AmerenUE PO Box 620 Callaway Plant Fulton, MO 65251 March 17, 2003 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Mail Stop P 1-137 Washington, DC 20555-0001 ULNRC-04823 wAmeren lie.

Ladies and Gentlemen:

Ur DOCKET NUMBER 50-483 CALLAWAY PLANT UNIT 1 UNION ELECTRIC CO.

FACILITY OPERATING LICENSE NPF-30 Results of the Thirteenth Steam Generator Tube In-Service Inspection The enclosed Special Report is submitted pursuant to the requirements of Callaway Technical Specification 5.6.1O.b concerning the Inservice Inspection of Callaway's Steam Generators performed in November 2002 during Callaway Plant's twelfth refueling outage. This report documents the final Steam Generator inspection results.

Additionally, Callaway is submitting the enclosed Steam Generator Condition Monitoring Report as described in Nuclear Energy Institute document NEI 97-06 Revision 1. With NEI 97-06 in effect, a report is required when greater than one percent of inspected Steam Generator tubes exceed the established Steam Generator repair criteria This condition monitoring report is required to be submitted within 120 days after the reactor coolant system re-enters hot shutdown conditions Licensee Event Report 2002-011-00 reported this condition in "A" Steam Generator following tube inspections conducted in the Refuel 12 outage Respectfully, Warren A. Witt Manager, Callaway Plant WAW/BEH/IB SC/ewh Enclosure 74oy7 a subsidiaryofAmeren Corporation

ULNRC04823 March 17, 2003 Page 2 cc: U. S. Nuclear Regulatory Commission (Original and 1 copy)

Attn: Document Control Desk Mail Stop P 1-137 Washington, DC 20555-0001 Mr. Ellis W. Merschoff Regional Administrator U.S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 400 Arlington, TX 76011-4005 Senior Resident Inspector Callaway Resident Office U.S. Nuclear Regulatory Commission 8201 NRC Road Steedman, MO 65077 Mr. Jack N. Donohew (2 copies)

Licensing Project Manager, Callaway Plant Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Mail Stop 7El Washington, DC 20555-2738 Manager, Electric Department Missouri Public Service Commission PO Box 360 Jefferson City, MO 65102

Pages 3 and 4 deliberately left blank ULNRC-04823 March 12,2003 Page 5 SPECIAL REPORT RESULTS OF THIRTEENTH STEAM GENERATOR TUBE IN-SERVICE INSPECTION REPORTING REQUIREMENTS:

Technical Specification AC 5.6.10.b requires that "complete results of the steam generator tube inservice inspection shall be submitted to the Commission in a report within 12 months following completion of the inspection. This report shall include:

1. Number and extent of tubes and sleeves inspected,
2. Location and percent of wall-thickness penetration for each indication of an imperfection, and
3. Identification of tubes plugged or repaired."

INSPECTION REPORT:

Callaway Plant shut down from October 23, 2002 to November 21, 2002 for its twelfth refueling outage. During that time an inservice inspection was performed on all four steam generators. The planned inspection scope was as follows:

0 100% full length (bobbin coil) examination of Steam Generators A and D 0 100% hot leg top of tubesheet (TTS) MRPC (+Point) examination of all four steam generators 0 100% Rows 1 and 2 U-bend MRPC (+Point) examination of Steam Generator C

  • Examine, with RPC (+Point), 33 tubes with previously installed Laser Welded Sleeves (LWS) in Steam Generator C
  • Examine, with RPC (+Point) 20% of all dents/dings greater than 2 volts identified with bobbin coil examination 0 Special interest RPC (+Point) of bobbin coil indications as required 9 Ultrasonic testing of 31 previously installed Electrosleeves in Steam Generator A

ULNRC-04823 March 12, 2003 Page 6 Table 1 lists the examinations performed.

Eddy Current Testing Task Summary (Tubes Inspected)

S/G A S/G B S/G C S/G D ECT Task H/L C/IL H/L C/L H/L C/L H/L C/L Total 100% Bobbin 5068 5164 10232 F/L MRPC TTS 5431 5568 5449 5528 21976 100%

MRPC U- 238 238 bend 100%

MRPC Dents 168 197 365 Dings >2 volts MRPC S.I. 83 49 132 MRPC LWS 33 33 Sleeves Low Row 363 364 727 Bobbin UT 31 31 Electrosleeve ____ 31 MRPC 31 31 Electrosleeve Table 1 Appropriate examination techniques, qualified to EPRI PWR Examination Guidelines, Appendix H were used for each inspection. Each technique was evaluated for applicability to Callaway's tubing and degradation mechanisms prior to actual use in the field. Table 2 lists those examination techniques approved for use in Refuel 12.

ULNRC-04823 March 12, 2003 Page 7 Qualified ECT Techni ues for Callaway Refuel 12 Damage Mechanism EPRI ETSS Coil Type Technique for Detection or Sizing?

Hot Leg Transition PWSCC axial 20511 +Point Both circumferential 20510 +Point Hot Leg Top of Tubesheet OD IGA/SCC axial and circumferential 96401 0.115" Pan Detection axial and circumferential 20409 +Point Both AVB wear 96004 Bobbin Both Tube Support Plate IGA/SCC OD flaws(without dents) 96007 Bobbin Detection OD flaws(without dents) 96008 Bobbin Both OD flaws(circ and axial) 96401 0.115" Pan Detection OD flaws(circ and axial at dents) 20409 +Point Both ID flaws(circ at dents) 20510 +Point Both ID flaws(axial at dents) 20511 +Point Both Freespan IGAISCC 96008 Bobbin Detection OD flaws (circ and axial) 20409 +Point Both U-bend PWSCC (circ and axial) 96511 +Point Detection Pitting 96005 Bobbin Both Thinning 96001 Bobbin Both Table 2 The bobbin inspection was performed from the cold leg (except the hot leg sections of the low row tubes) using dual probe pushers. Only six (6) tubes required plugging due to AVB wear. Five (5) tubes were repaired for tube support plate wear at various locations in the steam generators.

All Row 1 and 2 U-bends were inspected in steam generator C using a Plus Point RPC U bend probe. No degraded tubes were identified during this inspection.

Thirty-three (33) of the laser welded sleeves installed in Refuel 8 were examined using a Plus Point RPC probe. This completed the second 100% in-service inspection of the 77 sleeves installed in Refuel 8. No indications of defects were found.

20% of all "dents" or "dings" found by the bobbin coil, with amplitude greater than 2 volts, were further examined using a Plus Point coil to determine whether any IGA/SCC may have initiated due to the tube deformation. No indications were found.

The hot leg top-of-tubesheet examination was performed using dual guide tubes and Plus Point RPC probes. One hundred fourteen (114) tubes were repaired due to stress corrosion cracking or intergranular attack. All tubes were repaired using Inconel 690

ULNRC-04823 March 12, 2003 Page 8 rolled plugs. Sixty-four (64) tubes with circumferential indications were stabilized with wire rope stabilizers.

Table 3 summarizes the repairable indications found in Refuel 12. Table 4 identifies the total tubes repaired in the history of operation. Table 5 lists the tube repaired in Refuel 12.

Callaway Plant Refuel 12 (October 2002)

Characterization of Repairable Indications Indication Steam Steam Steam Steam Generator Generator Generator Generator A B C D Axial ID 39 1 3 2 Circumferential ID 43 4 19 3 Axial OD 0 0 1 0 Circumferential OD 0 0 0 0 Volumetric 8 0 0 1 Indications Total tubes with TTS indications Tubes Plugged due 0 0 3 to AVB wear Tubes Plugged due 4 0 0 1 to TSP wear Tubes Plugged due 0 0 0 0 to loose parts II_ I Total tubes repaired 91 5 19 9 in Refuel 12 Table 3 Table 4 summarizes the total tubes repaired in each steam generator up to the beginning of Cycle 13.

ULNRC-04823 March 12, 2003 Page 9 Effective Tubes Plu :ged (Start of Cycle 13)

Steam Tubes Westinghouse Framatome Effective  % plugged Generator Plugged LWS Electrosleeve tubes (total) plugged A 211 44 31 212.7 3.78 B 63 63 1.12 C 137 33 26 138.3 2.46 D 107 107 1.90 Total 518 77 57 521 2.31 Table 4 Identification of Tubes Repaired in Refuel 12 S/G A S/G B S/G C S/G D ROW COL. ROW COL. ROW COL. ROW COL.

1 34 12 52 11 68 5 70 11 68 14 104 13 56 12 73 11 98 29 90 13 68 29 82 12 64 33 77 13 69 36 43 12 65 42 65 14 72 42 57 12 99 15 28 42 89 13 66 17 77 47 34 13 75 18 77 50 95 14 83 19 63 52 73 15 48 21 65 16 72 21 101 17 43 22 101 17 51 23 84 17 101 27 57 18 42 29 68 18 44 30 93 18 49 36 46 18 50 37 75 19 42 47 39 19 68 19 69 20 39 20 50 20 82 21 45 21 59 21 64 22 58

ULNRC-04823 March 12, 2003 Page 10 S/G A S/G B S/G C S/G D 22 72 23 43 23 78 23 84 23 97 24 80 24 88 24 103 25 62 25 71 25 88 25 91 25 99 26 53 26 77 26 109 27 60 27 68 27 83 27 100 30 64 31 76 31 101 32 65 32 82 33 74 33 108 34 73 34 80 34 89 34 98 37 83 38 88 39 37 39 41 39 61 39 83 39 88 39 90 39 92 41 54 41 82 41 95

ULNRC-04823 March 12,2003 Page 11 S/G A S/G B S/G C S/G D 42 62 43 36 44 35 44 36 44 59 44 62 44 75 44 81 46 48 46 50 46 61 46 73 47 49 47 50 47 57 48 61 48 70 49 48 49 62 59 67 Table 4

ULNRC-04823 March 12, 2003 Page 12 Callaway performed Ultrasonic Testing of the installed Electrosleeves in steam generator A. Table 5 summarizes the inspection findings for the inspected sleeves.

Steam Generator A Electrosleeve Ultrasonic Testing Results Tube Row Column Refuel 10 Min. Refuel 12 Min. Refuel 12 Avg.

Number Thickness (in) Thickness (in) Thickness (in) 1 17 54 0.029 0.030 0.033 2 18 45 0.031 0.030 0.033 3 39 87 0.032 0.031 0.033 4 42 83 0.031 0.030 0.034 5 39 81 0.027 0.026 0.033 6 35 80 0.029 0.028 0.034 7 30 81 0.031 0.030 0.033 8 49 75 0.031 0.030 0.034 9 39 85 0.031 0.030 0.033 10 31 94 0.030 0.029 0.033 11 24 52 0.028 0.028 0.035 12 26 51 0.031 0.030 0.033 13 17 32 0.027 0.026 0.033 14 22 46 0.030 0.029 0.034 15 47 61 0.031 0.030 0.033 16 44 33 0.028 0.027 0.034 17 44 34 0.027 0.027 0.034 18 42 65 0.030 0.030 0.034 19 39 52 0.028 0.028 0.035 20 19 81 0.031 0.031 0.034 21 12 107 0.031 0.031 0.034 22 15 93 0.032 0.031 0.034 23 17 88 0.031 0.030 0.033 24 11 95 0.032 0.032 0.033 25 33 71 0.031 0.030 0.034 26 38 85 0.027 0.026 0.034 27 17 81 0.033 0.032 0.034 28 20 88 0.029 0.028 0.035 29 25 86 0.025 0.024 0.034 30 33 64 0.033 0.033 0.033 31 41 56 0.031 0.031 0.034 Table 5

ULNRC-04823 March 12, 2003 Page 13 NEI 97-06 Revision 1, Steam Generator Program Guidelines, Section 3.1.7 requires that the Utility Condition Monitoring Report be submitted within 120 days after the RCS reenters Hot Shutdown Conditions if the results of the steam generator inspection indicate greater than 1% of the inspected tubes in any steam generator exceed the repair criteria.

Steam generator A exceed this requirement. Therefore, the Condition Monitoring Report is being submitted as part of the 12 month report. It is included as Attachment 1 to this report.

The results of in-situ testing performed in Refuel 12 are also required to be submitted with the Condition Monitoring Report. These tables are included in Attachment 2. on the following pages list steam generator tube imperfections found during the Refuel 12 eddy current inspection. The imperfections listed in these tables are those detected by eddy current testing. The key below provides a description of the abbreviations used in these tables. key AV1,2,3,4,5,6 - Anti-Vibration Bars 02H, 04C, 07H, etc - Tube Support Plate Numbers/Cold Leg (C), Hot Leg (H)

TSH - Tubesheet Hot ADS - Absolute Drift Signal DDS - Distorted Dent Signal DFS -Differential Free Span Signal DNF - Degradation Not Found DNG -- Ding DNT - Dent DSI - Distorted Support Indication DSS - Distorted Support Signal with Indication DTS - Distorted Tubesheet Signal GEO - Geometry Signal INF - Indication Not Found INR - Indication Not Reportable MAI - Multiple Axial Indication MBM - Manufacturer's Burnish Mark MCI - Multiple Circumferential Indication MVI - Multiple Volumetric Indication NQS - Non-quantifiable Signal NQI - Non-quantifiable Indication PID - Positive Identification PLP - Possible Loose Part SAI - Single Axial Indication SCI - Single Circumferential Indication SVI - Single Volumetric Indication TWD - Through Wall Degradation

ULNRC-04823 March 12, 2003 Page 14 Attachment 1 Callaway Condition Monitoring Report Callaway Refuel 12 Outage

20440-9 (2/2002)

A ENGINEERING INFORMATION RECORD FRAMATOME ANP Document Identifier 51 - 5023426 -01 Title STEAM GENERATOR CONDITION MONITORING REPORT FOR CALLAWAY RF 12 PREPARED BY: REVIEWED BY:

Name J. A. BEGLEY Name VF NEWMAN Signature ' Date 1114/02-3 #z, Signature Date///

Technical Manager Statement: Initials Reviewer Is Independent.

Remarks:

This document evaluates the as-found condition of the Callaway steam generators in Refuel Outage 12. The steam generators were found to be operating within the condition monitoring limits at the end of the cycle.

'age I of 27

51-5023426-01 TABLE OF CONTENTS Page

1. Introduction 3
2. Condition Monitoring Results 4
3. Summary and Conclusions 25
4. References 26 Page 2 of 27

51-5023426-01 Section 1 INTRODUCTION This report describes condition monitoring evaluations of steam generator tubing at Callaway. The observed severity of degradation at the end of cycle, outage RF 12, was evaluated to determine if structural and leakage integrity requirements were maintained. The scope of this evaluation included all the forms of tubing degradation observed at RF 12, specifically:

"* Wear at AVB and Tube Support Locations

"* Expansion Transition Axial PWSCC

"* Expansion Transition Axial ODSCC

"* Expansion Circumferential PWSCC

"* Circumferential PWSCC Within the Tubesheet

"* Volumetric Degradation The observed degradation at the RF 12 outage was evaluated in a manner consistent with NEI 97-061, and EPRI guidelines 2'3. The observed degradation did not present serious challenges to the deterministic (3AP or 1.43 MSLB) structural margin requirement at the end of the last cycle of operation.

In terms of an overview of repair scenarios:

"* wear indications at AVBs or tube supports are left in service if maximum depths are sized less than 40% of the wall thickness

"* all other indications are repaired or plugged on detection.

The next section provides the results of condition monitoring evaluations for outage RF 12.

Page 3 of 27

51-5023426-01 Section 2 CONDITION MONITORING Condition monitoring evaluations relative to structural and leakage integrity are presented in this section. The following paragraphs present condition monitoring structural limits for axial cracks, circumferential cracks, volumetric degradation and wear scars for Callaway steam generator tubing. A discussion of leakage integrity then follows. Table 2.1 summarizes the number of indications of tubing degradation discovered at RF 12 and Table 2.2 summarizes structural and leakage integrity evaluation results.

In terms of an overview of steam generator tubing degradation at Callaway 4, axial and circumferential PWSCC has been observed at top of the tubesheet hydraulic expansion transitions for the past four cycles of operation. This is the primary degradation mode.

Occasional instances of ODSCC, both axial and circumferential, have been observed in this same region. Wear at AVB's is present. Approximately 250 wear scars are present in each of the four steam generators. Wear growth rates are low leading to plugging of about two tubes per generator per inspection for each steam generator for depths exceeding the 40% TW limit. Small volumetric indications are observed on a sporadic basis. These indications are plugged on detection as are all other degradation modes with the exception of wear at AVB's.

The inspection scope at RF12 was as follows:

100% Plus Point TTS Inspection "+2/-X" in all SG Hot Legs, Distance X Depends on Location in the Tube Bundle, The Required Distance X to Demonstrate Leakage and Structural Integrity is Defined in WCAP-15932-P 5 in Terms of Four Zones:

Zone A, X = 3.16", outer peripheral ring, 1892 tubes Zone B, X = 5.61", second inner ring, 2352 tubes Page 4 of 27

51-5023426-01 Zone C, X = 7.45", third inner ring, 1192 tubes Zone D, X = 7.99", innermost arc, 190 tubes 0 100% Full Length Bobbin Exams in SGs A and D

  • 100% Rows I and 2 U-bend RPC in SG C
  • All Electro-sleeves (31) in SG A H/L both ECT & UT
  • All Westinghouse Laser Welded Sleeves (33) in SG C
  • 20% Plus Point Inspection of Dents and Dings >2V in SGs A and D
  • Special Interest Plus Point Exams as Required No degradation was detected in Electro-sleeves and laser welded sleeves. The first ten rows of tubes at Callaway are thermally treated Alloy 600 tubing. Thermal treatment was performed after fabrication of the U-bends. Since this improves both the residual stress state and material resistance to stress corrosion, no degradation was expected in the Row 1 and Row 2 U-bends and none was observed. No degradation was observed in the sampling Plus Point inspection of dents and dings.

Detected instances of degradation, as listed in Table 2.1, follow the expectations from past experience at Callaway. The next section discusses a quantitative evaluation of degradation trends. Due to regulatory concerns with leakage integrity from possible PWSCC deep within the tubesheet, the inspection depth below the top of the tubesheet with the Plus Point probe was increased from past practice. Table 2.3 lists the indications found solely due to increased inspection depth within the tubesheet. These indications were located in Zones B and C. Leakage integrity was demonstrated via analysis and in situ testing as described in later paragraphs.

Structural limits for axial cracks, circumferential cracks, volumetric degradation and wear scars for steam generator tubing at Callaway are described in the degradation assessment 4 for RF 12. These structural limits provide the framework needed for condition monitoring evaluations and operational assessments.

Page 5 of 27

51-5023426-01 The combinations of wear scar lengths and depths leading to a 3AP burst pressure of 3825 psi are shown in Figure 2.1 for Callaway steam generator tubing. The upper curve, termed the structural limit curve using the nomenclature of the EPRI Steam Generator Degradation Specific Flaw Handbooks, is based on a best fit burst pressure equation and average, at temperature, material properties. The next lower curve is the EOC Allowable Limit curve which is the locus of actual physical degradation lengths and structural average depths leading to a burst pressure of 3825 psi at a probability of 0.95 at 50% confidence, considering uncertainties in both material properties and the burst pressure relationship. The lowest curve in Figure 2.1 is the Condition Monitoring Limit Curve. This curve includes NDE sizing uncertainties as well as uncertainties in material properties and in the burst pressure equation. The Condition Monitoring Limit curve shows the locus of NDE inferred degradation lengths and depths leading to a burst pressure of 3825 psi at 0.95 probability at 50% confidence. Indications with NDE inferred lengths and depths at or below the Condition Monitoring Limit curve meet the required deterministic structural performance criteria for minimum degraded tube burst pressure.

In applying NDE measured degradation dimensions to infer structural integrity, systematic errors, measurement uncertainties, and shape effects must be considered.

Historically, most NDE depth measurements refer to maximum depth. Figure 2.2 shows a plot of maximum wear scar depth from destructive examinations results versus NDE measured depths 7 using the eddy current technique applicable to Callaway. The best fit straight line shows an intercept of 2.92% TW and a slope of 0.96, resulting in a small systematic error. The scatter in actual depth about the best-fit line is normally distributed with a standard deviation of 3.52% TW. This value is termed the standard error of estimate in conventional straight-line linear regression evaluations. From Figure 2.2 it is seen that, at a measured NDE depth of 40% TW, the best estimate of actual maximum depth is 41.3% TW. Actual maximum depths will scatter about this value with a standard deviation of 3.52% TW. A summary of NDE sizing uncertainties applicable to Callaway is listed in Table 2.4. The term modified in reference to ETSS 21409.1 Page 6 of 27

51-5023426-01 indicates that sizing data for several laboratory produced flaws were deleted and sizing uncertainties were recalculated using only laboratory data which is representative of actual service degradation. Certain procedures for doped steam laboratory stress corrosion testing lead to extremely low signal amplitudes well beyond the bounds of pulled tube experience.

Structural integrity typically depends on average degradation depth, not maximum depth. Maximum degradation depths and total degradation lengths are conservative bounds to structurally significant depths and lengths. If more accuracy is required, crack depth versus length profiles need to be considered. The EPRI Flaw Handbook 6 provides a means of evaluating average depth from depth versus length profiles for predominantly axial degradation, whether crack-like or volumetric. Structurally significant. lengths are also defined. The depths and lengths referred to on Figure 2.1 are the structurally significant values. Plotting of maximum depths and lengths on this and later structural limit plots is conservative. Ifdepth/length profiles are not available, pulled tube examination results show that stress corrosion cracks have a roughly semi elliptical shape leading to an average depth equal to the maximum depth divided by a factor of 1.28.

Condition monitoring structural limit plots are shown in Figures 2.3 and 2.4 for AVB wear scars at Callaway. If NDE data is to be compared to the Condition Monitoring Limit curve, a bounding length of 0.3 inches is used, with NDE depth converted to actual depth using Figure 2.2. Given the short length of AVB wear scars, the average depth is assumed to be equal to the maximum depth. The CM curve already contains the 3.52%

TW sizing uncertainty standard deviation. Figures 2.3 and 2.4 show plotted points representing AVB wear scars observed at RF 12. These points fall well below the CM Limit curve. Required structural integrity is demonstrated. Since through wall tearing and burst will not occur at 3AP, leakage integrity at an SLB differential pressure of 2560 psi is also demonstrated.

Page 7 of 27

51-5023426-01 Figure 2.6 illustrates that volumetric IGA indications in steam generators A and D meet 3AP condition monitoring requirements. Of the total of 9 volumetric indications 5 were located at tube support plates and 4 were located near the top of the tubesheet. All are low level indications in terms of extent, depth and signal amplitude. These indications meet both structural and leakage integrity requirements by a wide margin.

Axial PWSCC indications had very short lengths. The maximum indication length was 0.25 inches. Considering material property, burst equation and NDE sizing uncertainties an axial PWSCC crack can be 0.275 inches long and 100% TW and meet 3AP condition monitoring structural integrity requirements. All axial PWSCC indications thus meet condition monitoring structural integrity requirements. Based on data in the EPRI Steam Generator In Situ Pressure Test Guidelines 8 , axial PWSCC indications must exhibit a Plus Point voltage of 2.5 volts before leakage integrity at postulated SLB conditions becomes an issue or sizing is required. The maximum Plus Point voltage for all observed axial PWSCC indications was 1.7 volts. In situ testing of this indication was performed to verify leakage integrity. No leakage occurred at either SLB or 3AP test pressures.

Only one axial indication was determined to be an OD indication with a length of 0.21 inches and an average depth of 27.6 %TW. Using the EPRI Flaw Handbook6 approach the depth/length profile of this indication led to a structural length of 0.19 inches and a structural depth of 33.8 % TW. Figure 2.7 shows that this indication easily meets the condition monitoring 3AP structural integrity requirement. Figure 2.8 shows that SLB leakage integrity is easily demonstrated. Since the Plus Point voltage of this indication was only 0.25 volts, it was substantially under the 0.4 volts threshold for structural integrity and the 0.75 volts threshold for leakage integrity without sizing as established in the Callaway RF12 Degradation Assessment 4 . However, it must be noted that sizing results of indications below the structural and leakage integrity thresholds can be misleading in terms of being grossly overconservative. NDE sizing results above voltage thresholds are the more reliable indicators of degradation severity.

Page 8 of 27

51-5023426-01 The circumferential PWSCC indications found in the vicinity of the top of tubesheet expansion transitions were of very limited circumferential extent. The maximum PDA value was 14 compared to the condition monitoring limit of 62 PDA. Hence, the degradation found at elevations typical of past practice met condition monitoring structural integrity requirements by a large margin. See Figure 2.9. Plus Point voltage levels were all below 1.0 volts satisfying SLB leakage integrity requirements on a voltage threshold basis as described in the Callaway RF12 Degradation Assessment 4.

The only circumferential degradation posing any threat to leakage integrity was located at least 4 inches below the top of the tubesheet. At this depth level, structural integrity is satisfied for degradation of any dimension since tube burst or pull out cannot occur.

The maximum SLB leak rate per tube for any degradation below this level is on the order of 1E-4 gpm based on WCAP-1 5932-P 5 and laboratory tests on rolled transitions With imposed tubesheet hole dilations 9. In situ testing of 14 circumferential indications expected to be 100% TW verified leakage integrity at pressures in excess of 3AP levels.

One of these indications had a PDA value greater.than 96 and a Plus Point voltage greater than 10 volts and exhibited no signs of leakage at either SLB or 3AP test pressures.

Circumferential cracking beyond previous inspection depths in the tubesheet is assumed to be caused by hydraulic expansion of tubes over machining irregularities in the drilled tubesheet holes. The number of possible degradation sites will thus scale with the length of the tubesheet hole. In the worst case steam generator, 14 circumferential PWSCC indications were found at depths previously uninspected with the Plus Point probe. The now remaining uninspected depth is about three times longer than the region found to contain the 14 indications. Thus, an upper bound estimate of undetected degradation within the tubesheet is about 42 indications of a severity matching the 14 detected indications. The upper bound analytical condition monitoring SLB leak rate is then 0.0056 gpm. In situ testing supports the analytical result that only very low leak rate levels are possible. The reported leak rate at normal operating conditions prior to outage RF12 was 0.3 gpd, which converts to 0.0002 gpm. This level challenges measurement capabilities. If it is true and is applied to circumferential Page 9 of 27

51-5023426-01 cracking deep in the tubesheet, it would convert to 0.0012 gpm at SLB conditions per the results of WCAP-15392. Hence the analytical upper bound SLB condition monitoring leak rate is conservative with respect to an adjusted NOP leakage prior to the RF 12 outage.

In summary, condition monitoring structural and leakage integrity requirements are shown to have been met via analysis and verified by in situ testing. Condition monitoring results are summarized in Table 2.2. In situ testing results are summarized in Table 2.5.

Page 10 of 27

51-5023426-01 Table 2.1 Summary of Indications at the RF 12 Inspection Degradation SG A SG B SG C SG D Mechanism 3 Plugged Tubes 3 Plugged Tubes AVB Wear (254 Total NA NA (326 Total Indications) Indications)

Expansion Transition Axial 39 1 3 2 PWSCC Expansion Transition Axial 0 0 1 0 ODSCC Expansion Transition 43 4 19 3 Circumferential PWSCC Volumetric Degradation 8 0 0 1 Page 11 of 27

51-5023426-01 Table 2.2 Summary of Condition Monitoring Results Leakage Integrity Degradation Mechanism Structural Integrity Limiting S/G Leak Rate

(_qpmORT)

Axial PWSCC at Expansion Passed via Analysis 0 Transitions Confirmed by In Situ Testing Axial ODSCC at Expansion Passed via Analysis 0 Transitions Circumferential PWSCC At Passed via Analysis 0.0056 gpm maximum and Below Expansion Confirmed by In Situ Testing analytical result Transitions no leakage observed at 3AP in situ pressure levels Volumetric Degradation Passed via Analysis 0 Wear Passed via Analysis 0 Page 12 of 27

51-5023426-01 Table 2.3 Location of Circumferential Indications Steam Generator Indications Above Indications Below Total Number of TSH -4.0 TSH -4.0 Indications A 36 7 43 B 3 4 C 5 14 19 D 1 2 3 Page 13 of 27

51-5023426-01 Table 2.4 NDE Sizing Relationships and Uncertainties Applicable to Callaway Mechanism/Location Technique Sizing Equations NDE (ETSS#) Uncertainty Depth y= 0 68x+7.07 1097 0

Hot Leg TTS 20511.1 Length- y= 97x+0 04 011 PWSCC Axial (Plus Point) Average Depth 7.27 Y=0.37x+14 56 Depth- 1676 Hot Leg Circumferential 205101 y=O 67x+19 66 PWSCC (Plus Point) Length 016 y=O 91x+0.22 PDA: 877 y=0 83x+3 41 Maximum Depth 21.7 Hot Leg TIS Axial 214091 y=l Ox ODSCC (Plus Point) (modified) Length 026 y=l.Ox PDA 169 y-1 Ox AVB Wear 960043 Maximum Depth 352 (Bobbin) y=0.96x+2.92 Volumetric OD Degradation 219981 Maximum Depth: 628 (Plus Point) y=1.02x+5 81 Page 14 of 27

51-5023426-01 Table 2.5 Summary of In Situ Test Results ROW COL VOLTS DEG CHN IND LOCATION DISTANCE EXT EXT CAL # LEG SG ID PROBE OUTAGE SCOPE 23 97 1.54 37 P2 SCI TSH -84 TSH TS6 18 HOT 1A 560PP RF12 HL TTS RPC 24 88 2.1 34 P2 SCI TSH -56 TSH TS6 2 HOT 1A 560PP RF12 HL TTS RPC 25 71 1 35 37 P2 MCI SBH -1.72 TS8 SBH 69 HOT 1A 4802C RF12 Below Sleeve RPC 34 80 166 34 P2 SCI TSH -4.76 TSH TS6 25 HOT 1A 560PP RF12 HL TTS RPC 46 73 1.7 33 4 SAI TSH 003 TSH TS6 26 HOT 1A 560PP RF12 HL TTS RPC 29 82 164 28 P2 SCI TSH -723 TSH TS6 6 HOT 1D 560PP RF12 HL TTS RPC 42 57 1029 43 P2 MCI TSH -5.63 TSH TS6 28 HOT 1D 560PP RF12 HL TTS RPC 13 68 4.18 37 P2 SCI TSH -536 TSH TS8 7 HOT IC 560PP RF12 HL TTS RPC 18 77 645 46 P2 MCI TSH -6.51 TSH TS8 6 HOT 1C 560PP RF12 HL TTS RPC 18 77 1137 49 P2 SCI TSH -709 TSH TS8 6 HOT 1C 560PP RF12 HL TTS RPC 18 77 1297 22 P2 SCI TSH -986 TSH TS8 6 HOT IC 560PP RF12 HL TTS RPC 21 65 4 38 P2 SCI TSH -10 58 TSH TS8 7 HOT 1C 560PP RF12 HL TTS RPC 21 101 322 33 P2 MCI TSH -4.25 TSH TS6 44 HOT IC 560PP RF12 HL TTS RPC 22 101 323 43 P2 MCI TSH -704 TSH TS6 45 HOT IC 560PP RF12 HL TTS RPC 29 69 809 44 P2 SCI TSH -568 TSH TS6 7 HOT 1C 560PP RF12 HL TTS RPC 36 46 1.58 37 P2 MCI TSH -5.1 TSH TS6 27 HOT 1C 560PP RF12 HL TTS RPC No Leakage Occurred at SLB or 3AP Test Pressures. Test pressures were elevated above SLB and 3AP to account for temperature differences and gage uncertainties.

Page 15 of 27

51-5023426-01 This Page IntentionallyBlank Page 16 of 27

51-5023426-01 AVB Wear Structural Limit Curves 100.00

-Structural Limit A EOC Allowable Limit 90.00 S-"-Condition Monitoring Limit 80.00 70.00 60.00

.2 50.00 CD "U

a 40.00 0

30.00 20.00 10.00 0.00

0. 000 0.500 1.000 1.500 2.000 2.500 3.000 Degradation Length, inches Figure 2.1 Structural Limit Curves Applicable to Wear Degradation Page 17 of 27

51-5023426-01 Linear Regression Straight Line Fit slope = 0.963 intercept = 2.919 100 90 80 70 60 0

50 40 30 20 10 0

0 20 40 60 80 100 X Value Figure 2.2 Actual Depth Versus NDE Measured Depth, Wear Scar Geometry Page 18 of 27

51-5023426-01 AVB Wear Structural Limit Curves 100.00

-- Structural Limit

-EOC Allowable Limit 90.00

- Condition Monitonng Limit A AVB Wear SG A 80.00 70.00 60.00 A

4 50.00

. a, C'

40.00 30.00 A

20.00 10.00 0.00 0.000 0.500 1.000 1.500 2.000 2.500 3.000 Degradation Length, inches Figure 2.3 Structural Limit Curve for Wear Scars at Callaway, Degradation Dimensions Derived from S/G A RF12 Inspection Data Page 19 of 27

51-5023426-01 AVB Wear Structural Limit Curves 100.00 90.00 80.00 70.00 60.00 CL 0

50.00 40.00 30.00 20.00 10.00 0.00 4-0.000 0.500 1.000 1.500 2.000 2.500 3.000 Degradation Length, inches Figure 2.4 Structural Limit Curve for Wear Scars at Callaway, Degradation Dimensions Derived from S/G D RF12 Inspection Data Page 20 of 27

51-5023426-01 VolumetricDegradation

< 135 Degrees Circumferential Extent at 3825 psi 100.00 i I

- Structural Umit A EOC Allowable Limit 90.00

-Condition Monitonng Limit E Voturnetic Indications inS3s A and 0 80.00 70.00 60.00 C 50.00 0

.2 V~

4000 30.00 U 20.00 10.00 0.00 ,--, , , , . . .. . . . .

0. 000 0.500 1.000 1.500 2.000 2.500 3.000 Degradation Length, inches Figure 2.5 Condition Monitoring Plot for Volumetric Indications Page 21 of 27

51-5023426-01 Axial Partial Throughwall OD Crack at 3825 psi 100.00 S-4--Structural Umit A---- EOC Allowable Limit

"---- Condition Monitonng Limit 90.00 --- ---.-- Throughwall Cutoff SL

.......... Throughwall Cutoff EOC Allowable


Throughwall Cutoff CM

"-R13 C56, SG C 80.00

"L~~ A...

70.00 60.00 CL 50.00 40.00 30.00 20.00 10.00 0.00 0.000 0.500 1.000 1.500 2.000 2.500 3 000 Structural Length, inches Figure 2.6 Condition Monitoring Plot for Axial ODSCC Page 22 of 27

51-5023426-01 Axial Crack Leak/No Leak Curve at 2560 psi 100 No NDE Uncertainty ID

90. 20511.1 80 OD 21409.1 I 70 modified 60 a.E x

E 50 R13, C56 SG D (3

E 40 E

x 30 20 10 0 0 0 0.2 0.4 0.6 0.8 1 Crack Length, inches Figure 2.8 SLB Leak/No Leak Limit Curves, ODSCC Indication Shown Page 23 of 27

51-5023426-01 Circumferential PWSCC 12000 10000 1- 1- f

- Structural Limit

-i--EOC.Alowable ibmit

- Condition Monitoring Umit 8000 Target Pressure = 3825 psi .-.---.

-- AJIGenerators Above TSH -4 0 CL Uc 6000 16 4000 2000 0

0 20 40 60 80 100 Percent Degraded Area, PDA Figure 2.9 Condition Monitoring Plot For Circumferential PWSCC Page 24 of 27

51-5023426-01 Section 3

SUMMARY

AND CONCLUSIONS Condition monitoring evaluations of steam generator tubing at Callaway were performed using inspection results from outage RF12. The observed severity of degradation at the end of cycle was evaluated to determine ifstructural and leakage integrity requirements were maintained. The scope of this evaluation included all forms of tubing degradation:

"* Wear at AVB and tube Support Location

"* Expansion Transition Axial PWSCC

"* Expansion Transition Axial ODSCC

"* Expansion Circumferential PWSCC

"* Circumferential PWSCC Within the Tubesheet

"* Volumetric Degradation Condition monitoring via analysis showed that deterministic structural margins and leakage integrity were maintained during the last cycle of operation. In situ testing verified analytical expectations.

Page 25 of 27

51-5023426-01 Section 4 REFERENCES

1. "Steam Generator Program Guidelines", Nuclear Energy Institute, NEI 97-06, December 1997.
2. "Steam Generator In Situ Pressure Test Guidelines", EPRI Report TR-107620 Ri, June, 1999.
3. "Steam Generator Integrity Assessment Guidelines: Revision 1", EPRI Report TR-107621-RI, March, 2000.
4. "Callaway Degradation Assessment, Framatome-ANP Report 51-5019993-00, October, 2002.
5. "Improved Justification of Partial-Length RPC Inspection of Tube Joints of Model F Steam Generators of Ameren UE Callaway Plant," Westinghouse Electric Company, Pittsburgh, Pa., USA., WCAP-15932-T, September, 2002.
6. "Steam Generator Degradation Specific Management Flaw Handbook", EPRI Report 1001191, March, 2001.
7. "Performance Demonstration Data Base, Appendix A, Technique Specification Sheets", Electric Power Research Institute, Palo Alto, CA, June, 2002.
8. "Technical Basis for Voltage as Screening Parameter for Selection of Indications for In Situ Testing", Appendix B of Steam Generator In Situ Pressure Test Guidelines, to be published.
9. OTSG Mechanical Rolled Plug Leak Test Results, FTI Document 51-5007035 00, March, 2000.
10. Begley, J. A., Begley, Begley, T. F., Peck, M. G., and Begley, C. J., "Condition Monitoring and Operational Assessment of Steam Generator Tubing at Sequoyah, Unit 1, E-Mech Technology Inc., EMECH-0729-SR-1, March, 2000.

11."Failure Behavior of Internally Pressurized Flawed and Unflawed Steam Generator Tubing at High Temperatures - Experiments and Comparison with Model Predictions", NUREG/CR-6575, ANL-97/17, March, 1998.

12.Pitterle, T. A., Srinivas, V., Keating, R. F., and Begley, J. A., "Indian Point-2 Supplement to U-Bend PWSCC and Sludge Pile ODSCC CMOA's for Sensitivity Page 26 of 27

51-5023426-01 to Cycle Length, POD and Burst Correlations, Westinghouse Electric Company, SG-00-06-010, June, 2000.

13.Begley, J. A. and Begley, C. J., "A Combined Probabilistic-Determinsitic Operational Assessment of Freespan Axial Degradation at Oconee Unit 2 for Cycle 17, E-Mech Technology Inc., Report EMECH-0710-1, Rev. 0, July, 1998.

14. "Depth Based Structural Analysis Methods for Steam Generator Circumferential Indications," Electric Power Research Institute, TR-107197, Palo Alto, CA, November, 1997.

15."Failure Behavior of Internally Pressurized Flawed and Unflawed Steam Generator Tubing at High Temperatures - Experiments and Comparison with Model Predictions", NUREG/CR-6575, ANL-97/17, March, 1998.

16. Steam Generator Tubing Burst Testing and Leak Rate Testing Guidelines, EPRI Draft Report, February, 2002.

Page 27 of 27

ULNRC-04823 March 12, 2003 Page 15 Attachment 2 Steam Generator In-Situ Pressure Testing Results Callaway Refuel 12 Outage

ULNRC-04823 Attachment 2 March 12, 2003 Page 1 The following indications were in-situ tested during Refuel 12 steam generator inspection activities:

Steam Generator A In-situ Testing Results Row Col Ind. Location Volts PDA Max % Circ axial test hold leak Ave TW Extent length pressures times rate pres.

degrees inch psi min gpm rate 23 97 SCI TSH -8.4" 1.54 9.1 42.4 1550 2 0 15 1 2900 2 0 24 3400 2 0 15 3900 2 0 14 4350 2 0 16 24 88 SCI TSH -5.6" 2.1 15.9 63.5 1550 2 0 15 2900 2 0 29 3400 2 0 17 3900 2 0 14 4350 2 0 14 25 71 MCI SBH -1.72 1.35 29.3 132.2 1550 2 0 12 2900 2 0 14 3400 2 0 14 3900 2 0 17 4350 2 0 14 34 80 SCI TSH -4.76 1.66 11.7 55.8 1550 2 0 8 2900 2 0 15 3400 2 0 15 3900 2 0 11 4350 2 0 10 46 73 SAI TSH +0.03 1.7 100 0.18 1550 2 0 14 2900 2 0 17 3400 2 0 13

_____13900 2 0 15 1 14350 2 0 11 Table 1

ULNRC-04823 Attachment 2 March 12,2003 Page 2 Steam Generator C In-situ Testing Results Row Col Ind. Location Volts PDA Max % Circ axial test hold leak Ave TW Extent length pressures times rate pres.

degrees inch psi min gpm rate 13 68 SCI TSH -5.36" 4.18 18.8 74.8 1550 2 0 22 2900 2 0 31 3400 2 0 24 3900 2 0 15 4350 2 0 24 18 77 SCI TSH-6.51" 6.45 37.5 155.6 1550 2 0 13 SCI TSH-7.09" 11.37 29.8 124.4 2900 2 0 19 SCI TSH -9.86 12.97 96.4 360 3400 2 0 18 3900 2 0 16 4350 2 0 14 21 65 SCI TSH -10.58 4.00 26.5 107.5 1550 2 0 27 2900 2 0 39 3400 2 0 24 3900 2 0 15 4350 2 0 11 21 101 MCI TSH -4.25 3.22 31 122.9 1550 2 0 13 2900 2 0 20 3400 2 0 16 3900 2 0 17 4350 2 0 15 22 101 MCI TSH -7.04 3.23 34.9 145.6 1550 2 0 12 2900 2 0 17 3400 2 0 13 3900 2 0 11 4350 2 0 9 29 69 SCI TSH -5.68 8.09 36.6 143.1 1550 2 0 22 2900 2 0 38 3400 2 0 28 3900 2 0 18 4350 2 0 18 36 46 MCI TSH-5.1 1.58 10.6 45.4 1550 2 0 35 2900 2 0 28 3400 2 0 24 3900 2 0 35 4350 2 0 10 Table 2

ULNRC-04823 Attachment 2 March 12,2003 Page 3 Steam Generator D In-situ Testing Results Row Col Ind. Location Volts PDA Max % Circ axial test hold leak Ave TW Extent length pressures times rate pres.

degrees inch psi min gpm rate 29 82 SCI TSH -7.23 1.64 7.8 36.9 1550 2 0 9 1 2900 2 0 12 3400 2 0 8 3900 2 0 8 4350 2 0 9 42 57 MCI TSH -5.63 10.29 55.3 223.6 1550 2 0 9 2900 2 0 11 3400 2 0 9 3900 2 0 12 4350 2 0 7 Table 3

ULNRC-04823 March 12, 2003 Page 16 Attachment 3 Listing of Steam Generator Tube Imperfections Callaway Refuel 12 Outage

ULNRC-04823 March 12, 2003 Page 17 Listing of Steam Generator Tube Imperfections Callaway Refuel 12 Outage Steam Generator A

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 1 7.18 178 DNG TSH 18.15 2 5.88 59 MBM TSC 13.78 11 1.9 126 DFS TSC 10.16 11 2.71 87 MBM TSC 1.17 11 1.21 18 GEO TSH 0.12 14 5.56 87 MBM 06H 34.16 19 2.56 89 MBM 06C 21.34 19 2.83 77 MBM 02H 36.92 20 2.37 74 MBM FBH 9.45 21 0.33 91 DFS TSC 15.2 22 5.99 88 MBM 04C 36.51 22 5.93 88 MBM 06H 39.41 23 2.96 89 MBM 05C 9.83 23 3.79 88 MBM 03H 15.14 29 2.09 82 MBM 04C 28.09 29 3.58 86 MBM 04C 24.75 29 3.83 81 MBM 02H 36.06 29 4.26 82 MBM TSH 16.54 33 2.85 86 MBM FBC 10.38 33 2.38 84 MBM FBC 7.74 33 1.08 102 DFS TSC 4.07 33 1.48 85 DFS TSC 2.5 33 3.95 182 DNG 02H 11.08 33 2.43 86 MBM 05H 25.56 33 2.71 69 MBM 04H 21.57 33 3.52 53 MBM 04H 8.94 34 0.44 125 DSI 01C -0.53 34 1.07 101 DFS TSC 2.89 34 0.12 0 TWD 6 01C -0.45 34 0.13 0 TWD 7 01C -0.47 34 0.33 38 PID 01C -0.39 34 0.27 135 MVI 01C -0.39 34 0.39 127 DSS 01H -0.52 35 1.93 111 DFS 05C 8.89 35 1.06 73 DFS TSC 0.94 35 0.58 143 DSS 01H -0.52 36 3.12 78 MBM 01C 23.83 36 3.69 82 MBM TSH 21.37 36 3.83 79 MBM TSH 8.8 41 0.61 96 DFS 05H 10.51 44 2.81 84 MBM 06H 23.96 52 2.78 75 MBM 06H 21.75 57 2.59 79 MBM 02H 36.56 67 5.04 82 MBM 06C 32.31 67 3.87 88 MBM 01H 15.6 67 2.72 85 MBM 03H 16.59 70 1.65 71 DFS 03H 1.76 70 1.2 80 DFS 03H 1.2 71 2.61 63 MBM 01C 11.3 72 0.58 73 DFS 03H 2.99 Page 1 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 1 75 0.81 75 DFS 02C 4.18 1 80 3.17 181 DNG 06H 36.08 1 82 3.58 89 MBM 01H 28.59 1 85 0.62 99 DFS TSH 6.1 1 89 3.78 175 DNT 07C -0.27 1 89 13.85 175 DNT 07C 0.45 1 89 6.64 178 DNT 07H -0.14 1 89 10.96 180 DNT 07H 0.44 1 93 2.73 73 MBM 06H 23.65 1 94 2.1 75 MBM 06C 4.32 1 96 2.67 85 MBM 03H 22.67 1 99 4.59 73 MBM 03C 36.21 1 99 3.53 73 MBM 05H 20.63 1 100 1.01 7 GEO TSH -0.47 1 100 1.43 17 GEO TSH -0.16 1 102 2.39 76 MBM 05H 2.62 1 102 2.23 80 MBM 05H 3.8 1 102 2.97 86 MBM 05H 7.36 1 102 3.12 86 MBM 06H 37.49 1 106 2.68 83 MBM 04C 2.61 1 106 1.14 20 GEO TSH 0 1 107 0.89 20 GEO TSH 0 1 112 3.8 79 MBM FBH 7.87 1 114 12.64 177 DNG TSC 18.23 1 114 2.08 47 MBM 04C 10.33 1 115 5.87 75 MBM 03C 15.23 1 115 4.46 88 MBM 04C 25.74 1 115 2.19 179 DNT 04H 0.54 1 115 2.85 82 MBM TSH 4.34 1 115 2.21 85 MBM 04H 7.55 1 115 2.01 88 MBM 04H 30.35 1 116 2.44 176 DNT 04H 0.59 1 116 2 174 DNT 04H -0.4 1 117 3.06 178 DNT 04H -0.39 1 117 3.99 179 DNT 04H 0.56 1 118 3.79 176 DNT 04H -0.38 1 118 5.72 177 DNT 04H 0.62 1 119 0.82 7 GEO TSH -0.2 1 119 4.77 177 DNT 04H -0.36 1 119 4.51 176 DNT 04H 0.63 1 119 3.84 79 MBM 02H 6.25 1 119 2.78 89 MBM FBH 8.06 1 120 3.11 177 DNT 04H -0.34 1 120 7.19 178 DNT 04H 0.67 1 121 3.99 176 DNT 04H -0.3 1 121 5.16 177 DNT 04H 0.67 1 122 3.44 62 MBM TSC 14.29 1 122 3.22 178 DNT 04H -0.3 1 122 6.28 177 DNT 04H 0.66 1 122 1.32 79 DFS TSH 14.23 1 122 0.92 83 DFS TSH 13.66 2 5 2.08 86 MBM FBC 9.94 Page 2 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 2 13 2.64 117 DFS 06H 9.26 2 15 2 86 MBM 04C 32.56 2 15 2.59 83 MBM 04C 30 2 19 3.76 79 MBM 01C 17.64 2 21 5.26 75 MBM 01C 29.32 2 22 2.26 65 MBM 06H 10.67 2 23 2.53 87 MBM 06H 27.83 2 25 1.02 109 DFS 05C 33.86 2 26 2.49 69 MBM 05C 20.21 2 26 2.6 73 MBM TSH 12.45 2 28 3.93 78 MBM 06H 27.64 2 28 4.25 78 MBM 06H 18.9 2 30 0.4 100 DFS 05C 8.07 2 39 0.92 99 DFS 01C 6.47 2 39 2.5 72 MBM 01H 28.25 2 41 2.24 175 DNG 02H 22.57 2 41 0.85 75 DFS 02H 1.23 2 41 1.26 46 DFS TSH 35.57 2 41 1.09 112 DFS 02H 36.44 2 47 3.99 73 MBM 06H 29.69 2 47 4.04 87 MBM 06H 18.5 2 48 2.42 90 MBM 01C 21.68 2 53 2.35 183 DNG TSH 32.21 2 58 3.47 174 DNT 07H 0.39 2 61 0.76 104 DFS 03H 14.68 2 63 2.98 59 MBM 02H 13.82 2 64 2.29 87 MBM 02H 38.43 2 65 2.48 81 MBM 04C 35.66 2 66 4.49 86 MBM 03C 9.46 2 68 2.58 75 MBM 05H 34.09 2 72 2.81 90 MBM TSH 17.82 2 78 3.73 70 MBM 01H 4.81 2 81 1.47 105 DFS 06H 13.96 2 82 2.34 79 MBM 05H 6.32 2 83 3.08 72 MBM 02H 16.66 2 88 0.5 84 DFS TSH 2.21 2 89 0.8 115 DFS 01C 10.39 2 92 3.2 75 MBM 05C 37.55 2 92 2.27 70 MBM 02H 22.15 2 94 2.51 74 MBM 01C 23.31 2 97 3.28 78 MBM 06H 4.45 2 97 5.06 90 MBM 06H 10.55 2 97 6.64 85 MBM 05H 31.91 2 101 2.9 170 DNT 07C 0.32 2 107 2.69 185 DNG 05H 38.73 2 107 2.28 82 MBM 01H 27.77 2 109 2.49 79 MBM 05H 28.73 2 114 2.32 84 MBM 02C 6.2 2 116 3.71 177 DNT 04H 0.6 2 117 4.04 177 DNT 04H -0.37 2 117 2.74 177 DNT 04H 0.56 2 118 4.86 177 DNT 04H -0.34 Page 3 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND  %/oTW LOCATION 2 118 4.36 176 DNT 04H 0.59 2 119 3.89 175 DNT 04H -0.36 2 119 4.75 175 DNT 04H 0.62 2 120 1.15 102 DFS 04C 36.42 2 120 3.36 178 DNT 04H -0.31 2 120 6.23 178 DNT 04H 0.63 2 121 4.32 177 DNT 04H -0.31 2 121 5.08 176 DNT 04H 0.66 2 122 0.95 90 DFS 04C 29 2 122 3.81 178 DNT 04H -0.3 2 122 5.28 177 DNT 04H 0.63 3 2 2.99 85 MBM 06H 13.52 3 2 2.02 88 MBM 06H 10.8 3 3 0.49 101 DFS 06C 18.51 3 7 4.7 84 MBM 05C 15.37 3 12 3.32 83 MBM 06C 18.49 3 15 2.4 90 MBM 01H 15.71 3 17 3.65 77 MBM 01H 32.65 3 27 3.65 83 MBM 05H 27.96 3 27 1.17 99 DFS 05H 21.94 3 27 2.96 84 MBM 05H 17.54 3 27 2.43 82 MBM 05H 14.5 3 32 6.03 181 DNG TSH 2.06 3 36 1.13 102 DFS TSC 0.91 3 37 2.51 77 MBM 03H 28.78 3 38 3.16 84 MBM 02C 15.69 3 38 3.87 89 MBM 03H 23.18 3 38 2.1 67 MBM TSH 3.18 3 38 6.34 77 MBM TSH 1.71 3 45 2.31 78 MBM 03C 37.01 3 50 2.94 84 MBM 06C 3.19 3 50 2.91 86 MBM 05C 16.1 3 50 0.87 95 DFS 04C 36.77 3 50 4.21 76 MBM TSC 34.5 3 53 2.25 77 MBM 01C 4.99 3 54 3.22 86 MBM 06C 32.76 3 64 2.91 88 MBM 02H 14.84 3 66 2.99 80 MBM 04C 32.06 3 72 2.67 33 DFS 03C 2.15 3 72 0.79 117 DFS 01H 2.43 3 74 2.54 77 MBM 06H 34.28 3 76 0.93 91 DFS TSC 9.97 3 77 0.73 103 DFS 01H 3.58 3 77 3.86 84 MBM 03H 37.23 3 77 3.64 34 DFS 05H 1.31 3 77 2.52 87 DFS 04H 36.79 3 78 1.62 61 DFS 06H 23.33 3 79 6.95 179 DNG 03C 12.71 3 79 2.1 173 DNG 03C 11.68 3 79 2.68 58 DFS 02C 1.37 3 79 2.09 45 DFS 03C 37.69 3 79 1.27 95 DFS 02H 1.49 Page 4 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 3 79 1.85 65 DFS 03H 37.55 3 79 1.33 100 DFS 04H 0.71 3 80 1.37 64 DFS 02C 1.42 3 80 2.73 67 DFS 04C 1.16 3 80 2.26 75 DFS 02H 1.15 3 83 4.19 58 MBM 03C 28.48 3 83 3.05 180 DNG 05H 31.81 3 86 2.29 80 MBM 05H 36.73 3 86 2.67 86 MBM 06H 29.85 3 89 2.99 83 MBM 01C 37.68 3 92 2.61 85 MBM 05C 14.16 3 94 2.57 79 MBM TSH 15.62 3 94 2.31 83 MBM 06H 7.22 3 99 9.81 82 MBM 03C 5.22 3 100 3.75 182 DNG 01C 2.64 3 100 3.59 53 MBM 04C 3.59 3 101 2.93 179 DNT 05H 0.89 3 101 2.04 175 DNG 05C 1.85 3 101 6.37 179 DNG 04C 3 3 101 2.71 50 MBM 02C 3.36 3 101 0.39 54 NOS TSC 3.08 3 101 0.68 23 MBM TSC 3.36 3 103 2.27 87 MBM TSH 18.71 3 105 2.45 45 MBM 04C 28.05 3 110 4.69 72 MBM 03H 1.16 3 115 4.15 88 MBM 05H 21.15 3 118 2.3 173 DNT 04H -0.38 3 118 3.07 175 DNT 04H 0.63 3 119 4.52 175 DNT 04H 0.63 3 120 2.32 175 DNT 04H -0.31 3 120 4.33 177 DNT 04H 0.64 3 121 2.58 175 DNT 04H 0.68 3 122 3.57 177 DNT 04H -0.33 3 122 5.48 174 DNT 04H 0.66 4 4 2.82 84 MBM 06C 6.36 4 4 2.75 79 MBM 06C 3.01 4 4 1.39 115 DFS 05C 37.88 4 4 2.23 84 MBM 05C 32.18 4 4 2.36 111 DFS TSC 13.57 4 5 0.98 83 DFS 04C 9.01 4 13 3.2 89 MBM 01C 3.4 4 14 2.38 76 MBM 06H 29.87 4 17 4.31 178 DNG 07H 5.72 4 20 6.33 181 DNG 06H 9.58 4 20 1.57 144 DDS 06H 8.55 4 23 2.17 177 DNG 06H 19.02 4 23 2.96 176 DNG 07H 20.35 4 25 0.5 108 DFS 06C 6.22 4 27 0.77 67 DFS 06H 7.98 4 29 0.34 27 GEO TSH -0.03 4 38 2.66 88 MBM 01C 18.19 4 43 2.34 85 MBM 04C 4.96 Page 5 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 4 43 5.05 83 MBM o1C 14.94 4 43 3.3 81 MBM 01C 13.36 4 43 3.36 83 MBM 01C 12.06 4 43 2.64 86 MBM 01C 9.76 4 43 2.14 81 MBM 04C 9.22 4 44 11.2 115 DFS 02H 38.72 4 46 2.17 87 MBM 06C 18.88 4 4B 4.57 82 MBM TSH 17.76 4 49 2 83 MBM 05C 7.24 4 49 1.02 104 DFS 04C 17.85 4 49 2.11 77 MBM TSC 11.43 4 58 4.71 80 MBM 04H 22.68 4 59 6.27 85 MBM 05H 36.39 4 61 2.52 83 MBM 06H 20.58 4 62 5.36 177 DNG 07H 6.87 4 62 4.94 177 DNG 07H 13.3 4 70 2.48 70 MBM 05H 37.86 4 71 3.67 81 MBM 05H 32.2 4 71 3.77 85 MBM 06H 8.31 4 75 2.94 84 MBM 05H 29.08 4 75 2.39 86 MBM 06H 24.08 4 76 2.71 87 MBM 06H 10.67 4 76 4.78 87 MBM 04C 23.67 4 78 1.08 108 DFS 05H 29.59 4 78 0.84 105 DFS 05H 35.87 4 78 4.63 84 MBM 06H 5.02 4 79 2.24 185 DNG 01C 6.48 4 87 3.43 78 MBM TSC 16.46 4 95 3.01 82 MBM 03H 36.3 4 99 2.22 87 MBM 03H 11.35 4 100 5.79 181 DNG TSH 2.8 4 103 4.78 182 DNG 07H 10.91 4 106 2.14 175 DNG 07H 7.55 4 106 2.77 77 MBM TSH 10.23 4 106 5.53 72 MBM 07H 10.63 4 111 2.12 186 DNG FBH 2.87 4 114 2.55 182 DNG 01H 25.91 4 114 2 80 MBM 02H 1.94 4 117 2.04 171 DNT 04H 0.7 4 118 4.22 175 DNT 04H 0.7 4 119 2.92 172 DNT 04H 0.73 4 119 2.6 172 DNT 04H -0.28 4 120 3.33 175 DNT 04H 0.73 4 120 2.98 176 DNT 04H -0.23 4 121 3.62 174 DNT 04H 0.73 4 121 3.76 176 DNT 04H -0.26 4 122 3.13 176 DNT 04H 0.73 4 122 3.76 177 DNT 04H -0.23 5 3 2.93 89 MBM 02C 10.52 5 3 2.72 76 MBM 06C 1.19 5 3 5.27 83 MBM 06C 3.67 5 3 3.9 83 MBM 06C 21.91 Page 6 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A

.ROW COL VOLTS DEG IND %TW LOCATION 5 3 4.76 89 MBM 06C 23.98 5 5 0.59 80 DFS TSH 5.61 5 5 0.76 107 DFS TSH 9.48 5 5 0.81 90 DFS TSH 11.13 5 7 13.63 175 DNT 07C -0.08 5 18 9.25 185 DNG 07H 21.87 5 25 2.59 183 DNG 01H 1.64 5 25 2.34 79 MBM 04H 22.76 5 25 0.71 106 DFS 04C 24.07 5 26 2.11 168 DNT 07C 0.47 5 26 4.09 88 MBM 01C 38.15 5 27 2.68 183 DNT 07C 0.54 5 35 3.99 182 DNG 01H 1.84 5 36 2.89 184 DNG TSH 2.47 5 36 0.88 62 DFS 04H 38.26 5 37 1.18 74 DFS 02H 3.95 5 37 2.99 31 MBM 03C 0.79 5 42 2.67 113 DFS 01C 19.52 5 45 10.37 89 MBM 05C 9.83 5 49 3.63 80 MBM 05H 6.66 5 52 5.09 77 MBM 02H 29.54 5 69 3.08 89 MBM 03C 18.9 5 72 1.72 111 DFS 03C 3.35 5 73 3.32 75 MBM 06H 21.84 5 74 5.21 177 DNG 07H 3.96 5 76 2.18 68 MBM 06H 35.05 5 88 2.86 88 MBM 05H 33.6 5 88 4.51 85 MBM 06H 20.47 5 88 3.21 86 MBM 06H 33.39 5 88 4.75 86 MBM 06H 37.08 5 88 2.6 88 MBM 03C 5.22 5 92 2.67 86 MBM 04C 25.35 5 92 2.59 77 MBM 04C 13.79 5 95 2.96 77 MBM 01H 7.71 5 100 0.44 95 DFS FBH 14.29 5 102 2.91 177 DNG 07H 8.76 5 102 0.89 5 GEO TSH 0 5 105 2.24 87 MBM 05H 33.67 5 105 4.3 89 MBM 04C 33.69 5 108 3.83 175 DNG 07H 4.63 5 111 2.23 179 DNG 07H 8.09 5 111 2.56 177 DNG 07H 10.64 5 111 3.11 177 DNG 07H 16.27 5 113 1.14 91 DFS 01H 20.74 5 114 2.06 183 DNG 02H 16.06 5 114 2.77 182 DNG 02H 17.05 5 116 4.25 81 MBM 06H 7.47 5 116 2.06 83 MBM 06H 9.31 5 116 2.67 83 MBM 06H 12.72 5 116 1.02 85 DFS 02C 33.58 5 116 4.15 50 DFS TSC 14.64 5 116 2.64 56 DFS FBC 0 Page 7 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 5 117 3.46 77 MBM 01C 32.13 5 118 3 80 MBM 01C 23.18 5 119 3.44 174 DNT 04H 0.7 5 119 4.53 176 DNG 07H 3.6 5 120 3.37 178 DNT 04H -0.34 5 120 4.87 177 DNT 04H 0.71 5 121 5.14 174 DNT 04H 0.73 5 121 3.54 175 DNT 04H -0.26 5 122 6.04 178 DNT 04H 0.72 5 122 4.57 177 DNT 04H -0.28 6 1 2.33 82 MBM 06C 23.86 6 3 2.08 90 MBM 03H 6.4 6 12 3.09 184 DNT 07C 0 6 18 2.93 86 MBM TSC 9.53 6 21 0.56 104 DFS 02C 11.74 6 31 2.21 85 MBM FBC 10.85 6 52 4.1 187 DNG 03H 16.11 6 52 3.31 186 DNG TSC 35.85 6 61 7.26 106 DFS 03C 20.34 6 68 3.38 81 MBM TSH 35.98 6 68 4.82 78 MBM TSC 23.31 6 69 2.9 85 MBM 01H 15.1 6 69 4.68 85 MBM 03H 27.22 6 69 2.43 88 MBM 06C 32.87 6 76 2.12 184 DNG 04C 15.39 6 84 2.85 181 DNT 07C -0.35 6 86 1.74 56 DFS 04H 30.24 6 87 2.89 181 DNT 07H -0.3 6 89 2.98 50 MBM 07H 13.92 6 95 2.84 177 DNG 07C 1.03 6 96 4.77 179 DNG 06C 25.49 6 97 4.6 179 DNG 06C 28.72 6 97 3.36 176 DNG 06C 24.69 6 97 3.32 39 MBM 06H 29.49 6 99 1.51 93 DFS 04C 2.29 6 103 3.16 73 MBM 02H 34.86 6 103 2.59 83 MBM 03C 6.29 6 112 2.86 78 MBM 01C 12.41 6 112 4.04 69 MBM TSC 13.84 6 116 2.39 85 MBM TSH 2.91 6 116 2.28 79 MBM TSC 5.28 6 119 2.29 172 DNT 04H 0.71 6 120 3.9 179 DNT 04H 0.68 6 120 3.48 177 DNT 04H -0.31 6 121 5.19 176 DNT 04H 0.73 6 121 3.61 176 DNT 04H -0.29 6 122 2.98 175 DNT 04H 0.68 7 5 5.71 78 MBM 02H 29.26 7 6 4.42 74 MBM 06H 10.53 7 6 2.06 73 MBM 06H 14.39 7 6 2.56 64 MBM 06H 19.95 7 6 2.29 71 MBM FBC 12.31 Page 8 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 7 7 2.15 84 MBM 02H 17.02 7 13 2.4 82 MBM 04C 14.06 7 14 2.2 178 DNG 07H 28.21 7 14 3.69 182 DNG 07H 28.51 7 17 2.15 173 DNG 06H 23.88 7 20 2.11 87 MBM 01C 27.36 7 22 2.95 78 MBM 06H 11.42 7 23 3.73 86 MBM 01H 23.3 7 23 4.35 90 MBM 06C 18.33 7 24 3.03 86 MBM 06H 1.53 7 27 1.21 112 DFS FBC 3.79 7 29 2 85 MBM TSH 10.43 7 29 2.59 84 MBM 06C 17.58 7 29 2.07 82 MBM 06C 24.07 7 29 4.59 79 MBM 06C 21.28 7 29 3.93 80 MBM 02C 26.42 7 30 2.96 74 MBM 01C 8.73 7 30 1 103 DFS 01C 24.32 7 31 3.69 80 MBM 02C 19.44 7 33 0.58 102 DFS 02H 15.72 7 35 2.34 81 MBM FBH 7.09 7 40 1.13 93 DFS 05C 26.46 7 41 1.04 114 DFS 01H 8.93 7 45 3.54 184 DNG 02C 18.7 7 47 2.66 83 MBM 01C 11.64 7 51 3.78 83 MBM TSH 26.91 7 51 2 83 MBM 06C 26.11 7 51 2.2 79 MBM 06C 19 7 51 3.54 77 MBM 06C 15.55 7 56 2.31 85 MBM 03C 17.2 7 57 3.28 88 MBM 05C 2.18 7 59 3.23 180 DNT 02C -0.22 7 60 2.44 90 MBM 05H 8.52 7 63 2 58 MBM 02C 1.88 7 68 0.69 75 DFS 03H 21.62 7 71 4.02 86 MBM 02H 23.25 7 71 2.25 76 MBM 02H 32.4 7 80 4.24 175 DNG 07H 4.01 7 89 2.67 76 MBM 04H 9.37 7 92 5.82 182 DNG 06C 15.33 7 92 15.38 177 DNG 06C 16.48 7 92 6.23 178 DNG 06H 15.79 7 92 15.99 179 DNG 06H 16.94 7 92 2.23 179 DNG 06H 21.01 7 95 3.03 185 DNG 05H 9.11 7 97 2.03 72 MBM 02C 22.9 7 97 2.5 81 MBM 06H 17.02 7 98 2.26 173 DNG 06H 18.97 7 98 2.04 174 DNG 06H 25.51 7 98 2.63 77 MBM 06H 12.25 7 100 2.17 68 MBM 05H 33.54 7 104 2.66 79 MBM 06H 18.21 Page 9 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 7 104 2.16 67 MBM 06H 20.26 7 104 5.38 82 MBM 06C 9.2 7 105 3.33 185 DNG 01C 24.89 7 105 2.65 84 MBM 06H 14.58 7 105 2.22 82 MBM 05C 17.16 7 105 2.13 68 MBM 04C 15.02 7 105 2.24 65 MBM 03C 36.01 7 105 3.54 89 MBM 01C 29.42 7 105 3.34 84 MBM 01C 25.03 7 112 5.26 179 DNG 07H 9.53 7 112 4.52 180 DNG 07H 15.89 7 112 3.63 181 DNG 07H 22.15 7 113 4.68 184 DNG 01H 20.03 7 117 3.29 179 DNG 07H 10.01 7 117 2.14 180 DNG 07H 10.41 7 117 2.72 179 DNG 07H 16.21 7 117 2.67 73 MBM 01H 37.57 7 117 2.55 181 DNG 07H 22.29 7 121 0.81 89 DFS 03C 6.09 7 121 2.88 78 MBM 02C 31.51 7 121 2.05 173 DNT 04H 0.72 7 122 2.3 172 DNT 04H 0.72 8 6 2.84 83 MBM 02H 30.87 8 6 2.53 89 MBM 02H 32.96 8 7 0.78 102 DFS 04C 5.18 8 7 0.58 91 DFS 04C 1.56 8 15 3.64 181 DNG 07H 15.3 8 16 2.92 167 DNT 07C -0.16 8 20 1.95 153 DDS 06H 24.06 8 23 4.73 77 MBM 06C 33.7 8 23 1.1 106 DFS 04C 21.98 8 24 5.09 85 MBM 04C 28.23 8 32 0.85 105 DFS 03H 36.52 8 32 2.27 83 MBM 06C 31.61 8 32 4.09 86 MBM 06C 15.53 8 33 2.6 184 DNG 06H 30.2 8 34 2.35 73 MBM 07H 8.74 8 35 2.2 79 MBM 04C 7.5 8 48 1.02 114 DFS 04C 19.99 8 51 3.54 85 MBM 03C 30.35 8 58 3.13 88 MBM 03H 19.91 8 66 2.56 83 MBM 05H 32.84 8 66 0.46 68 DFS 02C 37.26 8 66 1.18 103 DFS TSC 10.35 8 66 2.71 87 MBM TSC 4.73 8 73 10.01 83 MBM 04C 20.18 8 74 0.7 50 DFS 06C 29.72 8 74 3.49 74 MBM 02C 7.81 8 75 2.02 87 MBM 02C 11.88 8 76 3.35 81 MBM 03H 36.32 8 87 1.03 103 DFS 01H 4.72 8 91 2.44 71 MBM 04C 8.5 Page 10 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 8 96 6.9 181 DNG 06C 29.24 8 98 2.22 178 DNG 06C 23.61 8 100 3.01 179 DNG 06H 30.62 8 104 2.29 68 MBM TSH 6.33 8 106 2.31 90 MBM 07H 15.4 8 106 2.66 89 MBM 06C 26.07 8 114 3.45 89 MBM FBH 3.97 8 119 1.1 100 DFS 06H 15.3 8 119 2.09 75 MBM FBC 13.78 9 3 7 84 MBM 01C 2.5 9 7 2.16 80 MBM 0iC 3.66 9 18 3.71 185 DNG 05C 36.1 9 18 5.17 184 DNG 05C 4.09 9 19 0.62 22 GEO TSH 0 9 22 1.86 136 DDS 06H 27.4 9 28 1.14 114 DFS 05C 33.81 9 28 0.46 83 DFS 06C 21.71 9 29 2.09 181 DNT 06H -0.64 9 32 1.62 144 DDS 03C 26.07 9 41 0.46 68 DFS TSC 8.56 9 44 3.48 88 MBM 05H 18.11 9 46 7.77 183 DNG AV6 9.69 9 52 3.27 180 DNG 06C 14.95 9 52 2.15 171 DNT 07C 0.41 9 53 12.33 84 MBM 01C 29.54 9 60 2.1 77 MBM 02C 9.02 9 65 0.92 107 DFS 01H 23.86 9 69 1.05 101 DFS 02H 35.79 9 74 7.23 186 DNG 07H 3.27 9 75 7.24 186 DNG 07H 3.41 9 76 3.76 181 DNG 07H 18.71 9 93 2.15 82 MBM 02H 7.91 9 94 2.92 180 DNG 06H 24.81 9 94 2.11 177 DNG 06C 31.69 9 94 3.9 177 DNG 06C 28.81 9 97 5.87 72 MBM 07H 8.63 9 98 3.69 179 DNG 06H 25.4 9 99 2.65 177 DNG 06H 21.49 9 100 4.4 79 MBM 02H 30.63 9 108 2.27 73 MBM 06H 28.5 9 108 3.2 90 MBM 07H 9.39 9 111 2.15 178 DNG 06H 17 9 115 6.69 185 DNG 07H 3.64 9 117 3.96 81 MBM TSH 10.42 9 117 3.49 76 MBM TSH 12.7 9 117 2.81 74 MBM TSH 15.97 9 119 3.62 79 MBM 05C 32.03 9 119 2.38 75 MBM 04C 15.06 9 120 3.06 77 MBM 06C 5.2 10 2 3.26 77 MBM 01H 12.37 10 2 3.47 84 MBM 04H 7.22 10 7 2.43 81 MBM FBC 15.04 Page 11 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 10 8 3.12 80 MBM 03H 31.06 10 8 3.03 86 MBM 05C 36.46 10 8 2.91 87 MBM 05C 33.34 10 8 5.35 73 MBM 05C 31.79 10 8 3.53 86 MBM 05C 28.85 10 8 4.95 78 MBM 05C 30.53 10 15 2.17 175 DNT AV6 0.02 10 22 1.14 116 DFS 03C 25.11 10 23 2.31 185 DNG 06H 18.78 10 23 2.24 186 DNG 06H 24.71 10 23 2.94 89 MBM FBC 16.99 10 23 2.43 185 DNG FBC 18.61 10 23 1.17 101 DFS 05C 38.57 10 25 2.57 83 MBM 04H 27.06 10 25 4.8 81 MBM 06C 2.14 10 25 2.05 148 DDS 06H 32.11 10 26 2.48 183 DNT 03C 0.22 10 26 2.26 183 DNT 01H 0.44 10 26 2.91 88 MBM 05C 23.68 10 33 2.56 77 MBM 05C 19.03 10 38 4.27 84 MBM TSH 17.85 10 39 2.73 176 DNG 06H 34.24 10 39 5.06 180 DNG 06C 37.17 10 39 2.37 87 MBM 04C 15.15 10 48 3.6 86 MBM 01H 17.32 10 49 2.66 77 MBM 03C 17.3 10 52 3.7 186 DNG TSC 36.29 10 52 2.93 184 DNG TSC 35.05 10 68 8.11 178 DNT 07C 0.4 10 71 3.69 184 DNG 02H 12.71 10 74 2.76 85 MBM 01H 22.32 10 79 2.96 74 MBM 01C 23.96 10 80 1.56 68 DFS 04H 3.75 10 83 3.41 52 MBM 07H 6.2 10 87 3.37 81 MBM 06H 7.66 10 88 3.61 89 MBM 06H 20.81 10 90 2.17 79 MBM 01C 7.49 10 93 3.51 186 DNG 02C 8.11 10 94 2.38 177 DNG 06C 27.03 10 94 6.59 181 DNG 06C 11.34 10 94 1.07 86 DFS 06C 23.22 10 95 4.54 84 MBM 01H 28.74 10 95 3.89 87 MBM 01H 38.6 10 96 2.48 177 DNG 06C 23.31 10 96 6.98 181 DNG 06C 22.48 10 96 3.62 179 DNG 06C 13.61 10 98 2.09 176 DNG 06H 28.24 10 98 2.23 182 DNG 06C 28.17 10 98 2.26 176 DNG 06C 27.74 10 98 7.55 180 DNG 06H 29.33 10 99 7.05 64 MBM AV6 11.97 10 102 2.39 183 DNG 01C 21.36 Page 12 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 10 104 2.45 182 DNG 01H 12.66 10 111 3.45 176 DNT 07C -0.46 10 111 5.26 178 DNT 07C 0.66 10 118 2.18 80 MBM 06H 11.57 11 3 3.16 82 MBM 03H 33.2 11 5 3.04 79 MBM 01C 19.09 11 12 2.81 88 MBM 01H 14.06 11 12 2.49 80 MBM 01H 34.11 11 12 2.04 76 MBM 03H 35.77 11 12 2 77 MBM 03H 38.36 11 13 2.85 79 MBM 02H 12.92 11 14 2.66 181 DNG 06H 3.52 11 16 2.04 71 MBM 03H 8.11 11 22 2.04 106 DFS 01H 34.97 11 22 0.86 104 DFS 01H 35.5 11 25 3.34 183 DNG 06H 36.54 11 25 5.95 183 DNG 06H 37.58 11 25 8.37 180 DNG 06C 39.12 11 35 2.69 83 MBM 01C 14.35 11 36 6.07 80 ADS TSH 9.55 11 36 1.51 81 MBM TSH 9.55 11 48 4.54 86 MBM 01C 7.57 11 61 3.82 71 MBM 05H 15.74 11 68 2.23 62 MBM 06H 31 11 68 0 0 TWD 0 TSH -0.02 11 68 0.19 25 TWD 76 TSH -0.02 11 68 0.36 16 TWD 50 TSH -0.01 11 68 0.39 11 TWD 35 TSH -0.01 11 68 0.27 14 TWD 44 TSH -0.01 11 68 0.17 27 TWD 81 TSH -0.01 11 68 0 0 TWD 0 TSH -0.01 11 68 0.42 14 PID TSH 0.12 11 68 0.11 46 SCI TSH 0.12 11 70 3.34 83 MBM 05H 24.11 11 81 2.04 184 DNG 04H 33.88 11 81 3.72 184 DNG TSC 5.96 11 83 2.68 78 MBM 01H 12.52 11 88 0.83 65 DFS 05C 30.95 11 93 0.74 100 DFS 03H 15.67 11 96 2.57 77 MBM 01H 19.48 11 96 3.2 89 MBM 03H 11.63 11 97 3 182 DNT FBC -0.17 11 98 0.77 18 SC' TSH 0.06 11 98 5.58 181 DNT 07C 0.06 11 98 0.39 15 TWD 47 TSH 0.11 11 98 0.58 20 TWD 62 TSH 0.11 11 98 0.67 16 TWD 50 TSH 0.11 11 98 0.61 18 TWD 56 TSH 0.11 11 98 0.4 8 TWD 26 TSH 0.11 11 98 0 0 TWD 0 TSH 0.11 11 98 0 0 TWD 0 TSH 0.11 11 98 0.19 10 TWD 32 TSH 0.11 Page 13 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND °/oTW LOCATION 11 98 0.3 14 TWD 44 TSH 0.11 11 98 0.76 19 PID TSH 0.06 11 101 2.4 87 MBM 04C 13.6 11 108 4.34 82 MBM 01H 8.23 11 109 2.48 83 MBM 02H 34.63 11 112 4.02 71 MBM 01 H 5.97 11 115 3.37 81 MBM 04H 25.07 12 8 2.76 182 DNG 07H 3.41 12 12 2.64 182 DNG 07H 3.54 12 17 5.17 86 MBM 01H 20.06 12 17 4.47 83 MBM 05C 21.82 12 21 3.13 71 MBM 03C 9.87 12 22 5.23 79 MBM 05C 10.55 12 25 2.88 183 DNG 06C 35.08 12 25 2.35 184 DNG FBC 18.16 12 27 2.21 184 DNG AV1 3.89 12 31 2.97 181 DNG 07H 3.68 12 32 2.72 182 DNG 07H 3.53 12 33 3.15 67 MBM TSC 7.33 12 33 2.52 85 MBM 01C 5.37 12 34 2.58 184 DNG 07H 3.55 12 37 3.78 85 MBM 02H 35.97 12 37 2.51 75 MBM 04C 32.19 12 37 4.52 85 MBM TSC 11.48 12 39 2.52 83 MBM 01C 9.98 12 40 2.8 87 MBM 05C 38.3 12 40 3.46 82 MBM 03C 35 12 43 3.34 185 DNG 07H 3.78 12 43 2.88 70 MBM 01H 28.62 12 45 2.17 186 DNG 04H 23.73 12 45 2.01 182 DNG 05H 19.91 12 64 0.63 41 NOI TSH 0.58 12 64 0.61 17 PID TSH 0.23 12 64 0.62 15 SCI TSH 0.23 12 64 0 0 TWD 0 TSH -0.06 12 64 0.14 13 TWD 41 TSH -0.06 12 64 0.29 20 TWD 62 TSH -0.06 12 64 0.48 19 TWD 59 TSH -0.06 12 64 0.55 17 TWD 53 TSH -0.06 12 64 0.49 16 TWD 50 TSH -0.06 12 64 0.31 18 'TWD 56 TSH -0.06 12 64 0.07 70 TWD 68 TSH -0.06 12 64 0 0 TWD 0 TSH -0.06 12 65 0.48 14 PID TSH 0.1 12 65 0.5 16 SAI TSH 0.1 12 65 0 0 TWD 0 TSH -0.02 12 65 0.23 12 TWD 31 TSH 0 12 65 0.32 13 TWD 34 TSH 0.03 12 65 0.53 15 TWD 40 TSH 0.05 12 65 0.46 16 TWD 43 TSH 0.08 12 65 0.28 12 TWD 31 TSH 0.1 12 65 0.22 14 TWD 37 TSH 0.13 Page 14 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 12 65 0.08 203 TWD 0 TSH 0.15 12 71 2.75 75 MBM o1C 25.82 12 77 2.73 82 DFS 06C 17.84 12 77 0.54 29 GEO TSH -0.14 12 83 1.13 93 DFS TSH 13.49 12 84 2.64 77 MBM 02C 2.69 12 89 5.21 89 MBM 06H 32.1 12 91 2.61 75 MBM 04C 29 12 92 3.03 80 MBM 03H 38.37 12 99 0.53 27 PID TSH 0.07 12 99 0.63 26 TWD 13 TSH 0.06 12 99 0.5 29 SVi TSH 0.07 12 101 0.7 12 GEO TSH 0.01 12 103 1.23 108 DFS FBH 9 12 103 0.66 29 GEO TSH -0.05 12 104 2.56 88 MBM AV1 10.83 12 104 2.95 79 MBM 02C 29.84 12 106 2.26 83 MBM 02C 7.64 12 110 2.44 181 DNT 02C -0.13 12 111 2.56 88 MBM 02C 28.25 12 112 2.89 80 MBM 02H 38.46 12 113 2 184 DNG 01H 14.52 12 115 2.35 87 MBM 01H 22.32 12 117 5.55 79 MBM 01H 4.65 12 117 2 81 MBM 05H 29 12 118 5.03 90 MBM 01C 39 12 120 7.63 81 MBM 01H 6.16 12 121 3.2 85 MBM 01H 5.8 13 10 2.25 184 DNG 01C 1.63 13 14 2.04 82 MBM 03H 27.32 13 14 2.74 84 MBM 05H 35.24 13 14 1.02 87 DFS 02C 2.84 13 19 0.25 59 GEO TSH 0 13 25 2 69 MBM 01C 9.6 13 26 2.8 78 MBM 05C 14.11 13 26 2.61 79 MBM 05C 10.49 13 26 2.37 72 MBM AV6 -1.47 13 26 2.67 179 DNT 07C 0.64 13 26 5.88 72 MBM AV6 1.15 13 27 11.2 182 DNG 05C 3.87 13 27 8.24 183 DNG 03C 5.45 13 27 2.13 183 DNG 06C 3.72 13 27 2.13 90 MBM 04C 30.41 13 27 2.46 88 MBM 03C 10.86 13 28 2.84 184 DNG 06C 4.9 13 28 5.19 183 DNG 05C 4.85 13 28 8.55 184 DNG 03C 5.89 13 28 2.17 184 DNG 06C 6.39 13 31 1.26 92 DFS 01H 35.28 13 33 2.71 182 DNG 06C 4.33 13 35 2.04 85 MBM 01C 1.92 13 35 0.95 85 DFS TSC 19.02 Page 15 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 13 35 2.63 83 MBM TSC 15.11 13 38 5.02 85 MBM 04H 11.16 13 38 2.28 79 MBM 06C 4.53 13 38 3.61 82 MBM 03C 37.25 13 58 2.05 71 MBM 06H 27.49 13 66 0.54 27 PID TSH 0.16 13 66 0 0 TWD 0 TSH 0.16 13 66 0.17 28 TWD 84 TSH 0.16 13 66 0.32 31 TWD 92 TSH 0.16 13 66 0.36 25 TWD 76 TSH 0.16 13 66 0 0 TWD 0 TSH 0.16 13 66 0.58 17 SCI TSH 0.16 13 73 3.55 78 TWD 05C 15.61 13 75 0 0 TWD 0 TSH 0.11 13 75 0.37 15 TWD 47 TSH 0.11 13 75 0.46 15 TWD 47 TSH 0.09 13 75 0.3 17 TWD 53 TSH 0.09 13 75 0.4 19 TWD 59 TSH 0.09 13 75 0.24 29 TWD 87 TSH 0.09 13 75 0 0 TWD 0 TSH 0.09 13 75 0.34 13 PID TSH 0.16 13 75 0.36 13 SCI TSH 0.16 13 76 2.68 79 MBM 01H 15.73 13 80 2.56 63 MBM 03C 26.82 13 80 4.11 81 MBM 02C 37.83 13 89 3.72 102 DFS FBH 6.65 13 89 3.63 82 MBM 02C 26.26 13 90 2.22 88 MBM 01H 5.88 13 90 3.9 80 MBM 02C 19.38 13 94 3.68 101 MBM 03H 16.61 13 96 5.77 85 MBM 01H 7.76 13 99 6.66 86 MBM AV1 13.56 13 101 2.36 86 MBM 01H 8.57 13 103 3.9 80 MBM 05H 19.57 13 105 2.15 85 MBM 06H 32.73 13 110 4.79 84 MBM 04H 10.86 13 113 2.15 186 DNG 02H 24.94 13 113 2.02 184 DNT FBC -0.21 13 119 4.36 73 MBM FBH 16.75 13 119 2.25 86 MBM 05H 11.01 13 119 2.55 88 MBM 05H 12.57 13 119 2.36 80 MBM 05H 14.85 14 4 4.88 83 MBM FBC 7.52 14 20 0.51 111 DFS 02C 16.54 14 20 0.26 81 DFS 02C 11.76 14 20 0.35 89 DFS 01C 29.56 14 20 0.71 101 DFS 01C 28.87 14 24 2.42 178 DNT AV6 -0.18 14 25 0.5 96 DFS 03H 27.19 14 28 2.14 73 MBM 01C 9.54 14 29 2.28 182 DNG AV6 13.86 14 30 2.32 185 DNG 01H 30.8 Page 16 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 14 36 4.48 80 MBM 01C 1.65 14 38 2.06 84 MBM 01C 7.69 14 38 0.41 87 DFS 01C 3.62 14 38 2.45 83 MBM FBC 15.03 14 40 3.19 89 MBM 03H 33.63 14 41 3.23 83 MBM 01C 6.56 14 44 2.82 76 MBM 01C 7.99 14 48 2.73 78 MBM 01C 7.02 14 54 2.43 74 MBM 01H 25.86 14 54 2.19 75 MBM TSC 28.78 14 64 0.65 111 DFS 06H 35.63 14 79 2.38 65 MBM TSH 23.74 14 83 0 0 TWD 0 TSH 0 14 83 0.45 23 TWD 67 TSH 0.02 14 83 0.3 12 TWD 31 TSH 0.05 14 83 0.44 22 TWD 63 TSH 0.08 14 83 0 0 TWD 0 TSH 0.1 14 83 0.43 22 PID TSH 0.08 14 83 0.41 20 SAI TSH 0.08 14 85 3.97 185 DNG 07H 3.41 14 91 2.68 71 MBM 04H 34.05 14 99 3.28 186 DNG 07H 3.39 14 100 3.36 83 MBM 01H 7.87 14 101 3.23 76 MBM 01H 10.08 14 102 2.22 75 MBM 01H 5.98 14 107 4.24 74 MBM 01H 5.67 14 107 5.62 72 MBM 02C 20.01 14 108 2.41 84 MBM 06C 24.73 14 114 3.15 81 MBM 01H 15.59 14 115 9.34 80 MBM 03C -0.82 14 116 2.16 80 MBM 04C 28.76 14 117 3.89 181 DNG 06C 18.88 14 117 3.55 179 DNG 06C 18.54 14 117 3.34 185 DNG 07H 3.62 14 117 2.07 184 DNG 06C 17.63 14 118 3.23 182 DNG 06C 21.02 15 3 2.55 82 MBM 02H 8.05 15 8 2.61 73 MBM 03C 15.56 15 9 3 86 MBM 04H 36.9 15 9 4.34 75 MBM 02C 7.98 15 11 2.17 85 MBM 02H 25.1 15 23 2.08 183 DNG 01H 5.99 15 23 2.01 82 MBM 03C 17.23 15 27 2.37 84 MBM 02H 9.21 15 27 2.64 84 MBM 03H 31.3 15 32 3.96 85 MBM 02H 5.21 15 32 2.57 83 MBM 05H 30.39 15 32 4.34 77 MBM FBC 1.57 15 35 2.52 79 MBM 03H 14.35 15 40 0.72 91 DFS 06C 34.71 15 46 4 70 MBM 06H 12.41 15 48 0.51 160 SVI 07H 0.26 Page 17 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 15 48 0.41 154 PID 07H 0.27 15 48 0.38 110 DSI 07H 0.39 15 48 0.43 0 TWD 18 07H 0.31 15 59 2.65 84 MBM 02H 6.12 15 78 3.85 79 MBM 05C 1.92 15 78 0.68 105 MBM 05C 1.57 15 91 4 87 MBM 02H 21.46 15 91 4.3 79 MBM 03H 15.76 15 91 3.65 87 MBM 03H 20.99 15 94 0.75 90 DFS 04H 29.12 15 96 2 62 MBM 02C 2.64 15 98 2.37 80 MBM 01H 28.92 15 98 2.07 84 MBM 01H 30.76 15 98 2.74 77 MBM 04C 33.23 15 108 3.04 81 MBM 04H 24.02 15 110 2.58 87 MBM AV1 15.43 15 120 2.12 80 MBM 01C 7.05 16 3 1.27 70 DFS 04H 35.33 16 4 1.94 115 DFS 02H 26.47 16 5 2.62 90 MBM 01C 16.8 16 7 4.34 87 MBM 05C 33.68 16 10 2.66 78 MBM 03C 14.81 16 13 2.27 187 DNG 02C 9.15 16 13 4.92 85 MBM 03C 18.06 16 15 3.74 183 DNG 06H 34.67 16 15 4.97 87 MBM TSC 16.63 16 15 3.12 79 MBM TSC 8.85 16 16 10.42 180 DNG TSC 8.24 16 21 2.91 183 DNG 05H 3.83 16 21 5.53 182 DNG 06H 1.55 16 21 8.03 181 DNG 06H 35.47 16 21 6.68 182 DNG 06H 36.22 16 21 2.43 185 DNG 06H 34.38 16 21 2.23 183 DNG 06H 35.06 16 22 5.34 85 MBM 01C 10.63 16 25 3.71 183 DNG 06H 28.77 16 25 4.82 184 DNG 06H 29.85 16 25 9.97 182 DNG 06C 32.07 16 25 3.47 182 DNG 06C 30.86 16 26 2.2 87 MBM 01C 7.7 16 28 6.98 180 DNG 02H 17.49 16 28 3.45 182 DNG 06H 34.12 16 28 3.5 181 DNG 06C 32.67 16 32 3.24 79 MBM 03C 30.32 16 34 0.95 82 DFS 03H 36.12 16 36 2.49 79 MBM 01H 27.38 16 37 2.9 77 MBM 06H 30.25 16 43 3.79 81 MBM 04H 6.97 16 43 3.23 79 MBM 05H 1.28 16 45 4.4 65 MBM 07H 11.12 16 55 3.63 73 MBM TSH 37.3 16 58 0.62 95 MBM TSH 5.14 Page 18 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 16 72 0 0 TWD 0 TSH 0.05 16 72 0.27 9 TWD 29 TSH 0.05 16 72 0.53 14 TWD 44 TSH 0.05 16 72 0.61 16 TWD 50 TSH 0.05 16 72 0.38 21 TWD 65 TSH 0.05 16 72 0.24 24 TWD 73 TSH 0.05 16 72 0 0 TWD 0 TSH 0.05 16 72 0.56 20 PID TSH 0.17 16 72 0.55 16 SCI TSH 0.17 16 74 1.63 111 DFS 05C 1.83 16 76 0.89 54 DFS 03C 20.29 16 81 2.37 89 MBM 03H 37.26 16 83 4.74 77 MBM 01H 13.05 16 85 2.23 83 MBM 06H 14.69 16 86 2.84 179 DNG 06H 38.13 16 86 2.92 177 DNG 06H 38.84 16 86 4.15 178 DNG 06H 39.12 16 109 2.19 188 DNG 01C 4.84 16 118 2.51 81 MBM 05H 20.01 17 4 0.44 88 DFS 02C 34.97 17 4 0.57 87 DFS 02C 34.53 17 10 0.76 67 DFS 02H 5.92 17 16 2.6 74 MBM 03H 36.32 17 16 2.33 68 MBM 04H 18.08 17 16 2.51 76 MBM 04H 19.49 17 16 2.38 76 MBM 04H 19.87 17 16 2.14 73 MBM 04H 32 17 18 3.74 67 MBM 01C 26.94 17 20 3.67 80 MBM 04C 19.9 17 25 2.09 183 DNG 01H 19.7 17 27 3.09 182 DNG 04H 8.39 17 27 2.46 84 MBM 04C 20.61 17 28 5.35 80 MBM 02C 12.34 17 30 2.92 81 MBM 06C 31.75 17 38 3.6 76 MBM 06H 35.98 17 41 4.38 75 MBM 03H 38.75 17 42 3.23 84 MBM 06C 31.11 17 43 0.93 27 PID TSH -0.1 17 43 0.9 30 SAI TSH -0.1 17 43 0 0 TWD 0 TSH -0.27 17 43 0.22 47 TWD 92 TSH -0.25 17 43 0.81 28 TWD 85 TSH -0.23 17 43 0.94 27 TWD 81 TSH -0.2 17 43 0.47 36 TWD 98 TSH -0.18 17 43 0.29 20 TWD 56 TSH -0.15 17 43 0 0 TWD 0 TSH -0.13 17 47 2.92 79 MBM 06C 24.89 17 51 0.68 25 SAI TSH 0.12 17 51 0.68 25 PID TSH 0.12 17 51 0 0 TWD 0 TSH -0.12 17 51 0.16 11 TWD 28 TSH -0.1 17 51 0.5 22 TWD 63 TSH -0.08 Page 19 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 17 51 0.61 23 TWD 67 TSH -0.05 17 51 0.42 25 TWD 74 TSH -0.03 17 51 0 0 TWD 0 TSH 0 17 51 0 0 TWD 0 TSH -0.14 17 51 0.16 28 TWD 85 TSH -0.12 17 51 0.52 25 TWD 74 TSH -0.09 17 51 0.68 25 TWD 74 TSH -0.07 17 51 0.46 27 TWD 81 TSH -0.04 17 51 0.16 23 TWD 67 TSH -0.02 17 51 0 0 TWD 0 TSH 0.01 17 60 2.84 178 DNG 07H 11.75 17 60 2.26 179 DNG AV5 1.48 17 61 1.37 111 DFS 06H 27.13 17 61 2.7 178 DNG 07H 12.03 17 61 2.27 179 DNG AV5 1.53 17 62 2.4 175 DNG 07H 11.93 17 63 2.45 181 DNG 03H 33.74 17 63 2.42 177 DNG 07H 11.96 17 63 2.67 84 MBM TSC 17.22 17 63 4.61 83 MBM 01C 24.85 17 63 2.03 69 MBM 01C 29.34 17 63 2.87 83 MBM 02C 10.99 17 63 2.01 178 DNG AV5 1.66 17 64 2.94 87 MBM 02H 33.77 17 70 3.28 68 MBM 03H 37.65 17 72 3.95 66 MBM TSH 22.99 17 72 2.72 78 MBM TSH 26.08 17 80 2.71 88 MBM 05H 22.69 17 80 3.76 82 MBM 04C 25 17 86 3.25 182 DNG 04C 5.67 17 87 2.78 82 MBM 03H 25.39 17 87 2.23 79 MBM 07H 7.97 17 89 2.6 181 DNG 01C 35.77 17 95 3.68 79 MBM FBH 15.49 17 101 0 0 TWD 0 TSH 0.03 17 101 0.22 38 TWD 98 TSH 0.03 17 101 0.34 29 TWD 87 TSH 0.03 17 101 0.57 20 TWD 62 TSH 0.03 17 101 0.57 19 TWD 59 TSH 0.03 17 101 0.37 24 TWD 73 TSH 0.04 17 101 0 0 TWD 0 TSH 0.04 17 101 0.59 16 PID TSH 0.06 17 101 0.53 16 SCI TSH 0.06 17 115 2.01 182 DNG 01C 9.36 18 4 3.1 55 MBM 07H 18.72 18 8 6.03 74 MBM 01H 20 18 13 3.61 88 MBM 05C 9.29 18 17 2.62 68 MBM 02C 8.01 18 18 2 185 DNG FBH 5.43 18 18 3.21 182 DNG 04C 31.66 18 19 1.82 84 DFS 03H 26 18 29 1.59 102 DFS 02C 7.64 Page 20 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 18 30 2.79 86 MBM 02H 17.78 18 40 2.11 73 MBM 06C 31.66 18 42 0.37 34 PID TSH -6.02 18 42 0.32 39 MCI TSH -6.02 18 42 0 0 TWD 0 TSH -5.78 18 42 0.21 28 TWD 84 TSH -5.78 18 42 0.29 27 TWD 81 TSH -5.78 18 42 0.26 30 TWD 89 TSH -5.78 18 42 0.13 33 TWD 97 TSH -5.77 18 42 0 0 TWD 0 TSH -5.77 18 42 0 0 TWD 0 TSH -5.78 18 42 0.16, 54 TWD 86 TSH -5.78 18 42 0.26 45 TWD 93 TSH -5.78 18 42 0.3 41 TWD 96 TSH -5.78 18 42 0.29 36 TWD 99 TSH -5.78 18 42 0.2 32 TWD 94 TSH -5.78 18 42 0.13 34 TWD 100 TSH -5.78 18 42 0.08 13 TWD 41 TSH -5.78 18 42 0 0 TWD 0 TSH -5.78 18 42 0 0 TWD 0 TSH -5.79 18 42 0.12 37 TWD 98 TSH -5.79 18 42 0.15 36 TWD 99 TSH -5.79 18 42 0.16 27 TWD 81 TSH -5.79 18 42 0.12 27 TWD 81 TSH -5.78 18 42 0 0 TWD 0 TSH -5.78 18 44 0.44 18 SCl TSH -0.96 18 44 0.4 18 PID TSH -0.96 18 44 0.21 23 TWD 70 TSH -1.08 18 44 0.35 16 TWD 50 TSH -1.08 18 44 0.36 16 TWD 50 TSH -1.08 18 44 0.19 13 TWD 41 TSH -1.08 18 44 0 0 TWD 0 TSH -1.08 18 44 0 0 TWD 0 TSH -1.09 18 44 0.1 20 TWD 62 TSH -1.08 18 45 2.27 67 MBM 05C 26.3 18 45 3.63 86 MBM 05C 16.88 18 45 1.16 73 MBM 05C 17.11 18 49 1.37 26 MAI TSH 0.01 18 49 1.33 24 PID TSH 0.01 18 49 0 0 TWD 0 TSH -0.16 18 49 0.2 7 TWD 17 TSH -0.14 18 49 0.32 6 TWD 15 TSH -0.11 18 49 0.32 11 TWD 28 TSH -0.09 18 49 0.3 19 TWD 53 TSH -0.06 18 49 0.68 16 TWD 43 TSH -0.04 18 49 1.09 28 TWD 85 TSH -0.02 18 49 1.35 24 TWD 70 TSH 0.01 18 49 0.92 24 TWD 70 TSH 0.03 18 49 0.27 24 TWD 70 TSH 0.06 18 49 0.17 8 TWD 20 TSH 0.08 18 49 0 0 TWD 0 TSH 0.1 18 49 0 0 TWD 0 TSH -0.07 Page 21 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 18 49 0.3 23 TWD 67 TSH -0.05 18 49 0.93 19 TWD 53 TSH -0.02 18 49 1.07 17 TWD 47 TSH 0 18 49 0.81 13 TWD 34 TSH 0.02 18 49 0 0 TWD 0 TSH 0.05 18 50 0.65 27 SAI TSH -0.01 18 50 0.45 23 PID TSH -0.01 18 50 0 0 "TWD 0 TSH -0.09 18 50 0.19 19 TWD 53 TSH -0.06 18 50 0.35 22 TWD 63 TSH -0.04 18 50 0.6 23 TWD 67 TSH -0.01 18 50 0.38 25 TWD 74 TSH 0.01 18 50 0.22 31 TWD 96 TSH 0.04 18 50 0.09 28 TWD 85 TSH 0.06 18 50 0 0 TWD 0 TSH 0.09 18 56 3.29 177 DNT 07C 0.22 18 61 3.46 81 MBM 01C 19.93 18 75 2.47 79 MBM 05C 15.36 18 77 2.43 65 MBM TSC 33.9 18 78 1 106 DFS 04C 30.23 18 78 2.45 100 DFS 04C 37.96 18 81 1.67 93 DFS 03H 29.03 18 81 2.57 76 MBM 03C 23.16 18 81 2.16 78 MBM 01C 37.51 18 85 3.59 79 MBM 03H 32.15 18 100 0.96 92 DFS AV6 7.97 18 100 2.07 55 MBM AV6 10.09 18 116 4.98 82 MBM 03H 20.65 19 7 2.55 183 DNT 06C -0.75 19 18 2.14 184 DNG 04C 39.3 19 19 3.24 80 MBM 03C 27.37 19 29 2.35 82 MBM 06C 30.56 19 29 2.01 80 MBM 06C 23.48 19 36 0.97 97 DFS 01C 26.25 19 40 2.97 82 MBM FBC 13.38 19 40 1.12 115 DFS 01C 2.51 19 40 3.18 91 MBM 01C 1.4 19 42 0.43 13 SCI TSH 0.05 19 42 0.37 13 PID TSH 0.05 19 42 8.69 82 MBM FBC 13.39 19 42 0 0 TWD 0 TSH 0.02 19 42 0.26 14 TWD 37 TSH 0.04 19 42 0.49 19 TWD 53 TSH 0.07 19 42 0.59 17 TWD 47 TSH 0.09 19 42 0.35 18 TWD 50 TSH 0.12 19 42 0 0 TWD 0 TSH 0.14 19 44 5.75 71 MBM TSH 14.8 19 52 2.92 185 DNT 02C -0.36 19 59 3.23 70 MBM 01C 4.06 19 59 0.8 107 MBM 01C 4.06 19 66 2.58 186 DNG 02C 31.75 19 66 2.44 185 DNG 01C 22.59 Page 22 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 19 68 0.7 21 PID TSH 0.24 19 68 0 0 TWD 0 TSH 0.17 19 68 0.42 11 TWD 35 TSH 0.17 19 68 0.59 12 TWD 38 TSH 0.17 19 68 0.58 11 TWD 35 TSH 0.17 19 68 0.42 13 TWD 41 TSH 0.17 19 68 0 0 TWD 0 TSH 0.17 19 68 0 0 TWD 0 TSH 0.13 19 68 0.12 27 TWD 81 TSH 0.13 19 68 0.23 20 TWD 62 TSH 0.13 19 68 0.33 15 TWD 47 TSH 0.13 19 68 0.24 14 TWD 44 TSH 0.13 19 68 0.3 12 TWD 38 TSH 0.13 19 68 0.29 12 TWD 38 TSH 0.13 19 68 0 0 TWD 0 TSH 0.13 19 68 0.66 18 MCI TSH 0.24 19 69 0.55 34 SC0 TSH -5.45 19 69 0 0 TWD 0 TSH -5.48 19 69 0.12 17 TWD 53 TSH -5.48 19 69 0.21 35 TWD 99 TSH -5.47 19 69 0.39 35 TWD 99 TSH -5.47 19 69 0.55 32 TWD 94 TSH -5.47 19 69 0.6 33 TWD 97 TSH -5.47 19 69 0.53 35 TWD 99 TSH -5.47 19 69 0.35 39 TWD 97 TSH -5.47 19 69 0.16 31 TWD 92 TSH -5.47 19 69 0 0 TWD 0 TSH -5.47 19 69 0.7 33 PID TSH -5.45 19 73 4.1 80 MBM 05C 17.5 19 75 4.06 89 MBM 06H 14.55 19 75 4.18 61 MBM TSC 25.93 19 79 6.98 83 MBM AV1 4.36 19 87 1.32 91 DFS 01C 5.05 19 91 2.07 153 DDS AV6 6.85 19 98 4.4 89 MBM 01H 34.34 19 98 3.89 84 MBM 04H 21.09 19 98 5.03 87 MBM 04H 37.64 19 99 2.13 88 MBM 03H 25.42 19 101 6.32 185 DNG 02C 32.56 19 112 5.89 83 MBM 05C 24.46 19 115 2.33 110 DFS AV1 7.99 19 118 2.13 179 DNT 01H -0.32 19 118 2.26 179 DNT 04H -0.32 20 5 4.3 78 MBM 01C 36.97 20 5 2.82 80 MBM 02C 30.81 20 5 2.99 77 MBM FBC 17.45 20 6 2.63 80 MBM TSC 15.4 20 6 4.98 82 MBM 02C 16.43 20 6 3.94 80 MBM FBC 7.48 20 12 5.31 78 MBM 01C 4.69 20 12 4.34 76 MBM 01C 7.5 20 14 4.26 80 MBM TSC 10.14 Page 23 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 20 26 2.48 81 MBM 01H 38.78 20 34 2.26 74 MBM 02C 14.32 20 39 0.56 16 SAI TSH -0.01 20 39 3.65 61 MBM 06H 37.1 20 39 0.43 18 PID TSH -0.01 20 39 0 0 TWD 0 TSH -0.06 20 39 0.18 4 TWD 10 TSH -0.04 20 39 0.44 18 TWD 50 TSH -0.02 20 39 0.51 12 TWD 31 TSH 0.01 20 39 0.33 16 TWD 43 TSH 0.03 20 39 0 0 TWD 0 TSH 0.06 20 40 7.97 83 MBM 06C 22.47 20 42 4.76 62 MBM 06H 22.78 20 42 3.64 86 MBM 01C 11.79 20 45 2.55 72 MBM 06H 33.61 20 46 0.32 113 DFS 04H 32.33 20 50 0.32 15 SCI TSH 0.11 20 50 0.23 20 PID TSH 0.11 20 50 1.44 108 DFS TSC 3.07 20 50 0 0 TWD 0 TSH -0.02 20 50 0.35 5 TWD 17 TSH -0.02 20 50 0.39 4 TWD 13 TSH -0.02 20 50 0.33 10 TWD 32 TSH -0.02 20 50 0.32 10 TWD 32 TSH -0.02 20 50 0 0 TWD 0 TSH -0.02 20 59 2.93 60 MBM AV2 10.02 20 60 2.02 75 MBM 02C 35.53 20 73 2.35 79 MBM 06H 26.38 20 77 4.91 68 MBM 01H -26.8 20 77 4.01 80 MBM 01H 5.76 20 77 1.49 88 DFS AV2 1.82 20 77 5.87 88 MBM AV2 2.97 20 77 6.37 78 MBM AV5 4.01 20 81 2.97 182 DNT 04H 0.7 20 82 0 0 TWD 0 TSH 0.05 20 82 0.38 21 TWD 60 TSH 0.07 20 82 0.56 21 TWD 60 TSH 0.1 20 82 0.47 25 TWD 74 TSH 0.13 20 82 0.13 28 TWD 85 TSH 0.16 20 82 0 0 TWD 0 TSH 0.18 20 82 0.57 20 PID TSH 0.08 20 82 0.51 23 SAI TSH 0.08 20 91 2.41 84 MBM 01H 38.83 20 101 2.09 81 MBM 04C 32.24 20 112 2.67 184 DNG 01C 19.98 20 118 2.83 179 DNT 04H -0.23 20 118 2.37 178 DNT 01H 0.65 20 118 2.46 178 DNT 01H -0.28 20 118 2.48 179 DNT 04H 0.71 21 5 2.43 84 MBM 02C 1.95 21 5 3.31 60 MBM 06H 33.98 21 5 2.56 66 MBM 01H 9.24 Page 24 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 21 5 3.39 88 MBM 06C 21.04 21 5 2.34 57 MBM 05C 27.62 21 6 2.27 81 MBM FBC 14.36 21 6 7.1 76 MBM FBC 6.91 21 14 3.5 80 MBM 03C 17.34 21 14 3.05 78 MBM 06H 36.07 21 19 9.39 82 MBM 06C 2.56 21 26 2.3 87 MBM 06C 17.82 21 33 2.17 95 MBM 02C 33.81 21 45 0.25 23 SC' TSH -2.3 21 45 0.27 21 PID TSH -2.3 21 45 3.11 59 MBM 06H 25.17 21 45 3.36 68 MBM 01C 20.85 21 45 0 0 TWD 0 TSH -2.57 21 45 0.13 48 TWD 91 TSH -2.57 21 45 0.25 30 TWD 89 TSH -2.57 21 45 0.27 23 TWD 70 TSH -2.57 21 45 0.12 17 TWD 53 TSH -2.57 21 45 0 0 TWD 0 TSH -2.57 21 49 5.96 76 MBM 05C 27.97 21 55 1.52 108 DFS 05H 34.9 21 59 0.42 21 PID TSH 0.09 21 59 0.37 17 SAI TSH 0.09 21 59 0 0 TWD 0 TSH 0.02 21 59 0.11 1 TWD 2 TSH 0.04 21 59 0.25 24 TWD 70 TSH 0.07 21 59 0.42 21 TWD 60 TSH 0.09 21 59 0.28 20 TWD 56 TSH 0.12 21 59 0.09 1 TWD 2 TSH 0.14 21 59 0 0 TWD 0 TSH 0.16 21 59 4.41 79 MBM 01C 22.24 21 59 2.72 89 MBM 01C 16.28 21 63 2.8 88 MBM TSH 1.2 21 63 10.22 76 MBM TSH 1.22 21 64 0.36 18 PID TSH 0.06 21 64 0 0 TWD 0 TSH 0.12 21 64 0.13 17 TWD 53 TSH 0.12 21 64 0.25 12 TWD 38 TSH 0.12 21 64 0.38 9 TWD 29 TSH 0.12 21 64 0.37 11 TWD 35 TSH 0.12 21 64 0.23 16 TWD 50 TSH 0.12 21 64 0.13 10 TWD 32 TSH 0.12 21 64 0 0 TWD 0 TSH 0.12 21 64 0.31 9 SCI TSH 0.06 21 72 3.14 87 MBM AV5 1.3 21 76 0.29 0 TWD 11 AV2 -0.02 21 86 2.53 180 DNG TSH 1.77 21 86 4.1 182 DNG 06C 39.57 21 86 2.21 89 MBM 01H 34.34 21 86 2.95 82 MBM 02H 5.31 21 86 2.89 78 MBM 02H 11.66 21 86 3.57 72 MBM 02H 34.71 Page 25 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 21 86 2.38 64 MBM 03H 18.43 21 87 3 83 MBM 02C 27.16 21 91 2.21 85 MBM 01C 37.78 21 94 1.35 15 GEO TSH -0.05 21 99 2.05 82 MBM 04C 4.31 21 102 7.04 88 MBM 03H 37.2 21 116 2.9 181 DNT 04H 0.69 21 116 2.37 183 DNT 04H -0.34 21 117 2.51 179 DNT 04H -0.32 21 117 2.78 180 DNT 04H 0.71 21 118 2.15 180 DNT 01H -0.34 21 118 3.77 181 DNT 04H -0.32 21 118 3.6 180 DNT 04H 0.71 22 10 1.09 82 DFS 02H 30.57 22 10 2.32 87 MBM 06C 14.48 22 10 2.68 79 MBM 02H 32.38 22 18 2.03 185 DNG AV2 10.59 22 18 2.06 185 DNG AV5 1.87 22 18 2.25 185 DNG AV5 8.3 22 24 3.72 85 MBM AV6 1.94 22 24 3.2 89 MBM AV6 6.09 22 24 2.5 75 MBM AV6 9.69 22 24 2.29 68 MBM AV6 14.99 22 24 2.67 79 MBM 03H 15.9 22 24 2.65 89 MBM 03H 14.56 22 26 5.16 82 MBM 04C 2.05 22 32 2.24 68 MBM 02C 6.23 22 34 3.27 182 DNG 06H 25.55 22 34 4.8 182 DNG 06H 26.08 22 34 1.57 84 DFS 06H 22.55 22 34 4.9 60 MBM AV1 8.64 22 35 1.39 103 DFS 05C 36.51 22 41 2.7 71 MBM 02C 14.06 22 49 2.96 180 DNT 07H -0.39 22 53 2.34 175 DNG 06H 36.36 22 53 2.57 178 DNG 06C 34.03 22 53 2.07 177 DNG 06C 33.13 22 53 2.14 84 MBM AV1 3.35 22 58 0.45 6 PID TSH 0.05 22 58 0.67 19 SAI TSH 0.05 22 58 0 0 TWD 0 TSH -0.07 22 58 0.24 18 TWD 50 TSH -0.04 22 58 0.4 10 TWD 26 TSH -0.02 22 58 0.46 6 TWD 15 TSH 0.01 22 58 0.54 15 TWD 40 TSH 0.03 22 58 0.28 25 TWD 74 TSH 0.06 22 58 0 0 TWD 0 TSH 0.08 22 66 2.84 79 MBM 06H 16.92 22 69 2.61 181 DNG 07H 7.2 22 69 4.02 88 MBM 04H 15 22 72 0.58 16 SAI TSH 0.07 22 72 0 0 TWD 0 TSH -0.08 Page 26 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 22 72 0.31 17 TWD 47 TSH -0.06 22 72 0.36 18 TWD 50 TSH -0.03 22 72 0.53 21 TWD 60 TSH 0 22 72 0.79 19 TWD 53 TSH 0.02 22 72 0.8 18 TWD 50 TSH 0.05 22 72 0.78 18 TWD 50 TSH 0.08 22 72 0 0 TWD 0 TSH 0.11 22 72 0.79 18 PID TSH 0.07 22 73 2.44 87 MBM TSC 4.51 22 86 3.53 87 MBM 06H 37.23 22 91 4 88 MBM FBH 5.32 22 92 4.52 86 MBM 06C 30.48 22 92 4.75 86 MBM 04C 21.25 22 95 2.73 181 DNT 07C -0.17 22 113 4.17 76 MBM 01C 32.74 22 116 4.46 180 DNT 04H 0.67 22 116 4.12 181 DNT 04H -0.36 22 116 4.07 181 DNT 04H -0.45 22 116 4.42 182 DNT 04H 0.6 22 117 4.46 180 DNT 04H 0.68 22 117 4.2 181 DNT 04H -0.34 22 117 2.13 179 DNT 07H -0.35 22 118 5.86 182 DNT 04H 0.63 22 118 2.21 181 DNT 07H 0.71 22 118 2.26 179 DNT 07H -0.34 22 118 3.01 180 DNT 01H -0.31 22 118 3.11 183 DNT 01H 0.72 22 118 5.12 182 DNT 04H -0.29 23 6 1.74 97 DFS 06C 15.35 23 6 2.65 85 MBM 06C 7.71 23 6 2.15 74 MBM 06C 4.52 23 7 0.19 0 TWD 10 AV1 -0.19 23 10 4.02 185 DNG FBH 16.94 23 10 7.15 183 DNG 01H 9.14 23 11 2.02 182 DNG 06H 37.51 23 19 0.92 105 DFS 06C 23.47 23 19 0.89 97 DFS 06C 9.83 23 19 2.99 86 MBM 03C 25.34 23 19 0.94 92 DFS 05C 38.99 23 22 2.55 186 DNG 06H 1.72 23 22 3.86 69 MBM 01C 35.17 23 27 3.26 86 MBM 05C 7.91 23 33 1.42 59 DFS 06C 17.01 23 33 2.09 120 DFS 06C 18.59 23 33 1.68 118 DFS 06C 24.64 23 33 1.63 120 DFS 06C 36.84 23 33 2.61 64 MBM AV6 15.64 23 33 2.82 79 MBM AV6 13.38 23 34 2.53 76 MBM TSC 15.24 23 34 2.22 76 MBM 05C 7.44 23 34 2.84 75 MBM 01H 31.45 23 34 2.34 84 MBM TSH 17.58 Page 27 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 23 40 2.48 185 DNG AV2 13.5 23 40 3.81 180 DNT AV5 -0.76 23 43 0.48 27 PID TSH -0.33 23 43 0.56 21 SC' TSH -0.33 23 43 0 0 TWD 0 TSH -0.37 23 43 0.13 31 TWD 92 TSH -0.37 23 43 0.35 24 TWD 73 TSH -0.37 23 43 0.43 23 TWD 70 TSH -0.37 23 43 0.4 22 TWD 67 TSH -0.37 23 43 0.27 26 TWD 78 TSH -0.37 23 43 0.16 17 TWD 53 TSH -0.37 23 43 0 0 TWD 0 TSH -0.37 23 51 3.02 183 DNG 06C 35.05 23 54 4.56 182 DNG TSC 12.57 23 55 4.27 184 DNG 02H 23.88 23 55 1.14 65 DFS 04C 25.4 23 65 6.6 90 MBM 04H 36.74 23 74 4.19 81 MBM 06C 20.01 23 78 0 0 TWD 0 TSH -7.74 23 78 0.21 31 TWD 92 TSH -7.74 23 78 0.28 36 TWD 99 TSH -7.76 23 78 0.5 34 TWD 100 TSH -7.76 23 78 0.61 32 TWD 94 TSH -7.76 23 78 0.51 36 TWD 99 TSH -7.76 23 78 0.38 38 TWD 98 TSH -7.76 23 78 0.19 38 TWD 98 TSH -7.76 23 78 0 0 TWD 0 TSH -7.76 23 78 0.79 32 PID TSH -7.88 23 78 0.55 32 Sc' TSH -7.88 23 80 2.18 85 MBM 06C 9.17 23 83 4.54 81 MBM 06C 38.32 23 83 4.85 81 MBM 06C 34.89 23 83 3.42 90 MBM 06C 29.88 23 83 5.27 89 MBM 06C 26.33 23 84 0 0 TWD 0 TSH 0.07 23 84 0.24 11 TWD 35 TSH 0.07 23 84 0.31 13 TWD 41 TSH 0.07 23 84 0.15 15 TWD 47 TSH 0.07 23 84 0 0 TWD 0 TSH 0.07 23 84 0.52 19 PID TSH 0.16 23 84 0.35 18 SCl TSH 0.16 23 88 5.4 73 MBM FBH 15.29 23 88 2.08 79 MBM 01H 7.88 23 88 3.76 74 MBM 01H 3.44 23 89 2.16 185 DNG 05H 9.04 23 89 2.33 185 DNG 05H 31.37 23 89 3.49 185 DNG 06H 23.85 23 89 2.84 186 DNG 05H 38.92 23 93 3.31 182 DNG 02H 30.4 23 97 0 0 TWD 0 TSH -7.93 23 97 0.3 47 TWD 91 TSH -7.93 23 97 0.69 41 TWD 96 TSH -7.93 Page 28 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 23 97 1.15 37 TWD 98 TSH -7.93 23 97 1.4 36 TWD 99 TSH -7.93 23 97 1.38 38 TWD 98 TSH -7.93 23 97 1.05 43 TWD 94 TSH -7.93 23 97 0.67 43 TWD 94 TSH -7.93 23 97 0.28 69 TWD 70 TSH -7.93 23 97 0.11 90 TWD 33 TSH -7.93 23 97 0 0 TWD 0 TSH -7.93 23 97 1.65 40 PID TSH -8.4 23 97 1.54 37 Scl TSH -8.4 23 98 10.04 80 MBM 04C 35.3 23 108 4.07 89 MBM 03H 19.63 23 114 3.27 178 DNT 04H 0.66 23 114 3.95 181 DNT 04H -0.37 23 115 2.68 181 DNT 04H 0.68 23 115 4.61 182 DNT 04H -0.32 23 116 3.1 185 DNG 03C 11.93 23 116 7.13 180 DNT 04H 0.61 23 116 7.56 181 DNT 04H -0.34 23 116 2.94 179 DNT 01H 0.73 23 116 2.52 181 DNT 01H -0.36 23 117 2.24 181 DNT 01H -0.34 23 117 5.01 181 DNT 04H -0.32 23 117 5.96 180 DNT 04H 0.64 23 117 2.38 76 MBM 06C 5.94 23 117 6.94 77 MBM 06C 7.44 23 117 3.55 87 MBM 06C 12.71 24 8 0.18 0 TWD 9 AV1 -0.08 24 11 3.09 75 MBM FBH 11.84 24 23 2.79 188 DNG FBH 13.88 24 24 5.88 78 MBM 01H 5.8 24 25 3.24 182 DNG AV1 3.77 24 25 2.02 180 DNG 02C 21.79 24 36 2.21 81 MBM 06C 28.92 24 36 0.67 102 DFS 06C 18.48 24 37 3.09 87 MBM AV2 12.99 24 42 2.97 81 MBM TSC 9.06 24 46 0.76 109 DFS 05C 37.68 24 47 2.03 66 MBM FBH 16.95 24 47 2.01 75 MBM 01H 4.75 24 47 2.19 86 MBM 01C 34.89 24 48 0.89 120 MBM 02H -1.41 24 48 1.3 134 MBM 03H -18.95 24 48 1.64 128 MBM 03H -21.31 24 48 4.09 72 MBM 02H 18.94 24 48 4.28 71 MBM 02H 18.16 24 48 2.46 75 MBM 06C 16.16 24 48 1.43 53 DFS 04C 26.39 24 48 1.07 99 DFS 01H 38.98 24 48 3.16 77 ADS 02H 21.3 24 48 2.48 64 MBM TSH 14.03 24 48 2.07 73 MBM TSH 9.13 Page 29 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 24 49 2.14 184 DNG 06C 15.58 24 49 2.07 184 DNG 01 H 4.58 24 50 2.25 186 DNG 02H 25.05 24 51 3.53 82 MBM 04C 10.11 24 55 3.5 84 MBM TSH 1.79 24 55 3.21 59 MBM 03H 12.86 24 55 3.84 71 MBM 04H 33.81 24 55 4.21 88 MBM 01C 8.73 24 55 1.09 57 MBM TSH 2.1 24 56 3.9 88 MBM AV2 7.84 24 66 6.79 78 MBM TSC 21.71 24 69 2.96 83 MBM 05H 10.39 24 78 2.01 79 MBM 01H 6.56 24 78 2.77 83 MBM 05H 24.85 24 78 0.63 107 DFS 01C 8.87 24 80 0.4 9 TWD 29 TSH 0.11 24 80 0.26 17 TWD 53 TSH 0.11 24 80 0 0 TWD 0 TSH 0.11 24 80 0 0 TWD 0 TSH 0.11 24 80 0.34 9 TWD 29 TSH 0.11 24 80 0.36 14 TWD 44 TSH 0.11 24 80 0.4 5 TWD 17 TSH 0.11 24 80 0.53 14 PID TSH 0.2 24 80 0.29 17 SCl TSH 0.2 24 82 1.14 87 DFS 05H 37.18 24 82 4.47 83 MBM 06H 12.01 24 82 2.34 70 MBM 02C 33.06 24 84 2.09 69 MBM 07H 13.98 24 85 3.76 73 MBM 06H 22.31 24 88 0 0 TWD 0 TSH -5.4 24 88 0.12 51 TWD 88 TSH -5.4 24 88 0.19 43 TWD 94 TSH -5.4 24 88 0.49 45 TWD 93 TSH -5.4 24 88 1.09 38 TWD 98 TSH -5.4 24 88 1.63 36 TWD 99 TSH -5.4 24 88 1.86 36 TWD 99 TSH -5.4 24 88 1.97 36 TWD 99 TSH -5.4 24 88 2.03 35 TWD 99 TSH -5.4 24 88 2.02 36 TWD 99 TSH -5.4 24 88 1.9 37 TWD 98 TSH -5.4 24 88 1.58 38 TWD 98 TSH -5.4 24 88 1.01 38 TWD 98 TSH -5.4 24 88 0.46 38 TWD 98 TSH -5.4 24 88 0.2 40 TWD 96 TSH -5.4 24 88 0 0 TWD 0 TSH -5.4 24 88 2.26 39 PID TSH -5.6 24 88 2.1 34 SCI TSH -5.6 24 89 5.06 73 MBM 04C 7.16 24 98 6.87 182 DNG 04C 20.66 24 103 0.51 16 SAI TSH 0.1 24 103 0 0 TWD 0 TSH -0.03 24 103 0.19 12 TWD 31 TSH -0.01 Page 30 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 24 103 0.35 15 TWD 40 TSH 0.01 24 103 0.54 15 TWD 40 TSH 0.04 24 103 0.35 17 TWD 47 TSH 0.06 24 103 0.15 28 TWD 85 TSH 0.09 24 103 0 0 TWD 0 TSH 0.11 24 103 0.53 15 PID TSH 0.1 24 106 2.37 183 DNG AV5 4.06 24 106 5.55 79 MBM 04C 34.06 24 114 4.78 180 DNT 04H -0.26 24 114 3.96 181 DNT 04H 0.71 24 114 2.27 184 DNG 06H 22.27 24 115 3.44 179 DNT 04H 0.73 24 115 3.74 179 DNT 04H -0.34 24 116 7.37 179 DNT 04H 0.71 24 116 3.34 178 DNT 01H -0.39 24 116 2.9 179 DNT 01 H 0.73 24 116 9.91 180 DNT 04H -0.33 24 117 3.82 180 DNT 01H -0.34 24 117 7.3 182 DNT 04H -0.34 24 117 8.2 181 DNT 04H 0.65 24 117 3.25 75 MBM TSH 18.32 25 10 2.29 93 MBM 06H 37.83 25 10 2.85 81 MBM 07H 1.71 25 11 3.39 70 MBM AV5 2.91 25 18 2.15 186 DNT 07H 0.8 25 28 3.44 85 MBM 01C 12.3 25 31 3.51 74 MBM 06C 8.58 25 31 2.43 90 MBM 05C 21.66 25 32 0.53 105 DFS 06C 23.59 25 36 2.78 0 ADS 02C 6.3 25 36 0.79 111 MBM 02C 6.12 25 38 2.9 188 DNG 04C 29.75 25 38 3.71 89 MBM 01C 11.28 25 39 2.76 75 MBM 01C 7.22 25 43 5.25 185 DNG 04C 18.56 25 43 2.79 174 DNG 04C 17.79 25 43 3.43 184 DNG FBC 16.93 25 44 2.63 89 MBM 01H 35.24 25 49 2.56 74 MBM 01C 3.58 25 55 2.14 72 MBM TSC 9.72 25 56 0.99 102 DFS 04C 8.56 25 61 2.12 185 DNG TSC 2.83 25 62 0.5 18 PID TSH 0.06 25 62 0 0 TWD 0 TSH 0.12 25 62 0.52 15 SAI TSH 0.06 25 62 0 0 TWD 0 TSH -0.01 25 62 0.22 18 TWD 50 TSH 0.01 25 62 0.55 16 TWD 43 TSH 0.04 25 62 0.51 18 TWD 50 TSH 0.07 25 62 0.38 21 TWD 60 TSH 0.09 25 66 0.72 114 DFS 05C 24.06 25 68 3.13 183 DNG AV5 8.55 Page 31 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 25 68 2.33 188 DNG 04C 34.38 25 69 2.22 182 DNG TSC 17.45 25 69 4.85 183 DNG TSC 12.01 25 69 2.18 183 DNG TSC 11.44 25 69 3.2 183 DNG TSC 10.92 25 69 2.76 77 MBM 04C 20.98 25 69 2.19 72 MBM 04C 25.48 25 71 1.35 37 MCI SBH -1.72 25 71 0 0 TWD 0 SBH -2.04 25 71 0.33 15 TWD 50 SBH -2.04 25 71 0.48 29 TWD 93 SBH -2.03 25 71 0.87 29 TWD 93 SBH -2.03 25 71 1.17 29 TWD 93 SBH -2.03 25 71 1.13 29 TWD 93 SBH -2.03 25 71 0.75 32 TWD 100 SBH -2.03 25 71 0.34 37 TWD 97 SBH -2.03 25 71 0.23 33 TWD 99 SBH -2.03 25 71 0 0 TWD 0 SBH -2.03 25 71 0 0 TWD 0 SBH -2.05 25 71 0.34 22 TWD 72 SBH -2.05 25 71 0.65 28 TWD 90 SBH -2.05 25 71 0.96 28 TWD 90 SBH -2.05 25 71 1.27 30 TWD 96 SBH -2.05 25 71 1.38 33 TWD 99 SBH -2.05 25 71 1.22 40 TWD 96 SBH -2.05 25 71 1.17 39 TWD 96 SBH -2.05 25 71 1.03 35 TWD 98 SBH -2.05 25 71 0.63 39 TWD 96 SBH -2.05 25 71 0.38 41 TWD 95 SBH -2.05 25 71 0.36 36 TWD 98 SBH -2.05 25 71 0 0 TWD 0 SBH -2.05 25 71 0 0 TWD 0 SBH -2.05 25 71 0.6 39 TWD 96 SBH -2.05 25 71 1.17 33 TWD 99 SBH -2.05 25 71 1.68 32 TWD 100 SBH -2.05 25 71 1.75 31 TWD 100 SBH -2.04 25 71 1.35 32 TWD 100 SBH -2.07 25 71 0.79 30 TWD 96 SBH -2.07 25 71 0.49 25 TWD 81 SBH -2.07 25 71 0 0 TWD 0 SBH -2.07 25 71 1 41 PID SBH -1.72 25 76 4.21 64 MBM 01H 19.41 25 79 4.87 78 MBM 03H 10.48 25 80 2.03 79 MBM AV5 7.62 25 80 2.45 75 MBM 06C 26.16 25 81 2.63 80 MBM 01H 20.33 25 81 2.19 90 MBM 01H 29.86 25 81 3.22 86 MBM 02H 15.29 25 82 3.73 77 MBM 06H 31.12 25 84 2.32 185 DNG 06H 23.88 25 86 0.21 0 TWD 11 AV5 0 25 87 2.93 182 DNG FBC 12.71 Page 32 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 25 88 0.38 18 SAI TSH 0.1 25 88 0 0 TWD 0 TSH 0.02 25 88 0.35 11 TWD 28 TSH 0.05 25 88 0.5 14 TWD 37 TSH 0.07 25 88 0.45 14 TWD 37 TSH 0.1 25 88 0.33 7 TWD 17 TSH 0.12 25 88 0 0 TWD 0 TSH 0.15 25 88 0.49 14 PID TSH 0.1 25 91 0 0 TWD 0 TSH -0.07 25 91 0.38 11 TWD 35 TSH -0.07 25 91 0.41 13 TWD 41 TSH -0.07 25 91 0.44 13 TWD 41 TSH -0.07 25 91 0.48 14 TWD 44 TSH -0.07 25 91 0.5 16 TWD 50 TSH -0.07 25 91 0.52 17 TWD 53 TSH -0.07 25 91 0.53 18 TWD 56 TSH -0.07 25 91 0.54 18 TWD 56 TSH -0.07 25 91 0.54 18 TWD 56 TSH -0.07 25 91 0.53 16 TWD 50 TSH -0.07 25 91 0.53 21 TWD 65 TSH -0.07 25 91 0.65 22 TWD 67 TSH -0.07 25 91 0.82 21 TWD 65 TSH -0.07 25 91 0.84 22 TWD 67 TSH -0.07 25 91 0.74 24 TWD 73 TSH -0.07 25 91 0.6 23 TWD 70 TSH -0.07 25 91 0.47 23 TWD 70 TSH -0.07 25 91 0.42 22 TWD 67 TSH -0.07 25 91 0.39 25 TWD 76 TSH -0.07 25 91 0.33 30 TWD 89 TSH -0.07 25 91 0 0 TWD 0 TSH -0.07 25 91 0.5 25 PID TSH 0 25 91 0.43 21 SCl TSH 0 25 93 2.83 80 MBM 06H 32.82 25 96 6.16 88 MBM 06H 34.54 25 99 0.5 18 SAI TSH 0 25 99 0 0 TWD 0 TSH 0.05 25 99 0.36 17 TWD 47 TSH 0.08 25 99 0.45 19 TWD 53 TSH 0.1 25 99 0.52 20 TWD 56 TSH 0.13 25 99 0.42 14 TWD 37 TSH 0.15 25 99 0.16 11 TWD 28 TSH 0.18 25 99 0 0 TWD 0 TSH 0.2 25 99 0.47 19 PID TSH 0 25 111 2.56 84 MBM 03H 26.09 25 113 2.17 183 DNT 04H -0.32 25 114 7.75 180 DNT 04H 0.71 25 114 6.25 182 DNT 04H -0.34 25 115 2.28 182 DNT 01H 0.76 25 115 5.23 182 DNT 04H -0.34 25 115 5.17 181 DNT 04H 0.69 25 116 2.18 182 DNT 01H -0.34 25 116 3.24 181 DNT 01H 0.76 Page 33 of 82

ULNRC-04823 Attachment 3 March 12,2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 25 116 9.12 182 DNT 04H -0.37 25 116 9.6 181 DNT 04H 0.69 26 7 2.62 49 MBM AV1 20.51 26 7 2.47 76 MBM AV1 13.14 26 7 2.36 75 MBM AV6 6.79 26 15 2.39 70 MBM AV6 7.9 26 15 2.21 72 MBM AV5 6.8 26 15 2.76 71 MBM AV2 10.59 26 15 2.77 65 MBM AV2 15.48 26 17 4.43 89 MBM 01C 24.74 26 21 3.73 85 MBM FBC 9.43 26 21 5.17 79 MBM AV6 7.57 26 24 2.75 180 DNG 03C 14.96 26 24 2.14 183 DNG 02C 38.79 26 33 2.55 84 MBM 04H 16.29 26 33 2.7 83 MBM 04H 23.19 26 33 0.2 33 GEO TSH 0.09 26 41 0.78 119 DFS 05C 33.8 26 42 2.6 87 MBM 03H 27.48 26 43 2.29 75 MBM FBC 13.93 26 46 3.65 36 MBM 01C 2.84 26 49 3.75 81 MBM 04H 16.32 26 51 2.51 88 MBM AV2 7.39 26 51 4.65 77 MBM FBC 13.26 26 51 2.36 79 MBM FBC 9.21 26 51 4.31 88 MBM AV2 5.41 26 51 1.01 110 MBM 01C -6.57 26 53 0.15 53 SCI TSH -2.59 26 53 0.76 20 SAI TSH 0.06 26 53 0.3 39 PID TSH -2.59 26 53 0 0 TWD 0 TSH -2.68 26 53 0.13 32 TWD 94 TSH -2.68 26 53 0.16 29 TWD 87 TSH -2.68 26 53 0.18 38 TWD 98 TSH -2.67 26 53 0.18 47 TWD 91 TSH -2.67 26 53 0.15 23 TWD 70 TSH -2.67 26 53 0 0 TWD 0 TSH -2.67 26 53 0 0 TWD 0 TSH -0.01 26 53 0.62 22 TWD 63 TSH 0.02 26 53 0.72 20 TWD 56 TSH 0.04 26 53 0.57 30 TWD 92 TSH 0.07 26 53 0 0 TWD 0 TSH 0.1 26 55 3.51 79 MBM 06C 32.75 26 55 5.9 82 MBM 06C 24.45 26 55 2.3 85 MBM 06C 2.9 26 58 1.32 106 DFS 02C 3.03 26 62 3.19 184 DNG 04H 4.7 26 65 8.24 81 MBM 04C 3.4 26 65 6.34 80 MBM 04C 13.16 26 65 4.36 79 MBM 04C 17.25 26 65 7.37 81 MBM 04C 6.54 26 65 5.12 77 MBM 04C -0.6 Page 34 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 26 67 2.21 79 MBM 01H 23.32 26 67 2.47 84 MBM 01H 26.73 26 67 4.39 75 MBM 01 H 30.3 26 68 4.87 180 DNG AV2 6.26 26 68 2.42 80 MBM TSH 14.82 26 68 3.54 61 MBM TSH 16.25 26 70 3.21 81 MBM 02C 11.65 26 71 2.92 82 MBM 05C 23.94 26 74 2.02 87 MBM 02H 37.3 26 77 0 0 TWD 0 TSH 0.02 26 77 0.28 18 TWD 56 TSH 0.02 26 77 0.32 19 TWD 59 TSH 0.02 26 77 0.36 20 TWD 62 TSH 0.02 26 77 0.36 21 TWD 65 TSH 0.02 26 77 0.44 22 TWD 67 TSH 0.02 26 77 0.47 22 TWD 67 TSH 0.02 26 77 0.3 33 TWD 97 TSH 0.02 26 77 0.25 21 TWD 65 TSH 0.02 26 77 0 0 TWD 0 TSH 0.02 26 77 0 0 TWD 0 TSH -0.01 26 77 0.14 16 TWD 50 TSH -0.01 26 77 0.28 13 TWD 41 TSH -0.01 26 77 0.37 10 TWD 32 TSH -0.01 26 77 0.33 8 TWD 26 TSH 0 26 77 0.34 10 TWD 32 TSH 0 26 77 0.27 9 TWD 29 TSH 0 26 77 0 0 TWD 0 TSH 0 26 77 0.39 15 PID TSH 0.11 26 77 0.25 18 MCI TSH 0.11 26 86 0.26 0 TWD 9 AV1 0 26 86 0.24 0 TWD 12 AV1 0.14 26 88 3.19 83 MBM AV2 11 26 88 2.32 63 MBM AV2 17.44 26 88 2.44 67 DFS AV2 0.85 26 90 2.49 185 DNG 05H 4.04 26 90 3.06 64 MBM 0iC 18.04 26 95 14.12 78 MBM AVI 1.74 26 109 0.35 12 SCl TSH 0.07 26 109 0 0 TWD 0 TSH 0.06 26 109 0.22 9 TWD 29 TSH 0.06 26 109 0.23 5 TWD 17 TSH 0.06 26 109 0.16 3 TWD 10 TSH 0.06 26 109 0 0 TWD 0 TSH 0.06 26 109 0.36 10 PID TSH 0.07 26 113 2.25 178 DNT 04H 0.71 26 113 3.68 179 DNT 04H -0.33 26 113 1.27 69 DFS 02C 24.32 26 114 6.96 177 DNT 04H -0.32 26 114 5.72 179 DNT 04H 0.74 26 114 0.21 46 TWD 6 AV5 0 26 114 0.21 88 INF AV4 0.06 26 115 5.1 180 DNT 04H 0.68 Page 35 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 26 115 2.58 180 DNT 01H -0.31 26 115 5.71 180 DNT 04H -0.33 26 115 0.25 0 TWD 13 AV1 0.19 26 116 4.37 180 DNT 01H -0.34 26 116 5.11 180 DNT 01H 0.77 26 116 12.46 181 DNT 04H -0.34 26 116 8.26 184 DNT 04H 0.68 26 116 4.12 74 MBM 03C 5.52 26 116 8.35 78 MBM 03C 21.92 26 116 5.76 80 MBM 03C 6.86 27 9 3.18 186 DNG 01H 15.87 27 10 2.45 86 MBM AV6 0.93 27 13 4.55 87 MBM FBC 9.23 27 13 3.88 73 MBM FBC 3.61 27 18 5.12 76 MBM 03C 23.14 27 20 2.22 187 DNG 03H 3.08 27 20 5.95 86 MBM FBC 5.55 27 23 11.22 79 MBM 01C 35.75 27 23 7.6 82 MBM 01C 14.06 27 24 2.99 87 MBM 01C 3.07 27 25 7.87 72 MBM 06C 35.95 27 25 3.57 82 MBM 01C 15.73 27 26 8.05 75 MBM FBC 8.44 27 26 5.92 76 MBM 02C 17.13 27 29 6.83 68 MBM AV1 2.41 27 29 7.95 83 MBM 05C 12.93 27 29 4.18 82 MBM 04C 29.34 27 29 8.38 87 MBM AV1 1.15 27 30 12.15 84 MBM 06H 12.4 27 30 11.08 85 MBM 06H 30.51 27 33 2.17 178 DNG 06H 32.25 27 37 4.88 82 MBM 01H 3.61 27 37 10.38 87 MBM 05H 37.04 27 37 0.98 119 MBM TSH 2.62 27 39 9.57 78 MBM 01C 34.59 27 39 5.55 74 MBM FBC 10.81 27 40 7.54 89 MBM TSC 19.19 27 40 3.9 83 MBM 01C 19.79 27 41 12.43 75 MBM 05H 13.48 27 41 5.81 77 MBM 03C 19.49 27 41 4.89 79 MBM 02C 10.74 27 41 6.41 80 MBM 01C 7.24 27 41 6.43 67 MBM 01C 5.38 27 42 7.68 84 MBM 01C 16.37 27 42 5.28 85 MBM 05H 23.68 27 42 2.55 71 MBM 05H 22.1 27 43 2.82 88 MBM 03H 32.63 27 44 2.42 70 MBM 01C 16.29 27 44 4.62 73 ADS 01C 12.55 27 44 1.2 92 MBM 01C 12.99 27 44 1.04 125 MBM 01C 16.05 27 45 4.07 66 MBM 02H 29.41 Page 36 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 27 45 3.74 76 MBM 01C 9.15 27 51 1.62 106 DFS 01C 32.38 27 51 2.89 80 MBM 01C 25.07 27 55 3.19 68 MBM AV1 4.48 27 60 0.71 21 PID TSH 0.05 27 60 0.72 21 SAI TSH 0.05 27 60 0 0 TWD 0 TSH 0 27 60 0.17 18 TWD 50 TSH 0.02 27 60 0.57 19 TWD 53 TSH 0.05 27 60 0.68 20 TWD 56 TSH 0.07 27 60 0.55 17 TWD 47 TSH 0.1 27 60 0.38 21 TWD 60 TSH 0.12 27 60 0 0 TWD 0 TSH 0.14 27 60 3.61 183 DNG 05H 1.12 27 62 2.93 186 DNG 05H 1.93 27 65 2.87 86 MBM 05H 36.68 27 68 0 0 TWD 0 TSH 0.06 27 68 0.2 8 TWD 26 TSH 0.06 27 68 0.37 13 TWD 41 TSH 0.06 27 68 0.5 14 TWD 44 TSH 0.06 27 68 0.41 14 TWD 44 TSH 0.06 27 68 0.59 14 TWD 44 TSH 0.06 27 68 0.39 14 TWD 44 TSH 0.06 27 68 0.13 12 TWD 38 TSH 0.07 27 68 0 0 TWD 0 TSH 0.07 27 68 0.53 19 PID TSH 0.07 27 68 0.43 16 SCl TSH 0.07 27 68 3.45 84 MBM 06H 37.78 27 68 5.22 84 MBM 02H 11.38 27 72 2.7 82 MBM TSH 6.25 27 72 3.09 75 MBM 03H 29.83 27 74 1.35 106 DFS 07H 2.62 27 77 2.33 61 MBM TSH 4.3 27 80 8.83 83 MBM 06H 37.8 27 83 0 0 TWD 0 TSH 0 27 83 0.26 24 TWD 73 TSH 0 27 83 0.41 16 TWD 50 TSH 0 27 83 0.35 19 TWD 59 TSH 0 27 83 0.2 15 TWD 47 TSH 0 27 83 0 0 TWD 0 TSH 0 27 83 0.45 16 PID TSH 0.05 27 83 0.39 18 MCI TSH 0.05 27 84 5.11 90 MBM 06H 24.98 27 84 3.03 84 MBM 06H 36.35 27 85 5.66 85 MBM 04C 19.11 27 89 2.45 185 DNG 05C 37.19 27 89 2.06 79 MBM 02H 18.17 27 97 2.14 73 MBM TSC 18.36 27 99 3.68 181 DNG 03C 3.96 27 100 0 0 TWD 0 TSH 0.12 27 100 0.11 20 TWD 62 TSH 0.12 27 100 0.18 19 TWD 59 TSH 0.12 Page 37 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 27 100 0.24 16 TWD 50 TSH 0.12 27 100 0.31 15 TWD 47 TSH 0.12 27 100 0.34 19 TWD 59 TSH 0.12 27 100 0.32 26 TWD 78 TSH 0.13 27 100 0.61 16 TWD 50 TSH 0.13 27 100 0.89 14 TWD 44 TSH 0.13 27 100 0.59 17 TWD 53 TSH 0.13 27 100 0.21 30 TWD 89 TSH 0.13 27 100 0.15 31 TWD 92 TSH 0.13 27 100 0 0 TWD 0 TSH 0.13 27 100 0.84 11 PID TSH 0.14 27 100 0.91 15 MCI TSH 0.14 27 103 1.75 108 DFS 04C 21.08 27 111 2.54 185 DNG 06C 2.89 27 113 2.15 180 DNT 04H 0.71 27 113 2.06 180 DNT 04H -0.32 27 114 7.8 181 DNT 04H 0.71 27 114 6.58 181 DNT 04H -0.32 27 114 2.65 181 DNT 01H 0.76 27 114 2.31 182 DNT 01H -0.32 27 115 2.34 180 DNT 01H -0.32 27 115 2.62 181 DNT 01H 0.76 27 115 6.95 181 DNT 04H -0.37 27 115 7.05 181 DNT 04H 0.69 27 115 0.49 0 TWD 15 AV1 0 27 115 0.44 0 TWD 14 AV6 0 28 8 0.32 141 TWD 15 AV1 0 28 8 9.51 78 MBM 03C 17.48 28 8 3.73 86 MBM 03C 22.65 28 8 4.73 81 MBM 04C 17.7 28 8 6.12 79 MBM 04C 19.22 28 8 6.15 82 MBM 04H 2.58 28 9 7.06 77 MBM 01C 1.23 28 9 11.34 82 MBM 06H 38.2 28 9 8.66 81 MBM 04H 27.56 28 9 7.75 85 MBM 04H 6.32 28 15 6.4 89 MBM 05H 36.28 28 16 3.94 187 DNG TSC 8.44 28 16 3.13 85 MBM 06H 10.76 28 17 3.07 69 MBM 06C 35.62 28 21 3.54 186 DNG TSH 3.81 28 22 3.72 185 DNG FBH 10.56 28 22 4.28 185 DNG FBH 15.38 28 23 2.2 185 DNG AV2 4.21 28 23 2.58 185 DNG 03H 15.62 28 23 2.42 188 DNG 03H 21.76 28 23 3.29 183 DNG AV4 5.06 28 27 2.79 66 MBM 01H 4.74 28 27 6.69 79 MBM 05H 33.05 28 31 2.95 68 MBM FBC 11.74 28 31 3.61 68 MBM TSC 9.69 28 37 2.87 83 MBM 05C 9.8 Page 38 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 28 42 3.89 89 MBM 07H 8.41 28 64 2.02 83 MBM FBC 2.16 28 67 5.81 81 MBM 01H 6.6 28 67 6.08 81 MBM 02H 10 28 70 3.99 77 MBM TSH 14.87 28 70 3.16 75 MBM AV6 8.43 28 71 2.28 186 DNG 01H 13.39 28 81 8.87 76 MBM TSC 4.25 28 84 11.39 78 MBM 05H 15.49 28 84 3.5 80 MBM 06C 27.07 28 84 5.57 79 MBM 06C 24.21 28 84 4.23 85 MBM 05C 35.7 28 84 5.31 80 MBM 05C 28.33 28 84 8.86 77 MBM 03C 36.51 28 84 6.83 76 MBM 03C 33.96 28 84 9.09 77 MBM 02C 10.66 28 84 3.35 88 MBM 01C 2.99 28 84 3.2 88 MBM 02C 8.95 28 84 3.41 84 MBM TSC 15.1 28 84 4.26 84 MBM TSC 6.17 28 84 2.74 81 MBM TSC 4.83 28 85 3.92 81 MBM 05C 8.24 28 85 2.31 78 MBM 05C 6.3 28 85 3.44 71 MBM 05C 1.62 28 85 3.34 86 MBM 05C 3.54 28 86 6.11 55 MBM 01C 11.84 28 87 4.51 75 MBM 03H 16.99 28 87 8.93 76 MBM 03H 21.75 28 87 7.83 88 MBM AV2 2.51 28 87 10.34 51 MBM AV6 16.81 28 87 6.32 80 MBM 06C 29.24 28 87 8.75 54 MBM AV6 12.22 28 87 1.29 121 MBM TSH 3.04 28 88 3.89 84 MBM 02H 33.88 28 88 1.91 96 DFS 01C 26.96 28 110 5.89 88 MBM TSH 13.12 28 110 7.29 88 MBM 06H 16.54 28 110 2.73 76 MBM 06H 18.2 28 111 2.95 87 MBM 03C 10.1 28 111 5.23 74 MBM AV1 3.61 28 112 2.38 179 DNT 04H -0.34 28 112 2.16 179 DNT 04H 0.64 28 113 2.72 179 DNT 04H 0.79 28 113 2.74 181 DNT 04H -0.2 28 114 2.41 180 DNT 04C 0.58 28 114 8.83 179 DNT 04H 0.65 28 114 2.15 180 DNT 01H -0.31 28 114 8.63 181 DNT 04H -0.33 28 114 2.1 180 DNT 04C -0.42 28 115 2.36 180 DNT 01H 0.75 28 115 9.54 180 DNT 04H -0.31 28 115 8.99 182 DNT 04H 0.67 Page 39 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 28 115 2.19 180 DNT 04C -0.41 29 11 3.35 79 MBM 03C 36.42 29 12 3.5 77 MBM 04H 31.5 29 21 4.97 62 MBM AV2 0.59 29 22 2.8 86 MBM 04C 5.2 29 29 2.58 83 MBM 04C 33.72 29 33 2.83 181 DNG 06C 27.01 29 38 4.21 184 DNG 06H 23.14 29 39 3.71 82 MBM 04C 16.61 29 79 5.61 81 MBM 03H 8.01 29 81 3.27 181 DNG 06H 8.73 29 92 3.87 88 MBM 03H 32.71 29 92 2.54 84 MBM 01C 10.62 29 94 3.13 89 MBM 04H 15.37 29 94 0.9 110 DFS 01C 21.63 29 94 0.97 103 DFS FBC 11.42 29 97 2.29 183 DNG 03H 9.47 29 97 2.34 182 DNG 03H 3.17 29 102 2.67 69 MBM AV1 4.74 29 106 2.23 188 DNG 0iC 28.18 29 106 3.11 188 DNG 01C 23.14 29 106 2.8 188 DNG 01C 29.37 29 106 3.28 77 MBM 04C 8.57 29 107 2.26 83 MBM FBH 12.5 29 112 2.83 179 DNT 04H -0.3 29 113 2.24 190 DNG 04C 16.84 29 113 2.57 179 DNT 04H 0.74 29 113 3.65 179 DNT 04H -0.27 29 114 2.12 181 DNT 01H -0.32 29 114 2.16 179 DNT 01H 0.73 29 114 7.33 180 DNT 04H -0.27 29 114 6.36 179 DNT 04H 0.62 29 114 0.53 0 TWD 16 AV6 0 29 114 0.44 0 TWD 14 AV5 0 29 114 0.31 0 TWD 10 AV2 0 30 9 1.17 83 DFS 04C 28.44 30 9 1.04 95 DFS AV2 10.64 30 9 1.44 61 MBM AV2 6.77 30 10 1.91 108 DFS 03C 3.09 30 29 3.33 80 MBM 01C 27.43 30 30 2.07 74 MBM TSC 12.38 30 31 3.77 183 DNG 02C 1.18 30 31 14.41 83 ADS 05C 16.34 30 31 2.79 94 MBM 05C 16.34 30 33 5.03 85 MBM 07H 16.15 30 33 3.23 89 MBM 07H 9.77 30 33 1.12 110 DFS 01C 25.81 30 35 4.33 80 MBM 02C 25.44 30 35 3.39 88 MBM 06C 22.45 30 41 2.99 88 MBM 03H 18.38 30 42 2 94 DFS 01H 39.35 30 43 4.89 186 DNG 04C 11.6 Page 40 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 30 45 4.78 75 MBM 01C 37.88 30 45 4.64 76 MBM 01C 7.43 30 46 4.61 88 MBM 01H 28.8 30 46 3.29 76 MBM 06C 7.11 30 48 2.16 86 ADS 04H 36.46 30 50 2.33 73 ADS 05H 17.13 30 58 0.72 108 DFS 01H 11.1 30 58 2.06 52 MBM 06H 37.29 30 64 0.8 21 PID TSH -0.03 30 64 0.83 22 SAI TSH -0.03 30 64 0 0 TWD 0 TSH -0.03 30 64 0.38 23 TWD 67 TSH -0.01 30 64 0.65 21 TWD 60 TSH 0.01 30 64 0.8 21 TWD 60 TSH 0.04 30 64 0.75 22 TWD 63 TSH 0.06 30 64 0.5 22 TWD 63 TSH 0.09 30 64 0.24 19 TWD 53 TSH 0.11 30 64 0 0 TWD 0 TSH 0.14 30 66 9.31 89 MBM AV6 1.96 30 71 2.17 75 MBM 01H 17.18 30 75 3.59 184 DNG AV4 4 30 84 4.94 185 DNG 01H 38.28 30 86 2.21 78 MBM 03C 4.9 30 88 1.42 104 DFS 06C 6.6 30 93 4.09 184 DNT 01C -0.62 30 94 2.14 101 DFS 02H 14.32 30 95 3.74 180 DNT 07H 0.47 30 95 2.15 78 MBM 06H 15.17 30 103 2.32 79 MBM 02C 32.6 30 112 2.58 179 DNT 04H -0.31 30 113 3.36 179 DNT 04H -0.19 30 113 2.2 176 DNT 04H 0.75 30 114 2.02 179 DNT 01H 0.72 30 114 6.65 179 DNT 04H -0.29 30 114 5.93 178 DNT 04H 0.65 30 114 3.07 183 DNG 04C 32.58 31 10 2.21 77 MBM 01H 34.54 31 10 2.56 86 MBM 05C 37.52 31 10 4.41 77 MBM 04C 15.06 31 11 0.68 0 TWD 25 AV5 0 31 12 3.95 77 MBM 06C 37.25 31 12 8.53 78 MBM FBC 4.9 31 14 0.11 86 TWD 6 AV4 -0.25 31 16 2.36 61 MBM FBC 5.7 31 18 6.2 77 MBM 06H 19.87 31 31 2.39 82 MBM 01C 20.31 31 33 6.2 183 DNG 06C 32.64 31 33 2.41 181 DNG 06C 31.67 31 41 3.79 172 DNT 01C -0.17 31 42 2.58 86 MBM 04H 3.23 31 42 2.15 69 MBM 01C 12.87 31 47 0.3 71 MBM 03H 7.33 Page 41 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 31 47 0.87 99 MBM 05H 7.7 31 47 1.34 94 MBM 04C -!8.39 31 47 0.77 79 MBM 05C 1 1.37 31 47 3.18 187 DNG 05C 1'0.97 31 47 4.53 187 DNG 03C 3 1.57 31 47 2.11 53 ADS 05H 1 8.87 31 47 3.1 81 ADS 03H .32 31 47 2.97 86 ADS 05H 7.7 31 47 2.89 68 ADS 05C 1 1.43 31 47 3.77 75 ADS 03C 3 1.86 31 58 5.09 140 INF AV6 C).57 31 58 2.64 59 MBM AV5 C).59 31 59 5.74 80 MBM 01C 1.6.37 31 62 2.66 187 DNG 05C 2 0.49 31 74 3.66 84 MBM FBH 3.34 31 74 4.79 81 MBM 01H 3 2.73 31 76 0.47 11 SAI TSH C).08 31 76 0.48 15 PID TSH C).08 31 76 0 0 TWD 0 TSH C).03 31 76 0.26 13 TWD 34 TSH C).05 31 76 0.29 12 TWD 31 TSH C).08 31 76 0.46 15 TWD 40 TSH 0.1 31 76 0.4 14 TWD 37 TSH C).13 31 76 0.33 14 TWD 37 TSH C).15 31 76 0 0 TWD 0 TSH C).18 31 79 2.96 72 MBM 040 2.58 31 80 2.78 76 MBM 05H 15.06 31 80 2.55 74 MBM AV5 11.95 31 80 3.63 84 MBM AV5 5.31 31 80 4.07 55 MBM AV5 10.89 31 83 3.03 85 MBM FBC 110.5 31 84 1.43 111 DFS 05H 2 3.06 31 85 3.95 71 MBM 02H 2 3.27 31 86 2.56 83 MBM FBH 14.08 31 87 3.07 178 DNT 07C ().33 31 88 2.3 68 MBM 02H 4.85 31 90 3.7 185 DNG 02C 19.48 31 94 4.96 78 MBM 03C 3 3.32 31 94 1.1 77 MBM 04C -I6.93 31 96 5.66 178 DNT 07C ().35 31 101 0 0 TWD 0 TSH ().01 31 101 0.19 15 TWD 40 TSH ).03 31 101 0.58 20 TWD 56 TSH ).06 31 101 0.7 21 TWD 60 TSH ).08 31 101 0.29 10 TWD 26 TSH ).1 1 31 101 0.12 9 TWD 23 TSH ).13 31 101 0 0 TWD 0 TSH ).16 31 101 0.49 15 PID TSH ).13 31 101 0.21 0 TWD 10 AV3 ).05 31 101 0.52 14 SAI TSH ).13 31 103 1.55 103 DFS 02H 23.19 31 105 2.89 180 DNT 07H 0.7 Page 42 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 31 109 0.25 0 TWD 12 AV4 0.05 31 109 0.1 0 TWD 6 AV3 0.3 31 110 0.27 0 TWD 9 AV5 -0.17 31 110 2.52 75 MBM 02H 19.39 31 110 1.29 103 DFS TSH 17.68 31 111 0.24 0 TWD 10 AV3 0 31 111 0.13 0 TWD 7 AV5 0 31 111 0.13 0 TWD 7 AV6 0 31 112 2.18 180 DNT 04H 0.69 31 112 2.22 182 DNT 04H -0.32 31 112 0.33 0 TWD 14 AV4 0 31 113 2.86 178 DNT 04H 0.74 31 113 3.15 181 DNT 04H -0.3 32 11 0.31 0 TWD 15 AV2 -0.05 32 11 0.49 0 TWD 21 AV5 0.08 32 11 3.15 89 MBM 05C 34.78 32 12 0.63 0 TWD 25 AV3 0.08 32 12 0.19 0 TWD 10 AV4 0.18 32 14 0.27 0 TWD 11 AV3 -0.15 32 16 4.63 70 MBM 01H 6.63 32 20 0.96 84 DFS 02C 27.89 32 20 2.18 79 MBM 06H 16.03 32 20 2.32 65 MBM 02C 7.49 32 21 3.66 73 MBM 05H 32.63 32 21 3.6 85 MBM 02H 20.07 32 22 3.48 186 DNG 05C 33.28 32 22 0.53 0 TWD 22 AV2 0 32 24 1.61 99 DFS 01C 1.59 32 24 1.38 111 DFS TSC 16.9 32 24 2.73 78 MBM 04H 25.63 32 26 0.87 104 DFS AV1 1.61 32 26 1.88 112 DFS 03C 38.97 32 26 2.16 57 MBM TSC 7.26 32 28 3.66 189 DNG 04H 5.8 32 29 0.97 87 DFS 01C 2.24 32 29 0.93 94 DFS 01C 36.84 32 29 2.46 68 MBM AV5 7.06 32 29 2.33 73 MBM 05H 30.55 32 31 1.74 104 DFS TSC 11.42 32 35 1.06 104 DFS 01C 12.32 32 35 0.69 106 DFS 01C 13.5 32 36 1.54 130 DFS FBC 16.46 32 41 1 57 DFS 03C 16.09 32 42 0.27 0 TWD 13 AV2 -0.44 32 43 0.3 0 TWD 15 AV2 0.39 32 43 0.24 0 TWD 12 AV3 0.02 32 44 2.98 181 DNT 07H 0.51 32 46 3.47 44 MBM 03H 25.39 32 48 5.27 182 DNG 02H 19.75 32 48 0.39 0 TWD 19 AV3 -0.09 32 48 0.35 0 TWD 18 AV4 0.16 32 48 0.25 0 TWD 13 AV6 -0.09 Page 43 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 32 48 3.86 83 MBM 04C 13.21 32 49 3.3 87 MBM 02C 1.62 32 56 2.84 80 MBM 06H 31.54 32 60 2.8 186 DNG 04C 33.05 32 65 0.51 15 PID TSH -3.18 32 65 0.49 9 SCl TSH -3.18 32 65 0 0 TWD 0 TSH -3.06 32 65 0.14 18 TWD 56 TSH -3.06 32 65 0.29 20 TWD 62 TSH -3.06 32 65 0.43 13 TWD 41 TSH -3.06 32 65 0.36 14 TWD 44 TSH -3.06 32 65 0.16 16 TWD 50 TSH -3.06 32 65 0 0 TWD 0 TSH -3.06 32 70 4.01 79 MBM 01H 7.81 32 70 2.27 86 MBM 01H 10.23 32 70 2.21 90 MBM 02H 3.09 32 75 2.61 186 DNG AV6 13.72 32 76 0.22 0 TWD 11 AV6 0 32 76 0.22 0 TWD 11 AV3 0 32 77 2.25 182 DNT AV4 0.53 32 78 0.47 0 TWD 19 AV6 -0.1 32 82 0.66 24 PID TSH 0.07 32 82 0 0 TWD 0 TSH 0 32 82 0.15 26 TWD 77 TSH 0.02 32 82 0.53 22 TWD 63 TSH 0.05 32 82 0.78 20 TWD 56 TSH 0.07 32 82 0.67 24 TWD 70 TSH 0.1 32 82 0.29 31 TWD 96 TSH 0.12 32 82 0.13 21 TWD 60 TSH 0.15 32 82 0 0 TWD 0 TSH 0.17 32 82 0.7 21 SAI TSH 0.07 32 87 2.55 185 DNG TSC 4.63 32 88 2.06 178 DNT 07C -0.68 32 88 5.34 178 DNT 07C 0.33 32 88 6.34 178 DNT 07H 0.53 32 95 2.39 178 DNT 07C -0.24 32 97 0.38 0 TWD 18 AV3 0.12 32 97 0.39 0 TWD 18 AV2 0 32 106 0.18 0 TWD 9 AV3 -0.02 32 106 0.26 0 TWD 12 AV4 -0.05 32 110 0.23 0 TWD 12 AV4 -0.06 32 110 5.8 82 MBM 04C 2.77 32 111 3.21 84 MBM 03H 11.29 32 111 5.54 90 MBM 01H 11.57 32 111 4.86 85 MBM 01H 9.39 32 111 6.31 73 MBM 01H 5.88 32 112 0.36 0 TWD 16 AVI 0.25 32 112 0.45 0 TWD 20 AV2 -0.16 32 112 0.15 0 TWD 5 AV5 0 32 112 0.22 0 TWD 9 AV6 0 32 113 3.47 178 DNT 04H -0.31 32 113 2.67 182 DNT 04H 0.7 Page 44 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 33 11 0.19 0 TWD 10 AV1 0.08 33 11 1.46 0 TWD 38 AV2 -0.05 33 11 0.47 0 TWD 20 AV5 0 33 12 0.29 0 TWD 14 AV3 0 33 14 0.26 0 TWD 13 AV4 0 33 19 3.37 65 MBM 01H 29.06 33 19 2.75 89 MBM 04H 3.4 33 19 2.72 77 MBM FBC 13.01 33 32 2.87 183 DNG 01H 14.57 33 34 1.88 92 DFS TSH 8.98 33 35 2.59 106 DFS TSH 13.63 33 38 2.62 176 DNT 07C 0.36 33 43 4.61 188 DNG FBH 16.41 33 44 9.38 183 DNG 07H 9.04 33 45 2.72 74 MBM 04H 15.5 33 53 2.97 183 DNG 03H 21.61 33 53 0.65 103 DFS 01C 10.55 33 55 5.39 179 DNT 07H 0.53 33 57 2.21 182 DNG 02H 19 33 62 3.13 83 MBM FBC 16 33 68 3.53 87 MBM 04H 11.87 33 68 0.71 91 DFS FBH 10.63 33 68 0.79 95 DFS FBH 11.55 33 74 3.53 182 DNG 06H 36.54 33 74 0.78 21 PID TSH 0.08 33 74 0 0 TWD 0 TSH 0.03 33 74 0.1 21 TWD 60 TSH 0.05 33 74 0.37 23 TWD 67 TSH 0.07 33 74 0.82 20 TWD 56 TSH 0.09 33 74 0.58 27 TWD 81 TSH 0.12 33 74 0.29 10 TWD 26 TSH 0.15 33 74 0 0 TWD 0 TSH 0.17 33 74 0.88 17 SAI TSH 0.08 33 76 2.29 71 MBM AV6 14.27 33 79 1.09 103 DFS 01H 6.71 33 79 2.94 101 DFS 01H 23.94 33 79 1.52 81 DFS 02H 8.87 33 79 3.81 86 MBM 05H 6.26 33 79 1.02 93 DFS 05C 15.54 33 80 2.52 85 MBM 03H 15.05 33 80 2.47 82 MBM 05H 5.81 33 80 2.71 75 MBM 01C 32.74 33 81 2.35 182 DNG AV1 1.75 33 83 1.58 100 DFS FBC 13.73 33 83 2.31 81 MBM TSH 11.42 33 83 2.43 76 MBM AV3 6.3 33 84 2.06 89 MBM 01H 31.62 33 84 2.3 88 MBM 04H 26.99 33 85 0.89 112 DFS 01H 26.74 33 85 1.02 104 DFS 07H 9.15 33 88 2.32 177 DNT 07H 0.61 33 88 2.36 179 DNT 07C 0.27 Page 45 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 33 91 2.84 76 MBM 02C 11.82 33 92 4.54 181 DNG TSH 7.42 33 92 2.12 180 DNG TSH 6.38 33 94 5.86 84 MBM 01H 37.15 33 94 2.22 79 MBM 01H 38.14 33 94 2.93 85 MBM 02H 1.57 33 94 4.23 89 MBM 02H 21.36 33 95 5.36 81 MBM 04C 36.12 33 96 3.96 179 DNT 07C 0 33 96 2.07 180 DNG 06C 39.57 33 96 6.89 78 MBM 03C 36.95 33 96 3.38 180 DNG 06H 39.74 33 97 4.9 86 MBM 05H 31.78 33 100 8.97 82 MBM 05H 6.24 33 103 0.36 0 TWD 16 AV3 0.12 33 105 0.26 0 TWD 12 AV5 -0.2 33 108 0 0 TWD 0 TSH 0.09 33 108 0.19 23 TWD 70 TSH 0.09 33 108 0.38 14 TWD 44 TSH 0.09 33 108 0.5 13 TWD 41 TSH 0.09 33 108 0.36 16 TWD 50 TSH 0.09 33 108 0.16 28 TWD 84 TSH 0.09 33 108 0 0 TWD 0 TSH 0.09 33 108 0.44 15 PID TSH 0.08 33 108 0.42 6 SCI TSH 0.08 33 109 2.54 187 DNG FBC 13.06 33 109 0.2 0 TWD 10 AV2 -0.1 33 109 0.12 0 TWD 6 AV4 0.17 33 109 0.13 0 TWD 4 AV5 -0.15 33 109 0.15 0 TWD 8 AV6 0.1 33 111 0.57 0 TWD 23 AV5 0 33 111 0.49 0 TWD 20 AV3 0 33 111 0.21 0 TWD 7 AV2 0 33 112 12.5 183 DNG AV2 10.05 33 112 7.27 181 DNT AV4 0 33 112 12.06 183 DNG AV3 2.8 34 25 2.74 187 DNG 01H 38.85 34 25 2.23 186 DNG 02C 29.17 34 43 3.04 84 MBM 04H 36.22 34 45 7.54 39 MBM AV2 6.93 34 45 2.83 71 MBM 05C 8.67 34 45 2.86 74 MBM 01C 10.73 34 54 2.05 83 MBM 06H 15.08 34 54 2.19 87 MBM 05C 31.8 34 61 0.41 101 DFS 02H 9.8 34 62 3.25 78 MBM 02C 11.08 34 63 2.67 82 MBM 05C 30.23 34 66 3.85 77 MBM 02C 24.25 34 68 5.29 85 MBM 02H 3.08 34 73 0.21 23 PID TSH -3.53 34 73 0 0 TWD 0 TSH -3.44 34 73 0.16 17 TWD 53 TSH -3.44 Page 46 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND W LOCATION 34 73 0.16 16 TWD 50 TSH -3.44 34 73 0.14 21 TWD 65 TSH -3.44 34 73 0.15 24 TWD 7'3 TSH -3.44 34 73 0.09 18 TWD 56 TSH -3.44 34 73 0 0 TWD 0 TSH -3.44 34 73 0.21 25 SCI TSH -3.53 34 74 2.14 188 DNG TSH 10.95 34 74 3.39 188 DNG TSH 12.14 34 76 2.31 181 DNG 07H 7.07 34 79 0.41 0 TWD 7 AV2 0 34 79 0.39 0 TWD 17 AVI 0.2 34 80 1.78 36 PID TSH -4.76 34 80 0 0 TWD 0 TSH -4.65 34 80 0.12 34 TWD 1 1(00 TSH -4.65 34 80 0.16 22 TWD 617 TSH -4.65 34 80 0.15 20 TWD 62 TSH -4.65 34 80 0.33 48 TWD 91 TSH -4.65 34 80 0.78 39 TWD 917 TSH -4.65 34 80 1.2 35 TWD 9i9 TSH -4.64 34 80 1.6 34 TWD 1C00 TSH -4.64 34 80 1.6 32 TWD 94 TSH -4.64 34 80 1.27 33 TWD 97 TSH -4.64 34 80 0.5 35 TWD 99 TSH -4.64 34 80 0.17 15 TWD 47 TSH -4.64 34 80 0.13 9 TWD 9 TSH -4.64 34 80 0 0 TWD 0 TSH -4.64 34 80 1.66 34 SCI TSH -4.76 34 87 3.2 183 DNG 06H 32.07 34 89 0 0 TWD 0 TSH 0.01 34 89 0.24 21 TWD 635 TSH 0.01 34 89 0.4 15 TWD 47 TSH 0.01 34 89 0.45 13 TWD 4I1 TSH 0.01 34 89 0.25 20 TWD 32 TSH 0.01 34 89 0 0 TWD 0 TSH 0.01 34 89 0.49 16 PID TSH 0.05 34 89 0.46 14 SCI TSH 0.05 34 90 1.01 101 DFS 01H 30.3 34 97 2.82 81 MBM 01H 15.12 34 98 0 0 TWD 30 TSH 0.01 34 98 0.17 12 TWD 731 TSH 0.03 34 98 0.53 24 TWD 570 TSH 0.06 34 98 0.72 20 TWD 556 TSH 0.08 34 98 0.57 20 TWD 656 TSH 0.1 34 98 0.32 21 TWD 30 TSH 0.13 34 98 0 0 TWD 0 TSH 0.15 34 98 0.7 20 PID TSH 0.08 34 98 0.51 24 SAI TSH 0.08 34 99 0.12 0 TWD 7 AV4 0 34 103 1.11 99 DFS 02H 31.41 34 104 2.93 84 MBM AV1 7.44 34 108 2.04 184 DNG 03H 10.86 34 108 4.33 184 DNG 03C 14.23 Page 47 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 34 110 3.14 179 DNT 07C 0.33 35 13 0.22 0 TWD 11 AV1 0 35 13 2.41 187 DNG 03H 24.2 35 13 3.05 186 DNG AVi 10 35 14 0.19 37 TWD 10 AV1 -0.03 35 14 0.2 30 TWD 11 AV4 -0.17 35 16 3.67 85 MBM 05H 5.14 35 17 0.46 0 TWD 20 AV4 0 35 18 3.05 85 MBM AV6 17.04 35 18 4.39 78 MBM 04C 10.28 35 18 2.25 82 MBM 01C 38.16 35 18 2.48 64 MBM 02C 20.28 35 20 0.64 58 TWD 25 AV3 0.08 35 25 2.46 81 MBM 01C 6.63 35 36 7.4 86 MBM FBH 2.75 35 36 6.33 73 MBM 02H 22.38 35 37 1.27 88 DFS 03C 30.41 35 43 2.74 87 MBM 01C 6.3 35 44 4.08 76 MBM 05C 16.94 35 44 5.36 79 MBM 05C 4.73 35 47 0.38 0 TWD 17 AV2 0 35 47 0.23 0 TWD 10 AV3 0 35 47 0.7 0 TWD 27 AV4 0 35 47 0.36 0 TWD 16 AV5 0 35 47 0.18 0 TWD 7 AV6 0 35 47 2.69 188 DNG 02C 11.9 35 50 2.5 180 DNT 07H 0.54 35 64 2.68 79 MBM 02H 10.79 35 65 2.46 84 MBM 06C 34.16 35 72 5.63 181 DNT 07C 0.38 35 72 3.14 182 DNT 07C -0.73 35 72 2.14 78 MBM 01H 9.74 35 72 2.75 84 MBM 04H 20.52 35 72 2.13 77 MBM 04H 24.07 35 73 2.95 73 MBM 01H 13.65 35 76 2.35 75 MBM 06H 3.42 35 77 2.12 182 DNT 07C -0.2 35 79 3.03 75 MBM 06C 20.32 35 87 2.86 79 MBM 05C 13.07 35 87 2.52 79 MBM 05C 9.44 35 87 1.5 110 DFS 05C 5.76 35 87 1.19 103 DFS 05C 7.41 35 87 1.45 110 DFS 05C 4.65 35 87 2.48 76 MBM 04C 35.9 35 100 2.4 71 MBM 06H 8.82 35 101 2.4 183 DNG 06C 35.82 35 104 3.06 184 DNG 05C 10.69 35 105 2 182 DNT 07C -0.22 35 105 1.16 105 DFS FBC 14.25 35 106 2.49 186 DNG 06H 29.39 35 106 7.37 185 DNG 06H 30.48 35 106 4.5 183 DNG 06C 37.89 Page 48 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND  %/oTW LOCATION 35 106 4.52 183 DNG 06C 31.87 35 106 2.44 182 DNT 07C -0.71 35 106 2.23 182 DNT 07C 0.34 35 107 2.96 182 DNG 06C 32.76 35 107 2.04 184 DNG 06C 31.64 35 107 2.62 183 DNG 06H 34.24 35 108 2.59 73 MBM 03C 34.25 35 110 3 181 DNT 07C 0.32 36 13 0.78 0 TWD 28 AV4 0 36 13 0.32 0 TWD 15 AV1 0 36 15 0.39 86 TWD 18 AV4 0.14 36 18 2.65 182 DNG AV3 11.41 36 20 2.69 81 MBM 04H 1.69 36 22 0.91 0 TWD 16 AV4 -0.02 36 22 2.23 184 DNG 04H 26.94 36 23 0.32 30 TWD 16 AV4 0.17 36 24 3.54 182 DNT 07H 0.48 36 24 3.2 185 DNG 06C 37.54 36 28 2.2 69 MBM 01C 29.51 36 31 1.11 101 DFS 02H 34.06 36 31 0.98 99 DFS 03H 1.98 36 31 2.98 88 MBM 02H 30.11 36 32 3.62 78 MBM 06H 17.21 36 35 0.99 89 DFS FBC 2.41 36 41 4.38 183 DNT 07C 0.32 36 43 5.51 182 DNG 01C 1.21 36 44 2.26 188 DNG 01H 1.84 36 44 3.39 187 DNG 03C 4.37 36 44 3.3 183 DNT 07H 0.68 36 44 2.49 88 MBM 02H 28.17 36 46 3.83 87 MBM 03H 21.04 36 46 5.97 80 MBM 04C 8.29 36 46 3 85 MBM 04C 2.73 36 46 2.27 83 MBM 03C 24.84 36 47 6.05 70 MBM 03C 20.37 36 49 2.1 182 DNT 07H 0.58 36 50 4.65 182 DNT 07H 0.62 36 50 2.23 89 MBM 04H 38.18 36 55 5.63 76 MBM 05C 21.14 36 55 5.88 76 MBM 05C 18.9 36 55 4.68 85 MBM 05C 15.18 36 59 0.37 94 MBM 04H 1.29 36 59 2.64 73 MBM 06H 2.27 36 59 3.76 88 ADS 04H 1.41 36 75 3.17 73 MBM 01C 25.37 36 76 2.82 180 DNT 07C 0.35 36 78 1.14 9 GEO TSH -0.06 36 78 3.18 74 MBM FBH 5.46 36 78 2.01 74 MBM FBH 7.15 36 78 2.87 67 MBM FBH 14.77 36 79 2 182 DNT 02C 0.05 36 79 2.37 71 MBM FBH -11.84 Page 49 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 36 80 2.08 184 DNG 06C 39.66 36 85 3.3 87 MBM TSH 17.82 36 87 4.84 185 DNG 06H 35.51 36 87 17.26 182 DNG 06H 36.66 36 87 2.94 186 DNG 06C 37.71 36 87 0.3 0 TWD 12 AV2 0 36 97 4.05 79 MBM 05C 7.57 36 98 0.21 0 TWD 11 AV1 -0.32 36 101 2.43 83 MBM 05C 17.38 36 102 2.69 185 DNG 06H 37.54 36 102 6.34 182 DNG 06C 37.07 36 102 2.25 182 DNG 06C 35.95 36 102 2.92 60 MBM AV5 8.72 36 104 0.23 0 TWD 11 AV2 0.1 36 104 0.31 0 TWD 15 AV3 0.15 36 105 0.19 0 TWD 10 AV4 0 36 105 0.24 0 TWD 12 AV3 0 36 106 2.13 178 DNT 07C 0.37 36 107 0.28 0 TWD 14 AV3 -0.17 36 108 3.06 179 DNT 07C 0.32 36 110 8.02 177 DNT 07C 0.29 36 110 5.29 178 DNT 07C -0.73 37 16 3.73 79 MBM 06H 1.72 37 21 6.16 183 DNG 07H 1.43 37 21 3.08 181 DNT 07H 0.35 37 25 2.64 183 DNG 06H 36.2 37 25 6.86 183 DNG 06H 37.31 37 25 13.22 180 DNT 07C 0.25 37 25 3.29 182 DNG 06C 39.8 37 27 2.62 83 MBM 06H 28.87 37 29 2.05 88 MBM 03H 24.88 37 31 2.21 70 MBM 05C 26.56 37 31 3.55 87 MBM 02C 35.4 37 35 2.95 83 MBM 01C 27.71 37 39 2.86 182 DNT 07H 0.49 37 44 0.77 70 DFS 01H 8.29 37 44 3.23 79 MBM 03C 3.43 37 46 5.71 183 DNG 01H 15.22 37 47 3.36 183 DNG 01H 15.85 37 48 2.48 175 DNG 01C 21.18 37 49 2.35 181 DNT 07H 0.54 37 50 3.76 184 DNG 06C 35.86 37 50 2.16 185 DNG 06C 34.76 37 50 2.96 81 MBM 06C 26.09 37 55 3.18 180 DNT 07C 0.42 37 55 4.37 181 DNT 07H 0.64 37 58 2.36 77 MBM TSC 4.72 37 61 3.35 184 DNG 06H 36.04 37 62 2.27 78 MBM 02C 20.62 37 63 2.76 81 MBM 01H 13.25 37 63 2.93 81 MBM 01H 16.45 37 63 2.14 64 MBM 04C 1.62 Page 50 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 37 65 2.32 85 MBM FBC 8.3 37 72 2.25 184 DNG 06H 33.33 37 72 5.24 184 DNG 06C 37.69 37 72 2.25 184 DNG 06C 36.5 37 72 2.27 87 MBM 06H 33.87 37 75 4.41 84 MBM 03H 8.86 37 77 4.45 180 DNT 07H 0.5 37 81 2.48 188 DNG TSC 4.43 37 83 0.35 12 PID TSH 0.06 37 83 0 0 TWD 0 TSH 0.04 37 83 0.25 11 TWD 28 TSH 0.07 37 83 0.36 12 TWD 31 TSH 0.09 37 83 0.23 11 TWD 28 TSH 0.11 37 83 0 0 TWD 0 TSH 0.14 37 83 0.3 11 SAI TSH 0.06 37 84 2.04 85 MBM 02C 14.16 37 87 5.23 185 DNG 06H 37.48 37 87 9.46 183 DNG 06H 38.69 37 87 2.43 180 DNT 07H -0.48 37 87 2.13 178 DNT 07H 0.5 37 87 4.74 183 DNG 06C 38.15 37 87 3.13 82 MBM 07H 1.7 37 92 5.37 89 MBM AV2 4.04 37 93 3.59 60 MBM 06C -0.91 37 95 9.88 85 MBM 06H 29.59 37 96 1.89 191 INF AV4 67.25 37 96 3.18 70 DFS AV6 9.7 37 98 7.68 88 MBM 06H 20.16 37 100 3.4 84 MBM 01H 24.79 37 100 5.59 84 MBM 03H 23.16 37 103 12.37 69 MBM 03C 3.09 37 106 2.02 183 DNT 07C 0.32 37 106 7.11 89 MBM 03H 14.25 37 106 2.3 184 DNG 06C 39.92 37 108 2.44 182 DNT 07C -0.73 37 108 4.14 181 DNT 07C 0.32 37 108 6.01 68 MBM AV6 13.05 38 16 2.46 187 DNG 07H 6.87 38 16 2.54 185 DNG 07H 8.12 38 26 3.15 181 DNT 07C 0.33 38 28 2.02 78 MBM 04C 15.35 38 34 0.78 78 DFS 02C 23.22 38 36 2.29 187 DNG 03H 24.01 38 37 0.25 0 TWD 13 AV4 -0.02 38 37 0.22 0 TWD 11 AV2 -0.17 38 37 2.16 57 MBM 02H 32.35 38 43 3.42 87 MBM TSH 6.09 38 43 3.01 89 MBM TSH 13.35 38 51 1.36 89 DFS 03C 6.37 38 55 2.11 184 DNG 03C 13.01 38 58 1.3 107 DFS 02C 28.03 38 69 4 184 DNG 01C 2.85 Page 51 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 38 72 2.91 62 MBM 02C 7.72 38 72 4.9 77 MBM 02C 10.86 38 74 6.21 182 DNT 07C 0.33 38 74 0.57 94 DFS 01H 3.85 38 75 2.14 186 DNG 06C 18.67 38 77 3.5 76 MBM TSC 16.86 38 78 7.97 179 DNT 07C 0.37 38 78 2.09 181 DNT 07C -0.73 38 80 2.11 184 DNT 02C 0.84 38 80 2.48 182 DNG 07H 7.76 38 80 6.26 88 MBM 02H 17.1 38 83 0.85 94 MBM TSH 2.14 38 83 2.19 187 DNG 04C 6.3 38 83 7.77 77 MBM TSH 2.07 38 83 3.03 86 MBM FBH 8.21 38 84 5.44 84 MBM 02C 34.93 38 87 3.87 181 DNG 06H 37.2 38 87 2.71 180 DNG 06H 37.54 38 87 2.9 74 MBM 02C 30.48 38 87 0.67 90 MBM 03C -10 38 88 0 0 TWD 0 TSH -0.02 38 88 0.18 23 TWD 67 TSH 0 38 88 0.51 15 TWD 40 TSH 0.03 38 88 0.62 17 TWD 47 TSH 0.05 38 88 0.25 17 TWD 47 TSH 0.08 38 88 0.18 10 TWD 26 TSH 0.1 38 88 0 0 TWD 0 TSH 0.12 38 88 0.65 16 PID TSH 0.05 38 88 0.36 15 SAI TSH 0.05 38 92 2.91 61 MBM 05H 14.89 38 93 2.93 86 MBM 06C 31.31 38 103 3.41 83 MBM 01H 27.53 38 103 3.38 83 MBM 01H 29.32 38 106 3.73 180 DNT 07C 0.35 38 107 2.19 179 DNT 07C 0.3 38 107 2.12 72 MBM 02C 24.94 38 108 3.37 179 DNT 07C 0.3 38 108 2.11 180 DNG 06C 39.89 39 17 2.83 74 MBM FBC 15.99 39 18 0.85 76 TWD 29 AV3 0.11 39 18 0.41 67 TWD 19 AV4 -0.19 39 18 0.28 55 TWD 14 AV6 -0.03 39 20 1.13 101 MBM TSH 1.23 39 20 2.85 86 MBM 05C 19.22 39 21 4.64 181 DNG 06H 39.04 39 22 0.22 0 TWD 11 AV5 0 39 24 3.83 177 DNT 07H -0.05 39 24 6.06 180 DNG 06C 39.05 39 24 3.07 181 DNG 06C 37.97 39 24 2.17 179 DNT 07H 0.5 39 24 2.15 182 DNT AV6 -0.38 39 25 2.66 178 DNT 07H 0.45 Page 52 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 39 25 2.22 82 MBM 03C 6.31 39 25 2.28 79 MBM 03C 7.67 39 25 2.95 76 MBM 03C 15.68 39 25 6.23 75 MBM 03C 10 39 25 2.98 88 MBM 02C 39.11 39 25 2.24 91 DFS 01H 17.56 39 26 11.96 183 DNG 06H 39.45 39 26 3.46 184 DNG 06H 38.39 39 27 4.43 179 DNT 07H -0.63 39 27 3.13 180 DNT 07H -0.17 39 29 3.67 79 MBM 04C 23.93 39 29 3.09 71 DFS 03H 10.84 39 29 1.96 103 DFS 03H 6.77 39 30 0.21 0 TWD 11 AV4 -0.17 39 30 0.31 0 TWD 15 AV3 0 39 30 0.19 0 TWD 10 AV2 0 39 31 3.91 82 MBM 06C 11.67 39 34 0.63 0 TWD 24 AV3 -0.07 39 34 0.52 0 TWD 21 AV2 0.37 39 34 0.34 0 TWD 16 AV1 0.27 39 34 0.19 0 TWD 10 AV5 -0.24 39 34 0.3 0 TWD 14 AV6 0 39 34 1.04 0 TWD 32 AV4 0 39 35 3.2 83 MBM 02C 20.36 39 36 2.58 180 DNT 07H 0.1 39 37 1.82 0 TWD 42 AV5 0.15 39 37 1.63 0 TWD 40 AV4 0 39 37 0.6 0 TWD 24 AV2 -0.05 39 37 1.41 0 TWD 38 AV1 0.32 39 37 0.54 0 TWD 23 AV3 0 39 37 2.22 0 PID AV5 0 39 40 0.96 78 DFS 06C 33.43 39 40 2.23 72 MBM 05H 30 39 41 0.27 0 TWD 13 AV5 -0.12 39 41 2.05 0 TWD 42 AV4 -0.05 39 41 0.2 0 TWD 10 AV2 -0.05 39 41 0.39 0 TWD 17 AV3 0.1 39 41 2.08 0 PID AV4 -0.05 39 49 0.29 0 TWD 14 AV2 0.1 39 52 2.02 188 DNG 02H 24.63 39 55 3.78 181 DNT 07C 0.37 39 55 4.7 181 DNT 07H 0.54 39 55 2.42 182 DNG 06C 38.98 39 56 0.46 42 GEO TSH -0.06 39 61 1.06 23 PID TSH 0 39 61 0 0 TWD 0 TSH -0.15 39 61 0.17 25 TWD 74 TSH -0.13 39 61 0.51 32 TWD 100 TSH -0.1 39 61 0.56 28 TWD 85 TSH -0.08 39 61 0.93 22 TWD 63 TSH -0.05 39 61 0.36 26 TWD 77 TSH -0.03 39 61 0 0 TWD 0 TSH 0 Page 53 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %ATW LOCATION 39 61 0.47 17 SAI TSH 0 39 62 2.02 184 DNT 07C 0.6 39 65 3.5 183 DNG 06C 3 7.5 39 70 0.53 91 DFS 05H 1 5.16 39 73 3.8 74 MBM 02H 246.24 39 73 2.8 83 MBM 06C 19.5 39 75 3.26 81 MBM 03C 240.23 39 80 3.68 71 MBM 04C 2 4.82 39 80 2.07 81 MBM TSC 1!5.48 39 83 3.75 82 MBM 04H 2 3.04 39 83 0.47 19 PID TSH 0).04 39 83 0 0 TWD 0 TSH -().03 39 83 0.44 7 TWD 17 TSH 0 39 83 0.54 13 TWD 34 TSH 0).02 39 83 0.4 19 TWD 53 TSH 0).04 39 83 0.24 10 TWD 26 TSH 04.07 39 83 0 0 TWD 0 TSH 0).09 39 83 0.5 21 SAI TSH 04.04 39 84 0.27 0 TWD 9 AV5 0 39 84 0.39 0 TWD 16 AV4 0 39 84 0.4 0 TWD 16 AV3 0 39 84 0.41 0 TWD 17 AV2 0 39 84 0.25 0 TWD 7 AVl 0 39 84 0.63 53 TWD 27 AV6 0 39 84 2.1 89 MBM 03H 1 9.52 39 87 2.24 182 DNG 06H 218.62 39 87 4.89 182 DNG 06H 2!9.79 39 87 3.79 179 DNT 07H C4.53 39 88 0.18 55 TWD 85 TSH -,2.12 39 88 0 0 TWD 0 TSH -,2.11 39 88 0.79 39 PID TSH -11.98 39 88 0 0 TWD 0 TSH -,2.12 39 88 0.08 61 TWD 79 TSH -,2.12 39 88 0.34 41 TWD 96 TSH -,2.12 39 88 0.61 36 TWD 99 TSH -,?.12 39 88 0.7 36 TWD 99 TSH -,2.12 39 88 0.47 43 TWD 94 TSH -,2.12 39 88 0.69 33 SCI TSH -11.98 39 90 2.41 183 DNG 05C 3:2.08 39 90 0 0 TWD 0 TSH -().03 39 90 0.2 19 TWD 53 TSH 0 39 90 0.52 16 TWD 43 TSH 04.02 39 90 0.66 18 TWD 50 TSH C4.05 39 90 0.53 24 TWD 70 TSH C4.07 39 90 0.37 8 TWD 20 TSH 0.1 39 90 0 0 TWD 0 TSH C4.12 39 90 0.64 18 PID TSH C4.02 39 90 0.62 20 SAI TSH 04.02 39 92 0.38 0 TWD 18 AV4 0 39 92 3.36 85 MBM 04H 1 5.57 39 92 0 0 TWD 0 TSH C4.09 39 92 0.22 44 TWD 93 TSH C4.09 Page 54 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 39 92 0.32 39 TWD 97 TSH 0.09 39 92 0.41 30 TWD 89 TSH 0.09 39 92 0.52 27 TWD 81 TSH 0.09 39 92 0.52 26 TWD 78 TSH 0.09 39 92 0.47 24 TWD 73 TSH 0.09 39 92 0.49 21 TWD 65 TSH 0.09 39 92 0.4 20 TWD 62 TSH 0.09 39 92 0.27 17 TWD 53 TSH 0.09 39 92 0 0 TWD 0 TSH 0.09 39 92 0.58 21 PID TSH 0.13 39 92 0.5 20 SCI TSH 0.13 39 95 2.26 86 MBM 01H 10.26 39 98 3.43 88 MBM 03H 22.19 39 98 5.07 67 MBM AV3 8.99 39 99 4.1 187 DNG 02H 25.29 39 99 0.23 0 TWD 11 AV2 0.12 39 100 0.19 0 TWD 10 AV6 0 39 100 0.56 0 TWD 23 AV5 0.42 39 100 0.63 0 TWD 25 AV3 0.44 39 104 0.3 134 GEO TSH -0.04 39 105 16.99 182 DNG 06C 36.61 39 105 8.18 184 DNG 06C 35.99 39 105 3.49 185 DNG 06C 35.42 39 105 8.4 183 DNG 06C 34.6 39 105 4.47 185 DNG 06C 33.58 40 18 3.18 78 MBM 03C 20.74 40 20 2.09 75 MBM 01C 13.6 40 23 4.68 86 MBM 02H 19.15 40 27 3.42 182 DNT 07C 0.29 40 30 4.26 87 MBM 02H 36.34 40 32 2.2 184 DNG 06H 17.84 40 32 4.74 77 MBM TSC 6.7 40 32 1.15 108 DFS TSC 7.6 40 32 3.66 92 MBM 02H 33.29 40 35 1.29 101 DFS 01C 34.49 40 35 1.18 93 DFS 01C 35.96 40 36 2.45 179 DNT 07C 0 40 43 0.99 107 DFS 02C 17.9 40 44 3.51 182 DNT 07C 0.32 40 44 2.2 81 MBM 01H 8.62 40 45 3.53 88 MBM 03H 20.54 40 46 4.54 84 MBM 04H 7.33 40 47 2.77 69 MBM 03H 29.46 40 48 3.1 65 MBM FBC 10.13 40 49 2.92 75 MBM FBH 16.8 40 49 2.43 77 MBM 01H 24.39 40 49 1.93 75 MBM 01H 27.7 40 49 4.85 74 MBM 03C 2.3 40 52 2.8 75 MBM 01H 13.28 40 52 2.78 76 MBM 01H 14.87 40 52 2.27 103 DFS TSC 12.13 40 57 0.94 89 DFS FBC 17.55 Page 55 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 40 58 3.46 88 MBM 02H 25.67 40 60 4.05 80 MBM TSC 19.1 40 62 5.09 90 MBM 06H 28.12 40 63 5.51 82 MBM 05C 23.03.

40 63 2.21 56 MBM 05C 24.3 40 66 2.72 132 DDS AV6 22.05 40 66 8.46 79 MBM 02H 39.03 40 69 2.88 66 MBM 04C 29.08 40 71 0.19 0 TWD 10 AV4 -0.13 40 71 0.24 0 TWD 12 AV3 0 40 71 0.18 0 TWD 9 AV2 0 40 73 0.12 0 TWD 7 AV1 0.25 40 73 2.45 87 MBM 01H 5.22 40 75 2.2 104 DFS FBH 6.16 40 76 0.12 0 TWD 6 AV6 -0.08 40 76 0.4 0 TWD 18 AV3 -0.05 40 76 0.15 0 TWD 8 AV2 0 40 76 2.34 87 MBM TSH 15.67 40 76 2.4 80 MBM FBH 4.41 40 76 2.25 79 MBM 03H 29.12 40 77 2.24 70 MBM 04H 10.11 40 81 2.35 76 MBM 02C 15.94 40 81 2.98 83 MBM 02C 14.32 40 81 2.68 77 MBM 02C 12.53 40 81 3.55 82 MBM 02C 10 40 83 3.24 73 MBM 01H 21.37 40 83 2.52 78 MBM 06C 18.49 40 86 0.4 0 TWD 16 AVl 0.1 40 87 4.4 180 DNT 07H 0.58 40 87 2.14 182 DNT 07H -0.53 40 89 2.27 83 MBM O1C 37.17 40 89 4.42 109 DFS 01C 23.54 40 89 2.56 85 MBM 01C 28.8 40 89 5.38 81 MBM 01C 34.76 40 96 5.14 68 MBM AV6 8.29 40 96 4.96 88 MBM AV6 12.17 40 96 4.61 78 MBM AV6 14 40 96 6.74 82 MBM 02C 9.02 40 96 7.73 77 MBM 02C 7.64 40 101 1.64 109 MBM 05H 7.69 40 101 5.25 187 DNG 05H 7.69 40 103 2.76 183 DNG 06C 39.01 40 105 2.26 184 DNT 07C 0.27 40 106 2.11 181 DNT 07C 0.05 41 19 0.14 0 TWD 7 AV6 0 41 19 0.14 0 TWD 7 AV5 0 41 19 3.65 182 DNG 06H 32.03 41 20 0.26 31 TWD 14 AV4 0.05 41 20 0.16 71 TWD 9 AV5 -0.08 41 28 3.58 89 MBM 06H 4.52 41 29 0.2 91 TWD 11 AV5 0.1 41 30 2.57 180 DNG 07H 3.03 Page 56 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 41 31 2.88 179 DNG 07H 2.92 41 32 2.77 181 DNG 07H 2.96 41 34 2.92 179 DNG 07H 3.11 41 35 2.04 179 DNG 07H 3.01 41 36 3.52 186 DNG AV4 1.04 41 38 2.22 184 DNG 07H 2.87 41 40 3.1 186 DNG 02C 5.29 41 48 2.26 175 DNG 02C 1.7 41 50 2.48 185 DNG 04C 22.41 41 53 2.18 84 MBM 05H 21.53 41 54 1.13 30 PID TSH 0 41 54 1.33 28 SAI TSH 0 41 54 0.18 16 TWD 43 TSH 0.04 41 54 0 0 TWD 0 TSH 0.07 41 54 0 0 TWD 0 TSH -0.1 41 54 0.18 21 TWD 60 TSH -0.08 41 54 0.89 23 TWD 67 TSH -0.05 41 54 1.15 24 TWD 70 TSH -0.03 41 54 1.15 30 TWD 92 TSH 0 41 54 0.78 31 TWD 96 TSH 0.02 41 54 2.61 74 MBM 06C 25.11 41 54 2.19 74 MBM 06C 23.67 41 54 3.29 80 MBM 06C 22.26 41 54 3.61 65 MBM 06C 20.84 41 58 2.55 83 MBM 02H 26.54 41 61 0.58 0 TWD 24 AV3 0 41 61 0.8 0 TWD 29 AV4 0 41 61 0.36 0 TWD 17 AV2 0 41 66 2.47 78 MBM 06C 7.09 41 67 2.02 79 MBM 04C 22.69 41 67 2.45 80 MBM 03C 38.74 41 67 3.45 79 MBM 03C 35.95 41 69 2.1 184 DNG FBC 15.68 41 69 2.01 74 MBM 02C 27.94 41 69 3.36 88 MBM 05C 26.11 41 71 2.5 73 MBM 02C 37.71 41 72 2.62 187 DNG 06H 34.86 41 74 2.5 184 DNG 03C 13.05 41 80 2.46 76 MBM 06H 11.11 41 82 PID TSH 0.06 41 82 0 0 TWD 0 TSH 0 41 82 0.18 24 TWD 70 TSH 0.02 41 82 0.44 19 TWD 53 TSH 0.05 41 82 0.37 20 TWD 56 TSH 0.07 41 82 0.14 22 TWD 63 TSH 0.1 41 82 0 0 TWD 0 TSH 0.12 41 82 0.47 17 SAI TSH 0.06 41 82 3.15 184 DNT 02C 0.12 41 83 5.11 185 DNG 05C 37.64 41 84 2.01 109 DFS TSH 8.91 41 86 0.29 0 TWD 10 AV5 0 41 86 0.85 0 TWD 30 AV4 0 Page 57 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 41 95 0 0 TWD 0 TSH -0.01 41 95 0.33 19 TWD 53 TSH 0.01 41 95 0.68 17 TWD 47 TSH 0.04 41 95 0.69 15 TWD 40 TSH 0.06 41 95 0.4 19 TWD 53 TSH 0.09 41 95 0 0 TWD 0 TSH 0.11 41 95 0.51 18 PID TSH 0.03 41 95 0.61 21 MAI TSH 0.03 41 98 0.2 0 TWD 11 AV5 0 41 98 0.22 0 TWD 12 AV4 0 41 103 4 179 DNT 07C 0.3 41 103 6.94 79 MBM 01H 14.18 41 103 3.58 82 MBM 06C 37.43 41 103 2.63 72 MBM 06C 36.26 41 103 2.35 75 MBM 06C 35.24 41 103 8.38 83 MBM 06C 27.03 41 103 5.18 86 MBM 06C 24.07 41 103 3.65 82 MBM 06C 12.16 41 103 3.42 86 MBM 06C 10.49 41 103 3.43 89 MBM 06C 6.76 41 104 3.75 180 DNT 07C 0.28 41 104 9.45 81 MBM 06H 35.91 41 104 2.8 76 MBM 06H 39.11 41 104 4.29 81 MBM 02C 32.88 41 104 6.78 82 MBM 02C 31.2 41 105 4.85 180 DNT 07C 0.27 42 21 5.51 77 MBM TSC 8.37 42 23 0.14 0 TWD 8 AV4 0 42 25 2.64 102 MBM AV2 7.91 42 25 5.5 78 MBM AV2 11.39 42 25 4.32 181 DNT AV4 -0.4 42 25 3.09 179 DNT 07H 0.5 42 25 3.52 84 MBM 03C 36.78 42 25 2.12 104 DFS AV6 4.28 42 26 4.12 186 DNG 03H 14.23 42 26 2.46 187 DNG 02C 25.62 42 26 7.08 81 MBM 02C 26 42 26 10.13 89 MBM 03H 14.12 42 26 1.01 116 MBM 03H 14.27 42 27 3.8 183 DNG 03H 26.21 42 31 4.5 82 MBM FBC 1.39 42 34 3.84 187 DNG FBH 13.49 42 39 2 116 DFS 02C 22.34 42 40 0.44 0 TWD 73 AV3 0 42 40 0.61 0 TWD 23 AV4 0.07 42 40 0.22 0 TWD 11 AV5 -0.19 42 40 2.15 184 DNT 07C 0.29 42 40 0.35 0 TWD 16 AV2 -0.02 42 44 2.84 82 MBM 06H 32.67 42 44 2.35 87 MBM 03C 31.59 42 44 2.53 72 MBM 06H 33.65 42 45 2.54 88 MBM 04H 30.93 Page 58 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 42 45 2.45 74 MBM 01C 7.83 42 46 0.28 0 TWD 13 AV2 0 42 46 0.91 0 TWD 21 AV3 0 42 46 0.28 0 TWD 13 AV4 0 42 48 2.6 179 DNT 07H 0.59 42 53 0.07 58 GEO TSH 0 42 53 2.23 181 DNG 05H 26.36 42 54 4.05 68 MBM AV5 6.3 42 54 2.5 82 MBM AV4 16.29 42 59 1.75 108 DFS AV3 3.78 42 62 0.2 16 PID TSH -0.62 42 62 0.36 15 TWD 47 TSH -0.16 42 62 0 0 TWD 0 TSH -0.16 42 62 0 0 TWD 0 TSH -0.16 42 62 0.4 20 TWD 62 TSH -0.16 42 62 0.46 19 TWD 59 TSH -0.16 42 62 0.53 16 TWD 50 TSH -0.16 42 62 0.46 17 TWD 53 TSH -0.16 42 62 0.14 24 SCl TSH -0.62 42 63 2.16 187 DNG 04C 19.02 42 64 2.28 84 MBM 01H 22.69 42 67 7.09 78 MBM 03C 15.05 42 68 7.79 86 MBM 06H 10.28 42 68 2.33 89 MBM 06H 13.49 42 71 2.15 82 MBM 06C 30.36 42 76 2.4 75 MBM 01C 24.91 42 76 7.92 68 MBM FBC 17.3 42 77 3.33 183 DNG 06C 39.66 42 77 2.83 77 MBM 05C 17.84 42 77 2.33 80 MBM 03C 12.5 42 78 2.76 183 DNG 03C 16.42 42 78 2.66 88 MBM 05H 34.33 42 82 0.68 0 TWD 26 AV4 0.24 42 82 0.4 0 TWD 16 AV3 0.2 42 82 0.23 0 TWD 8 AV6 -0.29 42 83 1.08 109 DFS 02C 20.84 42 88 5.05 85 MBM 01H 1.83 42 88 0.26 0 TWD 10 AV4 -0.02 42 93 2.49 183 DNT 01C 0.39 42 94 0.41 0 TWD 18 AV3 0 42 94 0.14 0 TWD 8 AV2 -0.1 42 94 0.25 0 TWD 12 AV1 -0.35 42 94 0.52 0 TWD 21 AV5 -0.12 42 97 0.18 0 TWD 10 AV6 0 42 97 0.53 0 TWD 22 AV5 0 42 97 0.27 0 TWD 13 AV4 0 42 97 0.33 0 TWD 16 AV2 0 42 98 4.5 75 MBM 03C 9.82 42 100 5.87 77 MBM 03C 24.23 42 100 2.99 87 MBM 03C 20.54 42 101 3.36 77 MBM TSH 8.53 42 103 0.33 0 TWD 16 AV6 0 Page 59 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 42 103 0.38 0 TWD 17 AV5 0 42 103 0.24 0 TWD 12 AV4 0 43 25 2.71 187 DNG 01H 3 5.07 43 27 0.46 88 TWD 20 AV2 C).15 43 27 0.49 72 TWD 21 AV3 -(0.03 43 27 0.25 64 TWD 13 AV4 C).03 43 27 0.21 142 TWD 11 AV5 -0.1 43 27 0.11 125 TWD 6 AV1 -(0.05 43 27 0.15 82 TWD 9 AV6 -E0.03 43 28 3.06 79 MBM 02C 1 3.95 43 34 0.38 37 GEO TSH 0 43 34 4.05 182 DNG TSH ,.58 43 34 3.52 84 MBM 05C 2 4.16 43 34 2.42 81 MBM 05C 2 2.51 43 36 0.34 94 PID TSH C).03 43 36 0.35 87 TWD 11 TSH C).05 43 36 0.72 121 SVI TSH ).03 43 37 2.61 180 DNT 07C ).36 43 44 3.62 77 MBM 03C 3 8.99 43 44 2.44 100 DFS 04C 4.4 43 48 2.86 181 DNT 07H C).56 43 57 3.1 83 MBM FBH 10.51 43 59 2.08 82 MBM 07H 19.45 43 60 4.78 82 MBM 03H 3 6.56 3.21 86 MBM TSH 7.93 43 61 43 65 2.12 87 MBM 01H 2 9.39 43 70 0.25 0 TWD 13 AV3 0 43 78 1.05 58 DFS 01C 18.31 43 82 5.71 185 DNG AV5 I9.95 43 83 2.72 182 DNG 06C 3 5.89 43 83 5.66 184 DNG 05C 4.88 43 83 4.38 179 DNT 07C ).39 43 83 2.23 182 DNT 07H ).66 43 83 2.32 184 DNT 06C -' 0.29 43 83 5.43 89 MBM TSH 1 1.18 43 83 4.22 86 MBM 06C 24.6 43 83 3.32 79 MBM 03C 12.74 43 83 3.02 89 MBM AV5 15.4 43 90 2.33 80 MBM 06C 18.44 43 90 2.09 77 MBM 06C 15.09 43 90 4.53 88 MBM 020 3.62 43 90 3.1 76 MBM 02C 3.96 43 90 2.42 89 MBM TSC ).71 43 90 4.78 56 MBM AV4 1.15 43 91 6.94 81 MBM FBH  ?.78 43 91 4.13 80 MBM 01H  ?.39 43 93 4.55 78 MBM 03C ?1.6 43 94 4.18 185 DNG TSH 1 7.35 43 95 2.42 82 MBM TSH ).88 43 99 2.44 179 DNT 07C 0.3 43 100 3.68 180 DNT 07C 0.74 43 100 3.86 180 DNT 07C ).32 Page 60 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 43 101 2.97 178 DNT 07C 0.32 43 102 2.75 180 DNT 07C -0.74 43 102 5.3 179 DNT 07C 0.29 43 102 2.01 77 MBM 02C 29.31 43 103 2.62 179 DNT 04C -0.34 43 103 2.34 178 DNT 04C 0.64 43 103 2.18 178 DNT 07C -0.77 43 103 4.56 180 DNT 07C 0.32 43 103 3.08 83 MBM 05H 32.25 43 103 4.03 63 MBM 06C 1.14 44 21 2.84 182 DNG 06C 14.2 44 21 0.8 86 DFS 02H 30.77 44 22 2.1 81 MBM 06H 5.45 44 23 2.13 182 DNT 07C -0.75 44 23 7.16 181 DNT 07C 0.32 44 23 4.82 179 DNT 07H 0.43 44 24 2.61 186 DNG FBH 14.17 44 25 2.75 51 MBM AV4 1.97 44 26 8.73 90 MBM 03H 7.62 44 26 3.73 80 MBM 05C 2.85 44 27 4.05 176 DNT 07C 0.25 44 33 8.42 181 DNG AV5 8.87 44 35 0.63 100 PID TSH 0.09 44 35 0.66 92 SVI TSH 0.09 44 35 0.82 94 TWD 28 TSH 0.04 44 36 0.21 98 PID TSH 0.13 44 36 0.24 83 SVI TSH 0.13 44 36 0.23 93 TWD 10 TSH 0.12 44 39 7.16 182 DNG TSH 5.36 44 39 8.78 185 DNG AV6 25.93 44 42 2.84 89 MBM 04H 36.06 44 43 0.21 112 GEO TSH 0 44 43 3.36 81 MBM 06H 27.15 44 45 3.45 86 MBM 03H 4.28 44 46 5.12 88 MBM 03H 18.83 44 47 4.29 81 MBM 02C 7.87 44 51 13.6 71 MBM 07H 7.25 44 51 4.84 75 MBM 07H 5.16 44 56 6.3 79 MBM 02C 5.23 44 56 6.27 83 MBM 01C 38.51 44 59 0.54 19 PID TSH 0.05 44 59 0.48 25 SAl TSH 0.05 44 59 0 0 TWD 0 TSH -0.03 44 59 0.35 14 TWD 37 TSH -0.01 44 59 0.48 10 TWD 26 TSH 0.02 44 59 0.57 20 TWD 56 TSH 0.05 44 59 0.64 17 TWD 47 TSH 0.07 44 59 0.27 10 TWD 26 TSH 0.1 44 59 0 0 TWD 0 TSH 0.12 44 60 2.68 110 DFS 05C 6.26 44 62 0.25 24 PID TSH -0.67 44 62 0 0 TWD 0 TSH -0.82 Page 61 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 44 62 0.2 12 TWD 38 TSH -0.82 44 62 0.18 9 TWD 29 TSH -0.82 44 62 0.14 7 TWD 23 TSH -0.82 44 62 0.12 5 TWD 17 TSH -0.82 44 62 0 0 TWD 0 TSH -0.82 44 62 0.24 19 SCI TSH -0.67 44 64 2.74 103 DFS AV3 12.59 44 64 2.35 84 MBM 04C 16.96 44 65 3.12 78 MBM TSH 8.46 44 65 1.88 110 DFS 04C 6.03 44 65 1.43 106 DFS TSC 11.57 44 66 2.07 78 MBM FBC 17.23 44 67 0.07 85 GEO TSH -0.07 44 68 5.51 87 DFS 07H 22.6 44 69 2.89 190 DNG TSC 7.79 44 71 2.28 182 DNG 06C 39.45 44 72 0.19 108 GEO TSH 0 44 73 2.55 78 MBM 05C 33.9 44 74 3.91 78 MBM 03C 37.64 44 75 0.27 14 SCI TSH 0.09 44 75 0.31 15 PID TSH 0.09 44 75 0 0 TWD 0 TSH 0.07 44 75 0.15 42 "TWD 95 TSH 0.07 44 75 0.29 27 TWD 81 TSH 0.07 44 75 0.32 22 TWD 67 TSH 0.07 44 75 0.3 25 TWD 76 TSH 0.07 44 75 0.22 31 TWD 92 TSH 0.07 44 75 0 0 TWD 0 TSH 0.07 44 78 2.38 177 DNT 07C 0.32 44 79 2.6 89 MBM 02H 20.81 44 80 3.02 80 MBM FBH 11.28 44 81 0.29 11 SCI TSH 0.1 44 81 0.29 14 PID TSH 0.1 44 81 0 0 TWD 0 TSH 0.09 44 81 0.34 17 TWD 53 TSH 0.09 44 81 0.46 12 TWD 38 TSH 0.09 44 81 0.44 12 TWD 38 TSH 0.09 44 81 0.26 14 TWD 44 TSH 0.09 44 81 0.16 11 TWD 35 TSH 0.09 44 81 0 0 TWD 0 TSH 0.09 44 82 3.28 89 MBM 02H 26.9 44 84 3.49 80 MBM 01H 22.19 44 84 3.13 88 MBM 04C 28.08 44 84 4.46 87 MBM 04C 18.34 44 85 4.1 85 MBM 02H 26.45 44 87 3.93 75 MBM AV4 11.25 44 87 3.35 88 MBM AV4 13.01 44 92 5.71 74 MBM 04C -1.16 44 95 3.87 82 MBM 01H 8.9 44 95 4.43 72 MBM 02C 21.34 44 95 3.62 83 MBM 01C 32.55 44 97 2.91 181 DNT 07C 0.34 Page 62 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 44 97 4.87 82 MBM 03C 23.76 44 98 4.29 181 DNT 07C -0.72 44 98 2.37 180 DNT 07C 0.35 44 98 4.75 182 DNG 06C 26.69 44 99 3.25 182 DNT 07C -0.73 44 99 4.24 182 DNT 07C 0.32 44 100 5.94 182 DNT 07C -0.73 44 100 2.41 182 DNT 07C 0.32 44 100 3.64 88 MBM 01H 10.31 44 100 3.94 78 MBM 01H 12.11 44 100 4.01 89 MBM 01H 15.94 44 101 5.12 179 DNT 07C 0.32 44 101 6.37 182 DNT 07C -0.69 44 101 3.65 86 MBM 03H 30.63 44 101 2.3 88 MBM 05C 30.49 44 101 3 86 MBM 01C 26.36 44 102 2.21 181 DNT 04H 0.78 44 102 2.11 179 DNT 04C 0.64 44 102 6.15 181 DNT 07C -0.75 44 102 5.3 180 DNT 07C 0.34 44 102 7.25 71 MBM 06H 10.86 45 23 3.73 182 DNT 07C 0.35 45 23 2.81 180 DNT 07H 0.3 45 24 3.09 182 DNG 04C 36 45 33 3.29 190 DNG AV1 3.03 45 33 2.22 179 DNT 07C 0.46 45 33 5.36 84 MBM 06C 27.14 45 35 2.48 178 DNG 06H 23.96 45 35 2.74 179 DNG 06H 30.42 45 35 2.51 174 DNT 07C 0.39 45 38 2.42 186 DNG 02H 0.79 45 39 3.12 182 DNG 06C 37.76 45 44 3.33 73 MBM FBC 10.23 45 45 0.16 22 GEO TSH -0.08 45 48 3.51 181 DNT 07C 0.42 45 50 2.17 70 MBM 04C 36.45 45 50 0.83 105 DFS 01C 29.61 45 52 8.76 85 MBM AV4 1.31 45 55 0.07 45 GEO TSH 0 45 55 2.52 73 MBM TSH 4.99 45 55 2.4 75 MBM TSH 15.65 45 56 2.33 87 MBM 02C 10.92 45 57 6.53 89 MBM 03H 34.05 45 57 5.84 87 MBM 03H 38.88 45 64 3.9 71 MBM 03H 25.13 45 70 2.6 81 MBM 02C 22.61 45 71 2.59 181 DNT 07H 0.56 45 71 2.2 185 DNG 06C 38.42 45 71 4.87 185 DNG 06C 39.55 45 74 2.39 84 MBM 04H 36.93 45 76 1.19 72 DFS 02H 1.91 45 77 3.3 89 MBM 05C 35.81 Page 63 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 45 78 3.83 178 DNT 07C 0.38 45 79 2.98 84 MBM TSH 10.2 45 79 2.03 85 MBM 06H 3.68 45 80 2.01 183 DNG 02H 23.12 45 82 5.29 178 DNT 02C -0.17 45 85 0.99 73 DFS 02C 21.09 45 85 2.04 67 MBM FBC 4.94 45 87 2.91 181 DNT 07C 0.39 45 87 2.21 184 DNG 05C 35.22 45 90 2.83 88 MBM 02H 30.6 45 90 3.24 80 MBM 02H 33.24 45 90 4.29 90 MBM 03H 13.33 45 91 9.67 75 MBM 03H 31.94 45 93 4.88 89 MBM 02H 1.65 45 93 2.44 73 MBM 04C 11.53 45 93 2.02 82 MBM 04C 9.93 45 93 2.01 75 MBM 04C 2.88 45 94 2.1 181 DNT 07C -0.37 45 94 3.83 181 DNT 07C 0.29 45 94 4.76 181 DNT 07C 0.63 45 94 7.76 180 DNT 07H 0.51 45 94 5.04 180 DNT 07H -0.59 45 94 8.73 84 MBM 06C 10.4 45 95 0.82 49 DFS AV6 7.94 45 96 3.8 81 MBM FBC 9.4 45 96 2.24 74 MBM FBC 5.16 45 98 2.18 184 DNT 07C -0.78 45 98 2.88 182 DNT 07C 0.29 45 99 3.27 180 DNT 07C 0.3 45 99 2.09 178 DNT 07C -0.74 45 100 7.7 180 DNT 07C -0.72 45 100 4.2 181 DNT 07C 0.27 45 101 2.91 182 DNT 07C -0.77 45 101 5.55 180 DNT 07C 0.3 46 24 2.15 178 DNT 07C 0.35 46 29 0.52 97 TWD 22 AV4 -0.15 46 29 0.35 110 TWD 17 AV5 0 46 42 2.87 185 DNG TSC 2.49 46 45 2.44 84 MBM 05C 32.71 46 45 2.14 84 MBM 05C 13.98 46 45 2.21 77 MBM 01C 21.08 46 45 2.01 86 MBM 01C 16.73 46 45 3.11 80 MBM 01C 11.71 46 45 3.08 82 MBM 01C 9.73 46 45 2.33 72 MBM 01C 8.82 46 45 4.04 77 MBM FBC 17.82 46 45 2.45 69 MBM FBC 12.18 46 48 0.5 0 TWD 21 AV1 0 46 48 2.43 0 TWD 47 AV2 0 46 48 1.78 0 TWD 47 AV3 0 46 48 2.05 0 TWD 44 AV4 0 46 48 0.97 0 "TWD 32 AV5 0 Page 64 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 46 48 0.2 0 TWD 8 AV6 0 46 48 5.37 0 PID AV4 0 46 49 1.06 102 MBM 03C -1.37 46 49 0.63 140 MBM 04C 6.76 46 49 2.07 77 ADS 04C 7.14 46 49 2.53 118 DFS 02C 38.65 46 50 1.04 32 MAI TSH 0 46 50 1.08 35 PID TSH 0 46 50 0 0 TWD 0 TSH -0.02 46 50 0.13 25 TWD 74 TSH 0 46 50 0.44 32 TWD 100 TSH 0.02 46 50 0.86 35 "TWD 99 TSH 0.05 46 50 1.1 35 "TWD 99 TSH 0.07 46 50 0.79 33 TWD 100 TSH 0.1 46 50 0.38 27 TWD 81 TSH 0.12 46 50 0.38 26 TWD 77 TSH 0.15 46 50 0 0 TWD 0 TSH 0.17 46 50 0 0 TWD 0 TSH -0.04 46 50 0.08 16 TWD 43 TSH -0.02 46 50 0.44 24 TWD 70 TSH 0.01 46 50 0.81 24 TWD 70 TSH 0.03 46 50 0.87 24 TWD 70 TSH 0.06 46 50 0.53 27 TWD 81 TSH 0.08 46 50 0.21 5 TWD 12 TSH 0.11 46 50 0 0 TWD 0 TSH 0.13 46 53 1.17 78 DFS 05H 21.91 46 57 2.68 82 MBM 02C 15.41 46 58 2.04 89 MBM 04H 30.09 46 58 3.77 87 MBM 04H 34.94 46 58 2.04 67 MBM 05H 10.48 46 61 1.86 37 PID TSH -0.75 46 61 0 0 TWD 0 TSH -0.72 46 61 0.43 40 TWD 96 TSH -0.72 46 61 0.78 27 TWD 81 TSH -0.72 46 61 0.86 27 TWD 81 TSH -0.72 46 61 0.8 29 TWD 87 TSH -0.71 46 61 0.53 34 TWD 100 TSH -0.71 46 61 0.34 29 TWD 87 TSH -0.71 46 61 0.26 31 TWD 92 TSH -0.71 46 61 0.22 33 TWD 97 TSH -0.71 46 61 0 0 TWD 0 TSH -0.71 46 61 0 0 TWD 0 TSH -0.81 46 61 0.27 38 TWD 97 TSH -0.78 46 61 0.61 41 TWD 96 TSH -0.76 46 61 1.54 36 TWD 98 TSH -0.73 46 61 1.86 37 TWD 98 TSH -0.71 46 61 1.37 41 TWD 96 TSH -0.68 46 61 0.65 43 "TWD 95 TSH -0.66 46 61 0.38 31 TWD 96 TSH -0.63 46 61 0 0 TWD 0 TSH -0.61 46 61 0.54 42 MAI TSH -0.75 46 61 0.3 32 SCI TSH -0.74 Page 65 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 46 65 0.28 0 TWD 14 AV2 0.05 46 65 0.54 0 TWD 22 AV3 0.08 46 65 0.68 0 TWD 25 AV4 0.15 46 65 0.48 0 TWD 20 AV5 0.05 46 65 0.34 0 TWD 16 AV6 0.1 46 65 0.31 135 TWD 14 AV1 -0.28 46 66 2.34 83 DFS 01H 37.38 46 66 2.31 99 DFS 01H 38.43 46 66 2.28 89 DFS 02H 4.45 46 67 0.25 0 TWD 13 AV1 0 46 67 0.24 0 TWD 12 AV2 -0.1 46 67 1.11 0 TWD 33 AV4 -0.03 46 67 0.36 0 TWD 17 AV5 -0.1 46 68 2.41 183 DNG 03H 29.14 46 69 2.97 182 DNT 07H 0.1 46 71 0.37 0 TWD 17 AV3 0 46 71 0.75 0 TWD 27 AV4 0 46 71 0.22 0 TWD 12 AV1 0.53 46 71 0.3 0 TWD 15 AV6 -0.05 46 71 2.43 184 DNG 06C 37.78 46 71 3.98 183 DNT 07H 0.5 46 72 6.41 183 DNT 07C 0.33 46 72 2.8 185 DNG 07C -0.73 46 73 1.75 30 PID TSH 0.03 46 73 0 0 TWD 0 TSH -0.05 46 73 0.58 20 TWD 56 TSH -0.02 46 73 1.26 32 TWD 100 TSH 0.01 46 73 1.77 31 TWD 96 TSH 0.03 46 73 1.41 32 TWD 100 TSH 0.06 46 73 0.76 34 TWD 99 TSH 0.08 46 73 0.59 14 TWD 37 TSH 0.1 46 73 0 0 TWD 0 TSH 0.13 46 73 1.7 33 SAI TSH 0.03 46 74 2.75 181 DNT 07C 0.3 46 74 3.09 88 MBM 06H 22.89 46 75 5.84 181 DNT 07C 0.3 46 76 2.72 183 DNT 07C 0.25 46 76 2.24 80 MBM 06H 11.51 46 76 2.83 110 DFS 02C 24.43 46 77 3.66 182 DNT 07C 0.25 46 79 3.81 183 DNG 07H 21.48 46 80 2.7 181 DNG 07H 21.73 46 81 2.64 181 DNG 07H 21.45 46 81 0.62 101 DFS FBC 14.75 46 82 3.6 183 DNG 07H 21.15 46 82 3.32 75 MBM 06H 13.99 46 83 0.58 0 TWD 23 AV2 0 46 83 0.55 0 TWD 22 AV3 0 46 83 0.71 0 TWD 27 AV5 0 46 91 4.66 84 MBM 06H 7.96 46 91 5.05 84 MBM 06H 10.78 46 91 3.15 89 MBM 06H 12.85 Page 66 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 46 91 3.11 90 MBM 06H 16.34 46 91 5.72 87 MBM 06H 29.3 46 93 3.37 181 DNT 07C 0.34 46 93 5.78 89 MBM AV6 11.26 46 94 3.37 184 DNG 05H 28.97 46 94 2.25 183 DNG 05H 34.6 46 94 2.24 179 DNT 07C 0.32 46 98 2.44 181 DNT 04C -0.37 46 99 2.69 184 DNG 07H 13.27 46 99 3.12 183 DNG 07H 13.66 46 99 2.84 182 DNT 07C -0.76 47 24 5.04 179 DNT 07C 0.38 47 25 0.19 22 TWD 10 AV5 0.03 47 25 0.15 48 TWD 9 AV6 0 47 30 2.53 184 DNG 06C 32.13 47 31 2.12 181 DNT FBH 0.52 47 36 3.04 183 DNG 06H 36.79 47 36 3.04 183 DNG 06C 38.4 47 36 2.75 184 DNG 06C 35.73 47 37 3 181 DNT 07C 0.36 47 37 2.61 86 MBM FBC 14.19 47 38 0.92 0 TWD 32 AV5 0.07 47 38 0.29 0 TWD 13 AV4 0 47 38 0.76 0 TWD 28 AV2 0.17 47 38 0.29 0 TWD 14 AV1 -0.17 47 38 0.56 0 TWD 23 AV3 -0.27 47 39 0.98 101 DFS 05C 5.26 47 40 0.36 0 "TWD 17 AV1 0.15 47 40 0.26 0 TWD 13 AV2 0.34 47 40 0.26 0 TWD 13 AV3 0.05 47 44 0.26 0 TWD 12 AV2 -0.44 47 44 2.25 94 DFS AV1 1.9 47 44 3.19 73 MBM 07H 1.39 47 44 3.7 87 MBM 07H 2.46 47 44 7.95 65 MBM 07H 24.53 47 45 2.56 74 MBM TSC 2.94 47 49 1.44 25 PID TSH 0 47 49 0 0 TWD 0 TSH -0.09 47 49 0.47 25 TWD 74 TSH -0.06 47 49 0.54 19 TWD 53 TSH -0.03 47 49 0.54 22 TWD 63 TSH -0.01 47 49 0.9 25 TWD 74 TSH 0.02 47 49 1.34 25 TWD 74 TSH 0.04 47 49 0.51 26 TWD 77 TSH 0.07 47 49 0.35 24 TWD 70 TSH 0.1 47 49 0 0 TWD 0 TSH 0.12 47 49 1.31 25 SAI TSH 0 47 50 1.03 23 SAI TSH 0.01 47 50 1.13 21 PID TSH 0.01 47 50 0.76 75 DFS TSH 7.29 47 50 0 0 TWD 0 TSH -0.04 47 50 0.26 19 TWD 53 TSH -0.01 Page 67 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 47 50 0.78 20 TWD 56 TSH 0.01 47 50 1.15 21 TWD 60 TSH 0.04 47 50 1 21 TWD 60 TSH 0.06 47 50 0.51 21 TWD 60 TSH 0.09 47 50 0.24 14 TWD 37 TSH 0.11 47 50 0 0 TWD 0 TSH 0.14 47 54 2.4 85 MBM 05C 3.96 47 54 3.11 81 MBM 04C 15.95 47 55 0.16 0 TWD 9 AV6 0.17 47 55 0.35 TWD 17 AV1 -0.05 47 55 0.71 TWD 27 AV2 -0.17 47 55 0.51 TWD 22 AV3 -0.15 47 55 1.17 TWD 34 AV4 -0.39 47 55 0.46 72 TWD 20 AV5 -0.61 47 56 0.24 0 TWD 10 AV6 0 47 57 0.29 104 SVI FBH 0.07 47 57 0.15 0 TWD 8 AV6 0 47 57 0.29 0 TWD 14 AV5 -0.15 47 57 1.13 0 TWD 33 AV4 0 47 57 0.4 0 TWD 18 AV3 0.07 47 57 0.35 132 DSI FBH 0.14 47 57 0.17 75 PID FBH 0.07 47 57 0.21 0 TWD 10 FBH 0.08 47 58 2 81 MBM AV2 13.2 47 58 3.31 81 MBM 05C 11.14 47 59 0.3 0 TWD 15 AV6 0 47 59 0.84 0 TWD 28 AV5 -0.19 47 59 0.4 0 TWD 18 AV4 -0.05 47 59 0.92 0 TWD 30 AV3 0.24 47 59 0.16 0 TWD 9 AV2 -0.07 47 60 4.05 87 MBM 01H 33.43 47 61 8.21 78 MBM 02H 14.72 47 61 5 77 MBM 04C 14.82 47 61 0.72 99 MBM 04C 14.69 47 62 2.37 67 MBM TSH 5.75 47 66 0.64 86 DFS TSC 3.89 47 73 3.28 184 DNG AV6 6.15 47 73 3.25 183 DNG 06C 7.83 47 73 2.95 77 MBM 02C 37.47 47 77 3.33 178 DNT 07C 0 47 77 2.05 180 DNT 07C 0.3 47 77 3.33 180 DNT 07C -0.33 47 83 4.27 178 DNT 07C 0.33 47 86 3.06 77 MBM FBC 5.63 47 87 3.69 182 DNT 07C 0.36 47 89 2.35 84 MBM 01C 12.72 47 90 2.54 185 DNG 04H 3.67 47 95 5.63 81 MBM 03H 31.62 47 96 2.06 179 DNT 07C 0.3 47 97 2.63 179 DNT 07C 0.32 47 98 2.63 180 DNT 04C -0.32 47 98 2.23 182 DNT 07C -0.74 Page 68 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 47 98 4.61 182 DNT 07C 0.32 47 99 3.08 181 DNT 04C -0.29 47 99 3.03 179 DNT 04C 0.66 47 99 3.12 180 DNT 07C -0.77 47 99 7.43 180 DNT 07C 0.3 47 99 5.62 85 MBM 05H 4.64 48 25 4.85 179 DNT 07C 0.38 48 25 2.02 180 DNT 07C -0.68 48 26 2.48 185 DNG AV6 -0.63 48 31 2.24 185 DNG 04H 14.85 48 42 0.26 106 GEO TSH -0.04 48 46 3.06 182 DNG AV6 20.79 48 47 4.63 182 DNG AV6 20.86 48 48 3.85 183 DNG AV6 20.66 48 49 3.03 183 DNG AV6 20.93 48 52 4.24 80 MBM 04C 37.81 48 52 2.99 79 MBM 04C 32.02 48 54 1.73 145 MBM 07H -8.19 48 54 3.84 185 DNG 06C 5.27 48 54 2.09 182 DNG 06C 6.26 48 54 3.84 185 DNG 06C 5.25 48 54 6.68 90 ADS 06H 32.06 48 55 5.68 83 MBM 02H 14.3 48 55 5.58 87 MBM FBC 4.96 48 55 6.86 116 DFS 02H 11.92 48 57 2.09 182 DNG 01H 39.15 48 60 3.13 76 MBM 02C 23.79 48 60 2.31 87 MBM 02C 21.14 48 60 2.85 73 MBM 02C 18.17 48 60 5.11 83 MBM 01C 3.46 48 60 3.3 72 MBM 01C 2.33 48 60 4.09 83 MBM TSC 4.78 48 60 0.49 137 DSS 01C -0.74 48 61 0.39 17 PID TSH -0.98 48 61 0 0 TWD 0 TSH -0.9 48 61 0.19 19 TWD 59 TSH -0.9 48 61 0.32 20 TWD 62 TSH -0.9 48 61 0.4 22 TWD 67 TSH -0.9 48 61 0.34 16 TWD 50 TSH -0.9 48 61 0.21 10 TWD 32 TSH -0.9 48 61 0 0 TWD 0 TSH -0.9 48 61 0.3 22 SC' TSH -0.98 48 62 2.58 183 DNG 07H 8.42 48 63 2.82 183 DNG 07H 8.43 48 65 3.2 183 DNG 07H 8.28 48 66 2.44 181 DNG 07H 8.32 48 67 2.58 181 DNG 07H 8.3 48 68 2.79 181 DNG 07H 8.31 48 69 3.26 181 DNG 07H 8.37 48 70 0.52 21 PID TSH 0.06 48 70 0.19 37 TWD 98 TSH 0.01 48 70 0 0 TWD 0 TSH 0.01 Page 69 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 48 70 0 0 TWD 0 TSH 0.01 48 70 0.2 31 TWD 92 TSH 0.01 48 70 0.39 23 TWD 70 TSH 0.01 48 70 0.48 21 TWD 65 TSH 0.01 48 70 0.49 23 TWD 70 TSH 0.01 48 70 0.32 31 TWD 92 TSH 0.01 48 70 0.54 20 SCI TSH 0.06 48 71 2.93 182 DNG 07H 8.55 48 74 2.75 183 DNG 07H 8.19 48 76 2.94 182 DNG 07H 8.39 48 76 2.47 182 DNG 05C 4.33 48 77 3.26 182 DNG 07H 8.43 48 79 2.71 187 DNG 01C 14.06 48 83 2.49 183 DNG FBH 1.73 48 83 4.15 180 DNG 03C 25.33 48 84 5.92 85 MBM 02C 33.56 48 86 3.01 85 MBM 04H 18.86 48 86 4.41 78 MBM 04H 12.5 48 87 4.53 179 DNT 07H 0.48 48 90 3.68 79 MBM 03C 38.79 48 94 2.02 182 DNT 07C 0.3 48 95 2.34 179 DNT 07C 0.29 48 97 4.61 181 DNT 07C 0.27 48 98 2.18 180 DNT 04C -0.32 48 98 2.31 179 DNT 04C 0.64 48 98 2.12 181 DNT 07C -0.8 48 98 4.48 181 DNT 07C 0.27 48 98 2.15 73 MBM 04C 30.72 48 98 2.44 78 MBM 04C 28.3 49 35 2.76 183 DNG AV6 20.69 49 35 0.51 94 DFS 03C 27.54 49 38 2.36 63 MBM AV5 8.62 49 38 6.06 82 MBM 03C 22.04 49 42 3.11 105 DFS 03C 3.42 49 45 2.76 71 MBM FBC 8.35 49 48 0.53 12 SAI TSH 0.02 49 48 0.5 15 PID TSH 0.02 49 48 2.35 184 DNG 02C 16.38 49 48 4.85 79 MBM 06C 4.52 49 48 0 0 TWD 0 TSH -0.08 49 48 0.15 24 TWD 70 TSH -0.06 49 48 0.47 20 TWD 56 TSH -0.03 49 48 0.51 15 TWD 40 TSH -0.01 49 48 0.47 14 TWD 37 TSH 0.02 49 48 0 0 TWD 0 TSH 0.04 49 50 0.21 74 GEO TSH -0.01 49 53 4.27 82 MBM 01H 3.14 49 53 11.14 81 MBM 02H 6.72 49 53 3.98 69 MBM 02C 19.91 49 57 9.95 58 MBM AV4 -0.73 49 58 3.45 83 MBM 01H 7.62 49 58 4.34 83 MBM 02H 5.71 Page 70 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 49 58 4.61 82 MBM 02H 8.94 49 58 2.55 76 MBM 02H 10.26 49 58 5.86 84 MBM 02H 12.87 49 58 4.28 84 MBM 02H 16.6 49 58 3.18 81 MBM 02H 18 49 58 2.7 90 MBM 02H 22 49 58 2.29 86 MBM 02H 26.29 49 58 2.52 85 MBM 01C 2.94 49 60 2.1 80 MBM 06H 15.05 49 62 0.44 24 PID TSH 0.17 49 62 0 0 TWD 0 TSH 0.01 49 62 0.37 20 TWD 56 TSH 0.04 49 62 0.37 22 TWD 63 TSH 0.06 49 62 0.45 24 TWD 70 TSH 0.09 49 62 0.31 25 TWD 74 TSH 0.11 49 62 0.25 29 TWD 88 TSH 0.14 49 62 0 0 TWD 0 TSH 0.16 49 62 0.43 23 SAI TSH 0.17 49 64 0.19 0 TWD 10 AV1 0.18 49 66 3.7 184 DNG 01H 33.56 49 66 0.18 0 TWD 10 AV2 0 49 66 0.17 119 GEO TSH -0.03 49 78 3.79 184 DNG 01H 5.45 49 78 7.54 182 DNG 06C 32.99 49 78 2.73 184 DNG 06C 31.84 49 78 2.61 185 DNG 05C 4.43 49 78 6.45 183 DNT 04C 0 49 78 10.98 181 DNT 06C -0.7 49 78 2.14 181 DNT 07H -0.27 49 78 3.57 186 DNG 03C 4.89 49 78 3.06 82 MBM 05C 10.31 49 79 4.95 86 MBM 03H 4.49 49 80 11.98 78 MBM FBH 10.49 49 83 3.82 180 DNT 07C 0.32 49 84 2.52 182 DNG 06H 39.57 49 86 3.3 85 MBM 06H 37.48 49 86 5.1 73 MBM 02C 29.14 49 87 3.11 186 DNG 01C 37.22 49 87 2.39 180 DNT 07H -0.34 49 89 7.81 83 MBM 05C 26.1 49 90 6.2 86 MBM 02H 5.07 49 90 4.68 88 MBM 04H 33.55 49 92 6.94 85 MBM 03H 6.08 49 92 5.45 86 MBM 02H 11.08 49 92 4.7 88 MBM 02H 9.5 49 92 6.76 86 MBM 02H 6.07 49 92 3.58 81 MBM 01H 37.07 49 92 2.75 83 MBM 01H 31.93 49 92 3.24 78 MBM 01H 28.95 49 92 3.35 86 MBM 01H 22.81 49 92 4.31 84 MBM 01H 14.17 49 93 9.11 74 MBM 04C 16.6 Page 71 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 49 94 6.34 82 MBM AV5 0.51 49 95 4.04 181 DNT 07C -0.8 49 95 8.39 181 DNT 07C 0.32 49 96 6.43 181 DNT 07C 0.3 49 96 2 182 DNT 070 -0.8 49 96 2.19 85 MBM 03H 25.73 49 96 3.92 89 MBM 03H 33.78 49 96 2.71 88 MBM 04H 8.21 50 28 0.23 0 TWD 12 AV3 0 50 30 0.35 0 TWD 15 AV3 0 50 30 0.19 0 TWD 7 AV2 0 50 30 0.19 0 TWD 7 AV1 0 50 33 4.13 184 DNG 06H 36.84 50 36 5.87 81 MBM 03C 13.03 50 37 2.72 187 DNG TSH 6.38 50 39 5.03 183 DNG 04H 6.59 50 39 2.66 70 MBM 02H 3.74 50 44 3.88 103 DFS FBC 1.58 50 48 3.32 187 DNG 06C 36.49 50 49 3.53 186 DNG 06C 36.29 50 50 0.24 52 GEO TSH -0.03 50 50 2.01 176 DNG 01C 13.11 50 50 2.28 171 DNT 03C -0.02 50 53 2.53 66 MBM 02C 11.71 50 57 1.09 53 DFS 02H 33.93 50 57 0.94 54 DFS 04C 32.42 50 62 3.09 184 DNG 06H 36.63 50 63 2.65 186 DNG 06H 36.29 50 63 2.59 186 DNG 03C 27.93 50 64 2.96 186 DNG 06H 36.42 50 66 2.2 184 DNG 06H 36.45 50 67 2.24 184 DNG 06H 36.34 50 71 2.37 184 DNG 06H 36.45 50 73 2.67 186 DNG 06H 36.51 50 75 2.68 184 DNG 06H 36.51 50 77 2.8 187 DNG 01C 8.86 50 79 0.17 0 TWD 8 AV5 0 50 79 0.68 0 TWD 25 AV3 0.35 50 79 0.2 0 TWD 10 AV2 0 50 79 0.23 0 TWD 11 AV1 0.15 50 79 0.59 0 TWD 22 AV4 0 50 81 2.24 100 DFS 01H 8.19 50 81 3.26 76 MBM 01H 13.15 50 81 2.95 85 MBM AV3 1.47 50 83 3.66 179 DNT 07C 0.25 50 85 2.55 90 MBM 02H 2.41 50 85 3.25 90 MBM 03H 5.57 50 85 8.57 83 MBM 04H 35 50 85 5.61 85 MBM 05H 3.73 50 85 3.62 85 MBM 05H 8.43 50 85 6.24 88 MBM 05H 36.85 50 85 3.17 84 MBM 04C 6.36 Page 72 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 50 86 6.21 75 MBM 03C 16.45 50 86 5.89 78 MBM 03C 18.75 50 88 0.24 0 TWD 7 AV5 0 50 88 0.4 0 TWD 16 AV4 0 50 88 0.31 0 TWD 12 AV3 0 50 88 0.19 0 TWD 3 AV6 0 50 90 2.67 185 DNG 01C 21.99 50 91 2.66 88 MBM AV4 21.08 50 91 2.91 77 MBM 04C 25.98 50 92 2.24 72 MBM 03H 36.29 50 94 2.48 182 DNT 07C -0.8 50 94 5.14 182 DNT 07C 0.32 51 30 0.22 0 TWD 8 AV5 0 51 30 4.02 83 MBM 01C 31.02 51 33 3.18 184 DNT 07H 0.41 51 33 2.05 182 DNT 07H -0.66 51 39 7.13 183 DNG 06H 39.52 51 43 5.36 79 MBM 01H 29.71 51 45 2.5 80 MBM 01H 31.67 51 45 3.4 183 DNG 06H 39.6 51 45 0.28 144 GEO TSH -0.05 51 50 0.08 97 GEO TSH 0.01 51 52 2.37 186 DNG 05C 20.76 51 52 1.36 74 DFS 02H 2.91 51 55 0.19 0 TWD 10 AV3 0.1 51 55 0.31 0 TWD 15 AV2 -0.29 51 58 1.3 86 MBM 06C 15.91 51 58 3.93 185 DNG AV5 17.28 51 58 2.23 185 DNG 06C 16.03 51 58 4.48 83 ADS 06C 15.86 51 77 2.39 87 MBM 05H 14.69 51 83 3.8 180 DNT 07C -0.28 51 83 2.72 180 DNT 07C 0.15 51 84 2.68 180 DNT 03H -0.52 51 84 1.03 102 DFS 05C 17.03 51 84 0.61 87 DFS 05C 15.02 51 84 0.64 97 DFS 05C 13.17 51 87 3.77 183 DNG TSC 16.09 51 87 2.87 183 DNG TSC 15.04 51 89 2.4 89 MBM 03H 15.62 51 90 2.25 182 DNT 07C 0.24 51 91 6.46 86 MBM AV1 7.7 51 91 7.43 70 MBM AV1 9.54 51 91 4.59 70 MBM 06C 9.63 51 92 2.07 184 DNG 07H 8.48 51 92 2.68 182 DNT 07C 0.29 51 92 3.18 183 DNT AV2 0.1 51 93 2.25 181 DNG 07H 8.61 52 42 4.7 70 MBM 04C 4.21 52 43 0.18 115 GEO TSH -0.09 52 43 2.88 89 MBM 06C 2.79 52 43 5.09 66 MBM AV4 14.65 Page 73 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 52 43 5.28 89 MBM 06H 33.47 52 44 4.65 83 MBM 01 H 2.37 52 46 3.76 74 MBM 04C 3.3 52 48 4.12 68 MBM TSC 2.67 52 51 0.68 111 MBM 01H 5.26 52 51 2.42 79 ADS 01H 5.56 52 65 2.99 81 MBM 03C 9.81 52 65 2.04 73 MBM 01C 16.32 52 65 0.24 166 GEO TSH -0.09 52 72 9.43 180 DNT 07C 0.35 52 72 3.68 182 DNG 07C -0.75 52 73 3.42 183 DNG 06C 39.25 52 73 0.86 107 DFS 02H 27.39 52 73 2.75 75 MBM 03H 21 52 73 2.51 87 MBM 04H 16.25 52 77 4.28 180 DNT 07C 0.32 52 80 2.29 80 MBM 06C 24.53 52 81 3.14 184 DNG 06H 31.5 52 83 7.64 178 DNT 07C 0.34 52 83 2.27 179 DNT 07C -0.73 52 84 2.83 180 DNT 07C 0.3 52 87 6.12 184 DNG TSC 1.73 52 87 2.58 183 DNT 07C 0.24 52 88 3.11 185 DNG 01C 13.86 52 90 4.18 181 DNT 07C 0.3 52 91 2.8 179 DNT 07C 0.27 53 34 1.33 0 TWD 35 AV6 -0.24 53 34 1.01 0 TWD 31 AV5 0.24 53 34 2.54 188 DNG 03H 27.27 53 34 3.05 180 DNT AV1 0 53 34 3.08 183 DNG AV6 23.3 53 35 0.23 0 TWD 12 AV6 -0.07 53 35 0.22 0 TWD 11 AV5 -0.07 53 35 0.19 0 "TWD 10 AV4 -0.07 53 36 0.28 0 TWD 14 AV6 -0.1 53 36 0.25 0 TWD 13 AV4 -0.07 53 36 2 71 MBM 02C 36.81 53 36 2 85 MBM 05C 29.72 53 36 2.69 80 MBM 05C 32.88 53 36 2.94 186 DNG AV2 2.73 53 36 3.8 183 DNG AV6 23.61 53 39 4.68 184 DNG AV6 23.64 53 40 3.18 181 DNG 06H 27.37 53 41 3.64 183 DNG AV6 23.63 53 41 3.26 68 MBM 02H 1.91 53 43 3.83 182 DNG AV6 43.76 53 43 3.02 76 MBM 03C 25.62 53 43 2.47 59 MBM 01C 15.5 53 43 3.02 105 DFS 01C 11.17 53 43 1.81 92 DFS 01C 4.79 53 43 2.8 60 MBM FBC 16.81 53 45 4.47 179 DNT 07H 0.51 Page 74 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND  %/oTW LOCATION 53 50 0.14 70 GEO TSH 0.01 53 51 3.27 185 DNG AV6 21.99 53 52 2.04 182 DNG 06C 38.23 53 52 3.98 182 DNG AV6 21.97 53 53 3.95 184 DNG 07H 8.72 53 54 3.47 183 DNG 07H 8.86 53 55 3.25 185 DNG 07H 9.4 53 56 5.46 182 DNG 07H 8.98 53 57 3.55 185 DNG 07H 9.2 53 58 5.23 183 DNG 07H 9.17 53 59 4.56 183 DNG 07H 9.21 53 60 4.95 183 DNG 07H 9.2 53 60 2.53 83 MBM 02H 17.67 53 61 5.35 183 DNG 07H 9.12 53 61 2.45 85 MBM 01C 29.69 53 62 2.44 77 ADS 01H 17.23 53 64 0.51 0 TWD 22 AV5 0 53 64 0.77 0 TWD 28 AV6 0 53 64 4.02 85 MBM 04H 36.15 53 64 3.51 88 MBM 03H 34.77 53 64 9.93 78 MBM 01H 34.47 53 64 2.76 74 MBM TSH 10.32 53 64 3.54 89 MBM 02H 28.77 53 66 0.63 94 DFS TSH 17.46 53 69 3.56 81 MBM 01H 29.98 53 71 5.19 73 MBM AV6 25.22 53 72 4.65 83 MBM 01H 7.23 53 72 2.16 85 MBM 01H 33.52 53 78 3.48 182 DNG 07H 8.2 53 81 1.74 106 DFS TSH 7.71 53 81 2.49 78 MBM 04H 32.38 53 82 3.59 84 MBM 01H 8.01 53 82 3.21 89 MBM 01H 9.72 53 85 8.72 78 MBM 04C 18.03 53 86 2.85 181 DNT 07C 0.25 53 87 2.68 181 DNT 07C 0.28 53 87 2.14 180 DNT 07C -0.76 53 87 3.01 182 DNG 06C 23.81 53 87 7 80 MBM 01 H 27.08 53 87 8.71 78 MBM 01H 28.87 53 88 3.02 181 DNT 07C 0.25 53 88 7.34 79 MBM 01 H 36.43 53 89 2.49 181 DNT 07C 0.36 53 90 3.37 181 DNT 07C 0.24 53 90 2.07 185 DNG 04C 22.22 54 37 5.59 177 DNT 07H 0.46 54 37 3.71 181 DNT AV2 0.19 54 38 2.52 181 DNT AV2 0.12 54 46 2.15 183 DNT 07C 0.32 54 47 0.65 121 MBM 04C 5.92 54 47 3.6 79 MBM FBC 13.07 54 47 2.13 85 ADS 04C 6.18 Page 75 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 54 52 2.21 181 DNG AV6 20.27 54 53 2.73 182 DNG 07H 11.58 54 54 3.61 181 DNG 07H 11.16 54 55 3.05 182 DNG 07H 10.91 54 57 2.7 181 DNG 07H 11.32 54 57 4.57 115 DFS 01H 20.43 54 58 2.56 183 DNG 07H 10.97 54 59 2.61 183 DNG 07H 11.4 54 61 3.1 181 DNG 07H 10.65 54 64 2.16 84 MBM 06H 2.53 54 65 2.59 77 MBM FBH 17.97 54 73 2.78 182 DNT 07C 0.4 54 73 2.2 182 DNT 04C 0.52 54 73 2.59 183 DNT 04C -0.45 54 73 3.53 86 MBM 02C 22.43 54 75 2.85 181 DNT 04C -0.45 54 75 2.86 181 DNT 04C 0.57 54 76 4.26 181 DNT 07C 0.35 54 76 3.23 84 MBM 01H 9.9 54 76 4.16 79 MBM 01H 11.74 54 76 2.84 79 MBM 01H 30.74 54 76 6.17 83 MBM 02H 23.12 54 76 3.12 89 MBM 02H 18.36 54 76 2.47 84 MBM 04H 10.1 54 76 2.03 88 MBM 01H 5.5 54 77 2.03 83 MBM 02H 25.17 54 77 3.66 88 MBM 04H 33.15 54 79 2.83 183 DNT 07C 0.25 54 79 4.19 78 MBM 01C 24.33 54 83 4.37 185 DNG 07H 1.83 54 83 5.96 178 DNT 07C 0.24 54 83 3.08 181 DNT 07C -0.71 54 83 3.11 184 DNG 07H 1.17 54 85 2.71 178 DNT 07H 0.66 54 85 2.61 180 DNT 07C 0.27 54 85 4.49 181 DNT AV2 0.1 54 86 3.39 180 DNT 07C 0.24 54 87 4.83 180 DNT 07C 0.27 54 87 3.06 183 DNT 07C -0.73 54 87 2.18 186 DNG 07C -1.27 54 87 3.25 183 DNG 06C 1.47 54 88 2.77 182 DNG 06H 36.2 54 88 5.35 182 DNG 06H 36.93 54 88 6.41 185 DNG 06H 37.25 54 88 2.14 183 DNG 06H 38.43 54 88 2.98 179 DNT 07C 0.32 54 88 3.03 182 DNT 07C -0.73 54 88 3.96 182 DNG 06C 35.01 54 88 6.05 78 MBM 02C 9.5 55 39 3.2 182 DNT AV1 0 55 40 3.07 187 DNT AV4 0.05 55 40 2.37 187 DNT AV3 0.15 Page 76 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 55 40 4.22 183 DNT AV2 0.07 55 41 3.19 80 MBM TSC 12.2 55 42 3.7 84 MBM 03H 28.19 55 44 0.42 0 TWD 18 AV3 0.05 55 48 6.61 79 MBM 01C 24.12 55 51 2.09 78 MBM 07H 27.53 55 56 2.82 109 DFS 03C 3.28 55 58 4.08 105 DFS 04H 18.35 55 59 0.93 75 DFS 02H 19.18 55 71 5.67 80 MBM TSH 3.64 55 72 4.52 181 DNG AV2 3.8 55 72 20.56 180 DNG AV6 23.59 55 72 2.13 175 DNT 07H 0.48 55 72 2.46 180 DNG 07H 5.69 55 72 6.32 181 DNG AV6 24.89 55 72 6.87 179 DNT 07C 0.35 55 72 2.26 178 DNT 07C -0.83 55 72 3.14 178 DNT 04C 0.63 55 72 3.4 178 DNT 04C -0.43 55 72 2.79 179 DNT 03C 0.63 55 72 4.59 178 DNT 03C -0.45 55 73 2.64 182 DNT 04C -0.42 55 73 2.65 182 DNT 04C 0.55 55 74 5.42 182 DNT 07C 0.3 55 74 2.24 182 DNT 04C -0.42 55 75 3.46 180 DNT 03C -0.45 55 75 2.57 184 DNT 03C 0.57 55 75 5.77 181 DNT 04C -0.45 55 75 2.96 182 DNT 04C 0.55 55 75 2.19 174 DNT 04C 0.05 55 75 2.22 80 MBM 04H 9.02 55 76 4.65 187 DNG 02C 19.78 55 76 2.01 182 DNT 03C -0.45 55 76 2.6 71 MBM 01C 14.6 55 76 2.15 182 DNT 03C 0.62 55 77 3.11 182 DNT 03C -0.42 55 77 3.88 182 DNT 04C -0.45 55 77 3.34 180 DNT 04C 0.57 55 77 3.48 87 MBM FBH 14.98 55 77 3.77 77 MBM 02H 23.92 55 78 2.12 181 DNT 03C -0.45 55 79 2.57 179 DNT 04C -0.42 55 79 2.06 181 DNT 04C 0.55 55 81 2.11 179 DNT 04C -0.44 55 83 3.05 181 DNT 07C 0.24 55 84 3.37 63 MBM 03C 13.52 55 84 4.35 71 MBM 03C 15.72 55 84 7.3 74 MBM 02C 35.12 55 84 2.39 70 MBM 03C 5.89 56 42 5.29 181 DNG 06H 39.71 56 52 4.84 75 MBM 06H 14.28 56 52 2.73 65 MBM 06C 11.04 Page 77 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 56 56 3.73 60 MBM FBH 16.77 56 61 5.13 77 MBM TSH 15.41 56 63 3.11 77 MBM FBH 7.9 56 63 6.9 82 MBM 06H 18.47 56 65 2.11 69 MBM 01H 16.66 56 65 2.34 71 MBM 01H 20.31 56 65 2.11 74 MBM 01H 27.55 56 65 2.32 74 MBM 01H 32.74 56 65 2.03 73 MBM 01H 34.45 56 65 2.63 76 MBM 01H 37.09 56 66 2.48 78 MBM 02C 18.99 56 69 3.12 79 MBM 06C 7.3 56 72 4.02 183 DNT 03C -0.35 56 72 3.95 183 DNT 03C 0.6 56 72 3.9 183 DNT 04C -0.45 56 72 4.21 183 DNT 04C 0.57 56 72 2.58 187 DNT AV3 0 56 73 5.56 182 DNT 03C -0.45 56 73 4.69 182 DNT 03C 0.6 56 73 4.27 183 DNT 04C -0.4 56 73 4.11 182 DNT 04C 0.57 56 74 6.29 182 DNT 03C -0.42 56 74 5.43 182 DNT 03C 0.62 56 74 4.58 182 DNT 04C -0.45 56 74 3.71 182 DNT 04C 0.6 56 75 4.77 183 DNT 03C -0.42 56 75 6.18 182 DNT 03C 0.65 56 75 7.66 182 DNT 04C -0.42 56 75 5.08 182 DNT 04C 0.57 56 76 5.24 182 DNT 03C -0.42 56 76 4.27 183 DNT 03C 0.6 56 76 4.58 181 DNT 04C -0.42 56 76 3.79 183 DNT 04C 0.65 56 77 4.5 182 DNT 03C -0.4 56 77 5.53 182 DNT 03C 0.62 56 77 6.74 182 DNT 04C -0.42 56 77 3.51 182 DNT 04C 0.6 56 78 2.97 181 DNT 03C -0.42 56 78 2.29 181 DNT 03C 0.65 56 78 2.67 182 DNT 04C -0.42 56 78 2.43 180 DNT 04C 0.6 56 78 2.31 181 DNT AV5 -0.55 56 79 2.53 181 DNT 03C -0.42 56 79 4.9 184 DNT 04C -0.45 56 79 3.01 183 DNT 04C 0.62 56 80 2.27 182 DNG 05H 16.49 56 80 2.5 183 DNG 05H 20.42 56 80 4.23 184 DNG 06H 37.43 56 80 4.64 183 DNG AV4 20.22 56 81 2.09 177 DNT 04C 0.56 56 81 2.83 179 DNT 04C -0.36 56 81 2.37 184 DNG 07H 8.22 Page 78 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 56 82 3.18 179 DNT 07C 0.24 57 44 0.14 0 TWD 7 AV1 -0.1 57 46 2.26 183 DNT 07C 0.34 57 46 1.84 154 DDS 06H 36.59 57 47 12.84 183 DNG AV6 23.67 57 47 4.39 185 DNG 07H 4.99 57 47 2.28 70 ADS 03C 9.64 57 48 2.85 183 DNT 07H 0.49 57 49 5.72 181 DNG AV6 23.07 57 50 3.98 183 DNG AV6 23.32 57 52 2.32 78 MBM 06C 37.98 57 53 2.85 75 MBM 06C 14.22 57 53 2.93 79 MBM 04H 2.02 57 54 2.74 83 MBM 05C 30.26 57 55 2.76 183 DNG 03H 16.53 57 58 2.59 82 MBM AV6 11.22 57 59 1.22 109 DFS TSC 18.75 57 59 0.93 114 DFS TSC 18.07 57 62 3.13 183 DNT AV3 0.08 57 65 2.64 185 DNT AV3 0.05 57 66 3.38 184 DNT AV4 0 57 68 1.62 93 DFS 04H 8.87 57 69 4.06 185 DNT AV4 0 57 69 2.96 78 MBM 05C 6.96 57 70 4.82 182 DNG 07H 9.62 57 70 2.36 185 DNT AV3 0 57 70 2.57 186 DNT AV4 0 57 70 2.38 73 MBM 03H 25.97 57 71 2.21 67 MBM 04C 29.28 57 73 4.99 183 DNG 07H 10.01 57 73 5.14 181 DNT 03C -0.45 57 73 7.67 181 DNT 03C 0.6 57 73 5.15 182 DNT 04C -0.42 57 73 3.04 183 DNT 04C 0.55 57 74 5 183 DNG 07H 9.92 57 74 2.23 184 DNT AV4 0.1 57 74 3.31 181 DNT 04C 0.62 57 74 7.23 179 DNT 04C -0.4 57 74 6.5 179 DNT 03C 0.67 57 74 5.25 180 DNT 03C -0.37 57 75 4.98 183 DNG 07H 9.82 57 75 7.16 181 DNT 03C -0.42 57 75 7.91 182 DNT 03C 0.62 57 75 9.09 181 DNT 04C -0.45 57 75 6.2 182 DNT 04C 0.6 57 75 2.27 171 DNT 04C 0.07 57 75 4.61 84 MBM 03H 25.28 57 75 3.33 85 MBM 03H 3.95 57 77 4.86 183 DNG 07H 9.53 57 77 5.54 182 DNT 03C -0.4 57 77 7.36 180 DNT 03C 0.67 57 77 7.17 181 DNT 04C -0.4 Page 79 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 57 77 6.79 180 DNT 04C 0.6 57 77 2.95 184 DNT AV4 0.4 57 77 2.34 178 DNT 07H 0.4 57 78 4.93 181 DNT 03C 0.67 57 78 3.07 180 DNT 04C -0.37 57 78 2.58 182 DNT 04C 0.62 57 78 2.2 186 DNT AV4 0 57 78 5.09 182 DNG 07H 9.67 57 78 2.9 183 DNT 03C -0.37 57 79 4.46 183 DNT 03C -0.4 57 79 4.62 184 DNT 03C 0.62 57 79 5.81 183 DNT 04C -0.42 57 79 6.97 183 DNT 04C 0.62 57 79 2.56 182 DNT 07C 0.27 57 79 2.33 184 DNT 07H 0.43 57 79 1.93 77 DFS 07H 16.07 57 80 2.68 183 DNT 03C 0.65 57 80 2.38 184 DNT 04C -0.37 57 80 3.18 183 DNT 04C 0.67 57 80 3.23 184 DNT 07C 0.25 58 48 2.88 180 DNT 07C 0.39 58 49 2.67 189 DNG 02H 24.39 58 49 2.04 65 ADS 03C 31.81 58 51 6.39 183 DNT AV5 0.07 58 51 2.86 82 MBM AV2 14.09 58 52 2.28 178 DNT 07C -0.71 58 52 6.29 180 DNT 07C 0.37 58 58 2.48 187 DNT AV4 0.24 58 61 2.77 186 DNT AV4 0.25 58 62 3.29 183 DNG 07H 11.3 58 62 2.15 185 DNG 01C 2.85 58 62 3.26 186 DNT AV3 0.1 58 62 6.27 75 MBM 01C 3.08 58 63 3.07 182 DNG 07H 11.64 58 65 2.47 185 DNG 04H 28.08 58 65 3.39 181 DNG 07H 10.66 58 65 2.15 186 DNT AV3 -0.23 58 66 3.08 183 DNG 07H 11.01 58 66 2.76 185 DNT AV3 -0.2 58 66 2.51 186 DNT AV4 0.23 58 66 2.9 79 MBM 03H 21.03 58 67 2.27 184 DNT AV3 0 58 67 2.42 186 DNT AV4 0 58 68 2.17 183 DNG 06H 38.68 58 68 2.35 184 DNT AV4 0.28 58 71 2.79 181 DNT 07H 0.45 58 71 2.99 181 DNT 07H -0.53 58 71 2.35 182 DNT 07H 0.81 58 72 4.18 183 DNT 03C -0.37 58 72 6.45 182 DNT 03C 0.63 58 72 5.82 184 DNT 04C -0.48 58 72 3.61 184 DNT 04C 0.57 Page 80 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 58 72 3.39 182 DNT 07C -0.45 58 72 9.34 182 DNT 07C 0.6 58 72 6.1 186 DNT AV4 0 58 72 4.03 186 DNT AV3 0 58 72 6.03 185 DNT AV2 -0.08 58 73 5.2 184 DNG 07H 1.08 58 73 4 183 DNG 07H 1.71 58 73 5.07 182 DNT 03C -0.42 58 73 6.63 182 DNT 03C 0.6 58 73 6.12 182 DNT 04C -0.45 58 73 4 183 DNT 04C 0.55 58 73 6.24 182 DNT 07H 0.6 58 73 2.29 185 DNT 07H -0.03 58 73 2.3 183 DNT 07H -0.5 58 74 4.83 183 DNT 03C -0.37 58 74 6.74 182 DNT 03C 0.63 58 74 5 182 DNT 04C -0.4 58 74 4.53 183 DNT 04C 0.57 58 74 2.25 183 DNT 07C 0.68 58 74 2.14 184 DNT AV2 0 58 75 5.52 182 DNT 03C -0.42 58 75 7.22 182 DNT 03C 0.62 58 75 5.1 182 DNT 04C -0.45 58 75 2.38 184 DNT 04C 0.6 58 75 3.72 184 DNT 07C -0.73 58 75 7.65 181 DNT 07C 0.37 58 75 6.07 179 DNT 07H 0.48 58 75 2.18 183 DNT 07H -0.63 58 76 4.48 182 DNT 03C -0.4 58 76 6.63 182 DNT 03C 0.67 58 76 7.87 182 DNT 04C -0.37 58 76 6.25 183 DNT 04C 0.62 58 76 2.62 175 DNT 04C 0.12 58 77 4.85 182 DNT 03C -0.37 58 77 6.27 183 DNT 03C 0.7 58 77 7.93 182 DNT 04C -0.4 58 77 5.67 183 DNT 04C 0.65 58 77 2.09 182 DNT 07C 0.3 59 52 15.41 179 DNT 07H 0.46 59 52 2.48 178 DNT 07H -0.68 59 52 3.03 180 DNG 03C 16.54 59 52 3.43 180 DNG 03C 10.3 59 52 3.02 179 DNG 03C 4.07 59 52 2.6 180 DNG 02C 38 59 52 2.45 182 DNG 02C 31.83 59 52 3.38 183 DNT AV3 -0.22 59 56 2.71 186 DNT AV3 -0.15 59 57 4.22 183 DNT AV3 -0.15 59 59 3 186 DNT AV3 -0.2 59 60 2.17 183 DNG 06H 37.06 59 62 2.73 186 DNT AV4 0.3 59 62 3.5 184 DNT AV3 -0.18 Page 81 of 82

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator A ROW COL VOLTS DEG IND %TW LOCATION 59 63 2.5 186 DNT AV3 -0.23 59 65 4.67 185 DNT AV4 0.28 59 65 4.51 184 DNT AV3 -0.18 59 66 3.59 185 DNT AV4 0 59 66 3.13 185 DNT AV3 0 59 67 0.18 0 TWD 9 02C 0.29 59 67 0.41 120 SVI 02C 0.13 59 67 0.4 121 PID 02C 0.13 59 67 0.22 107 DSI 02C 0.17 59 67 4.56 184 DNT AV4 0 59 67 5.59 184 DNT AV3 0 59 67 3.13 184 DNG TSH 1.01 59 67 5.59 184 DNT AV3 0 59 68 3.15 186 DNT AV4 0 59 69 3.89 183 DNT AV5 0.38 59 69 3.31 185 DNT AV3 0 59 70 1.65 112 DFS 05H 8.4 59 71 2.52 181 DNT 07H 0.45 Page 82 of 82

ULNRC-04823 March 12, 2003 Page 18 Listing of Steam Generator Tube Imperfections Callaway Refuel 12 Outage Steam Generator B

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator B ROW COL VOLTS DEG IND %TW LOCATION 1 11 1 31 GEO TSH 0.14 1 99 0.54 28 GEO TSH 0.12 1 107 0.13 73 PLP TSH 0.29 8 20 0.47 24 GEO TSH 0.05 8 82 0.92 104 MBM TSH 1.12 11 69 0.28 108 GEO TSH -0.07 12 52 0.2 63 PID TSH 0.62 12 52 0.16 85 SAI TSH 0.62 12 52 0 0 TWD 0 TSH 0.46 12 52 0.11 130 TWD 0 TSH 0.49 12 52 0.14 106 TWD 0 TSH 0.51 12 52 0.18 82 TWD 0 TSH 0.53 12 52 0.17 71 TWD 64 TSH 0.55 12 52 0 0 TWD 0 TSH 0.58 12 74 0.26 16 GEO TSH -0.13 14 104 0.35 21 PID TSH 0.07 14 104 0.37 19 SCI TSH 0.07 14 104 0 0 TWD 0 TSH 0.06 14 104 0.27 25 TWD 82 TSH 0.06 14 104 0.37 22 TWD 73 TSH 0.06 14 104 0.29 25 TWD 82 TSH 0.06 14 104 0.18 11 TWD 38 TSH 0.06 14 104 0.15 7 TWD 24 TSH 0.06 14 104 0 0 TWD 0 TSH 0.06 17 55 1.49 106 MBM TSH 2.11 17 66 0.36 32 GEO TSH 0.03 22 46 0.42 46 GEO TSH -0.01 24 10 0.5 33 GEO TSH -0.02 28 19 0.44 106 MBM TSH 1.3 29 90 0 0 TWD 0 TSH -1.85 29 90 0.17 9 TWD 31 TSH -1.85 29 90 0.19 2 TWD 7 TSH -1.87 29 90 0.14 7 TWD 24 TSH -1.87 29 90 0.2 20 TWD 68 TSH -1.87 29 90 0.31 25 TWD 84 TSH -1.87 29 90 0.38 27 TWD 90 TSH -1.87 29 90 0.3 28 TWD 94 TSH -1.87 29 90 0.2 11 TWD 38 TSH -1.87 29 90 0 0 TWD 0 TSH -1.87 29 90 0.37 31 PID TSH -1.93 29 90 0.29 35 SCl TSH -1.93 30 25 0.26 34 GEO TSH 0 30 52 0.61 29 GEO TSH 0.19 31 55 0.44 75 MBM TSH 1.84 32 49 0.21 5 GEO TSH -0.01 33 38 1.18 151 MBM TSH 3.88 33 77 0 0 TWD 0 TSH -5.22 33 77 0.12 7 TWD 24 TSH -5.22 33 77 0.1 1 TWD 3 TSH -5.22 33 77 0.1 4 TWD 14 TSH -5.22 33 77 0.19 24 TWD 81 TSH -5.22 Page 1 of 2

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator B ROW COL VOLTS DEG IND %TW LOCATION 33 77 0.33 27 TWD 90 TSH -5.21 33 77 0.54 28 TWD 94 TSH -5.21 33 77 0.74 28 TWD 94 TSH -5.21 33 77 0.89 27 TWD 90 TSH -5.21 33 77 0.93 28 TWD 94 TSH -5.21 33 77 0.88 30 TWD 100 TSH -5.21 33 77 0.65 35 TWD 97 TSH -5.21 33 77 0.61 34 TWD 97 TSH -5.21 33 77 0.61 29 TWD 97 TSH -5.21 33 77 0.6 22 TWD 74 TSH -5.21 33 77 0.53 21 TWD 71 TSH -5.21 33 77 0.39 23 TWD 77 TSH -5.21 33 77 0 0 TWD 0 TSH -5.21 33 77 1.27 33 PID TSH -5.41 33 77 0.92 35 SC' TSH -5.41 36 60 0.32 129 GEO TSH -0.01 38 60 0.37 43 GEO TSH 0.03 41 76 0.14 70 GEO TSH -0.06 41 105 0.29 60 GEO TSH -0.06 42 59 0.31 26 GEO TSH -0.04 42 65 0 0 TWD 0 TSH -0.02 42 65 0.25 2 TWD 7 TSH -0.02 42 65 0.36 6 TWD 21 TSH -0.02 42 65 0.19 7 TWD 24 TSH -0.02 42 65 0 0 TWD 0 TSH -0.02 42 65 0.46 23 PID TSH 0.09 42 65 0.46 17 SCl TSH 0.09 44 49 0.28 30 GEO TSH 0 45 96 0.19 62 GEO TSH 0 46 92 0.38 67 GEO TSH -0.06 49 87 0.25 144 GEO TSH -0.06 54 85 0.3 26 GEO TSH -0.16 55 48 0.53 19 GEO TSH 0 Page 2 of 2

ULNRC-04823 March 12, 2003 Page 19 Listing of Steam Generator Tube Imperfections Callaway Refuel 12 Outage Steam Generator C

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator C ROW COL VOLTS DEG IND %TW LOCATION 3 117 0.13 86 GEO TSH 0.01 5 10 0.67 102 MBM TSH 2.39 7 118 1.16 12 GEO TSH -0.27 8 90 0.31 80 GEO TSH 0.04 8 121 0.52 350 GEO TSH -0.31 10 71 0.13 156 GEO TSH -0.05 11 68 0.74 40 PID TSH -5.22 11 68 0 0 TWD 0 TSH -5.21 11 68 0.26 44 TWD 95 TSH -5.21 11 68 0.55 35 TWD 99 TSH -5.21 11 68 0.66 36 TWD 99 TSH -5.21 11 68 0.5 38 TWD 98 TSH -5.21 11 68 0.28 45 TWD 95 TSH -5.21 11 68 0.13 37 TWD 98 TSH -5.21 11 68 0 0 TWD 0 TSH -5.21 11 68 0.71 43 SCl TSH -5.22 11 120 0.73 7 GEO TSH -0.04 12 115 0.34 5 GEO TSH -0.03 12 119 0.64 10 GEO TSH -0.02 13 56 0.22 93 PID TSH 0.54 13 56 0.25 68 SAI TSH 0.54 13 56 0 0 TWD 0 TSH 0.34 13 56 0.17 72 TWD 51 TSH 0.36 13 56 0.2 70 TWD 55 TSH 0.39 13 56 0.21 84 TWD 22 TSH 0.42 13 56 0.19 97 TWD 0 TSH 0.45 13 56 0.2 82 TWD 27 TSH 0.47 13 56 0.25 72 TWD 51 TSH 0.5 13 56 0.24 76 TWD 42 TSH 0.53 13 56 0.16 105 TWD 0 TSH 0.55 13 56 0 0 TWD 0 TSH 0.58 13 68 4.16 37 PID TSH -5.36 13 68 0 0 TWD 0 TSH -5.38 13 68 0.54 48 TWD 93 TSH -5.38 13 68 1.18 41 TWD 97 TSH -5.38 13 68 1.92 39 TWD 98 TSH -5.38 13 68 2.48 39 TWD 98 TSH -5.38 13 68 2.82 41 TWD 97 TSH -5.38 13 68 3.07 40 TWD 97 TSH -5.38 13 68 3.23 40 TWD 97 TSH -5.38 13 68 3.32 40 TWD 97 TSH -5.38 13 68 3.24 40 TWD 97 TSH -5.38 13 68 3.09 41 TWD 97 TSH -5.38 13 68 2.89 40 TWD 97 TSH -5.38 13 68 2.56 39 TWD 98 TSH -5.38 13 68 1.99 39 TWD 98 TSH -5.38 13 68 1.21 40 TWD 97 TSH -5.38 13 68 0.45 50 TWD 92 TSH -5.38 13 68 0 0 TWD 0 TSH -5.37 13 68 4.18 37 SCI TSH -5.36 13 69 0.21 25 PID TSH -0.08 Page 1 of 10

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator C ROW COL VOLTS DEG IND %TW LOCATION 13 69 0 0 TWD 0 TSH -0.09 13 69 0.11 26 TWD 78 TSH -0.09 13 69 0.23 17 TWD 48 TSH -0.09 13 69 0.22 13 TWD 36 TSH -0.09 13 69 0.14 4 TWD 11 TSH -0.12 13 69 0 0 TWD 0 TSH -0.12 13 69 0.26 25 SCl TSH -0.08 14 72 0.35 20 PID TSH -7.33 14 72 0 0 TWD 0 TSH -7.41 14 72 0.16 26 TWD 78 TSH -7.4 14 72 0.28 18 TWD 51 TSH -7.4 14 72 0.26 19 TWD 55 TSH -7.4 14 72 0.2 18 TWD 51 TSH -7.4 14 72 0 0 TWD 0 TSH -7.4 14 72 0.37 22 SCI TSH -7.33 14 117 3.15 27 MBM TSH -1 15 28 0 0 TWD 0 TSH -6.3 15 28 0.21 35 TWD 99 TSH -6.3 15 28 0.39 29 TWD 89 TSH -6.3 15 28 0.48 28 TWD 85 TSH -6.3 15 28 0.41 27 TWD 82 TSH -6.3 15 28 0.25 27 TWD 82 TSH -6.3 15 28 0 0 TWD 0 TSH -6.3 15 28 0.6 22 PID TSH -6.45 15 28 0.71 23 MCI TSH -6.45 17 77 0 0 TWD 0 TSH -3.51 17 77 0.48 21 PID TSH -3.51 17 77 0 0 TWD 0 TSH -2.69 17 77 0.36 27 TWD 82 TSH -2.69 17 77 0.5 26 TWD 78 TSH -2.69 17 77 0.66 25 TWD 75 TSH -2.69 17 77 0.77 23 TWD 68 TSH -2.69 17 77 0.8 23 TWD 68 TSH -2.69 17 77 0.77 22 TWD 64 TSH -2.69 17 77 0.71 22 TWD 64 TSH -2.69 17 77 0.71 22 TWD 64 TSH -2.69 17 77 0.62 28 TWD 85 TSH -2.69 17 77 0.51 30 TWD 92 TSH -2.69 17 77 0.42 33 TWD 99 TSH -2.69 17 77 0 0 TWD 0 TSH -2.69 17 77 0 0 TWD 0 TSH -3.51 17 77 0.51 26 TWD 78 TSH -3.51 17 77 0.62 26 TWD 78 TSH -3.51 17 77 0.77 23 TWD 68 TSH -3.51 17 77 0.88 22 TWD 64 TSH -3.51 17 77 0.85 22 TWD 64 TSH -3.51 17 77 0.78 23 TWD 68 TSH -3.51 17 77 0.73 23 TWD 68 TSH -3.51 17 77 0.69 24 TWD 71 TSH -3.51 17 77 0.66 24 TWD 71 TSH -3.51 17 77 0.63 25 TWD 75 TSH -3.51 17 77 0.61 26 TWD 78 TSH -3.51 Page 2 of 10

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator C ROW COL VOLTS DEG IND %TW LOCATION 17 77 0.6 26 TWD 78 TSH -3.51 17 77 0.58 22 TWD 64 TSH -3.51 17 77 0.55 24 TWD 71 TSH -3.51 17 77 0.52 27 TWD 82 TSH -3.51 17 77 0.5 28 TWD 85 TSH -3.51 17 77 0.5 24 TWD 71 TSH -3.51 17 77 0.55 28 SCI TSH -2.69 17 77 0.46 18 SCI TSH -3.51 18 77 6.49 31 PID TSH -9.86 18 77 11.4 48 PID TSH -7.09 18 77 6.15 44 PID TSH -6.51 18 77 0 0 TWD 0 TSH -6.55 18 77 0.76 28 TWD 85 TSH -6.55 18 77 0.88 30 TWD 92 TSH -6.55 18 77 1.07 34 TWD 99 TSH -6.55 18 77 1.33 34 TWD 99 TSH -6.55 18 77 1.86 48 TWD 93 TSH -6.55 18 77 2.6 48 TWD 93 TSH -6.55 18 77 3.33 47 TWD 94 TSH -6.55 18 77 3.81 46 TWD 94 TSH -6.55 18 77 4.05 44 TWD 95 TSH -6.55 18 77 4.26 43 TWD 96 TSH -6.55 18 77 4.55 43 TWD 96 TSH -6.55 18 77 5 43 TWD 96 TSH -6.55 18 77' 5.57 44 TWD 95 TSH -6.55 18 77 6 44 TWD 95 TSH -6.55 18 77 5.99 44 TWD 95 TSH -6.55 18 77 5.36 45 TWD 95 TSH -6.55 18 77 4.39 47 TWD 94 TSH -6.55 18 77 3.63 47 TWD 94 TSH -6.54 18 77 3.19 45 TWD 95 TSH -6.54 18 77 2.75 40 TWD 97 TSH -6.54 18 77 2.12 40 TWD 97 TSH -6.54 18 77 1.5 40 TWD 97 TSH -6.54 18 77 1.11 36 TWD 99 TSH -6.54 18 77 0.92 33 TWD 100 TSH -6.54 18 77 0.82 30 TWD 92 TSH -6.54 18 77 0.73 27 TWD 82 TSH -6.54 18 77 0 0 TWD 0 TSH -6.54 18 77 0 0 TWD 0 TSH -6.54 18 77 0.55 33 TWD 100 TSH -6.53 18 77 0.93 33 TWD 100 TSH -6.53 18 77 1.23 32 TWD 100 TSH -6.53 18 77 1.36 31 TWD 96 TSH -6.53 18 77 1.11 32 TWD 100 TSH -6.53 18 77 0.67 32 TWD 100 TSH -6.56 18 77 0.3 28 TWD 85 TSH -6.56 18 77 0 0 TWD 0 TSH -6.56 18 77 0 0 TWD 0 TSH -7.12 18 77 1.29 46 TWD 94 TSH -7.12 18 77 1.52 47 TWD 94 TSH -7.12 18 77 1.85 48 TWD 93 TSH -7.12 Page 3 of 10

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator C ROW COL VOLTS DEG IND %TW LOCATION 18 77 2.24 46 TWD 94 TSH -7.12 18 77 2.73 45 TWD 95 TSH -7.12 18 77 3.47 48 TWD 93 TSH -7.12 18 77 4.61 48 TWD 93 TSH -7.12 18 77 6.1 48 TWD 93 TSH -7.12 18 77 7.65 49 TWD 93 TSH -7.12 18 77 9.03 49 TWD 93 TSH -7.12 18 77 10.34 49 TWD 93 TSH -7.12 18 77 11.51 48 TWD 93 TSH -7.12 18 77 12.27 47 TWD 94 TSH -7.12 18 77 12.25 46 TWD 94 TSH -7.12 18 77 11.4 47 TWD 94 TSH -7.12 18 77 9.91 49 TWD 93 TSH -7.14 18 77 8.26 52 TWD 91 TSH -7.14 18 77 6.71 55 TWD 89 TSH -7.14 18 77 5.35 54 TWD 90 TSH -7.14 18 77 4.29 53 TWD 91 TSH -7.14 18 77 3.48 51 TWD 92 TSH -7.14 18 77 2.73 51 TWD 92 TSH -7.14 18 77 2.15 51 TWD 92 TSH -7.14 18 77 1.76 50 TWD 92 TSH -7.14 18 77 1.49 50 TWD 92 TSH -7.14 18 77 1.28 49 TWD 93 TSH -7.14 18 77 1.19 42 TWD 96 TSH -7.14 18 77 0 0 TWD 0 TSH -7.14 18 77 24.1 38 TWD 98 TSH -9.99 18 77 23.8 38 TWD 98 TSH -9.99 18 77 23.35 39 TWD 98 TSH -9.99 18 77 22.66 39 TWD 98 TSH -9.99 18 77 21.84 41 TWD 97 TSH -9.99 18 77 21.33 42 TWD 96 TSH -9.99 18 77 21.83 40 TWD 97 TSH -9.98 18 77 22.68 39 TWD 98 TSH -9.98 18 77 23.25 38 TWD 98 TSH -9.98 18 77 23.51 38 TWD 98 TSH -9.98 18 77 23.62 39 TWD 98 TSH -9.98 18 77 23.59 40 TWD 97 TSH -9.98 18 77 23.64 40 TWD 97 TSH -9.98 18 77 23.65 40 TWD 97 TSH -9.98 18 77 23.66 39 TWD 98 TSH -9.98 18 77 23.7 39 TWD 98 TSH -9.98 18 77 23.66 39 TWD 98 TSH -9.98 18 77 23.58 38 TWD 98 TSH -9.98 18 77 23.33 37 TWD 98 TSH -9.98 18 77 22.54 37 TWD 98 TSH -9.98 18 77 21.09 38 TWD 98 TSH -9.98 18 77 19.42 40 TWD 97 TSH -9.98 18 77 18.4 42 TWD 96 TSH -9.98 18 77 18.49 42 TWD 96 TSH -9.98 18 77 19.54 39 TWD 98 TSH -9.98 18 77 20.99 38 TWD 98 TSH -9.98 18 77 22.19 39 TWD 98 TSH -9.98 Page 4 of 10

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator C ROW COL VOLTS DEG IND %TW LOCATION 18 77 22.83 39 TWD 98 TSH -9.98 18 77 22.87 39 TWD 98 TSH -9.98 18 77 22.49 39 TWD 98 TSH -9.98 18 77 22.29 39 TWD 98 TSH -9.98 18 77 22.05 40 TWD 97 TSH -9.98 18 77 21.79 42 TWD 96 TSH -9.98 18 77 21.86 42 TWD 96 TSH -9.98 18 77 22.21 42 TWD 96 TSH -9.98 18 77 22.14 41 TWD 97 TSH -9.98 18 77 22.55 41 TWD 97 TSH -9.98 18 77 22.67 41 TWD 97 TSH -9.97 18 77 22.91 40 TWD 97 TSH -9.97 18 77 22.97 40 TWD 97 TSH -9.97 18 77 22.85 41 TWD 97 TSH -9.97 18 77 22.86 39 TWD 98 TSH -9.97 18 77 23.15 40 TWD 97 TSH -9.97 18 77 22.81 39 TWD 98 TSH -9.97 18 77 22.84 40 TWD 97 TSH -9.97 18 77 23.03 39 TWD 98 TSH -9.97 18 77 22.47 39 TWD 98 TSH -9.97 18 77 22.31 39 TWD 98 TSH -9.97 18 77 23.4 37 TWD 98 TSH -9.97 18 77 24.18 39 TWD 98 TSH -9.97 18 77 24.46 39 TWD 98 TSH -9.97 18 77 24.68 39 TWD 98 TSH -9.97 18 77 25.07 39 TWD 98 TSH -9.97 18 77 24.73 39 TWD 98 TSH -9.97 18 77 23.59 39 TWD 98 TSH -9.97 18 77 23.82 39 TWD 98 TSH -9.97 18 77 24.06 38 TWD 98 TSH -9.97 18 77 24.21 38 TWD 98 TSH -9.97 18 77 24.14 37 TWD 98 TSH -9.97 18 77 23.77 38 TWD 98 TSH -9.97 18 77 23.22 38 TWD 98 TSH -9.97 18 77 22.59 37 TWD 98 TSH -9.97 18 77 21.94 38 TWD 98 TSH -9.97 18 77 21.64 41 TWD 97 TSH -9.97 18 77 21.93 41 TWD 97 TSH -9.97 18 77 22.9 40 TWD 97 TSH -9.97 18 77 24.06 39 TWD 98 TSH -9.97 18 77 24.71 38 TWD 98 TSH -9.96 18 77 24.8 39 TWD 98 TSH -9.96 18 77 24.77 39 TWD 98 TSH -9.96 18 77 24.66 39 TWD 98 TSH -9.96 18 77 24.52 39 TWD 98 TSH -9.96 18 77 24.4 39 TWD 98 TSH -9.96 18 77 24.35 39 TWD 98 TSH -9.96 18 77 24.36 38 TWD 98 TSH -9.96 18 77 24.4 38 TWD 98 TSH -9.96 18 77 24.43 38 TWD 98 TSH -9.96 18 77 24.48 38 TWD 98 TSH -9.96 18 77 24.5 38 TWD 98 TSH -9.96 Page 5 of 10

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator C ROW COL VOLTS DEG IND °/oTW LOCATION 18 77 24.44 38 TWD 98 TSH -9.96 18 77 24.34 38 TWD 98 TSH -9.96 18 77 24.1 38 TWD 98 TSH -9.99 18 77 6.45 46 MCI TSH -6.51 18 77 11.37 49 SCl TSH -7.09 18 77 12.97 22 SCl TSH -9.86 19 63 0.6 33 PID TSH 0.02 19 63 0.93 29 SAI TSH 0.02 19 63 0 0 TWD 0 TSH -0.04 19 63 0.3 34 TWD 96 TSH -0.01 19 63 0.59 35 TWD 93 TSH 0.01 19 63 0.17 23 TWD 65 TSH 0.05 19 63 0 0 TWD 0 TSH 0.07 21 53 0.2 145 GEO TSH 0.13 21 65 3.78 37 PID TSH -10.58 21 65 0 0 TWD 0 TSH -10.49 21 65 0.97 24 TWD 71 TSH -10.48 21 65 1.25 29 TWD 89 TSH -10.48 21 65 1.81 33 TWD 100 TSH -10.48 21 65 2.39 33 TWD 100 TSH -10.48 21 65 2.71 33 TWD 100 TSH -10.48 21 65 2.95 34 TWD 99 TSH -10.48 21 65 3.19 34 TWD 99 TSH -10.48 21 65 3.53 34 TWD 99 TSH -10.48 21 65 3.88 34 TWD 99 TSH -10.48 21 65 4.15 33 TWD 100 TSH -10.48 21 65 4.12 35 TWD 99 TSH -10.48 21 65 3.78 35 TWD 99 TSH -10.48 21 65 3.26 36 TWD 99 TSH -10.48 21 65 2.87 32 TWD 100 TSH -10.48 21 65 2.8 33 TWD 100 TSH -10.48 21 65 2.57 32 TWD 100 TSH -10.48 21 65 2.24 32 TWD 100 TSH -10.48 21 65 1.76 32 TWD 100 TSH -10.48 21 65 1.29 30 TWD 92 TSH -10.48 21 65 0.98 23 TWD 68 TSH -10.48 21 65 0.89 22 TWD 64 TSH -10.48 21 65 0.86 21 TWD 61 TSH -10.48 21 65 0 0 TWD 0 TSH -10.48 21 65 4 38 SCI TSH -10.58 21 101 3.22 33 MCI TSH -4.25 21 101 2.59 32 PID TSH -4.25 21 101 0 0 TWD 0 TSH -4.59 21 101 0.39, 45 TWD 95 TSH -4.59 21 101 0.84 37 TWD 98 TSH -4.59 21 101 1.1 32 TWD 100 TSH -4.58 21 101 1.06 33 TWD 100 TSH -4.58 21 101 1 36 TWD 99 TSH -4.58 21 101 0.97 36 TWD 99 TSH -4.58 21 101 1 35 TWD 99 TSH -4.58 21 101 0.76 38 TWD 98 TSH -4.58 21 101 0.43 46 TWD 94 TSH -4.58 Page 6 of 10

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator C ROW COL VOLTS DEG IND %TW LOCATION 21 101 0.22 43 TWD 96 TSH -4.58 21 101 0 0 TWD 0 TSH -4.58 21 101 0 0 TWD 0 TSH -4.63 21 101 0.22 36 TWD 99 TSH -4.63 21 101 0.33 40 TWD 97 TSH -4.63 21 101 0.56 45 TWD 95 TSH -4.63 21 101 1.01 43 TWD 96 TSH -4.63 21 101 1.3 41 TWD 97 TSH -4.63 21 101 1.4 40 TWD 97 TSH -4.63 21 101 1.55 39 TWD 98 TSH -4.63 21 101 1.62 38 TWD 98 TSH -4.63 21 101 1.55 34 TWD 99 TSH -4.63 21 101 1.33 34 TWD 99 TSH -4.63 21 101 1.02 38 TWD 98 TSH -4.63 21 101 0.9 37 TWD 98 TSH -4.63 21 101 0.96 35 TWD 99 TSH -4.63 21 101 0.88 34 TWD 99 TSH -4.63 21 101 0.65 38 TWD 98 TSH -4.63 21 101 0.37 41 TWD 97 TSH -4.63 21 101 0 0 TWD 0 TSH -4.63 22 101 3.23 43 MCI TSH -7.04 22 101 3.98 38 PID TSH -7.04 22 101 0 0 TWD 0 TSH -7.12 22 101 0.3 24 TWD 68 TSH -7.12 22 101 0.52 28 TWD 83 TSH -7.12 22 101 0.81 30 TWD 90 TSH -7.12 22 101 1.06 28 TWD 83 TSH -7.12 22 101 1.11 31 TWD 94 TSH -7.12 22 101 1.03 30 TWD 90 TSH -7.12 22 101 0.94 28 TWD 83 TSH -7.12 22 101 0.83 25 TWD 72 TSH -7.12 22 101 0.68 20 TWD 55 TSH -7.12 22 101 0.56 17 TWD 45 TSH -7.11 22 101 0 0 TWD 0 TSH -7.11 22 101 0 0 TWD 0 TSH -7.14 22 101 0.57 28 TWD 83 TSH -7.14 22 101 0.61 30 TWD 90 TSH -7.14 22 101 0.76 32 TWD 100 TSH -7.14 22 101 1.05 34 TWD 99 TSH -7.14 22 101 1.45 35 TWD 99 TSH -7.14 22 101 1.88 36 TWD 99 TSH -7.14 22 101 2.25 36 TWD 99 TSH -7.14 22 101 2.55 36 TWD 99 TSH -7.14 22 101 2.83 35 TWD 99 TSH -7.14 22 101 3.07 35 TWD 99 TSH -7.14 22 101 3.27 36 TWD 99 TSH -7.14 22 101 3.5 37 TWD 99 TSH -7.14 22 101 3.74 37 TWD 99 TSH -7.14 22 101 3.82 37 TWD 99 TSH -7.14 22 101 3.61 37 TWD 99 TSH -7.13 22 101 3.17 37 TWD 99 TSH -7.13 22 101 2.63 38 TWD 98 TSH -7.13 Page 7 of 10

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator C ROW COL VOLTS DEG IND %TW LOCATION 22 101 2.13 38 TWD 98 TSH -7.13 22 101 1.7 37 TWD 99 TSH -7.13 22 101 1.45 38 TWD 98 TSH -7.13 22 101 0.99 39 TWD 98 TSH -7.13 22 101 0.63 41 TWD 97 TSH -7.13 22 101 0.42 41 TWD 97 TSH -7.13 22 101 0.34 33 TWD 100 TSH -7.13 22 101 0 0 TWD 0 TSH -7.13 23 84 0.47 36 PID TSH 0.07 23 84 0 0 TWD 0 TSH -0.01 23 84 0.19 49 TWD 72 TSH 0.02 23 84 0.39 44 TWD 79 TSH 0.04 23 84 0.45 43 TWD 80 TSH 0.07 23 84 0.45 41 TWD 83 TSH 0.1 23 84 0.28 37 TWD 90 TSH 0.13 23 84 0.1 19 TWD 51 TSH 0.16 23 84 0 0 TWD 0 TSH 0.18 23 84 0.51 36 SAI TSH 0.07 23 104 0.48 138 MBM TSH 2.82 25 18 0.2 44 GEO TSH 0.02 27 57 0 0 TWD 0 TSH 0.05 27 57 0.23 2 TWD 5 TSH 0.05 27 57 0.29 1 TWD 3 TSH 0.05 27 57 0.25 2 TWD 5 TSH 0.05 27 57 0 0 TWD 0 TSH 0.05 27 57 0.24 16 PID TSH 0.12 27 57 0.3 20 SCI TSH 0.12 29 20 0.22 51 GEO TSH -0.03 29 69 8.11 43 PID TSH -5.68 29 69 0 0 TWD 0 TSH -5.75 29 69 0.73 69 TWD 79 TSH -5.75 29 69 0.84 59 TWD 89 TSH -5.75 29 69 0.99 55 TWD 91 TSH -5.75 29 69 1.27 50 TWD 94 TSH' -5.75 29 69 1.87 44 TWD 96 TSH -5.75 29 69 2.9 46 TWD 96 TSH -5.75 29 69 4.16 48 TWD 95 TSH -5.75 29 69 5.52 49 TWD 94 TSH -5.75 29 69 6.68 48 TWD 95 TSH -5.75 29 69 7.48 46 TWD 96 TSH -5.75 29 69 7.6 46 TWD 96 TSH -5.75 29 69 7.05 46 TWD 96 TSH -5.75 29 69 6.16 47 TWD 95 TSH -5.75 29 69 5.36 49 TWD 94 TSH -5.75 29 69 5.16 49 TWD 94 TSH -5.75 29 69 5.6 48 TWD 95 TSH -5.75 29 69 6.01 46 TWD 96 TSH -5.75 29 69 5.62 46 TWD 96 TSH -5.75 29 69 4.37 47 TWD 95 TSH -5.75 29 69 2.94 50 TWD 94 TSH -5.75 29 69 2.23 50 TWD 94 TSH -5.75 29 69 2.52 46 TWD 96 TSH -5.74 Page 8 of 10

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator C ROW COL VOLTS DEG IND %TW LOCATION 29 69 3.3 46 TWD 96 TSH -5.74 29 69 3.99 44 TWD 96 TSH -5.74 29 69 4.38 44 TWD 96 TSH -5.74 29 69 4.45 44 TWD 96 TSH -5.74 29 69 4.33 44 TWD 96 TSH -5.74 29 69 4.17 43 TWD 97 TSH -5.74 29 69 3.76 42 TWD 97 TSH -5.74 29 69 3.2 41 TWD 97 TSH -5.74 29 69 2.31 42 TWD 97 TSH -5.74 29 69 1.41 40 TWD 98 TSH -5.74 29 69 0.85 45 TWD 96 TSH -5.74 29 69 0 0 TWD 0 TSH -5.74 29 69 4 42 TWD 97 TSH -5.74 29 69 8.09 44 SCl TSH -5.68 30 93 0 0 TWD 0 TSH -4.23 30 93 0.2 37 TWD 98 TSH -4.23 30 93 0.5 30 TWD 92 TSH -4.23 30 93 0.75 28 TWD 85 TSH -4.23 30 93 0.87 28 TWD 85 TSH -4.23 30 93 0.8 28 TWD 85 TSH -4.23 30 93 0.58 29 TWD 89 TSH -4.23 30 93 0.53 21 SCl TSH -6.91 30 93 1.08 30 SCI TSH -4.07 30 93 0.9 31 PID TSH -4.07 30 93 0.43 23 PID TSH -6.91 30 93 0.3 31 TWD 96 TSH -4.23 30 93 0.11 34 TWD 99 TSH -4.23 30 93 0 0 TWD 0 TSH -4.23 30 93 0 0 TWD 0 TSH -6.95 30 93 0.13 31 TWD 96 TSH -6.94 30 93 0.2 27 TWD 82 TSH -6.94 30 93 0.32 21 TWD 61 TSH -6.94 30 93 0.33 23 TWD 68 TSH -6.94 30 93 0.2 28 TWD 85 TSH -6.94 30 93 0.09 30 TWD 92 TSH -6.94 30 93 0 0 TWD 0 TSH -6.94 34 13 0.77 12 GEO TSH -0.07 36 46 0 0 TWD 0 TSH -4.83 36 46 0.14 51 TWD 92 TSH -4.83 36 46 0.35 37 TWD 98 TSH -4.83 36 46 0.67 41 TWD 97 TSH -4.83 36 46 1.02 39 TWD 98 TSH -4.83 36 46 1.29 38 TWD 98 TSH -4.83 36 46 1.37 36 TWD 99 TSH -4.83 36 46 1.26 37 TWD 98 TSH -4.83 36 46 0.96 37 TWD 98 TSH -4.83 36 46 0.57 39 TWD 98 TSH -4.83 36 46 0.2 25 TWD 75 TSH -4.83 36 46 0.09 20 TWD 58 TSH -4.83 36 46 0 0 TWD 0 TSH -4.83 36 46 1.57 37 PID TSH -5.1 36 46 1.58 37 MCI TSH -5.1 Page 9 of 10

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator C ROW COL VOLTS DEG IND %TW LOCATION 37 75 0 0 TWD 0 TSH -0.07 37 75 0.32 27 TWD 80 TSH -0.04 37 75 0.35 42 TWD 81 TSH -0.01 37 75 0.29 2 TWD 5 TSH 0.02 37 75 0 0 TWD 0 TSH 0.06 37 75 0.37 36 PID TSH -0.02 37 75 0.52 31 SAI TSH -0.02 40 91 0.12 130 GEO TSH 0.02 40 92 0.25 120 GEO TSH -0.01 43 22 0.72 38 GEO TSH -0.02 45 29 0.28 89 GEO TSH -0.1 47 39 0 0 TWD 0 TSH -0.05 47 39 0.16 4 TWD 11 TSH -0.05 47 39 0.14 2 TWD 5 TSH -0.05 47 39 0.11 2 TWD 5 TSH -0.05 47 39 0.09 1 TWD 3 TSH -0.05 47 39 0.09 2 TWD 5 TSH -0.05 47 39 0 0 TWD 0 TSH -0.05 47 39 0.22 21 PID TSH -0.04 47 39 0.3 21 SCI TSH -0.04 49 29 0.21 83 GEO TSH -0.03 53 78 1.02 90 MBM TSH 2.18 54 37 0.46 38 GEO TSH 0.02 55 50 0.34 89 GEO TSH -0.09 55 55 0.96 104 MBM TSH 2.47 Page 10 of 10

ULNRC-04823 March 12, 2003 Page 20 Listing of Steam Generator Tube Imperfections Callaway Refuel 12 Outage Steam Generator D

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 3 1.13 95 DFS 04C 1.28 6 5.81 87 MBM 06H 14.01 6 2.94 81 MBM 03H 5.19 8 9.07 179 DNG TSH 18.97 10 0.95 81 DFS 04H 10.28 10 2.39 78 MBM 04H 12.22 11 2.41 184 DNG 06C 5.11 12 3.47 174 DNG TSC 17.93 12 2.72 79 MBM 03C 21.33 13 4.42 180 DNT 07H 0.17 15 2.02 81 MBM 06C 32.69 23 7.65 84 MBM 06H 33.65 23 7.7 81 MBM 06H 35.25 26 3.81 86 MBM 03H 30.78 33 3.08 76 MBM 01C 5.27 33 0.6 58 DFS TSC 1.54 34 1.29 107 DFS 01C 25.53 34 0.53 85 DFS TSC 2.83 34 1.12 103 DFS TSC 2.35 37 3.18 175 DNT 07H 0.26 37 1.32 115 DFS 05C 1.67 37 1.47 113 DFS 05C 2.66 37 3.44 79 MBM 04C 36.76 37 2.5 76 MBM 04C 34.53 38 0.57 99 DFS TSC 5.22 43 3.3 77 MBM TSC 5.33 44 3.43 83 MBM TSC 32.1 47 6.84 180 DNT 07H -0.09 50 1.19 98 DFS 06H 26.45 51 3.27 185 DNG TSH 16.61 53 3 82 MBM 04H 23.69 53 1.18 95 DFS 04H 2.39 53 2.75 84 MBM 03H 34.45 53 2.07 84 MBM 04H 31.75 58 5.82 82 MBM 02H 26.61 63 3.17 72 MBM 02H 27.93 68 3.72 86 MBM 06C 25.97 68 3.6 85 MBM 06C 22.53 68 4.68 87 MBM 06C 17.79 68 3.99 89 MBM 06C 14.39 70 2.97 79 MBM 01C 8.64 78 6.46 181 DNT 05C -0.68 78 4.42 182 DNG 04C 39.22 78 1.7 76 DFS 01H 3.61 78 5.07 86 MBM 04H 35.46 78 3.74 41 MBM 05H 5.58 78 4.03 80 MBM 05H 19.63 78 3.29 181 DNT 05H -0.37 79 1.56 124 DFS 01C 31.46 79 2.34 61 MBM 05C 9.96 80 2.91 88 MBM 03C 1.33 Page 1 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 1 80 2.81 79 MBM 03C 9.02 1 80 2.12 181 DNG 04H 6.85 1 82 5.66 183 DNG 04C 6.26 1 82 2.41 66 MBM 04C 8.26 1 82 2.58 183 DNG 02H 4.84 1 83 0.46 115 DFS TSC 1.03 1 86 3.69 79 MBM 02C 22.46 1 89 2.56 82 MBM TSC 8.47 1 89 2.55 87 MBM 04H 24.98 1 89 3.42 81 MBM 04H 34.72 1 90 4.43 174 DNT FBC -0.33 1 90 3.41 75 MBM 04H 30.09 1 91 4.48 170 DNT FBC -0.39 1 93 2.88 82 MBM 04C 27.67 1 93 2.19 75 MBM 06H 1.65 1 98 6.12 179 DNT 07C -0.5 1 98 4 182 DNT 07H -0.61 1 99 2.31 185 DNG 06C 20.15 1 102 1.16 71 DFS 01C 12.22 1 104 6.05 87 MBM 05C 7.35 1 105 1.17 111 DFS TSC 11.82 1 105 1.66 111 DFS TSC 10.56 1 105 0.87 106 DFS TSC 8.25 1 109 0.98 16 DFS 06C 12.3 1 114 2.28 184 DNG 03C 28.04 1 116 2.3 176 DNG TSH 18.93 1 118 21.26 178 DNG TSC 18.87 1 119 5.33 179 DNG 04H 32.88 1 119 8.69 178 DNG TSC 18.83 1 120 6.27 176 DNG TSC 18.8 1 122 5.49 176 DNG TSH 18.77 1 122 4.05 172 DNG TSH 14.23 1 122 3.04 171 DNG TSH 19.17 1 122 15.6 180 DNG TSC 9.28 1 122 0.48 95 DFS TSC 4.21 2 8 2.94 81 MBM TSC 3.61 2 16 3.36 85 MBM 06H 9.01 2 26 3.05 81 MBM 03H 29.6 2 28 7.48 182 DNG 06C 36.48 2 32 2.47 106 DFS 01 H 25.68 2 33 2.53 81 MBM 05H 8.68 2 33 2.18 184 DNG 01C 8.14 2 34 3.32 85 MBM 02H 3.97 2 34 1.02 90 DFS TSC 2.49 2 36 4.37 79 MBM 01H 19.04 2 36 0.63 84 DFS TSC 2.11 2 36 2.66 81 MBM 05C 36.37 2 44 0.94 104 DFS 03C 13.19 2 52 1.42 99 DFS TSC 23.1 2 54 2.24 88 MBM 03H 20.18 2 55 1.53 102 DFS TSH 32.57 2 58 0.54 114 DFS TSC 26.07 Page 2 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 2 59 2.06 86 DFS 03H 0.99 2 70 2.42 87 MBM 06C 16.34 2 70 3.16 89 MBM 05C 38.88 2 70 2 84 MBM 06H 14.84 2 74 0.93 116 DFS 06C 8.88 2 74 1.04 104 DFS 04C 30.87 2 74 1.16 97 DFS 02C 7.84 2 74 1.12 115 DFS 01C 8.05 2 79 0.97 114 DFS 04C 10.7 2 79 1.39 111 DFS 02C 18.72 2 79 2.94 86 MBM 02C 12.69 2 79 3.64 88 MBM 01C 37.49 2 79 2.61 80 MBM 02H 10.24 2 80 6.1 83 MBM TSH 5.55 2 82 2.57 89 MBM 05C 27.48 2 82 2.85 76 MBM TSH 34.77 2 82 3.68 85 MBM 05H 8.92 2 84 2.98 87 MBM 05C 37.66 2 84 3.51 84 MBM 05C 24.33 2 87 2.57 80 MBM 06C 22.34 2 91 2.71 80 MBM 03C 32.56 2 91 2.29 78 MBM 03C 31.43 2 92 2.61 84 MBM 01H 6.06 2 94 1.12 106 DFS 01H 19.36 2 97 1.54 114 DFS 04C 9.71 2 98 0.95 115 DFS FBC 7.64 2 99 2.95 184 DNG 04C 3.7 2 99 0.91 108 DFS 03C 16.6 2 99 0.6 104 DFS 01C 22.26 2 99 0.88 104 DFS 06H 4.46 2 100 0.89 62 DFS 05H 30.29 2 101 3.06 184 DNG 06C 31.56 2 102 2.21 53 MBM 06C 18.03 2 107 0.52 89 MBM 02C 18.66 2 107 2.32 70 MBM 02C 11.86 2 107 2.21 85 ADS 02C 18.66 2 110 3.58 72 MBM 02H 4.45 2 110 2.24 85 MBM 02H 30.4 2 110 2.32 80 MBM 04H 31.38 2 114 5.52 83 MBM 01H 2.43 2 115 2.64 84 MBM 05C 15.01 2 115 0.57 105 DFS TSC 16.49 2 116 4.42 176 DNT 07C 0.71 2 116 3.67 177 DNT 07C -0.03 2 122 0.39 82 MBM FBC -9.71 2 122 0.45 74 DFS TSC 2.59 2 122 0.64 112 DFS TSC 8.23 2 122 0.32 79 DFS TSC 9.79 2 122 0.27 109 DFS TSC 10.29 3 3 0.59 94 DFS 01H 3.62 3 6 2.34 171 DNT 07H 0.2 3 6 2.14 170 DNT 07H 0.55 Page 3 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 3 17 3.11 186 DNG TSH 10.54 3 17 4.14 184 DNG TSH 9.46 3 23 3.14 89 MBM 06C 2.53 3 24 2.57 90 DFS 05H 32.35 3 30 5.56 81 MBM 02H 20.67 3 33 1.04 117 DFS 03C 36.26 3 35 2.23 173 DNG 07H 5.98 3 35 4.27 185 DNG 05H 26.24 3 45 3.76 120 DFS 07H 9.94 3 47 4 61 MBM 02H 3.13 3 47 1.54 45 DFS 02H 10.43 3 54 2.37 83 MBM 03H 9.22 3 57 3.06 87 MBM 03C 27.09 3 58 4.21 86 MBM 03H 36.67 3 58 2.41 79 MBM TSC 11.98 3 58 2.63 74 MBM 04C 29.57 3 58 1.96 92 MBM TSC 20.2 3 60 2.08 85 MBM 05H 21.17 3 63 2.58 88 MBM 02H 13.24 3 63 2.21 85 MBM 01H 23.92 3 71 3.16 120 DFS TSC 28.47 3 71 8.89 77 MBM 05H 1.72 3 73 0.39 72 DFS 05C 20.08 3 74 2.35 75 MBM 04C 2.12 3 74 2.02 82 MBM 01C 35.22 3 75 1.38 79 DFS 03H 33.05 3 76 2.94 89 MBM 06C 23.27 3 76 2.32 87 MBM 06H 37.51 3 78 3.99 89 MBM 06C 32.61 3 78 2.56 89 MBM 06H 4.18 3 81 1.26 107 DFS 01H 7.92 3 83 2.74 183 DNG 01C 9.36 3 83 2.9 184 DNG TSC 23.17 3 85 2.48 112 DFS 03C 7.14 3 86 3.06 82 MBM 06H 30.44 3 86 2.53 77 MBM 06H 28.83 3 87 3.56 88 MBM TSH 28.34 3 87 2.93 88 MBM 03H 1.57 3 95 1.26 109 DFS FBC 5.79 3 96 2.73 86 MBM 02H 32.05 3 97 2.19 77 MBM 05H 2.27 3 105 2.05 88 MBM 02C 30.56 3 120 5.8 85 MBM 02C 4.74 3 120 6.38 82 MBM FBC 4.75 3 121 2.7 79 MBM 02H 16.39 4 4 2.87 186 DNG 03C 30.17 4 5 2.25 82 MBM 03H 25.47 4 18 2.46 82 MBM 06H 27.66 4 34 5.95 178 DNG 07H 11.68 4 39 2.76 187 DNG 03H 33.21 4 39 2.21 186 DNG 03H 34.33 4 42 2.44 86 MBM 05C 14.95 Page 4 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 4 42 4.87 89 MBM 05C 33.76 4 50 2.47 85 MBM TSH 3.2 4 50 2.67 88 MBM 06H 26.65 4 50 0.47 102 MBM TSH 2.73 4 52 4.04 89 MBM 06H 4.69 4 54 5.93 90 MBM 05H 19.79 4 54 2.56 90 MBM 05H 24.46 4 54 2.24 90 MBM 05H 27.27 4 54 2.93 61 MBM 06H 38.87 4 54 3.11 87 MBM 03C 15.86 4 61 2.52 46 MBM 07H 11.61 4 73 1.56 112 DFS 01H 22.53 4 73 1.65 117 DFS 06C 11.05 4 74 2.53 185 DNG 03H 4.01 4 75 2 78 MBM TSC 29.22 4 76 3.44 77 MBM 01H 7.81 4 76 2.3 82 MBM 01H 36.69 4 76 3.34 77 MBM 02H 17.03 4 76 1.84 112 DFS 06C 35.98 4 82 1.11 117 DFS 05C 25.49 4 82 2.47 82 MBM 05C 12.76 4 83 4.06 82 MBM TSC 31.96 4 83 1.77 111 DFS 04C 12.5 4 83 2.39 85 MBM 04C 8.52 4 86 1.19 115 DFS 05H 37.31 4 89 1.46 111 DFS 05C 22.06 4 89 1.35 130 DFS 02C 33.05 4 92 3.28 183 DNG 06H 4.21 4 93 3.95 82 MBM 03C 35.68 4 104 2.48 187 DNG 02H 27.12 4 104 4.47 185 DNG 06H 2.56 4 108 4.27 74 MBM TSH 7.15 4 112 3.42 80 MBM TSC 4.94 4 113 2.7 69 MBM 06C 31.72 4 121 2.48 180 DNG 07H 9.64 4 121 2.31 89 MBM 02C 18.75 5 2 2.12 81 MBM 04H 16.66 5 16 0.89 112 DFS 06H 14.34 5 17 2.49 77 MBM TSH 14.67 5 24 2.66 185 DNG 02H 11.38 5 24 2.19 185 DNG 02H 12.44 5 27 2.52 187 DNG 02C 7.11 5 27 2.81 69 MBM 06H 7.04 5 27 0.86 81 DFS 06H 8.27 5 27 0.78 81 DFS 06H 9.25 5 27 1.16 76 DFS 06H 22.1 5 27 4.71 46 MBM 02C 7.36 5 32 2.15 81 MBM 02H 15.93 5 32 1.74 97 DFS FBC 1.95 5 34 5.02 182 DNG 07H 8.4 5 40 1.2 82 DFS 06C 9.86 5 40 1.45 94 DFS 06C 2 Page 5 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 5 40 1.5 84 DFS 04C 3.53 5 40 1.05 91 DFS 02C 2.37 5 47 2.07 88 MBM 04H 34.31 5 49 2.21 87 MBM 01H 10.62 5 49 3.53 86 MBM 02H 24.74 5 49 2.37 86 MBM 06H 13.4 5 50 6.46 80 MBM TSH 16.44 5 66 6.88 183 DNG 07H 21.81 5 67 4.13 180 DNG 06C 7.65 5 68 1.98 109 DFS TSH 20.41 5 70 0.53 63 PID 03C 0.55 5 70 0.54 53 SVi 03C 0.55 5 70 0.36 90 DSI 03C 0.44 5 70 0.34 0 TWD 16 03C 0.5 5 71 1.63 122 DFS 05C 3.49 5 72 2.48 89 MBM 03H 6.63 5 72 2.27 84 MBM 05H 28.79 5 74 2.65 181 DNG 04C 39.19 5 83 0.95 103 MBM 02C 7.57 5 83 2.84 75 MBM 02H 27.17 5 83 2.69 89 MBM 04C 27.98 5 83 2.4 82 MBM 03C 5.92 5 83 2.7 82 ADS 02C 7.57 5 109 2.08 68 MBM FBC 5.77 5 110 3.65 188 DNG 03H 6.1 5 114 0.97 61 DFS 06H 3.86 5 114 1.51 70 DFS 05H 37.93 5 115 2.25 87 MBM 01H 35.75 5 115 7.85 76 MBM 02C 14.43 5 116 3.1 183 DNG 02C 16.46 5 117 2.26 177 DNG 06H 20.36 5 117 5.71 67 MBM 06C 21.4 5 118 1.99 102 DFS 01H 4.87 6 6 3.46 177 DNT 07C 0.41 6 9 1.31 106 DFS 05C 6.69 6 12 2.15 88 MBM 03H 19.39 6 18 2.06 183 DNG 05H 6.84 6 21 5.17 85 MBM 05H 26.11 6 25 2.28 87 MBM 01H 31.73 6 31 2.35 186 DNG 03C 7.3 6 38 0.72 104 DFS 03C 3.62 6 38 5.2 185 DNG TSH 21.04 6 48 2.72 70 MBM 05C 10.4 6 54 2.51 80 MBM 06H 10.55 6 54 3.41 78 MBM 02H 34.05 6 56 3.5 83 MBM 06H 37.22 6 68 2.38 98 DFS 06H 25.65 6 71 0.97 104 DFS 05C 7.9 6 74 1.34 93 DFS 02C 5.19 6 77 2.29 184 DNG 01H 28.43 6 77 2.1 85 MBM 05C 21.25 6 79 2.78 81 MBM 02H 17.52 Page 6 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 6 79 2.73 76 MBM 03H 25.01 6 79 4.15 81 MBM 03C 32.17 6 81 4.53 180 DNG 07H 22.55 6 81 2.4 183 DNG 07H 4.44 6 81 3 181 DNG 07H 10.73 6 81 4.07 180 DNG 07H 17.12 6 84 2.08 88 MBM TSH 17.27 6 84 2.77 77 MBM 05H 35.37 6 90 2.02 114 DFS FBH 2.04 6 96 10.45 177 DNG 07H 21.56 6 99 2.19 56 DFS 07H 1.48 6 101 2.62 84 MBM 01H 20.74 6 102 2.72 80 MBM 03C 31.54 6 108 2.47 188 DNG 05C 22.09 6 108 5.76 85 MBM 05C 22.71 6 118 2.63 184 DNG 02C 10.4 6 119 2.01 190 DNG 03H 27.31 7 4 1 112 DFS 03C 14.98 7 6 2.96 86 MBM 03C 14.7 7 8 2.49 78 MBM 04H 24.19 7 15 2.77 185 DNG 06H 11.82 7 15 2.04 184 DNG 06C 7.13 7 20 0.6 69 DFS 03C 7.95 7 26 1.33 57 DFS 01C 28.67 7 27 2.32 79 MBM 04H 7.69 7 30 1.62 110 DFS 04C 19.21 7 35 2.63 79 MBM 01H 35.38 7 41 1.54 115 DFS TSC 22.84 7 42 3.08 81 MBM 03H 18.32 7 45 2.82 186 DNG 02C 15.76 7 56 6.69 183 DNG 06C 34.83 7 56 2.45 85 MBM TSH 34.27 7 56 1.96 89 MBM 01H 35.98 7 56 2.52 84 MBM 03H 15.88 7 56 3.03 83 MBM 03H 29.22 7 56 2.16 85 MBM 06H 31.59 7 56 2.02 77 MBM 05C 17.95 7 58 3.71 77 MBM TSH 7.92 7 61 0.98 111 DFS TSC 29.73 7 62 0.24 41 GEO TSH 0 7 64 4.21 88 MBM 06H 12.83 7 65 0.78 106 DFS 01C 13.36 7 66 4.48 54 MBM 07H 15.6 7 68 0.16 61 GEO TSH 0.05 7 74 1.84 97 MBM 07C -3.45 7 74 4.1 181 DNT 01C 0.57 7 74 6.79 66 MBM 07H 13.6 7 74 1.44 59 DFS 01C 2.57 7 74 5.01 86 ADS 06C 36.8 7 75 1.13 113 DFS 03C 6.12 7 76 2.44 89 MBM 06C 34.99 7 76 2.93 88 MBM 06C 30.53 Page 7 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 7 82 2.53 82 MBM 04C 7.64 7 82 3.48 85 MBM 04C 9.67 7 86 3.3 181 DNG 07H 0.97 7 89 2.13 87 MBM 05C 20.34 7 106 1.62 98 DFS 06C 8.72 7 110 3.14 82 MBM 03H 5.44 7 113 0.95 108 DFS FBC 9.45 7 118 2.47 175 DNG 06H 26.58 7 118 2.96 178 DNG 06H 27.61 7 118 1.9 81 MBM 02H 36.54 7 118 0.88 102 DFS 04H 33.58 7 118 2.58 82 MBM 03C 30.2 8 6 4.26 181 DNG AV6 12.02 8 7 3.19 188 DNG 03C 23.24 8 13 7.43 183 DNG 06H 39.71 8 13 2.37 183 DNG 05C 1.02 8 17 2.29 45 DFS 03H 31.15 8 24 2.53 89 MBM 05H 28.43 8 27 2.67 75 MBM 05H 18.95 8 32 8.65 63 MBM 07H 4.32 8 32 3.84 86 MBM 05C 1.99 8 40 2.15 79 MBM 04C 18.99 8 42 2.03 74 MBM 02C 37.65 8 48 2.19 81 MBM 06H 8.65 8 48 2.47 84 MBM 06H 21.85 8 48 4.09 88 MBM 06H 28.71 8 54 4.49 85 MBM 06H 15.1 8 54 4.41 82 MBM 06H 27.56 8 54 3.9 84 MBM 06H 31.42 8 63 2.44 87 MBM 03H 5.31 8 73 1.2 59 DFS 06H 21.52 8 73 1.77 72 DFS 06H 25.17 8 73 1.33 51 DFS 06H 22.32 8 73 0.8 57 DFS 06H 32.81 8 73 1.58 92 DFS TSC 7.26 8 75 4.39 79 MBM 03H 28.88 8 75 5.13 83 MBM 05C 36.64 8 75 5 80 MBM 05C 34.5 8 76 2.17 183 DNG 03H 37.84 8 76 1.63 53 DFS TSH 15.93 8 78 1.28 115 DFS 05C 3.34 8 79 0.71 0 TWD 28 AV1 0 8 79 0.54 0 TWD 24 AV6 0 8 79 2.12 183 DNG 06C 18.79 8 79 3.4 117 DFS 02H 28.2 8 79 0.63 0 TWD 26 AV2 0 8 79 0.64 0 TWD 27 AV5 0 8 81 2.67 86 MBM 05H 35.68 8 81 2.37 111 DFS 06C 39.5 8 81 2.87 86 MBM 04C 19.84 8 82 2.97 90 MBM 06C 24.76 8 82 2.33 89 MBM 06C 21.29 Page 8 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 8 82 2.93 67 MBM 06C 4.9 8 82 2.38 79 MBM 05C 37.87 8 89 5.77 180 DNG 05C 32.4 8 89 4.5 179 DNG 05C 20.14 8 89 2.53 175 DNG 05C 18.92 8 99 1.22 93 DFS 01H 11.64 8 99 5.49 57 MBM 01C 35.01 8 102 1.67 105 DFS 02C 28.35 8 102 3.1 78 MBM 02C 22.21 8 102 0.95 110 DFS 01C 12.43 8 103 2.14 77 MBM 01H 30.3 8 116 0.75 108 DFS 01H 10.66 8 116 0.98 117 DFS 04H 9.02 8 116 2.58 80 MBM 06C 34.75 8 119 1.7 64 DFS TSH 5.3 9 14 2.01 149 DDS 06C 8.94 9 41 2.16 74 MBM TSH 28.54 9 47 2.76 84 MBM 04C 31.01 9 50 4.18 82 MBM AV1 3.32 9 51 3.33 89 MBM AV1 3.81 9 52 0.86 51 MBM TSH 0.85 9 74 2.19 186 DNG 06C 3.79 9 75 3.26 71 MBM 01H 29.19 9 75 3.79 47 MBM 01C 1.36 9 75 4.05 75 MBM TSC 22.95 9 81 2.41 186 DNG TSH 5.69 9 104 2 109 DFS 04H 23.9 9 104 0.94 111 DFS 04H 26.24 9 109 0.86 74 DFS 03C 15.75 9 117 3.21 176 DNG 06H 34.94 9 117 7.31 179 DNG 06C 36.43 9 117 2.73 181 DNG 06C 35.47 9 117 4.18 187 DNG AV6 11.76 9 117 3.22 178 DNG AV6 3.81 9 117 2.98 179 DNG 07H 6.77 9 117 4.03 179 DNG AVl 5.56 9 117 3.05 179 DNG AV1 -0.81 9 118 3.56 180 DNG 07H 5.39 9 118 4.41 180 DNG 07H 11.76 9 118 4.14 180 DNG AV6 2.6 10 2 2.7 176 DNG 06C 6.84 10 10 2.18 82 MBM TSH 6.54 10 13 2.71 79 MBM 01H 4.9 10 18 2.96 81 MBM FBH 6.48 10 27 2.69 186 DNG 02H 11.91 10 35 0.19 40 GEO TSH 0.07 10 35 3.41 185 DNG TSH 16.84 10 36 2.79 186 DNG 07H 20.62 10 47 0.64 89 DFS 02C 6.55 10 51 3.31 86 MBM TSH 2.15 10 52 2.2 185 DNG 06C 9.75 10 54 3.38 185 DNG 06C 39.64 Page 9 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 10 56 4.58 89 MBM 01H 2.6 10 59 2.37 89 MBM 03H 33.73 10 60 5.45 185 DNG TSC 13.99 10 60 5.14 84 MBM 06H 19.66 10 62 0.43 154 GEO TSH -0.05 10 62 6.11 182 DNG 07H 3.65 10 72 0.68 116 DFS 01C 14.56 10 79 3.17 184 DNG 05H 35.85 10 80 2.36 54 MBM TSH 6.88 10 80 3.44 78 MBM TSH 30.08 10 80 1.3 101 DFS 01H 33.36 10 80 1.97 72 DFS 03H 3.96 10 81 5.16 187 DNG 06C 5.44 10 81 4.68 90 MBM TSC 29 10 85 2.61 78 MBM 07H 11.47 10 85 3.34 82 MBM 03C 34.47 10 85 5.61 80 MBM 03C 30.16 10 87 2.63 117 DFS 06C 36.72 10 87 2.07 118 DFS 06C 11.73 10 98 2.55 185 DNG AV1 5.7 10 106 3.05 84 MBM 01H 10.68 10 119 3.02 78 MBM FBC 7.19 11 22 0.83 109 DFS 05C 29.68 11 36 0.14 62 GEO TSH -0.03 11 37 3.5 182 DNG 02H 10.99 11 45 3.19 77 MBM 02C 18.8 11 47 2.12 76 MBM 06C 5.6 11 52 5.26 89 MBM 03H 7.57 11 56 1.84 86 DFS 01H 9.2 11 70 1.13 108 DFS 02H 16.16 11 70 0.49 107 DFS 03C 18.23 11 75 2.38 183 DNG 03H 25.74 11 75 2.71 87 MBM 03H 25.17 11 76 3.32 89 MBM 06C 35.84 11 86 2.17 81 MBM 01C 10.7 11 87 2.29 86 MBM 01C 11.33 11 88 3.35 84 MBM 06C 4.84 11 90 2.82 184 DNG 03H 37.93 11 90 2.01 76 MBM TSH 17.17 11 101 0.97 107 DFS 03C 37.6 11 107 1.84 87 DFS 01C 19.24 11 111 0.76 74 DFS TSC 4.53 11 120 3.87 178 DNG 07H 21.86 11 120 4.84 178 DNG 07H 28.19 11 120 4.82 178 DNG 07H 34.28 12 4 7.9 84 MBM 01H 35.13 12 4 5.82 86 MBM 02H 4.83 12 4 7.24 85 MBM 02H 1.87 12 4 6.3 84 MBM 04C 31.37 12 4 6.45 71 MBM 02H -0.91 12 5 3.76 83 MBM 02C 20.71 12 7 3.3 93 MBM 01H 8.69 Page 10 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 12 10 4.13 84 MBM 06H 21.14 12 15 2.95 182 DNG 05H 37.07 12 24 2.79 86 MBM 05H 27.09 12 39 4.89 89 MBM 01C 3.43 12 42 6.95 84 MBM 02C 32.19 12 48 2.33 84 MBM TSH 24.61 12 50 2.02 78 MBM 02C 8.53 12 54 0.75 96 DFS 03C 39.01 12 55 2.24 82 MBM 01H 19.51 12 59 2.41 84 MBM 06H 4.81 12 71 1.68 102 DFS 04C 24.69 12 73 0.98 36 SAI TSH 0.06 12 73 0 0 TWD 0 TSH -0.06 12 73 0.23 26 TWD 77 TSH -0.04 12 73 0.29 28 TWD 85 TSH -0.02 12 73 0.38 32 TWD 100 TSH 0 12 73 0.6 32 "TWWD 100 TSH 0.01 12 73 0.99 34 TWD 98 TSH 0.03 12 73 1.19 32 TWD 100 TSH 0.05 12 73 0.58 24 TWD 70 TSH 0.07 12 73 0 0 TWD 0 TSH 0.09 12 73 1.17 32 PID TSH 0.06 12 80 4.22 80 MBM 04C 18.1 12 80 3.16 71 MBM 01C 34.04 12 80 7.45 79 MBM 01C 3.91 12 81 1.8 86 MBM TSC 1.38 12 81 2.12 102 DFS TSC 1.33 12 83 1.17 109 DFS TSC 26.2 12 84 2.65 113 DFS 04C 17.99 12 84 1.39 95 DFS 02C 20.8 12 84 2.55 134 DFS AV1 14.7 12 96 4.93 182 DNG 06C 22.84 12 96 8.99 181 DNG 06C 23.94 12 96 4.59 182 DNG 06C 24.44 12 96 7.8 182 DNG 06C 25.6 12 106 2.98 186 DNG 06C 7.28 12 106 2.53 80 MBM 06C 7.77 12 106 2 76 MBM FBC 8.06 12 120 3.9 177 DNT 07C 0.54 12 121 3.3 183 DNG 05H 13.73 13 5 4.88 108 DFS 01H 3.67 13 5 4.32 89 MBM 06C 20.7 13 7 6.45 88 MBM 05C 38.93 13 9 5.47 84 MBM 05C 13.18 13 9 6.22 83 MBM 04C 28.07 13 10 5.79 185 DNG AV6 9.5 13 10 6.9 82 MBM TSC 13.01 13 13 2.92 188 DNG 02C 21.36 13 13 2.1 119 DFS TSC 5.68 13 14 8.11 85 MBM 06H 15.08 13 15 3.48 90 MBM 05H 26.85 13 18 3.1 184 DNG 05H 2.78 Page 11 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 13 30 2 78 MBM 01H 27.53 13 34 2.36 187 DNG 01H 1.8 13 36 1.66 102 DFS 01H 24.53 13 36 5.27 89 MBM 01H 29.38 13 36 3.48 72 MBM 01H 32.44 13 36 3.61 114 DFS 01H 36.83 13 36 5.75 89 MBM 02H 6.59 13 46 7.15 82 MBM 05H 7.84 13 48 2.57 86 MBM 06H 10.26 13 50 4.89 86 MBM 01H 2.14 13 51 5.64 85 MBM 01H 7.64 13 51 2.38 87 MBM 01H 9.94 13 51 3.61 81 MBM 01C 4.59 13 60 2 70 MBM 04C 26.37 13 61 3.55 103 DFS TSC 28.19 13 62 8.92 83 MBM 07H 2.93 13 72 3.42 182 DNG 06C 16.83 13 72 2.78 74 MBM 02H 28.36 13 77 3.1 182 DNG 06C 3.92 13 77 3.66 182 DNG 05C 4.85 13 77 2.98 80 MBM TSH 22.81 13 82 3.93 82 MBM 01C 8.25 13 92 2.64 65 MBM 02C 18.32 13 93 2.43 79 MBM FBC 17.19 13 95 2.03 86 MBM 03H 23.6 13 101 6.37 185 DNG TSC 5.07 13 101 1.62 126 DFS FBC 15.93 13 106 1.24 79 DFS 05C 33.01 13 106 0.75 96 MBM 06C -6.97 13 112 1.31 96 DFS 01 H 28.29 13 118 2.03 191 DNG 01H 29.42 13 119 2.65 180 DNT 07C 0.69 13 119 3.41 179 DNT 07C -0.36 13 120 3.11 180 DNT 07C 0.57 13 120 2.94 180 DNT 07C -0.44 13 120 4.08 75 MBM 02C 34.85 14 15 1.37 85 DFS 01C 29.29 14 21 2.75 80 MBM 01H 24.31 14 26 0.91 99 DFS 03C 11.74 14 31 0.1 91 GEO TSH -0.09 14 31 1.08 112 DFS 05C 34.44 14 40 2.13 81 MBM TSH 26.62 14 42 2.2 76 MBM 05C 4.18 14 49 2.14 71 MBM 01H 10.65 14 53 0.39 88 DFS 01H 29.96 14 53 2.18 81 MBM 02H 23.27 14 53 2.99 80 MBM 02H 33.34 14 54 6.67 77 MBM 06C 5.23 14 56 4.81 85 MBM 03H 35.66 14 65 0.36 164 GEO TSH -0.05 14 69 3.6 183 DNG AV6 12.6 14 70 1.3 91 DFS 04C 8.57 Page 12 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %IoTW LOCATION 14 76 4.09 81 MBM 05C 0.04 14 79 2.31 79 MBM 04C 13.46 14 83 2.37 78 MBM 01C 8.89 14 86 4.15 85 MBM 02H 4.09 14 86 3.6 86 MBM 03H 2.38 14 88 2.16 110 DFS 04C 22.6 14 103 2.49 187 DNG 05H 6.04 14 104 0.78 91 DFS 02H 33.94 14 104 2.03 89 MBM 07H 8.28 14 104 2.04 85 MBM 06C 21.13 14 105 0.94 83 DFS 04H 26.42 14 113 3.63 184 DNG 05H 6.6 14 120 3.09 179 DNG 07H 18.01 14 120 2.12 178 DNT 07C -0.42 14 120 3.38 176 DNT 07C 0.71 15 24 3.81 92 MBM TSH 13.22 15 24 5.4 88 MBM 05H 19.43 15 33 2.46 85 MBM 06H 2.14 15 33 0.39 32 GEO TSH -0.08 15 34 3.62 84 MBM FBH 15.14 15 35 4.41 81 MBM TSC 1.61 15 37 0.69 88 DFS FBH 7.89 15 39 2.12 72 MBM 04C 12.44 15 56 0.79 96 DFS 06C 5.83 15 59 7.68 77 MBM TSH 21.28 15 65 2.07 86 MBM TSC 26.38 15 66 0.15 0 TWD 6 AV6 0 15 73 6.27 86 MBM 05H 16.88 15 76 2.42 90 MBM 01C 10.19 15 83 3.21 78 MBM 03H 11.37 15 87 2.14 184 DNG 01C 19.79 15 98 2.8 189 DNG 05H 28.61 15 100 3.36 188 DNT 01H 0.42 15 101 2.4 57 MBM 05H 22.28 15 107 0.97 66 DFS 04H 15.46 15 107 1.32 109 DFS 04H 8.83 15 107 1.51 49 DFS 04H 19.21 15 107 1.23 69 DFS 04H 21.78 15 107 3 73 MBM 04H 23.53 15 107 2.28 88 MBM 04H 25.42 15 109 3.13 77 MBM 02C 28.83 15 110 3.58 88 MBM 01H 20.14 15 110 5.08 81 MBM 06C 9.74 15 110 3.65 79 MBM 02C 31.86 15 110 2.44 72 MBM FBC 14.97 15 116 2.07 79 MBM 06C 38.39 15 119 11.26 79 MBM 03C 2.08 15 120 5.32 181 DNT 07C 0.65 15 120 4.12 181 DNT 07C -0.44 16 6 2.66 50 MBM 07H 9.47 16 9 3.39 183 DNG 04C 18.66 16 10 2.02 183 DNG FBC 10.48 Page 13 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 16 27 9.25 85 MBM 02H 11.08 16 27 6.61 90 MBM 06C 28.37 16 27 4.26 79 MBM 02C 35.14 16 35 4.53 182 DNG 06C 36.13 16 35 3.07 184 DNG 06H 35.15 16 36 2.97 185 DNG 06H 35.28 16 46 2.66 181 DNT 06H 0.64 16 57 0.26 0 TWD 15 AV6 -0.02 16 63 0.46 20 GEO TSH 0.03 16 68 2.22 115 DFS 03H 31.92 16 68 1.7 98 DFS 05H 21.95 16 80 1.88 102 DFS TSC 7.79 16 82 1.18 110 DFS 03H 33.73 16 84 1.27 58 DFS TSH 4.02 16 87 2.08 187 DNG 06H 38.89 16 93 3.19 187 DNG FBH 7.09 16 93 2.81 187 DNG FBH 8.47 16 95 2.03 185 DNG 03H 2.25 16 101 2.52 88 MBM 02H 29.21 16 101 7.26 87 MBM 05H 14.21 16 104 4.67 183 DNG TSC 8.78 16 104 3.45 84 MBM 03H 38.25 16 105 2.68 184 DNT 01H -0.5 16 105 0.62 111 DFS 01H 8.67 16 105 0.79 111 DFS 06C 12.53 16 105 2.27 117 DFS 03C 10.85 16 106 1.64 110 DFS 04C 12.74 16 106 2.12 82 MBM 04C 9.81 16 113 2.08 67 MBM 01C 4.11 16 114 12.24 183 DNG FBH 1.6 16 115 8.76 182 DNG FBH 1.58 16 116 2.02 80 MBM 04H 16.58 16 119 2.99 183 DNG TSC 7.88 16 119 2.75 180 DNT 07C -0.41 16 119 2.32 176 DNT 07C 0.62 16 120 5.98 176 DNT 07C 0.66 16 120 3.4 179 DNT 07C -0.39 17 4 2.51 178 DNT 07H -0.35 17 4 2.41 185 DNG 06H 39.25 17 5 3.14 185 DNG 06H 33.46 17 5 6.02 185 DNG 06H 34.58 17 5 3.24 184 DNG 06C 29.6 17 5 7.77 82 MBM 02H 25.75 17 5 3.29 98 DFS AV1 2.32 17 5 3.22 103 DFS AV1 4.73 17 11 2.25 84 MBM 06H 2.02 17 13 3.23 80 MBM 03C 31.78 17 15 2.02 87 MBM 02C 3.46 17 18 0.92 101 DFS 02H 21.15 17 40 0.55 93 DFS 06C 22.41 17 41 2.56 72 MBM 06C 15.94 17 44 4.06 84 MBM 04H 22.39 Page 14 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 17 44 4.82 77 MBM 04H 28.09 17 44 7.22 79 MBM 04H 33.78 17 44 3.59 87 MBM 04H 35.44 17 44 2.47 87 MBM 04H 36.86 17 44 2.5 66 MBM 05H 2.03 17 49 3.43 89 MBM 01H 8.73 17 49 7.38 89 MBM 01H 0.87 17 56 0.21 102 GEO TSH 0.17 17 57 5.46 119 DFS 03C 15.13 17 59 2.58 186 DNG 01 H 7.09 17 64 0.18 134 GEO TSH 0.17 17 65 4.39 116 DFS 05C 2.78 17 71 7.68 85 MBM TSH 6.04 17 71 6.06 81 MBM 01H 8.09 17 73 4.16 89 MBM 01H 9.66 17 83 2.8 178 DNG AV6 4.77 17 83 2.16 176 DNT AV2 -0.52 17 85 2.83 178 DNG AV6 3.28 17 85 2.28 182 DNG AV2 5.44 17 87 2.44 176 DNG AV6 3.2 17 88 2.09 177 DNG AV6 3.08 17 89 2.36 178 DNG AV6 3.45 17 100 2.24 78 MBM 02C 37.84 17 104 2.05 182 DNG 01H 35.49 17 104 2.09 182 DNG 03C 8.57 17 104 1.13 100 DFS 05H 18.75 17 104 3.21 113 DFS 05H 21.72 17 104 0.56 104 DFS 05H 25.36 17 104 1.64 104 DFS 05H 31.06 17 104 1.08 77 DFS 05H 32.46 17 104 1.1 121 DFS 05H 35.39 17 104 1.13 100 DFS 05H 36.39 17 105 1.38 114 DFS 04H 39.24 17 107 2.15 82 MBM 01C 15.89 17 118 2.39 180 DNT 07C -0.33 17 118 2.83 174 DNT 07C 0.63 17 118 2.94 98 DFS FBC 17.2 17 119 5.89 175 DNT 07C 0.61 17 119 3.17 178 DNT 07C -0.44 18 4 2.65 181 DNT 07H 0.5 18 11 3.37 183 DNG 04C 13.22 18 18 2.28 90 MBM 04H 10.82 18 24 0.63 58 DFS 02H 6.42 18 26 3.01 78 MBM 05C 16.64 18 26 3.32 65 MBM FBH 9.07 18 28 2.72 79 MBM 04C 19.23 18 41 0.96 107 DFS 06C 25.52 18 41 3.8 70 MBM TSC 8.95 18 47 2.52 88 MBM 03H 7.58 18 51 2.22 88 MBM 02H 38.72 18 84 4.38 77 MBM 02H 18.94 18 88 2.46 186 DNG 02H 33.42 Page 15 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 18 111 2.92 186 DNG 06H 38.97 18 111 6.83 180 DNT 07H -0.58 18 118 2.06 180 DNG AV6 9.27 18 119 4.55 182 DNT 07C -0.37 18 119 3.8 182 DNT 07C 0.71 19 7 0.61 108 DFS 03H 28.31 19 8 3.62 73 MBM 05C 13.47 19 17 2.91 85 MBM 02H 20.2 19 17 6.24 89 MBM 03H 7.75 19 17 4.34 83 MBM 01C 7.21 19 19 4.06 89 MBM 02H 16.67 19 19 2.96 81 MBM AV1 7.4 19 22 3.15 111 DFS 03H 32.65 19 23 2.8 84 MBM FBC 7.28 19 27 1.89 107 DFS 01H 29.25 19 28 3.58 88 MBM TSC 7.28 19 28 2.43 86 MBM 04C 36.05 19 33 2.33 89 MBM 06C 36.82 19 33 2.1 76 MBM 01C 10.71 19 36 0.23 35 GEO TSH 0 19 37 0.63 78 DFS TSH 13.61 19 53 2.96 80 MBM 05C 9.98 19 54 3.02 79 MBM TSH 25.86 19 56 1.05 115 DFS 01C 7.42 19 69 4.4 113 DFS 06H 10.67 19 69 6.14 71 MBM AV6 3.83 19 73 0.85 108 DFS 01H 11.04 19 78 7.7 74 MBM 01C 6.67 19 83 1.27 106 DFS 01H 8.31 19 89 2.22 113 DFS 01H 14.96 19 94 1.79 110 DFS 02H 31.49 19 97 5.73 180 DNT 02H -0.78 19 98 0.69 98 DFS 06C 36.83 19 104 2.72 79 MBM 02C 22.21 19 109 2.91 182 DNG 06H 35.19 19 113 4.74 87 MBM 04C 7.97 19 113 2.76 89 MBM TSC 8.63 19 115 2.27 187 DNG 03H 36.69 19 118 4.32 179 DNT 07C 0.56 19 118 2.23 181 DNT 07C -0.35 19 119 2.18 182 DNT 07C -0.31 20 5 8.33 183 DNG 04H 4.74 20 5 2.22 184 DNG 04H 3.63 20 5 2.97 184 DNG 01H 18.98 20 10 2.77 87 MBM 01H 37.89 20 1i1 3.06 83 MBM 01H 8.85 20 14 0.69 57 MBM FBC 5.14 20 14 0.92 103 DFS 03H 20.68 20 14 0.76 114 DFS FBC 5.14 20 15 2.63 75 MBM TSH 8.89 20 15 2.68 78 MBM FBH 4.94 20 21 2.24 85 MBM 04C 27.83 Page 16 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 20 24 0.62 106 DFS 02C 4.23 20 24 1.44 118 DFS FBC 10.61 20 25 2.26 65 MBM 01H 7.57 20 29 2.62 77 MBM 05C 28.77 20 32 2.32 56 MBM FBC 7.04 20 44 8.98 75 MBM 05C 17.55 20 46 2.87 188 DNG 03H 32.83 20 46 4.48 88 MBM 05H 16.41 20 46 2.85 78 MBM 05C 9.79 20 49 3.09 72 MBM 01H 17.15 20 53 2.94 87 MBM 05C 18.34 20 65 2.87 188 DNG 01H 37.36 20 65 0.97 112 DFS 04C 4.98 20 69 2.58 85 MBM 03H 14.36 20 72 6.94 82 MBM 01H 29.2 20 75 6.35 80 MBM 06C 30.53 20 75 2.75 86 MBM 01H - 24.53 20 75 7.39 93 MBM AV1 5.28 20 79 5.99 117 DFS 06C 13.27 20 80 2.5 191 DNG 01H 28.98 20 80 2.14 186 DNT 06H -0.24 20 97 0.53 62 DSS 06C -0.56 20 99 3.52 179 DNT 07C 0.45 20 109 4.63 187 DNG 06H 30.99 20 109 9.23 186 DNG 06H 32.06 20 109 3.17 183 DNG 06H 35.5 20 109 3.21 181 DNT 07H -0.72 20 109 3.59 182 DNT 07H 0.35 20 109 3.96 181 DNT 07C -0.62 20 109 2.79 186 DNG 06C 38.98 20 109 3.85 186 DNG 06C 37.4 20 118 3.37 183 DNT 07C 0.64 20 118 3.17 180 DNT 07C -0.33 21 6 3.82 182 DNG 01C 19.56 21 13 0.99 101 DFS 05C 23.64 21 27 2.52 84 MBM 01C 3.69 21 27 2.61 82 MBM 04C 6.81 21 30 2.79 188 DNG 02C 19.77 21 33 6.44 64 MBM AV5 7.99 21 48 3.26 84 MBM 06H 14.28 21 52 2.39 189 DNG 05C 25.83 21 53 2.42 190 DNG 01C 13.25 21 59 6.57 83 MBM 01C 23.78 21 59 2.75 89 MBM 01C 19.08 21 59 4.9 87 MBM TSC 16.65 21 59 3.78 83 MBM 04C 31.26 21 63 7.59 84 MBM 02H 35.14 21 63 2.94 82 MBM 03H 7.92 21 63 4.82 82 MBM 01C 1.24 21 63 3.87 81 MBM TSC 4.15 21 63 2.73 115 DFS TSC 1.65 21 64 3.59 78 MBM 05C 37.82 Page 17 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 21 66 6.01 184 DNG 02H 8.89 21 66 3.95 183 DNG 05H 19.64 21 79 0.32 44 GEO TSH 0.03 21 89 3.17 186 DNG 03H 0.88 21 90 0.75 86 DFS 02H 19.6 21 109 2.34 184 DNG 06H 33.77 21 109 3.89 183 DNG 06H 34.87 21 110 2.42 179 DNT 07H 0.45 21 118 3.94 179 DNT 07C 0.43 21 118 3.16 181 DNT 07C -0.29 22 5 0.26 0 TWD 12 AV1 0.48 22 7 4.46 185 DNG AV6 17.49 22 7 2.36 189 DNG 03H 28.83 22 12 1 72 MBM 04C -11.35 22 12 3.5 184 DNG 03C 28.71 22 12 5.35 79 ADS 03C 28.9 22 17 1.83 107 DFS 04C 16.12 22 18 3.37 63 DFS 07H 10.03 22 18 1.86 83 DFS 07H 12.02 22 18 2.16 83 MBM 03H 14.19 22 25 4.29 84 MBM 01H 37.5 22 30 2.09 78 MBM 06C 15.44 22 51 2.71 190 DNG 01H 1.81 22 51 2.27 190 DNG 05H 2.05 22 51 11.86 182 DNG 04H 0.97 22 64 3.39 86 MBM 03H 4.96 22 66 3.51 185 DNG 06C 34.33 22 66 7.82 181 DNT 07H 0.11 22 66 2.91 183 DNG 06H 34.09 22 66 11.99 183 DNG 06C 35.5 22 66 3.92 89 MBM 02H 20.24 22 66 2.48 85 MBM 04H 23.23 22 66 1.73 107 DFS 05H 3.38 22 68 3.06 188 DNG 04H 17.97 22 71 2.43 185 DNG 04C 27.41 22 79 1.18 111 DFS TSH 1.95 22 79 0.69 83 MBM TSH 2.13 22 80 0.87 106 DFS 02C 31.56 22 80 0.99 94 DFS 03H 28.92 22 81 1.7 113 DFS FBH 16.88 22 84 2.8 83 MBM 05H 14.25 22 104 1.27 113 DFS 01 H 27.47 22 108 1 107 DFS 02H 22.12 22 108 1.32 76 DFS 02H 24.54 22 109 4.17 182 DNG 06H 34.38 22 109 2.49 185 DNG 06H 35.5 22 109 6.67 187 DNG 06H 36.62 22 109 8.41 187 DNG 06H 37.88 22 109 2.32 181 DNT 07H 0.22 22 109 6.15 183 DNG 06C 34.56 22 109 4.78 186 DNG 06C 33.51 22 113 1.15 128 DFS 01C 20.96 Page 18 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND  %/oTW LOCATION 22 116 3.2 180 DNT 07C 0.73 22 116 2 182 DNT 07C -0.44 22 117 3.37 179 DNT 07C 0.47 22 117 2.81 181 DNT 07C -0.31 22 117 2.31 189 DNG 01H 27.8 22 117 2.66 118 DFS 04H 5.99 22 117 1.03 94 DFS 03C 36.25 22 118 4.26 180 DNT 07C 0.47 22 118 3.47 183 DNT 07C -0.29 23 13 0.8 78 DFS 01H 19.77 23 33 3.33 185 DNG 06H 4.93 23 46 1.1 89 DFS 01H 37.56 23 47 0.88 75 MBM TSH 1.51 23 48 3.72 82 MBM 03C 37.79 23 50 2.53 183 DNG 02H 35.48 23 51 0.59 82 DFS TSC 13.84 23 51 0.74 112 DFS TSC 7.25 23 52 2.44 187 DNG 06H 5.28 23 52 3.8 182 DNT 07H -0.55 23 54 2.74 185 DNG 06C 36.71 23 54 2.47 190 DNG 06C 37.99 23 54 3.96 187 DNG 06C 39.11 23 54 2.48 189 DNG 06H 35.06 23 54 9.08 183 DNG 06H 36.23 23 54 4.64 184 DNG 06H 38.71 23 54 6.79 182 DNG 06H 39.11 23 54 2.69 186 DNG 06H 38.06 23 54 2.62 184 DNG 06H 31.35 23 54 2.2 185 DNG 06H 30.93 23 55 2.4 122 DFS 02C 25.39 23 58 10.76 77 MBM 02C 34.43 23 60 3.86 188 DNG 05C 38.05 23 73 1.25 116 DFS 03C 35.96 23 74 0.46 6 GEO TSH -0.01 23 74 2.63 86 MBM 04C 33.02 23 90 3.77 182 DNG 07C -1.05 23 92 3.42 184 DNG 04H 35.47 23 95 1.01 115 DFS 05C 17.74 23 95 2.38 83 MBM 05C 16.43 23 96 2.14 113 DFS 06C 13.88 23 100 2.96 89 MBM 05H 23.23 23 107 2.59 80 MBM 01C 10.67 23 110 2.91 115 DFS 06C 9.37 23 113 1.39 115 DFS FBC 18.06 23 116 2.41 182 DNT 07C 0.47 23 116 3.03 179 DNT 07C -0.29 23 117 2.51 180 DNT 05C -0.32 23 117 3.19 180 DNT 07C 0.68 23 117 2 182 DNT 07C -0.42 24 7 0.09 0 TWD 5 AV1 0 24 23 3.73 188 DNG TSH 13.32 24 27 1.24 109 DFS 05H 4.82 Page 19 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 24 31 3.07 87 MBM 02H 14.77 24 32 2.17 82 MBM 03C 13.44 24 33 3.13 77 MBM FBC 3.24 24 35 5.37 89 MBM 03H 29.96 24 35 5.54 89 MBM 04H 16.2 24 37 2.37 187 DNG 01H 23.51 24 43 4.2 86 MBM 04H 32.25 24 46 2.03 186 DNG 05C 13.35 24 48 3.07 187 DNG 01C 20.38 24 48 5.64 89 MBM 04H 24.56 24 51 2.58 185 DNG 02C 15.14 24 51 2.9 80 MBM 03C 19.55 24 52 4.16 88 MBM 02H 20.43 24 52 4.63 86 MBM 05H 18.06 24 54 3.14 182 DNT 07H 0.42 24 68 0.93 101 DFS 02H 5.44 24 68 2.12 79 MBM 06C 13.7 24 70 2.69 187 DNG TSC 35.23 24 72 2.47 185 DNG 06C 12.75 24 72 2.96 75 MBM 06C 29.98 24 95 2.04 186 DNG TSH 13.3 24 96 5.31 81 MBM 04C 37.15 24 109 5.7 187 DNG 06H 36.02 24 110 0.7 71 DFS 01C 26.76 24 111 2.86 113 DFS 02H 5.17 24 112 2.02 179 DNT 07C 0.66 24 113 2.77 180 DNT 07C 0.49 24 113 2.01 179 DNT 07C -0.51 24 114 2.44 180 DNT 07C 0.66 24 115 2.28 183 DNT 07C 0.47 24 115 2.72 179 DNT 07C -0.31 24 117 3.93 179 DNT 07C 0.48 24 117 4.31 182 DNT 07C -0.26 24 117 3.5 180 DNT 05C 0.63 24 117 2.07 182 DNT 05C -0.36 25 10 2.23 184 DNG 06H 19.72 25 14 7.24 85 MBM 02H 37.82 25 17 1.43 105 DFS 01H 3.05 25 23 1.85 117 DFS 01C 27.84 25 25 5.57 82 MBM FBC 5.36 25 31 8.84 78 MBM 04H 18.99 25 33 7.77 87 MBM 04H 8.73 25 33 3.92 85 MBM 01C 26.21 25 36 2.51 82 MBM AV2 6.14 25 38 3.78 187 DNG 04H 24.23 25 49 1.61 121 DFS TSC 19.24 25 49 3.03 182 DNG 03C 4.96 25 49 2.43 82 MBM 01C 8.59 25 49 2.08 87 MBM FBC 1.55 25 52 3.53 111 DFS 05C 18.76 25 62 0.69 92 DFS 01C 16.65 25 62 0.36 33 GEO TSH 0.03 Page 20 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 25 65 0.66 28 GEO TSH 0 25 67 6.71 183 DNG 03H 5.08 25 71 5.11 182 DNT 06C -0.37 25 72 2.74 73 MBM 04H 11.51 25 72 2.62 85 MBM 03H 33.46 25 82 0.12 0 TWD 8 AV2 0.47 25 82 0.17 0 TWD 11 AV5 -0.25 25 89 2.01 77 MBM FBH 9.1 25 102 3.37 76 MBM 04C 2.28 25 106 4.86 88 MBM 02H 13.96 25 109 9.49 182 DNG 06H 39.34 25 109 2.8 184 DNG 06H 38.21 25 112 3.11 179 DNT 07C 0.54 25 114 4.48 181 DNT 07C 0.58 25 114 3.39 181 DNT 07C -0.48 25 115 2.67 178 DNT 07C 0.73 25 115 4.06 181 DNT 07C -0.49 25 116 2.3 182 DNT 05C 0.75 25 116 4.25 182 DNT 07C -0.37 25 116 5.54 180 DNT 07C 0.7 26 7 2.23 89 MBM 05H 14.21 26 8 0.25 119 MBM 04C 6.36 26 8 2.04 77 MBM 01H 29.28 26 8 4.25 57 MBM 03H 5.73 26 8 2.28 70 MBM 04H 13.51 26 8 3.03 89 MBM 04H 15.88 26 8 2.59 81 MBM 04H 17.84 26 8 2.77 81 MBM 04H 22.72 26 8 0.23 0 TWD 13 AVI 0 26 8 3.91 86 MBM 06C 3.95 26 8 0.84 82 DFS FBC 17.34 26 8 2.78 86 ADS 04C 6.36 26 10 3.78 66 MBM 04H 31.81 26 11 2.9 60 MBM 07H 1.22 26 20 3.55 79 MBM 06H 6.64 26 20 1.32 94 DFS 02C 24.75 26 22 4.46 186 DNG FBC 11.29 26 29 1.55 109 DFS 05C 29.76 26 48 2.84 87 MBM FBH 16.34 26 50 3.11 185 DNG TSH 5.68 26 66 0.63 99 DFS 04H 17.43 26 68 0.18 0 TWD 10 AV5 0 26 68 0.11 0 TWD 7 AV2 0 26 69 2.79 77 MBM FBH 6.71 26 77 2.2 77 MBM TSH 4.14 26 77 0.8 127 MBM TSH 4.27 26 82 2.48 186 DNG 02C 33.21 26 86 4.31 184 DNG AV5 2.18 26 86 4.62 185 DNG AV2 18 26 86 3.03 185 DNG 06C 3.05 26 93 6.22 83 MBM 01C 36.33 26 93 2.7 78 MBM AV6 18.66 Page 21 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 26 103 2.16 89 MBM TSC 9.16 26 105 1.33 56 NQS TEH 6.76 26 105 1.29 56 NQS TEH 7.51 26 109 2.65 184 DNG 06H 36.09 26 109 3.81 186 DNG 06H 37.21 26 109 2.41 70 MBM 04H 37.98 26 110 2.7 181 DNT 07C 0.59 26 110 2.16 179 DNT 07H -0.75 26 112 2.24 182 DNT 07C 0.73 26 112 0.17 0 TWD 10 AV2 0.09 26 112 0.84 84 DFS 05C 31.14 26 113 2.76 181 DNT 07C 0.45 26 113 5.14 179 DNT 07C -0.31 26 113 1.79 117 DFS 04H 37.23 26 114 4 181 DNT 07C -0.42 26 114 3.87 183 DNT 07C 0.7 26 115 3.57 179 DNT 07C -0.29 26 116 4.39 183 DNT 07C 0.47 26 116 5.1 181 DNT 07C -0.28 26 116 2.52 181 DNT 05C -0.33 26 116 2.33 183 DNT 04C 0.69 26 116 0.39 0 TWD 20 AV1 0 27 8 0.56 0 TWD 23 AVI 0.27 27 8 0.51 0 TWD 22 AV1 -0.34 27 8 0.25 0 TWD 13 AV6 -0.11 27 11 3.18 79 MBM 03H 13.44 27 13 1.16 107 DFS 01H 34.39 27 15 1.37 96 DFS 05H 2.48 27 20 0.78 99 DFS 06C 22.62 27 33 1.72 105 DFS 01H 13.19 27 41 4.5 91 MBM 03H 18.91 27 41 2.48 90 MBM 03H 24.91 27 41 0.99 97 DFS AV6 5.26 27 41 2.14 64 MBM 02C 17.59 27 41 1.47 95 DFS 02C 10.23 27 60 0.13 0 TWD 7 AV2 0 27 60 0.16 TWD 10 AV5 0 27 60 0.2 TWD 12 AV6 0 27 60 1.13 80 DFS 05C 26.91 27 68 1.49 106 DFS 02C 32.29 27 73 1.59 105 DFS 03H 10.32 27 78 3.54 183 DNT 07H 0.45 27 78 2.23 184 DNT 07H -0.66 27 79 0.18 0 TWD 11 AV2 0.25 27 79 0.25 0 TWD 14 AV5 -0.1 27 81 3.46 84 MBM FBC 7.68 27 84 0.25 0 TWD 12 AV5 -0.15 27 91 4.49 112 DFS 04C 25.05 27 92 1.04 110 DFS 01H 28.33 27 99 1.61 121 DFS 02C 35.29 27 110 2.35 188 DNG 06H 38.6 27 110 3.37 180 DNT 07C 0.7 Page 22 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 27 110 5.12 179 DNG 07H -0.97 27 112 3.44 182 DNT 07C 0.48 27 112 2.51 182 DNT 07C -0.34 27 113 3.99 183 DNT 07C -0.4 27 113 3.94 181 DNT 07C 0.73 27 114 5.39 182 DNT 07C 0.6 27 114 5.62 179 DNT 07C -0.42 27 114 0.12 0 TWD 8 AV5 0 27 115 0.23 0 TWD 13 AV6 -0.51 27 115 4.48 183 DNT 07C -0.37 27 115 4.29 180 DNT 07C 0.68 28 8 0.35 0 TWD 15 AV1 0.2 28 8 0.6 0 TWD 22 AV6 0 28 17 3.47 182 DNG 06H 23.16 28 22 2.18 72 MBM 05C 19.68 28 23 4.87 102 DFS AV6 3.52 28 32 1.08 104 DFS 05H 6.14 28 34 2.31 86 MBM 01C 30.07 28 36 1.29 107 DFS TSH 5.57 28 36 2.11 86 MBM 03C 24.57 28 38 4.28 71 MBM 06C 16.63 28 41 1.06 105 DFS 02C 24.43 28 43 0.94 94 DFS 03H 20.96 28 43 2.76 74 MBM 04C 35.59 28 43 2.71 117 DFS 01C 24.45 28 44 6.71 84 MBM 04H 19.3 28 44 9.83 80 MBM 05H 28.33 28 44 6.22 88 MBM 05H 34.14 28 44 4.12 87 MBM 05H 38.08 28 44 3.24 83 MBM 07H 7.44 28 44 6.07 77 MBM 07H 11.51 28 44 3.24 79 MBM 07H 16.29 28 44 3.8 76 MBM AV1 4.29 28 44 7.65 78 MBM 06C 34.33 28 51 2.13 184 DNG 04H 1.26 28 57 11.1 88 MBM 06H 19.74 28 57 4.2 110 DFS 01C 30.5 28 62 0.31 27 GEO TSH 0 28 62 2.21 86 MBM 02H 27.92 28 68 2.73 188 DNG 01H 7.35 28 70 3.01 110 DFS FBC 0.96 28 75 3.01 186 DNG 06C 9.05 28 84 2.57 82 MBM 03H 34.18 28 88 1.07 102 DFS 01C 22.32 28 91 1.85 100 DFS 05C 7.05 28 96 2.59 68 MBM 05H 6.04 28 103 0.78 79 DFS 04H 6.05 28 103 2.47 84 MBM 04C 2.93 28 105 1.33 89 DFS 01H 38.41 28 105 0.93 101 DFS 02H 8.53 28 106 1.92 116 DFS 02H 9.1 28 111 2.55 181 DNT 07C -0.52 Page 23 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 28 112 6.52 181 DNT 07C 0.56 28 112 3.77 182 DNT 07C -0.51 28 113 5.68 182 DNT 07C 0.47 28 113 8.46 178 DNT 07C -0.33 28 114 7.62 181 DNT 07C -0.51 28 114 6.37 182 DNT 07C 0.61 28 115 2.79 181 DNT 07C 0.54 28 115 7.78 179 DNT 07C -0.35 28 115 2.02 182 DNT 05C 0.66 28 115 3.17 180 DNT 05C -0.32 28 115 2.06 178 DNT 04C -0.42 29 11 2.33 72 MBM 01 H 20.29 29 22 1.52 102 DFS 02H 2.01 29 30 2.18 67 MBM 01C 27.9 29 30 2.06 71 MBM 01C 17.33 29 33 1.57 103 DFS FBH 14.72 29 33 1.94 119 DFS 02H 18.37 29 38 2.01 119 DFS 06C 33.81 29 44 2.37 179 DNG 06C 37.82 29 44 3.11 180 DNG 06C 38.14 29 44 3.82 183 DNG 06C 38.9 29 44 9.48 181 DNG 07C -1.42 29 44 6.64 179 DNT 07C -0.71 29 44 4.29 181 DNT 07C -0.34 29 44 4.33 182 DNG 07H 1.24 29 44 2.51 176 DNT 07H 0.53 29 44 8.67 179 DNT 07H -0.11 29 44 4.7 181 DNG 07H -1.18 29 46 3.46 73 MBM 03H 9.66 29 52 2.22 184 DNG TSC 17.94 29 52 6.57 185 DNG TSC 18.93 29 57 2.81 182 DNT AV6 0.33 29 60 0.3 21 GEO TSH -0.04 29 65 3.92 185 DNG 02H 12.74 29 72 2.19 77 MBM 03H 35.91 29 82 3.66 186 DNG 05C 5.4 29 82 2.11 79 MBM 06H 7.51 29 82 1.64 28 SCl TSH -7.23 29 82 1.69 32 PID TSH -7.23 29 82 0 0 TWD 0 TSH -6.86 29 82 0.41 36 TWD 98 TSH -6.86 29 82 1.05 32 TWD 100 TSH -6.86 29 82 1.54 29 TWD 90 TSH -6.86 29 82 1.39 30 TWD 93 TSH -6.86 29 82 0.69 38 TWD 98 TSH -6.86 29 82 0.16 49 TWD 89 TSH -6.86 29 82 0 0 TWD 0 TSH -6.86 29 88 4.2 83 MBM 04C 34.06 29 88 4.21 82 MBM 04C 36.95 29 90 2.4 80 MBM 01C 3.73 29 98 1.5 115 DFS 02C 38.12 29 98 2.37 98 DFS 02C 35.4 Page 24 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 29 104 4.53 187 DNG TSC 1.06 29 105 4.27 187 DNG TSC 1.01 29 109 2.08 183 DNG 02C 28.2 29 110 3.09 180 DNT 07H 0 29 110 1.97 111 DFS TSH 12.93 29 112 5.17 182 DNT 07C 0.56 29 112 4.13 182 DNT 07C -0.45 29 113 4.35 183 DNT 07C -0.4 29 113 4.39 181 DNT 07C 0.68 29 114 5.33 183 DNT 07C 0.6 29 114 10.66 180 DNT 07C -0.48 29 114 0.11 0 TWD 7 AV5 0 29 114 0.21 0 TWD 12 AV2 0 29 114 2.1 181 DNT 05C -0.42 30 10 3.27 182 DNT 07C 0.36 30 10 0.56 0 TWD 21 AV5 0.17 30 20 3.43 186 DNG 06H 32.71 30 20 2.07 185 DNG 06C 33.74 30 21 4.92 185 DNG 06C 39.15 30 25 3.05 112 DFS 04C 7.26 30 25 3.6 83 MBM 04C 8.83 30 25 3.44 115 DFS 04C 10.97 30 25 3.89 115 DFS 04C 14.19 30 25 2.79 81 MBM 04C 24.77 30 25 4.18 74 MBM 04C 3.24 30 28 2.37 81 MBM FBH 7.95 30 28 3.23 81 MBM FBH 9.56 30 31 3.78 79 MBM 01H 39.03 30 31 5.25 70 MBM 03C 11.58 30 36 0.89 99 DFS 03H 27.51 30 39 1.15 70 DFS 02C 32.85 30 41 4.1 183 DNT 07H -0.11 30 48 9.89 184 DNG 02C 4.01 30 48 3.77 186 DNG 06H 1.01 30 53 2.36 187 DNG 02C 1.09 30 56 2.42 185 DNG 06H 14.92 30 58 1.6 110 DFS 02C 29.39 30 58 1 97 DFS 02C 31.58 30 67 0.18 0 TWD 10 AV1 0 30 69 2.46 184 DNG 06C 8.6 30 71 2.21 82 MBM 03C 15.65 30 71 1.51 115 DFS 06C 6.9 30 71 2.17 116 DFS 04H 32.8 30 74 3.49 182 DNG AV4 0.87 30 77 2.33 72 MBM 01H 9.69 30 78 0.98 115 DFS 01C 22.87 30 86 0.65 98 DFS 03H 23.35 30 88 3.1 74 MBM 01C 38.07 30 94 1.14 95 DFS 06C 25.78 30 96 2.31 107 DFS 04C 25.89 30 97 0.27 0 TWD 16 AV6 0 30 101 2.5 86 MBM 02H 32.26 Page 25 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 30 101 2.36 89 MBM 02H 33.72 30 102 1.55 105 DFS FBH 8.38 30 103 4.8 110 DFS 03H 37.48 30 103 2.28 87 MBM 01C 36.84 30 104 9.95 183 DNG TSC 1.32 30 105 5.66 185 DNG TSC 1.28 30 109 4.82 180 DNT 07C 0.52 30 110 3.87 181 DNT 07C 0.52 30 110 4.29 181 DNT 07H 0.4 30 110 2.5 181 DNT 07H -0.66 30 111 2.4 181 DNT 07C -0.52 30 111 2.51 183 DNT 07C 0.65 30 112 4.55 181 DNT 07C -0.42 30 112 4.11 181 DNT 07C 0.66 30 113 4.57 182 DNT 07C 0.51 30 113 5.37 178 DNT 07C -0.38 30 114 5.16 182 DNT 07C 0.64 30 114 8.2 179 DNT 07C -0.37 30 114 2.42 186 DNG 06C 38.03 30 114 9.68 184 DNG 06C 39.11 31 10 0.31 0 TWD 16 AV5 0 31 10 1.06 0 TWD 33 AV2 0 31 10 3.46 87 ADS FBH 5.09 31 10 0.83 128 MBM 01H -14.5 31 11 0.31 0 TWD 14 AV4 0.46 31 12 0.4 0 TWD 18 AV2 0 31 13 0.12 0 TWD 8 AV2 -0.03 31 15 1.42 71 DFS AV6 15.53 31 17 4.88 180 DNT 07C 0.39 31 23 2.49 86 MBM 01H 23.94 31 31 0.5 81 DFS 04H 18.04 31 34 4.73 181 DNT 07H 0.42 31 34 2.11 68 MBM 02H 28.77 31 43 2.42 82 MBM 01C 32.54 31 43 2.06 69 MBM 03C 6.8 31 44 2.68 186 DNG 01C 36.82 31 45 1.2 109 DFS 01C 27.28 31 53 0.7 89 DFS 03C 12.52 31 59 2.51 57 MBM 03C 17.12 31 64 1.65 104 DFS 03H 2.57 31 65 1.37 103 DFS FBC 18.22 31 68 2.01 84 MBM 03H 22.56 31 70 1.47 97 DFS 02H 35.08 31 79 2.87 90 MBM 04H 17.41 31 80 0.32 0 TWD 17 AV3 0.15 31 81 2.57 70 MBM 04C 19.6 31 83 0.13 0 TWD 7 AV6 0 31 83 0.19 0 TWD 10 AV1 0 31 83 0.28 0 TWD 14 AV2 0.24 31 83 0.15 0 TWD 8 AV5 0 31 102 3.42 75 MBM FBC 16.94 31 103 2.68 188 DNG AV3 3.54 Page 26 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 31 107 4.2 87 MBM 06C 35.29 31 110 0.17 0 TWD 11 AV3 0.05 31 110 2.42 184 DNT 07C 0.65 31 111 3.71 181 DNT 07C 0.66 31 111 0.28 0 TWD 15 AV3 0.21 31 111 2.46 183 DNT 07C -0.49 31 112 4.65 184 DNT 07C 0.52 31 112 5.97 181 DNT 07C -0.49 31 113 6.14 182 DNT 07C 0.59 31 113 0.19 0 TWD 11 AV6 -0.02 31 113 0.23 0 TWD 13 AV1 0.3 31 113 4.65 182 DNT 07C -0.47 32 11 5.5 182 DNT 07C 0.33 32 12 0.38 0 TWD 16 AV5 0.14 32 12 0.34 0 TWD 15 AV2 0.03 32 16 0.9 78 DFS 04C 35.57 32 17 6.89 180 DNT 07C 0.3 32 19 2.57 89 DFS 04H 15.98 32 20 1.23 103 DFS 06H 29.6 32 20 1.03 115 DFS 06C 16.82 32 27 1.52 95 DFS 03H 26.25 32 36 0.32 0 TWD 16 AV5 -0.22 32 48 4.1 86 MBM 02H 21.08 32 48 2.39 87 MBM 02H 26.24 32 57 2.47 57 MBM AV5 -0.41 32 62 3.19 71 MBM 01H 13.54 32 62 2.52 77 MBM 01H 15.49 32 62 3.51 70 MBM 01H 20.63 32 62 2.36 68 MBM 05H 13.57 32 67 4.25 88 MBM 06H 10.55 32 72 1.71 100 DFS FBH 6.74 32 80 2.29 89 MBM 03H 31.24 32 80 2.36 184 DNG 07H 7.51 32 82 0.15 0 TWD 8 AV4 0 32 82 0.15 0 TWD 9 AV3 0 32 92 2.1 74 MBM 04C 16.92 32 98 1.64 104 DFS 05C 13.93 32 98 2.87 120 DFS 03C 30.89 32 108 1.34 110 DFS 05H 21.75 32 110 3.12 184 DNG AV3 5.31 32 112 3.39 182 DNT 07C 0.56 32 112 2.98 180 DNT 07C -0.36 32 112 0.69 0 TWD 28 AV6 0 32 112 0.3 0 TWD 17 AV5 0 32 112 0.2 0 TWD 12 AV2 0 32 112 0.15 0 TWD 10 AV1 0 32 113 4.67 183 DNT 07C 0.49 32 113 7.35 180 DNT 07C -0.33 32 113 0.53 0 TWD 24 AV6 0 32 113 0.2 0 TWD 12 AV5 0 32 113 0.52 0 TWD 24 AV2 0 33 13 0.77 43 DFS 05C 7.7 Page 27 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 33 14 2.54 186 DNG 02C 30.94 33 17 3.55 182 DNG 06C 39.49 33 17 14.47 180 DNG 06C 35.56 33 17 5.37 182 DNG 06C 34.45 33 17 4.03 72 MBM TSH 0.46 33 21 4 76 MBM 01H 33.7 33 23 2.75 80 MBM AV6 19.4 33 34 3.08 182 DNT 07C 0.33 33 39 3.36 184 DNG 06C 34.86 33 39 6.86 184 DNG 06C 36.39 33 47 1.01 88 DFS FBH 11.33 33 52 1.17 117 DFS 01C 38.88 33 52 1.17 124 DFS 01C 26.22 33 53 1.56 99 DFS 02C 30.55 33 53 1.42 118 DFS 01C 20.06 33 53 1.19 101 DFS FBC 10.64 33 53 0.97 74 DFS FBC 4.04 33 57 2.2 79 MBM 03C 38.07 33 63 3.66 85 MBM 02C 24.4 33 64 2.58 180 DNG TSC 15.9 33 64 3.63 182 DNG TSC 7.53 33 64 2.47 182 DNG TSC 4.1 33 64 6.64 184 DNG TSC 3.06 33 68 4.44 185 DNG 01H 15.22 33 68 4.71 182 DNG 06C 22.11 33 68 2.19 183 DNG 06C 20.91 33 68 2.18 184 DNG FBH 9.07 33 70 2.48 187 DNG TSH 10.2 33 73 3.08 184 DNG FBC 5.8 33 74 6.44 86 MBM FBH 2.32 33 76 3.88 180 DNG FBC 4.89 33 76 0.85 95 DFS 03C 8.98 33 77 2.04 183 DNG 06H 29.72 33 77 4.72 182 DNG 06H 35.96 33 78 2.68 177 DNT 07H 0.52 33 79 7.89 81 MBM 04H 14.43 33 79 4.87 80 MBM 04H 1.71 33 80 4.19 78 MBM 05C 7.23 33 80 7.12 85 MBM 03H 12.04 33 82 4.94 112 DFS 01C 4.68 33 82 3 116 DFS 01C 11.93 33 82 4.73 90 MBM 07H 7.92 33 82 3.95 84 MBM 03H 13.19 33 83 4.5 86 MBM TSH 13.21 33 83 9.01 80 MBM 05C 31.98 33 89 3.7 115 DFS 05C 24.78 33 92 2.79 50 MBM AV3 7.41 33 93 0.17 0 TWD 10 AV4 -0.2 33 96 3 86 MBM 03C 23.4 33 96 2.13 87 MBM 02C 10.64 33 97 2.01 106 DFS 06C 5.03 33 97 2.68 114 DFS 06C 2.21 Page 28 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 33 97 1.48 100 DFS 05C 31.96 33 97 1.56 104 DFS 05C 29.94 33 97 2.3 103 DFS 05C 23.07 33 97 2.1 76 MBM 05C 20.7 33 97 2.7 81 MBM 05C 19.17 33 102 4.16 84 MBM 05H 34.87 33 108 1.48 103 DFS 02C 20.85 33 108 1.22 119 DFS FBC 12.54 33 108 1.47 80 DFS 03H 25.89 33 109 4.8 183 DNG 06H 35.67 33 111 1.34 73 DFS TSH 17.84 33 111 2.39 83 MBM 02C 27.99 34 13 0.64 0 TWD 25 AV3 0 34 13 0.34 0 TWD 16 AV5 0 34 13 0.63 0 TWD 25 AV4 0 34 17 2.71 86 MBM 01H 9.3 34 19 2.22 186 DNG 05H 30.45 34 21 2.76 88 MBM 02H 32.97 34 21 2.43 86 MBM 03H 25.95 34 24 1.43 68 DFS 06C 24.02 34 25 3.41 103 DFS 03C 29.86 34 29 0.56 102 DFS 06C 5.69 34 30 0.36 0 TWD 18 AV6 0.34 34 31 2.03 77 MBM TSC 15.3 34 41 2.34 185 DNG 06C 37.37 34 41 6.13 182 DNG 06C 37.83 34 41 4.38 181 DNG 06C 38.1 34 41 6.56 184 DNG 06C 38.48 34 41 3.2 87 MBM 01H 30.94 34 43 1.47 103 DFS 01C 22.14 34 49 1.3 114 DFS 02H 25.85 34 54 2.14 185 DNG TSH 15.56 34 54 2.45 185 DNG TSH 16.68 34 55 4.36 69 MBM 02C 3.69 34 59 2.91 109 DFS 01C 19.94 34 59 2.38 117 DFS 01C 20.63 34 59 1.43 119 DFS 01C 19.01 34 60 7.84 80 MBM TSH 5.08 34 64 7.36 89 MBM AV1 3.13 34 64 3.73 58 MBM AV6 2.78 34 65 2.04 189 DNG 01H 26.39 34 65 3.7 189 DNG 01H 27.45 34 65 3.48 189 DNG 01H 28.7 34 74 0.29 0 TWD 16 AV2 -0.02 34 74 0.22 0 TWD 12 AV3 0 34 74 0.15 0 TWD 9 AV4 -0.14 34 74 0.13 0 TWD 8 AV6 0.21 34 75 2.27 180 DNT 07C 0.37 34 75 3.08 180 DNT 07C -0.02 34 75 2.96 182 DNG 06C 38.02 34 75 2.04 183 DNG 06C 36.9 34 75 4.39 183 DNG 07C -1.12 Page 29 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND  %/oTW LOCATION 34 82 2.84 81 MBM 01H 27.44 34 87 2.39 89 MBM 05C 7.93 34 88 2.03 67 MBM 01C 12.29 34 90 0.31 0 TWD 14 AV3 0 34 91 0.21 67 GEO TSH -0.06 34 91 3.54 56 MBM AV6 3.57 34 92 3.16 63 MBM 02H 28.11 34 96 1.77 111 DFS AV5 8.36 34 96 1.39 96 DFS AV6 12.9 34 96 1.2 112 DFS 06C 38.57 34 97 2 188 DNG 01H 2.38 34 97 2.21 62 MBM 01C 35.54 34 101 3.06 77 MBM TSC 3.94 34 102 1.48 122 DFS 02H 4.72 34 102 2.06 73 MBM 01C 9.98 34 103 1.73 121 DFS 01C 7.9 34 106 2 181 DNG 06H 33.58 34 106 3.33 182 DNG 06H 34.76 34 111 3.94 182 DNT 07H 0.56 35 15 0.63 98 DFS 05C 35.96 35 16 1 0 TWD 33 AV3 0 35 17 0.18 0 TWD 11 AV2 0 35 17 0.9 0 TWD 32 AV3 0 35 17 0.26 0 TWD 14 AV4 0 35 17 0.78 88 DFS 05C 22.93 35 22 3.05 183 DNG 06H 6.5 35 27 0.91 100 DFS 01C 11.52 35 34 2.43 84 MBM 01H 10.88 35 37 0.26 0 TWD 13 AV4 -0.08 35 40 4.45 83 MBM FBH 10.25 35 40 3.5 90 MBM FBH 12.21 35 40 4.69 86 MBM FBH 15.52 35 40 5.15 86 MBM 04H 24 35 42 1.94 116 DFS 05C 3.71 35 42 3.34 78 MBM 03C 11.94 35 43 1.09 89 MBM 01H -0.54 35 44 3.1 185 DNG 03C 9.23 35 44 2.6 186 DNG 03C 11.7 35 44 2 187 DNG 03C 14.17 35 44 0.6 97 DFS 06H 27.52 35 60 2.45 67 MBM 04C 12.07 35 62 2.16 71 MBM 05H 37.89 35 63 2.76 79 MBM TSH 9.7 35 63 2.62 82 MBM 03H 38.42 35 63 2.82 72 MBM 04C 19.79 35 71 2.57 183 DNG 04H 4.01 35 71 4.68 183 DNG 03H 38.1 35 74 2.02 185 DNG 06H 27.46 35 80 2.4 87 MBM 04H 19.49 35 81 2.27 84 MBM 05C 6.83 35 91 3.09 54 DFS 07H 20.46 35 91 2.61 104 DFS AV2 6.07 Page 30 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 35 91 1.36 101 DFS 02C 12.67 35 93 2.67 77 DFS AV4 9.23 35 95 3.69 84 MBM 02C 16.75 35 98 2.6 83 MBM 02C 30.98 35 102 0.26 0 TWD 15 AV4 0.07 35 105 2.67 56 MBM TSC 16.09 35 108 4.66 65 MBM AVI 4.94 35 108 3.98 84 MBM AV1 6.21 35 109 2.77 184 DNG 06H 35.17 35 109 4.26 185 DNG 06H 36.3 35 109 2.83 185 DNG 06H 36.85 36 14 0.4 126 MBM FBC 7.93 36 14 1.27 106 DFS FBC 7.93 36 16 0.23 0 TWD 13 AV1 -0.03 36 20 2.82 87 MBM 04H 8.89 36 21 1.41 111 DFS 05C 13.45 36 22 3.12 89 MBM 04H 3.86 36 22 1.01 106 DFS FBC 14.99 36 25 2.01 183 DNG 01C 22.66 36 37 2.13 185 DNG 06H 38.88 36 38 0.21 41 GEO TSH 0 36 38 6.67 92 MBM 04H 30.32 36 43 0.49 28 SAI TSH -0.01 36 43 0 0 TWD 0 TSH -0.11 36 43 0.15 32 TWD 100 TSH -0.09 36 43 0.33 34 TWD 98 TSH -0.07 36 43 0.5 32 TWD 0 TSH -0.05 36 43 0.52 29 TWD 88 TSH -0.03 36 43 0.38 29 TWD 88 TSH -0.01 36 43 0.22 28 TWD 85 TSH 0 36 43 0 0 TWD 0 TSH 0.02 36 43 0.49 32 PID TSH -0.01 36 44 2.78 183 DNT 05H -0.47 36 44 4.18 183 DNG 06C 33.47 36 44 2.02 184 DNG 06C 32.36 36 50 2.98 184 DNG FBH 10.13 36 50 5.02 79 MBM 03H 23.94 36 55 2.99 184 DNG 02C 3.71 36 56 2.03 185 DNG TSH 12.8 36 56 3.17 183 DNG TSH 14.73 36 56 3.13 185 DNG TSH 15.84 36 67 4.03 80 MBM 05H 8.62 36 69 2.81 82 MBM 03C 15.22 36 72 2.56 73 MBM 07H 2.74 36 72 2.69 76 MBM 02C 30.93 36 72 2.44 77 MBM 02C 35.05 36 74 1.46 70 DFS 02H 35.9 36 79 1.58 117 DFS 01C 10.23 36 80 4.13 80 MBM AV3 0.68 36 80 0.91 98 DFS 05C 35.66 36 84 0.39 0 TWD 18 AV4 0 36 84 0.48 0 TWD 21 AV3 0 Page 31 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 36 84 3.23 70 MBM 03C 15.65 36 86 0.2 52 GEO TSH 0 36 89 0.29 0 TWD 16 AV4 -0.1 36 89 0.12 0 TWD 7 AV5 -0.07 36 93 0.39 0 TWD 18 AV4 -0.05 36 94 0.18 0 TWD 11 AV4 0 36 97 0.2 0 TWD 12 AV4 0 36 98 1.24 102 DFS AV4 5.34 36 100 2.17 181 DNT 07C 0.35 36 100 0.17 0 TWD 10 AV3 0.14 36 101 2.15 185 DNG 05C 19.62 36 101 0.17 0 TWD 10 AV6 0.12 36 101 0.19 0 TWD 11 AV5 -0.23 36 101 0.44 0 TWD 20 AV3 0 36 101 0.22 0 TWD 12 AV2 -0.21 36 105 0.26 0 TWD 14 AV5 0.16 36 105 0.33 0 TWD 17 AV3 0.14 36 105 0.17 0 TWD 10 AV1 0 36 106 0.25 0 TWD 14 AV6 0 36 106 0.41 0 TWD 20 AV5 0 36 106 0.45 0 TWD 21 AV4 0.09 36 106 0.17 0 TWD 10 AV3 0 36 106 0.22 19 TWD 12 AV1 0 36 107 1.06 102 DFS 04H 22.38 36 107 1.47 119 DFS 04H 23.66 36 107 1.16 102 DFS 04H 1.6 36 108 2.02 73 MBM 04C 2.2 36 108 2.22 86 MBM 03C 38.93 36 109 3.31 88 MBM 06H 27.78 37 16 4.03 78 MBM 05H 11.33 37 16 1.68 118 DFS 03H 26.22 37 20 3.44 80 MBM 01C 26.58 37 21 4.08 89 MBM 02H 23.22 37 30 2.02 81 MBM 05H 8.78 37 30 3.57 89 MBM 05H 20.49 37 30 2.08 77 MBM 06H 12.9 37 31 2.67 75 MBM TSC 18.2 37 39 5.01 80 MBM 05H 24.33 37 42 0.28 0 TWD 14 AV4 -0.06 37 42 0.12 0 TWD 7 AV2 0.14 37 42 1.83 117 DFS 06C 16.04 37 42 0.79 102 DFS 06C 14.96 37 43 2.22 81 MBM 02C 34.97 37 43 13.76 78 MBM 02C 31.66 37 44 0.3 0 TWD 15 AV4 0 37 44 0.69 0 TWD 27 AV3 0 37 44 0.47 0 TWD 21 AV2 0 37 44 2.47 188 DNG FBC 17.2 37 46 1.01 112 DFS TSC 12.3 37 51 2.65 182 DNT 07C 0.28 37 53 2.87 85 MBM 05H 2.41 37 54 3.26 187 DNG 04C 4.68 Page 32 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 37 55 2.57 187 DNG 04H 15.24 37 57 3.59 184 DNG 06C 36.93 37 60 3.75 77 MBM FBH 7.61 37 66 2.8 85 MBM 02C 5.14 37 69 2.56 185 DNG 06C 35.7 37 69 3.25 90 MBM 04H 38.88 37 72 0.12 0 TWD 8 AV3 -0.22 37 72 0.45 0 TWD 22 AV4 -0.35 37 72 0.16 0 TWD 10 AV5 0.1 37 72 6.02 79 MBM 02H 35.72 37 76 2.45 105 DFS TSC 0.83 37 77 2.07 184 DNG 02H 24.65 37 77 3.48 184 DNG 06H 17.49 37 77 2.94 182 DNG 01C 17.56 37 77 2.35 185 DNG AV3 4.21 37 78 2.32 80 MBM TSH 18.67 37 80 2.39 184 DNG 06C 39.17 37 80 2.23 181 DNT 07H 0.52 37 81 2.58 87 MBM TSC 3.18 37 86 1.32 105 DFS 05H 33.95 37 87 2.48 181 DNT 07C 0.35 37 91 4.17 179 DNT 07C 0.39 37 92 0.23 77 GEO TSH -0.08 37 93 0.95 79 DFS AV4 8.88 37 94 1.07 100 DFS 01C 9.67 37 94 0.92 121 DFS 01C 4.58 37 94 1.49 88 DFS 01C 8.67 37 96 0.18 0 TWD 11 AV3 0 37 96 0.18 0 TWD 11 AV2 0 37 97 3.25 85 MBM AV4 2.2 37 97 2.15 119 DFS 01C 7.53 37 98 2.24 87 MBM FBC 6.55 37 102 0.19 0 TWD 12 AV2 0 37 102 0.6 0 TWD 26 AV3 0 37 102 0.67 0 TWD 28 AV4 0 37 102 0.54 0 TWD 25 AV5 0 37 102 2.72 101 DFS AV5 11.89 37 102 0.36 0 TWD 19 AV6 0 37 104 3.25 77 MBM FBC 10.23 37 105 2.01 190 DNG 01C 1.45 37 106 3.47 189 DNG FBC 2.16 37 106 0.31 0 TWD 17 AV3 0 37 108 1.15 110 DFS 01H 13.64 38 15 3.65 181 DNT 07C 0.3 38 41 2.53 78 MBM 02H 37.64 38 43 4.86 181 DNG 06H 38.01 38 44 2.47 187 DNG 06C 33.11 38 52 3.11 185 DNG 06H 31.96 38 52 4 186 DNG 05C 30.74 38 52 3.4 185 DNG 05C 14.39 38 53 2.32 184 DNG 06C 37.76 38 53 2.74 59 MBM 02C 2.05 Page 33 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 38 55 7.28 87 MBM TSH 2.22 38 55 1.53 112 MBM TSH 2.51 38 56 7.27 184 DNG 06H 29.07 38 56 2.31 184 DNG 06H 27.96 38 60 3.35 186 DNG 06H 39.27 38 60 4.71 182 DNT 07H -0.33 38 60 7.34 181 DNT 07H 0.18 38 60 3.6 184 DNG 07H -0.94 38 66 3.19 183 DNG FBC 12.18 38 67 2.18 84 MBM 04H 28.34 38 69 2.34 185 DNG 04H 17.68 38 71 4.4 181 DNT 07C 0.5 38 74 2.36 79 MBM 04C 35.74 38 80 2 181 DNT 07C 0 38 80 3.26 82 MBM 01C 11.22 38 83 5.36 186 DNG 05H 12.52 38 85 1.45 52 DFS AV4 1.9 38 85 1.27 69 DFS AV4 5.21 38 86 4.67 183 DNT 07H -0.68 38 86 14.14 180 DNT 07H 0.44 38 86 2.04 182 DNT 07C 0.3 38 86 2.48 81 MBM 05C 4.77 38 98 2.83 180 DNT 07H 0.45 38 99 4.25 185 DNG 06H 38.8 38 99 4.78 180 DNT 07H 0.09 38 99 2.46 183 DNT 07H 0.47 38 99 7.14 179 DNT 07H -0.75 38 100 4.39 179 DNT 07H 0.33 38 101 2.67 180 DNG 03H 24.9 38 101 2.16 182 DNG 02C 21.31 38 102 3.91 183 DNT 07H 0.47 38 106 2.41 182 DNT 07H 0.42 38 107 3.83 180 DNT 06C 0.16 38 107 3.25 182 DNT 07C -0.75 38 107 10.58 181 DNT 07C 0.35 38 107 2.35 185 DNT 07H 0.4 38 107 4.36 181 DNT 07H -0.45 38 107 3.21 184 DNG 06H 39.13 38 108 3.14 182 DNT 07C 0.55 39 18 4.33 185 DNG AV6 19.55 39 18 2.04 181 DNT 07C -0.7 39 18 0.37 0 TWD 19 AV3 0 39 18 2.13 74 MBM 01C 18.68 39 20 5.33 69 MBM 06H 36.37 39 23 2.01 70 MBM AV1 3.26 39 23 1.91 94 DFS TSC 5.06 39 24 2.49 102 DFS 04H 30.27 39 25 2.06 69 MBM 01H 18.95 39 27 3.96 113 DFS 02C 20.77 39 30 7.43 84 MBM FBH 7.2 39 32 3.27 81 MBM FBH 7.7 39 32 5.23 82 MBM 02H 19.85 Page 34 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 39 35 2.9 85 MBM FBC 3.56 39 36 6.41 85 MBM 03H 33.9 39 37 2.1 89 MBM 01H 12.05 39 38 2.49 88 MBM 01H 37.51 39 43 3.05 185 DNG 06H 31.97 39 46 4.43 75 MBM FBH 7.7 39 46 1.51 85 DFS 06C 6.1 39 67 0.23 0 TWD 12 AV2 0.1 39 71 0.55 99 DFS TSH 9.78 39 74 0.15 0 TWD 10 AV5 0.07 39 74 3.74 51 MBM AV5 8.13 39 74 3.02 88 MBM AV5 9.72 39 74 3.83 82 MBM 02H 5.23 39 76 0.24 0 TWD 14 AV2 0.02 39 76 0.62 0 TWD 26 AV4 0.2 39 76 0.3 25 TWD 16 AV3 0.2 39 77 0.42 0 TWD 21 AV2 0 39 77 0.72 0 TWD 29 AV5 -0.35 39 80 1.84 102 DFS TSH 5.24 39 80 2.7 73 MBM FBH 14.74 39 84 1.04 111 DFS FBC 4.69 39 84 5.24 75 MBM TSC 12.21 39 84 2.4 111 DFS TSC 5.5 39 84 3.74 81 MBM TSC 6.06 39 85 2.79 181 DNT 07C 0 39 86 0.32 0 TWD 18 AV4 -0.19 39 86 0.08 0 TWD 6 AV5 -0.23 39 86 3.02 87 MBM 03H 27.51 39 87 0.22 0 TWD 13 AV3 0.17 39 87 0.48 0 TWD 22 AV4 0.15 39 87 0.25 0 TWD 14 AV6 -0.02 39 87 0.19 0 TWD 11 AV1 0 39 87 0.21 0 TWD 12 AV2 0 39 87 0.61 0 TWD 26 AV5 0 39 88 0.47 0 "TWND 21 AV4 0 39 88 0.29 0 TWD 15 AV2 0 39 88 0.3 TWD 17 AV3 -0.19 39 88 1.48 115 DFS FBC 14.28 39 88 2.61 51 MBM AV4 12.21 39 89 0.17 0 TWD 10 AV4 0 39 89 0.51 0 TWD 22 AV2 0 39 89 0.13 0 TWD 9 AV3 -0.14 39 89 1.94 106 DFS 02C 6.01 39 91 0.36 0 TWD 17 AV5 0.07 39 91 0.89 0 TWD 30 AV4 0 39 91 0.3 0 TWD 15 AV3 0 39 91 0.18 0 TWD 10 AV2 0.19 39 92 0.15 68 GEO TSH -0.06 39 93 0.24 0 TWD 14 AV3 -0.07 39 97 5.02 80 MBM 05H 6.63 39 99 2.15 176 DNT 07C 0.45 39 105 0.4 0 TWD 21 AV5 -0.1 Page 35 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 39 105 0.24 0 TWD 14 AV4 0 39 105 0.26 0 TWD 15 AV3 -0.05 39 105 0.17 0 TWD 11 AV2 0 40 21 1.16 100 DFS 06C 29.88 40 22 0.19 0 TWD 10 AV5 0.03 40 22 0.33 0 TWD 16 AV3 0.03 40 22 2.76 101 DFS 03H 16.44 40 23 0.32 0 TWD 16 AV6 -0.03 40 23 0.89 0 TWD 31 AV5 0.05 40 23 0.29 0 TWD 15 AV3 0.08 40 23 1.5 83 DFS 04C 14.74 40 23 1.38 109 DFS 03C 4.81 40 24 0.52 0 TWD 23 AV5 0 40 24 0.38 0 TWD 19 AV4 -0.08 40 24 0.12 0 TWD 7 AV3 -0.2 40 24 0.16 0 TWD 9 AV2 0 40 25 0.2 0 TWD 11 AV5 0 40 25 0.32 0 TWD 16 AV4 0 40 26 0.49 125 DSS 01H -0.42 40 36 0.13 0 TWD 7 AV4 0.17 40 36 0.18 0 TWD 10 AV3 -0.11 40 44 4.53 182 DNG 06C 37.89 40 57 3.13 74 MBM 02H 13.19 40 65 6.31 184 DNG 07H 6.41 40 68 2.1 78 MBM 04C 27.97 40 70 2.04 117 DFS 03C 21.27 40 74 1.38 68 DFS AV4 4.23 40 78 2.09 81 MBM AV1 10.33 40 79 2.06 112 DFS 02C 26.64 40 81 2.88 187 DNG AV6 16.2 40 87 4.1 183 DNG AV6 15.73 40 87 2.6 105 DFS FBC 5.18 40 88 2.48 188 DNG AV6 16.11 40 89 4.74 184 DNG AV6 16.73 40 91 4.15 179 DNT 07C 0.28 40 92 2.65 186 DNG AV6 16.83 40 93 5.99 78 MBM 02C 4.08 40 94 1.16 102 DFS TSH 6.69 40 95 2.33 78 MBM 02C 2.79 40 97 2.25 78 MBM AV4 10.82 40 98 2.9 70 MBM 05H -1.1 40 99 2.07 62 MBM AV2 13.73 40 101 3.19 184 DNG AV6 16.85 40 102 2.94 184 DNG AV6 16.52 40 103 2.63 184 DNG AV6 16.53 40 103 2.38 183 DNT 05C 0.75 40 104 3.18 84 MBM 03H 14.12 40 104 2.07 86 MBM AV3 6.4 40 104 2.87 117 DFS 01C 16.54 40 104 2.14 116 DFS FBC 8.93 40 104 1.9 123 DFS FBC 10.33 40 104 4.27 80 MBM AV4 0.76 Page 36 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 40 105 3.3 181 DNT 05C 0.47 40 105 3.13 178 DNT 05C 0.77 40 106 3.13 179 DNT 05C 0.44 40 106 2.54 178 DNT 05C 0.69 40 106 2.52 70 MBM AV3 2.52 41 18 2.91 182 DNT 07C 0.42 41 19 10.24 83 MBM 02H 23.03 41 19 4.58 83 MBM 02H 30.56 41 19 4.21 87 MBM 02H 35.17 41 19 4.82 87 MBM 02H 32.67 41 19 2.49 68 MBM 02H 36.73 41 19 0.77 106 DFS 02H 36.78 41 19 3.08 82 MBM 03H 11.65 41 19 4.97 87 MBM 03H 14.61 41 19 2.71 70 MBM 02H 37.08 41 19 9.65 79 MBM 03H 2.58 41 19 4.68 80 MBM 03H 4.88 41 19 4.48 82 MBM 03H 7.29 41 19 4.36 81 MBM 03H 9.46 41 23 0.15 0 TWD 9 AV6 0 41 23 0.72 0 TWD 28 AV4 0 41 23 0.9 0 TWD 31 AV3 0 41 23 0.31 0 TWD 16 AV2 0 41 23 14.16 82 MBM 05H 21.81 41 25 0.14 0 TWD 8 AV4 0 41 26 4.52 79 MBM 02C 25.63 41 26 0.64 0 TWD 26 AV4 -0.03 41 26 0.57 0 TWD 24 AV3 -0.03 41 26 6.37 79 MBM FBH 7.44 41 26 2.57 78 MBM 02C 30.64 41 26 6.34 82 MBM 02C 28.58 41 29 0.83 0 TWD 30 AV4 -0.25 41 29 0.12 0 TWD 8 AV1 0 41 38 0.22 0 TWD 14 AV4 -0.18 41 38 0.39 0 TWD 20 AV2 0.18 41 40 0.32 0 TWD 16 AV2 0.17 41 40 0.25 0 TWD 13 AV3 -0.06 41 40 0.23 0 TWD 12 AV4 -0.22 41 40 0.41 0 TWD 20 AV5 0.08 41 41 3.08 186 DNT 01C 0.19 41 44 2.52 182 DNG 04H 4.86 41 44 0.26 0 TWD 14 AV4 -0.1 41 44 0.87 69 DFS 01H 14.52 41 48 2.5 60 MBM 02C 8.6 41 56 2.9 92 DFS 01H 16.31 41 58 2.62 179 DNT 07C -0.62 41 67 0.22 49 GEO TSH -0.01 41 69 1.06 112 DFS 06C 28.21 41 77 2.23 186 DNG AV1 5.12 41 78 2.4 186 DNG 06C 38.44 41 81 2.25 179 DNT 07C 0.22 41 83 2.69 78 MBM 02C 18.68 Page 37 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 41 86 0.29 0 TWD 15 AV2 -0.05 41 87 2.23 187 DNG 06H 27.04 41 87 4.76 82 MBM 06C 7.21 41 87 2.34 116 DFS 01C 30.8 41 87 2.12 78 MBM 01C 23.31 41 87 3.36 89 MBM FBC 6.58 41 88 3.05 184 DNG 06H 36.71 41 89 2.11 179 DNT 07H 0.47 41 89 0.77 113 DFS 01C 28.75 41 89 0.85 106 DFS o1C 12.72 41 90 0.89 70 DFS QiC 9.67 41 92 2.61 177 DNT 07C -0.55 41 92 3 177 DNT 07C -0.83 41 92 2.9 186 DNG 07C -1.23 41 92 1.72 67 DFS 03C 12.96 41 94 1.13 108 DFS FBH 6.17 41 94 1.4 100 DFS FBH 8.55 41 95 2.05 180 DNT 07C -0.74 41 95 1.24 106 DFS 06H 23.72 41 96 2.21 85 MBM AV4 9.83 41 97 1.14 107 DFS 02C 24.19 41 99 1.37 71 DFS FBH 9.45 41 99 1.19 67 DFS FBH 10.45 41 102 2.9 179 DNT 05C 0.44 41 102 3.07 179 DNT 05C 0.74 41 103 2.3 179 DNT 05C -0.59 41 103 2.8 177 DNT 05C -0.25 41 103 4.7 180 DNT 05C 0.44 41 103 4.44 181 DNT 05C 0.74 41 103 2.9 179 DNT 07C -0.69 41 104 3.92 181 DNT 05C 0.44 41 104 2.8 180 DNT 05C 0.74 41 104 2.33 182 DNT 05C -0.37 41 105 2.08 180 DNT 05C -0.54 41 105 2.16 179 DNT 05C -0.27 41 105 4.03 182 DNT 05C 0.44 41 105 2.04 177 DNT 05C 0.77 41 105 3.39 180 DNT 07H 0.45 42 24 0.24 0 TWD 13 AV4 0 42 24 0.28 0 TWD 15 AV3 -0.19 42 34 1.1 101 DFS 01H 31.34 42 38 2.96 90 MBM 02H 21.77 42 38 3.96 89 MBM 02H 33.2 42 38 3.56 67 MBM AV4 12.36 42 44 1.72 104 DFS TSH 7.63 42 55 4.97 83 MBM 05C 16.58 42 55 2.22 80 MBM 04C 30.11 42 56 3.28 184 DNG 03C 29.27 42 57 10.29 43 MCI TSH -5.63 42 57 6.79 44 TWD 93 TSH -5.42 42 57 4.57 48 TWD 90 TSH -5.42 42 57 3.54 44 TWD 93 TSH -5.42 Page 38 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 42 57 3.7 37 TWD 97 TSH -5.42 42 57 3.54 36 TWD 98 TSH -5.42 42 57 2.61 37 TWD 97 TSH -5.42 42 57 1.4 47 TWD 91 TSH -5.42 42 57 0.62 62 TWD 78 TSH -5.42 42 57 0.37 60 TWD 80 TSH -5.42 42 57 0.35 48 TWD 90 TSH -5.42 42 57 0.32 47 TWD 91 TSH -5.42 42 57 0.23 51 TWD 88 TSH -5.42 42 57 0.14 62 TWD 78 TSH -5.42 42 57 0 0 TWD 0 TSH -5.42 57 10.25 46 PID TSH -5.63 42 42 57 0 0 TWD 0 TSH -5.43 42 57 0 0 TWD 0 TSH -5.41 42 57 0.14 20 TWD 62 TSH -5.41 42 57 0.25 24 TWD 75 TSH -5.41 42 57 0.31 35 TWD 98 TSH -5.41 42 57 0.36 45 TWD 92 TSH -5.41 42 57 0.44 55 TWD 85 TSH -5.41 42 57 0.56 50 TWD 89 TSH -5.41 42 57 0.61 45 TWD 92 TSH -5.41 42 57 0.51 45 TWD 92 TSH -5.41 42 57 0.71 63 TWD 78 TSH -5.41 42 57 1.67 48 TWD 90 TSH -5.41 42 57 3.03 39 TWD 96 TSH -5.41 42 57 4 38 TWD 97 TSH -5.41 42 57 4.46 39 TWD 96 TSH -5.41 42 57 4.95 39 TWD 96 TSH -5.41 42 57 5.31 39 TWD 96 TSH -5.4 42 57 5.55 40 TWD 95 TSH -5.4 42 57 5.49 40 TWD 95 TSH -5.4 42 57 5.49 40 TWD 95 TSH -5.4 42 57 4.44 40 TWD 95 TSH -5.4 42 57 3.74 40 TWD 95 TSH -5.4 42 57 3.84 41 TWD 95 TSH -5.42 42 57 5.16 41 TWD 95 TSH -5.42 42 57 6.92 42 TWD 94 TSH -5.42 42 57 8.49 44 TWD 93 TSH -5.42 42 57 9.56 46 TWD 91 TSH -5.42 42 57 10.06 46 TWD 91 TSH -5.42 42 57 9.68 45 TWD 92 TSH -5.42 42 57 8.23 46 TWD 91 TSH -5.42 42 57 6.74 47 TWD 91 TSH -5.42 42 57 5.86 44 TWD 93 TSH -5.42 42 57 5.42 41 TWD 95 TSH -5.42 42 57 5.35 42 TWD 94 TSH -5.42 42 57 5.84 44 TWD 93 TSH -5.42 42 57 7.19 43 TWD 93 TSH -5.42 42 57 8.74 42 TWD 94 TSH -5.42 42 57 8.65 43 TWD 93 TSH -5.42 42 61 2.91 73 MBM 04C 25.8 42 70 1.23 120 DFS FBC 2.35 Page 39 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 42 78 3.74 178 DNT 07H 0 42 78 5.19 180 DNT 07C 0.27 42 78 2.09 179 DNT 07C -0.66 42 78 2.53 184 DNG 06H 36.7 42 78 5.14 183 DNG 06H 37.78 42 79 3.34 182 DNT 07C 0.28 42 79 2.49 181 DNT 07C -0.83 42 79 3.69 185 DNG 06C 39.41 42 79 2.32 186 DNG 06C 38.35 42 79 2.37 183 DNG 06H 36.32 42 79 5.33 182 DNG 06H 37.63 42 79 2.13 185 DNG 02H 26.63 42 81 2.31 181 DNT 07H 0.13 42 81 3.47 179 DNT 07H 0.4 42 81 1.28 101 DFS AV3 7.18 42 81 1.04 87 DFS AV4 1.61 42 81 0.97 108 DFS 06C 35.23 42 81 1.42 107 DFS 02C 37.78 42 83 2.63 179 DNT 07H -0.67 42 87 2.5 189 DNG 05C 7.66 42 89 0.61 0 TWD 26 AV2 0 42 89 1.5 0 TWD 39 AV5 0 42 89 0.25 0 TWD 14 AV6 0.03 42 89 1.12 0 "TWVD 35 AV3 0 42 89 0.34 0 "TWiD 17 AV1 0 42 89 2.9 0 TWD 52 AV4 0 42 89 2.62 0 PID AV4 0 42 90 2.52 180 DNT 07H 0.33 42 91 5.62 179 DNT 07H 0.45 42 91 2.15 180 DNT 07H -0.7 42 92 2.2 193 DNG 01H 6.97 42 93 2.31 179 DNT 07C 0.38 42 93 6.22 180 DNT 07H 0.24 42 93 3.43 182 DNT 07H -0.87 42 94 0.3 0 TWD 16 AV3 0 42 94 0.21 0 TWD 13 AV5 0 42 97 4.23 177 DNT 07C -0.72 42 97 6.59 178 DNT 07C 0.32 42 97 2.75 184 DNG 06H 34.33 42 99 5.94 181 DNT 07H 0.42 42 99 2.22 181 DNT 07H -0.66 42 99 2.24 81 MBM 01H 14.48 42 99 2.73 86 MBM 02H 13.91 42 100 2.4 183 DNT 05C 0.47 42 100 4.01 180 DNT 05C 0.77 42 101 2.41 181 DNT 05C -0.7 42 101 2.68 181 DNT 05C -0.37 42 101 4.29 183 DNT 05C 0.33 42 101 4.64 180 DNT 05C 0.61 42 102 2.22 183 DNT 05C -0.68 42 102 3.03 181 DNT 05C -0.35 42 102 5.83 183 DNT 05C 0.35 Page 40 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 42 102 4.37 181 DNT 05C 0.66 42 103 5.51 180 DNT 05C -0.65 42 103 4.25 180 DNT 05C -0.33 42 103 7.52 183 DNT 05C 0.33 42 103 5.26 178 DNT 05C 0.68 42 104 2.21 180 DNT 04C 0.64 42 104 4.98 181 DNT 05C -0.59 42 104 3.81 180 DNT 05C -0.3 42 104 8.21 180 DNT 05C 0.45 42 104 4.39 178 DNT 05C 0.74 42 104 3.56 182 DNT 07C -0.67 42 104 2.57 182 DNT 07C 0.47 43 20 8.85 179 DNT 07C 0.33 43 20 3.85 180 DNT 07C -0.86 43 22 2.01 181 DNT 07C 0.31 43 25 0.27 0 TWD 15 AV3 -0.05 43 25 0.39 0 TWD 19 AV2 0.15 43 25 0.67 TWD 27 AV4 0.02 43 25 0.68 TWD 27 AV5 0.07 43 28 0.32 0 TWD 17 AV3 -0.15 43 28 0.14 0 TWD 8 AV2 -0.07 43 31 4 81 MBM 05H 6.83 43 34 4.76 179 DNT 07C 0.33 43 42 5.88 85 MBM 06H 26.12 43 43 2.44 183 DNG 06H 31.76 43 47 2.29 188 DNG 02C 32.86 43 48 2.14 183 DNT 07H 0.58 43 49 3.33 114 DFS FBC 6.27 43 49 3.56 77 MBM FBC 2.01 43 49 2.88 81 MBM FBC 3.48 43 49 4.12 112 DFS 06C 10.03 43 49 4.1 80 MBM 02H 1.54 43 50 2.79 113 DFS FBC 14.43 43 54 4.23 73 MBM AV3 9.31 43 57 1.07 106 DFS 05C 16.06 43 59 2.51 89 MBM 01H 31.48 43 59 4.5 118 DFS 05C 6.24 43 61 2.47 115 DFS 01C 25.63 43 71 4 112 DFS 04H 32.79 43 71 3.29 114 DFS 05H 1.8 43 71 3.12 42 DFS AV6 -0.76 43 73 1.85 58 DFS 03H 13.15 43 73 1.54 57 DFS 03H 17.41 43 75 4.35 78 MBM FBH 2.05 43 78 2.1 180 DNT 07H 0.45 43 78 4.1 183 DNT 07C 0.28 43 78 3.17 181 DNT 07C -0.81 43 81 2.63 181 DNT 07C 0.32 43 83 3.86 187 DNG 04C 1.53 43 86 1.33 111 DFS 01H 17.35 43 87 2.27 184 DNT 03C 0.07 43 91 2.9 181 DNT 07H -0.9 Page 41 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 43 91 5.92 181 DNT 07H 0.21 43 92 4.1 180 DNT 07H 0.37 43 92 3.1 77 MBM 01C 26.47 43 92 2.63 89 MBM TSC 9.16 43 94 3.52 81 MBM AV3 2.51 43 96 4.18 178 DNT 07H 0.35 43 98 3.03 179 DNT 05C 0.85 43 98 2.72 178 DNT 05C 0.45 43 98 3.2 88 MBM 02C 3.69 43 99 2.11 178 DNT 05C -0.62 43 99 2.67 178 DNT 05C -0.3 43 99 2.15 177 DNT 05C 0.39 43 100 3.72 178 DNT 05C -0.59 43 100 3.46 176 DNT 05C -0.27 43 100 4.54 179 DNT 05C 0.44 43 100 2.37 176 DNT 05C 0.73 43 101 5.03 178 DNT 05C -0.59 43 101 4.05 177 DNT 05C -0.3 43 101 6.65 178 DNT 05C 0.45 43 101 3.63 176 DNT 05C 0.72 43 102 4.91 180 DNT 05C 0.74 43 102 11.09 181 DNT 05C 0.44 43 102 5.11 180 DNT 05C -0.25 43 102 7.31 181 DNT 05C -0.57 43 103 2.72 180 DNT 04C -0.42 43 103 2.81 181 DNT 04C 0.64 43 103 10.35 180 DNT 05C -0.59 43 103 6.2 179 DNT 05C -0.3 43 103 11.65 180 DNT 05C 0.4 43 103 6.44 178 DNT 05C 0.72 43 103 3.66 180 DNT 07C -0.7 44 23 3.4 83 MBM 05C 4.74 44 25 2.24 72 MBM 01C 22.14 44 27 2.45 183 DNG 06H 31.27 44 27 3.2 75 MBM 05H 11.82 44 30 2.5 83 MBM 01H 2.28 44 34 2.05 189 DNG 02H 2.94 44 37 0.69 101 DFS TSC 10.17 44 44 2.9 80 MBM 01H 13.16 44 44 2.01 69 MBM 01H 16.02 44 44 5.05 80 MBM 01H 30.73 44 55 2.71 109 DFS 02C 37.89 44 57 1.7 104 DFS 04C 32.67 44 61 5.01 75 MBM 05C 5.39 44 66 0.18 0 TWD 10 AV3 0 44 66 0.19 0 TWD 11 AV2 0 44 67 0.15 0 TWD 9 AV3 0 44 67 0.18 0 TWD 10 AV1 0 44 71 2.47 182 DNT 07C 0.42 44 71 0.63 108 DFS 04C 4.81 44 71 0.23 0 TWD 13 AV2 0.02 44 71 2.31 128 DDS AV1 16.1 Page 42 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 44 72 1.43 116 DFS 01C 27.6 44 73 2.52 184 DNG 06H 30.8 44 75 7.28 179 DNT 07C 0.3 44 75 2.29 187 DNG 07C -0.8 44 76 3.89 184 DNG 06C 28.72 44 76 2.05 181 DNT 07H -0.05 44 76 4.59 181 DNT 07H 0.57 44 79 5.12 181 DNT 07C 0.3 44 79 2.42 179 DNT 07C -0.73 44 79 4.32 184 DNG 06C 32 44 79 13.63 182 DNG 06C 33.22 44 79 0.19 0 TWD 10 AV4 0 44 79 0.11 0 TWD 6 AV3 0 44 81 3.97 182 DNT 07H -0.82 44 81 5.81 181 DNT 07C 0.83 44 81 2.73 183 DNT 07C -0.2 44 84 2.45 78 MBM 05C 19.65 44 90 5.4 182 DNG 06H 14.93 44 91 4.85 179 DNT 07H -0.2 44 91 2.92 184 DNG 06H 39.42 44 93 2.6 79 MBM 06C 14.29 44 95 2.61 74 MBM 06C 23.85 44 95 5.32 77 MBM 06C 21.11 44 96 2.33 180 DNT 05C 0.77 44 96 3.15 180 DNT 07C -0.7 44 96 4.49 180 DNT 07C 0.42 44 97 2.18 186 DNG 01H 26.65 44 97 3.36 177 DNT 05C 0.42 44 97 4.17 179 DNT 05C 0.76 44 97 3.58 64 MBM 01H 25.66 44 97 0.35 43 MBM 02H -14.61 44 98 2.84 177 DNT 05C -0.7 44 98 3.19 180 DNT 05C -0.37 44 98 5.71 182 DNT 05C 0.35 44 98 5.92 180 DNT 05C 0.68 44 98 4.15 181 DNT 07H 0.42 44 99 5.09 179 DNT 05C -0.65 44 99 3.2 180 DNT 05C -0.33 44 99 5.06 184 DNT 05C 0.35 44 99 4.46 179 DNT 05C 0.66 44 99 0.45 83 DFS TSH 5.15 44 100 2.34 178 DNT 04C -0.39 44 100 2.32 178 DNT 04C 0.72 44 100 9.66 178 DNT 05C -0.64 44 100 6.36 177 DNT 05C -0.32 44 100 9.39 179 DNT 05C 0.42 44 100 6.45 177 DNT 05C 0.74 44 100 2.32 179 DNT 07C -0.74 44 100 1.13 109 DFS FBH 4.18 44 101 4.02 180 DNT 04C -0.33 44 101 2.89 178 DNT 04C 0.7 44 101 12.9 179 DNT 050 -0.63 Page 43 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 44 101 7.07 179 DNT 05C -0.37 44 101 8.1 182 DNT 05C 0.35 44 101 6.81 178 DNT 05C 0.66 44 101 2.2 178 DNT 07C -0.68 44 101 2 178 DNT 07C 0.47 44 102 3.69 180 DNT 04C -0.42 44 102 2.43 180 DNT 04C 0.67 44 102 12.51 180 DNT 05C -0.62 44 102 5.86 179 DNT 05C -0.3 44 102 11.1 180 DNT 05C 0.42 44 102 6.89 178 DNT 05C 0.69 44 102 3.31 180 DNT 07C 0.5 44 102 2.66 179 DNT 07C -0.64 45 23 3.28 82 MBM 03H 33.45 45 25 2.69 183 DNG 02H 18.76 45 28 0.5 0 TWD 22 AV5 -0.05 45 28 0.46 0 TWD 21 AV4 -0.08 45 28 0.47 0 "TWD 21 AV3 -0.1 45 28 0.56 0 TWD 24 AV2 0.05 45 28 2.49 77 MBM 01C 18.71 45 30 0.15 0 TWD 9 AV4 0 45 31 2.65 185 DNG 06H 39.17 45 31 3.04 182 DNT 07C 0.33 45 31 2.31 81 MBM 01C 15.99 45 32 1.99 96 DFS 06C 37.3 45 34 0.17 0 TWD 11 AV4 0 45 38 2.1 77 DFS AV1 5.58 45 38 2.24 66 MBM 01C 10.1 45 42 0.52 0 TWD 22 AV3 0.05 45 42 0.14 0 TWD 8 AV2 0.03 45 52 4.63 177 DNT 07H -0.56 45 52 6.56 178 DNT 07H 0.44 45 52 3.1 182 DNG 06H 26.93 45 52 4.12 183 DNG 06H 28.02 45 52 2.43 175 DNT 07C 0.41 45 57 2.15 86 MBM 02H 1.7 45 58 2.87 82 MBM 04C 30.83 45 64 3.69 73 MBM 02C 39.22 45 68 6.66 76 MBM FBC 4.85 45 69 1.56 105 DFS FBC 5.43 45 70 3.7 173 DNT 07C -0.75 45 71 5.28 107 DFS AV1 2.74 45 76 7.83 179 DNT 07C 0.35 45 76 6.76 182 DNG 06C 38.16 45 76 2.63 182 DNG 06C 37.06 45 76 3.46 185 DNG 07C -0.8 45 77 4.11 179 DNT 07C 0.35 45 78 3.01 180 DNT 07C 0.4 45 79 3.37 109 DFS FBC 17.2 45 81 4.38 183 DNG 06H 32.03 45 81 4.37 179 DNT 07H 0.55 45 81 2.88 178 DNT 07C -0.84 Page 44 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 45 81 2.07 186 DNG 06H 30.93 45 81 6.42 178 DNT 07C 0.44 45 84 2.33 180 DNT 07C 0.35 45 84 3.44 183 DNG 07C -1.18 45 84 1.22 113 DFS 03H 3.46 45 84 1.42 112 DFS 05C 4.92 45 85 5.78 172 DNT 07C 0.3 45 85 5.87 188 DNG AV5 7.03 45 85 2.89 172 DNT 07C -0.87 45 90 3.44 85 MBM 04C 23.31 45 91 3.68 178 DNT 07H 0.19 45 92 3.59 85 MBM 05C 38.66 45 93 2.5 178 DNT 07C 0.38 45 93 2.26 175 DNT 07H 0.45 45 95 2.19 183 DNG 06H 23.59 45 95 5.6 184 DNG 06H 24.73 45 95 3.37 181 DNT 07C 0.31 45 95 2.23 177 DNT 07C 0.7 45 95 2.86 180 DNG 06C 38.38 45 96 2.26 178 DNT 05C 0.79 45 97 2.06 183 DNG 06H 24.19 45 97 3.53 182 DNT 07C 0.35 45 97 2.46 179 DNT 07C -0.73 45 97 5.71 178 DNT 05C 0.66 45 97 5.8 182 DNT 05C 0.33 45 97 2.79 179 DNT 05C -0.37 45 97 2.42 180 DNT 04C 0.7 45 98 4.28 178 DNT 04C -0.39 45 98 3.04 179 DNT 04C 0.62 45 98 8.14 177 DNT 05C -0.6 45 98 7.15 175 DNT 05C -0.27 45 98 8.83 178 DNT 05C 0.44 45 98 6.64 177 DNT 05C 0.74 45 98 2.03 178 DNT 02H 0.74 45 99 4.66 179 DNT 04C -0.39 45 99 3.86 181 DNT 04C 0.62 45 99 6.75 179 DNT 05C -0.62 45 99 4.18 178 DNT 05C -0.3 45 99 6.29 180 DNT 05C 0.44 45 99 3.85 178 DNT 05C 0.71 45 99 2.29 181 DNT 07C 0.42 45 99 4.62 187 DNG 04H 9.23 45 99 3.49 187 DNG 04H 10.49 45 99 2.09 187 DNG 04H 11.67 45 99 2.17 186 DNG 04H 13.05 45 99 3.88 88 MBM 01H 10.15 45 100 4.42 180 DNT 04C -0.42 45 100 3.6 182 DNT 04C 0.64 45 100 2.78 182 DNT 07C -0.69 45 100 2.31 183 DNT 07C 0.37 45 100 3.3 180 DNT 02H 0.74 45 100 4.28 180 DNT 02H -0.27 Page 45 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 45 100 12.73 178 DNT 05C -0.67 45 100 6.74 178 DNT 05C -0.37 45 100 8.59 180 DNT 050 0.37 45 100 6.85 178 DNT 050 0.69 45 101 3.99 181 DNT 02H 0.76 45 101 3.23 178 DNT 02H -0.22 45 101 5.39 178 DNT 04C -0.34 45 101 2.33 180 DNT 04C 0.62 45 101 14.71 176 DNT 05C -0.62 45 101 8.83 176 DNT 05C -0.35 45 101 6.39 178 DNT 05C 0.45 45 101 6.63 176 DNT 05C 0.69 45 101 2.4 179 DNT 07C -0.68 46 24 0.31 0 TWD 16 AV1 0.16 46 24 2.62 84 MBM FBH 7.96 46 24 3.33 78 MBM 01H 17.65 46 24 3.6 87 MBM 03H 22.46 46 24 4.42 72 MBM AV3 6.62 46 25 0.22 0 TWD 12 AV5 -0.07 46 25 0.13 0 TWD 8 AV4 -0.2 46 25 0.13 0 TWD 8 AV3 0 46 25 0.21 0 TWD 12 AV1 -0.12 46 32 0.93 108 DFS 03C 2.7 46 35 2.55 183 DNG AV6 19.43 46 35 2.3 184 DNG AV6 19.76 46 37 5.38 184 DNG 06C 39.19 46 37 0.5 91 DFS 04H 32.53 46 40 3.81 82 MBM 06C 5.92 46 41 0.22 0 TWD 13 AV1 0 46 41 0.24 0 TWD 14 AV3 0 46 41 0.21 0 TWD 12 AV4 0 46 43 3.18 75 MBM AV5 15.49 46 44 0.18 0 TWD 10 AV3 -0.13 46 45 0.15 0 TWD 8 AV6 0 46 45 0.16 0 TWD 9 AV4 -0.19 46 45 0.33 0 TWD 16 AV1 0.25 46 45 1.15 0 TWD 35 AV3 0 46 47 2.08 178 DNT 07H 0.58 46 48 2.76 178 DNG 06C 14.66 46 48 2.91 180 DNG 06C 17.58 46 49 3.29 90 MBM 03C 39.04 46 50 0.22 0 TWD 12 AV6 -0.22 46 50 6.75 182 DNT 07C 0.52 46 50 0.14 0 TWD 9 AV1 0 46 50 0.57 0 TWD 25 AV2 0 46 50 1.14 0 TWD 35 AV3 0 46 50 1.1 0 TWD 35 AV4 0 46 50 0.52 0 TWD 23 AV5 0 46 52 3.02 179 DNT 07C 0.47 46 54 0.29 0 TWD 15 AV4 0 46 54 0.32 0 TWD 16 AV3 0 46 54 0.63 0 TWD 25 AV2 0 Page 46 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 46 59 3.45 187 DNG 07H 24.57 46 69 0.2 119 GEO TSH 0 46 70 2.59 86 MBM 06C 26.33 46 71 2.32 183 DNT 07H 0.47 46 73 7.27 179 DNT 07C 0.3 46 73 2.49 186 DNG 06C 39.81 46 77 2.68 183 DNT 07C 0.28 46 79 3.65 180 DNT 07H 0.4 46 81 0.17 0 TWD 10 AV5 0 46 81 0.75 0 TWD 28 AV3 0 46 82 2.95 186 DNG 06H 38.41 46 82 5.11 186 DNG 06H 39.51 46 82 5.25 183 DNT 07H -0.6 46 83 0.16 0 TWD 9 AV5 0 46 83 0.29 0 TWD 15 AV4 0 46 83 0.12 0 TWD 7 AV1 0 46 83 0.47 0 TWD 21 AV2 0 46 83 0.66 0 TWD 26 AV3 0 46 84 1.93 103 DFS 01H 24.24 46 87 2.32 84 MBM AV6 3.82 46 88 0.23 0 TWD 13 AV2 0 46 88 0.17 0 TWD 10 AV3 -0.07 46 90 2.54 76 MBM 04H 19 46 91 3.06 181 DNT 07H 0.25 46 92 3.77 179 DNT 07H 0.45 46 93 2.85 111 DFS 04H 26.86 46 95 2.37 185 DNG 06C 28.89 46 96 2.11 181 DNT 04C -0.4 46 96 2.69 181 DNT 05C -0.56 46 96 3.6 181 DNT 05C 0.82 46 96 2.07 182 DNT 07C -0.75 46 96 2 183 DNT 07C 0.35 46 97 2.73 180 DNT 04C -0.42 46 97 3.59 180 DNT 04C 0.62 46 97 4.5 178 DNT 05C -0.64 46 97 3.24 177 DNT 05C -0.3 46 97 4.69 179 DNT 05C 0.4 46 97 4.77 180 DNT 05C 0.74 46 97 3 180 DNT 07C -0.69 46 97 2.97 179 DNT 07C 0.3 46 97 3.54 179 DNT 07H 0.47 46 98 3.39 179 DNT 04C -0.4 46 98 3.04 181 DNT 04C 0.7 46 98 7.92 177 DNT 05C -0.7 46 98 5.49 180 DNT 05C -0.4 46 98 9.2 182 DNT 05C 0.4 46 98 8.8 179 DNT 05C 0.68 46 98 2.79 182 DNT 02H 0.74 46 98 2.35 182 DNT 02H -0.3 46 99 3.92 182 DNT 04C -0.49 46 99 6.79 182 DNT 04C 0.56 46 99 10.65 179 DNT 05C -0.7 Page 47 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 46 99 5.42 179 DNT 05C -0.4 46 99 6.16 184 DNT 05C 0.38 46 99 3.73 180 DNT 05C 0.68 46 99 2.3 75 MBM AV3 5.89 47 25 2.09 85 MBM AV6 4.58 47 32 0.48 0 TWD 23 AV5 0.03 47 32 0.21 0 TWD 13 AV4 0 47 32 0.28 0 TWD 16 AV3 0.08 47 32 0.34 0 TWD 19 AV2 0.11 47 32 0.28 0 TWD 16 AV1 -0.13 47 34 '1.88 0 PID AV4 -0.3 47 34 0.74 0 TWD 22 AV5 -0.08 47 34 2.01 0 TWD 43 AV4 -0.3 47 34 0.88 0 TWD 25 AV2 0.06 47 34 1.19 0 TWD 31 AV3 -0.01 47 36 0.45 0 TWD 22 AV5 0.13 47 36 0.29 0 TWD 16 AV4 -0.03 47 36 0.29 0 TWD 16 AV3 0.05 47 36 0.1 119 TWD 6 AV1 0.13 47 36 0.21 47 TWD 11 AV2 0 47 37 2.79 180 DNT 07C 0.45 47 40 0.15 0 TWD 10 AVI 0 47 40 0.16 0 TWD 10 AV2 0 47 40 0.21 0 TWD 13 AV3 0 47 43 2.93 183 DNG 06H 35.67 47 43 0.49 0 TWD 22 AV5 -0.03 47 43 0.69 0 TWD 27 AV4 -0.05 47 43 0.37 0 TWD 18 AV3 0 47 43 0.44 0 TWD 20 AV2 0.32 47 44 0.15 0 TWD 8 AV6 -0.11 47 44 0.76 0 TWD 28 AV5 0.41 47 44 0.78 0 TWD 29 AV4 0 47 44 0.76 0 TWD 28 AV3 0.11 47 44 0.42 0 TWD 19 AV2 -0.11 47 46 2.87 180 DNT 07H 0.5 47 49 0.25 0 TWD 13 AV2 0.06 47 49 0.27 0 TWD 14 AV3 0 47 49 0.93 0 TWD 31 AV4 -0.03 47 49 0.37 0 TWD 18 AV5 0 47 49 0.14 0 TWD 8 AV6 -0.03 47 50 0.13 0 TWD 8 AV6 0 47 50 0.55 0 TWD 23 AV5 0 47 50 0.31 0 TWD 16 AV4 0 47 52 0.18 0 TWD 10 AV1 -0.11 47 54 0.22 0 TWD 13 AV5 0 47 55 2.34 84 MBM 04H 14.89 47 56 0.23 0 TWD 13 AV2 0 47 56 0.18 0 TWD 10 AV3 0 47 57 2.99 185 DNG 02H 17.71 47 57 3.02 79 MBM 03H 20.79 47 61 0.34 0 TWD 17 AV2 0.33 47 61 0.55 0 TWD 23 AV3 0.1 Page 48 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 47 61 0.45 0 TWD 20 AV4 0.91 47 61 0.17 0 TWD 9 AV5 -0.03 47 61 0.73 115 DFS 02C 35.52 47 61 1.07 113 DFS 02C 32.81 47 68 2.05 181 DNG 01H 30.8 47 71 4.32 184 DNG 06H 3.2 47 72 2.78 182 DNT 07H 0.46 47 75 2.69 183 DNG 06H 14.56 47 75 3.72 186 DNG FBC 5.84 47 76 2.78 184 DNG 06H 8.71 47 76 2.83 183 DNG 06C 37.38 47 76 2.67 178 DNT 07H 0.45 47 76 5.15 124 DFS 03C 7.16 47 79 6.31 180 DNT 07C 0.37 47 79 2.24 184 DNG 06H 27.49 47 81 2.99 187 DNG 01H 37.77 47 83 2.56 81 MBM 01C 16.74 47 83 0.21 0 TWD 13 AV4 -0.02 47 85 2.07 71 MBM 05C 5.96 47 85 2.76 73 MBM 04C 17.72 47 87 1.76 72 DFS 01H 24.63 47 88 3.29 182 DNT 07H 0.57 47 88 0.36 0 TWD 18 AV5 0 47 88 0.38 0 TWD 18 AV4 0 47 95 2.7 178 DNT 05C 0.77 47 95 2.5 180 DNT 07C -0.7 47 95 2.3 177 DNT 07C 0.33 47 96 2.69 178 DNT 04C 0.64 47 96 4.64 177 DNT 05C -0.64 47 96 3.38 178 DNT 05C 0.78 47 96 5.91 177 DNT 07C -0.72 47 97 8.45 182 DNT 07C 0.52 47 97 6.03 182 DNT 07C -0.54 47 97 5.48 178 DNT 05C 0.66 47 97 4.99 182 DNT 05C 0.4 47 97 4.03 181 DNT 05C -0.42 47 97 2.5 177 DNT 05C -0.72 47 97 2.83 182 DNT 04C 0.68 47 97 3.08 77 MBM 02C 1.75 47 98 2.34 179 DNT 04C -0.39 47 98 4.05 180 DNT 04C 0.74 47 98 8.52 177 DNT 05C -0.62 47 98 6.85 175 DNT 05C -0.35 47 98 9.88 177 DNT 05C 0.45 47 98 8.83 176 DNT 05C 0.74 47 98 2.14 179 DNT 07C -0.71 47 98 0.21 0 TWD 13 AV6 0 47 99 5.45 178 DNT 04C -0.37 47 99 6.47 179 DNT 04C 0.72 47 99 12.13 176 DNT 05C -0.57 47 99 9.42 176 DNT 05C -0.27 47 99 5.79 179 DNT 05C 0.32 Page 49 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 47 99 2.82 179 DNT 05C 0.67 47 99 3.4 180 DNT 07C -0.67 47 99 3 178 DNT 07C 0.45 47 99 0.32 0 TWD 17 AV6 0.07 47 99 0.33 0 TWD 17 AV5 0 48 26 0.5 92 DFS 05H 5.48 48 28 6.22 79 MBM FBC 12.72 48 34 7.14 183 DNG 06C 29.45 48 34 2.06 186 DNG 01C 19.9 48 35 0.3 0 TWD 17 AV4 0.1 48 40 0.58 104 DFS 03C 29.97 48 46 2.36 182 DNG 07H 9.15 48 49 2.48 180 DNT 07H -0.59 48 49 3.78 182 DNT 07H 0.49 48 63 0.45 99 DFS 03C 10.03 48 68 3.88 185 DNG 05H 23.64 48 71 2.11 187 DNG 04H 11.36 48 71 3.82 186 DNG 04H 1.2 48 74 2.13 179 DNT 07C -0.43 48 79 4.9 182 DNG 06H 37.41 48 79 3.14 183 DNG 06H 36.34 48 83 2.25 179 DNT 07C 0.27 48 83 4.64 80 MBM 01C 31.12 48 85 2.94 73 MBM 06C 28.68 48 85 2.04 86 MBM 06C 27.46 48 85 2.48 88 MBM 04C 2.52 48, 90 2.04 54 MBM AV2 5.59 48 91 2.25 180 DNT 07C -0.8 48 94 4.71 188 DNG 02H 7.1 48 94 0.41 0 TWD 21 AV3 0 48 94 0.47 0 TWD 23 AV4 0 48 94 0.28 0 TWD 16 AV6 0 48 95 3.34 179 DNT 05C 0.74 48 95 2.3 179 DNT 05C 0.45 48 96 2.9 177 DNT 04C -0.42 48 96 2.23 180 DNT 04C 0.67 48 96 3.29 174 DNT 05C -0.27 48 96 3.96 178 DNT 05C -0.54 48 96 5.45 177 DNT 05C 0.44 48 96 6.3 178 DNT 05C 0.74 48 96 3.9 180 DNT 07C -0.74 48 96 6.12 179 DNT 07C 0.35 48 97 2.08 179 DNT 04C -0.44 48 97 3.75 179 DNT 04C 0.67 48 97 5.42 177 DNT 05C -0.74 48 97 8.62 176 DNT 05C -0.37 48 97 8.83 177 DNT 05C 0.42 48 97 6.41 177 DNT 05C 0.77 48 97 2.97 180 DNT 07C -0.71 48 97 5.77 179 DNT 07C 0.45 48 98 4.11 179 DNT 04C -0.39 48 98 5.21 179 DNT 04C 0.67 Page 50 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 48 98 11.83 176 DNT 05C -0.62 48 98 7.77 175 DNT 05C -0.35 48 98 7.89 177 DNT 05C 0.47 48 98 7.38 177 DNT 05C 0.74 48 98 2.49 180 DNT 07C -0.72 48 98 4.61 179 DNT 07C 0.45 48 98 2.23 178 DNT 02H -0.27 49 28 1.59 90 DFS 05C 28.64 49 28 1.86 110 DFS 05C 27.09 49 37 2.86 85 MBM FBC 12.55 49 38 4.59 184 DNG 06C 33.78 49 44 2.6 183 DNG AV3 8.84 49 44 2.12 87 MBM 06H 24.82 49 45 9.48 183 DNG AV5 11.66 49 45 3.54 87 MBM 05H 22.51 49 45 5.97 87 MBM 05H 26.57 49 45 1.78 107 DFS 06C 2.94 49 47 2.34 185 DNG AV6 23.74 49 47 0.77 100 DFS 03C 3.61 49 49 3.17 183 DNT 07H 0.47 49 58 3.27 187 DNG 01H 12.12 49 58 3.32 76 MBM 01C 6.69 49 64 4.86 79 MBM 02H 23.2 49 66 0.89 101 DFS TSH 8.7 49 70 0.68 102 DFS 05C 28.75 49 72 2.19 181 DNT 07C 0.33 49 79 3.89 181 DNT 07H -0.57 49 79 5.56 180 DNT 07H 0.52 49 79 2.52 109 DFS 02C 11.79 49 87 2.04 183 DNT 07H -0.57 49 87 3.21 182 DNT 07H 0.42 49 89 2.22 181 DNT 07C -0.73 49 89 3.56 181 DNT 07H 0.45 49 89 2.4 181 DNT 07H -0.73 49 89 3.15 183 DNG 06H 26.07 49 89 1.69 62 DFS AV2 12.6 49 92 0.24 0 TWD 13 AV4 -0.16 49 92 0.19 0 TWD 11 AV3 0 49 92 0.12 0 TWD 7 AV2 0 49 92 2.9 180 DNT 07H 0.4 49 94 0.25 0 TWD 14 AV1 0 49 94 0.54 0 TWD 25 AV2 0 49 94 0.41 0 TWD 21 AV3 0 49 94 0.53 0 TWD 24 AV4 0 49 94 1.24 0 TWD 37 AV5 0 49 94 0.27 0 TWD 16 AV6 0 49 95 3.58 186 DNG AV6 23.07 49 95 7.38 182 DNT 07C 0.45 49 95 5.77 182 DNT 07C -0.52 49 95 2.11 180 DNT 05C -0.4 49 95 4.55 181 DNT 05C 0.35 49 95 5.25 179 DNT 05C 0.7 Page 51 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 49 96 2.08 179 DNT 04C -0.42 49 96 4.26 180 DNT 04C 0.72 49 96 3.25 177 DNT 05C -0.59 49 96 3.05 176 DNT 05C -0.32 49 96 4.62 178 DNT 05C 0.45 49 96 3.06 177 DNT 05C 0.72 49 96 5.58 181 DNT 07C -0.67 49 96 7.95 180 DNT 07C 0.35 49 96 1.6 112 DFS TSH 17.49 49 96 1.24 116 DFS AV6 21.23 50 35 4.34 183 DNT 07H 0.52 50 35 2.81 184 DNG 06H 32.47 50 35 2.67 182 DNT 07H 0.99 50 36 4 181 DNT 07H 0.55 50 39 7.77 87 MBM 01H 18.92 50 40 4.41 182 DNT 07C -0.52 50 40 5.81 89 MBM 02H 1.69 50 42 2.53 181 DNT 07H 0.52 50 44 3.7 178 DNT 07H 0.57 50 44 8.69 77 MBM FBH 16.72 50 45 3.53 78 MBM 01C 5.39 50 45 0.91 114 DFS TSC 18.27 50 46 2.19 182 DNG 05C 12.54 50 46 3.01 187 DNG 06H 35.57 50 46 2.77 180 DNT 07H 0.52 50 46 1.38 58 DFS AV3 9.2 50 46 1.33 102 DFS 06C 33.7 50 46 2.55 85 MBM 01C 2.24 50 47 2.5 182 DNG 07H 9.12 50 48 2.35 185 DNG 07H 8.37 50 49 2.97 182 DNG 07H 8.02 50 50 2.71 185 DNG 07H 8.59 50 50 2.16 86 MBM FBC 4.31 50 51 3.12 182 DNG 07H 8.34 50 51 2.4 74 MBM 01C 34.92 50 53 2.13 185 DNG 07H 8.76 50 56 2.2 188 DNG 06H 37.12 50 56 1.5 99 DFS AV4 9.53 50 57 4.22 79 MBM AV1 -1.29 50 62 6.08 88 MBM 04H 28.65 50 62 5.8 85 MBM AV1 7.5 50 62 2.79 113 DFS 02C 17.92 50 73 3.99 184 DNG FBC 5.8 50 75 2.53 181 DNT 07C 0.37 50 75 5.01 185 DNG AV4 2.92 50 76 2.88 182 DNT 07C -0.71 50 76 7.09 181 DNT 07C 0.37 50 76 2.12 180 DNT 07H 0.52 50 79 3 182 DNT 07H -0.34 50 84 3.22 184 DNT 07H -0.79 50 84 3.64 183 DNT 07H 0.34 50 84 1.61 107 DFS FBC 16.83 Page 52 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 50 86 1.17 111 DFS 01C 11.63 50 87 0.19 0 TWD 12 AV6 -0.09 50 88 3.04 182 DNT 07C -0.77 50 89 4.26 182 DNT 07C -0.71 50 90 4.26 182 DNT 07C -0.77 50 91 2.27 182 DNT 07C -0.66 50 91 4.42 30 MBM AV4 8.48 50 92 4.51 178 DNT 070 -0.74 50 92 1.02 104 DFS 01C 17.84 50 93 3.69 181 DNT 07C -0.75 50 93 0.92 116 DFS FBC 7.24 50 94 2.18 179 DNT 05C 0.74 50 94 3.73 179 DNT 07C -0.72 50 94 5.83 179 DNT 07C 0.48 50 94 2.86 179 DNT 07H 0.42 50 95 0.56 29 SCI TSH 0.04 50 95 3.19 179 DNT 04C 0.69 50 95 2.47 176 DNT 05C 0.45 50 95 5.02 178 DNT 05C 0.7 50 95 4.3 180 DNT 07C -0.77 50 95 4.39 179 DNT 07C 0.42 50 95 0.17 0 TWD 10 AV6 0 50 95 0.46 30 PID TSH 0.04 50 95 0 0 TWD 0 TSH 0 50 95 0.39 14 TWD 44 TSH 0 50 95 0.44 23 TWD 72 TSH 0 50 95 0.6 25 TWD 78 TSH 0 50 95 0.73 24 TWD 75 TSH 0 50 95 0.8 21 TWD 65 TSH 0 50 95 0.58 22 TWD 69 TSH 0 50 95 0.37 22 TWD 69 TSH 0 50 95 0 0 TWD 0 TSH 0 51 30 1.44 95 DFS 02C 24.4 51 31 4.58 182 DNT 07C 0.5 51 31 3.14 185 DNT 07H 0.47 51 32 2.33 184 DNG 06H 20.16 51 34 2.3 69 DFS 06C 19.27 51 35 2.06 187 DNG AV1 12.71 51 36 2.04 183 DNG 06C 30.36 51 36 2.49 71 MBM 04C 26.39 51 38 5.25 184 DNG 06C 32.18 51 38 0.99 84 DFS 03H 14.76 51 38 3.07 75 MBM 03H 14.6 51 39 3.08 183 DNG 06C 32.3 51 42 3.54 182 DNG 07H 8.62 51 45 2.11 182 DNT 07H 0.55 51 45 2.03 184 DNG AV6 19.61 51 46 3.84 182 DNT 07C 0.86 51 47 0.37 0 TWD 17 AV5 -0.11 51 47 0.59 0 TWD 24 AV4 0.11 51 47 0.25 0 TWD 13 AV3 0 51 47 0.91 0 TWD 21 AV2 0 Page 53 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 51 48 0.88 116 DFS 05H 37.1 51 48 1.12 101 DFS 05H 25.91 51 48 1.54 101 DFS 05H 23.47 51 49 2.34 183 DNT 07H -0.08 51 56 4.52 185 DNG 05H 5.09 51 61 2.88 117 DFS 03C 1.23 51 67 0.17 0 TWD 9 AV5 -0.03 51 67 0.61 109 DFS 01C 25.14 51 71 3.36 181 DNT 07C 0.42 51 71 1.25 67 DFS AV4 8.72 51 73 2.3 119 DFS 03C 28.43 51 77 3.14 179 DNT 07H 0.47 51 78 2.7 182 DNT 07C 0.26 51 79 3.69 179 DNT 07H 0.45 51 79 5.74 79 MBM 05C 18.34 51 80 0.32 0 TWD 17 AV3 0.2 51 80 0.24 0 TWD 14 AV5 0 51 80 0.12 0 TWD 8 AV6 0 51 81 4.04 182 DNT 07H -0.55 51 81 8.51 181 DNT 07H 0.47 51 81 2.65 185 DNT 07H -0.05 51 81 7.36 180 DNT 07C 0.42 51 81 3.58 182 DNT 07C -0.67 51 81 2.88 74 MBM 01C 36.34 51 82 0.13 0 TWD 8 AV6 0 51 82 0.2 0 TWD 11 AV5 0 51 84 3.19 183 DNG 06H 21.26 51 84 2.9 180 DNT 07C 0.4 51 84 3.62 180 DNT 07H 0.42 51 84 2.16 181 DNT 07H -0.63 51 84 2.82 54 MBM 01H 36.1 51 84 2.46 181 DNT 07C -0.74 51 87 1.16 110 DFS AV2 9 51 87 5.58 108 DDS AV2 17.05 51 87 5.75 82 MBM 02C 35.2 51 88 2.8 182 DNT 07C 0.32 51 88 2.21 181 DNT 07C -0.74 51 88 1.71 114 DFS 01C 35.5 51 89 4.15 181 DNT 07C -0.77 51 90 2.54 182 DNT 07C 0.27 51 90 3.53 181 DNT 07C -0.77 51 90 1 96 DFS AV2 11.39 51 90 2.45 70 MBM AV3 12.81 51 90 0.66 92 DFS 01C 29.47 51 90 1.39 114 DFS 01C 17.47 51 91 2.87 181 DNT 07C -0.78 51 91 0.16 0 TWD 9 AV6 -0.14 51 92 5.37 179 DNT 07C -0.77 51 92 2.81 180 DNT 07C 0.25 51 92 2.11 182 DNT AV4 0 51 93 2.62 181 DNT 07C 0.35 51 93 4.8 181 DNT 07C -0.74 Page 54 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 51 93 0.14 0 TWD 9 AV6 0 52 32 3.04 186 DNG 02H 7.86 52 33 2.92 185 DNG 06H 36.61 52 35 3.02 186 DNG 04H 35.46 52 42 3.5 189 DNG 03C 30.33 52 45 3.23 182 DNT 07C 0.39 52 46 2.2 184 DNG 02C 24.82 52 46 2.74 183 DNG 05C 37.23 52 50 0.39 73 DFS 04H 34.54 52 54 2.71 75 MBM 03C 37.42 52 56 5.2 184 DNG 07H 9.78 52 60 0.14 0 TWD 8 AV5 0 52 60 0.11 0 TWD 7 AV4 0 52 60 0.19 0 TWD 11 AV3 0 52 60 0.16 0 TWD 9 AV2 0 52 60 0.11 0 TWD 7 AV1 0 52 68 0.14 0 TWD 8 AV1 0.02 52 68 0.84 0 TWD 29 AV2 -0.1 52 68 1.08 0 TWD 33 AV3 -0.3 52 68 0.58 0 TWD 24 AV4 0.12 52 68 0.79 0 TWD 29 AV5 0.27 52 73 0.16 0 TWD 10 AV1 0 52 73 1.14 0 TWD 35 AV4 0.02 52 73 0.43 0 TWD 21 AV5 0.02 52 73 2.39 0 TWD 48 AV2 0.15 52 73 2.3 0 TWD 47 AV3 0.2 52 73 2.22 62 PID AV2 0.15 52 78 2.34 75 MBM 04H 9.63 52 79 2.18 182 DNT 07C 0.29 52 81 2.29 183 DNT 07C 0.29 52 81 2.02 181 DNT 07C -0.78 52 81 2.1 184 DNG 06C 16.27 52 82 2.31 182 DNT 07C -0.76 52 82 2.28 182 DNT 07C 0.37 52 82 3.27 181 DNT 07H 0.39 52 84 3.56 184 DNG 06H 37.11 52 84 1.98 114 DFS 03C 9.95 52 84 2.07 118 DFS FBC 5.03 52 84 1.06 119 DFS 03C 8.69 52 84 0.59 110 DFS 03C 5.59 52 84 1.19 111 DFS 03C 4.53 52 84 0.73 102 DFS 03C 6.89 52 85 2.11 184 DNT 07C 0 52 86 4.51 182 DNT 07C 0.37 52 86 3.05 182 DNT 07C -0.69 52 87 4.38 181 DNT 07C -0.73 52 88 4.05 180 DNT 07C 0.35 52 88 2.57 180 DNT 07C -0.79 52 88 2.2 80 MBM 02C 24.29 52 89 2.04 181 DNT 07C 0.37 52 89 4.93 182 DNT 07C -0.67 52 89 2.41 184 DNG 06C 35.85 Page 55 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 52 90 7.74 182 DNT 07C 0.3 52 90 3.26 182 DNT 07C -0.7 52 90 1.52 119 DFS AV3 10.27 52 91 5.09 180 DNT 07C -0.72 52 91 8.13 178 DNT 07C 0.35 53 33 2.27 184 DNG 06C 23.52 53 33 4.15 183 DNG 07H 9.53 53 34 4.19 186 DNG 07H 9.16 53 34 1.13 98 DFS 04C 10.92 53 35 5.02 184 DNG AV6 18.45 53 35 4.65 183 DNG 06C 29.76 53 35 5.95 183 DNG 06C 29.03 53 35 3.34 184 DNG 06C 27.8 53 35 2.99 185 DNG 06C 8.19 53 35 2.96 178 DNG 06C 28.55 53 35 5.04 82 MBM 04H 22.77 53 36 5.15 185 DNG 07H 8.48 53 36 2.75 79 MBM AV2 6.49 53 36 2.8 61 MBM 02C 24.3 53 36 3.52 74 MBM 01C 18.53 53 37 5 185 DNG 07H 9.18 53 38 5.82 186 DNG 07H 9.57 53 38 1.55 96 DFS 04C 12.91 53 39 5.37 185 DNG 07H 10.02 53 40 5.77 185 DNG 07H 9.75 53 41 4.79 186 DNG 07H 9.37 53 42 3.94 182 DNG 07H 8.69 53 43 4.02 183 DNG 07H 9.14 53 44 6.14 185 DNG 07H 8.47 53 45 1.22 108 DFS FBC -1.49 53 45 4.49 184 DNG 07H 8.62 53 46 2.9 184 DNT 07C 0.47 53 46 3.42 183 DNT 07H 0.5 53 46 3.6 82 MBM 01H 15.19 53 46 2.74 87 MBM 06H -1.07 53 46 2.99 79 ADS 01H 13.15 53 46 0.86 125 MBM 01H 13.15 53 55 1.84 112 DFS TSH 8.34 53 57 2.37 181 DNG AV6 21.97 53 58 2.32 184 DNG AV6 21.48 53 58 3.55 187 DNG 03C 37.02 53 58 2.69 79 MBM AVI 19.03 53 59 3 189 DNG 03H 34.68 53 62 2.52 183 DNG 01H 18.34 53 62 3.48 184 DNG AV6 21.55 53 62 2.26 75 MBM 06H 36.62 53 64 3.05 183 DNG AV6 22.2 53 65 3.98 183 DNG AV6 22.64 53 68 4.39 183 DNG AV6 22.38 53 68 3.04 76 MBM 06H 25.06 53 69 2.9 184 DNG AV6 22.86 53 69 3.85 117 DFS 05H 3.2 Page 56 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 53 74 3.86 183 DNG AV6 22.4 53 74 2.65 178 DNT 07C -0.73 53 74 2.13 180 DNT 07C 0.33 53 75 2.19 181 DNT 07C -0.76 53 75 3.25 185 DNG AV6 22.7 53 76 2.32 178 DNT 07C 0.37 53 76 3.34 181 DNG 06H 33.66 53 76 3.75 182 DNG AV6 22.79 53 76 2.19 181 DNG 06H 9.15 53 76 2.13 181 DNG 06H 0.83 53 76 2.26 181 DNG 07C -0.85 53 77 3.56 182 DNG AV6 22.93 53 77 7.4 177 DNT 07C 0.42 53 77 3.15 186 DNG 07C -0.87 53 78 3.83 184 DNG AV6 23.22 53 78 4.39 178 DNT 07H 0.52 53 78 4.28 177 DNT 06H 0.43 53 78 2.13 183 DNG 06H 27.7 53 78 4.71 184 DNG 06H 28.78 53 78 3.98 180 DNT 07C 0.33 53 78 3.84 179 DNT 07C -0.76 53 78 2.31 180 DNT 07H -0.53 53 79 8.6 181 DNT 07C 0.17 53 79 3.8 181 DNT 07C -0.88 53 80 2.88 179 DNT 07C 0.35 53 80 4.84 180 DNT 07C 0 53 81 6.55 181 DNT 07C 0.32 53 81 4.44 180 DNT 07C -0.74 53 82 4.18 181 DNT 07C -0.75 53 82 2.42 71 MBM 06H 5.67 53 83 3.1 181 DNT 07C 0.3 53 84 4.65 181 DNT 07C -0.7 53 85 0.76 112 DFS 01C 28.34 53 85 5.63 181 DNT 07C 0.28 53 85 5.08 181 DNT 07C -0.74 53 86 5.28 183 DNT 07C 0.26 53 86 3 182 DNT 07C -0.65 53 87 3.47 182 DNT 07C 0.3 53 87 6.69 182 DNT 07C -0.72 53 88 4.29 180 DNT 07C 0.34 53 88 4.47 182 DNT 07C -0.72 53 88 2.05 69 DFS 03H 30.49 53 89 3.04 181 DNT 07H -0.63 53 89 6.06 181 DNT 07H 0.42 53 89 6.6 182 DNT 07C 0.4 53 89 4.18 183 DNT 07C -0.79 53 89 2.62 81 MBM 03C 27.44 53 89 2.42 80 MBM 01C 11.99 53 90 4.3 183 DNT 07C 0.32 53 90 2.13 182 DNT 07C -0.62 54 37 2.33 185 DNG 02H 24.05 54 39 0.12 0 TWD 6 AV6 -0.05 Page 57 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 54 41 2.15 56 DFS AV6 2.11 54 42 2.35 79 MBM 04H 26.94 54 42 4.07 82 MBM 05H 27.26 54 48 2.31 79 MBM 01C 26.25 54 71 2.92 87 MBM 02H 2.54 54 73 3.19 180 DNT 07C 0.32 54 73 2.97 180 DNT 07C -0.72 54 74 3.08 180 DNT 07C 0.35 54 74 3.86 180 DNT 07C -0.8 54 75 2.47 179 DNT 07C 0.37 54 75 3 180 DNT 07C -0.85 54 76 3.15 182 DNT 07C -0.81 54 76 3.71 183 DNT 07C 0.33 54 77 4.06 182 DNT 07C -0.71 54 77 5.33 182 DNT 07C 0.35 54 78 3.24 176 DNT 07H 0.53 54 78 6.68 181 DNT 07C -0.75 54 78 12.54 177 DNT 07C 0.37 54 79 5.56 180 DNT 07C 0.31 54 79 6.7 181 DNT 07C -0.69 54 79 3.31 185 DNG AV6 21.35 54 80 3.6 179 DNT 07C 0.36 54 80 7.14 180 DNT 07C -0.71 54 80 3.86 184 DNG AV6 21.46 54 81 5.8 180 DNT 07C 0.34 54 81 8.37 181 DNT 07C -0.73 54 81 3.7 185 DNG AV6 21.42 54 81 0.23 70 MBM TSH 1.94 54 82 4.53 185 DNG AV6 21.62 54 82 3.59 180 DNT 07H 0.4 54 82 5.77 180 DNT 07C -0.72 54 83 4.94 181 DNT 07C 0.32 54 83 3.74 184 DNG AV6 21.33 54 83 8.05 180 DNT 07C -0.71 54 84 2.53 182 DNT 07H 0.4 54 84 4.2 183 DNT 07C 0.3 54 84 4.65 182 DNT 07C -0.76 54 84 1 98 DFS FBC 1.58 54 85 4.52 184 DNG AV6 21.76 54 85 5.13 180 DNT 07C 0.37 54 85 11.49 180 DNT 07C -0.69 54 85 2.92 183 DNT AV2 0 54 86 3.44 183 DNG AV6 21.84 54 86 3.01 181 DNT 07C 0.32 54 86 5.62 181 DNT 07C -0.74 54 86 4.04 84 MBM 05H 6.05 54 87 2.6 180 DNT 07H 0.42 54 87 3.43 184 DNG AV6 21.61 54 87 4.67 181 DNT 07C 0.37 54 87 6.11 181 DNT 07C -0.64 54 88 2.59 182 DNT 07H -0.62 54 88 6.77 181 DNT 07H 0.4 Page 58 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 54 88 6.69 182 DNT 07C 0.37 54 88 5.69 183 DNT 07C -0.67 55 40 2.78 183 DNT 07C -0.6 55 40 7.73 182 DNT 07C 0.36 55 40 2.43 188 DNG 07C 1.08 55 41 3.51 179 DNT 07C 0.41 55 41 4.54 179 DNT 07H 0.44 55 44 3.91 185 DNG 06C 37.75 55 46 2.51 187 DNG 06C 22.96 55 49 2.52 182 DNT 07H 0.47 55 54 2.11 184 DNG 05H 4.48 55 71 3.42 182 DNT 07C 0.42 55 71 5.85 181 DNT 07C -0.75 55 71 2.06 182 DNG 05C 25.16 55 72 2.21 181 DNT 05C 0.7 55 72 3.35 178 DNT 07C -0.74 55 72 2.17 179 DNT 07C 0.28 55 73 5.22 181 DNT 07C -0.69 55 73 2.5 180 DNT 07C 0.31 55 74 2.41 180 DNT 05C -0.4 55 74 2.48 179 DNT 05C 0.63 55 74 5.03 181 DNT 07C -0.76 55 74 3.89 183 DNT 07C 0.35 55 75 7.38 181 DNT 07C -0.73 55 75 4.27 181 DNT 07C 0.35 55 76 2.71 180 DNT 07C 0.3 55 76 5.01 187 DNG 07C -0.75 55 77 2.62 180 DNT 07C 0.37 55 77 5.57 185 DNG 07C -0.89 55 78 3.77 181 DNT 07H 0.4 55 78 7.56 180 DNT 07C 0.31 55 78 7.29 181 DNT 07C -0.71 55 78 2.26 178 DNT 05C 0.72 55 78 2.1 182 DNT 05C -0.31 55 78 2.19 79 MBM 01H 19.13 55 79 6.08 180 DNT 07H -0.6 55 79 12.58 179 DNT 07H 0.47 55 79 8.81 178 DNT 07C 0.34 55 79 2.82 179 DNT 07C -0.1 55 79 7.12 182 DNT 07C -0.77 55 79 2.06 180 DNG 06H 26.54 55 79 4.66 181 DNG 06H 28.5 55 79 2.47 182 DNG 02H 20.7 55 79 2.29 178 DNT 07C 0.96 55 80 3.41 180 DNT 07H -0.6 55 80 2.65 180 DNT 07H 0.47 55 80 11.08 180 DNT 07C 0.37 55 80 9.07 180 DNT 07C -0.79 55 80 3.04 181 DNG 06C 23.76 55 80 2.47 179 DNT 05C 0.76 55 81 10.6 180 DNT 07C 0.39 55 81 2.31 177 DNT 07H 0.5 Page 59 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 55 81 11.27 185 DNG 07C -0.74 55 82 6.1 180 DNT 07H 0.32 55 82 8.81 180 DNT 07C 0.32 55 82 6.5 180 DNT 07C -0.76 55 83 9.73 180 DNT 07C 0.35 55 83 11.7 180 DNT 07C -0.71 55 84 6.35 183 DNT 07C -0.77 55 84 10.84 181 DNT 07C 0.3 55 84 5.04 182 DNT 07H 0.47 55 84 3.76 182 DNT 07H -0.6 55 84 2.7 74 MBM FBH 16.23 56 45 2.14 184 DNG 06H 11.82 56 49 2.38 176 DNT 07H -0.61 56 49 3.91 179 DNT 07H 0.49 56 49 3.31 180 DNG 06C 15.61 56 50 2.67 89 MBM 05H 20.9 56 51 2.71 185 DNT AV4 0 56 53 2.6 82 MBM 05H 11.59 56 53 2.62 87 MBM 05H 16.4 56 61 4.47 84 MBM 05H 15.12 56 71 2.26 180 DNT 07C 0.33 56 72 5.28 178 DNT 07C 0.3 56 72 9.48 75 MBM 06C 27.5 56 72 7.06 186 DNG 06C 39.91 56 73 7.89 178 DNT 07C 0.4 56 73 10.28 178 DNT 07C -0.72 56 74 6.89 180 DNT 07C 0.34 56 74 7.28 179 DNT 07C -0.77 56 74 2 179 DNT 05C 0.66 56 75 6.74 178 DNT 07C 0.4 56 75 9.99 185 DNG 07C -0.92 56 76 7.11 181 DNT 07C -0.73 56 76 8.07 181 DNT 07C 0.33 56 77 3.88 182 DNT 07C -0.76 56 77 4.85 182 DNT 07C 0.4 56 77 2.27 182 DNT 07H 0.45 56 78 2.46 178 DNT 07H 0.45 56 78 10.8 178 DNT 07C 0.37 56 78 7.48 180 DNT 07C -0.74 56 78 2.73 187 DNG 03H 8.59 56 78 2.05 179 DNT 05C -0.29 56 78 1.28 74 DFS AV3 7.87 56 79 3.56 180 DNT 07H -0.61 56 79 7.5 180 DNT 07H 0.44 56 79 14.66 180 DNT 07C 0.36 56 79 10.35 181 DNT 07C -0.76 56 79 6.05 75 MBM 05H 6.66 56 79 1.65 121 DFS AV1 18.32 56 79 3.14 72 MBM AV3 11.86 56 79 2.49 65 DFS AV4 2.62 56 79 1.83 114 DFS 04C 27.39 56 79 1.33 102 DFS 05H 1.52 Page 60 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 56 80 3.33 180 DNT 07H -0.7 56 80 12.24 180 DNT 07H 0.41 56 80 11.51 181 DNT 07C 0.72 56 80 7.62 181 DNT 07C -0.7 56 80 2.33 182 DNT 05C -0.31 56 80 3.19 181 DNT 05C 0.72 56 82 2.18 182 DNG 06H 19.67 56 82 12.24 180 DNT 07C 0.32 56 82 10.91 181 DNT 07C -0.72 57 45 2.46 185 DNT AV2 0.11 57 45 1.6 106 DFS 04C 19.13 57 46 2.95 180 DNT 07H 0.44 57 46 4.37 187 DNG 07H 9.3 57 47 2.44 181 DNT 07H 0.52 57 49 3.25 184 DNT 07H -0.66 57 49 12.73 181 DNT 07H 0.41 57 55 3.68 184 DNG 07H 8.62 57 56 4.29 185 DNG 01H 1.91 57 56 4.24 185 DNG 07H 8.5 57 56 3.82 182 DNT AV4 0.06 57 56 0.87 82 DFS 05C 11.17 57 67 2.67 84 MBM 02C 21.69 57 70 2.1 185 DNG AV3 -1.07 57 73 12.28 180 DNT 07C 0.37 57 73 11.19 180 DNT 07C -0.74 57 73 2.53 179 DNT 01C 0.63 57 74 10.96 179 DNT 07C -0.76 57 74 11.49 180 DNT 07C 0.33 57 75 8.37 181 DNT 07C 0.35 57 75 3.37 182 DNT 07H 0.43 57 75 2.58 183 DNT 07H -0.62 57 75 13.86 180 DNT 07C -0.76 57 76 14.06 177 DNT 07C 0.39 57 76 11.91 179 DNT 07C -0.72 57 76 3 179 DNT 05C 0.71 57 76 2.07 178 DNT 05C -0.29 57 77 2.43 180 DNT 07H -0.62 57 77 2.23 178 DNT 07H 0.45 57 77 13.57 177 DNT 07C 0.39 57 77 9.76 185 DNG 07C -0.77 57 78 5.63 179 DNT 07H -0.62 57 78 10.77 178 DNT 07H 0.5 57 78 14.21 177 DNT 07C 0.44 57 78 15.71 177 DNT 07C -0.83 57 78 3.45 179 DNT 05C 0.66 57 78 3.61 178 DNT 05C -0.29 57 78 2.03 183 DNG 06H 9.54 57 78 4.24 182 DNG 06H 10.08 57 78 8.98 182 DNG 06H 10.66 57 78 6.78 182 DNG 06H 11.75 57 78 2.45 184 DNG 06H 12.55 57 78 4.75 183 DNG 06H 13.59 Page 61 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 57 78 2.58 184 DNG 06H 15.99 57 78 4.11 184 DNG 06H 17.11 57 78 6.94 179 DNG 06H 19.57 57 78 3.24 179 DNG 06H 19.84 57 78 3.53 181 DNG 06H 21.26 57 78 5.43 181 DNG 06H 21.69 57 78 11.09 181 DNG 06H 23.5 57 78 2.75 184 DNG 06H 25.32 57 78 2.41 183 DNG 06H 27.41 57 78 3.58 182 DNG 06H 28.48 57 78 2.74 182 DNG 06H 30.03 57 78 3.56 184 DNG 06H 18.38 57 78 4.6 182 DNG 06H 22.61 57 78 1.04 98 DFS 01C 16.41 57 78 1.3 92 DFS 01C 25.61 57 78 2.09 77 MBM AV4 16.69 57 79 2.66 182 DNT 07H -0.64 57 79 5.62 180 DNT 07H 0.45 57 79 6.08 185 DNG 07H 13.11 57 79 4.07 182 DNG 07H 14.35 57 79 18.35 179 DNT 07C -0.74 57 79 9.67 182 DNG 06C 27.78 57 79 2.68 183 DNG 06C 27.26 57 79 4.95 183 DNG 06C 26.66 57 79 4.23 182 DNG 06C 24.8 57 79 2.12 182 DNG 06C 23.71 57 79 5.01 182 DNG 06C 22.51 57 79 2.09 183 DNG 06C 21.4 57 79 3.72 182 DNG 06C 19.44 57 79 2.36 181 DNG 06C 15.07 57 79 2.49 183 DNG 06C 13.43 57 79 13.41 178 DNT 07C 0.49 57 80 4.34 181 DNT 07H -0.6 57 80 9.79 180 DNT 07H 0.47 57 80 6.32 182 DNT 07C 0.34 57 80 6.63 182 DNT 07C -0.72 57 80 2.48 180 DNT 05C 0.74 57 80 3.48 180 DNT 05C -0.29 58 46 2.27 181 DNT 07H 0.47 58 46 2.5 73 MBM 03H 23.99 58 47 1.25 116 DFS 03C 23.52 58 47 0.57 78 DFS 01C 14.64 58 47 2.63 105 DFS FBC 12.73 58 49 2.08 176 DNT 07H -0.71 58 49 2.76 181 DNT 07H 0.31 58 51 2.45 182 DNT AV2 -0.16 58 51 2.92 183 DNG 06H 33.77 58 56 3.78 77 MBM 02C 15.39 58 58 3.43 81 MBM TSC 15.6 58 61 3.21 82 MBM 04H 25.12 58 66 1.71 117 DFS FBC 14.91 58 72 2.29 178 DNT 07H 0.45 Page 62 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 58 72 21.79 175 DNT 07C 0.39 58 72 14.02 178 DNT 07C -0.86 58 72 3.16 181 DNT AV2 0.13 58 72 4.34 181 DNT AV3 -0.28 58 72 7.15 180 DNT AV4 0 58 73 2.27 178 DNT 07H -0.6 58 73 3.77 179 DNT 07H 0.47 58 73 11.41 176 DNT 07C 0.37 58 73 12.82 178 DNT 07C -0.77 58 74 11.88 176 DNT 07C 0.42 58 74 12.39 177 DNT 07C -0.75 58 75 3.91 176 DNT 01H -0.34 58 75 2.74 177 DNT 07H 0.45 58 75 11.79 177 DNT 07C 0.42 58 75 2.55 181 DNG 01H 0.73 58 75 15.15 183 DNG 07C -0.82 58 76 2.37 178 DNT 01H -0.32 58 76 10.9 178 DNT 07C 0.37 58 76 9.75 179 DNT 07C -0.77 58 77 10.45 178 DNT 07C 0.39 58 77 11.01 179 DNT 07C -0.75 59 53 2.58 179 DNT 07C -0.64 59 54 2.65 184 DNG 06C 33.62 59 54 2.82 188 DNG 06C 34.22 59 54 5.11 181 DNG 06C 35.28 59 54 5.26 182 DNG 06C 35.85 59 54 4.64 181 DNG 06C 36.23 59 54 3.01 180 DNG 06C 37.3 59 54 4.53 181 DNG 06C 37.94 59 54 6.76 181 DNG 06C 37.06 59 54 2.41 182 DNT AV3 -0.34 59 54 2.22 181 DNG AV3 8.18 59 55 6.03 181 DNG AV3 6.42 59 55 6.65 182 DNG AV3 8.19 59 56 4.12 184 DNT AV3 -0.3 59 56 4.86 185 DNG AV3 1.67 59 56 2.81 183 DNG AV3 5.9 59 56 2.68 181 DNG AV3 6.22 59 56 3.2 185 DNG AV3 13.35 59 56 4.43 182 DNG AV3 13.75 59 56 2.36 186 DNG AV3 23.06 59 57 2.99 182 DNT AV3 -0.31 59 58 2.17 185 DNT AV3 -0.2 59 58 2.31 182 DNT AV2 0 59 60 1.74 86 DFS 07H 15.34 59 60 1.27 52 DFS 07H 27.46 59 62 3.13 184 DNT AV2 -0.1 59 63 2.62 183 DNT AV1 -0.3 59 64 2.55 183 DNG 07H 3.5 59 64 5.9 184 DNT AV6 0.4 59 65 2.51 184 DNT AV1 -0.25 59 66 2.33 182 DNT AV1 -0.27 Page 63 of 64

ULNRC-04823 Attachment 3 March 12, 2003 Steam Generator D ROW COL VOLTS DEG IND %TW LOCATION 59 67 2.47 185 DNT AV3 -0.25 59 68 2.07 185 DNT AV2 -0.2 59 70 3.95 185 DNT AV3 -0.3 59 71 5.67 180 DNT 07H 0.52 59 71 2.99 181 DNT 07H -0.55 59 71 2.36 176 DNT AV3 -0.25 Page 64 of 64