Letter Sequence RAI |
|---|
|
Results
Other: ML13212A367, ML14050A304, ML14071A620, ML14072A369, ML14092A346, ML14177A430, ML14238A691, ML14245A371, ML14300A218, ML14317A783, ML15027A196, ML15098A181, ML15106A736, RS-14-183, Updated Responses to NRC Set 14 Requests for Additional Information, Related License Renewal Application, RS-14-249, Results of Detailed Review Performed in Response to Request 1 of NRC RAI B.2.1.7-7 from Set 17, Related to License Renewal Application, RS-15-049, Units 1 and 2 - LRA Impact Assessment Associated with Earlier Responses to Set 29 RAI B.2.1 .5-1a, Related to the License Renewal Application, ULNRC-06118, Updated RAI Response to the License Renewal Application, Enclosures 1 and 2
|
MONTHYEARML13212A3672013-08-12012 August 2013 Plan for the Aging Management Program Regulatory Audits Regarding the Byron and Braidwood Nuclear Stations License Renewal Application Review Project stage: Other ML13262A0352013-10-0707 October 2013 Requests for Additional Information for the Review of the Byron Nuclear Station, Units 1 and 2, and Braidwood Nuclear Station, Units 1 and 2, License Renewal Application -Aging Management, Set 1 Project stage: RAI ML13281A5572013-10-28028 October 2013 Summary of Telephone Conference Call Held on September 25, 2013 Between the U.S. Nuclear Regulatory Commission and Exelon Generation Company, LLC, Concerning RAIs Pertaining to the Byron-Braidwood License Renewal Application (TAC Nos. MF187 Project stage: RAI ML13303B4632013-11-25025 November 2013 Summary of Telephone Conference Call Held on October 22, 2013, Between the U.S. Nuclear Regulatory Commission and Exelon Generation Company, LLC, Concerning RAI Set 3 for the Byron-Braidwood LRA Project stage: RAI ML13281A5742013-11-25025 November 2013 Requests for Additional Information for the Review of the Byron Nuclear Station, Units 1 and 2, and Braidwood Nuclear Station, Units 1 and 2, License Renewal Application - Aging Management, Set 3 (TAC Nos. MF1879, MF1880, MF1881, and MF1882 Project stage: RAI ML13281A5692013-12-12012 December 2013 Request for Additional Information for the Review of the Byron Nuclear Station Units 1 and 2, and the Braidwood Nuclear Station Units 1 and 2, LRA - Aging Management, Set 4 Project stage: RAI ML13282A3692013-12-13013 December 2013 Requests for Additional Information for the Review of the Byron Nuclear Station, Units 1 and 2, and Braidwood Nuclear Station, Units 1 and 2, License Renewal Application - Aging Management, Set 2 Project stage: RAI RS-13-273, Responses to NRC Requests for Additional Information, Set 3, Dated November 25, 2013, Related to the License Renewal Application2013-12-17017 December 2013 Responses to NRC Requests for Additional Information, Set 3, Dated November 25, 2013, Related to the License Renewal Application Project stage: Response to RAI RS-13-274, Response to NRC Requests for Additional Information, Set 5, Dated November 22, 2013, Related to License Renewal Application2013-12-19019 December 2013 Response to NRC Requests for Additional Information, Set 5, Dated November 22, 2013, Related to License Renewal Application Project stage: Response to RAI ML13317A0752014-01-13013 January 2014 Requests for Additional Information for Review of Byron, Units 1 & 2, and Braidwood, Units 1 & 2, License Renewal Applications, Set 6 Project stage: RAI RS-14-003, Bryon, Units 1 and 2, Response to NRC Requests for Additional Information, Set 2, Dated December 13, 2013, Related to the License Renewal Application2014-01-13013 January 2014 Bryon, Units 1 and 2, Response to NRC Requests for Additional Information, Set 2, Dated December 13, 2013, Related to the License Renewal Application Project stage: Response to RAI ML14017A0072014-01-16016 January 2014 Enclosure 1 to ULNRC-06072, Callaway Plant, Unit 1, Responses to Request for Additional Information (RAI) Sets 29 and 27 (RAI B2.1.6-4b) Project stage: Response to RAI ML14007A6582014-01-22022 January 2014 Requests for Additional Information for the Review of the Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2, License Renewal Application, Set 9 Project stage: RAI ML13309A9322014-01-23023 January 2014 Summary of Telephone Conference Call Held on October 31, 2013, Between the U.S. Nuclear Regulatory Commission and Exelon Generation Company, LLC, Concerning Draft Requests for Additional Information Pertaining to the Byron Station and Braid Project stage: Draft RAI ML13330A9322014-01-23023 January 2014 Bbs Record of Conference Call-Regarding-RAI Set 4 110513 Project stage: RAI ML13318A4152014-01-23023 January 2014 November 12, 2013, Summary of Telephone Conference Call Held Between the U.S. Nuclear Regulatory Commission and Exelon Generation Company, LLC, Concerning Draft Requests for Additional Information Pertaining to the Byron Station and Braidwo Project stage: Draft RAI RS-14-030, Response to NRC Requests for Additional Information, Set 6, Dated January 13, 2014, Related to License Renewal Application2014-02-0404 February 2014 Response to NRC Requests for Additional Information, Set 6, Dated January 13, 2014, Related to License Renewal Application Project stage: Response to RAI ML14006A0212014-02-0606 February 2014 Requests for Additional Information for the Review of the Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2, License Renewal Application- Aging Management, Set 8 Project stage: RAI ML14023A5642014-02-0707 February 2014 RAI for the Review of the Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2, License Renewal Application, Set 13 Project stage: RAI ML14030A5962014-02-10010 February 2014 Requests for Additional Information for the Review of the Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2, License Renewal Application, Set 12 Project stage: RAI ML14007A6032014-02-18018 February 2014 Request for Additional Information for the Review of the Byron Nuclear Station, Units 1 and 2, and Braidwood Nuclear Station, Units 1 and 2, LRA - Aging Management - Set 17 Project stage: RAI ML14034A0682014-02-18018 February 2014 Request for Additional Information for the Review of the Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2, License Renewal Application, Set 11 Project stage: RAI ML14035A5342014-02-20020 February 2014 January 22, 2014, Summary of Telephone Conference Call Held Between NRC and Exelon Generation Company, Llc., Concerning Draft Requests for Additional Information Pertaining to the Byron Station and Braidwood Station, License Renewal Applica Project stage: Draft RAI ML14035A1892014-02-20020 February 2014 Summary of Telephone Conference Call Held on January 30, 2014, Between the U.S. Nuclear Regulatory Commission and Exelon Generation Company, LLC, Concerning Draft Request for Additional Information Pertaining to the Byron Station and Braidw Project stage: Draft RAI ML14050A1222014-02-24024 February 2014 Summary of Telephone Conference Call Held on January 16, 2014, Between the U.S. Nuclear Regulatory Commission and Exelon Generation Company, LLC, Concerning RAI Set 7, Tor the Byron-Braidwood License Renewal Application (TAC Nos. MF1879, Mf Project stage: RAI ML14038A3362014-02-26026 February 2014 Request for Additional Information for the Review of the Byron Nuclear Station, Units 1 and 2, and Braidwood Nuclear Station, Units 1 and 2, License Renewal Application - Aging Management - Set 10 Project stage: RAI RS-14-051, Response to NRC Requests for Additional Information, Set 8, Dated February 6, 2014 Related to the License Renewal Application2014-02-27027 February 2014 Response to NRC Requests for Additional Information, Set 8, Dated February 6, 2014 Related to the License Renewal Application Project stage: Response to RAI ML14063A4952014-03-0404 March 2014 Response to NRC Requests for Additional Information, Set 13, Dated February 7, 2014 Re License Renewal Application Project stage: Response to RAI ML14051A4312014-03-0404 March 2014 Summary of Telephone Conferene Call Held on January 29, 2014, Between the NRC and Exelon Generating Company, Llc., Concerning RAI Set 10, for the Byron and Braidwood Station License Renewal Application (TAC Nos. MF1879, MF1880, MF1881, and Project stage: RAI ML14036A3102014-03-0404 March 2014 Summary of Telephone Conference Call Held on January 28, 2014, Between NRC and Exelon, Concerning RAI Set 10, for the Byron and Braidwood Station, LRA Project stage: RAI ML14050A1672014-03-0404 March 2014 Summary of Telephone Conference Call on January 23, 2014, Between U.S. Nuclear Regulatory Commission and Exelon Generation Company, LLC, Concerning RAI Set 11, for Byron-Braidwood License Renewal Application (TAC Nos. MF1879, MF1880, MF1881 Project stage: RAI ML14051A4282014-03-0606 March 2014 January 13, 2014, Summary of Telephone Conference Call Held Between the NRC and Exelon RAI Set 8, for the Byron and Braidwood Station LRA Project stage: RAI ML14050A0812014-03-0707 March 2014 Correction to Request for Additional Information B.2.1.10-1, Letter Dated February 7, 2014, for the Review of the Byron Station and Braidwood Station, Units 1 and 2, LRA Set 13 Project stage: RAI ML14064A3912014-03-11011 March 2014 Request for Additional Information for the Review of the Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2, License Renewal Application, Set 15 Project stage: RAI ML14064A4032014-03-11011 March 2014 Summary of Telephone Conference Call on February 27, 2014, Between U.S. Nuclear Regulatory Commission & Exelon Generation Company, LLC Concerning Draft Request for Additional Information Re Byron Station & Braidwood Station License Renewal Project stage: Draft RAI ML14058B1802014-03-11011 March 2014 Summary of Telephone Conference Call on February 18, 2014, Between U.S. Nuclear Regulatory Commission & Exelon Generation Company, LLC Concerning Draft Request for Additional Information Regarding Byron & Braidwood Stations, License Renewal Project stage: Draft RAI ML14072A3692014-03-13013 March 2014 AMP Audit Enclosure (3) Project stage: Other ML14071A6202014-03-13013 March 2014 Aging Management Programs Audit Report Regarding the Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2 (Tac Nos. MF1879, MF1880, MF1881, and MF1882) Project stage: Other ML14050A3042014-03-14014 March 2014 Scoping and Screening Methodology Audit Report Regarding the Byron Station, and Braidwood Station, Units 1 and 2, LRA Project stage: Other ML14058B1822014-03-18018 March 2014 Request for Additional Information for the Review of the Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2, License Renewal Application, Set 14 Project stage: RAI ML14051A5032014-03-20020 March 2014 Request for Additional Information for the Review of the Byron Nuclear Station Units 1 and 2, and Braidwood Nuclear Station, Units 1 and 2, License Renewal Application - Set 17 Project stage: RAI RS-14-084, Responses to NRC Requests for Additional Information, Set 10, Dated February 26, 2014 Related to the License Renewal Application2014-03-28028 March 2014 Responses to NRC Requests for Additional Information, Set 10, Dated February 26, 2014 Related to the License Renewal Application Project stage: Response to RAI ML14073A7052014-04-0303 April 2014 Summary of Telephone Conference Call Held on February 12, 2014, Between the NRC and Exelon, Concerning Drais Pertaining to the Byron and Braidwood Station, LRA Project stage: RAI ML14084A3352014-04-0303 April 2014 Request for Additional Information for the Review of the Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2, License Renewal Application, Set 16 Project stage: RAI ML14084A4882014-04-0707 April 2014 Summary of Telephone Conference Call Held Between NRC and Exelon Generation Company, LLC, Concerning Draft Request for Additional Information Pertaining to the Byron and Braidwood License Renewal Application Set 16 Project stage: Draft RAI ML14092A2612014-04-0707 April 2014 Request for Additional Information for the Review of the Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2, License Renewal Application, Set 20 Project stage: RAI ML14092A3462014-04-0707 April 2014 Project Manager Change for the License Renewal of Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2 Project stage: Other ML14094A3662014-04-0808 April 2014 Request for Additional Information for the Review of the Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2, License Renewal Application, Set 19 Project stage: RAI ML14093B2472014-04-10010 April 2014 Request for Additional Information for the Review of the Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2, License Renewal Application, Set 18 Project stage: RAI ML14099A4852014-04-17017 April 2014 Request for Additional Information for the Review of the Byron Station, Units 1 & 2, and Braidwood Station, Units 1 & 2, License Renewal Application, Set 21, Project stage: RAI 2014-02-27
[Table View] |
Request for Additional Information for the Review of the Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2, License Renewal Application, Set 27| ML14135A540 |
| Person / Time |
|---|
| Site: |
Byron, Braidwood  |
|---|
| Issue date: |
05/21/2014 |
|---|
| From: |
Robinson L License Renewal Projects Branch 1 |
|---|
| To: |
Gallagher M Exelon Generation Co |
|---|
| Robinson L, 415-4115 |
| References |
|---|
| TAC MF1879, TAC MF1880, TAC MF1881, TAC MF1882 |
| Download: ML14135A540 (6) |
|
Text
May 21, 2014 Mr. Michael P. Gallagher Vice President, License Renewal Projects Exelon Generation Company, LLC 200 Exelon Way Kennett Square, PA 19348
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW OF THE BYRON STATION, UNITS 1 AND 2, AND BRAIDWOOD STATION, UNITS 1 AND 2, LICENSE RENEWAL APPLICATION, SET 27 (TAC NOS. MF1879, MF1880, MF1881, AND MF1882)
Dear Mr. Gallagher:
By letter dated May 29, 2013, Exelon Generation Company, LLC, submitted an application pursuant to Title 10 of the Code of Federal Regulations Part 54, to renew the operating licenses NPF-37, NPF-66, NPF-72, and NPF-77 for Byron Station, Units 1 and 2, and Braidwood Station, Units 1 and 2, respectively, for review by the U.S. Nuclear Regulatory Commission (NRC or the staff). The staff is reviewing the information contained in the license renewal application and has identified, in the enclosure, areas where additional information is needed to complete the review.
These requests for additional information were discussed with John Hufnagel, and a mutually agreeable date for the response is within 30 days from the date of this letter. If you have any questions, please contact me at 301-415-4115 or e-mail Lindsay.Robinson@nrc.gov.
Sincerely,
/RA/
Lindsay R. Robinson, Project Manager Projects Branch 1 Division of License Renewal Office of Nuclear Reactor Regulation Docket Nos. 50-454, 50-455, 50-456, and 50-457
Enclosure:
Request for Additional Information cc: Listserv
ML14135A540
- concurred via email OFFICE LA:DLR PM: RPB1:DLR BC:RPB1:DLR PM:RPB1:DLR NAME YEdmonds LRobinson YDiazSanabria (JDaily for)
LRobinson DATE 5/20/14 5/20/14 5/21/14 5/21/14
Letter to M.P. Gallagher from Lindsay R. Robinson dated May 21, 2014
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW OF THE BYRON STATION, UNITS 1 AND 2, AND BRAIDWOOD STATION, UNITS 1 AND 2, LICENSE RENEWAL APPLICATION, SET 27 (TAC NOS. MF1879, MF1880, MF1881, AND MF1882)
DISTRIBUTION EMAIL:
PUBLIC RidsNrrDlr Resource RidsNrrDlrRpb1 Resource RidsNrrDlrRarb Resource RidsNrrDlrRasb Resource RidsOgcMailCenter RidsNrrPMByron Resource RidsNrrPMBraidwood Resource LRobinson DMcIntyre, OPA JMcGhee, RIII EDuncan, RIII JBenjamin, RIII AGarmoe, RIII JRobbins, RIII VMitlyng, RIII PChandrathil, RIII
ENCLOSURE BYRON STATION, UNITS 1 AND 2, AND BRAIDWOOD STATION, UNITS 1 AND 2, LICENSE RENEWAL APPLICATION REQUEST FOR ADDITIONAL INFORMATION, SET 27 (TAC NOS. MF1879, MF1880, MF1881, MF1882)
RAI B.2.1.16-1a Applicability:
Byron Station (Byron) and Braidwood Station (Braidwood), all units
Background:
The applicants response, dated March 13, 2014, to Request 1 for request for additional information (RAI) B.2.1.16-1 states that the Fire Water System program will be enhanced to include non-destructive examinations (NDE) capable of detecting internal flow blockage (e.g.,
digital radiography) or internal visual inspections. The response also states that inspections will be performed by opening a flushing connection at the end of one [emphasis added by NRC]
main in each structure containing in-scope water-based fire suppression systems.
Issue:
The staff notes that the National Fire Protection Association (NFPA) 25, Section 14.2.2, requires an internal inspection of every other wet pipe system (in buildings with multiple wet pipe systems) and that the alternate systems (not inspected during the previous inspection) be inspected during the next inspection. Since the response only stated that one main in each structure will be opened, it is not clear whether there are multiple wet pipe systems in any of the structures containing in-scope fire water systems and, if so, whether all wet pipe systems will be inspected as stated in NFPA 25.
The staff also notes that LR-ISG-2012-02 AMP XI.M27 Table 4a limits the alternative NDE methods, which are permitted by NFPA 25, Sections 14.2.1.1 and 14.3.2.3, to those that can ensure that flow blockage will not occur. Because of its similarity to raw water applications in fire water systems, the staff further notes that the Electric Power Research Institute (EPRI)
TR-102063, Guide for the Examination of Service Water System Piping, cites radiography as an effective NDE method capable of measuring the extent of occlusions or biofouling conditions.
Although the EPRI guide includes ultrasonic testing, the discussion of its capability is limited to wall thickness measurement. Because the response proposes digital radiography as an example and not the only method, it was not clear how other NDE methods, if used, would be demonstrated to be capable of detecting flow blockage.
Request:
- 1.
State whether there are multiple wet pipe systems in any of the structures containing in-scope fire water systems and, if there are, confirm that internal inspections will be conducted as stated in NFPA 25, Section 14.2.2, or provide the basis for not conducting the internal inspections on every other wet pipe system every five years.
- 2.
If NDE methods other than digital radiography are used, state how the other NDE methods will be demonstrated to be capable of detecting flow blockage.
RAI B.2.1.16-1b Applicability:
Byron and Braidwood
Background:
RAI B.2.1.16-1 requested that either: (a) it is confirmed that follow-up volumetric examinations will be conducted whenever internal fire water system visual inspections detect surface irregularities indicative of material loss below nominal wall thickness [emphasis added by NRC]; or (b) the bases be provided for why the visual inspection alone will provide reasonable assurance that the current licensing basis intended functions of in-scope components will be met.
The applicants response, dated March 13, 2014, to RAI B.2.1.16-1 states that noticeable deposits in excess of a normal oxide layer, which could be indicative of wall loss below nominal, are documented; inspection results that are unusual or unexpected (e.g., surface irregularities indicative of significant loss of material [emphasis added by NRC]) are documented in the corrective action program for evaluation; and, based on the results of the evaluation, appropriate corrective actions are taken including repair, replacement, or followup volumetric examinations to quantify the remaining wall thickness, as applicable.
Issue:
The staff noted that LR-ISG-2012-02 AMP XI.M27 states that, [i]nternal visual inspections used to detect loss of material are capable of detecting surface irregularities that could be indicative of wall loss below nominal pipe wall thickness due to corrosion and corrosion product deposition. Where such irregularities are detected, followup volumetric examinations are performed. Based on the wording surface irregularities indicative of significant loss of material, it is not clear to the staff that surface irregularities indicative of wall loss below nominal would be documented in the corrective action program. It is also not clear to the staff that volumetric wall thickness measurements would be conducted when visual inspection results reveal surface irregularities that could be indicative of wall loss below nominal pipe wall thickness.
Request:
- 1.
State whether surface irregularities indicative of wall loss below nominal would be documented in the corrective action program.
- 2.
State whether volumetric wall thickness measurements would be conducted when visual inspection results reveal surface irregularities that could be indicative of wall loss below nominal pipe wall thickness.
- 3.
If not, state the basis for the portion(s) of the response that represent an exception to LR-ISG-2012-02 AMP XI.M27.
RAI 3.5.2.10-1 Applicability:
Byron and Braidwood
Background:
Title 10 of the Code of Federal Regulations (10 CFR) Part 54.21 (a)(3) states that for structures and components (SCs) subject to an aging management review (AMR) it shall be demonstrated that the effects of aging will be adequately managed so that the intended function(s) will be maintained consistent with the current licensing basis for the period of extended operation.
LRA Table 3.5.2-10, Main Steam & Auxiliary Feedwater Tunnels and Isolation Valve Rooms Summary of Aging Management Evaluation, states that polymer blowout panels exposed to air-indoor (uncontrolled) or air-outdoor will be managed for change in material properties by the Structures Monitoring Program. The AMR items cite generic note J, which states that neither the component nor the material and environment combination is evaluated in NUREG-1801, Generic Aging Lessons Learned (GALL) Report, Revision 2. The AMR items also cite plant specific note 1, which states that the blowout panels are constructed of extruded polystyrene.
Issue:
Although the scope of the Structures Monitoring Program has been enhanced to include inspection of blowout panels, the parameters monitored or inspected and acceptance criteria for this material have not been specified in the program elements. Unlike GALL Report aging management programs (AMPs) XI.M36, External Surfaces Monitoring of Mechanical Components, and XI.M38, Inspection of Internal Surfaces in Miscellaneous Piping and Ducting Components, GALL Report AMP XI.S6, Structures Monitoring Program, does not include examples of inspection parameters for polymeric components. Based on the staffs review of this material exposed to an air-indoor and air-outdoor environment, the staff noted that at high temperatures, this material may begin to degrade. The staff does not have sufficient information to conclude that the visual inspections performed under the Structures Monitoring Program would identify a change in material properties, prior to a loss of intended function.
Request:
State how the visual inspections performed under the Structures Monitoring Program would identify a change in material properties for these components, and provide the acceptance criteria by which they would be evaluated.