: C

7.0 REFERENCES

1. Seabrook Foreign Print No. 100629, "Concrete Test Report," Revision 5.
2. ACI 318-71, "Building Code Requirements for Structural Concrete and Commentary,"

American Concrete Institute, 1971.

3. Pauw, A., "Static Modulus of Elasticity of Concrete as Affected by Density," Journal of the American Concrete Institute, Vol. 32, No. 6, December 1960, pg. 679-687.
4. United Engineers Calculation No. CD-20, "Design of Mats at El. 20' 0" and 0' 0" and Walls Below Grade for Electrical Tunnels and Control Building," Revision 2.
5. MPR Special Test and Inspection Record No. STIR-0326-0062-24-9, Revision 0.
6. MPR Special Test and Inspection Record No. STIR-0326-0062-24-17, Revision 0.
7. MPR Special Test and Inspection Record No. STIR-0326-0062-24-21, Revision 0.
8. MPR Special Test and Inspection Record No. STIR-0326-0062-24-24, Revision 0.
9. MPR Special Test and Inspection Record No. STIR-0326-0062-24-30, Revision 0.
10. MPR Special Test and Inspection Record No. STIR-0326-0062-24-34, Revision 0.
11. MPR Special Test and Inspection Record No. STIR-0326-0062-24-50, Revision 0.
12. MPR Special Test and Inspection Record No. STIR-0326-0062-24-45, Revision 0.
13. MPR Special Test and Inspection Record No. STIR-0326-0062-24-93, Revision 0.
14. MPR Special Test and Inspection Record No. STIR-0326-0062-24-1 10, Revision 0.
15. MPR Special Test and Inspection Record No. STIR-0326-0062-24-86, Revision 0.
16. MPR Special Test and Inspection Record No. STIR-0326-0062-24-96, Revision 0.
17. MPR Special Test and Inspection Record No. STIR-0326-0062-24-13, Revision 0.
18. MPR Special Test and Inspection Record No. STIR-0326-0062-24-19, Revision 0.
19. MPR Special Test and Inspection Record No. STIR-0326-0062-24-23, Revision 0.
20. MPR Special Test and Inspection Record No. STIR-0326-0062-24-26, Revision 0.

MPR QA Form: QA-3.1-3, Rev. 0 Page 66 of 88

MPR Associates, Inc.

OM PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page:

12 0326-0062-CLC-01 Revision: 0

21. MPR Special Test and Inspection Record No. STIR-0326-0062-24-3 1, Revision 0.
22. MPR Special Test and Inspection Record No. STIR-0326-0062-24-35, Revision 0.
23. MPR Special Test and Inspection Record No. STIR-0326-0062-24-84, Revision 0.
24. MPR Special Test and Inspection Record No. STIR-0326-0062-24-106, Revision 0.
25. MPR Special Test and Inspection Record No. STIR-0326-0062-24-1 17, Revision 0.
26. MPR Special Test and Inspection Record No. STIR-0326-0062-24-1 1, Revision 0.
27. MPR Special Test and Inspection Record No. STIR-0326-0062-24-47, Revision 0.
28. MPR Special Test and Inspection Record No. STIR-0326-0062-24-95, Revision 0.
29. MPR Special Test and Inspection Record No. STIR-0326-0062-24-1 11, Revision 0.
30. MPR Special Test and Inspection Record No. STIR-0326-0062-24-89, Revision 0.
31. MPR Special Test and Inspection Record No. STIR-0326-0062-24-98, Revision 0.
32. MPR Special Test and Inspection Record No. STIR-0326-0062-24-87, Revision 0.
33. MPR Special Test and Inspection Record No. STIR-0326-0062-24-107, Revision 0.
34. MPR Special Test and Inspection Record No. STIR-0326-0062-24-90, Revision 0.
35. MPR Special Test and Inspection Record No. STIR-0326-0062-24-123, Revision 0.
36. MPR Special Test and Inspection Record No. STIR-0326-0062-24-124, Revision 0.
37. MPR Special Test and Inspection Record No. STIR-0326-0062-24-127, Revision 0.
38. MPR Special Test and Inspection Record No. STIR-0326-0062-24-128, Revision 0.
39. MPR Special Test and Inspection Record No. STIR-0326-0062-24-135, Revision 0.
40. MPR Special Test and Inspection Record No. STIR-0326-0062-24-136, Revision 0.

MPR QA Form: QA-3.1-3, Rev. 0 Page 67 of 88

320 King Street Alexandria, VA 22314 Calculation No.

0326-0062-CLC-01 A

Sample Concrete Density Calculation The density of S8 was calculated using data provided in STIR-24-90. (Reference 34)

The relevant data and density calculation are provided in Table A-1.

Table A-1. Concrete Density Calculation MPR QA Form: QA-3.1-3, Rev. 0 Page 68 of 88

MPR Associates, Inc.

  • M PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: B-i 0326-0062-CLC-01 Qw*CRevision:

0 B

Test Data and Calculations The information used to perform this calculation and to generate the graphs included herein is provided in Table B-1 and Table B-2.

Table B-1. Compressive Strength and Calculated Elastic Modulus MPR QA Form: QA-3.1-3, Rev. 0 Page 69 of 88

MPR Associates, Inc.

FIM P R 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: B-2 0326-0062-CLC-01 Revision:

0 Table B-1. Compressive Strength and Calculated Elastic Modulus MPR QA Form: QA-3.1-3, Rev. 0 Page 70 of 88

320 King Street Alexandria, VA 22314 Calculation No.

0326-0062-CLC-01 Table B-1. Compressive StrencQth and Calculated Elastic Modulus MPR QA Form: QA-3.1-3, Rev. 0 Page 71 of 88

MPR Associates, Inc.

UM PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: B-4 0326-0062-CLC-01 O A Revision: 0 i and Calculated Elastic Modulus MPR QA Form: QA-3.1-3, Rev. 0 Page 72 of 88

MPR Associates, Inc.

IIM P R 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: B-5 0326-0062-CLC-01 Revision:

0 Table B-2. Elastic Modulus MPR QA Form: QA-3.1-3, Rev. 0 Page 73 of 88

320 King Street Alexandria, VA 22314 Calculation No.

0326-0062-CLC-01 Table B-2. Elastic Modulus MPR QA Form: QA-3.1-3, Rev. 0 Page 74 of 88

MPR Associates, Inc.

320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: B-7 0326-0062-CLC-01 Revision:

0 Table B-2. Elastic Modulus MPR QA Form: QA-3.1-3, Rev. 0 Page 75 of 88

C Compressive Strength of Concrete at Seabrook Station This appendix includes MPR Calculation 0326-0062-CLC-02, Compressive Strength Values for Concrete at Seabrook Station, Revision 0.

MPR-4153 C-1 Revision I Page 76 of 88

MPR Associates, Inc.

&MPR 320 King Street Alexandria, VA 22314 CALCULATION TITLE PAGE Client:

NextEra Energy Seabrook, LLC Page 1 of 8 plus Appendix A Project:

Task No.

Approach for Estimating Through-Wall Expansion from Alkali-Silica Reaction at Seabrook Station 0326-1405-0074

Title:

Calculation No.

Compressive Strength Values for Concrete at Seabrook Station 0326-0074-CLC-02 Preparer / Date Checker / Date Reviewer & Approver / Date Rev. No.

David H. Bergquist Christina Hamm John W. Simons January 28, 2015 January 28, 2015 January 28, 2015 0

QUALITY ASSURANCE DOCUMENT This document has been prepared, checked, and reviewed/approved in accordance with the QA requirements of 10CFR50 Appendix B and/or ASME NQA-1, as specified in the MPR Nuclear Quality Assurance Program.

MPR-QA Form QA-3.1-1, Rev. 2 Page 77 of 88

MPR Associates, Inc.

  • M PR 320 King Street Alexandria, VA 22314 RECORD OF REVISIONS Calculation No.

Prepared By Checked By Page: 2 0326-0074-CLC-02 Revision t Affected Pages Description 0

All Initial Issue Note:

The revision number found on each individual page of the calculation carries the revision level of the calculation in effect at the time that page was last revised.

MPR QA Form QA-3.1-2, Rev. 0 Page 78 of 88

MPR Associates, Inc.

3 M PR King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: 3 0326-0074-CLC-02 Revision: 0 Table of Contents 1.0 2.0 3.0 4.0 5.0 6.0 A

Purpose..........................................................................................................

4 Sum m ary of Results.........................................................................................

4 Background........................................................................................................

5 Methodology.....................................................................................................

6 Results...........................................................................................................

6 References.......................................................................................................

8 Compressive Strength Data..........................................................................

A-1 MPR QA Form: QA-3.1-3, Rev. 0 Page 79 of 88

MPR Associates, Inc.

320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: 4 0326-0074-CLC-02 Revision: 0 1.0 PURPOSE This calculation evaluates available 28-day compressive strength values determined from concrete cylinders during the original construction of Seabrook Station. These values are then displayed on a histogram to show the data distribution, mean, and standard deviation.

Additionally, the data are separated by location and by the strength class of the concrete (i.e.

specified compressive strength).

2.0

SUMMARY

OF RESULTS All available 28-day compressive strength data points were compiled to form the histogram given in Figure 1. The average 28-day compressive strength is 5456 psi and the standard deviation is 568 psi. Seventy-five percent of the data fall within one standard deviation of the mean and ninety-four percent of the data fall within two standard deviations of the mean.

60 Standard Deviation (a) = 568 psi 50 40 30 20 10 12 11 0

0 D

3184 3752 4320 4888 5456 6023 6591 7159 7727

-4o

-30

-20

-lo Mean 410

+2o

+3o 44o 28-Day Compressive Strength (psi)

Figure 1. 28-Day Compressive Strength Values for Concrete Cylinders at Seabrook Station MPR QA Form: QA-3.1-3, Rev. 0 Page 80 of 88

MPR Associates, Inc.

00MPR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: 5 0326-0074-CLC-02 L V Revision: 0 Table I shows the data presented in Figure 1 along with the data categorized by room at Seabrook and by concrete strength class.

Table 1. 28-Day Compressive Strength Data for Seabrook Station Standard No. Of Data

% of data

% of data Mean Min Max wthnIa ihn2 Deviation (a)

Points within I o within 2 o All Data 5456 568 121 4240 7360 75%

94%

3000 PSI Strength Class 5621 691 50 4270 7360 74%

96%

4000 PSI Strength Class 5339 430 71 4240 6150 70%

99%

(Note 1)

Containment Enclosure 5426 380 24 4880 6080 67%

100%

Building RHR Equipment 5503 491 35 4240 6150 63%

97%

Vault EFW Pump House 5390 269 12 4950 5870 67%

100%

Stairway A RCA Walkway 4891 404 12 4270 5450 50%

100%

B EDG Buidg 5197 371 21 4600 5840 62%

100%

Building B Electrical 6163 705 17 5220 7360 65%

100%

Tunnel Note 1: The strength class of 9 samples from the RHR Equipment Room cannot be identified with certainty due to poor resolution of the reference document. These samples are most likely 4000 psi strength class samples based on their proximity to other 4000 psi strength class samples. See Appendix A for more details.

3.0 BACKGROUND

MPR is developing a methodology to determine the through-thickness expansion of concrete structures at Seabrook Station due to the Alkali-Silica Reaction (ASR). The through-thickness expansion is related to the reduction in elastic modulus of the concrete over time. One approach for estimating the original elastic modulus is to calculate it from the 28-day compressive strength of the concrete using an equation from ACI 318 (Reference 1).

MPR QA Form: QA-3.1-3, Rev. 0 Page 81 of 88

MPR Associates, Inc.

320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: 6 0326-0074-CLC-02 Revision: 0 4.0 METHODOLOGY Seabrook Foreign Print No. 100629 and United Engineers Calculation No. CD-20 (References 2 and 3) include 28-day compressive strength results for concrete used in original construction for the following buildings at Seabrook Station:

Containment Enclosure Building RHR Equipment Vault EFW Pump House Stairway A RCA Walkway B Diesel Generator Building B Electrical Tunnel These references provide the 121 data points used in this calculation. These 28-day compressive strength data points are included in Appendix A.

5.0 RESULTS The average 28-day compressive strength of all data points is 5456 psi and the standard deviation is 568 psi. Seventy-five percent of the data fall within one standard deviation of the mean and ninety-four percent of the data fall within two standard deviations of the mean. Therefore, the mean is a representative value for the 28-day compressive strength of all concrete used at Seabrook. See Section 2.0 for a histogram of all data points as well as a table of the compressive strength data by room and concrete strength class. Figures 2 and 3 display the data for the 3000 psi and 4000 psi strength class concrete cores, respectively.

MPR QA Form: QA-3.1-3, Rev. 0 Page 82 of 88

MPR Associates, Inc.

320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: 7 0326-0074-CLC-02 Revision: 0 25 22 Standard Deviation (o) = 691 psi 20 15 10 5

15 5

4930 5621 6312 28-Day Compressive Strength 0

0-3547 0

4239 7004 7695 Figure 2. 28-Day Compressive Strength Values for 3000 psi Strength Class Concrete Cores 30 Standard Deviation (o) = 430 psi 25 25 25 20 15 12 10 5-1 0

47 4479 8

4909 5339 28-Day Compressive Strength 5769 6199 Figure 3. 28-Day Compressive Strength Values for 4000 psi Strength Class Concrete Cores MPR QA Form: QA-3.1-3, Rev. 0 Page 83 of 88

MPR Associates, Inc.

320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page:

8 0326-0074-CLC-02 Revision: 0

6.0 REFERENCES

1.

ACI 318-71, "Building Code Requirements for Structural Concrete," American Concrete Institute, 1971.

2.

Seabrook Foreign Print No. 100629, "Concrete Test Report," Revision 0.

3.

United Engineers Calculation No. CD-20, "Design of Mats at El. 20' 0" and 0' 0" and Walls Below Grade for Electrical Tunnels and Control Building," Revision 4.

M PR QA Form: QA-3.1-3, Rev. 0 Page 84 of 88

MPR Associates, Inc.

  • M PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: A-1 0326-0074-CLC-02 Revision: 0 A

Compressive Strength Data Table A-1 contains the 28-day compressive strength data for concrete cores at Seabrook Station.

Table A-1: 28-Day Compressive Strengths for Concrete Cores at Seabrook Station Room Sample Compressive Strength Class No.

Strength (psi)

(psi) 4405 5130 4000 4406 5200 4000 4407 5620 4000 4405A 6080 4000 4406A 5700 4000 4407A 5410 4000 4641 5200 4000 4642 5060 4000 4643 5410 4000 4641A 5980 4000 4642A 6050 4000 Containment Enclosure 4643A 6010 4000 Building 4648 5020 4000 (Reference 2) 4649 5090 4000 4650 4950 4000 4655 5380 4000 4656 5240 4000 4657 4880 4000 4648A 5020 4000 4649A 5160 4000 4650A 5360 4000 4655A 5780 4000 4656A 5730 4000 4657A 5770 4000 MPR QA Form: QA-3.1-3, Rev. 0 Page 85 of 88

MPR Associates, Inc.

3MPR King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: A-2 0326-0074-CLC-02 Revision: 0 Table A-1: 28-Day Compressive Strengths for Concrete Cores at Seabrook Station Room Sample Compressive Strength Class No.

Strength (psi)

(psi) 94 6070 3000 RHR Equipment Vault (Reference 2) 95 5780 3000 96 5710 3000 101 5800 3000 102 5730 3000 103 5700 3000 108 6140 3000 109 5960 3000 110 6030 3000 430 5020 40001 431 4990 40001 432 5060 40001 430A 5450 4000 431A 5480 4000 432A 5380 4000 437 6010 4000 438 5620 4000 439 5980 4000 437A 6010 4000 438A 6150 4000 439A 6120 4000 unknown 4670 4000 unknown 4740 4000 unknown 5660 4000 unknown 5450 4000 unknown 5480 4000 unknown 5620 4000 unknown 5700 4000 unknown 5700 4000 unknown 4600 40001 unknown 5130 40001 unknown 4240 40001 unknown 5270 40001 unknown 5240 40001 Concrete strength class cannot be determined with certainty due to poor resolution of reference document.

MPR QA Form: QA-3.1-3, Rev. 0 Page 86 of 88

MPR Associates, Inc.

U M P R 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: A-3 0326-0074-CLC-02 Ll-.7A..

Revision: 0 Table A-1: 28-Day Compressive Strengths for Concrete Cores at Seabrook Station Room Sample Compressive Strength Class No.

Strength (psi)

(psi)

RHR Equipment Vault unknown 4920 40001 590 5700 3000 591 5700 3000 592 5590 3000 590A 4950 3000 591A 5200 3000 EFW Pump House 592A 5240 3000 Stairway A 597A 5290 3000 (Reference 2) 598A 5870 3000 599A 5380 3000 604A 5180 3000 605A 5340 3000 606A 5240 3000 489 5310 3000 490 4440 3000 491 4950 3000 489A 5200 3000 490A 5450 3000 RCA Walkway 491A 4880 3000 (Reference 2) 484 4470 3000 485 4270 3000 486 4370 3000 484A 5040 3000 485A 5090 3000 486A 5220 3000 unknown 4620 4000 unknown 4700 4000 unknown 4600 4000 unknown 5150 4000 B EDG Building unknown 5660 4000 (Reference 2) unknown 5200 4000 315 5520 4000 316 5590 4000 317 5470 4000 315A 5840 4000 MPR QA Form: QA-3.1-3, Rev. 0 Page 87 of 88

MPR Associates, Inc.

FWM PR 320 King Street Alexandria, VA 22314 Calculation No.

Prepared By Checked By Page: A-4 0326-0074-CLC-02 L

Revision: 0 Table A-1: 28-Day Compressive Strengths for Concrete Cores at Seabrook Station Room Sample Compressive Strength Class No.

Strength (psi)

(psi) 316A 5110 4000 317A 5640 4000 unknown 4600 4000 unknown 4950 4000 B EDG Building unknown 4950 4000 (Reference 2) unknown 5380 4000 unknown 5310 4000 unknown 5040 4000 unknown 5340 4000 unknown 5040 4000 unknown 5430 4000 427 5410 3000 428 5220 3000 426A 6560 3000 427A 6490 3000 428A 6100 3000 433 5470 3000 434 5550 3000 435 5890 3000 B Electrical Tunnel 433 7000 3000 (Reference 3) 433A 7000 3000 434A 7220 3000 435A 7360 3000 440 5730 3000 441 5480 3000 442 5390 3000 440A 6330 3000 441A 6810 3000 442A 6760 3000 MPR QAk Form: QA-3.1-3, Rev. 0 Page 88 of 88

  • MPR June 25, 2015 DRN 0326-0062-69 Mr. Rick Noble NextEra Energy Seabrook LLC P.O. Box 300 Lafayette Road Seabrook, NH 03874

Subject:

Withholding MPR-4153 from Public Disclosure under 10 CFR 2.390

Dear Mr. Noble:

We understand that NextEra Energy Seabrook intends to submit MPR-4153, Seabrook Station -

Approach for Determining Through-Thickness Expansion from Alkali-Silica Reaction, Revision 1 on the docket to support the NRC's review of the alkali-silica reaction (ASR) issue at Seabrook Station. Further, we understand that NextEra is requesting that the documents be withheld from public disclosure under 10 CFR 2.3 90(a)(4). The report is marked proprietary to NextEra Energy Seabrook and MPR Associates as it contains information which has a commercial value to both parties. Specifically, the report includes details on the test programs that MPR is sponsoring on behalf of NextEra, as well as results from the test programs. Public release of the information would concede intellectual property and a commercial advantage to others pursuing similar test programs or assessing the structural implications of ASR.

We hereby grant our consent to docket MPR-4153, Revision 1 in support of the NRC's review of the Seabrook ASR issue provided it is withheld from public disclosure. In support of NextEra requesting that the information be withheld from public disclosure under 10 CFR 2.390(a)(4), we are providing the following:

A notarized affidavit for withholding the report from public disclosure under 10 CFR 2.390.

Three versions of MPR-4153, Revision 1:

A version that includes a heading that states "proprietary information - withhold from public disclosure under 10 CFR 2.390."

A markup that shows the proposed redactions using red boxes. It includes a statement on the cover regarding the basis for redacting information.

A non-proprietary version in which the proprietary information is redacted.

(Headings and statements about it being proprietary have been removed to be consistent with a non-proprietary designation.)

320 KING STREET ALEXANDRIA, VA 22314-3230 703-519-0200 FAX: 703-519-0224 www.mpr.com

Mr. Rick Noble Please contact me (703-519-0258) if you have any questions.

June 25, 2015 Sincerely, John W. Simons Director, Plant Systems & Components

K LF-eraG; ENERGfY _

SEABROOK NextEra Energy Seabrook, LLC AFFIDAVIT IN SUPPORT OF APPLICATION FOR WITHHOLDING PROPRIETARY INFORMATION FROM PUBLIC DISCLOSURE County of Rockingham

))

State of New Hampshire

)

I, Dean Curtland, being duly sworn according to law, depose and state the following:

(1)

I am the Site Vice President of NextEra Energy Seabrook, LLC (NextEra Energy Seabrook),

and have been delegated the function of reviewing the information described in paragraph (3) which is sought to be withheld, and have been authorized to apply for its withholding.

(2)

I am making this Affidavit in conjunction with NextEra Energy Seabrook's "Application for Withholding Proprietary Information from Public Disclosure" accompanying this Affidavit and in conformance with the provisions of 10 CFR Section 2.390.

(3)

The information sought to be withheld is contained in Enclosures 4 of NextEra Energy Seabrook's letter SBK-L-15107, Dean Curtland (NextEra Energy Seabrook) to U.S. Nuclear Regulatory Commission, entitled "Seabrook Station Response to Requests for Additional Information for the Review of the Seabrook Station, License Renewal Application-SET 23 (TAC NO. ME4028)

Relating to the Alkali-Silica Reaction (ASR) Monitoring Program," dated June 30, 2015. The NextEra Energy Seabrook proprietary information in Enclosure 4 of SBK-L-15107, is identified by enclosing boxes (").

(4)

The information sought to be withheld is considered to be proprietary and confidential commercial information because alkali-silica reaction (ASR) is a newly-identified phenomenon at domestic nuclear plants. The information requested to be withheld is the result of several years of intensive NextEra Energy Seabrook effort and the expenditure of a considerable sum of money. This information may be marketable in the event nuclear facilities or other regulated facilities identify the

presence of ASR. In order for potential customers to duplicate this information, similar technical programs would have to be performed and a significant manpower effort, having the requisite talent and experience, would have to be expended. The extent to which this information is available to potential customers diminishes NextEra Energy Seabrook's ability to sell products and services involving the use of the information. Thus, public disclosure of the information sought to be withheld is likely to cause substantial harm to NextEra Energy Seabrook's competitive position and NextEra Energy Seabrook has a rational basis for considering this information to be confidential commercial information.

(5)

The information sought to be withheld is being submitted to the NRC in confidence.

(6)

The information sought to be withheld has, to the best of my knowledge and belief, consistently been held in confidence by NextEra Energy Seabrook, has not been disclosed publicly, and not been made available in public sources.

(7)

The information is of a sort customarily held in confidence by NextEra Energy Seabrook, and is in fact so held.

(8)

All disclosures to third parties, including any required transmittals to the NRC, have been or will be pursuant to regulatory provisions and/or confidentiality agreements that provide for maintaining the information in confidence.

I declare that the foregoing affidavit and the matters stated therein are true and correct to the best of my knowledge, information, and belief. Further, the affiant sayeth not.

Dean Curtland Site Vice President NextEra Energy Seabrook, LLC 626 Lafayette Road Seabrook, New Hampshire 03874 Subscribed and sworn to before me this Zo day of June, 2015.

JAN-'~

Notary Pub/ic My commission expires 9

,,"