IR 05000269/2023002

From kanterella
Jump to navigation Jump to search
Integrated Inspection Report 05000269/2023002, 05000270/2023002 and 05000287/2023002
ML23208A326
Person / Time
Site: Oconee  
(DPR-038, DPR-047, DPR-055)
Issue date: 07/28/2023
From: Eric Stamm
NRC/RGN-II/DRP/RPB1
To: Snider S
Duke Energy Carolinas
References
IR 2023002
Download: ML23208A326 (17)


Text

SUBJECT:

OCONEE NUCLEAR STATION - INTEGRATED INSPECTION REPORT 05000269/2023002, 05000270/2023002 AND 05000287/2023002

Dear Steven Snider:

On June 30, 2023, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Oconee Nuclear Station. On July 27, 2023, the NRC inspectors discussed the results of this inspection with Jamie Dodson and other members of your staff. The results of this inspection are documented in the enclosed report.

No findings or violations of more than minor significance were identified during this inspection.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely, Eric J. Stamm, Chief Reactor Projects Branch 1 Division of Reactor Projects Docket Nos. 05000269, 05000270 and 05000287 License Nos. DPR-38, DPR-47 and DPR-55

Enclosure:

As stated

Inspection Report

Docket Numbers:

05000269, 05000270 and 05000287

License Numbers:

DPR-38, DPR-47 and DPR-55

Report Numbers:

05000269/2023002, 05000270/2023002 and 05000287/2023002

Enterprise Identifier:

I-2023-002-0021

Licensee:

Duke Energy Carolinas, LLC

Facility:

Oconee Nuclear Station

Location:

Seneca, South Carolina

Inspection Dates:

April 1, 2023, to June 30, 2023

Inspectors:

J. Nadel, Senior Resident Inspector

N. Smalley, Acting Senior Resident Inspector

A. Ruh, Resident Inspector

A. Hutto, Senior Project Engineer

B. Kellner, Senior Health Physicist

D. Neal, Health Physicist

N. Peterka, Senior Fuel Facility Project Inspector

J. Rivera, Health Physicist

Approved By:

Eric J. Stamm, Chief

Reactor Projects Branch 1

Division of Reactor Projects

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting an integrated inspection at Oconee Nuclear Station, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

None.

PLANT STATUS

Unit 1 operated at or near 100 percent rated thermal power (RTP) for the entire inspection period.

Unit 2 operated at or near 100 percent RTP for the entire inspection period.

Unit 3 operated at or near 100 percent RTP from the beginning of the inspection period until June 24, 2023, when a power reduction to 20 percent RTP was conducted for leak hunt activities. On June 25, 2023, the unit was shut down to repair a leak on low pressure service water system piping. Unit 3 was started up and returned to 20 percent RTP on June 26, 2023.

On June 27, 2023, Unit 3 operated at or near 100 percent RTP for the remainder of the inspection period.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors performed activities described in IMC 2515, Appendix D, Plant Status, observed risk significant activities, and completed on-site portions of IPs. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

REACTOR SAFETY

71111.04 - Equipment Alignment

Partial Walkdown Sample (IP Section 03.01) (4 Samples)

The inspectors evaluated system configurations during partial walkdowns of the following systems/trains:

(1) Units 1 and 2 low pressure service water system following restoration of low pressure service water train C on April 11, 2023
(2) Keowee Hydro Unit 1 governor oil and actuator systems while Keowee Hydro Unit 2 was out of service for planned maintenance on May 9, 2023
(3) Keowee Hydro Unit 1 electrical alignment while Keowee Hydro Unit 2 was out of service for planned maintenance on May 9, 2023 (4)2A low pressure injection train following maintenance on May 23, 2023

71111.05 - Fire Protection

Fire Area Walkdown and Inspection Sample (IP Section 03.01) (5 Samples)

The inspectors evaluated the implementation of the fire protection program by conducting a walkdown and performing a review to verify program compliance, equipment functionality, material condition, and operational readiness of the following fire areas:

(1) Fire zone 112: Unit 3 control room on April 28, 2023
(2) Fire zone 19: Unit 1 main feed pump area on April 28, 2023
(3) Fire zone 89: Unit 3 equipment room on May 15, 2023
(4) Fire zone 105: Unit 2 cable room on June 22, 2023
(5) Fire zone 85: Unit 1 auxiliary building 200 level hallway on June 23, 2023

71111.06 - Flood Protection Measures

Flooding Sample (IP Section 03.01) (1 Sample)

(1) The inspectors evaluated internal flooding mitigation protections in the embedded conduits for diesel generator cabling in the standby shutdown facility.

71111.11Q - Licensed Operator Requalification Program and Licensed Operator Performance

Licensed Operator Performance in the Actual Plant/Main Control Room (IP Section 03.01) (1 Sample)

(1) The inspectors observed and evaluated licensed operator performance in the main control room during Keowee hydro station over frequency testing on May 3, 2023, and Unit 3 downpower on June 24, 2023.

Licensed Operator Requalification Training/Examinations (IP Section 03.02) (1 Sample)

(1) The inspectors observed and evaluated SEG 2211, Cold Crew Simulator Evaluation, on May 22, 2023.

71111.12 - Maintenance Effectiveness

Maintenance Effectiveness (IP Section 03.01) (1 Sample)

The inspectors evaluated the effectiveness of maintenance to ensure the following structures, systems, and components remain capable of performing their intended function:

(1) Nuclear condition reports (NCR) 2473173, 2466960, low pressure service water pump C fail to run events on March 29, and May 17, 2023

71111.13 - Maintenance Risk Assessments and Emergent Work Control

Risk Assessment and Management Sample (IP Section 03.01) (6 Samples)

The inspectors evaluated the accuracy and completeness of risk assessments for the following planned and emergent work activities to ensure configuration changes and appropriate work controls were addressed:

(1) Units 1, 2, and 3, green risk during underground emergency power path planned maintenance, on April 11, 2023
(2) Unit 2 green risk during control rod drive pulse generator and monitoring module replacement, on April 12, 2023
(3) Units 1, 2, and 3, green risk during heavy lifts and construction activity in 230kV switchyard, on April 18, 2023
(4) Units 1, 2, and 3, green risk during Keowee Hydro Unit 2 planned maintenance, on May 9, 2023
(5) Units 1 and 2, green risk during low pressure service water pump inoperability and troubleshooting, on May 18, 2023
(6) Units 1, 2, and 3, yellow risk during standby shutdown facility annual maintenance outage, on June 14, 2023

71111.15 - Operability Determinations and Functionality Assessments

Operability Determination or Functionality Assessment (IP Section 03.01) (8 Samples)

The inspectors evaluated the licensee's justifications and actions associated with the following operability determinations and functionality assessments:

(1) NCR 2468647, low pressure service water suction strainer to pump expansion joint control unit gaps different than specified on drawings
(2) NCR 2471437, deficiencies with essential siphon vacuum post modification testing from 2001
(3) NCR 2473099, low pressure service water pump testing concerns due to flow instrument accuracy
(4) NCR 2474520, essential siphon and vacuum system pump suction check valves may not fully open at low air pressures
(5) NCR 2436929, Unit 1 inservice inspection exam failure to comply with all aspects of 10 CFR 50.55a and ASME IWL for containment tendon maintenance
(6) NCR 2465304, increased Keowee hydro unit station sump flow challenging time critical actions
(7) NCR 2477210, low pressure service water leak from instrument line on 3A1 reactor coolant pump upper bearing oil cooler outlet piping
(8) NCR 2477220, 3MS-8 main steam line relief valve lifted during Unit 3 shutdown

71111.18 - Plant Modifications

Temporary Modifications and/or Permanent Modifications (IP Section 03.01 and/or 03.02) (1 Sample)

The inspectors evaluated the following temporary or permanent modifications:

(1) Engineering change 422866, repair broken Unit 3 reactor coolant pump motor cooler A1 bearing outlet pressure connection with alternate piping configuration

71111.24 - Testing and Maintenance of Equipment Important to Risk

The inspectors evaluated the following testing and maintenance activities to verify system operability and/or functionality:

Post-Maintenance Testing (PMT) (IP Section 03.01) (5 Samples)

(1) PT/2/A/0620/009, Keowee Operation, following replacement of 13.8kV transformer K2-ELK-TF-2E, on May 10, 2023
(2) OP/0/A/1650/005, PSW AC Power, following replacement of protected service water breaker B7T-2 with a refurbished unit, on May 11, 2023
(3) Work orders (WO) 20549009 and 20549064, Auxiliary service water pump functional test following lubrication and alignment check on June 14, 2023,
(4) PT/0/A/0400/011, SSF Diesel Generator Test, following annual maintenance, on June 15, 2023
(5) MP/0/A/1200/089, Valve - Main Steam Safety - Setpoint Test, on June 26, 2023

Surveillance Testing (IP Section 03.01) (3 Samples)

(1) Unit 1 ASME IWL year 50 containment tendon surveillances, WO 20376931-34
(2) PT/1/A/0204/07B, 1B Reactor Building Spray Pump Test, on April 20, 2023
(3) PT/0/A/0620/019, Keowee Over Frequency Protection Functional Test, on May 3, 2023

Inservice Testing (IST) (IP Section 03.01) (1 Sample)

(1) PT/1/A/0251/001, Low Pressure Service Water Pump Test of 'A' pump, on June 21,

RADIATION SAFETY

71124.06 - Radioactive Gaseous and Liquid Effluent Treatment

Walkdowns and Observations (IP Section 03.01) (4 Samples)

The inspectors evaluated the following radioactive effluent systems during walkdowns:

(1) Unit 3, auxiliary building ventilation system discharge to plant vent stack
(2) Unit 3, penetration room ventilation system discharge to plant vent stack
(3) Unit 1, auxiliary building ventilation system discharge to plant vent stack
(4) Radioactive liquid waste line to the Keowee dam mixing line and ultimate discharge point

Sampling and Analysis (IP Section 03.02) (3 Samples)

Inspectors evaluated the following effluent samples, sampling processes and compensatory samples:

(1) Rad waste facility ventilation exhaust gas sample (8-hour compensatory sample due to RIA-45 being out of service), on June 13, 2023
(2) Unit 2 vent stack routine weekly gaseous grab sample, on June 14, 2023
(3) Unit 2 vent stack routine weekly tritium grab sample, on June 14, 2023

Dose Calculations (IP Section 03.03) (2 Samples)

The inspectors evaluated the following dose calculations:

(1) Gaseous radioactive release permit #G2023661, (including dose calculation for the maximum individual receptor) May 11, 2023
(2) Liquid radioactive release permit #L2023542, (including dose calculation for the maximum individual receptor) May 15, 2023

71124.07 - Radiological Environmental Monitoring Program

Environmental Monitoring Equipment and Sampling (IP Section 03.01) (1 Sample)

(1) The inspectors evaluated environmental monitoring equipment and observed collection of environmental samples.

Radiological Environmental Monitoring Program (IP Section 03.02) (1 Sample)

(1) The inspectors evaluated the implementation of the licensees radiological environmental monitoring program.

GPI Implementation (IP Section 03.03) (1 Sample)

(1) The inspectors evaluated the licensees implementation of the groundwater protection initiative program to identify incomplete or discontinued program elements.

OTHER ACTIVITIES - BASELINE

===71151 - Performance Indicator Verification The inspectors verified licensee performance indicators submittals listed below:

MS05: Safety System Functional Failures (SSFFs) Sample (IP Section 02.04)===

(1) Unit 1 (April 1, 2022, through March 31, 2023)
(2) Unit 2 (April 1, 2022, through March 31, 2023)
(3) Unit 3 (April 1, 2022, through March 31, 2023)

MS08: Heat Removal Systems (IP Section 02.07) (3 Samples)

(1) Unit 1 (April 1, 2022, through March 31, 2023)
(2) Unit 2 (April 1, 2022, through March 31, 2023)
(3) Unit 3 (April 1, 2022, through March 31, 2023)

MS10: Cooling Water Support Systems (IP Section 02.09) (3 Samples)

(1) Unit 1 (April 1, 2022, through March 31, 2023)
(2) Unit 2 (April 1, 2022, through March 31, 2023)
(3) Unit 3 (April 1, 2022, through March 31, 2023)

BI02: RCS Leak Rate Sample (IP Section 02.11) (3 Samples)

(1) Unit 1 (April 1, 2022, through March 31, 2023)
(2) Unit 2 (April 1, 2022, through March 31, 2023)
(3) Unit 3 (April 1, 2022, through March 31, 2023)

PR01: Radiological Effluent Technical Specifications/Offsite Dose Calculation Manual Radiological Effluent Occurrences (RETS/ODCM) Radiological Effluent Occurrences Sample (IP Section 02.16) (1 Sample)

(1) March 31, 2022, through May 31, 2023

71152S - Semiannual Trend Problem Identification and Resolution Semiannual Trend Review (Section 03.02)

(1) The inspectors reviewed the licensees corrective action program for potential adverse trends in complacency and procedure use and adherence that might be indicative of a more significant safety issue.

71153 - Follow Up of Events and Notices of Enforcement Discretion Personnel Performance (IP Section 03.03)

(1) The inspectors evaluated a Unit 3 unidentified reactor building normal sump level transient, leak hunt activities, power reduction, and the licensees performance on June 23,

INSPECTION RESULTS

No findings were identified.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

On June 15, 2023, the inspectors presented the public radiation safety inspection results to Steven Snider and other members of the licensee staff.

On July 27, 2023, the inspectors presented the integrated inspection results to Jamie Dodson, Plant Manager, and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Corrective Action

Documents

2473822

OFD-102A-2.2

Flow Diagram of Low Pressure Injection System LPI Pump

Discharge

Drawings

OM 260-0114.002

20 High Pressure Exp. Jnt. W/ Retaining Rings & Control

Units

Miscellaneous

Clearance OPS-2-17-LP-2LP-154-2001

71111.04

Work Orders

1997065, 20091928, 20214933, 20375226, 20518466,

20534642

OSC-10816

ONS TCCA A and B Area Basis for AD-EG-ALL-1520

005

OSC-9314

NFPA 805 Transition Risk-Informed Performance-Based

Fire Risk Evaluation

006

Calculations

OSC-9375

ONS Fire PRA - Fire Scenario Report

011

Corrective Action

Documents

2453993, 2456397, 2469135, 2454161, 2454234, 2458096

CSD-ONS-PFP-

1AB-0783

Pre-Fire Plan for U1 Auxiliary Building Elevation 783

000

CSD-ONS-PFP-

1TB-0775

Pre-Fire Plan for U1 Turbine Building Elevation 775

000

CSD-ONS-PFP-

2AB-0809

Pre-Fire Plan for U2 Auxiliary Building Elevation 809

000

CSD-ONS-PFP-

3AB-0796

Pre-Fire Plan for U3 Auxiliary Building Elevation 796

001

CSD-ONS-PFP-

3AB-0822

Pre-Fire Plan for U3 Auxiliary Building Elevation 822

000

O-0310-K-004

Auxiliary Building Unit 1 Fire Protection Plan & Fire Barrier,

Flood, & Pressure Boundaries Plan at EL 783+9

009

O-0310-K-011

Auxiliary Building Unit 2 Fire Protection Plan & Fire Barrier,

Flood, & Pressure Boundaries Plan at EL 809+3

009

O-0310-L-001

Fire Protect Turbine Building Unit 1 EL 775+0

011

71111.05

Fire Plans

O-310-K-09

Auxiliary & Reactor Building Unit 3 Fire Protection Plan &

Fire Barrier, Flood & Pressure Boundaries Plan at EL 796+6

& 797+6

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

O-310-K-15

Auxiliary & Reactor Building Unit 3 Fire Protection Plan &

Fire Barrier, Flood & Pressure Boundaries Plan at EL 822+0

& 825+0

O-310-S3-13

Unit 3 Equipment Room Sprinkler System Plan

AD-FP-ALL-1520

Transient Combustible Control

O-0423-AA

Temporary Piping Layout at Alternate RBCU Cooling RBCU

Hale Pump and Hose Layout

2

OFD-124C-1.2

Flow Diagram of High Pressure Service Water System

Turbine Building

Miscellaneous

OFD-124C-3.2

Flow Diagram of High Pressure Service Water System

Turbine Building

AP/3/A/1700/050

Challenging Plant Fire

007

OP/0/A/1106/029

C

Alternate Chilled Water System

2

Procedures

OP/1/A/1104/015

Reactor Building Cooling System

046

Work Orders

20547696, 20597879, 20597865, 20597997, 20597919

Corrective Action

Documents

1907447, 1933544, 2468954

Drawings

O-954-B

Electrical Equipment Layout Standby Shutdown Facility

Embedded Conduit Diesel Room

71111.06

Work Orders

1649300

Miscellaneous

Simulator Exercise Guise SEG 2211

AD-OP-ALL-0203

Reactivity Management

OP/0/A/1108/001

Curves and General Information

118

OP/3/A/1102/001

Controlling Procedure for Unit Startup

284

OP/3/A/1102/004

Operation at Power

141

71111.11Q

Procedures

OP/3/A/1104/007

LWD [Liquid Waste Disposal] System

71111.12

Corrective Action

Documents

2473173, 2466960

Corrective Action

Documents

2466960, 2473173

Drawings

OEE-217-22

Elementary Diagram 4160V Switchgear #2TC Unit #11 L.P.

Service Water Pump Motor No. C0LPSPU000C

71111.13

Miscellaneous

SSF Annual Outage Protected Equipment

06/13/2023

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Unit 1 and 2 Phoenix Online Risk Monitor report for

scheduled work week 23W15

IP/0/A/0380/006

Standby Shutdown Facility Diesel Load and Speed Control

IP/0/B/0350/010

CRD Triplex TMR Module Hot/Smart Swap

Procedures

OP/0/A/1600/010

Operation of the SSF Diesel-Generator

Work Orders

20595122, 20603157, 20603158

KC-2003

Turbine Sump Pump Flow Calculation

004

OSC-10899

Analysis of Condensate Coolers A & B Suction and

Discharge Piping, Problem No. 1-13-13

OSC-2708

Rigorous Piping Analysis for Problem 1-14-19 (From LPSW

Strainers to LPSW Pumps)

OSC-6118

Loss of Non Emergency AC Power Event Mitigation

Requirements Type III

016

OSC-6868

Design Input Calculation for NSM-1/33002 Installation for

Reduced NPSH Impeller in Units 1,2,3 LPSW Pumps

OSC-7177

Parametric Study of ESV Float Valve Opening

Characteristics

OSC-7349

Functional Testing of Prototype ESV Float Valve

OSC-7734

Maximum Hypothetical Accident (MHA) Dose Analysis

016

Calculations

OSC-8966

Allowable LPSW Leakage for Containment Operability

Corrective Action

Documents

1773377, 2465304, 2465908, 2465300, 2462512, 181218,

2459895, 2477220, 2477611

KFD-102A-1.1

Flow Diagram of Turbine Sump Pump System

O-2480D

Piping Layout Section and Details Intermediate Floor

Reactor Building

OFD-107B-3.1

Flow Diagram of Liquid Waste Disposal System Reactor

Building Normal Sump

OFD-124B-3.2

Flow Diagram of Low Pressure Service Water System

Reactor Building Cooling Units Cooling Coils 3A, 3B & 3C

OFD-124B-3.4

Flow Diagram of Low Pressure Service Water System RC

Pump Motor Cooling and RB Fire Protection

Drawings

OM 245-1672.001

1878 Socket Ends Stainless Steel Swing Check Valve Non

Cobalt Trim with Resilient Seated Disc

71111.15

Engineering

Changes

410347

Evaluation of Keowee Station Sump Inputs in Support of EC 405339

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

2900

Various, Expansion Joints, Garlock, LFC/KCM Dimension

Changes

LCOTR O-3-23-

00979

U3 RBCU leak isolation

OSS-0254.00-00-

1046

(MECH) Design Basis Spec for Keowee Turbine Generator

Cooling Water (WL) System

017

OSS-0254.00-00-

1047

(Mech) Design Basis Spec for Keowee Turbine Sump Pump

(TS) System

015

Miscellaneous

OSS-0254.00-00-

4001

(Mech) Design Basis Spec for Reactor Building Containment

Isolation

AP/0/A/2000-002

Keowee Hydro Station - Emergency Start

IP/1/A/0400/022

KHU-1 Turbine Sump Pump Level Control Switch

Calibration

011

OP/0/A/2000/013

KHU-1 Generator

29

PT/1/A/2200/019

KHU-1 Turbine Sump Pump IST Surveillance

28

PT/3/A/0150/034

Leak Rate History Record and Reactor Building Leak Rate

Verification

PT/3/A/0251/001

Low Pressure Service Water Pump Test

101

PT/3/A/0251/072

LPSW System Flow Balance Verification

TT/2/A/0261/011

ESV Float Valves Retest

TT/2/A/0261/012

ESV Float Valve Test

Procedures

TT/3/A/0251/064

LPSW Pump Test

Work Orders

01734488, 20500888, 20582077, 20610258

Corrective Action

Documents

2477210

Engineering

Changes

2866

Repair Broken 3LPSPX0009 Pressure Connection with

Alternate Piping Configuration

001

71111.18

Work Orders

20610262, 20610255

Calculations

ONTC-3-MS-008

Unit 3 Relief Valve Test Acceptance Criteria

Corrective Action

Documents

2466315, 2475870, 2476203, 2476262

O-6700

One-Line Diagram Main PSW Switchgear 13.8/4.16 kV

System

71111.24

Drawings

OFD-135B-1.4

Flow Diagram of Lube Oil System SSF Diesel Engines

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

IP/0/A/2001/015

PSW 13.8/4.16 kV Square D Type VR Vacuum Circuit

Breaker Inspection and Maintenance

005

IP/0/A/2001/016

PSW 13.8/4.16 kV Vacuum Circuit Breaker Removal and

Installation

OP/0/A/1650/005

PSW AC Power

20

PT/0/A/0620/009

Keowee Hydro Operation

056

PT/0/A/0620/019

Keowee Over Frequency Protection Functional Test

015

Procedures

PT/1/A/0204/007

Reactor Building Spray Pump Test

106

Work Orders

20595783, 20610258

Corrective Action

Documents

AR 02342810, AR 02377923, AR 02412872, AR 02434482,

AR 02442786, and AR 02464568,

Various

Corrective Action

Documents

Resulting from

Inspection

AR 02475972

Radiological Posting Sign found on the floor

06/13/2023

Memorandum: 2023 Oconee Annual Land Use Census

06/14/2023

Memorandum: 2020 Oconee Annual Land Use Census

06/04/2020

Memorandum: 2021 Oconee Annual Land Use Census

06/17/2021

Memorandum: 2022 Oconee Annual Land Use Census

06/07/2022

Out of Service (OOS) effluent monitor reports and control

room logs from June 2020 thru May 2023

Various

20 Oconee Nuclear Station Units 1, 2, and 3 Annual

Radioactive Effluent Release Report

04/30/2021

21 Oconee Nuclear Station Units 1, 2, and 3 Annual

Radioactive Effluent Release Report

04/30/2022

22 Oconee Nuclear Station Units 1, 2, and 3 Annual

Radioactive Effluent Release Report

04/30/2023

Performance Test

Penetration Room Ventilation System Functional Test per

PT/3/A/0170/019, Revision 2

11/03/2022

PT/1-

2/A/0150/025

LWD System Leakage

10/17/2022

Miscellaneous

PT/3/A/0150/026

GWD [Gas Waste Decay] System Leakage Test

07/06/2022

71124.06

Procedures

Oconee Nuclear Station Selected Licensee Commitments

(SLC), Section 16.11, Radiological Effluents Control

10/26/2022

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Oconee Nuclear Station Units 1, 2, and 3 Offsite Dose

Calculation Manual (ODCM)

Oconee Nuclear Station Units 1, 2, and 3 Offsite Dose

Calculation Manual (ODCM)

AD-CP-ALL-0023

Preparation of the Annual Radioactive Effluent Release

Report

HP/0/B/1000/060

D

Vent and Air Ejector Sampling

OP/0/A/1104/068

Waste/Recycle Monitor Tank Release from Radwaste

Facility

OP/0/A/1104/076

Manual Calculations for Liquid Effluent Releases

Qualification

Number: ON-RP-

041

Perform Gaseous Waste Release Rate Determinations

TQ-RWO-0011

Training and Qualification Guide No. ON-OPS-RWO0011,

Liquid Waste Release to Keowee Tailrace

22-ONS-

RPCH-01

Nuclear Oversight Audit - Oconee Radiation Protection and

Chemistry

10/20/2022

Self-Assessments

AR 02362921

Radioactive Effluents 10CFR20 Compliance Assessment

06/02/2021

WO 20500895

Penetration Room Ventilation System Functional Test per

PT/3/A/0170/019, Revision 2

06/11/2022

WO 20516627

Unit 2 Reactor Building Stack Flow Instrument Calibration

01/23/2023

Work Orders

WO 20446378

Unit 2 Reactor Building Stack Flow Instrument Calibration

01/20/2022

Corrective Action

Documents

AR 02333218

06/02/2020

AR 02475826

Pump Found Unplugged for REMP SW Location 062

06/12/2023

Corrective Action

Documents

Resulting from

Inspection

AR 02477126

NRC Inspection Question on MET Tower Inspections for

Guyed Wires / 10L rule

Miscellaneous

Tower Systems South, Inc. MET Tower Inspection Reports,

10M and 60M

06/08/2020

Procedures

AD-CP-ALL-0017

Radiological Groundwater Protection

20522453 01

Meteorological Equipment Calibration (Semi-Annual)

09/20/2022

71124.07

Work Orders

20556051 01

Meteorological Equipment Calibration (Semi-Annual)

03/30/2023

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Corrective Action

Documents

AR 02432377, and AR 02436130

Various

Oconee Liquid and Gas Dose Summary Report, January 1

through 5/13/2023 [including monthly, quarterly, and annual

dose totals]

06/14/2023

MSPI Derivation Report Oconee Unit 3 Cooling Water

System Unreliability Index, March 2023

MSPI Margin Report Oconee Units 1, 2 and 3 Cooling Water

and Heat Removal Systems, March 2023

MSPI Derivation Report Oconee Unit 2 Heat Removal

System Unreliability Index, March 2023

Miscellaneous

22 Oconee Liquid and Gas Dose Summary Report

[including monthly, quarterly, and annual dose and individual

isotopic activity totals]

05/16/2023

AD-RP-ALL-1101

Performance Indicators (PI) for the Occupational Radiation

Safety Cornerstone and for the Public Radiation Safety

Cornerstones

PT/1/A/0600/010

Reactor Coolant Leakage

2

PT/2/A/0600/010

Reactor Coolant Leakage

71151

Procedures

PT/3/A/0600/010

Reactor Coolant Leakage

Corrective Action

Documents

2456972, 2415853, 2357711, 2443366, 2450253, 2423411,

2436929, 2425299, 2444507, 2467763, 2468647, 2470090,

2468145, 2474146, 2474149

AD-PI-ALL-0100

Corrective Action Program

AD-PI-ALL-0106

Cause Investigation Checklists

71152S

Miscellaneous

AD-PI-ALL-0200

Performance Trending

Miscellaneous

AD-OP-ALL-1000

Conduct of Operations

AP/3/A/1700/053

Abnormal Feedwater Heater Operations

000

71153

Procedures

OP/3/A/1104/017

Quench Tank Operation

53