ML091800009

From kanterella
Jump to navigation Jump to search

Additional Draft RAI Question Regarding the Steam Dryer in Extended Power Uprate
ML091800009
Person / Time
Site: Monticello 
(DPR-022)
Issue date: 06/26/2009
From: Tam P
Plant Licensing Branch III
To: Gunderson L, Pointer K, Salamon G
Northern States Power Co, Xcel Energy
Tam P
References
TAC MD9990
Download: ML091800009 (2)


Text

Accession No. ML091800009 From:

Tam, Peter Sent:

Friday, June 26, 2009 2:10 PM To:

'Pointer, Kenneth'; 'Salamon, Gabor'; Gunderson, Lynne Cc:

Basavaraju, Chakrapani; Khanna, Meena

Subject:

Monticello - Proposed EPU Amendment, additional draft question re. steam dryer (TAC MD9990)

Ken:

On 3/20/09 I sent you a draft RAI consisting of 19 questions regarding the steam dryer. I just received an additional question from our Mechanical and civil Engineering Branch. Please let me know if you want to discuss this question with the NRC staff in a conference call:

EMCB-SD-RAI-20 In the steam dryer evaluation for MNGP, the main steam line (MSL) strain gage measurements from 2007 at CLTP power level were reduced by subtracting: 2008 data acquired at low power (LP) conditions in the plant.

According to Attachment II of Enclosure 11 to its letter of November 5, 2008, the licensee utilizes the acoustic circuit model (ACM), Rev. 4 (described in Reference 3, CDI Report 07-09P, Rev. 0) that was benchmarked using Quad Cities 2 (QC2) main steam line and steam dryer measurements. The licensee used the QC2 benchmark data to compute the frequency dependent bias errors and uncertainties for applying to MNGP. The MSL strain gage measurements used for the QC2 benchmark did not subtract LP data, whereas MNGP data used for dryer qualification subtracted the LP data.

Address the apparent inconsistency with the conclusion that the bias errors and uncertainties in CDI Report 07-09P are conservative given that the benchmarked code (QC2) did not subtract the LP data. Demonstrate by analyses that the bias and uncertainties assumed in CDI Report 07-09P are applicable to MNGP where LP noise is subtracted.

Peter S. Tam, Senior Project Manager Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Tel. 301-415-1451 E-mail Properties Mail Envelope Properties (3D6B1F4F51D25E4E9B6C93FF92DAE5171443BF3DA0)

Subject:

Monticello - Proposed EPU Amendment, additional draft question re. steam dryer (TAC MD9990)

Sent Date: 6/26/2009 2:10:04 PM

Received Date: 6/26/2009 2:10:00 PM From: Tam, Peter Created By: Peter.Tam@nrc.gov Recipients:

Kenneth.Pointer@xenuclear.com ('Pointer, Kenneth')

Tracking Status: None Gabor.Salamon@xenuclear.com ('Salamon, Gabor')

Tracking Status: None Lynne.Gunderson@xenuclear.com (Gunderson, Lynne)

Tracking Status: None Chakrapani.Basavaraju@nrc.gov (Basavaraju, Chakrapani)

Tracking Status: None Meena.Khanna@nrc.gov (Khanna, Meena)

Tracking Status: None Post Office:

HQCLSTR02.nrc.gov Files Size Date & Time MESSAGE 14902 6/26/2009 Options Expiration Date:

Priority: olImportanceNormal ReplyRequested: False Return Notification: False Sensitivity: olNormal Recipients received: