ML032100780
| ML032100780 | |
| Person / Time | |
|---|---|
| Site: | Oconee |
| Issue date: | 07/28/2003 |
| From: | Haag R NRC/RGN-II/DRP/RPB1 |
| To: | Rosalyn Jones Duke Energy Corp |
| References | |
| IR-03-003 | |
| Download: ML032100780 (42) | |
See also: IR 05000269/2003003
Text
July 28, 2003
Duke Energy Corporation
ATTN: Mr. R. A. Jones
Site Vice President
Oconee Nuclear Station
7800 Rochester Highway
Seneca, SC 29672
SUBJECT:
OCONEE NUCLEAR STATION - NRC INTEGRATED INSPECTION
REPORT 05000269/2003003, 05000270/2003003, AND 05000287/2003003
Dear Mr. Jones:
On June 28, 2003, the NRC completed an inspection at your Oconee Nuclear Station. The
enclosed report documents the inspection findings which were discussed on July 1, 2003, with
you and other members of your staff.
The inspection examined activities conducted under your licenses as they relate to safety and
compliance with the Commissions rules and regulations and with the conditions of your
licenses. The inspectors reviewed selected procedures and records, observed activities, and
interviewed personnel.
Based on the results of this inspection, there were four NRC-identified findings of very low
safety significance (Green). These findings were determined to involve violations of NRC
requirements. However, because of their very low safety significance and because they have
been entered into your corrective action program, the NRC is treating these issues as a non-
cited violations (NCVs), in accordance with Section VI.A.1 of the NRCs Enforcement Policy.
Additionally, one licensee-identified NCV is listed in Section 4OA7 of this report. If you contest
any of the NCVs in this report, you should provide a response within 30 days of the date of this
inspection report, with the basis for your denial, to the United States Nuclear Regulatory
Commission, ATTN: Document Control Desk, Washington, DC 20555-0001, with copies to the
Regional Administrator, Region II; the Director, Office of Enforcement, United States Nuclear
Regulatory Commission, Washington, DC 20555-0001; and the NRC Resident Inspector at the
Oconee facility.
In accordance with 10 CFR 2.790 of the NRC's "Rules of Practice," a copy of this letter and its
enclosure will be available electronically for public inspection in the NRC Public Document
Room or from the Publicly Available Records (PARS) component of NRC's document system
2
(ADAMS). ADAMS is accessible from the NRC Web site at
http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).
Sincerely,
/RA/
Robert Haag, Chief
Reactor Projects Branch 1
Division of Reactor Projects
Docket Nos.: 50-269, 50-270, 50-287
License Nos.: DPR-38, DPR-47, DPR-55
Enclosure:
NRC Integrated Inspection Report 05000269/2003003, 05000270/2003003, and
05000287/2003003 w/Attachment - Supplemental Information
cc w\\encl.:
L. E. Nicholson
Compliance Manager (ONS)
Duke Energy Corporation
Electronic Mail Distribution
Lisa Vaughn
Legal Department (ECIIX)
Duke Energy Corporation
422 South Church Street
Charlotte, NC 28242
Anne Cottingham
Winston and Strawn
Electronic Mail Distribution
Beverly Hall, Acting Director
Division of Radiation Protection
N. C. Department of Environmental
Health & Natural Resources
Electronic Mail Distribution
Henry J. Porter, Director
Div. of Radioactive Waste Mgmt.
S. C. Department of Health and
Environmental Control
Electronic Mail Distribution
R. Mike Gandy
Division of Radioactive Waste Mgmt.
S. C. Department of Health and
Environmental Control
Electronic Mail Distribution
County Supervisor of
Oconee County
415 S. Pine Street
Walhalla, SC 29691-2145
Lyle Graber, LIS
NUS Corporation
Electronic Mail Distribution
M. T. Cash, Manager
Nuclear Regulatory Licensing
Duke Energy Corporation
526 S. Church Street
Charlotte, NC 28201-0006
Peggy Force
Assistant Attorney General
N. C. Department of Justice
Electronic Mail Distribution
3
Distribution w/encl:
L. Olshan, NRR
A. Hiser, NRR
L. Slack, RII, EICS
RIDSNRRDIPMLIPB
PUBLIC
OFFICE
RII:DRP
RII:DRP
RII:DRP
RII:DRS
RII:DRS
RII:DRS
RII:DRS
SIGNATURE
MXS1
GAH2
MSL1 for
MSL1 for
MSL1 for
DWJ
NAME
MShannon
GHutto
ERiggs
SVias
MScott
JBlake
DJones
DATE
7/28/2003
7/28/2003
7/28/2003
7/24/2003
7/24/2003
7/24/2003
7/28/2003
E-MAIL COPY?
YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO
OFFICE
RII:DRS
RII:DRS
RII:DRS
RII:DRS
SIGNATURE
GWL1
REC1
MSL1 for
MSL1 for
NAME
GLaska
RCarroll
RMaxey
RCortes
DATE
7/24/2003
7/28/2003
7/24/2003
7/24/2003
E-MAIL COPY?
YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO
PUBLIC DOCUMENT
YES
NO
OFFICIAL RECORD COPY DOCUMENT NAME: C:\\ORPCheckout\\FileNET\\ML032100780.wpd
U. S. NUCLEAR REGULATORY COMMISSION
REGION II
Docket Nos:
50-269, 50-270, 50-287
License Nos:
Report No:
50-269/03-03, 50-270/03-03, 50-287/03-03
Licensee:
Duke Energy Corporation
Facility:
Oconee Nuclear Station, Units 1, 2, and 3
Location:
7800 Rochester Highway
Seneca, SC 29672
Dates:
April 6, 2003 - June 28, 2003
Inspectors:
M. Shannon, Senior Resident Inspector
A. Hutto, Resident Inspector
E. Riggs, Resident Inspector
J. Blake, Senior Project Manager (Section 1R08)
D. Jones, Senior Health Physicist (Section 4OA5.1D)
G. Laska, Operator Licensing Examiner (Section 1R11.2)
M. Scott, Senior Reactor Inspector (Sections 1R02 and 1R17)
K. Maxey, Reactor Inspector (Sections 1R02 and 1R17)
R. Cortes, Reactor Inspector (Sections 1R02 and 1R17)
S. Vias, Senior Reactor Inspector (Sections 1R02, 1R17 and
40A5.1A-C)
R. Carroll, Senior Project Inspector (Sections 1R20)
Approved by:
Robert Haag, Chief
Reactor Projects Branch 1
Division of Reactor Projects
Enclosure
CONTENTS
Page
SUMMARY OF FINDINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S1
REACTOR SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1R02
Evaluation of Changes, Tests, or Experiments
. . . . . . . . . . . . . . . . . . . . . . . . . 1
1R04
Equipment Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1R05
Fire Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1R07
Heat Sink Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1R08
Inservice Inspection Activities
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1R11
Licensed Operator Requalification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1R12
Maintenance Effectiveness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1R13
Maintenance Risk Assessments and Emergent Work Evaluations
. . . . . . . . . 11
1R14 Personnel Performance During Non-routine Plant Evolutions
. . . . . . . . 12
1R15
Operability Evaluations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1R17
Permanent Plant Modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1R19
Post-Maintenance Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1R20
Refueling and Outage Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1R22
Surveillance Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1EP6
Drill Evaluation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
OTHER ACTIVITIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4OA1 Performance Indicator Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4OA2 Identification and Resolution of Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4OA3 Event Followup
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4OA5 Other Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4OA6 Meetings, Including Exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4OA7 Licensee-Identified Violations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
ATTACHMENT: SUPPLEMENTAL INFORMATION
Key Points of Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
List of Items Opened, Closed, and Discussed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
List of Documents Reviewed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
List of Acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7
SUMMARY OF FINDINGS
IR 05000269/2003-003, IR 05000270/2003-003, IR 05000287/2003-003; Duke Energy
Corporation; 04/06/2003 - 06/28/2003; Oconee Nuclear Station; Maintenance Effectiveness,
Personnel Performance During Non-routine Plant Evolutions, and Other Activities.
The inspection was conducted by the resident Inspectors and eight regional based inspectors:
one senior project manager; one senior project engineer; one senior health physicist; two senior
reactor inspectors; one operator licensing examiner; and two reactor inspectors. The
inspectors identified four Green findings, which were identified as NCVs. The significance of
most findings is indicated by their color (Green, White, Yellow, Red) using IMC 0609,
Significance Determination Process (SDP). Findings for which the SDP does not apply may
be Green or be assigned a severity level after NRC management review. The NRC's program
for overseeing the safe operation of commercial nuclear power reactors is described in
NUREG-1649, Reactor Oversight Process, Revision 3, dated July 2000.
A.
NRC Identified and Self-Revealing Findings
Cornerstone: Mitigating Systems
Green. A non-cited violation (NCV) of 10CFR50, Appendix B, Criterion XVI, Corrective
Action, was identified by the inspectors for failure to promptly identify the degraded
standby shutdown facility (SSF) diesel cooling water seals in the problem investigation
process (PIP) program.
This finding was considered to be more than minor based on the fact that subsequent
analysis of the grommets noted significant degradation and this analysis would likely not
have been performed without initiation of the PIP. Therefore, if the cause of the
degradation was left uncorrected, the mitigation systems cornerstone objective of
ensuring the continued reliability of equipment needed to respond to initiating events
would be affected. In addition, continued degradation of the grommets would become a
more significant safety concern. This issue was considered to be of low safety
significance (Green) because the grommets were replaced during the SSF diesel
overhaul before they failed in service. (Section 1R12.2)
Green. A NCV of Technical Specification (TS) 5.4.1 and 10CFR50, Appendix B,
Criterion XVII Quality Assurance Records, was identified by the inspectors for failure to
maintain sufficient records [logs] to furnish evidence of activities affecting quality [TS
Limiting Conditions for Operation (LCOs)]. Specifically, operator logs provided
insufficient data to reconstruct the activities related to the June 22, 2003, Unit 1
Engineered Safeguards (ES) power supply failure, which affected the Engineered
Safeguards Protection System (ESPS) Digital Automatic Actuation Logic Channels 2, 4,
6, and 8.
The ESPS automatic initiation of ES functions to mitigate accident conditions is
assumed in the accident analysis and is required to ensure that consequences of
analyzed events do not exceed the accident analysis predictions. The failure to
adequately document TS LCO entry and action times for the failed automatic ES
actuation circuitry was considered to be more than minor because it impacted the
2
operators ability to accurately implement the TS LCO action statements, and if left
uncorrected, this type of improper documentation could become a more significant
safety concern. The finding was considered to be of very low safety significance based
on the fact that the ES power supply was returned to service before any LCO condition
would have required the unit to be in Mode 3. (Section 1R14b.(1))
Green. A NCV of TS 3.3.7 Condition A , Engineered Safeguards Protection System
(ESPS) Digital Automatic Actuation Logic Channels, was identified by the inspectors
when it was discovered that the licensee failed to declare a number of ES configured
system components inoperable following the loss of ESPS digital channels 2, 4, 6, and
8.
The ESPS automatic initiation of ES functions to mitigate accident conditions is
assumed in the accident analysis and is required to ensure that consequences of
analyzed events do not exceed the accident analysis predictions. Consequently, this
issue is more than minor, in that by not recognizing the importance of the lost automatic
ES initiation function and taking the compensatory actions of TS 3.3.7, the mitigating
systems cornerstone objective of ensuring the continued reliability of equipment needed
to respond to initiating events was affected. However, this issue was determined to be
of very low safety significance, based on the fact that there was no loss of function of
the Low Pressure Service Water system or the Keowee Hydro Units resulting from the
loss of ESPS Digital Automatic Actuation Logic Channels 2, 4, 6, and 8. Additionally,
the ES power supplies were restored and digital channels returned to service prior to
exceeding any TS allowed outage times for the affected components. (Section
1R14b.(2))
Cornerstone: Initiating Events
Green: A NCV of 10CFR50.55a(g)(4) and 10CFR50, Appendix B, Criterion VII was
identified by the inspectors, in that measures taken to preclude the installation of non-
conforming replacement parts and the ability to evaluate the suitability of replacement
during the Quality Assurance (QA) receipt inspection process were not adequate.
Specifically, this was identified for inadequate QA review during receipt inspections that
resulted in the licensee installing one non-conforming Control Rod Drive Mechanisms
(CRDM) (Split Nut) Flange Ring on Unit 2, and discovering, prior to the installation in
Unit 3, 68 CRDMs and 552 CRDM Hold Down Bolts that did not meet the design and
procurement specifications.
This finding was more than minor because non-conforming material was actually
installed in Unit 2. However, it was determined to be of very low safety significance
because there was not a loss of system function. (Section 40A5.1C)
B.
Licensee Identified Violations
One violation of very low safety significance, which was identified by the licensee has
been reviewed by the inspectors. Corrective actions taken or planned by the licensee
have been entered into the licensees corrective action program. This violation is listed
in Section 4OA7.
Report Details
Summary of Plant Status:
Unit 1 operated at 100 percent rated thermal power (RTP) during the inspection period except
for one power reduction. The unit was reduced to approximately 50 percent RTP on May 17,
2003, following a safety group 4 dropped rod. The rod was recovered and the unit was
returned to 100 percent RTP on May 18, 2003.
Unit 2 operated at 100 percent RTP during the inspection period except for two power
reductions. The unit was reduced to approximately 88 percent RTP on April 13, 2003, to
perform turbine valve movement testing. The unit was returned to 100 percent power later that
same day. On June 22, 2003, the unit was reduced to approximately 87 percent RTP to again
perform turbine valve movement testing. The unit was returned to 100 percent power later that
same day.
Unit 3 entered the report period at 93 percent RTP with an end of core life coastdown in
progress. The unit was shutdown on April 26, 2003, for a refueling outage. Following the
outage, the unit entered Mode 1 on June 14, 2003, and reached 100 percent RTP on June 18,
2003. On June 28, 2003, the unit was reduced to 15 percent RTP and the turbine taken off-line
for turbine balancing. The report period ended with the unit at 15 percent RTP.
1. REACTOR SAFETY
Cornerstones: Initiating Events, Mitigating Systems, Barrier Integrity
1R02
Evaluations of Changes, Tests or Experiments
a.
Inspection Scope
The inspectors reviewed selected samples of evaluations to confirm that the licensee
had appropriately considered the conditions under which changes to the facility,
Updated Final Safety Analysis Report (UFSAR), or procedures may be made, and tests
conducted, without prior NRC approval. The inspectors reviewed evaluations for nine
changes and additional information, such as calculations, supporting analyses, the
UFSAR, and drawings to confirm that the licensee had appropriately concluded that the
changes could be accomplished without obtaining a license amendment. The nine
evaluations reviewed are listed in the Attachment to this report.
The inspectors also reviewed samples of changes such as design changes, UFSAR
changes, commercial grade dedication packages, equipment problem issues, and like-
for-like evaluations for which the licensee had determined that evaluations were not
required, to confirm that the licensees conclusions to screen out these changes were
correct and consistent with 10CFR50.59. The twenty-one screened out changes
reviewed are listed in the List of Documents Reviewed.
The inspectors also reviewed an audit of the 10CFR50.59 process and selected
Problem Investigation Process reports (PIPs) to confirm that problems were identified at
2
an appropriate threshold, were entered into the corrective action process, and
appropriate corrective actions had been initiated.
b.
Findings
(1)
Introduction: One Unresolved Item (URI) was identified in that potentially the air
temperature inside of the units control room boards (vertical and unit boards) may reach
a higher than anticipated value than previously understood during design basis events.
Description: During the review of an UFSAR change to Section 3.11.5, Loss of
Ventilation, the inspectors observed the control room area temperature maximum was
stated to be 120 degrees F. The section did not address control board interior
temperature rise nor did it discuss the maximum value that could be reached inside
boards for the discussed event. The inspectors realized that other events not discussed
in the reviewed section could cause a loss of forced ventilation to the boards. When the
licensee was informed that the heat generating temperature sensitive electronics interior
to the boards may see a higher temperature than the control room ambient temperature,
PIP O-03-04052 was written on the issue. During normal operations, Technical Specification (TS) 3.7.16 limits the control room general area temperature to 80
degrees F.
The temperature difference between the ambient control room temperature and the
interior temperature of the boards was not clearly documented. Forced ventilation to the
boards and to the control room is postulated to be lost during such events as loss of
offsite power and seismic occurrences. There is a degraded control room ventilation
abnormal procedure. All related event and abnormal procedures do not address control
board interior temperatures nor do they have special instructions for reducing the interior
temperature of the boards during the loss of forced ventilation cooling. With the loss of
forced ventilation, a rise in temperature inside the board may occur and this rise may be
greater than that experienced in the control room inhabited space where control room
temperature is measured. Such a rise may be detrimental to critical electronic
equipment operation.
The aforementioned PIP stated that there was reasonable assurance that the equipment
inside of the control boards is operable during the event scenarios. This was based on
calculations that determined that the general area temperature rise after six hours would
be approximately 90 degrees F (calculation OSC-6667). The licensee stated that the
most limiting equipment in the boards has continuous duty temperature of 122 degrees
F, which is 32 degrees F higher than the six hour rise value. The event and abnormal
procedures are written to limit the time without forced ventilation. Further, the licencee
indicated in PIP O-00-4643, that the time required to restore cooling following a loss of
offsite power event was estimated to be less than 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. PIP O-03-4052 indicated
that an operability evaluation would be performed to further investigate the relationship
between the temperature inside the main control boards and the control rooms on all
three units.
The inspectors were aware that there are some passive vents and holes in the top of the
control boards and louvers on the side of the boards could possibly dissipate board
interior heat buildup. Further, the inspectors were aware of procedures and equipment
3
in other locations that could be relied upon for safe shutdown purposes should the
abandonment of the control room be required.
However, the following issues require additional review by the licensee: an
understanding of the peak temperature reached in each unique control cabinet in each
control room space; the critical electronic components needed for plant operation during
the postulated events; the suitability of equipment in the control boards to withstand
environmental temperature such as records documenting the component vendors
continuous duty temperatures for the considered critical parts; and, critical components
locations relative to possible warm spots on the boards should also be understood
(board thermal profile relative to component location).
Until the licensee can demonstrate a clear understanding of the thermal effects on
control room board components during a postulated loss of control board forced cooling
occurrence, this issue will be identified as URI 05000269,270,287/2003003-001:
Control Room Board Component Thermal Reliability.
(2)
Introduction: An URI was identified concerning Oconee UFSAR Section 3.6.1.3 that was
changed on May 17, 2001, under the old 50.59 program revision. During a review of the
change, the inspectors were concerned that the change may involve an unreviewed
safety question (USQ) under the old rule or a departure from a method of evaluation
under the new rule.
Discussion: The UFSAR change was associated with high energy line break (HELB) on
a main feedwater line. The escaping water/steam is assumed to disable the 4160 Volt
breakers for at least the motor driven emergency feedwater (EFW) pumps and for the
high pressure injection HPI pumps. The change increased the time allowed for initiation
of EFW and (HPI) after the HELB from 15 minutes to 30 minutes and from 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> to 8
hours, respectively.
The 1998 UFSAR version used RETRAN program analysis and the lower equipment
recovery times that kept the reactor coolant system (RCS) subcooled and capable of
natural circulation (minimally voided) due to the small amount of water loss. Under the
May 2001 revision, the licensee used RELAP 5 program and extended times for
equipment recovery of EFW and HPI. This results in significant voiding in the RCS, loss
of subcooling, increased number of cycles of the pressurizer safety valves, loss of
natural circulation, and reliance on the boiler/condenser mode (BCM) of decay heat
removal for up to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> without safety injection. Under BCM, the expansion and
collapsing of the RCS remaining volume would cause some pressure spikes within the
RCS. This evaluation was based on licensee calculation OSC-7299, Revision 1. Page
4 of the 10 CFR 50.59 evaluation discusses RELAP5 in that:
The analytical model utilized to evaluate these effects was changed from RETRAN
to RELAP5 because of the significant RCS voiding that will occur and the
importance of boiler condenser mode of decay heat removal. The version of
RELAP5 used is similar [to] a version approved by the NRC for use by Frametone
Technologies in small break loss of coolant accident (SBLOCA) UFSAR analysis of
OTSG plants. Additionally, the NRC has approved this version for use by Duke
4
Power Company in both SBLOCA and large break loss of coolant accident
(LBLOCA) mass and energy release analysis. The additional delays in EFW and
HPI restoration result in a transient that is essentially a small break LOCA.
The inspectors were concerned that this change appears to represent an USQ, as
defined by the previous version of 10 CFR 50.59. (The evaluation was completed under
the old 10 CFR 50.59 rule on May 17, 2001, and the licensee implemented the revised
rule on July 2, 2001). In this scenario, the pressurizer safety valves are challenged to lift
and reseat multiple times while passing steam and then water until EFW is recovered.
The licensee did not consider that the increased number of cycles of these valves would
increase the probability of a malfunction (i.e., sticking open) and create the possibility of
an accident of a different type (loss of coolant). With a stuck open valve and no safety
injection, core damage would result. The licensees evaluation states that RELAP 5 has
been approval for LOCA analysis, but it is not clear as to the acceptability of this method
of evaluation for HELB. Furthermore the concept of allowing the RCS to become
significantly voided, saturated, without natural circulation, without HPI for eight hours,
and reliance on BCM for decay heat removal, appears to be a departure from a method
of evaluation as described in the UFSAR, which would require prior NRC approval under
the current regulation. Until the NRC completes its review of the above issue, it will be
identified as URI
05000269,270,287/2003003-002: HELB Accident Scenario Review.
1R04
Equipment Alignment
.1
Partial Walkdown
a.
Inspection Scope
The inspectors conducted partial equipment alignment walkdowns to evaluate the
operability of selected redundant trains or backup systems while the other train or
system was inoperable or out of service. The walkdowns included, as appropriate,
reviews of plant procedures and other documents to determine correct system lineups
and verification of critical components to identify any discrepancies which could affect
operability of the redundant train or backup system. The following systems were
included in this review:
Unit 2 HPI trains 2A and 2B while the 2C HPI pump was out of service for preventive
maintenance
Unit 2 train A low pressure injection (LPI) while the B train of LPI was out of service
for maintenance
Units 1 and 2 primary instrument air system with the backup instrument air
compressor out of service for preventive maintenance
b.
Findings
No findings of significance were identified.
5
.2
Complete System Walkdown.
a.
Inspection Scope
The inspectors conducted a detailed review of the alignment and condition of the Unit 3
component cooling (CC) system. The inspectors utilized licensee procedures and other
documents listed in the Attachment to verify proper system alignment.
The inspectors also verified electrical power requirements, labeling, hangers, support
installation, and associated support system status. The operating pump was examined
to ensure that any noticeable vibration was not excessive, bearings were not hot to the
touch, and the pump was adequately ventilated. The walkdown also included an
evaluation of the system piping and supports against the following considerations:
Piping and pipe supports did not show evidence of water hammer
Hangers were properly sized and were within the setpoints
Piping insulation was adequate and showed no evidence of prior system leaks
Component foundations were not degraded
A review of PIPs and maintenance work orders was performed to verify that material
condition deficiencies did not significantly affect the ability of the CC system to perform
its design functions and that appropriate corrective action was being taken by the
licensee.
The inspectors also held discussions with the system and design engineers on
temporary modifications, future modifications, and operator workarounds to ensure that
the impact on the equipment functionality was properly evaluated.
b.
Findings
No findings of significance were identified.
1R05
Fire Protection
a. Inspection Scope
The inspectors conducted tours in thirteen areas of the plant to verify that combustibles
and ignition sources were properly controlled, and that fire detection and suppression
capabilities were intact. The inspectors selected the areas based on a review of the
licensees safe shutdown analysis and the probabilistic risk assessment based
sensitivity studies for fire related core damage sequences. Inspection of the following
areas were conducted during this inspection period:
Units 1 and 2 and Unit 3 HPI Rooms (2)
Units 1, 2 and 3 Equipment Rooms (3)
6
Units 1, 2 and 3 LPI/RBS Rooms (5)
Keowee Hydro Units (2)
Unit 2 Turbine Building Switchgear Area (1)
b.
Findings
No findings of significance were identified.
1R07
Heat Sink Performance
.1
Unit 3 Low Pressure Injection System Cooler Test
a.
Inspection Scope
The inspectors reviewed TT/3/A/0150/061, Unit 3 Low Pressure Injection System Cooler
Test, used to gather data for the LPI cooler performance evaluation. This testing was
performed to ensure that the cooler is able to meet TS and design basis requirements.
The inspection focused on compliance with the procedure requirements and appropriate
data collection during the testing. The inspectors also reviewed design calculation
OSC - 4338 Revision 7, to ensure that the LPI heat exchanger, based on the test data,
was capable of performing its design function per the calculation.
b.
Findings
No findings of significance were identified.
.2
Unit 1 Reactor Building Cooling Units (RBCU) Performance Test
a.
Inspection Scope
The inspectors reviewed Unit 1 RBCU Performance Test, PT/0/A/0160/006, used to
gather data for the RBCU performance evaluation. This testing was performed to verify
that the RBCU cooling capacity meets TS and design basis requirements. The
inspection focused on compliance with the procedure requirements and appropriate
data collection during the testing. The inspectors also reviewed design calculation
OSC - 5665, Attachment 27, which calculated the RBCU capacity factors from the
obtained test data.
b.
Findings
No findings of significance were identified.
7
1R08 Inservice Inspection (ISI) Activities
a.
Inspection Scope
Unit 3 Steam Generator (SG) Inspection
The inspectors reviewed the implementation of the licensees program for monitoring the
performance of the U3 once-through steam generators (OTSG). The inspector
observed examinations and reviewed selected inspection records for:
-
Eddy current examination (ET) data for eleven OTSG tubes.
-
Tube plugging operations including quality control verification of tube locations.
-
In-situ pressure testing data used to evaluate SG tube structural and leak tight
integrity of thirteen SG tubes (twelve in SG A and one in SG B)
-
Certifications for ten Quality Assurance (QA) Level III Eddy Current Data Analysts
-
SG tube repair (plugging) lists generated as a result of the Unit 3 SG ET inspection.
The above activities and records were compared to the TS, License Amendments, and
applicable industry established performance criteria to verify compliance. Documents
reviewed are listed in the Attachment to this report.
b.
Findings
No findings of significance were identified.
1R11
Licensed Operator Requalification
.1
Simulator Scenarios
a.
Inspection Scope
The inspectors observed licensed operator simulator training on June 27, 2003. The
scenario involved a dropped rod, a reactor trip, a steam generator tube leak in the 1B
steam generator, and a main steam line break. The inspectors also observed entry into
the emergency action levels (Unusual Event and Alert). The inspectors observed crew
performance in terms of: communications; ability to take timely and proper actions;
prioritizing, interpreting, and verifying alarms; correct use and implementation of
procedures, including the alarm response procedures; timely control board operation
and manipulation, including high-risk operator actions; and oversight and direction
provided by the shift supervisor, including the ability to identify and implement
appropriate TS actions.
8
b.
Findings
No findings of significance were identified.
.2
Annual Operating Test Results
a.
Inspection Scope
Following the completion of the annual operating examination testing cycle, which ended
on May 9, 2003, the inspectors reviewed the overall pass/fail results of the biennial
written examination, the individual Job Performance Measure operating tests, and the
simulator operating tests administered by the licensee during the operator licensing
requalification cycle. These results were compared to the thresholds established in
Manual Chapter 609 Appendix I, Operator Requalification Human Performance
Significance Determination Process.
b.
Findings
No findings of significance were identified.
1R12
Maintenance Effectiveness
.1
Routine Maintenance Effectiveness Reviews
a.
Inspection Scope
The inspectors reviewed the licensees effectiveness in performing routine maintenance
activities. This review included an assessment of the licensees practices pertaining to
the identification, scoping, and handling of degraded equipment conditions, as well as
common cause failure evaluations. For each item selected the inspectors performed a
detailed review of the problem history and surrounding circumstances, evaluated the
extent of condition reviews as required, and reviewed the generic implications of the
equipment and/or work practice problem. For those systems, structures, and
components (SSCs) scoped in the maintenance rule per 10 CFR 50.65, the inspectors
verified that reliability and unavailability were properly monitored and that 10 CFR 50.65
(a)(1) and (a)(2) classifications were justified in light of the reviewed degraded
equipment condition. The inspectors reviewed the following item:
PIP O-03-02888, Turbine Driven Emergency Feedwater Pump Steam Nozzle Bolt
Failure Issue
b.
Findings
No findings of significance were identified.
9
.2
Effectiveness of Standby Shutdown Diesel Preventive Maintenance and Problem
Identification
a.
Inspection Scope
The inspectors observed the 10-year overhaul of the Standby Shutdown Facility (SSF)
diesel, and selected for further review, those problems which were identified by outside
contractors. Specifically, the inspectors reviewed problems being identified by Engine
Service, Inc. contractors who were contracted by the licensee to provide technical
oversight for the 10-year overhaul of the SSF diesel engines and to assist with the
maintenance activities. For this inspection activity, the inspectors reviewed the daily
field service reports provided by the contractors to the licensee to evaluate the
adequacy of previous maintenance activities and to verify that problems identified by the
contractors were being appropriately documented in the licensees corrective action
program.
b.
Findings
Introduction: Two separate issues were identified as a result of this inspection:
(1) A Green non-cited violation (NCV) was identified by the inspectors for failure to
promptly identify degraded SSF diesel cooling water seals in the PIP program.
(2) An URI was identified, in that the licensee failed to implement the 6-year
recommended diesel manufacturer (EMD) preventive maintenance grommet
replacements. Consequently, at 10 years some of the grommets were found to be
at or near failure. Failure of the grommets could have led to diesel coolant leaks
and loss of cooling to the diesel. This issue will remain unresolved pending
completion of a Phase 3 risk review.
Description: During the June 2002, SSF diesel overhaul, the inspectors discussed
diesel equipment problems with the maintenance contractors from Engine Systems, Inc.
(ESI) who were providing technical oversight for the SSF diesel overhaul. The day shift
ESI contractor noted that the SSF diesel coolant grommets, located on the cylinder
heads (power packs), had been found degraded. He informed the inspectors that this
adverse condition would be provided to the licensee in a daily field service report. The
inspectors subsequently discussed the degraded grommet condition with maintenance
management to ensure that they were aware of the potential problem. The June 18,
2002, ESI daily field service report documented that Cylinder 7 on Engine B, had
deformed grommets on the cylinder head, unable to determine if the deformities were
from overheating or from installation damage. The June 19, 2002, ESI daily field
service report documented that Cylinder 8 on Engine A, had deformed head
On June 27, 2002, prior to returning the diesel to service and after noting that a PIP
report had not been initiated, the inspectors discussed the deformed grommet issue with
licensee management. On June 28, 2002, PIP O-02-03526 was initiated to capture the
potential degraded grommet condition.
10
Subsequent discussions with engineering noted that some of the deformed grommets
were going to be sent off for analysis. At this time, the inspectors also noted that the
grommets from Cylinder 7 on Engine B and Cylinder 8 on Engine A had not been
segregated from the grommets from the other 26 cylinders. It was also noted that the
licensee could not account for all of the replaced grommets, in that only 282 of the 336
replaced grommets could be located.
During various discussions regarding the grommets, the licensee noted that the diesel
manufacturer (EMD) had recommended a 6-year replacement interval for these
grommets. However, the grommets were being replaced on a 10-year interval and the
EMD owners group was discussing the possibility of EMD changing the replacement
interval to 12 years.
In October 2002, the remaining 282 grommets were sent off to ESI for analysis. On
May 8, 2003, the results of the ESI analysis were received by the licensee. The report
noted that Diesel engines used in standby service see thermal cycling which
contributes to the hardening of these grommets. Therefore, the recommended
replacement interval is on a 6 year calendar basis. ESIs analysis concluded the
following: 31 grommets were approaching the end of life; 6 grommets had been torn
during removal and that a new grommet cannot be readily torn by hand, the ability to
tear these grommets indicates their pliability has been compromised, likely due to aging
and their brittle nature indicates they were near the end of life; 43 grommets show a
high degree of brittleness and degradation, these are considered abnormal to a typical
reseal interval, It can be assumed these grommets were still capable of performing
their sealing function, and the state of brittleness and separation they exhibit indicates
they have exceeded their useful life; and last 19 grommets were distorted into a D
shape, considered to be classic examples of cylinder combustion leaks and with no
reported leaks, it must be assumed they performed their sealing function; however,
these grommets have exceeded their useful life. EMD went on to state that Continued
operation with grommets exposed to combustion gases will lead to failure and coolant
leaks.
EMD concluded the analysis with the following: Many of the components examined in
this investigation were at or near failure, and although no coolant leaks were reported,
combustion leaks were definitely occurring in some cylinders. Coolant leaks were likely
to follow, as those cylinders grommets exposed to combustion gases would have
continued to decay until their sealing ability was exhausted. EMD also stated that
Diesel engines in standby service experience more severe thermal cycling at each
surveillance run as compared to engines in continuous duty. This thermal cycling
promotes age-hardening in these seals, and the recommended 6-year maintenance
interval is a preventive maintenance practice that must be adhered to for continued
reliability.
Analysis
The issue of not initially writing a PIP to capture the ESI identified grommet degradation
was considered to be greater than minor based on the fact that subsequent analysis of
the grommets noted significant degradation and this analysis would likely not have been
performed without initiation of the PIP. Therefore, if the cause of the degradation was
11
left uncorrected, the mitigation systems objective of ensuring the continued reliability of
equipment needed to respond to initiating events would be affected. In addition,
continued degradation of the grommets would become a more significant safety
concern. This issue was considered to be of low safety significance (Green) because
the grommets were replaced during the SSF diesel overhaul before they failed in
service.
The issue of not performing the recommended grommet replacements was considered
to be more than minor in that the degraded grommets affected the equipment reliability
of a mitigation system (i.e., the SSF diesel). The finding was first evaluated in the
Phase 1 SDP based on the degraded reliability of a mitigating system under the Reactor
Safety Cornerstone. Based on the manufacturers conclusion that the grommets had
exceeded their useful life and that continued operation with grommets exposed to
combustion gases would lead to failure and coolant leaks, it was assumed that the
finding represented an actual loss of safety function of the SSF diesel, as the loss of
coolant could preclude operation of the diesel for its 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> mission time. Since this
system was designated as a risk significant system per 10 CFR 50.65, a Phase 2
analysis was performed. The Phase 2 analysis indicated that the issue could be greater
than Green; therefore, a Phase 3 analysis was required. Pending completion of the
Phase 3 analysis, the issue of not implementing the manufacturers recommendations
for replacement of the SSF diesel coolant grommets will be identified as URI
05000269,270,287/2003003-03: Failure to Implement Manufacturers Recommendations
for Replacement of SSF Diesel Coolant Grommets. This issue is in the licensees
corrective action program as PIP O-02-03526.
Enforcement
10 CFR 50, Appendix B, Criterion XVI, requires that measures shall be established to
assure that conditions adverse to quality, such as...deficiencies, deviations, defective
material and equipment, and non-conformances are promptly identified. The licensees
quality assurance (QA) program implements this requirement through Nuclear Station
Directive 208, Problem Investigation Process, Revision 22. Section 208.6, Problem
Identification, states that a PIP should be initiated within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of recognition of the
issue. Contrary to 10 CFR 50 Appendix B, Criterion XVI, following the June 19, 2002,
identification of the degraded grommets which could be the result of improper
installation, a PIP was not initiated until June 28, 2002, which was after all of the SSF
diesel grommets had been replaced. This inadequate corrective action issue is being
treated as an NCV, consistent with Section VI.A.1 of the enforcement policy and is
identified as NCV 05000269,270,287/2003003-04: Failure to Identify the SSF Degraded
Grommets as a Deficient Condition in the PIP Corrective Action Program. This issue is
in the licensees corrective action program as PIP O-02-03526.
1R13
Maintenance Risk Assessment and Emergent Work Evaluations
a.
Inspection Scope
The inspectors evaluated, as appropriate for the selected SSCs listed below: (1) the
effectiveness of the risk assessments performed before maintenance activities were
conducted; (2) the management of risk; (3) that, upon identification of an unforseen
12
situation, necessary steps were taken to plan and control the resulting emergent work
activities; and (4) that maintenance risk assessments and emergent work problems
were adequately identified and resolved.
PIP O-03-3584, Unexpected Closure of 1HP-5 Letdown Isolation Valve, caused by
failure of an improperly installed control air solenoid
IP/0/A/2005/003, Keowee Hydro Station Westinghouse Voltage Regulator Test,
performed as part of troubleshooting for failed voltage regulator
PIP O-03-2925, Increased HPI Motor Cable Insulation Leakage
Preventive Maintenance on Unit 2 Electro Hydraulic Control (EHC) System per Work
Orders 98592430 and 98592429
PIP O-03-3800, Unit 3 RC-4 Power Operated Relief Valve (PORV) Block Valve
Leakage and Repair
PIP O-03-02381, 3MS -155 (Main Steam Line B Atmospheric Vent) could not be
opened when attempting to depressurize the steam generator
PIP O-03-04140, Identification of Risk Assessment Error for Previous Repair of
3RC-4. Credit was inappropriately given for availability of the steam generators
although the RCS loops were not filled.
b.
Findings
No findings of significance were identified.
1R14
Personnel Performance During Non-routine Plant Evolutions
a.
Inspection Scope
The inspectors reviewed, the operating crews performance during selected non-routine
events and/or transient operations to determine if the response was appropriate to the
event. As appropriate, the inspectors: (1) reviewed operator logs, plant computer data,
or strip charts to determine what occurred and how the operators responded;
(2) determined if operator responses were in accordance with the response required by
procedures and training; (3) evaluated the occurrence and subsequent personnel
response using the SDP; and (4) confirmed that personnel performance deficiencies
were captured in the licensees corrective action program. The non-routine evolution
reviewed during this inspection period included the following:
Loss of 700 Gallons of RCS in Unit 3 Due to Over-pressurization of LPI Suction (PIP
O-03-02362)
Unit 1 Dropped Rod and Subsequent Recovery
Failure of the Unit 1 Channel B Engineered Safeguards (ES) Power Supply
13
b.
Findings
(1)
Introduction: A Green NCV was identified by the inspectors for failure to maintain
sufficient records [logs] to furnish evidence of activities affecting quality [TS Limiting
Conditions In Operations (LCOs)].
Description: On June 22, 2003, the Unit 1 ES channel B power supply failed. This
failure, caused a loss of power to the Engineered Safeguards Protection System (ESPS)
Digital Automatic Logic Channels 2, 4, 6, and 8. Subsequently, the inspectors reviewed
the licensees operator logs and TS tracking systems. The inspectors noted that the
operator logs provided insufficient data to reconstruct the activities related to the ES
power supply failure. The inspectors noted that the documented time for declaring the
components related to ES channels 2, 4, 6, and 8 per TS 3.3.7, had been improperly
changed and backdated from 9:55 a.m. to 9:15 a.m. In addition, the time of discovery
of the failed power supply was backdated to 8:15 a.m., although the ES channel B
power supply was functioning properly at that time. The logs did not provide any
justification for this change. Also, the inspectors noted that the logs indicated the
control room operators were informed of the loss of power to the ES digital channels at
8:51 a.m.; however, the TS tracking documents noted that the ES digital channels
became inoperable at 8:55 a.m. The various times were considered to be important
because they provided evidence for activities associated with meeting the 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> action
statement of TS 3.3.7 for placing the associated components in their ES positions or
declaring the components inoperable.
Analysis: The ESPS automatic initiation of ES functions to mitigate accident conditions
is assumed in the accident analysis and is required to ensure that consequences of
analyzed events do not exceed the accident analysis predictions. The failure to
adequately document TS LCO entry and action times for the failed automatic ES
actuation circuitry was considered to be more than minor because it impacted the
operators ability to accurately implement the TS LCO action statements, and if left
uncorrected, this type of improper documentation could become a more significant
safety concern. The finding was considered to be of very low safety significance
(Green) based on the fact that the ES power supply was returned to service before any
LCO condition would have required the unit to be in Mode 3. This observation was
based on the inspectors review of the associated completed surveillances and use of
computer alarm summaries as a basis for the initial failure time.
Enforcement: TS 5.4.1 requires that written procedures be established, implemented,
and maintained covering activities related to procedures recommended in Regulatory
Guide 1.33 Rev. 2, Appendix A, 1978. Regulatory Guide 1.33, Section 1(g),
Administrative Procedures, requires log entries. 10 CFR 50, Appendix B, Criterion XVII,
Quality Assurance Records, requires that sufficient records shall be maintained to
furnish evidence of activities affecting quality. Contrary to the above, sufficient
logkeeping and TS tracking records were not sufficiently maintained to furnish evidence
of activities related to TS LCO action statements. Because the finding is of very low
safety significance and has been entered into the corrective action program as PIP O-
03-04408, this violation is being treated as NCV 05000269/2003003-05: Failure to
Maintain Sufficient Records (logs) to Furnish Evidence of Activities Affecting Quality (TS
LCOs).
14
(2)
Introduction: A Green NCV of TS 3.3.7 Condition A , Engineered Safeguards Protection
System (ESPS) Digital Automatic Actuation Logic Channels, was identified by the
inspectors when it was discovered that the licensee failed to declare a number of ES
configured system components inoperable following the loss of ES digital channels 2, 4,
6, and 8 as required.
Description: As indicated in (1) above, the June 22, 2003, power supply failure of Unit 1
ES Analog Channel B resulted in the subsequent loss of Unit 1 ES Digital Actuation
Channels 2, 4, 6, and 8. Upon declaring one or more ES digital automatic actuation
logic channels inoperable, TS LCO 3.3.7 Condition A .1, requires that ES configured
components associated with that channel be placed in their ES configuration, or
Condition A.2 requires that the components associated with that channel be declared
inoperable. The inspectors determined that the licensee failed to either place the
affected components in their ES configuration or declare them inoperable within one
hour as required by the TS. Since placing the affected components in their ES
configuration would in this case violate unit safety or operational considerations, the
licensee was required to declare the components inoperable within one hour and enter
the associated component TS LCO. Specifically, the licensee failed to enter TS 3.3.17
Condition A, one channel of the emergency power switching logic (EPSL) automatic
transfer function inoperable [channel B from ES channel 2], TS 3.3.21 Condition A, one
channel of the EPSL Keowee Hydro Unit (KHU) emergency start function inoperable
[channel B from ES channel 2], and TS 3.7.7 Condition A, one required low pressure
service water (LPSW) pump inoperable [LPSW pump B from ES channel 4].
Analysis: The ESPS automatic initiation of ES functions to mitigate accident conditions
is assumed in the accident analysis and is required to ensure that consequences of
analyzed events do not exceed the accident analysis predictions. Consequently, this
issue is more than minor, in that by not recognizing the importance of the lost automatic
ES initiation function and taking the compensatory actions of TS 3.3.7, the mitigating
systems cornerstone objective was affected. However, this issue was determined to be
of very low safety significance (Green), based on the fact that there was no loss of
function of the LPSW system or the KHUs resulting from the loss of ESPS Digital
Automatic Actuation Logic Channels 2, 4, 6, and 8. Additionally, the ES power supplies
were restored and digital channels returned to service prior to exceeding any TS allowed
outage times for the affected components.
Enforcement: TS 3.3.7 Condition A .1 requires that ES configured components
associated with an inoperable ESPS Digital Automatic Actuation Logic Channel be
placed in their ES configuration, or TS 3.3.7 Condition A.2 requires that the components
associated with the inoperable channel be declared inoperable. Contrary to the above,
the licensee failed to place all effected ES components in their ES configuration or
declare the associated components inoperable following the loss of ES digital channels
2, 4, 6, and 8. Because this finding is of very low safety significance and has been
entered into the corrective action program as PIP O-03-04408, this violation is being
treated as a NCV, consistent with Section VI.A.1 of the NRC Enforcement Policy. It will
be identified as NCV 05000269/2003003-06: Failure to Declare ES Configured
Components Inoperable per TS.
15
1R15
Operability Evaluations
Quarterly Operability Evaluations
a.
Inspection Scope
The inspectors reviewed selected operability evaluations affecting risk significant
mitigating systems, to assess, as appropriate: (1) the technical adequacy of the
evaluations; (2) whether continued system operability was warranted; (3) whether other
existing degraded conditions were considered; (4) if compensatory measures were
involved, whether the compensatory measures were in place, would work as intended,
and were appropriately controlled; and (5) where continued operability was considered
unjustified, the impact on TS LCO. The inspectors reviewed the following items for
operability evaluations:
PIP O-03-02132, Unit 2 Installed Control Rod Drive Mechanism (CRDM) Split Ring
Flange Assembly Does Not Meet ASME Requirements
PIP O-03-03042 Increased Containment Sump Leakage in Unit 1 From RCS and
LPSW Leakage
PIP O-03-02226, 2B and 1C HPI Motor Vibration Increase Following New Pump
Installations
PIP O-03-3183, Increased Leakage From the 1B1 RCP Seal
PIP O-03-02492, Unit 1 RCS Leakage From Incore Instrument Tank
PIP O-03-3036, The 1A LPI Motor Space Heaters Have Not Functioned Since June
2001
PIP O-03-02569, Evidence of Borated Water Leakage Down Inside Primary Shield
Walls Below the Unit 3 Reactor Vessel
PIP O-03-02268, Indications of Increased RCS Leakage in Unit 1
b.
Findings
No findings of significance were identified.
1R17
Permanent Plant Modifications
.1
Feedwater Whip Restraint Modification
a.
Inspection Scope
The inspectors reviewed minor modification (ONOE) -17539, Modify Two Pipe Whip
Restraints on Unit 3 Main Feedwater Piping, to verify that the feedwater whip restraints
16
had been properly adjusted as per the design drawings following replacement of the
bolting material and clevises.
The inspectors observed work in progress during the removal and replacement of the
whip restraints and reviewed the work documentation for setting the whip restraints
following return to normal operating temperatures of the feedwater piping.
The inspectors reviewed the following documents during the inspection:
NSM ONOE-17539
MP/O/A/3019/004, Revision 53, Hangers - QA Condition 1 and 4 - Removal,
Installation or Modification
Work Request/Work Orders 98590970 (11) making final adjustments hot
Design Drawing O-494, Main Feedwater Pipe Whip Restraint
PIP O-01-01408, Adequacy of Existing Feedwater Pipe Rupture Restraints,
Corrective Action 7
In addition, the inspectors discussed with engineering the adjustments made to the whip
restraints once hot temperature operations were reached.
b.
Findings
No findings of significance were identified.
.2
Biennial Plant Modification Review
a.
Inspection Scope
The inspectors evaluated design change packages for nine modifications in the Barrier
Integrity and Mitigating Systems cornerstone areas, to evaluate the modifications for
adverse affects on system availability, reliability, and functional capability. The
modifications and the associated attributes reviewed are as follows:
ONOE- 10642, Upgrade Seismic Supports and Add Isolation Valve 3N-305 to Nitrogen
Line
Materials/Replacement Components
Flowpaths
Pressure Boundary
Structural
Process Medium
Failure Modes
ONOE- 12107, Upgrade Discharge LPSW Piping from the Motor Driven EFW coolers to
Materials/Replacement Components
17
Structural
Process Medium
ONOE- 15414, Replace Valve 2LP-15 with Item DMV-1296, 2A LPI Discharge to RBS
Pump Spray and HPI Suction
Materials/Replacement Components
Pressure Boundary
Structural
ONOE- 12094, Modification of Unit 2 RC Vent System Supports/Restraints
Materials/Replacement Components
Structural
ONOE- 12800, Provide Clearance Between the Valve Body of 2SF-101 and SSF RC
Makeup Pump Discharge Piping
Materials/Replacement Components
Pressure Boundary
Structural
ONOE- 17011, Upgrade 3-CCW-269 to Meet EQ Requirements
Materials/Replacement Components
Nuclear Station Modification (NSM) 33090, Add RBCU Time Delay Relays
Energy needs
Seismic qualification
Response time
Operations procedures
Modes bounded by the existing analysis
NSM 23053, Automatic Feedwater Isolation System
Environmental Qualification
Response Time - Testing
Modes bounded by existing analysis
NSM 23092, 600 V MCC and Load Center
Energy Needs
Seismic qualification
Control signals appropriate under accident conditions
Failure modes bounded by the existing analysis
For selected modification packages, the inspectors observed the as-built configuration.
Documents reviewed included procedures, engineering calculations, modifications
design and implementation packages, work orders, site drawings, corrective action
documents, applicable sections of the UFSAR, supporting analyses, TS, and design
basis information. Documents reviewed are listed in the Attachment to this report.
The inspectors also reviewed selected PIPs associated with modifications to confirm
that problems were identified at an appropriate threshold, were entered into the
corrective action process, and appropriate corrective actions had been initiated.
18
b.
Findings
No findings of significance were identified.
1R19
Post-Maintenance Testing (PMT)
a.
Inspection Scope
The inspectors reviewed PMT procedures and/or test activities, as appropriate, for
selected risk significant mitigating systems to assess whether: (1) the effect of testing
on the plant had been adequately addressed by control room and/or engineering
personnel; (2) testing was adequate for the maintenance performed; (3) acceptance
criteria were clear and adequately demonstrated operational readiness consistent with
design and licensing basis documents; (4) test instrumentation had current calibrations,
range, and accuracy consistent with the application; (5) tests were performed as written
with applicable prerequisites satisfied; (6) jumpers installed or leads lifted were properly
controlled; (7) test equipment was removed following testing; and (8) equipment was
returned to the status required to perform its safety function. The inspectors observed
testing and/or reviewed the results of the following tests:
PT/2/A/0202/11, 2C High Pressure Injection Pump Inservice Testing (IST)
Following Mechanical Seal Cleaning and Inspection
PIP O-03-02797, Anderson Greenwood Relief Valves 3MS-52 and 3MS-70
Failed to Lift as Specified Pressure During IST
PIP O-03-02864, 3HP-25, BWST Supply to LPI Suction, Failed IST Stroke Test
PIP O-03-02831, 3HP23, Letdown Storage Tank Outlet Isolation, Failed IST
Stroke Test
PT/3/A/0152/007, Core Flood System valve Stroke Test, IST Stroke Test
Following Inadvertent Backseating of Core Flood Isolation Valve 2CF-2 During
Maintenance per PIP O-03-03061
IP/0/A/0203/001A, Low Pressure Injection System Borated Water Storage Tank
Level Instrument Calibration, calibration of level instrument reviewed following
indication of false level reading per PIP O-03-0316
TT/3/A/0600/022, Turbine Driven Emergency Feedwater (TDEFW) Pump Speed
Response During AFIS Initiation Test, Following AFIS Modification
PIP O-03-02955, Following Maintenance the Unit 3 TDEFW Pump Lube Oil
Cooler Developed a Water Leak
b.
Findings
No findings of significance were identified.
19
1R20
Refueling and Outage Activities
a.
Inspection Scope
The inspectors conducted reviews and observations for selected licensee outage
activities to ensure that: (1) the licensee considered risk in developing the outage plan;
(2) the licensee adhered to the outage plan to control plant configuration based on risk;
(3) that mitigation strategies were in place for losses of key safety functions; and (4) the
licensee adhered to operating license and TS requirements. Between April 26, 2003,
and June 15, 2003, the following activities related to the Unit 3 refueling outage were
reviewed for conformance to the applicable procedure and selected activities associated
with each evaluation were witnessed:
defueled (no Mode) operations
refueling operations
reduced inventory and mid-loop conditions for installation and removal of steam
generator nozzle dams
activities involving the reactor vessel head replacement
reactor startup
Mode changes from Mode 6 (Refueling) to Mode 1 (Power Operation)
system lineups during major outage activities and Mode changes
final containment walkdown prior to startup
b.
Findings
No findings of significance were identified.
1R22
Surveillance Testing
a.
Inspection Scope
The inspectors witnessed surveillance tests and/or reviewed test data of the selected
risk-significant SSCs listed below, to assess, as appropriate, whether the SSCs met TS,
UFSAR, and licensee procedure requirements. In addition, the inspectors determined if
the testing effectively demonstrated that the SSCs were ready and capable of
performing their intended safety functions.
PT /1/A/0600/013, 1A Motor Driven Emergency Feedwater Pump Test [IST]
PT/3/A/0151/20, Penetration 20 Leak Rate Test (3PR-1 and 3PR-2) [local leak
rate test (LLRT)]
20
PT/3/A/0151/019, Penetration 19 Leak Rate Test (3PR-5 and 3PR-6) [LLRT]
PT/0/A/0600/021, Standby Shutdown Facility Diesel Generator Operation
PT2/A0202/011, 2B HPI Pump test [IST]
PT/3/A/0251/019, Main Steam Atmosphere Dump Valve Functional Test
1P/0/A/0305/001P, Reactor Protective System Channel D RC Pressure
Instrument Calibration
IP/A/0380/004C, SSF D/G Water Expansion Tank Level Instrument Calibration
IP/0/A/305/0005D Reactor Building High Pressure Trip Channel D
b.
Findings
No findings of significance were identified.
Cornerstone: Emergency Preparedness
1EP6
Drill Evaluation
a.
Inspection Scope
The inspectors observed and evaluated the licensees conduct of a simulator based
emergency preparedness drill held on June 10, 2003. The drill scenario involved
tornado damage to the Unit 1 turbine building with a subsequent loss of all AC power.
Additionally, Unit 3 developed a steam generator tube leak as part of the drill scenario.
The inspectors observed the scenario from the simulator control room and the Technical
Support Center. The inspectors observed performance of the licensees ability to
correctly classify the event and notify state and county authorities. For this drill, the
scenario progressed to a site area emergency. The drill scenario did not provide an
opportunity for the emergency response organization to make protective action
recommendations. The inspectors also reviewed the post-drill critique that was
conducted by the licensee evaluators.
b.
Findings
No findings of significance were identified.
21
4. OTHER ACTIVITIES
4OA1 Performance Indicator (PI) Verification
.1
Initiating Events, Mitigating Systems, and Barrier Integrity Cornerstones
a.
Inspection Scope
The inspectors reviewed the PIs listed in the table below (for all three units), to deter-
mine their accuracy and completeness against requirements in Nuclear Energy Institute
(NEI) 99-02, Regulatory Assessment Performance Indicator Guideline, Revision 2.
Cornerstone: Initiating Events
Performance Indicator
Verification Period
Records Reviewed
Unplanned Scrams
3rd and 4th
quarter, 2002,
and
1st quarter, 2003
Licensee Event Reports
NRC Inspection Reports
Monthly Operating
Reports
operator logs
licensee power history
curves
Scrams with Loss of Normal
Heat Removal
Unplanned Power Changes
Cornerstone: Barrier Integrity
Performance Indicator
Verification Period
Records Reviewed
Specific Activity
3rd and 4th
quarter, 2002,
and
1st quarter, 2003
daily plant chemistry
data
Leakage
daily status reports
operator logs
b.
Findings
No findings of significance were identified.
4OA2 Identification and Resolution of Problems
a.
Inspection Scope
The inspectors performed an in-depth review of issues entered into the licensees
corrective action program. The samples selected were within the cornerstone of
mitigating systems and involved risk significant systems. The inspectors reviewed the
actions taken to determine if the licensee had adequately addressed the following
attributes:
22
- Complete, accurate, and timely identification of the problem
- Evaluation and disposition of operability and reportability issues
- Consideration of previous failures, extent of condition, generic or common cause
implications
- Prioritization and resolution of the issue commensurate with the safety significance
- Identification of the root cause and contributing causes of the problem
- Identification and implementation of corrective actions commensurate with the safety
significance of the issue
The following issue and corrective actions were reviewed:
b.
Findings
No findings of significance were identified.
4OA3 Event Followup
.1
Unit 1 Dropped Rod
On May 17, 2003, Unit 1 dropped Safety Group 4, Rod 9 during rod movement
verification surveillance testing at 100 percent RTP. The dropped rod was a result of a
blown fuse on one of the control rod drive motor phases. The operators reduced power
to less than 55 percent as a result of the dropped rod. The inspectors responded to the
site and verified that TS and core operating limits report requirements were met by the
licensee for quadrant power tilt ratio, axial flux, and rod alignment. The inspectors also
verified that the appropriate abnormal operating procedures were implemented by the
operators. Repairs were made, the rod was subsequently recovered, and the unit was
returned to 100 percent power on May 18, 2003.
.2
Standby Shutdown Facility Cable Routing
The inspectors followed up on a 10 CFR 50.72, eight hour notification made by the
licensee for an unanalyzed condition relating to the licensee's discovery of safe
shutdown cabling routed through an Appendix R, III.G.3 area. These cables included
control and indication wiring for several valves that isolate the reactor coolant system
from potential leakage paths during safe shutdown. The inspectors walked down the
cabling to verify the licensees assessment of the condition and reviewed the adequacy
of the compensatory measures put in place.
.3
Failure of the Engineered Safeguards Channel B Power Supply
The inspectors reviewed the licensees response to the failure of the engineered
23
safeguards channel B power supply. The failure resulted in multiple TS LCO entries
and included a loss of the digital engineered safeguards digital actuation circuits. In
addition, multiple alarms were received in the control room. Following the initial loss,
discussions were conducted with the licensee concerning the failure of the power
supply, the various TS LCO entries, and ongoing repair efforts. Followup of the ES
power supply failure is discussed further in Section 1R14 of this report.
4OA5 Other Activities
.1
Unit 3 Reactor Vessel Head Replacement Project (RVHRP)
A.
Engineering Preparation and Implementation for the RVHRP
a.
Inspection Scope
The inspectors reviewed engineering preparations including: selected Design
Modification Packages, engineering calculations, analyses, and drawings for the
Oconee RVHRP, in order to assess adequacy and completeness. To obtain a greater
understanding of the entire project scope, the inspectors also held discussions with
project management. To determine that proper Code Sections and Editions were
applicable for this RVHRP, the inspectors also reviewed applicable sections of the
Oconee Final Safety Analysis Report and various scope documents.
b.
Findings
No findings of significance were identified.
B.
Review of RVHRP Lifting and Transportation Program Activities
a.
Inspection Scope
The inspectors reviewed the adequacy of the RVHRP lifting program as described in
Modification Package ON-33112, Part AS1, Reactor Vessel Head Rigging and
Handling, assuring that it was prepared in accordance with regulatory requirements,
appropriate industrial codes and standards, and verified that the maximum anticipated
loads to be lifted would not exceed the capacity of the lifting equipment and supporting
structures.
The inspectors examined the RVHRP lifting equipment including the Polar Crane, a
down-ender placed inside the Reactor Building, three four-point lift systems, three skid
systems and a Self Propelled Modular Transport.
The inspectors reviewed the adequacy of the transport programs, procedures, work
packages, and load test records, to assure that they had been prepared and/or tested in
accordance with regulatory requirements, appropriate industrial codes, and standards.
The inspectors also reviewed the licensee's analyses for buried piping located beneath
the transport path as documented in Modification Package ON-53112, Part AS4,
Reactor Vessel Head Transport, to ensure that piping would not be damaged.
24
b.
Findings
No findings of significance were identified.
C.
Quality Assurance (QA) Oversight
a.
Inspection Scope
The inspectors reviewed licensee procedures relative to QA oversight of contractor
activities for the RVHRP replacement. In addition, the inspectors discussed
procurement and quality control inspection of various parts, including the Control Rod
Drive Mechanisms (CRDM), Hold Down Bolts, and CRDM (Split Nut) Flange Ring that
were utilized in the attachment of the CRDMs to the Reactor Vessel CRDM flanges.
The inspectors also reviewed a sample of PIPs, non-conformance reports, Purchase
Orders, and Receiving Inspection Reports (Form SCD-311A) pertaining to the above
parts. The inspectors also reviewed the Unit 3 Reactor Vessel Head Penetration
Preservice Inspection conducted in February 2003. The Unit 3 Oconee replacement
reactor vessel head contains sixty-nine alloy 690 penetration tubes that are shrunk fit in
the reactor vessel head and attached with alloy 152/52 partial penetration J-groove
welds. The inspectors reviewed aspects of the inspection program that provided a
baseline of the condition of the accessible outside diameter and inside diameter
surfaces of the vessel head penetration tubes and the partial penetration J-groove welds
attaching the penetration tubes to the reactor vessel head. The review included Scope
of Work, Procedures, Personnel Certifications, Equipment Certifications, and
examination results.
b.
Findings
Introduction: The inspectors identified a Green NCV of 10CFR50.55a(g)(4), which
requires meeting the ASME Boiler and Pressure Vessel Code,Section XI, IWA-7000,
Replacement, and of 10 CFR 50, Appendix B, Criterion VII, Control of Purchased
Material, Equipment, and Services. This resulted in the licensee installing one non-
conforming CRDM (Split Nut) Flange Ring on Unit 2, assembly #18, and discovering
prior to the installation in Unit 3, 68 CRDM (Split Nut) Flange Rings and 552 CRDM Hold
Down Bolts that did not meet the design and procurement specifications.
Description: In April 2003, while the licensee was performing an inspection during the
replacement of the reactor vessel head project, they determined that the CRDM Hold
Down Bolts, and CRDM (Split Nut) Flange Rings did not receive proper QA reviews of
the mechanical/chemical properties and non-destructive examinations (NDE) as
specified in the procurement and design specifications. These reviews and testing were
conducted during the initial mechanical/chemical and NDE testing performed by
independent testing facilities, and subsequently during the receipt inspections performed
by Framatome ANP, who was acting as the contractor for the RVHRP project, and
finally the licensee.
While performing Supply Chain Directive, SACD311, Rev. 1, Receipt Inspection &
Testing of QA Condition Items, the licensee failed to identify that the CRDM (Split Nut)
Flange Rings did not meet the required design and procurement specifications (i.e., a
25
yield strength of 100 ksi and a tensile strength of 125 ksi) for material quality as stated
in the Certificate of Compliance and as defined by ASME SA-320, Grade L43. The
CRDM (split nut) flange rings also did not meet the NDE ultrasonic testing (UT) as
described in ASME Section III, Sub-Article NB-2580 Examination of Bolts, Nuts and
Studs, specifically NB-2586 Ultrasonic Examination for Sizes Over 4 in., requiring the
examination be performed at a nominal frequency of 2.25 Mhz. Also the 552 CRDM
Hold Down Bolts for Unit 3 did not meet the same NDE-UT testing as described in
ASME Section III, Sub-Article NB-2580 Examination of Bolts, Nuts and Studs. Although
not a code requirement, the examination was called for by the design and procurement
specification.
A QA review, performed prior to installation of the components during Unit 3 End of
Cycle (EOC) 20 refueling outage (RFO) in the spring of 2003, led to the identification of
of one non-conforming CRDM (Split Nut) Flange Ring for CRDM Assembly #18 installed
on Unit 2 during the Unit 2 U2EOC19 RFO in the fall of 2002, and removal of 68
uninstalled, non-conforming CRDM (Split Nut) Flange Rings from the site for failure to
meet the mechanical property requirements of the components. This non-conforming
condition was not identified during the Unit 2 EOC19 RFO.
Based on the discovery that one non-conforming CRDM (Split Nut) Flange Ring was
installed on Unit 2, the licensee performed an engineering evaluation that is
documented in Framatome ANP Document 32-5027297-00, Operability Assessment of
CRDM Nut Ring with Reduced Tensile Strength Material. The one CRDM (Split Nut)
Flange Ring installed on Unit 2 was declared to be operable, but degraded, and could
remain in place until the end of the current Unit 2 operating cycle (which is scheduled to
end in the spring of 2004) when the reactor vessel head will be replaced. New CRDM
(Split Nut) Flange Rings with different heat numbers were procured and installed on the
Unit 3 head. The inspectors reviewed the methodology utilized in the engineering
evaluation for the non-conforming flange ring and found that the review was thorough.
The evaluation involved the redoing of all the ASME Code-required calculations for the
connection using the actual strength of the material supplied rather than the minimum
strength required by the material specification.
Analysis: The inspectors determined that this finding was associated with an inadequate
receipt inspection for the above parts. The finding was more than minor because
non-conforming material was actually installed in Unit 2. This deficiency was evaluated
under the SDP. Since there was no loss of function, the Initiating Events and Mitigation
Systems cornerstones were not impacted. The SDP Phase 1 RCS Barrier cornerstone
required an evaluation under SDP Phase 2. A regional senior reactor analyst performed
a SDP Phase 3 analysis and determined that since there was not a loss of function of
the system, there was no increase in risk. The finding was evaluated as Green (very
low safety significance).
Enforcement: 10CFR50.55a(g)(4) specifies in part that components classified as ASME
Code Class 1, Class 2, and Class 3 meet the requirements set forth in Section XI of the
ASME Boiler and Pressure Vessel Code. The ASME Boiler and Pressure Vessel Code,
Section XI, 1989 Edition, with no Addenda, subsection IWA-7220, states in part that
Prior to authorizing the installation of an item to be used for replacement, the Owner
shall conduct an evaluation of the suitability of that item.
26
Also, 10CFR50, Appendix B, Criterion VII, Control of Purchased Material, Equipment,
and Services, states that Measures shall be established to assure that purchased
material, equipment, and services, whether purchased directly or through contractors
and subcontractors, conform to the procurement documents. These measures shall
include provisions, as appropriate, for source evaluation and selection, objective
evidence of quality furnished by the contractor or subcontractor, inspection at the
contractor or subcontractor source, and examination of products upon delivery.
Contrary to the above, during the Unit 2 EOC19 RFO in the fall of 2002, measures taken
to evaluate the suitability of replacement parts were not adequate in that they did not
preclude the installation of one non-conforming CRDM (Split Nut) Flange Ring on CRDM
Assembly #18 on Unit 2. The same QA reviews of the remainder of the 68 CRDM (Split
Nut) Flange Rings and 552 CRDM Hold Down Bolts in the warehouse did not identify the
non-conforming parts prior to the attempt to install them on the Unit 3 reactor vessel
head. Because the finding is of very low safety significance and because the issue is in
the licensees corrective action program under PIPs O-03-2211, O-03-2132, O-03-2177
and O-03-2171, it is being treated as an NCV, consistent with Section VI.A.1 of the NRC
Enforcement Policy. Accordingly, it will be identified as NCV 05000270,287/2003003-
07: Failure to Detect Non-Conforming Parts During Receipt Inspections.
D.
Radiation Protection
a.
Inspection Scope
Radiation safety controls for removal of the Unit 3 reactor vessel head and preparation
of the head for temporary storage were reviewed and evaluated. Licensee procedures
for posting, surveying, and controlling access to radiologically significant areas were
assessed for adequacy. During tours of the Auxiliary Building and the Unit 3
Containment Building, the inspectors evaluated radiological postings and barricades
against current radiological surveys and procedurally established radiological controls.
Radiation Work Permits (RWPs) issued for the RVHRP were reviewed for incorporation
of established access controls. RWP specified alarm setpoints for electronic dosimeters
were also evaluated against current radiological surveys. Health Physics Technician
(HPT) proficiency in providing job coverage and occupational workers adherence to
RWP requirements were evaluated through worker interviews, work area tours and job
site observations. The inspectors observed radiation dose rates measured by an HPT in
the work areas adjacent to the vessel head after it was placed on the head stand. The
observed work area dose rates were compared to the licensees most current
documented survey results.
As Low As Reasonably Achievable (ALARA) planning and controls for the RVHRP were
reviewed and evaluated for consistency with Section IV, ALARA Planning, of the
licensees System ALARA Manual. ALARA Planning Worksheets, ALARA controls,
dose estimates, dose tracking, exposure controls including temporary shielding,
contamination and airborne radioactivity controls, project staffing and training,
emergency contingencies, and temporary storage of the original reactor head assembly
were reviewed and discussed with the licensee. RWPs issued for the RVHRP and their
associated ALARA job briefing packages were examined for incorporation of the ALARA
controls established for the project. Worker adherence to those controls was assessed
27
through job site observations during the movement of original reactor head assembly to
the head stand.
Through the above reviews and observations, the licensees radiation safety program
implementation and practices for the RVHRP were evaluated by the inspectors for
consistency with 10 CFR 20 requirements and approved licensee procedures. Licensee
plans, procedures, and records reviewed during the inspection are listed in the
Attachment to this report.
b.
Findings
No findings of significance were identified.
.2
Institute of Nuclear Power Operations (INPO) Report Review
The inspectors reviewed the final report issued by INPO on April 28, 2003, for the
evaluation that was conducted at the Oconee facility during the weeks of August 5,
2002, and August 12, 2002. The inspectors did not identify any safety issues in the
INPO report that either warranted further NRC followup or that had not already been
addressed by the NRC.
4OA6 Management Meetings
Exit Meeting Summary
The inspectors presented the inspection results to Mr. Ron Jones, Site Vice President,
and other members of licensee management at the conclusion of the inspection on
July 1, 2003. The licensee acknowledged the findings presented.
The inspectors asked the licensee whether any of the material examined during the
inspection should be considered proprietary. No proprietary information was identified
4OA7 Licensee Identified Violation
The following violation of very low safety significance (Green) was identified by the
licensee and is a violation of NRC requirements, which meets the criteria of Section VI
of the NRC Enforcement Policy, NUREG-1600, for being dispositioned as a NCV.
TS Surveillance Requirement (SR) 3.4.12.5 specifies, in part, the required channel
functional test frequency of the PORV to be within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after decreasing RCS
temperature to less than or equal to 325 degrees F. On June 8, 2003, at 4:25 p.m.,
RCS temperature was lowered to less than 325 degrees F. On June 9, 2003, at 4:00
p.m., it was discovered that the channel functional test of the Unit 3 PORV had not
been completed. The functional test was subsequently completed satisfactorily at
3:26 a.m., on June 10, 2003. The circumstances involving this missed surveillance
are described in PIP O-03-03840. Because the subsequent performance of the
missed TS SR was satisfactorily, this violation is of very low safety significance, and is
being treated as a NCV.
Attachment
SUPPLEMENTAL INFORMATION
KEY POINTS OF CONTACT
Licensee
S. Batson, Mechanical/Civil Engineering Manager
J. Batton, Oconee Steam Generator Engineer
D. Baxter, Engineering Manager
N. Constance, Operations Training Manager
C. Curry, Maintenance Manager
T. Curtis, Reactor & Electrical Systems Manager
D. Covar, Training Instructor
C. Eflin, Requalification Supervisor
W. Foster, Safety Assurance Manager
P. Fowler, Access Services Manager, Duke Power
T. Gillespie, Operations Manager
B. Hamilton, Station Manager
B. Jones, Training Manager
R. Jones, Site Vice President
T. King, Security Manager
B. Lowrey, Steam Generator Engineer
L. Nicholson, Regulatory Compliance Manager
R. Repko, Superintendent of Operations
J. Smith, Regulatory Affairs
J. Twiggs, Manager, Radiation Protection
J. Weast, Regulatory Compliance
NRC
L. Reyes, Regional Administrator, Region II
V. McCree, Deputy Director, Division of Reactor Projects, Region II
B. Haag, Chief, Branch 1, Division of Reactor Projects, Region II
C. Carpenter, Chief, Inspection Program Branch, NRR
L. Olshan, Project Manager
ITEMS OPENED, CLOSED, AND DISCUSSED
Opened
05000269,270,287/2003
003-01
Control Room Board Component Thermal
Reliability (Section 1R02b.(1))
05000269,270,287/2003
003-02
HELB Accident Scenario Review (Section
1R02b.(2))
2
05000269,270,287/2003
003-03
Failure to Implement Manufacturers
Recommendations for Replacement of
SSF Diesel Coolant Grommets (Section
1R12.2)
Opened and Closed
05000269,270,287/2003
003-04
Failure to Identify the SSF Degraded
Grommets as a Deficient Condition in
the PIP Corrective Action Program
(Section 1R12.2)05000269/2003003-05
Failure to Maintain Sufficient Records
(logs) to Furnish Evidence of Activities
Affecting Quality (TS LCOs) (Section
1R14b.(1))05000269/2003003-06
Failure to Declare ES Configured
Components Inoperable per TS (Section
1R14b.(2))
05000270,287/2003003-07
Failure to Detect Non-Conforming Parts
during Receipt Inspections (Section
40A5.1C)
Items Discussed
None
LIST OF DOCUMENTS REVIEWED
(Sections 1R02 and 1R17)
Screened Out Items
NSM 12995, Temporary Wiring Procedure
NSM 23092, 600 V MCC and Load Center
NSM 53065, UFSAR revision Section 9.5.1.4.3 Cable Splicing
ONOE- 10642, Upgrade Seismic Supports and Add Isolation Valve 3N-305 to Nitrogen
Line
ONOE- 12107, Upgrade Discharge LPSW Piping from the MDEFDWPM coolers to
1LPSW-527 ONOE- 15414, Replace Valve 2LP-15 with Item DMV-1296 2A LPI
Discharge to RBS Pump Spray and HPI Suction
ONOE- 12094, Modification of Unit 2 RC Vent system Supports/Restraints
ONOE- 12800 ,Provide Clearance Between the Valve Body of 2SF-101 and SSF RC
Makeup Pump Discharge Piping
3
ONOE- 17011, Upgrade 3-CCW-269 to Meet EQ Requirements
ONOE-16856, Revise OSS-0254.00-00-1028
ONOE-16872, UST TAC Sheets
ONOE-16876, Revise Controlled Documents for RM-23A Module
ONOE-16990, Revise Test Acceptance Criteria Sheets for ECCW
ONOE-17068, Adjustable Trip Setting Correction for MCCs
NSM 23092, 600/208 VAC Load Capacity, Rev. 0
ONOE 11721, Include Alarm Setpoints of Stations Transformers in EDB and the OAC, 1
ONOE 14030, Modify Keowee Auxiliary Power Alignment Circuitry
ONOE 14409, Add fuses Between QA1 and Non-QA1 LPI Pump Circuits
ONOE 15256, Upgrade of Red Bus x/y Metering Transformers
ONOE-16712, Revise Maintenance Rule Design Basis Document to Add Reactor Building
Ventilation Functions
Evaluations
NSM 33090, Voltage Adequacy Project NSM-ON-33090/AL3 (RBCU Three Minute Delay),
NSM-23053, Automatic Feedwater Isolation System
Calculation OSC-5325, ECCW Lake Level Verification
EP 3A 1800-01, Revision 39, Turbine Building Flooding [emergency operating porcedure]
NSM 13058, MSLB Leak Detection Circuitry
ONOE 15735, Removed ESF Signal to 3LP-21 and 22
UFSAR Section 3.11.5, Loss of Ventilation
PIPS
PIP O-99-0204
PIP O-91-0121
PIP O-96-0387
PIP O-00-1845
PIP O-98-3062
PIP O-98-2221
PIP-O-01-04635
PIP-O-02-02669
PIP-O-02-00619
PIP-O-02-00054
Audits
Assessment Report Number GO-02-01(NPA)(50.59)(ALL), Applicability Determination and 10
CFR 50.59 Process Evaluation, Assessment Dates 2/4/02 - 2/7/02
PIP-O-03-01300, Level II Assessment of Frametome ANP Compliance to Oconee Contractor
Agreements, 2/18/03 - 2/18/03
PIP-O-03-01736, Level II Assessment 2MOD03001, Review of ONS Temporary Mod Process
4
Calculations
OSC-5267, Flow from UST to Hotwell - MSN-291
OSC-6901, Determination of Average Reactor Building Temperature (Type IV), Rev. 3
04158901-1SP, 12VDC Power Supply, SE P/N 50015966-001
Other Documents Reviewed
MARF #79
(Section 1R04)
Drawings
OFD-114A-1.4, Units 1 & 3 Flow Diagram of CC System (Drain Tank), Revision 5
OFD-144A-3.1, Unit 3 Flow Diagram of CC System (Supply and Return),
Revision 7
OFD-144A-3.2, Unit 3 Flow Diagram of CC System (Reactor Building and Heat Exchangers),
Revision 11
OFD-144A-3.3, Unit 3 Flow Diagram of CC System (Control Rod Drive Service Structure and
Filters), Revision 6
Procedures
Selected Licensee Commitment 16.9.10, CC and HPI Seal Injection to Reactor Coolant
Pumps (RCP)
AP/3/1700/014, Loss of Normal HPI Makeup and/or RCP Seal Injection
AP/3/1700/016, Abnormal Reactor Coolant Pump Operation
AP/3/1700/020, Loss of Component Cooling
Section 6.2.3, Containment Isolation System
Section 9.2.1, Component Cooling System
(Section 1R08)
Procedures
Framatome Technologies Procedure 54-ISI-400-11, Multifrequency Eddy Current Examination
of Tubing, (with Procedure Qualification 54-PQ-400) and Change Notice 30-5027221-00 for
Oconee Unit 3 EOC20 Requirements, dated April 22, 2003
Eddy Current Acquisition Guidelines for Duke Power Companys Once-Through Steam
Generators (OTSG), Rev. 9, April 22, 2003
Data Management Guidelines, Rev. 0, April 23, 2003
Eddy Current Analysis Guidelines for Duke Power Companys Once-Through Steam
Generators (OTSG), Rev. 6, April 22, 2003
5
Other Documents
Framatome ANP Engineering Information Record 51-5028238-00, In-Situ Pressure Test
Summary for Oconee Unit 3 (May 2003)
Duke Power Steam Generator Management Program SGMEP 105, OTSG Specific Assessment
of Potential Degradation Mechanisms for Oconee Unit 3 EOC 20, April 28, 2003
(Sections 40A5.1A-C)
Procedures
Procedure QEP 07.12-3,10CFR50.65(a)(4) Assessment
Procedure QEP 07-12, 10CFR50.59 Evaluations and 10CFR50.65 Assessments
NSD 403, Shutdown Risk Management (Modes 4, 5, 6, and No-Mode) per 10CFR 50.65 (a)(4),
Rev. 11.
NSD 415, Operational Risk Management (Modes 1, 2, 3) per 10CFR 50.65 (a)(4), Rev. 1.
NSD 209, 10CFR50.59 Process, Rev. 9.
Mcinnes Steel Company Ultrasonic Test (UT) Procedure No. UT-SA388-95, Rev. 0
General Nuclear Corporation, Magnetic Particle Examination, Wet Continuous Method GNC-
054, Rev. 1
Supply Chain Directive, SACD311, Rev. 1, Receipt Inspection & Testing of QA Condition Items
Other Documents
Modification Package - RV Head Components Modification, Modification #33112, Part No. AM7,
Rev. 0.
Reactor Vessel Closure Head Replacement Project, Oconee Nuclear Power Plant Units 1, 2, &
3, Input Document for Replacement RVCHA Licensing and Safety Evaluation April 2003.
Modification Package - Reactor Vessel Head Rigging and Handling, Modification # ON33112,
Part No. AS1, Rev. 1.
Modification Package Review - Replacement of Reactor Vessel Closure Head, Service
Structure and Associated Components, Modification # ON33112, Part No. 000, Rev. 0
(including 10CFR50.59 Screen).
Specification for Reactor Vessel for Duke Power Company, March 19, 1973
Oconee Unit 3, Rector Vessel Head Penetration Preservice Inspection, February 2003
Input Document for Replacement RVCHA Licensing and Safety Evaluation, April 2003
Oconee Unit 3 Reactor Vessel Head Penetration Preservice Inspection - February 2003, Final
Report
Various site engineering drawings including Head Movement Drawings from Mammoet
Various FANP calcs and NCRs
Framatome ANP Document 32-5027297-00, Operability Assessment of CRDM Nut Ring with
Reduced Tensile Strength Material
PIPs: O-03-2132, O-03-2211, O-03-2177, O-03-2171, O-03-2922, O-03-2998, O-03-2844, O-
03-1218, O-03-2898
Framatome ANP NCRs: 6025753, 32-5027297-00, 6024468, 6024579, 6025325
Purchase Orders (POs): NS146-001, NS146-002, ON52461, ON13513
Receipt Inspection Reports for: PO NS146-001, PO NS146-002, PO ON52461, PO ON13513
Corrective Action Reports (CARs): 6025777-00
6
(Section 40A5.1D)
Procedures, Plans, and Manuals
Standard Health Physics Procedure (SH) SH/0/B/2000/005, Posting of Radiation Control
Zones, Revision (Rev.) 1
SH/0/B/2000/012, Access Controls for High, Extra High, and Very High Radiation Areas,
Rev. 1
Duke Power Company System ALARA Manual,Section IV, ALARA Planning, Rev. 15,
10/15/02
Radiation Protection (RP) Job Coverage Plan, Rev. 1, 4/9/03
RP-012, Surveillance Plan, Rev. 0, 4/15/03
Records
ALARA Planning Worksheet - Unit 3 Reactor Head Replacement - Install and Remove
Scaffolding (Equipment Chase Area and Reactor Head Stand)
ALARA Planning Worksheet - Unit 3 RHRP Install Shielding, Encapsulate Reactor Head and
Decon Activities
ALARA Planning Worksheet - Unit 3 Reactor Head Replacement - Remove and Install
Interferences in Equipment Chase Area
ALARA Planning Worksheet - Unit 3 Reactor Head Replacemant - Electrical/Mechanical
Disconnects and Reconnects, Remove/Install Interferences, CRD Remmoval
ALARA Planning Worksheet - Unit 3 Reactor Head Replacement - Install and Remove
Lifting Equipment, Remove ORVH and Install RRVH
Radiation Survey Report 050603-30, Reactor Vessel Head, 5/6/03
Radiation Survey Report 050703-1, Reactor Vessel Head, 5/6/03
ALARA Briefing Packages for Radiation Work Permits 6375, 6376, 6377, 6378, 6379,
and 6380
Daily Exposure reports for 5/6 & 7/03
Radiation Work Permits (RWPs)
RWP 6375, U3 Rx Bldg - RHRP - Install and Remove Scaffolding, Rev. 0, 02/06/03
RWP 6376, U3 Rx Bldg - RHRP - Install Shielding, Encapsulate Rx Head, and Decon
Activities, Rev. 0, 02/06/03
RWP 6377, U3 Rx Bldg - RHRP - Remove and Install Interferences in the Equipment
Chase Area, Rev. 0, 02/06/03
RWP 6378, U3 Rx Bldg - RHRP - Remove and Install Rx Head Interferrences, Piping, and
all CRDM Work, Rev. 0, 02/06/03
RWP 6379, U3 Rx Bldg - RHRP - Install and Remove Lifting Equipment, Remove Original
Reactor Head Assembly (RHA) and Install Replacement RHA, Rev. 0, 02/06/03
RWP 6380, U3 Rx Bldg - RHRP - Load, Transport and Store Original RHA, Incluses All
Outside Work, Rev. 0, 02/06/03
7
LIST OF ACRONYMS
-
Agencywide Documents Access and Management System
-
As Low As Reasonably Achievable
-
American Society of Mechanical Engineers
BCM
-
Boiler/Condenser Mode
BWST
-
Borated Water Storage Tanks
-
Component Cooling
CFR
-
Code of Federal Regulations
-
Core Operating Limits Report
-
Control Rod Drive Mechanism
-
Duke Energy Corporation
-
Duke Power Company
-
Emergency Feedwater
-
-
End of Cycle
-
Engineered Safeguards
-
Engine Systems, Inc
-
-
Final Safety Analysis Report
-
-
High Pressure Injection
HPT
-
Health Physics Technician
-
Institute of Nuclear Power Operations
IR
-
Inspection Report
-
Inservice Testing
-
Large Break Loss of Coolant Accident
LCO
-
Limiting Condition for Operation
-
Local Leak Rate Test
-
Low Pressure Injection
-
Low Pressure Service Water
-
Non-Cited Violation
-
NRC
-
Nuclear Regulatory Commission
-
Nuclear Reactor Regulation
NSM
-
Nuclear Station Modification
OFD
-
Oconee Flow Diagram
ONOE
-
Minor Modification
-
Oconee Nuclear Station
-
Once-Through Steam Generator
-
Performance Indicators
-
Problem Investigation Process (report)
-
Performance Test
-
Post-Maintenance Testing
-
Power Operated Relief Valve
-
Quality Assurance
-
Quality Control
RBCU
-
Reactor Building Cooling Unit
-
Reactor Building Spray
8
-
Reactor Coolant Pump
-
-
Refueling Outage
-
Rated Thermal Power
RVHRP
-
Reactor Vessel Head Replacement Project
-
Radiation Work Permit
-
Small Break Loss of Coolant Accident
-
Significance Determination Process
-
SR
-
Surveillance Requirement
-
Structure, System and Component
SSF
-
Standby Shutdown Facility
-
Turbine Driven Emergency Feedwater
TS
-
Technical Specification
-
Updated Final Safety Analysis Report
-
Unresolved Item
-
Ultrasonic Testing