ML13333A423
| ML13333A423 | |
| Person / Time | |
|---|---|
| Site: | San Onofre |
| Issue date: | 10/23/1979 |
| From: | Baskin K Southern California Edison Co |
| To: | Ziemann D Office of Nuclear Reactor Regulation |
| References | |
| TAC-48143 NUDOCS 7910300307 | |
| Download: ML13333A423 (40) | |
Text
Southern California Edison Company P. 0. BOX 800 2244 WALNUT GROVE AVENUE ROSEMEAD, CALIFORNIA 91770 K. P. BASKIN TELEPHONE
- MANAGER, GENERATION ENGINEERING 213-572-1401 October 23, 1979 Director, Office of Nuclear Reactor Regulation Attention:
Mr. D. L. Ziemann, Chief Operating Reactors Branch #2 Division of Operating Reactors U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Gentlemen:
Subject:
Docket No. 50-206 Operating License No. DPR-13 Fire Protection Program Review San Onofre Nuclear Generating Station Unit 1 This letter is provided in response to two NRC Staff requests for information concerning their ongoing review of the fire protection program at San Onofre Unit 1. The requests involve:
(1) the schedule for submittal of a revised plan for safe shutdown following a fire, as requested in your letter dated September 14, 1979, and (2) the additional design information for certain items identified in the Fire Protection Safety Evaluation Report dated July 19, 1979.
Our responses to each of these requests are discussed below.
- 1. Response to September 14, 1979 Letter By letter dated January 15, 1979, we submitted for NRC Staff review, a conceptual plan for providing the capability to establish a safe shutdown of San Onofre Unit 1, following a fire in the 4160 Volt Switchgear Room or the Lube Oil Reservoir Area.
The conceptual plan included the use of a charging pump and was not dependent on the Chemical and Volume Control System test pump. As discussed in the NRC Staff's Fire Protection Safety Evaluation Report dated July 19, 1979, the modifications associated with the conceptual plan have been deferred pending completion of the integrated assessment of potential modifications identified by review of station design and operation in connection with the Systematic Evaluation Program (SEP).
Since the information requested in your letter dated September 14, 1979 is dependent upon final engineering of the safe shutdown capability, submittal of that information will be delayed until after the integrated assessment of SEP modifications, at the time when final engineering of the modifications is in progress.
The fire protection criteria included in the enclosure to your September 14, 1979 letter will be used as guidance in the final engineering of the safe shutdown capability.
1-910 300 0
Mr. D. L. Zieman
-2
- 2. Additional Design Information The Fire Protection Safety Evaluation Report dated July 19, 1979 requires that additional design information be supplied to the NRC Staff.
The additional design information is required for the items of Section 3.0 of the Fire Protection SER which are identified with an asterisk. The enclosure to this letter contains the required information for those modifications which are to be completed by the end of the next refueling outage, now scheduled for March April, 1980 and also included is the information for the 480 volt room halon system which has been deferred to SEP review.
If you have any questions or desire further information regarding this submittal, please contact me.
Very truly yours, Enclosure cc:
M. Antonetti (Gage Babcock & Associates)
ENCLOSURE ADDITIONAL DESIGN INFORMATION FIRE PROTECTION PROGRAM REVIEW SAN ONOFRE UNIT 1 The following sections provide the design information requested in the Fire Protection Safety Evaluation Report (SER).
The information is arranged by station area or major system with each section title page identifying the SER items covered.
SECTION 1 This section includes the additional information requested for the following item of the Fire Protection Safety Evaluation Report for San Onofre Unit 1.
3.1.7 Gas Suppression Systems An automatic total flooding Halon 1301 gas suppression system will be provided for the 4160 volt switchgear room.
4 KV SWITCHGEAR ROOM FIRE SUPPRESSION SYSTEM 1.0 DESIGN CRITERIA The primary design objective of the Fire Detection and Suppression System for the 4 kV room is to protect the cable trays from propagation of fire by early detection and extinguishment.
The Fire Detection and Suppression System for the room shall encompass the surveillance of the room by an early warning Fire Detection System and the Halon Fire Suppression System.
The Halon Fire Suppression System shall provide the Halon to extinguish a fire upon a signal from the Detection System or by manual actuation.
The detail criteria shall include:
1.1 The System shall be capable of a second Halon application, manually, immediately following the initial application.
1.2 The Halon Fire Suppression System shall be a fixed pipe system.
1.3 The Halon Fire Suppression System shall be designed in accordance with NFPA 12A.
1.4 As much of the Fire Suppression System as possible shall be located outside of the room being protected and in a minimum fire hazard area.
1.5 Upon detection of a fire or release of Halon the room shall be automatically sealed to prevent loss of Halon.
1.6 Design concentrations of Halon shall not be less than 5% by volume nor greater than 10% by volume.
1.7 Discharge of the Halon shall not cause the rupture of penetrations, walls, doors or the openings to the room.
1.8 The Halon vessels and distribution piping shall be designed such that the equipment cannot fall upon or damage safety-related components.
1.9 The Halon fire suppression system shall be sized with sufficient capacity to supply the required Halon concentration quickly to extinguish any fire in the room.
1.10 The fire detection system shall include the existing high voltage ionization (smoke) detectors and local detection panel.
1.11 Halon release shall be automatic, resulting from a 2 out of 2 fire detection system input signal. Manual release shall also be provided.
1.12 The detection and Halon control system circuits, including the detector circuits, detection actuation signaling circuits and Halon release circuits shall be electrically supervised, redundant and routed in separate cable and conduits.
-2 1.13 The Halon Control System shall meet NFPA 72D requirements.
1.14 The Detector installation shall meet NFPA 72E Appendix A requirements.
1.15 The Main Control Room (MCR) and local panel shall be provided with alarm and indication for any electrical malfunction of the fire detection or Halon Control System circuits.
1.16 The MCR shall be provided with alarm and indication of deluge valve actua tion.
1.17 The MCR and local panel shall be provided with alarm and zone indication when a fire detector goes into an alarm condition.
1.18 The total Fire Suppression System for the room shall be powered from a 120 AC utility bus which shall be connected to the diesel generators upon loss of off site power.
1.19 The Halon Control System panels shall be located outside the area being protected.
2.0 SYSTEM DESCRIPTIONS 2.1 The Fire Detection System 2.1.1 Detector Installation Pyrotronics DIS 3/5A ionization detectors shall be mounted on the ceiling of the 4 kV switchgear room in two independent and redun dant circuits.
Each detection circuit cabling shall be routed in separate cable and conduit and be connected to a separate zone alarm unit in the local detection panel.
Detector spacing for each of the two circuits shall meet NFPA 72E Appendix A requirements and manufacturers recommendations for detection coverage of the entire 4 kV switchgear room. The detec tors shall operate on the ionization principle and shall detect the presence of aerosols from the first incipient, smoldering stages of a fire.
2.1.2 Detection System Supervision The Detection System shall be continuously electrically supervised so that a malfunction in the detection circuitry shall be immediately recognized, and a trouble buzzer and indication in the local and MCR panel shall be energized. The trouble signal shall not be extin guishable until there is no longer a malfunction.
NOTE: There are an existing local and remote (MCR) fire detection panels with a separate indicating light for the 4 kV switch gear room which will light and alarm sound upon detection of a fire in the 4 kV room. System malfunction will also be alarmed and indicated from these panels.
-3 2.1.3 Alarm Condition When the presence of fire is detected by a detector, the detector shall go into an alarm condition, a lamp in the base of the detector shall light, the alarm bell in the 4 kV switchgear room shall sound, the zone alarm lamp and bell in the MCR shall energize and the normally lite green lights above the 4 kV switchgear room doors, both inside and outside, shall turn off and flashing red lights shall light.
Hence, anyone in or entering the 4 kV switchgear room shall be able to determine that a fire condition exists and identify the detector(s) which are in an alarm condition, provided smoke does not obscure the view.
The MCR operator shall be aware of the fire condition and location.
He will expect further signals from the FP annunci ator to follow immediately.
NOTE: A Compudyne annunciator shall be installed in the MCR which is dedicated to the Fire Protection System.
Reset of the MCR or local detection panels by the operator shall not be possible until the detector(s) in an alarm condition are restored to normal.
2.2 Halon Control System 2.2.1 Halon Control System Supervision The Halon Control System supervises the signaling circuitry between the detection and Halon systems. Malfunction of this circuitry shall be indicated and annunciated in the local Halon Control Panel.
The alarm condition signal circuits from the Detection System to the Halon Control System shall be redundant and installed in separ ate conduits over different routes.
2.2.2 Alarm Condition Upon receipt of the Detection System alarm condition signal, the Halon Control System shall cause the vent fan to shut-off, the smoke dampers to close, door releases to actuate and provide signals to the MCR FP annunciator if the 4 kV switchgear room is not properly closed off to seal in the Halon.
When the Halon is discharged, a signal shall be provided to the MCR FP annunciator to let the operator know that the Halon System is released as required.
In the event that Halon discharge is initiated by operation of manual mechanical release or electric switch, all Halon Control System functions shall occur as if the System had been initiated automati cally.
2.2.3 Halon Discharge Two banks of Halon cylinders shall be capable of being discharged manually or automatically.
Automatic discharge of one cylinder bank shall occur, after a short time delay, when an alarm condition is experienced in both detector circuits and signals are then provided from the Detection System.
The other bank shall be subsequently discharged when the transfer switch has been manually operated.
The short time delay prior to the initial Halon discharge shall pro vide sufficient time for the smoke dampers to close and doors to close, thereby isolating the room.
It will also allow personnel to evacuate.
3.0 System Testing 3.1 Detection System Testing After detector sensitivity checking, in situ testing shall be con ducted to demonstrate adequate time response of the detectors to a single simulated fire.
Aerosols which simulate the burning of cable insulation shall be released in the 4 kV switchgear room at a specific point. The response time and location of the detectors which go into an alarm condition shall be recorded.
This procedure shall be repeated for several elevations and locations within the 4 kV switch
- gear room. Normal environmental and air flow conditions shall exist during the testing.
3.2 Halon Control System Testing The Halon Control System shall be tested to verify that all functions to seal the 4 kV switchgear room occur upon receipt of an alarm condition signal from the Detection System or the manual discharge of the Halon.
3.3 Halon Discharge Testing After the Halon discharge piping system has been installed and leaks checked, one bank of Halon cylinders shall be replaced by a set of Freon 12 cylinders for the purpose of testing. The Freon 12 shall be released into the room and the concentration monitored from at least three locations within the room. The tests shall be conducted in the presence of NML using previously approved test report forms.
The test reports shall be submitted to NML for approval.
SECTION 2 This section includes the additional information requested for the following item of the Fire Protection Safety Evaluation Report for San Onofre Unit 1.
3.1.7 Gas Suppression Systems An automatic total flooding Halon 1301 gas suppression system will be provided for the 1480 volt switchgear room.
This item has been deferred to SEP review.
480V SWITCHGEAR ROOM FIRE SUPPRESSION SYSTEM 1.0 DESIGN CRITERIA The primary design objective of the Fire Detection and Suppression System for the 480V room is to protect the cable trays from propagation of fire by early detection and extinguishment.
The Fire Detection and Suppression System for the room shall encompass the surveillance of the room by an early warning Fire Detection System and the Halon Fire Suppression System.
The Halon Fire Suppression System shall provide the Halon to extinguish a fire upon a signal from the Detection System or by manual actuation.
The detail criteria shall include:
1.1 The System shall be capable of a second Halon application, manually, immediately following the initial application.
1.2 The Halon Fire Suppression System shall be a fixed pipe system.
1.3 The Halon Fire Suppression System shall be designed in accordance with NFPA 12A.
1.4 As much of the Fire Suppression System as possible shall be located outside of the room being protected and in a minimum fire hazard area.
1.5 Upon detection of a fire or release of Halon the room shall be automatically sealed to prevent loss of Halon.
1.6 Design concentrations of Halon shall not be less than 5% by volume nor greater than 10% by volume.
1.7 Discharge of the Halon shall not cause the rupture of penetrations, walls, doors or the openings to the room.
1.8 The Halon vessels and distribution piping shall be designed such that the equipment cannot fall upon or damage safety-related components.
1.9 The Halon fire suppression system shall be sized with sufficient capacity to supply the required Halon concentration quickly to extinguish any fire in the room.
1.10 The fire detection system shall include the existing high voltage ionization (smoke) detectors and local detection panel.
1.11 Halon release shall be automatic, resulting from a 2 out of 2 fire detection system input signal. Manual release shall also be provided.
1.12 The local detection panel and halon control panel shall be located outside, but adjacent to, the area being protected.
-2 1.13 The local detection and halon control panel circuits, including the detector circuits, detection actuation signalling circuits and halon release circuits, shall be electrically supervised, redundant and routed in separate cable and conduits.
1.14 The Halon Control System shall meet NFPA 72D requirements.
1.15 The Detector installation shall meet NFPA 72E Appendix A requirements.
1.16 The Main Control Room (MCR) and applicable local panel shall be provided with alarm and indication for any electrical malfunction of the Fire detec tion or halon control system circuits.
1.17 The MCR shall be provided with alarm and indication of deluge valve actuation.
1.18 The MCR and local detection panel shall be provided with alarm and zone indication when a fire detector goes into an alarm condition.
2.0 SYSTEM DESCRIPTIONS 2.1 The Fire Detection System 2.1.1 Detector Installation Pyrotronics DI$ 3/5A ionization detectors shall be mounted on the ceiling of the 480V switchgear room in two independent and redun dant circuits.
Each detection circuit cabling shall be routed in separate cable and conduit and be connected to a separate zone alarm unit in the local detection panel.
Detector spacing for each of the two circuits shall meet NFPA 72E Appendix A requirements and manufacturers recommendations for detection coverage of the entire 480V switchgear room. The detec tors shall operate on the ionization principle and shall detect the presence of aerosols from the first incipient, smoldering stages of a fire.
2.1.2 Detection System Supervision The Detection System shall be continuously electrically supervised so that a malfunction in the detection circuitry shall be immediately recognized, and a trouble buzzer and indication in the local and MCR panel shall be energized. The trouble signal shall not be extin guishable until there is no longer a malfunction.
NOTE: There are existing local and remote (in MCR) fire detection panel with a separate indicating light for the 480V switch gear room which will light and alarm sound upon detection of a fire in the 480V room. System malfunction will also be alarmed and indicated from these panels.
-3 2.1.3 Alarm Condition When the presence of fire is detected by a detector, the detector shall go into an alarm condition, a lamp in the. base of the detector shall light, the zone alarm lamp and bell in the local panel and MCR shall energize and the normally lite green lights above the 480V switchgear room doors, both inside and outside, shall turn off and flashing red lights shall light.
Hence, anyone in or entering the 480V switchgear room shall be able to determine that a fire condition exists and identify the detector(s) which are in an alarm condition, provided smoke does not obscure the view.
The MCR operator shall be aware of the fire condition and location. He will expect further signals from the FP annuncia tor to follow immediately.
NOTE: A Compudyne annunciator shall be installed in the MCR which is dedicated to the Fire Protection System.
Reset of the MCR or local detection panels by the operator shall not be possible until the detector(s) in an alarm condition are restored to normal.
2.2 Halon Control System 2.2.1 Halon Control System Supervision The Halon Control System supervises the signaling circuitry between the detection and Halon systems. Malfunction of this circuitry shall be annunciated and indicated in the MCR in the local Halon Control Panel.
The alarm condition signal circuits from the Detection System to the Halon Control System shall be redundant and installed in separ ate conduits over different routes.
2.2.2 Alarm Condition Upon receipt of the Detection System alarm condition signal, the Halon Control System shall cause the vent fan to shut-off, the smoke dampers to close, door releases to actuate and provide signals to the MCR FP annunciator if the 4 kV switchgear room is not properly closed off to seal in the Halon.
When the Halon is discharged, a signal shall be provided to the MCR FP annunciator to let the operator know that the Halon System is released as required.
In the event that Halon discharge is initiated by operation of manual mechanical release or electric switch, all Halon Control System functions shall occur as if the System had been initiated automatically.
-4 2.2.3 Halon Discharge Two banks of Halon cylinders shall be capable of being discharged manually or automatically.
Automatic discharge of one cylinder bank shall occur, after a short time delay, when an alarm condition is experienced in both detector circuits and signals are then provided from the Detection System.
The other bank shall be subsequently discharged when the transfer switch has been manually operated.
The short time delay prior to the initial Halon discharge shall pro vide sufficient time for the smoke dampers to close and doors to close, thereby isolating the room.
It will also allow personnel to evacuate.
3.0 System Testing 3.1 Detection System Testing After detector sensitivity checking, in situ testing shall be con ducted to demonstrate adequate time response of the detectors to a single simulated fire. Aerosols which simulate the burning of cable insulation shall be released in the 480V switchgear room at a specific point.
The response time and location of the detectors which go into an alarm condition shall be recorded. This procedure shall be repeated for several elevations and locations within the 480V switchgear room.
Normal environmental and air flow condi tions shall exist during the testing.
3.2 Halon Control System Testi The Halon Control System shall be tested to verify that all functions to seal the 480V switchgear room occur upon receipt of an alarm condition signal from the Detection System or the manual discharge of the Halon.
3.3 Halon Discharge Testing After the Halon discharge piping system has been installed and leaks checked, one bank of Halon cylinders shall be replaced by a set of Freon 12 cylinders for the purpose of testing. The Freon 12 shall be released into the room and the concentration monitored from at least three locations within the room. The tests shall be conducted in the presence of NML using previously approved test report forms.
The test reports shall be submitted to NML for approval.
SECTION 3 This section includes the additional information requested for the following item of the Fire Protection Safety Evaluation Report for San Onofre Unit 1.
3.1.15 Control of Combustibles An automatic deluge system will be provided to protect transformers 2 and 3.
0 0
STATION SERVICE TRANSFORMERS 2 AND 3 FIRE SUPPRESSION SYSTEM 1.0 GENERAL DESIGN CRITERIA The primary design objective of this fire suppression system is to provide auto matic actuation of a water sprinkler system by a detection system in order to prevent the spread of fire to adjacent safety related cables and equipment.
The following are the detail criteria which support the primary design objective:
1.1 Fire detection shall be performed by a line-of-sight type of detector which is recommended for flammable liquid fire detection and outdoor application.
1.2 The fire detection system shall be designed, fabricated, installed and tested per NFPA 72D and 72E Appendix A requirements.
1.3 Indication and annunciation shall be provided at the local detection panel and in the MCR in the event of system fire detection or system electrical malfunction.
1.4 The local detection panel(s) shall be located out of the area being pro tected but in an adjacent area.
1.5 The actuation portion of the system, including deluge valve, solenoid valve and pressure switches shall be located out of the area being protected.
1.6 Water spray actuation shall be automatic, resulting from a I out of 2 de tection system input signal. Manual actuation shall also be provided.
1.7 The spray system will be designed as a dry-pipe deluge system.
1.8 The System's spray nozzles will be located directly above the transformers and pointed down so that they can spray the tops of the transformers and curb enclosed area with no blockage by structural members or other obstacles.
1.9 The MCR shall be provided with annunciation when flow occurs through the deluge valve.
1.10 Spray nozzles shall be designed to NFPA 15 and shall be capable of pro ducing a solid cone fine spray in a downward directional pattern.
1.11 The water source for this system shall be the same as that for the existing sprinkler system.
1.12 Sprinkler System design pressures at the interface with the remainder of the plant fire protection system are as follows:
Minimum - 75 psig Normal - 125 psig Maximum - 165 psig
-2 The Sprinkler System shall be designed to withstand the effects of water hammer when water is supplied at 165 psig.
1.13 The Sprinkler System shall be designed, fabricated, installed and tested to comply with NFPA 13 and 15.
1.14 All equipment shall be UL listed or FM approved.
1.15 Design water density is 0.15 gpm/ft 2 2.0 SYSTEM DESCRIPTIONS 2.1 The Fire Detection System 2.1.1 Detector Installation Each transformer shall have a Pyrotronic Model C-7050B ultra violet flame detector mounted directly above and pointing down at the transformer.
The cone of vision of each detector shall overlap.
The two detectors shall be in one circuit with either detector being capable of providing the alarm condition signal and sprinkler system actuation signal.
2.1.2 Detection System Supervision The detection system shall be continuously supervised so that a malfunction in the detection circuitry shall be immediately recog nized, and a trouble buzzer and indication energized locally and in the Main Control Room (MCR).
The trouble signal shall not be extinguishable until there is no longer a malfunction.
The mal functions shall include loss of power, open circuit, short circuit and grounding.
2.1.3 Detection System Alarm Condition and Sprinkler When a detector goes into an alarm condition, an alarm and indi cation shall be provided in the local detection panel and MCR. At the same time, an actuation signal shall be sent to the sprinkler system solenoid.
The actuation signal shall not be capable of being extinguished from the control room.
The alarms in the local detection panel and MCR may be silenced but the indication shall be maintained until the detector alarm condition has been reset.
2.2 Sprinkler System When solenoid valve is energized, the deluge valve shall open and water shall flow to the nozzles.
Flow of water through the deluge valve shall cause a pressure switch to send an annunciation signal to the MCR that the sprinkler system has been actuated.
The solenoid shall remain energized until the detection system has been reset.
-3 The deluge valve may be released by manually actuating the Emergency Trip Valve adjacent to the deluge valve.
Except for the detectors, all other detection and actuation equipment shall be located outside the transformer area.
3.0 SYSTEM TESTING 3.1 Detection System Testing The ultraviolet detectors shall be equipped with a self test feature which permits optical surfaces and electrical circuitry to be completely checked from a local test. station.
The detectors shall be thus checked prior to actuation testing.
After this self test and calibration, a special "flashlight" shall be used to simulate a fire to the detector. This "flashlight" shall be directed at each detector and the detection system monitored for proper response.
3.2 Water Spray Discharge Testing The piping system shall be pressure tested and all operating parts required to achieve manual and automatic actuation of the water spray shall also be tested.
Testing shall be in the presence of an NML respresentative. Testing shall be performed in accordance with applicable NFPA codes and standards.
No water shall actually be discharged onto the transformers.
SECTION 4 This section includes the additional information requested for the following item of the Fire Protection Safety Evaluation Report for San Onofre Unit 1.
3.1.1 Fire Detection Systems Early warning automatic fire detection systems will be provided in the folllowing areas:
(1) In the vital bus cabinet in the control room.
VITAL BUS CABINET FIRE DETECTION 1.0 DESIGN CRITERIA The primary design objective is to install fire detectors in each Vital Bus Cabinet cubicle to detect the first incipient, smoldering stages of a fire.
Detail design criteria to support this objective are:
1.1 Ionization type smoke detectors shall be used.
1.2 The detectors shall be electrically supervised so that any malfunction shall be indicated and alarmed in the MCR.
The indication shall be capable of reset only after the detection circuitry has been restored to normal.
1.3 When a detector goes into an alarm condition, an alarm and indication shall be provided in the MCR.
The indication shall be capable of reset only after the detector in an alarm condition has been restored to normal.
1.4 The detectors shall be U.L. listed or F.M. approved.
1.5 The detectors shall be included in the existing MCR area detection system circuit.
2.0 DETECTION SYSTEM DESCRIPTION When a malfunction in the detector circuit occurs, the supervisory function of the system causes a trouble buzzer and indication in the MCR to energize. While the buzzer can be silenced, the trouble lamp cannot be extinguished until the malfunc tion has ceased.
When one of the new pyrotronics DIS 514 high voltage ionization detectors in the vital bus cabinet goes into an alarm condition, a lamp in the base of the detector lights, and an alarm bell and zone indicating lamp in the MCR energizes.
While the alarm bell may be silenced, the lamp cannot be extinguished until the detector in an alarm condition has been reset.
3.0 SYSTEM TESTING After detector sensitivity checks have been conducted, in situ testing shall be conducted to demonstrate responsiveness of the detection system to a fire.
Aerosols simulating combustibles from the area shall be released in regulated quantities and the time response of the system recorded. Normal environmental conditions will be maintained during testing.
SECTION 5 This section includes the additional information requested for the following iteims of the Fire Protection Safety Evaluation Report for San Onofre Unit 1.
3.1.1 Fire Detection Systems Early warning fire detection systems will be provided in the following areas:
(5) Additional smoke detectors-will be provided in the turbine lube oil reservoir area of the turbine building.
3.1.5 Water Suppression Systems The east wall of the 480 volt switchgear room will be protected by a directed water spray system.
A sectionalized directed water spray system will be provided to protect the large concentration of cable trays in the north turbine building area.
The north wall and structural steel members in the turbine lube oil area will be protected by'a direct water spray system.
A fuse link wet-pipe area sprinkler system will be provided for the large concentration of combustibles in the north turbine area.
3.1.6 Foam Suppression System The deluge system for the lube oil reservoir and conditioner will be modified to provide an automatic foam suppression system.
LUBE OIL RESERVOIR AND CONDITIONER AREA 1.0 GENERAL The fire detection and suppression systems for the area include the following:
1.1 Foam Fire Suppression System with accompanying Fire Detection System.
1.2 Cable Tray Water Spray System with accompanying Fire Detection System.
1.3 Area Fusible Link Sprinkler System.
1.4 Area Fire Detection System.
Each of the above four systems are covered separately in the following pages.
2.0 FOAM SYSTEM 2.1 General Design Criteria The primary design objective of the Foam Fire Suppression and Detection System is to provide automatic suppression of oil fires in the vicinity of the lube oil storage tank and conditioner and to prevent the spread of fire to other areas of the plant.
The following are the detail criteria which support the primary design objective:
2.1.1 Curbing shall be installed around the equipment to be protected.
The curbing shall contain oil spills and allow proper action of the foam systems.
2.1.2 The foam system shall Ye sized to provide a minimum average coverage of 0.15 gpm/ft.
2.1.3 The systems shall be sized to allow complete submergence of an oil spill to a depth of 2 feet.
2.1.4 The water source for the foam systems shall be the same as that for the existing sprinkler system.
2.1.5 Foam Concentrate storage shall be maintained in an area where high ambient temperatures (greater than 120 0F) will be encoun tered.
Foam storage capacity will guarantee a minimum flow time of 10 minutes.
2.1.6 Provision shall be made to test for deterioration of foam concen trate quality without disabling the system.
2.1.7 System Actuation shall be automatic, resulting from a 2 out of 2 fire detector system input signal. Manual actuation of the foam proportioner shall also be provided.
-2 2.1.8 Inadvertent discharge of the foam system shall not impair the operation of safety related systems.
2.1.9 Fire detection shall be performed by a line-of-sight type of detector which is recommended for flammable liquids.
2.1.10 The detection system shall be provided with local alarms as well as alarms in the control room.
2.1.11 Provision shall be made to prevent excess water from flooding the surroundings or spreading oil away from the curbed area and to minimize oil overflow into the station sump and drain system.
2.1.12 All equipment shall be FM approved or UL listed.
2.1.13 The foam system shall be an approved Foam Water Sprinkler System employing Aqueous Film Foaming Foam (AFFF).
2.1.14 The foam system shall be designed, fabricated, installed and tested in compliance with NFPA 11, 13 and 16.
2.1.15 The fire detection system shall be designed, fabricated, installed and tested per NFPA 72D and 72E Appendix A requirements.
2.1.16 Foam System discharge nozzles will be located so that they are capable of spraying the tops of the lube oil reservoir, conditioner and other equipment with no blockage by structural members or other obstacles.
2.1.17 The actuation portion of the system, including deluge valve, solenoid valve and pressure switches shall be located out of the area being protected.
2.1.18 Sprinkler System design pressures at the interface with the remainder of the plant fire protection system are as follows:
Minimum -
75 psig Normal - 125 psig Maximum - 165 psig The Sprinkler System shall be designed to withstand the effects of water hammer when water is supplied at 165 psig.
2.2 System Descriptions 2.2.1 The Fire Detection System A.
Detector Installation Two independent and redundant circuits of two each pyro tronics DFS-10 infrared flame detectors shall be mounted above the area enclosed by the wall. Each detector circuit shall be routed in separate cable and conduit to a separate zone alarm unit in the local detection panel.
-3 The two detectors in each circuit shall have a line-of-sight surveillance over the entire area enclosed by the wall. Each detector shall be capable of responding to the presence of a flame which is sustained for a minimum of 10 seconds.
B.
Detection System Supervision The detection system shall be continuously supervised so that a malfunction in the detection circuitry shall be immediately recognized, and a trouble buzzer and indication energized locally and in the Main Control Room (MCR). The trouble signal shall not be extinguishable until there is no longer a malfunction. The malfunctions shall include loss of power, open circuit, short circuit and grounding.
C.
Detection System Alarm Condition When the presence of a fire is detected by the detector, the detector shall go into an alarm condition and:
- 1.
A lamp in the base of the detector shall light.
- 2.
An alarm bell and zone lamp in the MCR and local detection panel shall energize.
- 3.
An: alarm signal shall be sent to the Foam Control Panel.
- 4.
A signal to discharge the foam shall be sent to the Foam Control Panel when at least one detector in each detection circuit is in an alarm condition.
Thus, the MCR operator shall be aware of the fire condition and location and will expect further signals, i.e., annuncia tion from the FP annunciator.
Reset of the MCR and local detection circuits and panels shall not be possible until the detector(s) in an alarm condi tion are restored to normal.
2.2.2 Foam System Control Panel A.
Control System Supervision Pyrotronics System 3, which meets Class A requirements, shall be used.
The Local Control Panel (LCP) shall be located out of the area being protected but in an adjacent area. The LCP shall supervise the signalling circuit to the solenoid valve which causes the release of the foam. A malfunction in any of this circuitry shall result in activation of a local trouble buzzer and indicaton and the MCR FP annunciator.
-4 Each signalling circuit shall be in a separate cable and conduit installed over different routes.
B.
Control Panel Alarm Condition Upon receipt of an alarm signal from one detector circuit, the Control Panel shall energize the area horns.
Ten seconds after receipt of a signal to discharge foam, the Control Panel shall energize the solenoid valve which activates the deluge valve.
(The time delay permits personnel to clear the area prior to foam discharge.)
C.
Foam Discharge When the deluge valve is opened, a presure switch shall signal the MCR FP annunciator.
When the foam begins to discharge, another pressure switch shall also signal the same annunciator.
Thus, the MCR operator can monitor the system for proper function.
The foam may also be released by manually actuating the emergency trip valve adjacent to the deluge valve.
When the solenoid valve is deenergized, the deluge valve shall close and foam discharge shall cease.
2.3 Foam System Testing 2.3.1 Detection System Testing After installation of the detectors, insitu testing shall be conducted to demonstrate adequate time response of the detec tion system to a single, simulated fire.
Each detector shall be given a sensitivity (voltage) check and, then, a special flashlight with a built-in transistorized flasher shall be directed at each detector from within the walled area.
2.3.2 Supervisory Testing Each type of malfunction shall be employed in the detector and signalling circuits to verify proper opeation of the supervisory circuitry, annunciation in the MCR and local trouble alarm and indication.
2.3.3 Foam Discharge Testing Prior to foam discharge testing, system piping shall be flushed per NFPA 13 and 111 requirements and then hydrostatically tested.
An actual foam dischage test shall be conducted in accordance with applicable NFPA codes and standards.
An NML representative shall witness all testing.
-5 3.0 CABLE TRAY FIRE DETECTION AND WATER SPRAY SYSTEM 3.1 General Design Criteria The primary design objective of this system is to provide sectionalized directed water spray into the cable trays by automatic actuation from a line-type heat detection system in order that the cable trays may be protected from fires in the area and to prevent the spread of a fire in the cable trays.
The following are the detailed criteria which support the primary design objective:
3.1.1 The line-type heat detector loops (circuits) shall be coincident with the sectionalization of the water spray piping loops.
3.1.2 The line-type heat detection system shall be designed, fabri cated, installed and tested in compliance with NFPA 72D.
3.1.3 All equipment shall be FM approved or UL listed.
3.1.4 Water spray actuation shall be automatic, resulting from a 2 out of 2 detection system input signal. Manual actuation shall also be provided.
3.1.5 The water source for the water spray shall be the same as other plant fire protection systems.
3.1.6 The line-type heat detector shall be capable of operating before, during and after water flooding without malfunction.
3.1.7 The line-type heat detectors shall be installed in all cable trays in the area to prevent the spread of fire in the cable trays.
3.1.8 Line-type heat detectors shall also be installed under the lowest tier, of cable trays which are above the Lube Oil Storage Tank and Conditioner, to provide protection from a lube oil fire.
3.1.9 The temperature alarm setpoint of the detector shall be high enough above the worst-case ambient temperature and safe operating temperature of the cables to preclude a false alarm condition but well below a hot spot (incipient fire) temperature.
3.1.10 Indication and annunciation shall be provided at the local control panel and in the MCR in the event of system operation or system electrical malfunction.
3.1.11 The local control panel(s) shall be located out of the area being protected but in an adjacent, available area.
3.1.12 The Water Spray System shall be designed, fabricated, installed and tested in compliance with NFPA 13 and 15.
0 3.1.13 The sprinkler and spray system shall be zoned so that cable tray sprays are actuated only in areas requiring fire suppression.
3.1.14 The spray systems shall be designed for a flow of 0.15 gpm/ft 2 per square foot of cable tray.
No credit is taken for drainage through stacked trays.
3.1.15 The spray system will be designed as a dry-pipe deluge system to minimize possible leakage in the trays and to assure fast response to a fire.
3.1.16 All supports in the system within the area shall be designed as seismic category "A" to prevent damage from the spray system piping to any safety related systems or components near the piping.
3.1.17 The deluge valve for each zone shall have manual actuation capability.
3.2 System Descriptions 3.2.1 The Line-Type Heat Detection System A.
Detector Installation The cable trays in the area shall be divided into three sections with a separate water spray and deluge valve for each section.
Each section shall have two electrically independent and redundant Protectowire line-type heat detector cables installed in the cable trays of that section.
Each detector circuit to the local control panel shall be routed in separate cable and conduit from its redundant companion detector.
B.
Detection System Supervision The local control panel(s) shall be located in an area adjacent to the one being protected.
The local control panel(s) shall meet Class A requirements in supervising the detector circuits and the signalling circuits to the solenoid valves. A malfunction in any of these circuits shall produce a trouble buzzer and indication in the local control panel and annunciation in the MCR.
C.
Detection System Alarm Condition When the heat (temperature setpoint reached) from a fire is detected by a detector cable loop, the detector shall go into an alarm condition and:
- 1.
The area horn and lamp in the local panel shall energize.
- 2.
An alarm bell and zone lamp in the MCR shall energize.
-7
- 3.
When both detector cable loops in the same cable tray section go into an alarm condition, a signal to open the section's deluge valve shall be sent to the solenoid valve.
Thus, the MCR operator shall be aware of the fire condition and location, and will expect further annunciationj9n the operation of the water spray system.
Reset of indication in the MCR and local control panel detection system circuits shall not be possible until the detector cables in an alarm condition have been repaired or replaced.
D.
Water Spray Discharge When the solenoid valve for a water spray section is ener gized, the deluge valve shall open and flow to the spray nozzles shall take place. A pressure switch shall signal the MCR annunciator when the deluge valve opens.
The actuation signal to the solenoid shall not by extinguish able from the MCR.
The deluge valve may also be opened by manually actuating the Emergency Trip Valve adjacent to the deluge valve.
3.3 System Testing 3.3.1 Detection System Testing After calibration of the detector circuits, a fire condition in the cable trays shall be simulated by altering the detector cable loop resistance and monitoring the detection system for proper response.
3.3.2 Supervisory Testing Same as 2. 3. 2 3.3.3 Water Spray Discharge Testing The piping system shall be pressure tested and all operating parts required to achieve manual and automatic actuation of the water spray into the cable trays shall also be tested.
Testing shall be in the presence of an NML representative.
Testing shall be performed in accordance with applicable NFPA codes and standards.
No water shall actually be discharged into the cable trays.
-8 4.0 AREA FUSIBLE LINK SPRINKLER SYSTEM 4.1 General Criteria Fusible link wet pipe sprinkler systems shall be provided for two areas:
- 1) the east wall of the 480 volt switchgear room, and the north wall and structural steel members in that area, and 2) the general area of the lube oil reservoir and chemical feed equipment.
The east and north wall shall have directed water spray to act as a water screen to cool the wall in the event of a fire. The primary objective is to protect the safety related equipment which could be jeopardized in the event of wall failure. The primary objective of the general area sprinklers is to limit the spread of fire of the combustibles in the area. The general area sprinklers are intended to act as backup to the Foam System and the Cable Tray Water Spray System.
The following are detail criteria which support the primary objectives:
4.1.1 Spray nozzles shall be designed to NFPA 15 and shall be capable of producing a solid cone fine spray in a directional pattern.
4.1.2 Spray nozzles shall be of an approved design and have standard temperature ratings in accordance with NFPA 15.
4.1.3 The water.Source for this system shall be the same as the existing sprinkler system which it replaces.
4.1.4 The MCR shall be provided with annunciation when flow occurs from a spray nozzle.
4.1.5 Sprinkler System design pressures at the interface with the remainder of the plant fire protection system are as follows:
Minimum - 75 psig Normal - 125 psig Maximum - 165 psig The Sprinkler System shall be designed to withstand the effects of water hammer when water is supplied at 165 psig.
4.1.6 The Sprinkler System shall be designed, fabricated, installed and tested to comply with NFPA 13 and 15.
4.1.7 All equipment shall be UL listed or FM approved.
2 4.1.8 Design water density is 0.15 gpm/ft 4.2 Sprinkler System Description When heat from a fire reaches the fusible link melting temperature at a spray nozzle, water shall spray from the nozzle until the isolation valve for the piping loop can be closed.
-9 4.3 Sprinkler System Testing The system piping shall be flushed, hydrostatically checked and tested per NFPA 13.
System tests shall be conducted in the presence of a NML representative. A fuel discharge test will not be conducted.
5.0 AREA FIRE DETECTION SYSTEM 5.1 Design Criteria The area has smoke (ionization) detectors installed above the lube oil reservoir and conditioner, and over the cable trays. This detection system provides an early warning in identifying the commencement of a fire and also acts as backup to Foam and Cable Tray Detection Systems.
The detection system is electrically supervised so that any malfunction will be indicated and alarmed at the local detection panel and in the main control room.
The spacing of the detectors meets the intent of NFPA 72E Appendix A.
The local detection panel is located out of the area being protected.
The detection system indication cannot be reset in the event of trouble or detector alarm, condition until the system has returned to a normal state.
5.2
System Description
When a malunction in the detector circuit or local detection panel occurs, the supervisory function of the system causes a trouble buzzer and indi cation in the local detection panel and MCR to energize.
While the buzzers can be silenced, the trouble lamps cannot be extinguished until the malfunction has ceased.
When one of the pyrotronics DIS 3/5A high voltage ionization detectors in the single loop goes into an alarm condition, a lamp in the base of the detector lights, an alarm bell and zone indicating lamp in the local detec tion panel energizes, and an alarm bell and zone indicating lamp in the MCR energizes. While the alarm bells may be silenced, the lamps cannot be extinguished until the detector in an alarm condition has been reset.
5.3 System Testing After detector sensitivity checks have been conducted, in situ testing shall be conducted to demonstrate responsiveness of the detection sytem to a fire.
Aerosols simulating combustibles from the area shall be released in regulated quantities and the time response of the system recorded.
Normal environmental and air flow conditions will be main tained during testing.
SECTION 6 This section includes the additional information requested for the following item of the Fire Protection Safety Evaluation Report for San Onofre Unit 1.
3.1.15 Control of Combustibles An oil collection system will be provided for the reactor coolant pumps.
0 0
hEtACTOR COCLANT PUNP LUBE OIL biiAIN PANS AND SPHAY SHIELDS 1.0 UENERAL Drip pans and spray shields shall be installed for each of the three reactor coolant pumps.
The shield consists of a fabricated stainless steel housing for the lube oil pump on each reactor coolant pump (RCP).
Also installed will be drain pans beneath the lube oil pump, the upper and lower liquid level controls, the lube oil cooler, and the lube oil cooler/RCP flanged connections.
2.0 DESIGN CRITERIA 2.1 GENERAL DESIGN CRITERIA Spray shields shall be installed to prevent leaking lubricating oil from the RCP motors from dripping onto the reactor coolant lines. The detailed criteria supporting the primary design objectives follow:
2.1.1 Drain pans shall be provided under each lube oil connection to the RCP motor which is pressurized to less than 5 psig.
2.1.2 Spray shields and drip pans shall be provided for all connections pressurized to greater than 5 psig.
2.1.3 A drain line shall be provided to conduct any leakage to a floor drain.
2.1.4 The drain pans and spray shields shall be designated non-safety related.
2.1.5 All fabrication shall be done using Type 304 stainless steel sheet metal and stainless steel tubing.
2.1.6 Where welding is impractical, joints shall be sealed with a silicone type adhesive sealant.
2.1.7 All drain pans and spray shields shall be designed for easy removal to minimize additional work for maintenance on the RCP motor.
2.1.8 Drain tubing shall be 1 inch diameter to allow a minimum flow of at least 1 gpm.
3.0 SYSTEM DESCRIPTION The following are typical for each of the three reactor coolant pump motors:
e-2 3.1 Spray Shields A stainless steel housing shall be provided for each RCP motor lube oil pump.
The housing shall completely enclose the pump while providing an opening for the pump shaft to connect to the pump motor.
A single drain pan and a drain line shall be provided under both the lube oil pump and motor.
3.2 Drain Pans Drain pans shall be provided under each of tne following:
3.2.1 Upper lube oil liquid level control.
3.2.2 Lower lube oil liquid level control.
3.2.3 Upper flanged connection from RCP motor to motor lube oil cooler.
3.2.4 Lower flanged connection from RCP motor to motor lube oil cooler.
3.2.5 Lube oil cooler.
3.3 Drain Lines Each of the drain pans shall be connected to a common drain header for each RCP motor. The drain header shall conduct any leakage from the drain pans into a local floor drain below the level of the reactor coolant piping.
4.0 TESTING Each drain pan shall be tested by pouring water into the drain pan and checking the pan and drain lines visually for any leakage.
Pressure testing shall not be required.
SECTION 7 This section includes the additional information requested for the following items of the Fire Protection Safety Evaluation Report for San Onofre Unit 1.
3.1.2 Fire Water Supply Test features will be provided for the fire pumps which meets the requirements of NFPA 20.
An isolation valve(s) will be provided in the above ground cross connection of the yard loop which is routed through the turbine building to prevent the loss of both manual and automatic water suppression due to a single impairment.
A self-actuated pressure valve or a check valve with a parallel bypass valve will be provided in: the Units 2 and 3 connection to the Unit 1 fire water loop.
YARD FIRE LOOP 1.0 GENERAL Modifications to the yard fire loop include the following:
1.1 Intertie to Units 2 and 3 fire water system.
1.2 Isolation valves in turbine building (fire area No. 9).
1.3 Second fire water source for Unit 1 Administration Building hose reels.
1.4 Crosstie and isolation valve between hose reel No. 6 and fire hydrant No. 10.
Each of the above modifications is described below.
2.0 DESIGN CRITERIA 2.1 General Design Criteria 2.1.1 The design objective of the intertie to the Units 2 and 3 fire water system is to provide a separate, independent backup water supply to the existing Unit 1 fire water pumps and salt water cooling water pump.
2.1.2 The primary design objective of the various isolation valves and crossties (1.2, 1.3 and 1.4 above) is to allow removal of portions of the fire water system from service for maintenance without requiring an outage on the entire fire water system.
2.2 Detailed Design Criteria 2.2.1 All valves installed shall be UL listed or FM approved.
2.2.2 Maximum design pressure for the Unit 1 fire system is 165 psig.
2.2.3 All piping and valves shall be installed in accordance with NFPA Standard Nos. 13 and 16.
2.2.4 The intertie shall be designed to prevent flow from Unit 1 to the Units 2 and 3 fire water system.
2.3
System Description
2.3.1 Fire Water System Intertie A check valve shall be installed to allow flow from the Units 2 and 3 fire water system to the Unit 1 fire water system.
-2 During normal operation, the higher pressure in the Unit 1 system will keep this valve closed.
In case of loss of system pressure and loss of the Unit 1 fire pumps, the check valve will open allowing flow into the Unit 1 system. A normally closed block valve will also be provided as a bypass to allow the Unit 1 fire pumps to be used as backups to the Units 2 and 3 fire system, if required.
Both systems are pressurized by the Units 2 and 3 fire water jockey pump. Pressure switches within the system control the operation of the various pumps so that the jockey pump will be actuated first on pressure decay in the system followed sequentially by the Unit 1 fire pump G-11, Unit 1 fire pump G-11S, and finally by the Units 2&3 fire pumps.
The Units 2 and 3 fire pumps are set at lower pressure settings ensuring that the jockey pump will maintain system pressure and that the Units 2 and 3 fire pumps will not start prior to the Unit 1 fire pump.
2.3.2 Additional Isolation Valves Isolation valves shall be installed in the following locations:
2.3.2.1 Block valves shall be installed in lines 8052-3"-KN (BV3) and 856-3"-KN (BV7).
These valves allow isolation of the hose cabinets within the Unit 1 Administration Building, allowing maintenance in the Administration Building without requiring the removal of other portions of the fire water system from service.
2.3.2.2 Block valves shall be installed in line 814-8n-KN between the fire pump discharge line (BV2) and downstream of the branch lines to the lube oil area foam and sprinkler systems (lines 8066-6"-KN, 8072-2"-KN, 843-4"-KN, valve BV1).
These valves permit the separate isolation of each fire pump as well as isolation of the system between BV1, BV7 and PIVH.
2.3.2.3 The second fire water source and block valve (BV6) shall be installed between fire hydrant No. 10 and line 846-3"-KN.
This provides a second fire water source to fire hydrant No.
10 while allowing isolation of fire pump G-11S.
2.4 Testing All modifications to the fire system shall be pressure tested per IFPA No. 13 prior to release for normal operation.
0 3.0 Fire Water Supply Test features will be provided for the fire pumps which meet the requirements of NFPA 20.
A review of NFPA 20 of the National Fire Codes, 1979, has resulted in the identification of the following test requirements:
"A-12-3.1 Weekly Tests A centrifugal pump should be operated every week at rated speed with water discharging through some convenient opening.
This is desirable to make sure of the condition of the pump, bearings, stuffing boxes, suction pipe and strainers, and the various other details pertaining to the driver and control equipment (see 7-5.2.1, 8-6.1, 9-5.2.1 and 9-5.2.6).
When automatically controlled pumping units are to be tested weekly by manual means, at least one start should be ac complished by reducing the water pressure either with the test drain on the pressure sensing line or with a larger flow from the entire system."
n7-5.2.1 Water Pressure Control In the controller circuit there shall be provided a pressure actuated switch having independent high and low calibrated adjustments, and responsive to water pressure in the fire protection system. The pressure sensing element of the switch shall be capable of withstanding a momentary surge pressure of 400 psi (27.6 bars) without losing its accuracy.
Suitable provision shall be made for relieving pressure to the pressure-actuated switch, to test the operation of the controller and the pumping unit.
(See Fig. A-7-5.2.1.)
(a) Each controller for multiple pump installations shall have its own individual pressure sensing line."
"12-3.1 Yearly Test A yearly test shall be made at full capacity and over to make sure that neither pump nor suction pipe is constructed.
Where the water supply is from a public service main, pump operation shall not reduce the suction head, at the pump, below the pressure allowed by the local regulatory authority."
Section 9-5.2.1 referenced in A-12.3.1 above is a duplication of 7-5.2.1 and the other referenced sections of NFPA 20 are not applicable to the Unit 1 fire pumps.
The inspection and testing requirements for the Unit 1 fire pumps are contained in Technical Specification 4.15, Fire Protection System Surveillance. The station procedures which are used to implement these requirements are:
Station Order S-A-2, Fire Protection Operating Instruction S-7-1, Fire Protection Maintenance Procedure S-I-1.55, Fire Water Systems.
-4 Attachments 5A,B,C of S-I-1.55 (enclosed) provide the procedure for performance of the tests as required by NFPA 20.
The guages used in this test are calibrated annually.
By testing the fire pumps using this procedure, the testing requirements of NFPA 20 are met.
SAN ONOFRE NUCLEAR GENERATII&
TATION MAINTENANCE bCEDURE S-I-1.55 Revision 3 -
June 15, 1979 A FTRE PUMP FLOW AND READ TEST
& FIRE PUMP AUTO START TEST EQUIPMENT REQUIREDs 3 -
21" 50 FOOT FIRE HOSES 1 -
TEST NOZZLE SET 1 -
PITOT TUBE & GAGE 2o Notify control room of test and affeoted system,
- 2.
Install hoses and nossle test sot to fire pump test manifold,
- 3.
Insure intake and discharge gages have valid calibration date and 4,"
the west fire pump started,
- 4.
Read and record intake and discharge pressures with a dead head on the pump (discharge valve closed).
- 5.
Open two (2) valves on test manifold and read flow at end of nozsles with pitot gage.
- 6.
Open the third valve and take readings on all three nossle.
- 7.
Shut down the vest pump and have the east pump started.
- 8.
Take readings on all three (3) nossles.
- 9.
Close one (1) valve on test manifold and take readings on thq Iwo (3) remaining nossles.
- 10.
Close all valves on the test manifold and take readings of the sution and discharge pressure at pump (pump discharge valve closod)*
- 11.
Have east pump shut down and mode to automatic and open slightly a valve on the test manifold to determine at which pressure the pump starts #uto atically.
Return pump to normal status (pump discharge valve qpen).
- 32.
Have vest pump started long enough to establish pressure po otop 4 gn be repeated for the west pump.
Repeat step U,
- 13.
Secure all test equipment to normal status.
- 14.
Notify control room of conclusion of test.
- 15.
Record all pertinent information for the test on sttaokent 3D Test Conducted tyS Det*)
(Signature)
Date) 8.P.H.* RE
__VIEW (Signature)
W*
SAO "MJ~ NUCLIM GENERATMl STATION 1VADTENCE PRCEDURE S-1.1.55 fivsln3June 15, 1979 B pUMP AND WATER lEST DATA Pump Data Pmsiure Data firm Data let um Prsur e sh NtR tocahion. I Static 111esid tocaine 0
Dijioi r:,ijt
. Volts, No N-sut ic. N t 1..
or I Id N. I Ir Il t'e"' of I I~d No (ci.Cof IPr", I I)%
%e.r It5IICt r
HlEADER 3,,
'AAND 2-14 2
S HOSE 3.'
3 Tr 1
-HEADER 3-1z 4
2 S
H0SE 3
T Mo01del No._______
IitJMin.
&PA
_rier_-fl-orsepower at Rated R.P.M.
EST Purmnp Design Data:
I..GYMD..S.I..IP.M JJSP.S.
L31;n LV
-Speed Governor setting NONE R.P.M.
Relief valve -setting NN Size:___________
-Type of priming for centrifugal pump llE'AD PRFESS.
I W'SB mJ___________
Horizontal, Vertical Pump IQT.(Signature)
(
Number of Stages Lft Water Leel to Discharge)
S.P.L'S REVfM4
(
)gntw (Dt)
SAN ONOflM NUCLEAR GENERATING STATION KMfl(TENUJCE PRJOCEDURE 3-1-1.55 N oyjgj 4on.3-, June 15, 1979 Ateokba.t 5C FIRE '
PEFOMAC HCURVES